STRUCTURAL INVESTIGATION REPORT


Tower Type : 18M 3-LEGGED RT SST
Site ID : 978
Site Name : SINGALONG
Site Address : Felisa Bldg., Pres. Quirino Ave., Malate, Manila
Project Name : SMART HUAWEI PROJECT
Scope of work : A3
Revision : 0.0
Date : June 18, 2019

Submission EFB Checked SMART Approved Comments


Rev
date by Date by Date
Elizalde Cabangon
1
           

E.F.B. GEOSTRUKT, INC.


BUILDERS ENGINEERS  CONSULTANTS  SITE ACQUISITION
805 Cityland 10 Tower II,#154 H.V. Dela Costa St.,1227 Makati City
TEL: (+63 2) 817-0022FAX: (+63 2) 817-4477
978_SINGALONG
18M 3L SST 270KPH_B

TABLE OF CONTENTS
i. Certification

ii. Analysis Questionnaires/Parameter’s Summary

iii. Analysis Results Summary (Existing Loads)

iv. Analysis Results Summary (Existing + Proposed Loads)

v. Analysis Results Summary (Existing + Proposed + Future Loads)

vi. Analysis Results Summary (With Retrofitting)

vii. Maximum Reaction Summary

viii. Antenna Loading Summary

ix. Retrofitting Scheme

I. TOWER STRUCTURAL EVALUATION

I.A. Executive Summary


I.B. Design Criteria
I.C. NSCP 2015 Wind Map

II. ATTACHMENT

II.A. Photographs
II.B. Drawings
II.C. PRC AND PTR
II.D. MS Tower License
II.E. Bentley Cloud Service Subscription Voucher

EFB GEOSTRUKT INC. 
E.F.B. GEOSTRUKT, INC.
BUILDERS ENGINEERS  CONSULTANTS  SITE ACQUISITION

805 Cityland 10 Tower II,#154 H.V. Dela Costa St.,1227 Makati City
Tel: (+63 2) 817-0022Fax: (+63 2) 817-4477

 
CERTIFICATE OF STRUCTURAL STABILITY 
 
Site Code/ID  :  978 
Site Name  :  SINGALONG 
Location  :  Felisa Bldg., Pres. Quirino Ave., Malate, Manila 
Date  :  June 18, 2019 
 
 
This is to certify that our office EFB Geostrukt Inc. has conducted a structural evaluation of 
the existing tower of 978_SINGALONG, a Smart Communications Inc. cell site with a 18m 3‐
legged roof top SST located at Felisa Bldg., Pres. Quirino Ave., Malate, Manila. 
 
The  structural  members  of  the  existing  antenna  support  structure  with  the  antenna  loads 
listed in the “Antenna Loading Summary” were evaluated in accordance with the minimum 
load  and  design  provisions  of  the  National  Structural  Code  of  the  Philippines  (NSCP  2015, 
7th  Edition)  and  Telecommunications  Industry  Association  Standards  (ANSI/TIA‐222‐G‐
2005). Along with the following considerations the structure with retrofitting was found to 
be ADEQUATE to support the proposed and additional antenna upgrade. 
 
1. Site location basic wind velocity of 270 Kph for Occupancy Category I Exposure B 
2. The structural pipe members all conforms with ASTM A53 standard and ASTM A36 for steel 
plates and other sections. 
 
Additionally, the immediate members of the building frame that is affected by the poles and globe 
equipment have satisfactorily met the minimum strength and serviceability requirements set forth 
by the following governing codes:  
• Concrete compressive strength at 28 days assumed at 21 Mpa (3000 Psi).  
• Reinforcing bars yield strength assumed at 414Mpa (60000 Psi) for all members.  
• National Structural Code of the Philippines 2015 7th Edition  
• Structural Standard for Antenna Supporting Structures and Antennas (TIA‐222‐G)  
• American Institute of Steel Construction (AISC)  
• American Concrete Institute (ACI Publications)  
 
This  certification  is  issued  upon  the  request  of  SMART  COMMUNICATIONS  INC.  for 
whatever purpose it may serve them. 
 
 
 
ELIZALDE S. CABANGON a.asep 
PRC No : 0104270 
PTR No.:  2429298 
DATE  : 01‐08‐2019 
PLACE  : Plaridel, Bulacan 
 
NO. QUESTION / PARAMETER YES NO

1 Was the BASIC WIND SPEED  determined based on NSCP? If YES, which was used for

Strength/Survival Wind Speed = 270 kph

2 Did the EXPOSURE CLASSIFICATION  take into account the local environment as well as the
distance from the shore line? If not, please specify why not? 
What classification is applicable?

