LG Air Conditioning Academy

Building Characteristics and


Air Conditioning System
Air Conditioning Academy
Introduction

Key words : Understand air conditioning methods for each


types of architectural process & building usage. Be familar
with regulations related to architectures.

Basic terms: Air conditioning, Air conditioning & heating load,


HVAC System, Static pressure, AHU

Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 1
3. Characteristics for each type of building

Process의 Map 이미지

Characteristics of
each type of building
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 2
1.1 Residential Facility 1. Residential

Classification &Characteristics of Facility Building(Collective Residential Standard)

General Residential complex


Apartment Apartment

☞ Definition &Characteristics ☞ Definition &Characteristics


① Collective Residence where many households live in the ① A combination of the Commercial Facility(generally 2~4floors)
same building with over 5 floors. & Residential Facility(generally over 5floors)
② Widely spread, including the urban area ②Generally located in the downtown area with convenient
③ There is a neighborhood facility that offers cultural/ transportation
entertainment/convenience within the apartment area. ③ There is a neighborhood facility that offers cultural/
④ Residential law is applied. entertainment/convenience within the building
④ Architectural law is applied.
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 3
1.1.1 Division of Room based on
1. Residential
their purpose of use

Kitchen/
Dining room
Living room
• Large space that plays a pivotal role in the
• Cooking and dining area within the residential space.

Residential Facility • Multi-purpose functions such as Relaxation /

• Living Dining Entertainment/Reading/Dining/house chores /


Child care/Socializing, etc.
→ By installing the dining table in the side of living
• Gaining importance in the Residence Designing.
room near the kitchen, use it as a living

room/dining room.
• Dining Kitchen
→ Installation of dining table in the kitchen, used
also as a Dining Room.
• Living-Dining Kitchen
→ Install the kitchen and the dining table in the
corner of the living room to combine all three
functions. (Living room, Kitchen and Dining
Room are all put together)

Bedroom/
Balcony Master room
• Classified as theMaster room for the
• Supplementary space of living room/
Bedroom/Kitchen located outside the married couple & bedroom for other children
unit • Space for sleep and relaxation
• Space facing the open air • Often contains a bathroom/book room if it is
• Can be used as a playground for a Master room and also used as a study
children , as a space for tanning, relaxing, space for a bedroom.
and viewing, and as a storage.
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 4
1.1.2 Load & Management Characteristics 1. Residential

Living room Characteristic of the Load


• HVAC system should operate during the evenings, which is the time for
families to gather and spend time in the living room.
• Internal heating energy is high from the electronic products& body heat
• Requires relatively high ventilation capacity
• Exterior load(sunlight & thermal conduction) through windows is large
• There is a discrepancy in the indoor temperature due to the large space
• Air conditioning & heating load increase due to the expansion of living room.
• There is a large load discrepancies for each directions and floors.
• Generally connected to the Kitchen & Dining Room
(Living-Dining Kitchen Structure)

☞ More households are expanding the living rooms to utilize the


balcony spaces as the extra spaces for the living room.

HVAC Management
Characteristics
• Apply individual Air conditioning Systems, considering
different hours of operation for different rooms.
• Indoor equipments Capacity selection by considering
Electronic Products, Body heat Energy, Balcony expansions,
window side, and exterior load.
☞ Generally, to increase air freshness and sunlight exposure, • Ventilation System application &Sufficient Ventilation
living rooms are designed with all-window structure. → indoor Capacity Selection
sunlight load increases
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 5
1.1.2 Load & Management Characteristics 1. Residential

Characteristic of the Load


Kitchen/ Dining Room
• It is an intermittent zone in which the HVAC system operates during
the dining hours.
• Internal heating energy from kitchen appliances (microwaves, etc)
is high.
• There is large latent heat load due to foodstuffs/ body movements
• If using the Kitchen hood, indoor pressure status is negative
pressure.Continuous negative pressure adds more trouble to get rid
of contaminated air.
• Consider sufficient ventilation to get rid of food smell
• Mostly connected to nearby living room Living-Dining Kitchen)
• Be wary of indoor air contamination if applying luxurious interior
☞ Generally located close to the living room and there is an increasing
design
tendency to use luxurious interior materials for the interior design (consider
the Indoor air contamination)

