Professional Documents
Culture Documents
Motor Starters
Compact starters IP 65 (AC 400 V)
Actuator-Sensor-Interface
■ Overview
The AS-Interface compact start- The load itself and any other nsa0334h
er is a load feeder with IP 65 de- compact starters are supplied
gree of protection, which is fully using the same connection
prewired inside, for switching technique. All the supply and
and protecting any three-phase data cables can thus be laid
loads up to 5.5 kW at AC 400/ through the system like a bus.
500 V (electromechanical com- Whereas the controlgear is
pact starter) or up to 2.2 kW switched via the outputs by the
(electronic compact starter) – 24 V auxiliary power supply, the
mostly 3-phase standard mo- inputs are supplied by the AS-
tors in direct-on-line and revers- Interface data cable. This princi-
ing operation. It consists either ple of separate auxiliary power
of an electromechanical con- supplies facilitates selective
trolgear combination or an elec- emergency stop concepts.
tronic overload relay and circuit-
breaker unit. The overload or Addressing
short-circuit protection is located The addressing of the AS-Inter-
below a sealable, transparent face compact starter can still be
cover and is therefore available used even if it is fully wired, be-
for diagnosis. Two LEDs are pro- cause the module is disconnect-
vided to the left of the cover for ed from the AS-Interface network
diagnostic purposes for the AS- as soon as the addressing con- The ERS compact starter is de- Spare inputs
Interface and the auxiliary pow- nector is inserted. signed for direct on-line starting
er. The compact starters are also
in reversing mode. The elec-
DS/RS compact starters equipped with two spare inputs.
It is not possible for live parts to tronic overload protection and
(electromechanical) the shutdown response in the The M12 socket is a "Y" connec-
be touched even when the cov-
er is open. The control elements The electromechanical compact event of overload can be ad- tor. The signal inputs are con-
are activated via the integrated starters consist of a conventional justed directly at the device. nected to pins 2 and 4. In this
outputs. The device status is switchgear combination with a manner, it is possible for exam-
scanned via the inputs, e.g. SIRIUS 3R circuit-breaker for Version with brake contact ple, to connect an optical prox-
checkback from auxiliary con- protection against short-circuits All compact starters are availa- imity switch which supplies a
tacts of circuit-breaker and con- and overloading and SIRIUS 3R ble optionally with a separately signal as well as the alarm
tactor(s). A further input is used contactor(s) for normal switch- activated brake contact for "Fouled".
to detect the operating state of ing. The advantages of the elec- electrically operated motor A "T" adapter can be used to
the optional hand-held terminal. tromechanical starters are the re- brakes. For externally-fed motor split the signal inputs onto two
The three power connectors are liable isolation during disconnec- brakes, the DC 24 V supply is M12 sockets. Compact starters
used to feed and loop through tion and tripping, the integrated fed in with the load voltage via modified in this way offer addi-
to the load supply voltage fuseless protection against short- the power connector on -X1. Via tional advantages. At no extra
(power bus) and to connect to circuits and the favorable price.
-X3, the supply can be looped cost, it is possible to save AS-i
the load itself. Prefabricated What is more, direct currents can
on to the next compact starter addresses, reduce the space
power supply lines can be used also be switched with the elec-
tromechanical starters. on -X1. The DC 24 V voltage for requirement and to build up
to connect compact starters the brakes can only be bridged logical groupings.
which are directly adjacent to Planning information: In the in the devices that have brake
each other. The maximum case of temperature-critical ap- contacts. At the project plan-
number of starters that can be plications, we recommend op- ning stage, it is important to en-
supplied via a power supply ca- eration in the lower setting sure that these starters are lo-
ble is limited by the maximum range of the circuit-breaker. cated alongside each other.
permissible total current (up to
max. 4 mm2 ≅ ~ 35 A), see EDS/ERS compact starters All compact starters can be
Technical Data (electronic) equipped with a brake contact
for DC 500 V with a brake con-
Wiring and assembly The electronic compact starters tact AC 400.
