1.1
Weight calculations:-
2× (48+0.55+6+0.55)
Weight of the tank wall 7273.2 KN
×0.55×25×4.8
1.2
mi /m=0.1 hi/h=0.375
mc/m=0.8 hc / h=0.51
mi=impulsive mass of the liquid
mc=convective mass of the liquid
hi=height of the impulsive mass above the bottom of the tank(without connecting the base pressure)
hc= height of the convective mass above the bottom of the tank(without connecting the base pressure)
Seismic X direction 1
mc=convective mass of the liquid mc=.8x1382400 1105920 Kg
hi =Hieght of the impulsive mass above the hi 1.8
bottom of tank wall m
hc=Hieght of theconvective mass above the hc 2.448
bottom of tank wall m
Seismic X direction 2
Time period=T = 2π√(d/g)
d=deflection of the tank wall on the vertical centre line at the height h when loaded by a uniformly distributed
pressure q
ħ={(mi)*hi/2+(mw)*h/2}
{mi/2+mw} = 1.9964154771 m
To find the deflection of the wall due to this pressure it can be considered to be fixed at three edges and free at the
top. A strip of unit width of the wall is considered as cantilever and subjected to concentrated load P and length of
cantilever as ħ
P=q×h×1=58483.6x4.8= 201613.44 N
Ah(i)=(Z/2) (Sa/g)(I/R)
As per IS 1893 part-1, pg 5 fig 10.1 zone(IV) and zone factor (severe) vide pg-16 of IS 1893 z=0.24 seismic zone
(Darjeeling) of IS 1893-2002 is considered. The site has a hard soil therefore considering damping of 5% of the
critical.Importance factor=1.5 pg no-18 table no-6 of IS 1893-2002 response reduction factor(R) =4 (pg-30 for
guidance of seismic design)
Seismic X direction 3
I/R 0.375
Convective
Sa/g 0.25 For Rocky or hard soil sites
Ah(c)= 0.01125
t= 13.7144313375 sec
Z/2= 0.12
I/R 0.375
Mc=(Ah)c×mc×g×hc
298783.531008 N-m
Total Bending Moment at the bottom of the wall
0.9999999399
Qib(x)= Sinh(0.866 L/H)
Cosh(0.866 L/H)
Seismic X direction 4
Convective hydrodynamic pressure at the base of wall
Pcw=Qcw(y)Ah(c) egL
Qcw=0.4165xCosh(3.162 y/L) =
Cosh(3.162 h/L) 0.3965121663
Seismic X direction 5
Pressure due to wall inertia
Pww=Ah(i)×t×em×g 1.40765625 KN/m2
The presssure due to vertical excitation
Time period of vertical mode of Vibration=3 sec as per sec 4.10 of IITK GSDMA
Av=2/3(Z/2×I/R×Sa/g) 0.07500375
Pv=(Av)(egh)(1-y/h) 3531.77658 N/m2
Similarly, equivalent linear distribution for convective liquid mass per unit circumferential length q c
qc=(Ah(c) mcg )/2B
10171.008 N/m2
ac={qc/h2(4h-6hc)} Bottom Pr 991.24286625 N/m2
bi=qc/h2(6hc-2h) Top pr 2246.0976 N/m2
Seismic X direction 6
Seismic X direction 7
Moment Due To Max Hydrodynamic Pr Pxhieght2/6 26617.5521 N-m
Seismic X direction 8
nk
30
N/mm2
27386.128 N/mm2
essure)
pressure)
Seismic X direction 9
ormly distributed
0.0138646 m4
Seismic X direction 10
Seismic X direction 11
Sa/g (5% 2.5
Damping)
mferential length q i
ntial length q c
Seismic X direction 12
Seismic X direction 13
Seismic Design Of Under Ground Forebay Tank
GRADE
HEIGHT OF TANK 4.8 30
OF CONC
N/mm2
EC=5000 27386.13
LENGTH OF TANK 48 √FCK N/mm2
WIDTH OF TANK 6
BASE THICKNESS 0.7
WALL THICKNESS 0.55
1.1
Weight calculations:-
2×
Weight of the tank wall (48+0.55+6+0.55) 7273.2 KN
×0.55×25×4.8
1.2
Analysis along y=direction
For this case L=6m h=4.8
mi /m=0.7 hi/h=0.375
mc/m=0.3 hc / h=0.625
mi=impulsive mass of the liquid
m =convective
hi=height
c of themass of themass
impulsive liquidabove the bottom of the tank(without connecting the base
