HVAC Peak Load Calculation Methods – History and
Comparisons
by Bill Smith, president of Elite Software
Copyright © 2011

This article discusses both commercial and residential
HVAC (heating, ventilation and air conditioning) load
calculation methods, and explains why results are often
so different between methods. This article is intended
to be understood by both the lay person and the HVAC
professional. To help the lay person, some definitions
are in order.

When most people hear the word "load" they naturally
think of a load of firewood they carry into the house, or
a load of dirt in a dump truck, or maybe even a load
held up by a beam or structural member. All of those
loads are a "weight" to be carried or supported in some
way. Such loads are measured in pounds, kips, or
kilograms, depending on the units involved.

So what are heating and cooling loads? As pertains to heating and cooling equipment (an
HVAC System), a load is a rate of heat transfer. Not a single quantity of heat, but an
amount of heat that must be continually (at least for the worst case hour) removed or added
to maintain the desired indoor temperature. In the coldest time of winter, the peak heating
load is the amount of heat that must be added over an hour’s time to keep the space warm.
In the U.S. imperial units system, this rate of heat transfer is in Btu’s per hour which is
commonly abbreviated as Btuh. In the metric system the equivalent unit is a watt and one
watt is equal to 3.41 Btuh. In the hottest time of summer, the peak cooling load is the
amount of heat that must be removed in an hour to maintain a comfortable room
temperature. Again, the cooling load unit is either Btuh or watts.

What causes heating and cooling loads? A summer cooling load is a heat gain to the
building. The sun provides all of the heat that comes in through the exterior of the
building. And within the building itself, heat is generated by people, lights, equipment, and
appliances. A winter heating load is a heat loss that is caused by loss of heat from the
warm physical mass of the building to the cold air surrounding the building. Heat is lost
through the walls, windows, roof, and through cracks and crevices where cold air seeps
into the building.

It is important to know the peak heating and cooling loads on a building so that the HVAC
equipment can be adequately sized. An undersized HVAC system will not be able to
maintain the desired indoor temperatures. An oversized HVAC system will be inefficient,
and struggle to maintain comfort conditions, particularly with humidity control during
summer months.

Differences in HVAC Load Calculation Methods

HVAC load calculations are most often done using computer programs, although some
methods are still able to do be done by hand. Many people are often alarmed to learn that
http://www.elitesoft.com/web/newsroom/loadcalcs.html 1/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

various computer programs and hand calculations can differ so widely on calculation
results. After all, if each calculation is done with the same outside and inside temperatures,
same building material types, areas and quantities of roofs, walls, glass, people, lights,
equipment, etc., why should the results ever differ by more than a few percent?

Complex Problem

The physics involved in the transfer of heat and energy between buildings, occupants, and
the environment is quite complex. The most current and best math models of this problem
require significant input data and thousands of calculations in an iterative process. The
calculations are so involved that researchers have been forced for years to create various
simplified procedures that are doable by hand or within reasonable calculation time on a
personal computer. The cost of these simplifications from the theoretical best math models
is accuracy.

In theory, one generalized HVAC load calculation procedure should work for all types of
buildings. There would be no need for separate procedures for different types of structures,
either residential or commercial in nature. In fact, such a generalized method has been
developed in recent years, and it is called the Heat Balance (HB) method. And it can be
used on buildings of all types. However, there are various issues with HB, discussed later,
that make it less popular to use for peak load calculations than many of the less
sophisticated methods that are designed only for residential or commercial buildings.

Early HVAC researchers learned that simplifications in calculation methods could be made
if generalizations about the subject buildings could be assumed. This led to HVAC load
calculation methods that were designed only for residential or commercial buildings.

Residential buildings, in particular, were believed to be more simple in construction and
usage. Home owners were traditionally considered to be less demanding than commercial
building owners, especially since commercial buildings usually cost far more than houses.
For these reasons, residential HVAC load calculations procedures have traditionally been
much less sophisticated than commercial procedures.

Besides separate methods for commercial and residential buildings, another major factor
that has influenced load calculation methods over the years is the use of computers. Before
personal computers were widely available, simple procedures were even more important to
have, as doing calculations by hand is slow and tedious. Many procedures to this day still
have simplifications for the reason of making hand calculations possible.