HVAC Management
Characteristics
• Apply Individual Air conditioning System that considers
differences in driving hours of each room.
• Select Indoor equipments capacity by considering all aspects
of Kitchen tools , Body heat Energy, etc.
• Sufficient Ventilation Capacity selection to get rid of food
☞ If Kitchen Ventilation hood is used, the pressure within the kitchen is negative smell

pressure. Continuous negative pressure adds more trouble to get rid of • Interlocked with Kitchen hood and Ventilation System
contaminated air.
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 6
1.1.2 Load & Management Characteristics 1. Residential

Characteristic of the Load


Master Room/Bedroom
• It is a zone in which the HVAC system operates during the night times.
• As a relatively sealed space, indoor air contamination from architecture
and interior materials is worrisome.
• Exterior load(sunlight & thermal load) from the window sides is large.
• Minimize night-time Noise & Vibration
• Minimize the noise and vibration caused by the AC & heating equipments,
and prevent the transmission of noise from other sources.
• Heating and cooling loads increase due to the expansion of the living
room.
• If it’s a bedroom, prevent the products from being damaged by the
☞ Due to various indoor air contamination materials from the walls and children.
bedrooms, the necessity to use ventilation system that introduces
open air is emphasized.

HVAC Management
Characteristics
• Apply Individual Air conditioning System that considers differences
in driving hours of each room.
• Select Indoor equipments Capacity by considering all aspects of
window-side exterior load, indoor electronic products, etc.
Indoor equipments Capacity Selection
• Ventilation Capacity Selection by considering the architecture and
interior furniture
☞ To obtain additional indoor space, balcony expansion is generally
• If it’s a duct-type, prevent the crosstalk.
applied. -> Rise of sunlight load from the window sides.
• Select ceiling-type products to prevent damage done by the children.
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 7
1.2 Definition & Classification of
Office Buildings 2. Office Building

Office facility is a facility that carries out administrative tasks for economic activities of a
General corporation and government/local organizations.
Further divided into smaller types &
Office facility
usage forms

The user and owner of the building is the


Owned-Building
same.

Semi owned- There is only one tenant and only one


Building owner of the building.

The owner and user of the building are


Leased Building different.
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 8
1.2.1 Office Facility’s Space Composition 2. Office Building

Office facility’s space is composed of Office facility, Lobby/Hall, Dining Room&Arcade.

Office facility
■ Office/ Meeting room
■ Lecture &Seminar
rooms
■ Control Room for
Computers

Lobby/Hall
■ Lobby

■ Client meeting room

Dining Room/Rented
store ■ Employee Dining
Room / Big auditorium
■ Arcade / Rented store

■ Facility Management
Room
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 9
1.2.2 Characteristics of Office facility 2. Office Building

Many of the latest office facilities are high-rise buildings or skyscrapers with curtain-wall structures. They
frequently use the OA equipments, and the exterior surfaces of the buildings hold high intensity of illumination.

Extremely high-rise
CO₂concentration
is high.
All Glass Structure

Equipment/Equipment
load is large.
Perimeter radiant
heat load is large.

Human body load is large.

Lighting load is large.


Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 10
1.2.3 Design Conditions to be Considered 2. Office Building

In designing the office facility, consider the owner of the architectural structure, site & surrounding environment, plan
contents & relevant regulations etc.

1) Conditions for Use 1) Weather


• About people
• Yearly Temperature · Humidity·Wind
• About equipments direction·Wind speed· sunshine condition
• About usage hours Site & • Open air temperature in winter

• About the user environment Surrounding


Client Environment 2) Local characteristics
2) Grade, Cost of Construction
• Beaches, airports, etc.
• Set the Air conditioning • Site or local area’s characteristics
grade depending on the
building grade. 3) Infrastructure
3) Management
• Electric power, Gas etc.
• Self-Management Regulations • Energy Supply

• External- Management related to the Regional Air conditioning &


IntegratedElectric power Contents of the
• Individual Management of Heating Supply
BMS Decision Plan
the building

• Management for each


building 1) Plan Contents 2) Relevant regulations

• Value Energy Conservation & Safety factor • Long-


• Obtainment of Highly functional & refreshing environment life:, consider our planet's environmental proble
• Obtain high flexibility and credibility ms
• Economical efficiency is important (Initial cost & Running costs)
• About safety factors for fire-prevention/evacuation • About energy saving
• About quality obtainment such as indoor environment • About prevention of noise/ atmospheric contamination
and sanitation etc.
• About the safety of the structure

Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 11
1.2.3 Designing condition 2. Office Building

Follow the following condition for the temperature and humidity of general office rooms
that are not for multi-purpose use.

