Professional Documents
Culture Documents
User’s Manual
PowerPD, Inc.
Center Park Plaza
6131 Orange Thorpe Ave. Suite 260
Buena Park, CA 90620
U.S.A
Web Site: http://www.powerpd.net
PowerPD Inc. 1
System Manual
PowerSys™:PD-MAT400 2
System Manual
Table of Contents
1. INTRODUCTION ..................................................................................................... 6
1.1. OVERVIEW .......................................................................................................... 6
2. PD-MAT400 SYSTEM ............................................................................................ 7
2.1. PD-MAT400A (POWERSYSTM )........................................................................ 9
2.2. SYSTEM CONFIGURATION ................................................................................. 10
3. INSTALLATION..................................................................................................... 11
3.1. HARDWARE INSTALLATION ............................................................................... 11
3.1.1. AE sensors Installation.......................................................................... 11
4. INSTALLING PD-MAT400 SOFTWARE ........................................................... 13
PowerSys™:PD-MAT400 3
System Manual
Figure List :
Fig. 1 PD-MAT400A......................................................................................... 9
Fig. 2 System Configuration ......................................................................... 10
Fig. 3 List of Installation Program ................................................................ 13
Fig. 4 Installation Start................................................................................... 14
Fig. 5 License Agreement............................................................................. 15
Fig. 6 Choose Destination Location ............................................................ 16
Fig. 7 Choose Folder Window...................................................................... 17
Fig. 8 Setup Type........................................................................................... 18
Fig. 9 Select Component .............................................................................. 19
Fig. 10 Exploring- PD-MAT400 .................................................................... 20
Fig. 11 PD-MAT400 main screen ................................................................ 22
Fig. 12 Schedule Time .................................................................................. 23
Fig. 13 Manual Load...................................................................................... 24
Fig. 14 Phase Graph ..................................................................................... 25
Fig. 15 Phase Group Graph ......................................................................... 26
Fig. 16 Setup Screen..................................................................................... 28
Fig. 17 CH Status Screen ............................................................................. 30
Fig. 18 Communication Port Setting ........................................................... 33
Fig. 19 Time Setting Dialog .......................................................................... 35
Fig. 20 Create transformer ........................................................................... 36
Fig. 21 Alarm/Fault Window ......................................................................... 38
Fig. 22 Data View Display............................................................................. 39
Fig. 23 Time Chart ......................................................................................... 43
Fig. 24 Test View ........................................................................................... 44
Fig. 25 Communication Mode & Unit ID Setting........................................ 55
PowerSys™:PD-MAT400 4
System Manual
Table List :
Table 1 Dip Switch(SW1) Setting for Communication mode................... 56
Table 2 Dip Switch(SW3) Setting for Unit ID ............................................. 57
Table 3 Pin description of RS-232 Connector in PC & PD-MAT400A.. 58
Table 4 Pin description of RS-422 Connector in PD-MAT400A ............. 59
Table 5 Pin description of RS-422 Input/Output Connector in PD-
MAT400A ................................................................................................ 61
Table 6 Dry Contact Status .......................................................................... 62
PowerSys™:PD-MAT400 5
System Manual
1. Introduction
1.1. Overview
PD-MAT400 is a diagnostic system with capabilities to continuously
detect and monitor partial discharge (PD) signals that radiates from the
power equipment such as transformer, GIS, breaker, and contact areas of
a high voltage cable. PD-MAT400 is a cost-effective, user-friendly
diagnostic system for PD.
Amplitude of PD signals.
PD radiation in phases.
PowerSys™:PD-MAT400 6
System Manual
2. PD-MAT400 System
Functions
PowerSys™:PD-MAT400 7
System Manual
Specifications
PowerSys™:PD-MAT400 8
System Manual
②
③
④
⑤
⑨
⑥
⑦
⑧
Fig. 1: PD-MAT400A
① Status Display
② Gain Selection Switch
③ Power Switch
④ External In/Output Port(Dry contact, DC Output,
Temperature Sensor Input)
⑤ AE Sensor Input Port(BNC, 4 Channel)
⑥ RS-232/RS-422 Input Port (D-sub 9 Pin)
⑦ RS-422 Output Port(D-sub 9Pin )
⑧ Modem Port
⑨ 110 ~ 220V AC Power In
PowerSys™:PD-MAT400 9
System Manual
PowerSys™:PD-MAT400 10
System Manual
3. Installation
PowerSys™:PD-MAT400 11
System Manual
PowerSys™:PD-MAT400 12
System Manual
PowerSys™:PD-MAT400 13
System Manual
STEP 2 : You will see a License Agreement (see Fig. 5) for PD-
MAT400.