Commercial Load Calculation Methods

In the calculation of commercial building peak heating and cooling loads, many methods
have been developed over the years. ASHRAE has TETD (Total Equivalent Temperature
Difference), CLTD (Cooling Load Temperature Difference), TFM (Transfer Function
Method), HB (Heat Balance) and RTS (Radiant Time Series). ACCA has the Manual N
method, an updated variation of the ASHRAE CLTD method.

There are two other calculation methods primarily used for 8,760 hour­by­hour annual
energy analysis that are also sometimes used for peak load calculations. All the various
computer programs such as EnergyPro, eQUEST, EnergyGauge USA, REM/Rate, and
others that are based on the DOE (Department of Energy) 2.1e program use what is known
as a weighting factor (WF) method. The most current and sophisticated energy analysis
program was developed by the U.S. government, and is called EnergyPlus. It uses the Heat
Balance (HB) method.

http://www.elitesoft.com/web/newsroom/loadcalcs.html 2/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

In general, the energy analysis methods, WF and HB, are more sophisticated than most of
the methods used just for peak heating and cooling loads, such as TETD and CLTD.
Although the WF and HB methods were primarily intended for 8,760 hourly analysis, they
can also find peak heating and cooling loads during the course of a year for all types of
buildings, both commercial and residential.

Residential Load Calculation Methods

ACCA has a residential load calculation procedure called Manual J. It has been updated
over the years, and is now on its eighth edition. As ACCA upgrades its procedures, it does
not create new names for the procedures. The name stays as Manual J and only the edition
number changes. The current ACCA residential method is commonly called MJ8.

ASHRAE has offered residential load calculation procedures for many years as well.
Unlike ACCA, ASHRAE creates a new name for a procedure when it undergoes a major
change or replaces an earlier procedure. In 1985, ASHRAE used the Design Equivalent
Temperature Difference (DETD) approach, and from 1989 through 2001 the procedures
were called the residential CLTD method. In 2005, ASHRAE introduced both the
Residential Load Factor (RLF) method and the Residential Heat Balance (RHB) method.

While ASHRAE introduced two new residential methods in 2005, the ASHRAE
Handbook of Fundamentals (HOF) in 2005 and 2009 supplies tables and shows an
example calculation using only the RLF method. In fact, the ASHRAE 2009 HOF states
that RHB is a research­oriented implementation of the HB method and that it is expected
that RHB will one day be incorporated into third­party software. As of the time of this
writing in April 2011, there is no software available that implements the ASHRAE RHB
method.

As explained above for the commercial procedures, the sophisticated WF (weighting
factor) and HB (Heat Balance) methods used in several building energy analysis programs
can also be used for calculating peak loads on residential buildings.

Result Differences

Once you realize that significant simplifications have been made in all the popular HVAC
load calculation methods, it is easy to understand why there will often be significant
differences in results from those procedures. Over time, these various methods have been
applied to the same buildings, with results sometimes differing by as much as 40%.
Inevitably, the question becomes, which results are the most accurate?

The greatest difference between calculation methods always happens when one method is
misapplied. For example, entering a complex building like a hospital as equally as possible
into an ASHRAE RTS computer program and into an ACCA MJ8 program will yield
hugely different results, with the RTS loads being much higher. This is easily
understandable, as the RTS program calculates hour by hour, and the MJ8 program uses
simplified weighted average factors for roof and wall loads. In such an example, there is
no problem at all in acknowledging which results are more accurate.

Let's consider a more realistic case where the ACCA MJ8 procedures are used on the same
house as the ASHRAE RLF procedures. In this case you have two residential specific
procedures used appropriately on their intended type of building, a house. Additionally,
both procedures are based primarily on the use of lookup tables such that the calculations
are still doable by hand. Will the results from these procedures differ? Absolutely!

Assuming all areas, temperatures and other data have been entered as equally as possible,
http://www.elitesoft.com/web/newsroom/loadcalcs.html 3/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

result differences between MJ8 and RLF will vary much less than between disparate
methods such as RTS and RLF. However, loads will still tend to be higher with MJ8
because it has hourly load factors on glass (but not on roofs and walls), while the RLF
method uses averaged load factors (no unique hourly load factors) for all exterior building
surfaces, including glass.