Temperature Humidity

26℃ 50%

Office Building’s Indoor


Heating 22℃Temperature/Humidity
50% condition

Classification

Air conditioning

Air refreshness of the indoor office building

Classification Ventilation amount per area Ventilation amount


per person
General Office room 10㎥/h·㎡ 25~30 ㎥/h

Personal Office room 8㎥/h·㎡ 25~30 ㎥/h


※ Since the Meeting room has more indoor contamination due to cigarette smokes, respond by increasing
ventilation capacity.

Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 12
1.2.4 Load & Management Characteristics 2. Office Building

Zoning based on load characteristics, directions, usage, driving hours etc. is


important for office facilities.

Air conditioning
Designing Point
System
Perimeter wall-side load Indoor equipments
is large. - Ceiling Cassette Type
- Built-in Duct Type
Equipment load of inner part & - Floor-fixed type
Lighting load is also large. To prevent cold draft, concurrently
run the floor fixed type & ceiling
Zoning based on load
type
characteristics( Inner Perimeter)

Zoning based on direction and Outdoor equipments


usage. - Air EHP System
- Water EHP System

Perimeter Zoning based on driving hours Ventilation


Inner Part - Electric heat exchange ventila
E.P.S-2

Office space Efficiency tion, AHU (ventilation + humidi


P.S

회의실-2
Maintenance(Ceiling-type Product) fication)

- Single zone constant air volume


UP

P.S
Appropriate CO₂ concentration
Inner Part Maintenance Control
Perimeter Open-air Air conditioning Centrifugal - Individual, 16 rooms
Chiller - 64 rooms PC control
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 13
1.2.4 Load & Management Characteristics_
Standard floors 2. Office Building

For office facility, zoning by load characteristics, directions, Usage, driving hours
etc. is important.

EHP + Electric heat exchange


Ventilation

OA • Zone-based Air conditioning &


EA
heating possible

• Room-based/zone-based
Ventilation possible

• Unit-based duct working


necessary

EHP + AHU

• Room-based/zone-based
Air conditioning & heating
possible
(duct cost increases)
EA OA • Common duct working
• open air- Air
conditioning better
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 14
1.2.4 Load & Management Characteristics_
Lobby/Hall 2. Office Building

The all-air-system, which is suitable for the structure with larges spaces and
high ceilings, and the air-water system is favorable.

Air conditioning
Designing Point System

Open air entry prevention


Indoor equipments, AHU
(Pressurization Necessary)
- Preventing cold draft, by using the
ducts located near the outer peri
All-glass structure; radiant meter of the building and by using
heat load is large. the floor fixed type
- AHU type + duct method application
(Air Conditioning & heating + venti-
Prevention of window-side lation + Humidification)
cold draft
Air Conditioning Units
- Air EHP System
Eruption air current’s reaching - Water EHP System
distance is important
Ventilation/Humidification
- AHU application (humidification)
Flow and balance of ventilation
air are important Control
- Individual, 16 rooms
- 64 rooms PC control
Open-air Air conditioning of
centrifugal chiller
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 15
1.2.4 Load & Management Characteristics_
2. Office Building
Employee Dining Room

Separate the zoning between the Kitchen and the Dining Room and maintain
the indoor space with negative pressure.

Air conditioning/
Designing Point Heat Source System

Dining Room &Kitchen zoning Indoor equipments, AHU


separation - Dining Room/Kitchen – focused
zoning.
Maintain with negative pressure - High ceiling dining room over
for the indoor dining room. 4 mtr : AHU
- Dining room under 4 mtr :
built-in duct, cassette
Air flow/balance( Dining Air Conditioning Units
Room→Kitchen) - Air EHP System
- Water EHP System
Ventilation frequency is Ventilation/Humidification
sufficiently considered - Electric heat exchange Ventila
tion or AHU (humidification
Kitchen Cooking part: Air omitted))
conditioning Installation
Control
- Individual, 16 rooms
Particular(Dining hours) hours - 64 rooms, PC control
load is large.
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 16
1.2.4 Load & Management Characteristics_
Rented store/Arcade 2. Office Building

For leased store, it is necessary to divide the electric power system of each
space for air conditioning.