pressure)
hc= height of the convective mass above the bottom of the tank(without connecting the base
pressure)
h={(mi)*hi/2+(mw)*h/2}
{mi/2+mw} = 1.8462034745 m
To find the direction of the wall due to this pressure it can be considered to be fixed at three edges
and free at the top. A strip of unit width of the wall is considered as cantilever and subjected to
concentrated load
P=q×h×1=58483.6x4.8= 857078.4 N
M.I
=I=(bd3/1
deflection={ph3/3EIW}= 0.0047347879 m 2) 0.013865 m4
Time period of the inductive mode
Time period=Ti = 2π√(d/g) = 0.137967 sec
Ah(i)=(Z/2) (Sa/g)(I/R)
Mc=(Ah)c×mc×g×hc
137308.608 N-m
Total Bending Moment at the bottom of the wall
Mc=√(mi2+mw2) 4379178.68858188 N-m
Hydrodynamic pressure
0.9999999399
Qib(x)= Sinh(0.866 L/H)
Cosh(0.866 L/H)
Qcw=0.4165xCosh(3.162 y/L) =
Cosh(3.162 h/L) 0.3965121663
Similarly, equivalent linear distribution for convective liquid mass per unit circumferential length q c
qc=(Ah(c) mcg )/2B
3814.128 N/m2
ac={qc/h2(4h-6hc)} Bottom Pr 1689.92578125 N/m2
bi=qc/h2(6hc-2h) Top pr 1390.5675 N/m2
Empty case with short wall for backfill of Ø=30° (sloping angle)
BM at the base long wall due to earth
pr 1/2kaγH3/3 336.6409421 KN-m
Short wall act as slab supported on long wall from H/4 to H i.e. from 1.5 to 4.8 M from the bottom
Empty case with short wall for backfill of Ø=30° (sloping angle)
Short wall Slab top portion
Mf At support =paL2/12 180.813006 KN-m
Mf At centre =paL2/24 90.406503 KN-m
Total B.M at the base of of Long Wall = seismicMoment+Static Moment 363258.4942 N-m
Permissible Stress in steel σsc 140 N/mm2
Permissible Stress in steel σst 130 N/mm2
Permissible Bending Stress for M30 σ
cbc 10 N/mm2
m 9.3333333333
Kc =mxσ cbc/( mxσ cbc+σst) 0.4179104478
Jc= 0.8606965174
Rc 1.7984703349
Ka 0.866
d eff = 449.423988676 mm
Doverall 550 mm
Final d eff 492 mm
Mf At supports=paL2/12 causes
tension outside the short wall 180.813006 KN-m
Mf At supports=paL2/12 causes
tension outside the short wall 105840 N-m
Ast=M/(σst Jc deff) 1922.6105911571 mm2
Spacing=(1000*AØ)/Ast 163.3820189303 mm
C=Coeff 1.8
H=HEAD= 0.5 m
L= 5.342585 m
P= 1.24 m
P/H 2.48
A/H= 0.28 IS 6934:1998 Fig 2, Pg 6
A= 0.14 m
B/H= 0.165 IS 6934:1998 Fig 2, Pg 6
B= 0.0825 m
A X
√(M/(Rc×b))=deff 527.9019869 mm
D= 600 mm
deff final= 536 mm
Ast=M/(σst Jc deff) 8357.024668 mm2
Spacing=(1000*AØ)/Ast 96.22410271 mm
Hence provide reinforcement at 32Ø@90mm mm
bottom face of thebase slab c/c spacing
About the
Three forces acts on it Force in KN base of Moment
the stem
Vertical
Item Forces(KN) Lever arm from Point A Moment (KN-m)
Left Side wall(w2) 10.9375 0.125 1.3671875
right Side wall(w3) 10.9375 2.075 22.6953125
Bottom Slab(w3) 13.75 1.1 15.125
Water 20.4 0.85 17.34
Horizontal
Item Forces(KN) Lever arm from Point A Moment (KN-m)
Ka=1-sinØ/1+sinØ 0.333
unit wt of soil γ 18.639 KN/m3
Active earth Pr Pa=(ka)(γ)(H) 10.86187725 KN/m2
Force .5*Pa*H 9.5041425938
Point Of application of
load 0.5833333333 m
Water Pr
column(horizontal
Seismic Coeff=.15) 3.06 0.85 2.601
Vertical Seismic Forces and Moment for water
Horizontal
Item Forces(KN) Lever arm Moment (KN-m)
Water Pr column(Vertical
Seismic Coeff=.1) 2.04 1.1 2.244
Provide nominal Reinforcement of 0.2% of c/s area considering the temp stress
Spacing S= Spacing=(1000*A
Ø
)/Ast 89.7142857143 mm
Spacing S= Spacing=(1000*A
Ø
)/Ast 71.3636363636 mm
Overturning