PowerSys™:PD-MAT400 14
System Manual
STEP 3 : When you agree, then click ‘Yes’ to continue the PD-
MAT400 windows installation.
You can choose the folder for destination location in which you
want the PD-MAT400 installed. We suggest you use the default
folder as the destination location.
PowerSys™:PD-MAT400 15
System Manual
PowerSys™:PD-MAT400 16
System Manual
Typical will install the execution files needed to run the PD-
MAT400 program, DLLs, and Database.
PowerSys™:PD-MAT400 17
System Manual
Select the type, and then click the ‘Next’ button to go on.
Program will start to install all files you choose. But when you select
'Custom' type and then click the ‘Next’ button, will go into Fig. 9
You should select the file group in this window, and click the Next
button to go on.
PowerSys™:PD-MAT400 18
System Manual
PowerSys™:PD-MAT400 19
System Manual
the folders and files installed under the destination folder in the
Windows Explorer (Fig. 10).
PowerSys™:PD-MAT400 20
System Manual
MATData: A directory which has data files acquired when you click
on ‘Data Request’ button in 'Test' screen or during 'Auto' mode.
When you see Fig. 10, the initial Program installation of PD-
MAT400 is completed. Next step is to install MSODBC for the
database.
PowerSys™:PD-MAT400 21
System Manual
PowerSys™:PD-MAT400 22
System Manual
The data will only be shown in this dialog box if the On button
under status is pressed in the setup dialog box. Auto function
measures only the sensor which status is set as On in the SetUp
screen. If none of sensor’s status is On, it will not measure at all.
When running the Auto mode, two kinds of measurement are
performed. Firstly, the Current Data Req. of the Manual Load
screen is performed in every selected minute. Secondly, the Data
Request of the Test screen is performed in every selected minute if
the Test screen is activated. To be more specific, click on the button
labeled Test in the main screen and close the screen. Then the Test
screen is activated.
For example, if the user sets the time period as 10 minutes, auto
performs PD signal measurement in every 10 minutes. Also, it saves
measured data in Database during auto mode. In auto mode, the
measured data of the sensor signal in Test screen will be saved once
per hour operation time under the path of ‘C:\Program Files\PD-
MAT400\MATData’. The measured data can be viewed by clicking
on the Data Load button in the Test screen. After click on the button,
PowerSys™:PD-MAT400 23
System Manual
① ②
Fig. 13: Manual Load Screen
In this section we will provide you with a quick start guide to explain
the display that PD-MAT400 provides in this section. Click on the
button labeled MANUAL START of main screen. Manual Load display
data received from PD-MAT400 and the data consists of 12-group
PowerSys™:PD-MAT400 24
System Manual
PowerSys™:PD-MAT400 25
System Manual
Fig. 15 Phase Group Graph shows Fig. 14 with the unit of 30 degrees
and this can be seen on top of the Manual Load dialog box.
Fig. 15 Phase Group Graph shows in the Manual Load screen.
PowerSys™:PD-MAT400 26
System Manual
PowerSys™:PD-MAT400 27
System Manual
5.3. Setup
The setup screen sets up the information from the installed PD-
MAT400 and communication mode. All of information and acquired
conditions of data are maintained and determined by setup in the PD-
MAT400 system. The setup screen was designed so that commonly
used parameters are readily accessible. Make sure all the following
parameters are set as per your requirements.
PowerSys™:PD-MAT400 28
System Manual
Contents of Table (○
1 of Fig.16)
PowerSys™:PD-MAT400 29
System Manual
Temperature Range:
Temperature sensor is installed inside of Transformer and
user must set up temperature range properly. Apply 4-20mA
inputs current into positive temperature into temperature
terminal. Set the minimum and maximum temperature range
for 4-20mA temperature board in the temperature table by
clicking on button. After enter your temperature range and
then select the temperature display unit on the Celsius or
Fahrenheit. This allows temperature value to be converted
automatically according selected temperature unit.
CH: Channel number of PD-MAT400.
Status (Auto Mode Status):
1.
Locate the mouse cursor under Status column on the table ○
The On button is pressed if it is an automatically measured
device, if not the OFF button is pressed.
When the OFF button is pressed, PD-MAT400 will not
process the selected transformer during auto mode.