Air conditioning/
Designing Point Heat source System
Air conditioning/ Heating
equipments Installation for each AHU
store - individual unit installation for
each store
- Consider the interior/indoor
Indoor Lighting load is large. space
- Ceiling type product better
(Cassette, duct)

Air Conditioning Units


internal Equipment load is large. - Air EHP System
- Water EHP System

Ventilation/Humidification
- Electric heat exchange Ventila
Air conditioning period is long tion or AHU (humidification
omitted))

Control
- Individual, 16 rooms
No window and low sunlight load - 64 rooms, PC control
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 17
1.2.4 Load & Management Characteristics_
Auditorium 2. Office Building

The central AC system and the method of using individual AHU (with the use of duct),
which are suitable for large spaces with high ceilings, are preferable for the
auditoriums.
Air conditioning
Designing Point System
AHU
Large space/High-ceiling - Central Air conditioning system
Structure - The air gets supplied from the
floor and returns to the
Only the lower-level floors ceiling
are living space - Big auditorium : AHU application
- Small auditorium under 4 mt :
Air conditioning & heating concealed duct
Necessary for living area
Air Conditioning Units
Horizontal/Perpendicular
- Air EHP System
Temperature &Air current spread
- Water EHP System
is important
Ventilation/Humidification
High population density
- Big auditorium :AHU (humidifi
cation)
The air gets supplied from the
- Mid/small auditorium : electric
floor and returns to the ceiling.
heat exchange ventilation . AHU
(humidifation)
Sufficient Ventilation Necessary
Control
Mushroom-type Intakes - Individual, 16 rooms
- 64 rooms, PC control
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 18
1.3 Medical Building 3. Medical Building

Classification Definition Characteristics

General Hospital • Large medical facility with various medical staffs, facility and • Drop-in patients &mid/long term

latest medical equipments • Patients are targeted.


• Can accommodate more than 100 inpatients • Composed of a number of
• When there are over 300 sickbeds, have over 9 medical specialties buildings such as hospitals/
for under 300 sickbeds, have over 7 medical specialties Funeral homes

Special Hospital
• Has the equipments and medical staffs for the specialty area
• Mostly targets in-patients
and managed by personal or small-sized organization.
• Generally composed of
• Can handle over 30 in-patients
1 floors ~ 1 building
• Has 1~2 specialized area of medical care

A doctor's office
• Primary medical institution managed by individual or • Mostly targets drop-in patients.
small-scale organization. • Generally composed of
• Generally has less than 20 beds 1~2 floors
• Has 1~2 specialized area of medical care

Nursing home • Its purpose is to accommodate

the inpatients in need of


• A medical institution with facilities to take in patients and provide
long-term care.
nursing care.
• Composed of a number of
• Can handle over 30 patients for medical treatment/support.
buildings, nursing home and
special hospitals, etc.

Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 19
1.3.1 Room Classification for each use 3. Medical Building

Ward section
Ward section

• Area to handle long-term treatment of


in admitted patients
• Composed of ICU, rooms & patient
rooms, quarantine rooms, recovery
Ward rooms, etc
section

Affiliated Treatment
Affiliated Treatment
Facilities
Facilities
Affiliated
Treatment • Area shared by admitted patients &
Facilities drop-in patients
• Composed of X-ray room,
physiotherapy, testing rooms, surgery
Drop-in rooms, gynecology, etc.
section

Drop-in section
Drop-in section

• Area handling patients who commute


from home to hospital.
• Composed of the reception area,
doctor’s office (internal medicine,
surgery, ophthalmology, otolaryngology ,
gynecology, dermatology, dental
health) &pharmacy, etc
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 20
1.3.2 Load & Management Characteristics_
Drop-in section 3. Medical Building

Drop-in section_Lobby &Hall Characteristic of the Load

• It is a zone in which the HVAC system operates for about


8 hours in every weekdays.
• High-ceiling/large space Structure
• All Glass Structure with large exterior load
• Heavy invading open air due to frequent entrance/exit as
well as indoor/outdoor temperature difference (Indoor Static
pressure maintenance is necessary)
• Hourly/daily/seasonal traffic discrepancy is large
• Lobby/Hall are sometimes used as waiting room.