The above two examples illustrate relatively straight forward reasons for differences in
results between methods. Some load calculation procedures have very obvious differences
in methods. The method using the more advanced technique is usually more accurate.

More Reasons for Result Differences

There are many difficulties in trying to compare HVAC load calculation methods.
Assuming that all quantities of load components (roof, wall, and glass areas, number of
people, lights, equipment, etc.) are made equal, and that all indoor and outdoor design
temperatures are equal, there is still a great deal of variability for many other input items.

For example, one method like the CLTD procedure offers only seven types of walls in
categories A­G. You can assign what ever U­factor you like to a wall, but every wall in the
world must fall into one of the seven categories that is primarily distinguished by the
thermal mass of the wall. Other methods like HB, allow for smooth and infinite variations
of wall types with different thermal mass.

When using the CLTD method, many real world walls could be legitimately selected as
either of two CLTD wall type categories, as they are not clearly in one category or another.
The same thing happens for roofs under the CLTD method, where only 13 roof types are
provided.

The MJ8 method is derived from the CLTD method, and thus has similar limitations on the
roof and wall categories. The ASHRAE RLF method has even more limited selections for
roofs and walls. These finite "type" selections cause abrupt differences in loads calculated
for a roof or wall of the same U­factor and same indoor­outdoor temperature differences.
The more simple the load calculation method, the fewer the "type" categories provided for
roofs and walls.

There is also a chance for great disparity on glass loads because there is both a
transmission and solar component to deal with. Many of the tabular based methods make
great simplifications, especially with the solar gains. Even fairly sophisticated methods can
show significant differences on glass solar gains.

More than actual calculation method differences, the most common reasons for differences
in load calculation reports from different computer programs on the same building are
from quantity discrepancies. Sometimes there are just outright mistakes on roof, wall, and
glass areas. Same goes for the count on people, lights, and equipment. Confusion over how
to handle fresh air in terms of ventilation or infiltration causes significant differences as
well.

Even when expert load calculation software users compare results on the same building
there will be differences. As discussed above, there are judgment calls on building material
type selections that experts can disagree on, and yet can defend their selections with equal
validity.

Which Method is Most Accurate?

The first question many people often ask is, which HVAC load calculation method is most
http://www.elitesoft.com/web/newsroom/loadcalcs.html 4/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

accurate? There is unanimous agreement that the Heat Balance method most accurately
reflects the true physics involved in heat gains and losses to buildings. And yet at this time,
there is no dedicated residential or commercial peak load computer program that uses the
HB method. Only the EnergyPlus software uses the Heat Balance method and EnergyPlus
is used primarily for building energy analysis, not peak load analysis.

There are two main reasons HB is not yet widely used in HVAC peak load calculation
software. First, there is the complexity of the HB method. A designer must be prepared to
enter more data and more details for all the load components. This is time consuming, and
requires more thought and engineering judgment. Second, and most importantly, is that the
HB procedures "blend" all the component loads (roofs wall, glass, etc.) together during the
calculation process. At the end of the calculation process, only a single number as a gain or
loss in heat results. There is no way to see how much effect there was from the windows or
the people or the lights, etc.. Everything is blended, or rather "balanced," before a final
result is obtained.

Since so many economic decisions are made as to whether to use certain building materials
or not, HVAC designers often find it imperative to be able to review component details of
an HVAC load calculation. All non­HB load calculation methods preserve this ability. The
Radiant Time Series (RTS) method is the closest in accuracy to the HB method while still
providing component load details.

At this point in time, the RTS method is only available as an ASHRAE sponsored method
primarily for use on commercial buildings. The RTS method is robust enough that, like the
HB method, it could theoretically be used on both commercial and residential buildings.
However, the RTS method relies heavily on the conduction time series (CTS) concept,
which helps to model the time lag of heat transfer for various building materials. Very light
poorly insulated materials can transfer all the heat from a test heat "pulse" in as few as four
hours, whereas well insulated heavy materials might need a full 24 hours to transfer all the
heat from a test pulse. The CTS series for a material describes that reaction to heat.

