Professional Documents
Culture Documents
Page No.
LIGHTNING ARRESTER 6
ISOLATOR 13
RELAYS 21
POWER TRANSFORMER 23
BUCHHOLZ RELAY 25
CURRENT TRANSFORMERS 29
POTENTIAL TRANSFORMER 31
CAPACITOR BANK 36
WAVE TRAP 37
BATTERY ROOM 41
CONTENTS
Page No.
Chapter 1: INTRODUCTION
1
Chapter 4: INSULATORS 10
Chapter 5: ISOLATORS 13
8.1: WINDINGS 23
8.4.4: CONSERVATOR 27
CONCLUSION 45
REFERENCES 46
CHAPTER 1
INTRODUCTION
Electrical power is generated, transmitted in the form of alternating current. The electric
power produced at the power stations is delivered to the consumers through a large network of
transmission & distribution. The transmission network is inevitable long and high power lines
are necessary to maintain a huge block of power source of generation to the load centers to inter
connected. Power house for increased reliability of supply greater.
The assembly of apparatus used to change some characteristics (e.g. voltage, ac to dc,
frequency, power factor etc.) of electric supply keeping the power constant is called a substation.
Substations have switching, protection and control equipment and one or more
transformers. In a large substation, circuit breaker are used to interrupt any short-circuits or
overload currents that may occur on the network.
Depending on the constructional feature, the high voltage substations may be
further subdivided:
(a) Outdoor substation
(b) Indoor substation
(c) Base or Underground substation
1.1) 220KV Grid Substation, Sanganer:
Its part of RVPN. It is situated 13.4km away from Jaipur. The power mainly comes from 220 KV
K.T.P.S, 220KV Heerapura (400KV) and 220 KV Heerapura (220KV) 132 KV Heerapura
(220KV). The substation is equipped with various equipments and there are various
arrangements for the protection purpose. The equipments in the GSS are listed previously. At this
substation following feeders are established.
1. TIE FEEDERS
2. RADIAL FEEDERS
220KV GSS SANGANER is an outdoor type primary substation and distribution as well it has
not only step down but the distribution work
The electrical work in a substation comprises to:
1. Choice of bus bar arrangement layout.
2. Selection of rating of isolator.
3. Selection of rating of instrument transformer.
4. Selection of rating of C.B.
5. Selection of lighting arrester [LA]
6. Selection of rating of power transformer
7. Selection of protective relaying scheme, control and relay boards.
8. Selection of voltage regulator equipment.
9. Design a layout of earthing grids and protection against lightening stockes.
Page-2
A) 132 KV:
1) Sitapura
2) Heerapura
3) Mansarovar
4) SMS Stadium
5) Balawala
6) Chaksu
B) 33KV:
1) Durgapura -1
2) Durgapura-2
3) Sanganer
4) Sitapura
5) I.O.C
6) Watika
7) Phagi
8) Malpura gate
9) Mandi
Page-3
C) 11KV:
1) Muhana
2) Tejawala
3) Prem nagar
4) Industrial
Rajasthan Rajya Vidyut Prasaran Nigam Limited (RVPN) a company under the Companies
Act, 1956 and registered with Registrar of Companies as "RAJASTHAN RAJYA VIDYUT
PRASARAN NIGAM LIMITED" vide No. 17-016485 of 2000-2001 with its Registered Office
at VIDYUT BHAWAN, JYOTI NAGAR, JAIPUR-302005 has been established on 19 July, 2000
by Govt. of Rajasthan under the provisions of the Rajasthan Power Sector Reform act 1999 as
the successor company of RSEB. The RERC has granted RVPN a license for transmission and
bulk supply vide RERC/Transmission and Bulk Supply License 4/2001 dated 30.