Distance from the coastline:

Exposure B
Exposure C
Exposure D

3 Was the Topographic Factor  calculated based on actual condition as per NSCP?
If not, please specify factor was used?

Factor Used: Flat Area = 1.0

4 Was the Directional Factor  determined as per NSCP? If not, please specify why not.
If yes, what value was used?

Lattice structures triangular, square or rectangular cross section ‐ 0.85
Tubular pole structures, lattice structures with other cross sections ‐ 0.95

5 Was an Ultimate Strength Design (USD/LRFD) used for the analysis?
If not, please specify why not below.

6 Was MS Tower  utilized for the software analysis? If yes, What version?
If not, please specify what was used, what version and why?

Notes:  MS TOWER V6
NO. QUESTION / PARAMETER YES NO

7 Was ANSI/TIA/EIA 222‐G  used to determine the following? If not please specify
why not below.
Gust Effect Factor 0.85
Appurtenances Loading
Member Effective Lengths and Slenderness Ratio

Notes:

8 What Wind Directions  were considered for the analysis? Please specify below.

0°, 30°, 60°, 90°, 120°, 150°, 180°, 210°, 240°, 270°, 300°, 330°

9 For Access Antennae Wind & Dead Loading , was it based on the factory/actual test
results? If not, please specify what was used and why.

Notes: Wind Forces were based on TIA‐222‐G

10 For Microwave Antennae Wind & Dead Loading , was it based on the factory/actual test
results? If not, please specify what was used and why

Notes: Wind Forces were derived from TIA‐222‐G

11 Was the actual orientation of the antennae and feeder cables taken into consideration?
If not, please specify why not below

Notes:

12 Was the Eccentricity of the Access Antennae  taken into consideration? If not please specify
why not below

Notes:
NO. QUESTION / PARAMETER YES NO

13 Was the Eccentricity of the Microwave Antennae  taken into consideration? If not please specify
If not, please specify why not below.

Notes:

14 Were the Antennae Mounting Brackets  for both the Access & Microwave Antennae taken into
account in the analysis? If not, please specify why not below.

Notes:

15 Was Shielding onto another Antenna  applicable for the structure?
If Yes, please specify what antennas and corresponding heights were affected.

Notes: None of the antenna shielded the others

16 Was Shielding of Antennae onto Tower members  taken into account for the analysis?
If not please specify why not below.

Notes: in accordance with TIA‐222‐G Provisions

17 How the climbing/Cable ladder wind loads  modelled in the analysis?

Not Considered
Applied as lateral point loads at ladder connection points to the tower
Applied as a lateral Uniform Distributed Load up to the Tower

Notes:

18 How was the climbing/cable ladder & Feeder Dead Loads  modelled in the analysis?

Applied as lateral point loads at ladder connection points to the tower
Not applied to the tower, all loads are assumed to be supported by the foundation

Notes:
NO. QUESTION / PARAMETER YES NO

19 Were the following Recommended Loads  used for the analysis? 
If not, What was the adopted loads?

ITEM RECOMMENDED LOADS LOAD ADAPTED


Steel Weight 77 kN/m3
Concrete Weight 24 kN/m3
Soil Weight 16 kN/m3
2.4 kN/m2 or a minimum 
Live Load
point load of 2 kN
Single 7/8" Feeder Cable 0.05 kN/m
Single 15/8" Feeder Cable 0.13 kN/m
Single 1/2" Feeder Cable 0.025 kN/m

20 Were there any As‐built drawings available for the foundation ?

Notes:

21 If no As‐built drawings were available for the foundation , How was its capacity determined?

Not applicable as‐built available
Not checked
A comparison was made between the reaction loads
based on the standard loading to the new reaction loads
The capacity of the bottom tower legs was used as a guide
to determine the foundation capacity

Notes:  The analysis of foundation is not included in our scope of work.

