Professional Documents
Culture Documents
216 1MRB520270-Uen
Edition August 2001
p
Operating Instructions
ICC
COM581 SCS
PC
PC-Card
Card PC
PC-Card
Card BA + SC
RE. .16
RE..16 RE. .16 RER 581
PC
PC-Card
Card PC
PC-Card
Card
500BOM11 500BIM11
BIM
2000 ABB Power Automation Ltd
Baden/Switzerland
2nd Edition
All rights with respect to this document, including applications for patent and
registration of other industrial property rights, are reserved. Unauthorised use, in
particular reproduction or making available to third parties, is prohibited.
This document has been carefully prepared and reviewed. Should in spite of this
the reader find an error, he is requested to inform us at his earliest convenience.
The data contained herein purport solely to describe the product and are not a
warranty of performance or characteristic. It is with the best interest of our
customers in mind that we constantly strive to improve our products and keep
them abreast of advances in technology. This may, however, lead to discrep-
ancies between a product and its Technical Description or 'Operating Instructions'.
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
Contents
1. INTRODUCTION.........................................................................3
1.1. General .......................................................................................3
1.2. Abbreviations and definitions ......................................................3
1.3. References..................................................................................4
1.4. Application in the system ............................................................5
1
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
6. INDEX .......................................................................................31
2
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
1. INTRODUCTION
1.1. General
The RE. .16 is coupled to the MVB which is used as interbay bus
by an MVB personal computer card (PCC). This provides the
slave functions that are needed to exchange data with the
COM581 and interlocking data between the various RE. .16
units.
Interlocking data can be exchanged in binary form between
RE. .16 units connected to the same MVB interbay or process
bus.
The user thus has the possibility of transferring process control
data and data between RE. .16 units and between an RE. .16
unit and the station automation system (SCS).
This document describes the operation of the MVB interbay bus
software from Version V4.4 onwards. A corresponding descrip-
tion of the software for the MVB process bus is to be found in [6].
3
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
1.3. References
[1] 1MRB520050-Ude: Operating Instructions REL 316*4
[2] 1MRB520051-Ude: Operating Instructions RET 316*4
[3] 1MRB520049-Ude: Operating Instructions REG 316*4
[4] 1MRB520044-Ude: Operating Instructions REC 316*4
[5] 1MDU02005-DE: Operating Instructions RE. 216
[6] 1MRB520192-Ude: Operating Instructions RIO 580
[7] IEC TC9 WG22: Train Communication Network, Parts 1 - 6,
Specification of the Multifunction Vehicle Bus and Wire
Train Bus, Edition November 95
[8] IEC 60870-5-101: Telecontrol Equipment and Systems,
Transmission Protocols, Companion Standard for Basic
Telecontrol Tasks, 1994
[9] MVB Application Guidelines for Substation Automation
(Interbay Bus) Version 2.0
4
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
ICC
COM581 SCS
PC
PC-Card
Card PC
PC-Card
Card BA + SC
RE. .16
RE..16 RE. .16 RER 581
PC
PC-Card
Card PC
PC-Card
Card
500BOM11 500BIM11
BIM
The interbay bus is used for exchanging data between the intel-
ligent communication controllers (COM 581) and the bay units
(e.g. REC 216) and between the bay units themselves. The bus
administrator runs on an RER 581 device which also includes
the star-coupler for the optical fibre cable bus.
5
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
6
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
The RE. 316*4 has four Type 2 PCC slots (Figure 2.2). The MVB
PCC’s can be inserted in slots A and B.
Slot C Slot A
Slot D Slot B
The RE. 216 has two Type 2 PCC slots per 216VC62(a) (Figure
2.3). However, because of mechanical restrictions, the MVB
PCC can only be inserted in Slot A and a second 216VC62(a)
has to be fitted where two PCC’s are necessary (e.g. for the
MVB process bus).
Slot B Slot A
Caution:
• Do not insert or withdraw an MVB PCC while the supply is
switched on.
