You are on page 1of 4

Substation ?

Electrical Bus-Bar and its Types


Substation is point of controlling supply of power on Definition: An electrical bus bar is defined as a
different routes by means of various equipments, conductor or a group of conductor used for collecting
Transformers, Breakers, Compensating equipments, electric power from the incoming feeders and
Isolators etc. with suitable bus bar arrangement distributes them to the outgoing feeders. In other
Allows for the control of power flows in the network words, it is a type of electrical junction in which all the
and general switching operations for maintenance incoming and outgoing electrical current meets. Thus,
purpose. the electrical bus bar collects the electric power at one
Purpose of Substation location.
The substations are very much essential to The bus bar system consists the isolator and the circuit
-Evacuate power from generating stations. breaker. On the occurrence of a fault, the circuit
-Transmit to the load centers. breaker is tripped off and the faulty section of the
-Distribute to the utilities & ultimate consumers. busbar is easily disconnected from the circuit.
The Electrical power generation from Hydel, Thermal, The copper and aluminium are used for the
Nuclear and other generating stations has to be manufacturing of the electrical bus bar.
evacuated to load centers. The generation voltage is The various types of busbar arrangement are used in the
limited to 15/18 kV due to the limitation of the rotating power system. The selection of the bus bar is depended
machinery. This bulk power has to be stepped up to on the different factor likes reliability, flexibility, cost
higher voltages depending on quantum of power etc.
generated and distance to the load centers. Again the The following are the electrical considerations
power has to be stepped down to different lower governing the selection of any one particular
voltages for transmission and distribution. arrangement.
In between the power houses and ultimate consumers - The bus bar arrangement is simple and easy in
a number of Transformation and switching stations maintenance.
have to be created. These are generally known as sub- - The maintenance of the system did not affect
stations. their continuity.
Voltage Class & Rating - The installation of the bus bar is cheap.
Generally the following voltage class substations The small substation where continuity of the supply is
prevailing in India not essential uses the single bus bar. But in a large
6.6 kV, 11 kV, 22 kV/33kV substation, the additional busbar is used in the system
(Primary distribution Voltage) so that the interruption does not occur in their supply.
66kV, 100/110/132kV
The different type of electrical busbar arrangement are
(High voltage)
as detailed below:
220/230kV , 400 kV, 765 kV, 1200kV
Single Bus-Bar Arrangement: The arrangement of such
(Extra high Voltage)
type of system is very simple and easy. The system has
Types of Substations only one bus bar along with the switch. All the
-Outdoor Conventional Air insulated substations (AIS) substation equipment like the transformer, generator,
-Indoor substations the feeder is connected to this bus bar only.
-Compressed Air insulated Advantages:
-Gas insulated substations (GIS) -Low initial Cost
-Requires less maintenance
The types of Sub Stations depends upon:
-Simple in operation
-The availability of the land in the required place.
-Environmental conditions.
Drawbacks:
-The only disadvantage of such type of arrangement is
Main and Transfer Bus Arrangement:
that the complete supply is disturbed on the occurrence
of the fault.
-The arrangement provides the less flexibility and
hence used in the small substation where continuity of
supply is not essential.

Single Bus-Bar Arrangement With Bus Sectionalized:


In this type of busbar arrangement, the circuit breaker
and isolating switches are used. The isolator
disconnects the faulty section of the busbar, hence
protects the system from complete shutdown. This type
of arrangement uses one addition circuit breaker which
does not much increase the cost of the system.

Advantages:
-The faulty section is removed without affecting the
continuity of the supply.
-The maintenance of the individual section can be done
without disturbing the system supply.

Disadvantages: Such type of arrangement uses two type of busbar


-The system uses the additional circuit breaker and namely, main busbar and the auxiliary or transfer or
isolator which increases the cost of the system. reserve bus bar. The busbar arrangement uses bus
coupler which connects the isolating switches and
circuit breaker to the busbar. The bus coupler is also
used for transferring the load from one bus to another Advantages:
in case of overloading. The following are the steps of -This type of arrangement provides the maximum
transferring the load from one bus to another. reliability and flexibility in the supply. Because the
a) The potential of both the bus bar kept same by fault and maintenance would not disturb their
closing the bus coupler. continuity.
b) Bus bar on which the load is transferred is kept close. -The continuity of the supply remains same because the
c) Open the main bus bar. load is transferrable from one bus to another on the
Thus, the load is transferred from the main bus to occurrence of the fault.
reserve bus. Disadvantages:
Advantages: -In such type of arrangement two buses and two circuit
-The continuity of the supply remains same even in the breakers are used which increases the cost of the
fault. When the fault occurs on any of the buses the system.
entire load is shifted to the another bus. -Their maintenance cost is very high.
-The repair and maintenance can easily be done on the Because of its higher cost, such type of bus-bars is
busbar without disturbing their continuity. seldom used in substations.
-The maintenance cost of the arrangement is less.
-The potential of the bus is used for the operation of the Sectionalized Double Bus Bar Arrangement:
relay. In this type of bus arrangement, the sectionalized main
-The load can easily be shifted on any of the buses. bus bar is used along with the auxiliary bus bar. Any
Disadvantages: section of the busbar can be removed from the circuit
-In such type of arrangements, two bus bars are used for maintenance and can be connected to any of the
which increases the cost of the system. auxiliary bus bars. But such type of arrangement
-The fault on any of the bus would cause the complete increases the cost of the system. Sectionalization of the
shutdown on the whole substation. auxiliary bus bar is not required because it would
increase the cost of the system.
Double Bus Double Breaker Arrangement:
This type of arrangement requires two bus bar and two
circuit breakers. It does not require any additional
equipment like bus coupler and switch.
Bus levels Earthing:
First level ---- Equipment interconnection level. Main objective of earthing system in the substation is,
Second level ---- Bus levels. -To ensure that a person in the vicinity of substation is
Third level ---- Cross Bus / Jack Bus level. not exposed to danger of electrical shock
-To provide easy path for fault currents into earth
under fault condition without affecting the continuity
Main electrical equipments in a Substation : of service
Power Transformers ( ICTs).
Circuit breakers. The main earth mat shall be laid horizontally at a
Instrument Transformers-CT, PT, CVT regular spacing in both X & Y direction based upon soil
Isolators resistivity value and short circuit value at substation.
Lightning / Surge Arrestors
Control panels The main earth mat shall be designed to limit the
Protection & Relay panels. following;
P.L.C.C Equipments Touch Potential – The potential difference between
Control & Power cables. two points, one on the ground where a man may stand
Substation Automation and any other point which can be simultaneously
Fire Fighting equipments touched by either hand.
Step Potential – The potential difference between any
Electrical safety clearances: two points on ground surface which can be
The various clearances which need to be defined. simultaneously touched by feet.
-Phase-to-earth clearance.
-Phase-to-phase clearance.
-Sectional clearance.
-Ground clearance.
-Equipment to equipment spacing

Bay width:
For 132kV : Bay width : 12 meters
For 220kV : Bay width : 18 meters
For 400kV : Bay width : 27 meters
For 765kV : Bay width : 54 meters

Phase to phase clearances:


For 132kV : 3 meters
For 220kV : 4.5 meters
For 400kV : 7.0 meters
For 765kV : 15.0 meters

Ground clearances:
For 132kV : 4.6 meters
For 220kV : 6.5 meters
For 400kV : 8.20 meters
For 765kV : 15 meters

You might also like