EDS (direct starter) and ERS
All the connections are either of (reversing starter) consist of an Hand-held terminal
the plug-in type or use the electronic overload relay and an
easy-installation insulation- electronic circuit-breaker unit. The hand-held terminal enables
piercing method. the compact starter to be oper-
The advantages of these elec- ated locally and autonomously,
The shaped cables for the 24 V tronic compact starters are the providing that the auxiliary volt-
auxiliary power supply which is broad limits within which the age supply is connected. Thus,
used to control the contactors overload protection can be ad- assuming that the automation
as well as the AS-Interface data justed (the power range up to level is functioning correctly, lo-
cable must simply be inserted in 2.2 kW at AC 400/500 V is cov- cal switching operations can be
the mounting plate. The com- ered with just 2 variants), the carried out in addition to normal
pact starter is then cradled in fact that the electronic contact manual operations in the event
the mounting plate and screwed elements in the power section of a programmable controller /
tight. The compact starter and are non-wearing, current detec- bus system failure (emergency
the mounting plate must be or- tion (used for monitoring the en- mode) or during test runs be-
dered separately. The connec- ergy connector), emergency op- fore commissioning, e.g. for
tors used to supply power to the eration in the event of an over- testing the direction of rotation
main circuit must likewise be or- load as well as remote resetting
of the motor. The hand-held ter-
dered separately (see Acces- via the AS-Interface after over-
minal can be connected to the
sories in the Selection and Or- load tripping.
compact starter by means of a
dering Data). connecting cable via a socket
underneath the transparent
cover.
■ Overview
Display characteristics
LED States Status description
Under normal operation, the
LEDs on the compact starters AS-Interface On On Flash- Flash- Off
indicate the following device ing ing
states (see Tables NSA00322 AUX PWR On Off
and NSA00323). STATE 1) On
NSA0_00322
Station address 0
AS-Interface communication absent
AS-Interface communication o.k.
Main circuit on
Rotary coding switch in position
Tripping REMOTE: Continued ope-
ration when programmed in the user
program
Main circuit off
Rotary coding switch in position
Tripping LOCAL: Direct shut-off
Rotary coding switch in position
Tripping REMOTE: Remote shut-off
when programmed in the user
program
Main circuit off
(test finished)
Main circuit off
(test running)
Main circuit on
Main circuit off, e.g. through
Failure of two phases
Drawn motor connector
Supply voltage drop
(< 18 V)
Simultaneous control of clockwise
and anti-clockwise rotation
NSA0_00323
■ Overview
Diagnosis of the electromechanical compact starter with the user programme
The input and output signals of Output DO2 is only controlled in Note: The brake contact is con- freewheeling or blocking of the
the DS2E and RS2E electrome- those variants with a brake con- trolled via the bus separately motor. This also applies to local
chanical compact starters can tact. from the main circuit. shutdown, e.g. in response to
be evaluated in the user pro- This makes it possible to switch an overload tripping operation.
The I/O assignment corre-
gramme. the motor and brake independ- Input signal DI0 can be used to
sponds to the AS-Interface mo-
ently. In the user programme, it check the status of the device.
tor starter profile 7D.
is must therefore be ensured
that dangerous system states
cannot occur, e.g. unintentional
Inputs
Input signals Device status Meaning
DI0 "ready" 0 Device not ready / error Manual mode
Device has been switched to manual
mode locally (switch back to automatic
mode using handheld unit).
Overload/short-circuit tripping
Reclosure of circuit-breaker following a
cooling off phase.
FAULT signal
• Defective coil.
• Contact welded.
• Output driver defective
(contactor must be tested).
• Simultaneous activation of clockwise and
counterclockwise rotation (user pro-
gramme must be checked).
1 Device is ready / automatic
mode
DI1 "running" 0 Contactor OFF
1 Contactor ON
DI2 "special information 1" 0 No input signal IN1
1 Input signal IN1
DI3 "special information 2" 0 No input signal IN2
1 Input signal IN2
Outputs
Output signals Device status Meaning
DO0 "run forward" 0 Clockwise rotation OFF
1 Clockwise rotation ON
DO0 "run reserve" 0 Counterclockwise rotation OFF
1 Counterclockwise rotation ON
DO2 "special command 1" 0 Open brake contact
1 Close brake contact
DO3 "special command 2" 0 –
1 –
■ Overview
Diagnosis of the electronic compact starter with the user programme
The input and output signals of Output DO2 is only controlled in Note: The brake contact is con- freewheeling or blocking of the
the EDS2E and ERS2E electro- those variants with a brake con- trolled via the bus separately motor. This also applies to local
mechanical compact starters tact. from the main circuit. shutdown, e.g. in response to
can be evaluated in the user This makes it possible to switch an overload tripping operation.
The I/O assignment corre-
programme. the motor and brake independ- Input signal DI0 can be used to
sponds to the AS-Interface mo-
ently. In the user programme, it check the status of the device.
tor starter profile 7E.
must therefore be ensured that
dangerous system states can-
not occur e.g. unintentional
Inputs
Input signals Device status Meaning
DI0 "ready" 0 Device not ready / error Manual mode
Device has been switched to manual
mode locally (switch back to automatic
mode using handheld unit).