Our aim is to provide reliable electric transmission service to these customers. As a public
utility whose infrastructure serves as the link in transporting electricity to millions of electricity
users, RVPN has following duties and responsibilities:
Page-4
Page-5
CHAPTER 2
LIGHTNING ARRESTER
Fig.2.1- Lightning arrester [Ref.-7]
A lightning arrester (also known as surge diverter) is a device connected between line and
earth i.e. in parallel with the over headline, HV equipments and substation to be protected. It is a
safety valve which limits the magnitude of lightning and switching over voltages at the
substations, over headlines and HV equipments and provides a low resistance path for the surge
current to flow to the ground. The practice is also to install lightning arresters at the incoming
terminals of the line.
Page-6
All the electrical equipments must be protected from the severe damages of lightning strokes.
The techniques can be studied under:-
2.1.1) Rod/sphere gap:- It is a very simple protective device i.e. gap is provided
across the stack of Insulators to permit flash-over when undesirable voltages are
impressed of the system.
2.1.2) Expulsion type LA:- It have two electrodes at each end and consists of a fiber
tube capable of producing a gas when is produced. The gas so evolved blows the
arc through the bottom electrode.
2.1.3) Valve type LA:- It consists of a divided spark-gap in series will a non linear
resistor. The divided spark gap consists of a no. of similar elements, each of it
two electrode across which are connected high resistor.
Page-7
CHAPTER 3
BUS BARS
Bus Bars are the common electrical component through which a large no of feeders
operating at same voltage have to be connected.
If the bus bars are of rigid type (Aluminum types) the structure height are low and
minimum clearance is required. While in case of strain type of bus bars suitable ACSR conductor
are strung/tensioned by tension insulators discs according to system voltages. In the widely used
strain type bus bars stringing tension is about 500-900 Kg depending upon the size of conductor
used.
Here proper clearance would be achieved only if require tension is achieved. Loose bus
bars would effect the clearances when it swings while over tensioning may damage insulators.
Clamps or even effect the supporting structures in low temperature conditions.
The clamping should be proper, as loose clamp would spark under in full load condition
damaging the bus bars itself.
Page-8
3.1.1) SINGLE BUS BAR ARRANGEMENT :
This arrangement is simplest and cheapest. It suffers, however, from major defects.
1. Maintenance without interruption is not possible.
2. The load circuit may be divided in to two separate groups if needed from
operational consideration. Two supplies from different sources can be put on
each bus separately.
The normal bus selection insulators can not be used for breaking load currents.
The arrangement does not permit breaker maintenance without causing stoppage of
supply.
The double bus bar arrangement provides facility to change over to either bus to carry out
maintenance on the other but provide no facility to carry over breaker maintenance. The
main and transfer bus works the other way round. It provides facility for carrying out
breaker maintenance but does not permit bus maintenance. Whenever maintenance is
required on any breaker the circuit is changed over to the transfer bus and is controlled
through bus coupler breaker.
Page-9
CHAPTER 4
INSULATOR
The insulator for the overhead lines provides insulation to the power conductors from the ground
so that currents from conductors do not flow to earth through supports. The insulators are
connected to the cross arm of supporting structure and the power conductor passes through the
clamp of the insulator. The insulators provide necessary insulation between line conductors and
supports and thus prevent any leakage current from conductors to earth. In general, the insulator
should have the following desirable properties:
High mechanical strength in order to withstand conductor load, wind load etc.
These insulators are generally made of glazed porcelain or toughened glass. Poly come type
insulator [solid core] are also being supplied in place of hast insulators if available indigenously.
The design of the insulator is such that the stress due to contraction and expansion in any part of
the insulator does not lead to any defect. It is desirable not to allow porcelain to come in direct
contact with a hard metal screw thread.
Page-10
4.1.1) PIN TYPE: pin type insulator consist of a single or multiple shells adapted to
be mounted on a spindle to be fixed to the cross arm of the supporting structure.
When the upper most shell is wet due to rain the lower shells are dry and provide
sufficient leakage resistance these are used for transmission and distribution of
electric power at voltage up to voltage 33 KV. Beyond operating voltage of 33 KV
the pin type insulators thus become too bulky and hence uneconomical.