4.68
5.54408318
2.601
1.435546875
1.435546875
0.2578125
2.244
0.13671875
2.26953125
1.5125
22.11673943
39.0907605703
Moment (KN-m)
Overturning
5.54408318
5.54408318
33.6434168203
5.54408318
1.435546875
1.435546875
0.2578125
0.13671875
2.26953125
1.5125
12.59173943
26.5957605703
4.68
5.54408318
10.22408318
50.9834168203
4.68
5.54408318
2.601
1.435546875
1.435546875
0.2578125
2.244
0.13671875
2.26953125
1.5125
22.11673943
Vertical
Item Lever arm from Point A Moment (KN-m)
Forces(KN)
Top slab (w1) 13.75 1.1 15.125
Left Side wall(w2) 10.9375 0.125 1.3671875
right Side wall(w3) 10.9375 2.075 22.6953125
Bottom Slab(w3) 13.75 1.1 15.125
Water 20.4 0.85 17.34
Horizontal
Item Lever arm from Point A Moment (KN-m)
Forces(KN)
Ka=1-sinØ/1+sinØ 0.333
unit wt of soil γ 18.639 KN/m3
Active earth Pr Pa=(ka)(γ)(H) 10.86187725 KN/m2
Force .5*Pa*H 9.5041425938
Point Of application of
load 0.5833333333 m
Water Pr
column(horizontal Seismic
Coeff=.15) 3.06 0.85 2.601
Vertical Seismic Forces and Moment for water
Horizontal
Item Forces(KN) Lever arm Moment (KN-m)
Provide nominal Reinforcement of 0.2% of c/s area considering the temp stress
Spacing S= Spacing=(1000
*AØ)/Ast 89.7142857143
100 c/c @
Hence Provide bothways
10mm Ø
Spacing S= Spacing=(1000
*AØ)/Ast 71.3636363636
100 c/c @
Hence Provide bothways
12mm Ø
4.68
5.54408318
2.601
3.8671875
1.435546875
1.435546875
0.2578125
2.244
1.5125
0.13671875
2.26953125
1.5125
27.49642693
48.8360730703
5.54408318
5.54408318
48.7684168203
Moment (KN-m)
Overturning
5.54408318
3.8671875
1.435546875
1.5125
0.13671875
2.26953125
1.5125
17.97142693
36.3410730703
Overturning
4.68
5.54408318
10.22408318
66.1084168203
4.68
5.54408318
2.601
3.8671875
1.435546875
1.435546875
0.2578125
2.244
1.5125
0.13671875
2.26953125
1.5125
27.49642693
48.8360730703
Moment
Sl no. Designation Force Lever Arm about Toe
59 Design of Counterfort
W total 290.9712 M total 731.0136
60 Design of Counterfort
Horizontal Earth Pressure .5* Ka * γ * H2 210.4006 KN
Lever arm 1.6 m
Overturning Moment 336.64094208 KN-m
Factor of safety = Mr/Mo 2.1714934478 >2 Hence Safee
Net Moment =Mr-M0 394.37265792 KN-m
X=Net moment/ƩW total 1.3553666408
e=(b/2)-x 0.5446333592 < b/6= 0.633333
q=(P/BxL)(1+6*e/L) Toe 142.4187183158
q=(P/BxL)(1-6*e/L) Heel 10.7240185263
q @ 1.6m from heel 66.1744184377 1.6 m
q @ 2.2m from heel 86.9683184044 2.2 m
Design Of Heel Slab
1)Downward Load Due To the
Weight Of the earth 101.232 KN/m2
61 Design of Counterfort
M=Astσst Jc deff 60509176.2690547 N-mm
Lo=12Ø or deff Whichever is
greater 538 mm
M/V+L0>=Ld 985.7762031848 mm > 720 mm Safe
62 Design of Counterfort
Max + ve B.M at the Middle 41.2140552632 KN-m
between the counterforts
Ast2 684.6516756638 mm
2
Spacing=(1000*AØ)/Ast 165.1689523587 mm
63 Design of Counterfort
At the Ends of the
12 mm Ø= 150 mm c/c counterfort
64 Design of Counterfort
Area of the steel reinfiorcement near the counterfort
Max +ve B.M at the middle 34244887.5 N-mm
The Vertical atem slab has the tendency to separate out from the counterfort and hence should be Tied
by horizontal ties
65 Design of Counterfort
The horizontal presssure ph=Ka*γ*H KN/m
causing seperation 87.66691
Steel Area Reqd= ph*1000/σst 674.3609 mm2
Spacing=(1000*AØ)/Ast 167.6894470744 mm
hence provide 12mm Ø 2 legged stirrup @ 150mm c/c
66 Design of Counterfort
67 Design of Counterfort
68 Design of Counterfort