You are on page 1of 1

N

ECP
DS
HD SD

A
FM 200 FIRE SUPPRESSION SYSTEM
NTS.
ELECTRONICS LAYOUT

LEGENDS

SD HD SYMBOL DESCRIPTION

SD

DS

ECP

B.I. PIPE SEAMLESS SCH. 40 B.I. PIPE SEAMLESS SCH. 40

B.I. PIPE SEAMLESS SCH. 40

B.I. PIPE SEAMLESS SCH. 40 B.I. PIPE SEAMLESS SCH. 40


FM 200 FIRE SUPPRESSION SYSTEM
NTS.
MECHANICAL LAYOUT

ROOM VOID

S
S

ZONE-2

ZONE-1
RADIUS = 9.04m RADIUS = 13.92m

FM200 A
FIRE
PL EXTINGUISHING
CEILING HT. = 30.5cm TO 4.8m CONTROL PANEL
- + E N L SL C NO NC
(OPTIONAL)
CEILING HT. = 30.5cm TO 4.8m
360° NOZZLE
TO TRIP AHU/HVAC/DROP CURTAIN
DOOR HOLDER ETC. (BY VENDORS)

180° NOZZLE OUTPUT TO SOLENOID VALVE 24V DC.

230V, 60Hz, 1Ø, AC POWER SUPPLY


PSL
2x12V DC, 7AH, BATTERY BACK UP.

SUPERVISORY PRESSURE SWITCH

FM200

NOZZLE TYPE & MAX. SECTION A-A


CYLINDER

NOZZLE COVERAGE AREA TYPICAL NOZZLE MOUNTING DETAIL NTS


SCALE N.T.S SERVER ROOM
SCALE N.T.S P&I DIAGRAM
SCALE N.T.S
OWNER:

OWNER REPRESENTATIVE:

6.0"
152mm
PROJECT TITLE:

JUNCTION BOX
1/2"FLEXIBLE ADAPTOR EMT ADAPTOR INSTALLATION OF IG 55 FIRE SUPPRESSION SYSTEM

JUNCTION BOX CEILING VOID


PROJECT LOCATION:
H1
D2
H2 SMOKE DETECTOR
IN ROOM VOID
ENGINEER:
REG. #
H3

STROBE HORN 1/2" DIA EMT PIPE ALARM BELL 1/2" DIA EMT PIPE P.T.R. #
1/2" DIA EMT PIPE
UTILITY BOX UTILITY BOX

DATE/PLACE ISSUED
CONTROL PANEL

D1 FIRE PROTECTION CONTRACTORS:


ROOM VOID

2320
2320
Nominal CYLINDER DIMENSIONS 1/2" DIA EMT PIPE

UTILITY BOX
MANUAL PULL

Cylinder 420 LBS

1200
1300
Size in mm FFL

FFL FFL FFL


drawing title
H1 76.37 1940 SECTION-4
SECTION-1 SECTION-2 SECTION-3
H2 62.19 1580 FFL. FM200 FIRE SUPPRESSION SYSTEM LAYOUT
H3 36.8 935 TYPICAL ARRANGEMENT OF FIRE ALARM DEVICE job no. date.
D1 16.0 406 SERVER ROOM SCALE NTS

D2 17.9 455 drawn by. checked by. approved by.


DETAILS OF BRACES AND BRACKET SMOKE DETECTOR ,REMOTE INDICATOR & RISER
VZU
SCALE N.T.S
MOUNTING DETAIL SCALE N.T.S.
drawing no.
CYLINDER DETAILS scale.
SCALE N.T.S IG-O1