Page-11
4.1.2) SUSPENSION TYPE: suspension type insulators consist of a number of
porcelain disc connected in series by metal links in the form of a string. Its
working voltage is 66KV. Each disc is designed for low voltage for 11KV.
4.1.3) STRAIN INSULATOR: the strain insulators are exactly identical in shape
with the suspension insulators. These strings are placed in the horizontal plane
rather than the vertical plane. These insulators are used where line is subjected to
greater tension. For low voltage lines (< 11KV) shackle insulator are used as
strain insulator.
Page-12
CHAPTER 5
ISOLATORS
“Isolator" is one, which can break and make an electric circuit in no load condition. These are
normally used in various circuits for the purposes of Isolation of a certain portion when required
for maintenance etc. Isolation of a certain portion when required for maintenance etc. "Switching
Isolators" are capable of
Page-13
Its main application is in connection with transformer feeder as this unit makes it possible to
switch out one transformer, while the other is still on load. The most common type of isolators is
the rotating centre pots type in which each phase has three insulator post, with the outer posts
carrying fixed contacts and connections while the centre post having contact arm which is
arranged to move through 90` on its axis.
Page-14
CHAPTER 6
CIRCUIT BREAKER
The function of relays and circuit breakers in the operation of a power system is to
prevent or limit damage during faults or overloads, and to minimize their effect on the remainder
of the system. This is accomplished by dividing the system into protective zones separated by
circuit breakers. During a fault, the zone which includes the faulted apparatus is de-energized
and disconnected from the system. In addition to its protective function, a circuit breaker is also
used for circuit switching under normal conditions.
Each having its protective relays for determining the existence of a fault in that zone and
having circuit breakers for disconnecting that zone from the system. It is desirable to restrict the
amount of system disconnected by a given fault; as for example to a single transformer, line
section, machine, or bus section. However, economic considerations frequently limit the number
of circuit breakers to those required for normal operation and some compromises result in the
relay protection.
Circuit breaker can be classified as "live tank", where the enclosure that contains the
breaking mechanism is at line potential, or dead tank with the enclosure at earth potential. High-
voltage AC circuit breakers are routinely available with ratings up to 765,000 volts.
Page-15
Page-16
The principle of arc interruption in air blast circuit breakers is to direct a blast of air, at
high pressure and velocity, to the arc. Fresh and dry air of the air blast will replace the
ionized hot gases within the arc zone and the arc length is considerably increased.
Consequently the arc may be interrupted at the first natural current zero. In this type of
breaker, the contacts are surrounded by compressed air. When the contacts are opened the
compressed air is released in forced blast through the arc to the atmosphere extinguishing
the arc in the process.
Fig.6.2-Air Blast Circuit Breaker [Ref.-7]
Page-17
Advantages:
An air blast circuit breaker has the following advantages over an oil circuit breaker:
The arcing products are completely removed by the blast whereas the oil deteriorates
with successive operations; the expense of regular oil is replacement is avoided
The growth of dielectric strength is so rapid that final contact gap needed for arc
extinction is very small. this reduces the size of device
The arcing time is very small due to the rapid build up of dielectric strength between
contacts. Therefore, the arc energy is only a fraction that in oil circuit breakers, thus
resulting in less burning of contacts
Due to lesser arc energy, air blast circuit breakers are very suitable for conditions where
frequent operation is required
The energy supplied for arc extinction is obtained from high pressure air and is
independent of the current to be interrupted.
Disadvantages:
Air blast circuit breakers are very sensitive to the variations in the rate of restriking
voltage.
Considerable maintenance is required for the compressor plant which supplies the air
blast
Air blast circuit breakers are finding wide applications in high voltage installations.
Majority of circuit breakers for voltages beyond 110 kV are of this type.
Page-18
1. It absorbs the arc energy to decompose the oil into gases, which have excellent cooling
properties.
2. It acts as an insulator and permits smaller clearance between live conductors and
earthed components.