22 KEY ASSUMPTIONS

1. All tower members with solid round sections, all the rest of the tower members, and plates 
were assumed to be A36 Type (Fy = 248 mPa).
2. All tower members with pipe sections were assumed to be A53 Grade B with yield strength of 240 mPa
3. All guy wires were assumed to be 6x19 IWRC type steel ASTM 475 Extra High Strength Grade.
Accessories were assumed heavy duty type per ASTM Standard.
4. Connection bolts for leg splices were assumed to be ASTM A325 (Fy = 628 mPa)
5. Anchor bolts were assumed to be ASTM A307 Type.
6. Site topographic factor used was based on assumed parameters and area condition.
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULTS SUMMARY

Scenario: Existing Tower with Current Loads

TOWER STRESS DIAGRAM

SERVICEABILITY PERFORMANCE 
Height  LC  Item Value Remarks

18.00  5040  Tower Top Sway  0.200359 deg  ADEQUATE 

18.00  5030  Tower Rotation  0.175898 deg  ADEQUATE 

BASE PLATE AND ANCHORAGE 
  Member  Description FOS Remarks
BASEPLATE  180ø x 16mm thk 3.634 ADEQUATE

ANCHOR 6– M16 4.118 ADEQUATE

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULT SUMMARY                
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

10  0 ‐ 2.5  LEG  CHS73.025X5.156  137  0.87  ‐  ‐  ADEQUATE 


4  13.3 ‐ 15  BRC  EA40X40X6  35  0.09  27  0.12  ADEQUATE 
10  0 ‐ 2.5  HOR  EA40X40X6  11  1.32  27  0.56  FAIL 
7  7.5 ‐ 10  XBR  EA40X40X6  13  0.97  27  0.48  ADEQUATE 
 

TOWER LEG RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 


2  16 ‐ 17  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
3  15 ‐ 16  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
4  13.3 ‐ 15  LEG  CHS48.26X3.683  63  0.21  80  0.17  ADEQUATE 
5  12.5 ‐ 13.3  LEG  CHS48.26X3.683  97  0.18  ‐  ‐  ADEQUATE 
6  10 ‐ 12.5  LEG  CHS73.025X5.156  137  0.16  80  0.27  ADEQUATE 
7  7.5 ‐ 10  LEG  CHS73.025X5.156  137  0.32  ‐  ‐  ADEQUATE 
8  5 ‐ 7.5  LEG  CHS73.025X5.156  137  0.52  80  0.89  ADEQUATE 
9  2.5 ‐ 5  LEG  CHS73.025X5.156  137  0.71  ‐  ‐  ADEQUATE 
10  0 ‐ 2.5  LEG  CHS73.025X5.156  137  0.87  ‐  ‐  ADEQUATE 
 

TOWER DIAGONAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  BRC  EA40X40X6  52  0.01  27  0.02  ADEQUATE 


2  16 ‐ 17  BRC  EA40X40X6  52  0.02  27  0.04  ADEQUATE 
3  15 ‐ 16  BRC  EA40X40X6  52  0.03  27  0.06  ADEQUATE 
4  13.3 ‐ 15  BRC  EA40X40X6  35  0.09  27  0.12  ADEQUATE 
5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.07  27  0.08  ADEQUATE 
6  10 ‐ 12.5  XBR  EA40X40X6  14  0.36  27  0.21  ADEQUATE 
7  7.5 ‐ 10  XBR  EA40X40X6  13  0.97  27  0.48  ADEQUATE 
8  5 ‐ 7.5  XBR  EA50X50X6  23  0.62  27  0.55  ADEQUATE 
9  2.5 ‐ 5  XBR  EA50X50X6  21  0.69  27  0.55  ADEQUATE 
10  0 ‐ 2.5  XBR  EA50X50X6  19  0.90  27  0.64  ADEQUATE 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

TOWER HORIZONTAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  HOR  EA40X40X6  62  0.00  27  0.00  ADEQUATE 


2  16 ‐ 17                      
3  15 ‐ 16                      
4  13.3 ‐ 15  HOR  EA40X40X6  62  0.00  27  0.01  ADEQUATE 
5  12.5 ‐ 13.3                      
6  10 ‐ 12.5  HOR  EA40X40X6  60  0.02  27  0.05  ADEQUATE 
7  7.5 ‐ 10  HOR  EA40X40X6  36  0.04  27  0.06  ADEQUATE 
8  5 ‐ 7.5  HOR  EA40X40X6  22  0.34  27  0.29  ADEQUATE 
9  2.5 ‐ 5  HOR  EA40X40X6  15  0.72  27  0.42  ADEQUATE 
10  0 ‐ 2.5  HOR  EA40X40X6  11  1.32  27  0.56  FAIL 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULTS SUMMARY

Scenario: Existing Tower with Current + Proposed Loads

TOWER STRESS DIAGRAM

SERVICEABILITY PERFORMANCE 
Height  LC  Item Value Remarks

18.00  5040  Tower Top Sway  0.24086 deg  ADEQUATE 

18.00  5030  Tower Rotation  0.20455 deg  ADEQUATE 

BASE PLATE AND ANCHORAGE 
  Member  Description FOS Remarks
BASEPLATE  180ø x 16mm thk 2.904 ADEQUATE