Tripped signal
Rotary coding switch in position
• Tripping LOCAL: Direct shut-off
• Tripping REMOTE: Remote shut-off or
continued operation when programmed
in the user programme
FAULT signal
• No current flowing
– Failure of two phases
– Drawn motor connector
– Supply voltage drop
(< 18 V)
– Current imbalance limit exceeded
– Fault in main circuit of the device
• Device fault (Reset after error rectifica-
tion)
1 Device is ready / automatic
mode
DI1 "running" 0 No current flowing
1 Current is flowing
DI2 "special information 1" 0 No input signal IN1
1 Input signal IN1
DI3 "special information 2" 0 No input signal IN2
1 Input signal IN2
Outputs
Output signals Device status Meaning
DO0 "run forward" 0 Clockwise rotation OFF
1 Clockwise rotation ON
DO1 "run reserve" 0 Counterclockwise rotation OFF
1 Counterclockwise rotation ON
DO2 "special command 1" 0 Open brake contact
1 Close brake contact
DO3 "special command 2" 0 Remote Reset OFF
1 Remote Reset ON
■ Overview
Connector pin assignment
digital inputs Pin 1: Supply L+
(Y assignment) Pin 2: Signal input
Pin 3: Supply L–
Pin 4: Signal input
g_nsa_xx_00100b Pin 5: not assigned
NSA00100
L2 L2 L2
1 2 3 6 8 3 1
7 2
4 5 4 5 5 4
g_nsa_xx_00165m
g_nsa_xx_00166b
g_nsa_xx_00167b
L3 L1 L1 L3 L1 L3
6 8 1 3 8 6
7 2 7
NSA00165b
NSA00167
NSA00166
-X1 -X2 -X3
1) Only for AS-Interface compact starters with DC 24 V brake contact (3RK1 322-..S..-.AA1).
1 unit Unit
Electronic starter EDS compact starters C 3RK1 322- @@ S12-0AA @ 131 1
Electronic direct on-line starter with two spare
digital inputs
Power rating P
kW A
0.18 ... 0.8 0.6 ... 2.18 0A
0.75 ... 2.2 2.0 ... 5.95 0B
NSA00098
g_nsa_de_00098b
Power rating P
kW A
< 0.06 0.14 ... 0.20 0B
0.06 0.18 ... 0.25 0C
0.09 0.22 ... 0.32 0D
0.10 0.28 ... 0.40 0E
g_nss0_xx_00142b
1 unit Unit
Accessories for DC 24 V, M12 plugs
6SE7 194-1KA01-0XA0 Coupler plug, M12 A 3RX1 667 122 1
for connecting actuators and sensors
5-pole
Angular coupler plug, M12 A 3RX1 668 122 1
for connecting actuators and sensors
5-pole
Y-shaped coupler plug, M12 6ES7 194-1KA10-0XA0 1
for connecting two sensors by means of individual
cables
nsa0067
5-pole
M 12 covering caps 1 packg.
for closing unused input or output sockets } 3RX9 802-0AA00 131 10
1 packg. = 10 units
Accessories for AS-Interface compact starter (Han Q 8/0)
3RK1 902-0CA00 Connector set
for power infeed, 9-pole
comprising
1 connector housing with Pg 16 cable gland
Female insert, 9-pole
6 female contacts
• suitable for 4 × 2.5 mm2, 6 × 2.5 mm2 cables A 3RK1 902-0CA00 121 1
nsa0068 • suitable for 4 × 4 mm2 , 6×4 mm2 cables A 3RK1 902-0CB00 121 1
Connector set
3RK1 902-0CC00 for power loop-through connection, 9-pole
comprising
1 connector housing with Pg 16 cable gland
1 male insert, 9-pole
6 male contacts
• suitable for 4 × 2.5 mm2, 6 × 2.5 mm2 cables A 3RK1 902-0CC00 121 1
• suitable for 4 × 4 mm2 , 6×4 mm2 cables A 3RK1 902-0CD00 121 1
nsa0069 Connector set A 3RK1 902-0CE00 121 1
for motor connection, 1.5 mm 2, 9-pole,
3RK1 902-0AH00 comprising
1 connector housing with Pg 16 cable gland
1 male insert, 9-pole
8 male contacts 1.5 mm2
nsa0074 Blank plug for 9-pole power socket (-X3)
• (1 packg. = 1 unit) A 3RK1 902-0CK00 121 1
1 packg.
• (1 packg. = 10 units) A 3RK1 902-0CJ00 121 1 packg.
