Professional Documents
Culture Documents
� � �
Abstract— During an islanding operation of a microgrid
comprised of multiple distributed generation (DG) units serving �
�
a load, DG units interfaced with voltage-sourced converters
(VSC) are regarded as the only energy sources. Hence, DG units
should be controlled to form the frequency and voltage, pick up �
��
DG , DG �, �
�
� ∠� 0 �� ∠0° B. Power Sharing Analysis
� � �
𝑉𝑡the
First, (𝑡)power flow in Fig. 2a at the sending and receiving
ends, and across the feeder is expressed in the dq frame.
�
� �
After that, the power sharing in Fig. 3 will be examined
��
with particular regard to feeder impedances, assuming X1 =
X + δX and X2 = X.
(a) All phasors in Fig. 2a are transformed to the dq frame
with respect to the terminal voltage phase angle, θt . Thus the
𝐼𝑚 terminal voltage at the fundamental frequency is expressed
𝜔(𝑡) as follows
𝑖𝑑 𝑉𝑡
𝛾𝑜 𝑅𝑒
𝑉𝑡𝑑 Vtd + j0 = (VLd + jVLq ) + (Rk + jXk )(ikd + jikq ) (4a)
𝑖𝑞 𝑖
Vtd = VLd + Rk ikd − Xk ikq (4b)
During islands, local controllers must be self-aware so that + j ( 32 )ikq (Xikq − Rk ikd )
| {z }
DG units pick up their share of the load with proportion Qloss k
to their capacities. The P − f /Q − V droop controller is
1) Without Droop: From (5), it is inferred that powers at
conventionally adopted, which is based on a predominant
the DG terminals are influenced by the feeder resistance and
inductive behavior of the feeder achieved by physical or static
reactance. For a droopless power sharing of equally-rated
virtual inductnace. Therefore, when (θz ≈ 90◦ ) and a small
DG units in Fig. 3, QDG1 <QDG2 and PDG1 <PDG2 , which
phase angle, θt , are considered, the power flow equations
is dangerous as one unit could be forced to supply more than
between the two buses in Fig. 2a are expressed as
its capacity.
Vt VL XPDG In order to accurately share the load without droop con-
PDG = sin θt ⇒ θt ≈ (1a)
X Vt VL trollers, and in proportion to DG units’ capacities, assuming
Vt (Vt − VL ) XQDG their output voltage phasor Vt ∠θt are exactly the same, the
QDG = ⇒ (Vt − VL ) ≈ (1b)
X Vt following constraints must be satisfied
PDG and QDG are proportional to the phase angle and volt- a) Even Sharing: When all DG units have the same
age difference; respectively. The droop control should output capacities, resistances and reactances of both feeders must
the reference value for the terminal (capacitor) voltage phasor be unified.
Vt ∠θt . The formed phase angle, θt , is used to transform the
R1 = R2 X1 = X2 (6)
terminal voltages, filter currents and feeder currents to the
dq frame, resulting in [Vtd 0]T , [if d if q ]T and [id iq ]T , b) Uneven Sharing: When DG units have different
where quadrature currents are negative because their space capacities, resistances and reactances must be inversely pro-
vectors lag the voltage space vector. Fig. 2b illustrates the portional to ikd and ikq ; respectively.
space vectors of the terminal voltage and feeder current, and
their corresponding dq components in the complex plane. R1 i1d = R2 i2d X1 i1q = X2 i2q (7)
As a result, the dq-frame active and reactive powers derived
from S = 32 Vtd (id − jiq ) are Put simply, voltage drops across the feeders must be unified.
2) With Droop: Despite the impedance’s influence on
3 3 active powers, the id − f droop should promise accurate
PDG = Vtd id QDG = − Vtd iq (2)
2 2 active power sharing because the frequency is a global
id and (−iq ) track the DG active and reactive powers; re- quantity in the microgrid, hence (id = i1d = i2d ). On
spectively. The conventional droop can therefore be replaced the other hand, the iq − V droop achieves accurate reactive
with current sharing id − f /iq − V as follows power sharing if and only if feeders have matched voltage
drops, satisfying (6)-(7). Otherwise, DG units will generate
ω = ω ∗ − mid (3a)
disparate reactive powers (i1q 6= i2q ) as shown in Fig. 4a,
Vtd = Vd∗ + niq (3b) and compensation is therefore required.
� ��
��
DG 1 ,
�,
DG 1
�
� 1 ∠� 1 �� ∠0° QDG1
=
n + X2
(11)
� � �1 � + ��
1 QDG2 n + X1
In contrast, if the conventional droop were employed with
� 1 the voltage drop effect approximated as 2(XQDG +RPDG )
3Vd∗ , the
� � ratio would be
��
2X2
QDG1 n+ 3Vd∗
DG 2 , DG 2
= 2X1
(12)
QDG2 n+
� �
� 2 ∠� 2 3Vd∗
�2 2 � The compensation methods based on the constraint in (10)
are as follows
𝑍𝑜1 𝑍1 𝑖1 � 𝑉𝑠 ∠0 2𝑖2𝑍𝑜1 𝑍2 𝑍1 𝑍𝑜21)𝑖 Large
1 𝑉𝑠 ∠0Droop
𝑖2 𝑍2 𝑍𝑜2By enlarging n in (10), the
Coefficient:
� � feeder reactances will be outweighed, and the ratio will
𝑃2𝑚𝑎𝑥 𝑉𝑖𝑛𝑣 1 𝑃1 , 𝑄1 𝑃2 , 𝑄2 𝑉𝑖𝑛𝑣 1 𝑃1 , 𝑄1
approximately 𝑃be
2 , 𝑄2unity.