• An MVB PCC can only be inserted in an RE. 216 or
RE. 316*4 unit the one way round (mechanical key).
• Cover optical channels that are not in use.
• Take care to secure the MVB PCC in the RE. 216 /
RE. 316*4 using the holder supplied.
• Always handle the MVB PCC carefully.
7
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
TX TX
PC Card Star-coupler
RX RX
2.3. Commissioning
Using the HMI, firstly check that all the settings have be set to
the values determined when engineering the project. It is most
important to make sure that the MVB PCC is inserted in the cor-
rect slot. A PCC for the process bus must not be active in the
same slot.
Use the HMI diagnostic function to determine that the PCC soft-
ware runs properly (after initialisation, Ready and No error must
be display for PCC status and PCC error respectively).
8
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
Interlocking Yes No
9
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
Note:
The node address identifies a device connected to the interbay
bus. Of the available eight Bits, only six are used at present
(0...63).
Bus refers to the MVB segment.
Reference is also made to the RE. .16 address format and in this
respect, note should be taken of the following:
The SPA slave number of an RE. .16 unit is the same as the
node number and has to be in the range 1...63. The Byte ‘Bus’
always has to be set to 1.
The station address is the SPA channel number. As far as pos-
sible, the numbers defined for the SPA bus are used (with ex-
tensions in some cases):
101 ... 116 Input signal events: RE. 216, Slots 6 ... 21
and RE. 316*4, Slots 1 ... 4
71 ... 88 Protection function events
121 ... 126 Protection function events
129 ... 134 Double commands to the FUP
153 ... 192 Events from a device connected to the pro-
cess bus (BIM, PBI)
10
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
11
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
11 Spare
12 Spare
13 Spare
14 Spare
Note:
Input signals received from the process are automatically con-
nected to the corresponding Bit in the dataset. Function outputs
and measured variables, on the other hand, have to be assigned
to the respective dataset using the HMI.
The address actually used for a dataset on the MVB interbay bus
is determined from: MVB address = 16 * Node No. + Dataset No.
An RE. 216 input module uses 32 Bits and an RE. 316*4 16 Bits.
A BIM module also uses 16 Bits.
The first input of an input module is always transferred at the first
position of the dataset for the corresponding slot.
Example: RE. 316*4 Input 1, Slot 2: Bit 16 in LBI_Set [1].
12
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
• Value (WE):
The value to be downloaded in the case of a write command.
13
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
Example 1
Assuming the first signal relay on the first binary board of an
RE. 316*4 has to be set, the device address (slave / node ad-
dress) is 8:
Command: 8W101O1:1:
Response: 8A:Checksum
Example 2
Assuming the second binary input on the first binary input board
of an RE. 316*4 has to be read, the device address (slave / node
address) is 6:
Command: 6R101I2:
Response: 6D:Value:Checksum
14
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
^__=méñÉë=^îìéå~ìáéç=iìÇob`PNSGQ=J=`éçìëéä=rçáì
bÇáì=cîçÅìáéç=m~ë~åÉìÉëí!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!"
⌐============================================================================⌐
⌐=cîçÅ=kë=N=J=`îëëÉçìJaq==================G==G===============================⌐
⌐============================================================================⌐
⌐==m~ëpÉìQKKN================pÉäÉÅì=_áç~ëò=lîìèîì!"=========pÉäÉÅì==========⌐
⌐==qëáè======================⌐=====================⌐=========================⌐
⌐==aÉä~ò=====================⌐=pá,pÉäÉÅì=p`pJdëéîè....................../====⌐
⌐==fJpÉììáçÖ=================⌐=pá2======================================2====⌐
⌐==j~ójáç====================⌐=bï2=[==N=================================2====⌐
⌐==këlÑmÜ~íÉí================⌐=që2======================================2====⌐
⌐==`îëëÉçìfçè================⌐=pá2=rí~ÄäÉ=p`pJdëéîè=====================2====⌐
⌐==_äéÅâfçè==================⌐=lî2======================================2====⌐
⌐==qëáè======================⌐=lî2====NKKOQINÅKKOQÅ=====================2====⌐
⌐==pì~ëì=====================⌐=ob2======================================2====⌐
⌐==obqrokLbkqbo==============⌐===>......................................?====⌐
⌐============================@!!!!!!!!!!!!!!!!!!!!!A=========================⌐
⌐============================================================================⌐
⌐============================================================================⌐
@!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!A
lç=J=iáçÉ=VSMM=Äèí===p`pWjs_sSKO=ú=sSKO
Note:
Signal acquisition is only available for signals generated by func-
tions and not for binary signals directly connected from the input
boards.