Power connection cable, 9-pole
• 6 × 4 mm2 , 0.12 m long A 3RK1 902-0CH00 121 1
• 4 × 4 mm2 , 0.12 m long A 3RK1 902-0CG00 121 1
Motor connection cable, 4 × 1.5 mm 2
with power connector, 9-pole
• Length: 3 m A 3RK1 902-0CM00 121 1
• Length: 5 m A 3RK1 902-0CP00 121 1
• Length: 10 m A 3RK1 902-0CQ00 121 1
Motor connection cable, 6 × 1.5 mm 2
with power connector, 9-pole
• Length: 3 m A 3RK1 902-0CN00 121 1
• Length: 5 m A 3RK1 902-0CR00 121 1
• Length: 10 m A 3RK1 902-0CS00 121 1
Crimping tool
• for male and female contacts, 1.5 up to A 3RK1 902-0AH00 121 1
2.5 mm2
• for male and female contacts, 1.5 up to A 3RK1 902-0CT00 121 1
4 mm2
Disassembling tool A 3RK1 902-0AJ00 121 1
for disassembling male and female contacts
in 9-pole inserts
1 unit Unit
Miscellaneous accessories
3RK1 902-0AP00 Manual for AS-Interface compact starters
• German, English A 3RK1 702-2GB10-2AA0 131 1
• French, Italian A 3RK1 702-2HB10-2AA0 131 1
Mounting plate for compact starters A 3RK1 902-0AP00 121 1
for accommodating the trapezoidal-section cable
for AS-Interface line and auxiliary supply
Gasket set for mounting plate 1 set
for sealing the housing in case of unilateral entry } 3RK1 902-0AR00 121 1 set
nsa0049
nsa0075
■ Dimension drawings
3RK1 322-. . S . - . AA . 3RK1 902-0AP00
9
40,5
34
4,8
107
265
197
270
265
214
33
39
5
25
NSA00101b
NSA00102
120 54 25 120
126 9
190
■ Technical data
DS/RS Motor starters
Housing
Protection IP 65 (with covered connecting elements and cover flap)
Material Thermoplastic (glass-fiber reinforced)
Colour Anthracite RAL 7016
Cover flap Latching, sealable
Dimensions (W x H x D) in mm 120 × 265 × 134
Temperature range
• Operating temperature in °C –25 ... +55 (derating must be observed: See manual)
• Storage temperature in °C –40 ... +70
Permissible service position 22,5° 22,5° Important:
NSA00104
90° 90° in accord. with DIN 43 602
Start-up command "I"
at the right or top
Shock resistance
Rectangular pulse (g/ms) 2/unlimited
10/5 or 5/10
Sine pulse (g/ms) 2/unlimited
8/10 or 15/5
External voltage supply
For output supply (contactor control) DC 24 (PELV; – must be earthed)
Rated operational voltage Ue in V
For electronics and inputs (acknowledgements of DC 26.5 ... 31.6 (in compliance with AS-Interface specification)
switchgear status) via AS-Interface data cable in V
I/O configuration (hex) 7
ID code (hex) D E
Power consumption of AS-Interface in mA max. 100
Current input U aux in mA approx. 100
Watchdog built-in
(shutdown of outputs in case of AS-Interface fault)
Diagnostics
Via AS-Interface Check-back signalling of circuit-breakers and contactor(s)
via positively driven auxiliary contacts and separated inputs
Via LED at the housing Auxiliary voltage applied
AS-Interface communication o.k.
AS-Interface communication fault
Station address = 0 (module not addressed)
Via LED at the hand-held terminal ON or clockwise rotation or anti-clockwise rotation
Addressing After the 15th addressing, the module keeps the last address
Main circuit
Rated operational voltage AC 500 V to DIN VDE 0106 Part 1014, AC 600 V to CSA and UL
Safety separation between main and auxiliary circuit up to 400 V –
(to DIN VDE 0106, Part 101)
Rated output 5.5 kW 2.2 kW
Permissible operating duties Continuous duty, temporary duty, periodic duty, intermittent periodic duty
(50 % rel. ON-time at 80 operations/h at 5.5 A)
Permissible operating frequency ≤ 80 1/h ≤ 600 1/h
with a start-up time of t A = 0.1 s
and a cyclic duration factor tc.d.f. = 50%
Trip class Class 10
Conductor cross-sections for power connector ≤ 4 mm2 AWG (15-11)
Infeed/feeder/loop-through connection, 9-pole
Max. permissible current via power connector
(dependent on conductor cross-section)
• Tu = 60 °C 30 A (4 mm2), AWG (11); 20 A (2.5 mm2), AWG (15); 12 A (1.5 mm2), AWG (13)
• Tu = 40 °C 35 A (4 mm2), AWG (11); 25 A (2.5 mm2), AWG (15); 15 A (1.5 mm2), AWG (13)
Short-circuit strength of starter combination in kA 50 (to type of co-ordination "1") 100
Electrical service life of the circuit-breaker component See service-life characteristics for ≥ 10 mill. operating cycles
for a load Ia (AC-3) 3RT10 contactors