Page-23
Tank shall be of welded construction & fabricated from tested quality low carbon steel of
adequate thickness. After completion of welding, all joints shall be subjected to dye
penetration testing.
At least two adequately sized inspection openings one at each end of the tank shall be provided
for easy access to bushing & earth connections. Turrets & other parts surrounding the conductor
of individual phase shall be non-magnetic. The main tank body including tap changing
compartment, radiators shall be capable of withstanding full vacuum.
(a.) Each radiator bank shall have its own cooling fans, shut off valves at the top and
bottom (80mm size) lifting lugs, top and bottom oil filling valves, air release plug at the
top, a drain and sampling valve and thermometer pocket fitted with captive screw cap on
the inlet and outlet.
(b.) Cooling fans shall not be directly mounted on radiator bank which may cause
undue vibration. These shall be located so as to prevent ingress of rain water. Each fan
shall be suitably protected by galvanized wire guard.
Page-24
This has two Floats, one of them with surge catching baffle and gas collecting space at
top. This is mounted in the connecting pipe line between conservator and main tank. This
is the most dependable protection for a given transformer.
Gas evolution at a slow rate that is associated with minor faults inside the
transformers gives rise to the operation or top float whose contacts are wired for alarm.
There is a glass window with marking to read the volume of gas collected in the relay.
Any major fault in transformer creates a surge and the surge element in the relay trips the
transformer. Size of the relay varies with oil volume in the transformer and the mounting
angle also is specified for proper operation of the relay.
Most of the transformer (small transformers have only OTI) are provided with indicators
that displace oil temperature and winding temperature. There are thermometers pockets
provided in the tank top cover which hold the sensing bulls in them. Oil temperature
measured is that of the top oil, where as the winding temperature measurement is indirect.
Page-25
This is done by adding the temperature rise due to the heat produced in a heater coil
(known as image coil) when a current proportional to that flowing in windings is passed in
it to that or top oil. For proper functioning or OTI & WTI it is essential to keep the
thermometers pocket clean and filled with oil.
Fig.8.4-Winding and oil temperature indicator [Ref.-5]
Both transformer oil and cellulosic paper are highly hygroscopic. Paper being more
hygroscopic than the mineral oil The moisture, if not excluded from the oil surface in
conservator, thus will find its way finally into the paper insulation and causes reduction
insulation strength of transformer. To minimize this conservator is allowed to breathe
only through the silica gel column, which absorbs the moisture in air before it enters the
conservator air surface.
Page-26
8.4.4) Conservator:
With the variation of temperature there is corresponding variation in the oil volume. To
account for this, an expansion vessel called conservator is added to the transformer with a
connecting pipe to the main tank. In smaller transformers this vessel is open to
atmosphere through dehydrating breathers (to keep the air dry). In larger transformers, an
air bag is mounted inside the conservator with the inside of bag open to atmosphere
through the breathers and the outside surface of the bag in contact with the oil surface.
132/33 KV--------------------------------------20/25MVA 2
132/33KV---------------------------------------40/50MVA 1
Page-27
MAKE Company
Page-28
CHAPTER 9
CURRENT TRANSFORMER
As you all know this is the device which provides the pre-decoded fraction of the primary
current passing through the line/bus main circuit. Such as primary current 60A, 75A, 150A,
240A, 300A, 400A, to the secondary output of 1A to 5A.
Now a day mostly separate current transformer units are used instead of bushing
mounting CT’s on leveled structure they should be for oil level indication and base should be
earthed properly. Care should be taken so that there should be no strain as the terminals.
When connecting the jumpers, mostly secondary connections is taken to three unction boxes
where star delta formation is connected for three phase and final leads taken to protection
/metering scheme. There should be no chance of secondary circuit remaining opens as it leads to
extremely high voltage which ultimately damages the CT itself
Page-29
It can be used to supply information for measuring power flows and the electrical inputs for the
operation of protective relays associated with the transmission and distribution circuit or for
power transformer. These current transformers have the primary winding connected in series
with the conductor carrying the current to be measured or controlled. The secondary winding is
thus insulated from the high voltage and can then be connected to low voltage metering circuits.