𝜔 i1q n+X
𝜔𝑚𝑖𝑛 𝑡 = 2𝑠 DG units conected to a load with X1 >X2 .
Fig. 3: Two nX = ≈1 (13)
i2q n + X + δX
However, n is bounded by the voltage deviation. With the
𝜔 𝑉 𝑉 voltage deviation being fixed at 5%, it can be concluded that
𝜔∗ 𝑉𝑡1,2 𝐺𝐶 𝑉𝑡1,2 𝐺𝐶 n depends primarily on the reactive power rating. Therefore,
𝑉𝐿 𝐺𝐶 𝑉𝐿 𝐺𝐶 for small reactive power ratings, iq is small and n can be set
𝑚1
𝜔𝐷𝐸𝑅1
𝑉𝑡1
𝑛1
𝑉𝑡1 𝑛1
large to limit the error. Although difficult to achieve accuracy,
𝑚2
𝜔𝐷𝐸𝑅2 = 𝜔𝑚𝑖𝑛 n partially compensates for the mismatched impedance.
𝑉𝑡2 𝑉𝑡2
𝑛2 𝑛2
𝑉𝐿 𝑉𝐿 2) Adaptive Mismatch Virtual Reactance: The adaptive
𝑃𝑖𝑛𝑗 1 𝑃𝑖𝑛 𝑗2
𝑃
virtual reactance, δXv , is calculated (X1 − X2 = δXv ),
𝑃 𝑃𝐷𝐸𝑅2−𝑖1𝑞 −𝑖2𝑞
−𝑖𝑞 −𝑖𝑞
𝑃𝐷𝐸𝑅1 −𝑖1𝑞,2𝑞 and incorporated into n. This suggests that different droop
(a) (b) coefficients should be assigned to result in a unity ratio as
Fig. 4: iq − V droop with (a) uncompensated slopes (b) i1q n2 + X n∗ + X
= = ∗ = 1 (14)
compensated slopes with adaptive virtual reactance. i2q n1 + X + δX (n − δXv ) + X + δX
However, the method requires communication between DG
local controllers to exchange feeder reactances and calculate
C. Correction of Reactive Power Sharing the mismatch.
For simplification, even sharing case is considered with 3) Adaptive Feeder Virtual Impedance: It is based on
two equally-rated DG units using the id − f /iq − V droop compensating for the entire feeder impedance. With knowl-
controller, where an accurate reactive power sharing is equiv- edge of the PCC voltage as shown in Fig. 1, the virtual
alent to having matched i1q and i2q . impedance is realized utilizing separate real and imaginary
equations in (4a) as follows.
With effective terminal voltage regulation, (Vtd = Vd∗ +
ikq
niq ) is substituted into (4), yielding Vd − VLd − ikd VLq
Rvk = Rk = i2
kq
Vd∗ + ni1q = VLd + R1 i1d − X1 i1q (8a) ikd + ikd (15)
Vd∗ + ni2q = VLd + R2 i2d − X2 i2q (8b) −VLq − Rk ikq
Xvk = Xk =
ikd
The quadrature-current error is By incorporating the virtual voltage drops, (8) becomes
i1d
X2 i2q − X1 i1q + (R1 − R2 )id Vd∗ + (n∗ + Rv1 − Xv1 ) i1q = VLd + R1 i1d − X1 i1q (16a)
i1q − i2q = (9) i1q
n | {z }
n1
Assuming inductive feeder impedance, and (R1 − R2 = 0), i2d
Vd∗ ∗
+ (n + Rv2 − Xv2 ) i2q = VLd + R2 i2d − X2 i2q (16b)
the following ratio is obtained i2q
| {z }
n2
i1q n + X2 n+X
= = (10) This method does not require further communication. After
i2q n + X1 n + X + δX
realizing the virtual impedance, the signal carrying the PCC
Therefore, for accurate reactive power sharing, the ratio voltage phasor can be disrupted. Moreover, increasing the
should be constrained to unity. (10) can also be expressed terminal voltage by the amount of the voltage drop improves
in terms of reactive powers, with the approximation QDG ≈ the PCC voltage. The 5% voltage deviation will be allocated
−3 ∗
2 iq Vd for the PCC voltage rather than the terminal voltage.
Droop Controller �∗ DG1
�1 + � 1 �
_
���
�1� �1�
�
�1 �2 ��
�1
1 �1
� Feeder-Load
�2
�� Equations �2
�� �� ��1
�2
DG2
With ~ikabc and ~iLabc identified as the feeder and load state P DG2
Rf = 10mΩ P DG2
δL1 = 2mH
ωB = 2000 rad/s 135
Controller parameters θpm = 53◦
m = 0.15
QDG1
n=5 75
QDG2
30
2 3 5 7
Time (s)
B. Operation Scenario
(b)
Considering the following scenario, the testbed model in 100
Voltage Magnitude (V)
V t1
Fig. 5 is validated with two DG units that should evenly V t2
share 540W and 270 VAR. The simulation parameters are 90 VL
listed in Table I. 85
1) The microgrid is initially grid-tied, and the PCC volt- 80
age is provided. Each DG supplies 175W and 75VAR. 2 3
Time (s)
5 7
f2
3) At t = 5 s, a mismatch inductance, δL1 , is instilled
into F eeder 1.
59.95
Conducted case studies and simulation analysis are pre- 59.94
sented as follows 2 3
Time (s)
5 7
135
QDG1
75
QDG2
30
2 3 5 7 9
Time (s)
(a)
100
Voltage Magnitude (V)
V t1
V t2
90 VL
85
80
2 3 5 7 9
Time (s)
(b)
IV. CONCLUSIONS
This paper presents a modified droop controller based
on the dq-axis feeder current sharing. The power sharing