ASHRAE provides about 35 suggested CTS values for mostly commercial building
material combinations. For the RTS method to be used properly for residential peak load
calculations, CTS values would need to be generated for more residential roof and wall
materials, and this has not yet been done.

If the HB method is the acknowledged most accurate method, but has the drawbacks
mentioned above that make it so rarely used for peak load calculations, what then are the
most accurate practical peak load calculations methods available today?

For commercial buildings, it is this writer’s opinion that the ASHRAE RTS method is the
best overall method, as high accuracy is obtained while also preserving the details of load
contributions from all the various internal and external components. Good results can be
obtained from older and simpler methods such as the ASHRAE CLTD and TFM methods,
as well as the ACCA Manual N commercial method. So stating a preference for the RTS
method is in no way saying that the other methods should be avoided. An experienced
designer using those methods may very likely calculate more accurate results with those
methods than a novice using the RTS method.

For residential buildings, the ACCA Manual J 8th edition method is the best overall
method. It definitely lacks in sophistication compared to the ASHRAE HB and RTS
methods, but those methods are not fully developed for use on residential buildings. The
ACCA Manual J method has been honed for many years on residential structures, and has
a very successful track record.

http://www.elitesoft.com/web/newsroom/loadcalcs.html 5/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

Comparison of Residential Methods

It is not uncommon for individual HVAC designers to have a favorite HVAC load
calculation method that they use on all buildings. Consulting engineers often like using
ASHRAE commercial methods on all their projects, both residential and commercial.
HVAC contractors, on the other hand, often like to use the ACCA MJ8 method on all their
projects both commercial and residential. Both types of HVAC professionals generally
have a long history with their preferred method and know how to adjust the method for
various types of projects.

I am going to go out on a limb and state some broad generalizations that are based purely
on my own anecdotal experiences and what I have heard from thousands of HVAC
designers served by Elite Software for over 31 years. It is important to understand that
these generalizations have no scientific basis and could be completely wrong.

Skilled users of any load calculation method are able to adjust inputs in subtle ways that
can steer results high or low. All of my observations are based on a knowledgeable user
entering data as equally as possible, and with no attempt to influence the results.

Unlike with commercial methods, where there is more competition amongst the methods,
the Manual J method has been extremely dominant over the years with its number of users
versus anything else. In my opinion, the ACCA MJ8 method produces the most accurate
equipment sizing information for houses, even though it uses one of the more simplistic
methods (a simplified variation of CLTD). With many successful users of Manual J over
many years, I have developed a high confidence in Manual J. Thus, the current MJ8
method is what I will compare all other residential methods to.

The feedback I have from the very few people who have done ASHRAE RLF comparisons
with MJ8, indicates reasonable closeness of results, with RLF usually being slightly lower.
In the case of peak residential load calculations involving a DOE2 based program on a
house and using the weighting factor method, the MJ8 method will tend to be 15­20%
higher. The same thing happens when compared with the Heat Balance method. MJ8 tends
to be higher in the same range.

When MJ8 is compared to the ASHRAE CLTD or RTS method on a house, those two
commercial methods tend to be 15­25% higher than MJ8. Consulting engineers are often
conflicted about this. They know the ASHRAE commercial methods have built­in
assumptions for commercial buildings, but they wonder whether that matters much. Many
engineers prefer using the higher loads from the ASHRAE commercial methods and
believe there is no problem with using those methods on houses.

As a final note on residential methods, a lot of questions come up about how MJ8
compares to MJ7. When MJ8 was first released in 2003, many MJ8 calculations were
coming out higher than MJ7 for the same house. It turned out that the way users were
interpreting duct inputs in MJ8 caused those loads to go much higher than MJ7. Addenda
C of MJ8 added additional duct inputs that tended to reduce the duct heat gains. After
further testing, it was found that MJ8 and MJ7 tended to agree within plus or minus 5%,
with MJ8 sometimes being lower and higher than MJ7.