15
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
^__=méñÉë=^îìéå~ìáéç=iìÇob`PNSGQ=J=`éçìëéä=rçáì
j~áç=jÉçî!!!!!!!!!!!"₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=bÇáìéë!!!!!!!!!!!!!!!!!!!!!"₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=bÇáì=e~ëÇñ~ëÉ=cîçÅìáéçí!!!!"₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=,f__=`éçÑáÖK................/₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2===========================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2=dÉçÉë~ä=f__=m~ë~åÉìÉëí====2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2=pm^=m~ë~åÉìÉëí============2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2=ilk=m~ë~åÉìÉëí============2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2=js_Jf__=m~ë~åÉìÉëí========2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2=js_Jofl=m~ë~åÉìÉëí========2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=⌐=2=js_Jfqi=m~ë~åÉìÉëí========2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
@!@!⌐=2=js_J_^=m~ë~åÉìÉëí=========2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧@!2=ié~Ç=j_^m~ëí=Ñëéå=cáäÉ====2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧2=p~ïÉ=oflJm~ëí=ìé=cáäÉ=====2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧2=ié~Ç=oflJm~ëí=Ñëéå=cáäÉ===2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧2=obqrok====================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧2===========================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧>...........................?₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
lç=J=iáçÉ=VSMM=Äèí===p`pWjs_sSKO=ú=sSKO
16
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
17
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
Explanation of parameters:
IBB-PCC-Slot
Defines the slot into which the PCC for the interbay bus is in-
serted. The following settings are possible:
• notUsed
• A
• B
• C (RE. 316*4 only)
• D (RE. 316*4 only)
IBB-TimeSync
The setting of this parameter switches the time synchronisation
on and off. The following settings are possible:
• no: Time synchronisation is switched off
• yes: Time synchronisation is switched on
SOE-DestAddr1...4
These four parameters define the target nodes to which the
events (SOE) have to be transmitted. Up to four target nodes
can be defined (addresses 1 to 4). A value of ‘0’ for a target ad-
dress means that no events are transferred to the interbay bus.
Normally the COM581 node address(es) is (are) displayed here.
BusSegNr
Defines to which bus segment an RE. .16 is connected.
Cycle
Defines the refresh rate for measured variables transmitted via
the interbay bus. Note: The actual cycling time for process data is
determined by the configuration of the bus administrators. The re-
fresh rate defined by this parameter should agree with the one
actually measure. The following settings are possible:
• 4 ms
• 8 ms
• 16 ms
• 32 ms
• 64 ms
• 128 ms
• 256 ms
• 512 ms
• 1028 ms.
18
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
Block SCSCmd
This parameter defines a binary signal which if TRUE, blocks
commands received via the interbay bus.
F: - Not blocked
T: - Blocked
xx: - All binary inputs or outputs of a protection function
BlockProcDat
This parameter defines a binary signal which if TRUE, blocks the
transfer of process data which have changed and SOE’s via the
interbay bus.
F: - Not blocked
T: - Blocked
xx: - All binary inputs or outputs of a protection function
BlckPrDatSig
A binary signal for reporting the status of the BlockProcDat sig-
nal. It is TRUE when the transfer of process data is blocked.
IBB-MW 1...15
These parameters are for selecting up to 15 measured variables
from protection functions and/or FUP programs for transfer as
process data via the interbay bus.