PowerSys™:PD-MAT400 30
System Manual
Threshold (mV):
Set up the value of threshold level in the PD-MAT400. Select
the threshold level in mV and the threshold level is a very
important parameter in measuring PD pulse. The threshold
level should be set to optimize the conditions of system
installation and environment for measurement accuracy.
Clicking on the button will cause a parameter setting
dialog box to be displayed containing the parameter setting of
PD-MAT400 system. Set up the parameters information.
After you click on the OK button, the new parameters
information is updated in the table ○
1 .
PowerSys™:PD-MAT400 31
System Manual
Description:
Write down the comment about PD-MAT400 system.
PowerSys™:PD-MAT400 32
System Manual
RS-232 (○
1 of Fig. 18)
RS-232 can be used for short distances, and it allows only two
devices to communicate. A converter to RS-422 is added for
longer distance communication.
In order to use RS-232 communication, you must change the
jumper setting inside of PD-MAT400 equipment. Please refer to
hardware setting. Note that RS-232 is default setting.
Port: Select the port name where RS-232 cable is connected.
Baud rate: Communication speed, which is fixed at 19200.
RS-422 (○
3 of Fig. 18)
PowerSys™:PD-MAT400 33
System Manual
Comm. Mode (○
4 of Fig. 18)
PowerSys™:PD-MAT400 34
System Manual
○
1
PowerSys™:PD-MAT400 35
System Manual
Create (○
4 of Fig.16)
PowerSys™:PD-MAT400 36
System Manual
Delete (○
5 of Fig.16)
Edit (○
6 of Fig.16)
The Edit is used for editing the setup information of the PD-
MAT400. The edit operation is used to change parameter
information of a group of selected transformer. Once you
have edited parameters, click on the OK button to apply the
new setting to PD-MAT400 system. After you click on the OK
button, the new parameters information is updated in the table
1.
○
PowerSys™:PD-MAT400 37
System Manual
PowerSys™:PD-MAT400 38
System Manual
PowerSys™:PD-MAT400 39
System Manual
Latest Data
Click on the button and select the Latest Data option. Then
click on the View button. The Latest Data shows saved data of
very previous month from the defined date(the box ) in hour unit.
During very previous month of selected setting date period, all the
measured data for the selected transformer and channel is
displayed in a table. Detailed information can be found that help to
analyze and to identify PD signal in daily basis data.
Week Data
Click on the button and select the Week Data option. Then click
on the button labeled View. Week data shows all the data for the
very previous week in day unit and is updated on a weekly basis.
PowerSys™:PD-MAT400 40
System Manual
PowerSys™:PD-MAT400 41
System Manual
Graph ○
3 in Fig. 22 Data View displays the value of Amplitude
Month Data
Month Data shows very previous month from the defined date(the
box ) in day unit and is updated on a monthly basis. Click on the
button and select Month Data option. Then click on the button
labeled View. This function performs exactly same as Week Data
request except that it has additional function which is to display
Time chart as shown in Fig. 23. Firstly, click on the combo box
labeled “3D Chart” and then select “Time Chart” from the shortcut
menu. It will show selected current mode in combo box. Select
PowerSys™:PD-MAT400 42
System Manual
CH number and then click on the button labeled Chart View. The
measured data for the selected channel data will be displayed on
the chart as shown in Fig. 23 The Time Chart is used for showing
the Pulse’s trend related to measured date.
Select the 3D Chart on combo box and this displays the graphs
same as in Fig. 22.
Year Data
Click on the button and select the Year Data option. Then click
on the button labeled View. Year data shows all measured data
for the selected transformer and channel in day unit and is
updated on a yearly basis. Displaying data may take a while to
load from database due to a yearly basis data. One of the most
useful features of this data view is to display overall data trend
over past 365days from the selected date. Detailed information
can be found in monthly, weekly, and the latest data mode and
that help to analyze and identify the PD signal.
PowerSys™:PD-MAT400 43
System Manual
PowerSys™:PD-MAT400 44
System Manual
PowerSys™:PD-MAT400 45
System Manual
PowerSys™:PD-MAT400 46
System Manual
PowerSys™:PD-MAT400 47
System Manual
PowerSys™:PD-MAT400 48
System Manual
PowerSys™:PD-MAT400 49
System Manual
PowerSys™:PD-MAT400 50
System Manual
Search ( ○
4 of Fig. 25): Selects the date, equipment, and
channel.