While MJ8 results compared closely with MJ7 results on equivalent building materials,
new materials is where MJ8 surpassed MJ7. MJ8 includes hundreds of more roof, wall,
and glass material types than MJ7. With some modern material types, like insulated
concrete forms, MJ7 simply can’t calculate well for those, while MJ8 can. Besides material
issues, infiltration and duct gains and losses were made more accurate in MJ8 as well. So
while overall results on projects that both methods can address aren't huge, MJ8 was still a
http://www.elitesoft.com/web/newsroom/loadcalcs.html 6/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

big improvement over MJ7.

Comparison of Commercial Methods

In the comparison of commercial load calculation methods, there is more controversy over
which method is best than there is with residential methods. The three most popular
commercial methods are ASHRAE CLTD, TFM, and RTS. ACCA has a commercial
method called Manual N, which is a variation of the CLTD method, so all comments
concerning the ASHRAE CLTD method are applicable to the ACCA Manual N method.

The HB method is not used in any dedicated commercial peak load calculation program at
this time, but it is used in the EnergyPlus energy analysis program, which is sometimes
used by a very small percentage of designers as a peak loads program. The WF method
used in all the DOE2 derivative programs is also used by a small percentage of designers
for the calculation of peak loads

The ASHRAE CLTD method is the oldest of the current popular commercial methods, and
was first introduced back in the 1977 HOF. It was further explained in the 1979 ASHRAE
GRP­158 manual. It is actually a simplification of the TFM method much in the same way
that RTS is a simplification of the HB method. The basis for the TFM method was first
published in the 1972 ASHRAE HOF. However, the TFM method is more math intensive
than CLTD, so it took much longer to develop into useable a form for HVAC designers.

Being a simplified method derived from TFM and able to be tabularized, the CLTD
method was able to be used by designers with slide rules, early calculators, and pencil and
paper. It was also simple enough that it could be automated on very early small 64k
memory personal computers (called microcomputers in those days). Elite Software was the
first to implement CLTD on personal computers back in 1979. In the mid 90’s, personal
computers gained enough memory and computational capability that the TFM method was
able to be implemented.

The CLTD method enjoyed popularity right from 1977, and if it was derived from TFM,
shouldn't a true TFM method become more popular than CLTD? In my opinion, the TFM
method did not become more popular than the CLTD method. Carrier exclusively adopted
TFM into its software, while Trane offered it as an option along with CLTD and other
methods.

Elite Software never adopted the TFM method, as there were a lot of discrepancies with
CLTD results on glass solar loads, especially with the south orientation. Some people
argued that TFM, being more math oriented, should be trusted over CLTD in those cases,
but many engineers believed that the reduced TFM solar loads, sometimes as much as 40%
lower than CLTD, were not believable. This controversy was large enough that Elite
Software never implemented the TFM method into its software.

Besides questions about glass solar load accuracy, another reason so many HVAC
designers continued to prefer the CLTD method was that it was manually verifiable. A
designer was still able to verify by hand the calculations of any computer program that
used the CLTD method. With the TFM method, the calculations were so involved that
there was no practical way for a designer to manually verify them. Results from a
computer program using the TFM method were essentially "black box" results that had to
be accepted on faith alone.

As time passed, HVAC designers became more comfortable accepting results that could
not be manually verified. This helped increase the popularity of TFM, but also opened the
door for accepting other improved methods that could not be easily hand verified.
http://www.elitesoft.com/web/newsroom/loadcalcs.html 7/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

In the 2001 ASHRAE HOF, the HB and RTS methods were introduced. As mentioned
previously, the HB method is theoretically the most accurate method of peak load
calculations. Elite Software studied these methods and learned why two methods were
introduced simultaneously, something ASHRAE had never done before. HB was
developed for maximum accuracy while RTS was derived from HB to preserve component
load contributions in the final results that the HB method does not preserve.

In discussion with various developers of the HB and RTS methods, Elite Software was
able to determine that RTS was preferred by most consulting engineers. And just as
important, it was discovered that glass load results from RTS did not differ as much from
CLTD as TFM differed from CLTD. Thus, anecdotal confidence in the accuracy of the
RTS results was high, and Elite Software became the first software company to implement
the RTS method in commercially available software in 2004.