DeltaVal 1...15
These parameters enable a value, the so-called delta, to be de-
fined for each measured variable in order to reduce the number
of changes that have to be transferred. A new value is then only
transferred when it varies in relation to the last value transferred
by the amount of the setting for this parameter.
Nothing is transferred if the measured variable is lower than half
of the setting (suppresses small fluctuations of measure vari-
ables).
The principle of transferring measured variables is shown sche-
matically in Figure 4.3.
19
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
Measured variable
t1 t2 t3 t4 t5 t6 t7 t8 t9 t10 t11 t
20
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
ITL-PCC-Slot
This parameter determines whether ITL data are used or not and
if so, via which bus they are transferred. The following settings
are possible:
• notUsed
• on MVB-RBIO (transferred via process bus)
• on MVB-IBB (transferred via interbay bus).
21
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
REaxx.EVT
This file contains a list of all the events transferred via the inter-
bay bus. All the events configured for an RE. .16 are set to “ON”
and the others to “OFF”. This file can be edited in cases where
fewer events have to be transferred via the IBB as recorded in
RE. .16 (replace “ON” by “OFF”). The edited file can be down
loaded to the RE. .16 using the menu item ‘Load SCS masks’ (see
Figure 5.1).
REaxx.INP
This is a text file with sections separated by dash-dot lines. It
contains information on all the inputs connected to data points
controlled by the SCS and can be edited using MS EXCEL.
22
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
REaxx.OUT
This is a text file with sections separated by dash-dot lines. It
contains information on all the system’s binary output signals
connected to local relay outputs or SCS data points and can be
edited using MS EXCEL.
REaxx.PBI
This is a text file with sections separated by dash-dot lines. It
contains information on all the system’s binary output signals
connected to a relay in a BOM or PBI module and can be edited
using MS EXCEL.
REaxx.SIG
This is a text file with sections separated by dash-dot lines. It
contains information on all the system’s binary signals and all
protection and control functions and can be edited using MS
EXCEL.
23
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
5.1. Diagnostics
The menu items ‘Diagnostics’, ‘IBB information’ and ‘MVB-
DiagnosisInfo’ enable various details of the PCC and the status
of the connection to it to be viewed.
^__=méñÉë=^îìéå~ìáéç=iìÇob`PNSGQ=J=`éçìëéä=rçáì
j~áç=jÉçî!!!!!!!!!!!"₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=,aá~ÖçéíìáÅí........../₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=====================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=iáíì=aá~ÖfçÑé=======2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=dÉì=eÉó=aîåè========2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=`äÉ~ë=eÉó=aîåè======2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=f__JfçÑéëå~ìáéç=====2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=oflJfçÑéëå~ìáéç=====2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=oÉíÉì=p`pJfçèîìÇ~ì~=2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=ié~Ç=p`pJj~íâí======2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=2=obqrok==============2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
@!2=====================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧>.....................?₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
lç=J=iáçÉ=VSMM=Äèí===p`pWjs_sSKO=ú=sSKO
^__=méñÉë=^îìéå~ìáéç=iìÇob`PNSGQ=J=`éçìëéä=rçáì
j~áç=jÉçî!!!!!!!!!!!"₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=aá~ÖçéíìáÅí!!!!!!!!!!"₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=,f__JfçÑéëå~ìáéç........../₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=2=========================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=2=dÉì=js_Jaá~ÖçéíáífçÑé===2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=2=`äÉ~ë=js_Jaá~ÖçéíáífçÑé=2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=2=dÉì=js_=jÉíí~ÖÉí========2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=2=obqrok==================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=2=========================2₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=>.........................?₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
⌐=⌐=obqrok==============⌐₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
@!⌐=====================⌐₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧@!!!!!!!!!!!!!!!!!!!!!A₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧₧
lç=J=iáçÉ=VSMM=Äèí===p`pWjs_sSKO=ú=sSKO
24
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
^__=méñÉë=^îìéå~ìáéç=iìÇob`PNSGQ=J=`éçìëéä=rçáì
,............................................................................/
2============================================================================2
2=js_Jf__Jaá~ÖfçÑéW==========================================================2
2============================================================================2
2téëâáçÖ=jéÇÉW========fçìÉëÄ~ò_îí============================================2
2m`J`~ëÇ=pì~ìîíW======oÉ~Çò==================================================2
2m`J`~ëÇ=bëëéëW=======ké=bëëéë===============================================2
2m`J`~ëÇ=qòèÉW========fçìÉëÄ~ò_îí============================================2
2m`J`~ëÇ=ptJsÉëíW=======NKMO==NVVUJNNJMU=====================================2
2m`J`~ëÇ=eÉ~ëì_É~ìW======QTPO================================================2
2aëáïÉë=pì~ìÉW==================ëÉ~Çò========================================2
2aëáïÉë=eÉ~ëìÄÉ~ìW=========QP================================================2
2këK=éÑ=ëÉÅÉáïÉÇ=jÉíí~ÖÉíW===========O=======================================2
2këK=éÑ=ìë~çíåáììÉÇ=jÉíí~ÖÉíW=======ON=======================================2
2këK=éÑ=që~çíåáííáéç=c~áäíW==========M=======================================2
2këK=éÑ=äéíì=áçÅéåáçÖ=jÉíí~ÖÉíW======M=======================================2
2============================================================================2
2============================================================================2
>............................................................................?
lç=J=iáçÉ=VSMM=Äèí===p`pWjs_sSKM=J=sSKM
25
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
26
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
No State The RE. .16 driver software did not start. A likely
cause is that the slot for the PCC has not been
configured.
Not Ready The RE. .16 driver software is not ready. Probably
there is no PCC in the slot configured.
27
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
28
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
5.4.1. General
Process data transferred via the MVB interbay bus can be
viewed using the HMI (see [1] to [5], Section 5.7.).
29
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
Caution:
Event information can be lost when events are generated in
the test mode (and the menu item “Test functions” is se-
lected in the HMI), because the monitor that checks whether
the COM581 has accepted the last event to be transmitted is
switched off in the test mode. Thus the generation of events
can be checked even though no COM581 is active.
30
MVB Interbay Bus 1MRB520270-Uen / Rev. A ABB Power Automation Ltd
6. INDEX
Dataset addresses, 12
Device addresses, 17
Diagnostics, PCC, 25
Event addresses, 10
Event mask file, 22
Event masks, loading and deleting, 28
Event target address, 18
Event transmission, checking, 29
Events, viewing, 29
Target address, 18
31
ABB Power Automation Ltd MVB Interbay Bus 1MRB520270-Uen / Rev. A
Viewing events, 29
32
Daten löschen
Dear User,
Have you discovered any mistakes in this publication? If so, please note here the
pages, sections etc.
Do you find the publication readily understandable and logically structured? Can you
make any suggestions to improve it?
Is the information sufficient for the purpose of the publication? If not, what is missing
and where should it be included?
Name Date
Company
Dear User,
Should you be obliged to call on our repair service, we kindly ask you to attach a note
to the unit describing the fault as precisely as possible. This will assist us to carry out
the repair swiftly and reliably and you will gain the benefit.
Please attach a completed form to every unit and forward them to the address below.
---------------------------------------------------------------------------------------------------------------
Equipment data:
Unit type:
Serial No.: HE ..................................
In operation since:
❑ Overfunction
❑ No function
❑ Outside tolerance
❑ Abnormal operating temperature
❑ Sporadic error
❑ Unit for checking
Remarks/Description of fault:
Customer: Date:
Address:
Dear User,
It is common experience that software does not always function as expected for all
applications. A precise description of the problem and observations will help us to
improve and maintain the software to your benefit. Please complete this form and
send it together with any supporting information or documents to the address below.
Description of problem:
Customer: Date:
Address:
___________________________________________________________________
ACTION (internal use of ABB Power Automation Ltd, Dept. NSS only)