5 of Fig. 25): Search of setting (search ○
Search Button (○ 4 )
from DB.
6 of Fig. 25): Clears the searched result
Data Clear Button(○
on display (Data will not be deleted).
PowerSys™:PD-MAT400 51
System Manual
PowerSys™:PD-MAT400 52
System Manual
Operation
1 of Fig. 27): Shows (search option ○4) the QM
QM Graph (○
value in Positive Phase and Negative Phase.
2 of Fig. 27): Shows (search option ○
NQN Graph (○ 4 ) the NQN
PowerSys™:PD-MAT400 53
System Manual
Data List (○
3 of Fig. 27): The following list is under the Search
Option ○
4
PowerSys™:PD-MAT400 54
System Manual
6. HARDWARE SETTING
6.1. Communication mode & Unit ID setting
PowerSys™:PD-MAT400 55
System Manual
PowerSys™:PD-MAT400 56
System Manual
DIP SW(SW 3) #
Unit ID
4 3 2 1
0 0 0 0 1(Default)
0 0 0 1 2
0 0 1 0 3
0 0 1 1 4
0 1 0 0 5
0 1 0 1 6
0 1 1 0 7
0 1 1 1 8
1 0 0 0 9
1 0 0 1 10
1 0 1 0 11
1 0 1 1 12
1 1 0 0 13
1 1 0 1 14
1 1 1 0 15
1 1 1 1 16
Table 2 Dip Switch (SW3) Setting for Unit ID
PowerSys™:PD-MAT400 57
System Manual
Communication configuration
PowerSys™:PD-MAT400 58
System Manual
PowerSys™:PD-MAT400 59
System Manual
RS-232 can be used for short distances, and it allows only two
devices to communicate. A converter to RS-422 is added for longer
distance communication and it allows multi communication. A daisy
chain, which is a number of PC and multiple devices, are connected to
each other in a series. When devices are daisy chained to a PC, the
first device of in port must connect to the PC with terminal connector.
The second device of in port is connected to the first device’s out port
as shown in Figure below. Signals are passed through the daisy-
chained devices from one device to the next since each device has its
own unique ID.
PowerSys™:PD-MAT400 60
System Manual
PowerSys™:PD-MAT400 61
System Manual
Shows the Alarm status when the value exceeds the user’s set-up
value. The Dry Contact under “Normal” keeps the “Open” status and
changes from “Open”(=Normal) to “Short”(=Alarm) under the alarm
status of PPS and distribution rate (%)
Normal Open
Alarm Close
PowerSys™:PD-MAT400 62
System Manual
PowerSys™:PD-MAT400 63
System Manual
PowerSys™:PD-MAT400 64
System Manual
PowerSys™:PD-MAT400 65
System Manual
Appendix A
A. Analysis of PD signals using the Phase Distribution:
The method of PD Signal Handling Algorithm applied to PD-
MAT400 is the way of using a characteristic that is to gather the
data based on specific phase distribution of PD Signal
Characteristics of PD signal (Acoustic Signal):
Burst waveform: less than 500uS
Band width of 80Khz – 300Khz
Synchronized AC Cycle shown in the Phase with pattern.
PD signals are separated from the noise patterns and
analyzed using synchronized AC cycle with Phase.
Characteristic of Noise Signal
Generally have characteristics of wide-range of frequency with
random signals (no pattern: e.g., sand or rain hitting the
transformer tank)
The noise signals are filtered through H/W and BPF.
From the “Setup” Menu, PD levels are selected for each channel
to distinguish PD signals from the noise.
For analysis, the study of detected data (burst pattern, phase
distribution, frequency range, etc.) will provide more accuracy.
The analysis of Phase Distribution is computed in the following
method:
The 0-360 Phase is divided into 12 groups, each group counting
the PD Pulse (PD[n]) , n= Group index (0,1,2….,11) and
computing PD Distribution on the overall Pulse Count. See
below:
PowerSys™:PD-MAT400 66
System Manual
Theoretical equation as :
This allows an “Alarm” to activate when PPS and PDDistribue exceed the
ranges set up by the operator. (Refer to 5.3, 6.5.1) For the convenience,
PDDistribute is shown in percentage (%) and can be set-up in the range of
0% - 95%. The default value of Alarm is set at 20% or above of the
probability of PD occurrence. The default value of the alarm detection
level (%) can be changed from the Set-up Menu.
PowerSys™:PD-MAT400 67