Current transformers are also used for street lighting circuits. Street lighting requires a
constant current to prevent flickering lights and a current transformer is used to provide that
constant current. In this case the current transformer utilizes a moving secondary coil to vary the
output so that a constant current is obtained.
Page-30
CHAPTER 10
POTENTIAL TRANSFORMER
A potential transformer (PT) is used to transform the high voltage of a power line to a
lower value, which is in the range of an ac voltmeter or the potential coil of an ac voltmeter.
Electromagnetic type.
Page-31
Capacitive voltage transformer is being used more and more for voltage measurement in
high voltage transmission network, particularly for systems voltage of 132KV and above where
it becomes increasingly more economical. It enables measurement of the line to earth voltage to
be made with simultaneous provision for carrier frequency coupling, which has reached wide
application in modern high voltage network for tele-metering remote control and telephone
communication purpose.
Pushing Type
The performance of CVT is affected by the supply frequency switching transient and
magnitude of connected Burdon. The CVT is more economical than an electromagnetic voltage
transformer when the nominal supply voltage increases above 66KV.
The carrier current equipment can be connected via the capacitor of the CVT. There by
there is no need of separate coupling capacitor. The capacitor connected in series act like
potential dividers, provided, the current taken by burden is negligible compared with current
passing through the series connected capacitor.
The carrier current equipments is connected to the power line via coupling
capacitor. The coupling CVT combines the function of coupling and voltage transformer.
Page-32
CHAPTER 11
The porcelain in multi unit stack, all the potentials points are electrically tied and suitably
shielded to overcome the effect of corona RIV etc. Capacitive voltage transformers are available
for system voltage. [Ref.-4]
Page-33
CHAPTER 12
CONTROL ROOM
Control panel contain meters, control switches and recorders located in the control
building, also called the dog house. These are used to control the substation equipment to send
power from one circuit to another or to open or to shut down circuits when needed.
12.1.3) FREQUENCY METER: To measure the frequency at each feeder there is the
provision of analog or digital frequency meter.
12.1.4) VOLTMETER: It is provided to measure the phase to phase voltage .It is also
available in both the analog and digital frequency meter.
12.1.5) AMETER: It is provided to measure the line current. It is also available in both the
forms analog as well as digital.
12.1.6) MAXIMUM DEMAND INDICATOR: There are also mounted the control panel to
record the average power over successive predetermined period.
Page-35
CHAPTER 13
CAPACITOR BANK
The capacitor bank provides reactive power at grid substation. The voltage regulation
problem frequently reduces so of circulation of reactive power.
Unlike the active power, reactive power can be produced, transmitted and absorbed of
course with in the certain limit, which have always to be workout. At any point in the system
shunt capacitor are commonly used in all voltage and in all size.
Benefits of using the capacitor bank are many and the reason is that capacitor reduces the
reactive current flowing in the whole system from generator to the point of installation.
1 .Increased voltage level at the load
2. Reduced system losses
3. Increase power factor of loading current
Page-36
CHAPTER 14
This is relevant in Power Line Carrier Communication (PLCC) systems for communication
among various substations without dependence on the telecom company network. The signals are
primarily teleprotection signals and in addition, voice and data communication signals.
The Line trap OFFERS HIGH IMPEDANCE TO THE HIGH FREQUENCY COMMUNICATION SIGNALS thus
obstructs the flow of these signals in to the substation bus bars. If there were not to be there, then
signal loss is more and communication will be ineffective/probably impossible.
Page-38
CHAPTER 15
In the event of over voltage on the system due to lightening discharge or other system
fault. These parts of equipment, which are normally dead, as for as voltage, are concerned
do not attain dangerously high potential.
In a three phase, circuit the neutral of the system is earthed in order to stabilize the
potential of circuit with respect to earth.