In my observations over the years and across a broad spectrum of projects and locations,
the CLTD method has tended to calculate overall higher than TFM, typically about 10­
15%. As mentioned before, specific glass solar calculations could be higher by as much as
40%. The CLTD and RTS methods compare fairly closely, and either method can be plus
or minus 5­10% of each other. This close agreement happens when making close matches
of CLTD material types with RTS material types, i.e., first selecting a CLTD building
material, and then matching it to an RTS material.

If you go in the other direction from RTS to CLTD, RTS allows so much variation and
sensitivity on material variations that you can’t always get a good match with a CLTD
material. A major benefit of RTS over CLTD is the provision for absorptance, emittance,
Delta R, and H­outside coefficients. The effects of these factors are built into the CLTD
tables and are not specific user inputs as they are with RTS.

When compared to peak loads obtained from the DOE2 WF method and the EnergyPlus
HB method, it always seems to me that those methods calculate lower than CLTD, TFM,
and RTS, usually in the range of 10­25% lower. This is very easy to explain for winter
heating loads. The energy analysis programs when used as peak load programs always take
credit for any solar gains, people, lighting and equipment loads to help offset winter heat
losses.

The specific peak load methods are more conservative and do not give credit for any
offsetting loads to winter heat losses. To me, the conservative approach is justifiable, as
the peak winter heat loss can easily occur in the dark of night with no one at home and no
lighting or equipment operating.

Why the energy programs using WF and HB methods tend to always calculate low on peak
cooling loads compared to MJ8, CLTD, TFM, and RTS is harder to understand. One
reason that it is hard to analyze is that the energy programs don’t give a good break out of
the individual component loads. So you can’t compare differences in the roof, wall, and
glass loads at the worst case outdoor design conditions.

Another reason I believe there are frequent differences in the peak loads of energy
programs is that it is harder for a designer to control what the extreme upper and lower
outside temperatures are. Many designers don’t make sure the outside design temps are
equal when comparing peak loads from an energy program to a dedicated peak loads
program. The energy programs tend to use less extreme outdoor temperatures and this
reduces the peak loads they calculate.

Whatever the reasons for these differences, many designers do not trust sizing HVAC
equipment based on the peak heating and cooling loads obtained from software primarily
http://www.elitesoft.com/web/newsroom/loadcalcs.html 8/9
13/10/2015 HVAC Peak Load Calculation Methods – History and Comparisons

developed for building energy analysis. I agree with that concern, as there is a high risk of
under sizing HVAC equipment when it is sized based off the peak load calculations from
various energy analysis programs. This concern is valid for equipment sizing in both
residential and commercial applications.

In my opinion, the ASHRAE RTS method is the best overall commercial peak load
calculation method available today, as it provides both high accuracy and component load
contribution (roof, wall, glass, etc.) reporting. Perhaps someone will develop an approach
in the future that allows the HB method to retain component loads in the final results.
Perhaps designers may evolve to where component load details are not so important to
them. Perhaps a completely new theory will be developed that is more accurate than HB
and with preservation of component loads. But until then, I believe RTS is the best overall
commercial HVAC peak load calculation method available today.

Summary

In the residential world, the ACCA MJ8 procedures remain the most popular residential
sizing method. The MJ8 procedures are not technically advanced compared to the
dedicated commercial methods such as TFM and RTS. And MJ8 is certainly not as
advanced as the methods able to do both residential and commercial peak loads and energy
analysis such as the WF and HB methods.

But what MJ8 has going for it is years of dedicated specific residential structure heat
transfer analysis. This has allowed the development of hundreds of load factor tables that
represent very well what happens in peak HVAC loads on residential structures. As ACCA
continues to refine its procedures, I think the Manual J method will see big changes in the
coming years as it catches up on calculation theory with the more advanced commercial
and energy analysis methods.

As mentioned before, the ASHRAE RTS method is a great method in that it employs only
a small compromise from the HB method in order to maintain component load
contributions. I think the RTS method has a very long future, with only small refinements
needed.

About the Author:

Bill Smith is the president, owner, and founder of Elite Software. Mr. Smith wrote the first
commercially available load calculation program using ASHRAE CLTD procedures in
1979. Elite Software was the first company to sell an ACCA Manual J program based on
the 6th edition in 1984. Mr. Smith invites your comments on this article, and will continue
to update it as more developments occur.