ANCHOR 6– M16 3.500 ADEQUATE

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULT SUMMARY                
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

10  0 ‐ 2.5  LEG  CHS73.025X5.156  137  1.06  ‐  ‐  FAIL 


5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.13  27  0.16  ADEQUATE 
10  0 ‐ 2.5  HOR  EA40X40X6  11  1.62  27  0.71  FAIL 
7  7.5 ‐ 10  XBR  EA40X40X6  13  1.27  27  0.62  FAIL 
 

TOWER LEG RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 


2  16 ‐ 17  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
3  15 ‐ 16  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
4  13.3 ‐ 15  LEG  CHS48.26X3.683  63  0.22  80  0.17  ADEQUATE 
5  12.5 ‐ 13.3  LEG  CHS48.26X3.683  97  0.19  ‐  ‐  ADEQUATE 
6  10 ‐ 12.5  LEG  CHS73.025X5.156  137  0.19  80  0.33  ADEQUATE 
7  7.5 ‐ 10  LEG  CHS73.025X5.156  137  0.41  ‐  ‐  ADEQUATE 
8  5 ‐ 7.5  LEG  CHS73.025X5.156  137  0.66  80  1.13  ADEQUATE 
9  2.5 ‐ 5  LEG  CHS73.025X5.156  137  0.88  ‐  ‐  ADEQUATE 
10  0 ‐ 2.5  LEG  CHS73.025X5.156  137  1.06  ‐  ‐  FAIL 
 

TOWER DIAGONAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  BRC  EA40X40X6  52  0.01  27  0.02  ADEQUATE 


2  16 ‐ 17  BRC  EA40X40X6  52  0.02  27  0.04  ADEQUATE 
3  15 ‐ 16  BRC  EA40X40X6  52  0.03  27  0.06  ADEQUATE 
4  13.3 ‐ 15  BRC  EA40X40X6  35  0.11  27  0.15  ADEQUATE 
5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.13  27  0.16  ADEQUATE 
6  10 ‐ 12.5  XBR  EA40X40X6  14  0.63  27  0.34  ADEQUATE 
7  7.5 ‐ 10  XBR  EA40X40X6  13  1.27  27  0.62  FAIL 
8  5 ‐ 7.5  XBR  EA50X50X6  23  0.78  27  0.69  ADEQUATE 
9  2.5 ‐ 5  XBR  EA50X50X6  21  0.85  27  0.68  ADEQUATE 
10  0 ‐ 2.5  XBR  EA50X50X6  19  1.10  27  0.79  FAIL 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

TOWER HORIZONTAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  HOR  EA40X40X6  62  0.00  27  0.00  ADEQUATE 


2  16 ‐ 17                      
3  15 ‐ 16                      
4  13.3 ‐ 15  HOR  EA40X40X6  62  0.00  27  0.01  ADEQUATE 
5  12.5 ‐ 13.3                      
6  10 ‐ 12.5  HOR  EA40X40X6  60  0.03  27  0.07  ADEQUATE 
7  7.5 ‐ 10  HOR  EA40X40X6  36  0.07  27  0.10  ADEQUATE 
8  5 ‐ 7.5  HOR  EA40X40X6  22  0.44  27  0.38  ADEQUATE 
9  2.5 ‐ 5  HOR  EA40X40X6  15  0.90  27  0.54  ADEQUATE 
10  0 ‐ 2.5  HOR  EA40X40X6  11  1.62  27  0.71  FAIL 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULTS SUMMARY

Scenario: Existing Tower with Current + Proposed + Future Loads

TOWER STRESS DIAGRAM

SERVICEABILITY PERFORMANCE 
Height  LC  Item Value Remarks

18.00  5040  Tower Top Sway  0.407097 deg  ADEQUATE 

18.00  5030  Tower Rotation  0.361536 deg  ADEQUATE 

BASE PLATE AND ANCHORAGE 
  Member  Description FOS Remarks
BASEPLATE  180ø x 16mm thk 1.994 ADEQUATE

ANCHOR 6– M16 2.315 ADEQUATE

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULT SUMMARY                
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

10  0 ‐ 2.5  LEG  CHS73.025X5.156  137  1.55  ‐  ‐  FAIL 


5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.33  27  0.42  ADEQUATE 
10  0 ‐ 2.5  HOR  EA40X40X6  11  2.45  27  1.06  FAIL 
7  7.5 ‐ 10  XBR  EA40X40X6  13  1.98  27  0.95  FAIL 
 