Technical consideration the current carrying path should have enough capacity to deal with more
faults current. The resistance of earth and current path should be low enough to prevent voltage
rise between earth and neutral. The earth electrode must be driven in to the ground to a sufficient
depth to as to obtain lower value of earth resistance. To sufficient lowered earth resistance a
number of electrodes are inserted in the earth to a depth, they are connected together to form a
mesh. The resistance of earth should be for the mesh in generally inserted in the earth at 0.5m
depth the several point of mesh then connected to earth electrode or ground conduction. The
earth electrode is metal plate copper is used for earth plate.
Page-39
Neutral earthing of power transformer all power system operates with grounded
neutral. Grounding of neutral offers several advantages the neutral point of generator
transformer is connected to earth directly or through a reactance in some cases the neutral
point is earthed through an adjustable reactor of reactance matched with the line.
The neutral earthing is provided for the purpose of protection arcing grounds unbalanced
voltages with respect to protection from lightening and for improvement of the system.
Page-40
CHAPTER 16
BATTERY ROOM
In a GSS, separate dc supply is maintained for signalling remote position control, alarm circuit
etc. Direct current can be obtained from 220volt 3 phase ac supply via rectifier and in event of ac
failure, from the fixed batteries, which are kept, charged in normal condition by rectifier supply.
Page-41
CHAPTER 17
RATINGS
17.1) TRANSFORMER:
Total No. of transformers = 6 No. of transformers
220/132 KV------------------------------------ 100MVA 2
132/33 KV--------------------------------------20/25MVA 2
132/33KV---------------------------------------40/50MVA 1
132/11 KV---------------------------------------10/12.5 MVA 1
MAKE Company
220/133 KV, 100MVA X-Mer 1----------------------------------- TELK
220/133KV, 100 MVA X-Mer 2---------------------------------- ALSTOM
132/33 KV, 20/25 MVA X-Mer 1---------------------------------- TELK
132/33 KV, 20/25 MVA X-Mer 2-----------------------------------BBL
132/33 KV, 40/50 MVA X-Mer 3-----------------------------------T&R
132/33 KV, 10/12.5 MVA X-Mer 1---------------------------------EMCO
Page-42
SF6 CB
BREAKER SERIAL NO. 030228
RATED VOLTAGE 145KV
NORMAL CURRENT 1250A
FREQUENCY 5OHz
LIGHTNING IMPULSE WITHSTAND 650KV (Peak)
FIRST POLE TO CLEAR TO CLEAR FACTOR 1-2
SHORT TIME WITHSTAND CURRENT 31.5KA
DURATION OF SHORT CIRCUIT 3 Sec.
(SHORT CIRCUIT SYM. 31.5KA
BREAKING CURRENT) ASYM. 37.5KA
SHORT TIME MAKING CURRENT 8.0KA
OUT OF PHASE BREAKING CURRENT 7.9KA
OPERATING SEQUENCE 0-0.3-CO-3min-CO
SF6 GAS PRESSURE AT 20C 6.3 Bar
TOTAL MASS OF CB 1300Kg
MASS OF SF6 GAS 8.7Kg
Page-43
Page-44
CONCLUSION
Training at 220KV GSS Sanganer, Jaipur gives the insight of the real instruments used. There are
many instruments like transformer, CT, PT, CVT, LA, relay, PLCC, bus bars, capacitor bank,
insulator, isolators, control room, Battery room etc. What is the various problem seen in
substation while handling this instruments. There are various occasion when relay operate and
circuit breaker open, load shedding, shut down, which has been heard previously.
To get insight of the substation, how things operate, how things manage all is learned
there. Practical training as a whole proved to be extremely informative and experience building
and the things learnt at it would definitely help a lot in snapping the future ahead a better way.
Page-45
REFERENCES
1. B.R.GUPTA (2005), “POWER SYSTEM ANALYSIS AND DESIGN”
4. http://upload.wikimedia.org/wikipedia/en/6/63/cvt.png
5. http://images.google.co.in/(Equipment’s name)
6. www.browzen.com/relay
7. Manual of G.S.S.
Page-46