☞ High-ceiling/all glass ☞ Hourly/daily/seasonal


windows traffic discrepancy is large
(Large hospital)

HVAC Management
Characteristics
• Consider High-ceiling/large space/ /all glass windows
structure/ hourly traffic change etc., for system selection
• Consider windshield room/Pressurization-type AHU to prevent
invasion of open air
• Consider floor-fixed type indoor equipments to eliminate
exterior load.
• Air conditioning for occupying residents
☞ A log of open air due to frequent entrance/exit • For the space with high-ceiling, consider the facts like the
(small/medium hospital) height that can be reached by the air (Selection of the diffuser)

* AHU : Air Handling Unit


Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 21
1.3.2 Load & Management Characteristics_
Drop-in section 3. Medical Building

Drop-in section_Waiting Room Characteristic of the Load


• It is a zone in which the HVAC system operates for about 8 hours
in every weekdays.
• Hourly/daily/seasonal traffic discrepancy is large
• Occupants (live load) &Lighting heating load is large.
• Sufficient Ventilation is necessary to eliminate odors such as
disinfectants etc.(Consider preventing secondary contamination
within the hospital)
• System Selection based on luxurious indoor interior design
• Low noise/low vibration designing
☞ Luxurious indoor interior designs

HVAC Management
Characteristics

• Sufficient Indoor equipments capacity must be

selected by considering occupants’ movements


for hours/seasons/days
☞ There are big discrepencies in occupancy depending on
• Apply sufficient Ventilation Capacity.
\ hours/seasons/days
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 22
1.3.2 Load & Management Characteristics_
Drop-in section 3. Medical Building

Drop-in section_Treatment Room Characteristic of the Load

• It is a zone in which the HVAC system operates for about 8


hours in every weekdays.
• Heavy exterior load in winter time
(Larger load compared to waiting rooms in the inner part of
the building)
• Prevent secondary contamination within the hospital
T.B. etc. treatment room: negative pressure considered
• For Orthopedics/ Hydro-therapy, consider the state of the
patient’s outfit
☞ Optimal air conditioning is necessary for treatment method in
each treatment room

HVAC Management
Characteristics
• Consider exterior load elimination system if the window
area is large
• Sufficient Ventilation capacity application (contamination
treatment room should be ventilated separately)
• Apply Higher DesigningTemperature compared to waiting room.
• Consider preventing a direct exposure of diffused air current
☞ Space for doctor’s tasks/medical examinations/Relaxation, on the patient for orthopedics and Hydro-therapy.
louver degree control&Diffuser location/specification
so consider low noise/low vibration of indoor equipments. selection
Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 23
1.3.2 Load & Management Characteristics_
Ward section 3. Medical Building

Ward section_In-patients Room


And Recovery Room Characteristic of the Load

• It is a zone in which the HVAC system operates for 24 hours.


• Due to the usage of random number of people, there is a big
discrepancy on comfortableness (Stability and comfortableness
are necessary in both emotional and physical senses)
• For large rooms, minimizing the indoor Temperature discrepancy
of left-right/top-bottom should be considered.
• Based on patient’s preference/health/outfit status and the room
location, Banquet Halldriving of centrifugal chiller Air conditioning
& heating . Banquet Halldriving may be possible

☞ Indoor Temperature discrepancy &window-side cold draft


may occur for multi-patients room.

HVAC Management
Characteristics
• Individual control is necessary, considering different hours of
operation for different rooms.
• Consider Sufficient Ventilation & Humidification (AHU Ventilation/
Humidification)
• Respond to the emergency situations, such as the system breakdown,
by utilizing the dual-zoning system of the AHUs and the air
-conditioning units (When necessary, apply the floor heating).
☞ Emergency response is necessary if the system goes out • Ensure that the patient is not directly exposed to the diffusion air
of order current in sleeping hours
louver degree control &Diffuser location/ Spec. Selection

Building Charecteristics and A/C System Copyright 2010@LG Electronics / AC Company All Rights Reserved 24
1.3.2 Load & Management Characteristics_
Ward section 3. Medical Building

Ward section_ICU Room /


Newborn room Characteristic of the Load
• It is a zone in which the HVAC system operates for 24 hours.
• Sufficient Ventilation & Humidification Necessary
• Indoor Static pressure is necessary to maintain cleanness
(high cleanness area)
• Indoor heating is high due to the installation of medical
equipments with large heat emissions.
• Ensure that the patient is not directly exposed to the diffused
air current.
☞ Maintenance of sufficient Ventilation/ Humidification &Indoor
cleanness are required for ICU.

HVAC Management
Characteristics
• Sufficient Ventilation Capacity &Static pressure Maintenance
• Duct zoning separation with doctor's office/ halls etc.
Prevent the inflow of contaminated air from nearby rooms
• Maintain cleanness through Pre filter + high-performance filter
application (Multi V AHU application)
☞ Indoor static pressure for Newborn room/ICU room. (Indoor
cleanness should be maintained.) • If necessary, apply floor heating.

* ICU : Intensive Care Unit