TOWER LEG RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 


2  16 ‐ 17  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
3  15 ‐ 16  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
4  13.3 ‐ 15  LEG  CHS48.26X3.683  63  0.50  80  0.39  ADEQUATE 
5  12.5 ‐ 13.3  LEG  CHS48.26X3.683  97  0.47  ‐  ‐  ADEQUATE 
6  10 ‐ 12.5  LEG  CHS73.025X5.156  137  0.45  80  0.77  ADEQUATE 
7  7.5 ‐ 10  LEG  CHS73.025X5.156  137  0.76  ‐  ‐  ADEQUATE 
8  5 ‐ 7.5  LEG  CHS73.025X5.156  137  1.07  80  1.84  FAIL 
9  2.5 ‐ 5  LEG  CHS73.025X5.156  137  1.35  ‐  ‐  FAIL 
10  0 ‐ 2.5  LEG  CHS73.025X5.156  137  1.55  ‐  ‐  FAIL 
 

TOWER DIAGONAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  BRC  EA40X40X6  52  0.01  27  0.02  ADEQUATE 


2  16 ‐ 17  BRC  EA40X40X6  52  0.02  27  0.04  ADEQUATE 
3  15 ‐ 16  BRC  EA40X40X6  52  0.03  27  0.06  ADEQUATE 
4  13.3 ‐ 15  BRC  EA40X40X6  35  0.33  27  0.43  ADEQUATE 
5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.33  27  0.42  ADEQUATE 
6  10 ‐ 12.5  XBR  EA40X40X6  14  1.33  27  0.71  FAIL 
7  7.5 ‐ 10  XBR  EA40X40X6  13  1.98  27  0.95  FAIL 
8  5 ‐ 7.5  XBR  EA50X50X6  23  1.19  27  1.05  FAIL 
9  2.5 ‐ 5  XBR  EA50X50X6  21  1.23  27  0.98  FAIL 
10  0 ‐ 2.5  XBR  EA50X50X6  19  1.55  27  1.10  FAIL 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

TOWER HORIZONTAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  HOR  EA40X40X6  62  0.00  27  0.00  ADEQUATE 


2  16 ‐ 17                      
3  15 ‐ 16                      
4  13.3 ‐ 15  HOR  EA40X40X6  62  0.06  27  0.14  ADEQUATE 
5  12.5 ‐ 13.3                      
6  10 ‐ 12.5  HOR  EA40X40X6  60  0.09  27  0.21  ADEQUATE 
7  7.5 ‐ 10  HOR  EA40X40X6  36  0.21  27  0.30  ADEQUATE 
8  5 ‐ 7.5  HOR  EA40X40X6  22  0.75  27  0.66  ADEQUATE 
9  2.5 ‐ 5  HOR  EA40X40X6  15  1.43  27  0.86  FAIL 
10  0 ‐ 2.5  HOR  EA40X40X6  11  2.45  27  1.06  FAIL 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANALYSIS RESULTS SUMMARY

Scenario: Retrofitted Tower with Current + Proposed + Future Loads

TOWER STRESS DIAGRAM

SERVICEABILITY PERFORMANCE 
Height  LC  Item Value Remarks

18.00  5040  Tower Top Sway  0.407097 deg  ADEQUATE 

18.00  5030  Tower Rotation  0.361536 deg  ADEQUATE 

BASE PLATE AND ANCHORAGE 
  Member  Description FOS Remarks
BASEPLATE  180ø x 16mm thk 1.994 ADEQUATE

ANCHOR 6– M16 2.315 ADEQUATE

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

 
ANALYSIS RESULT SUMMARY                
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

7  7.5 ‐ 10  LEG  CHS73.025X5.156  137  0.70  ‐  ‐  ADEQUATE 


5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.33  27  0.42  ADEQUATE 
8  5 ‐ 7.5  HOR  EA40X40X6  22  0.82  27  0.72  ADEQUATE 
7  7.5 ‐ 10  XBR  DAE40X40X6  81  0.42  53  0.64  ADEQUATE 
 

TOWER LEG RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 


2  16 ‐ 17  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
3  15 ‐ 16  LEG  CHS48.26X3.683  91  0.07  ‐  ‐  ADEQUATE 
4  13.3 ‐ 15  LEG  CHS48.26X3.683  63  0.49  80  0.39  ADEQUATE 
5  12.5 ‐ 13.3  LEG  CHS48.26X3.683  97  0.47  ‐  ‐  ADEQUATE 
6  10 ‐ 12.5  LEG  CHS73.025X5.156  137  0.40  80  0.69  ADEQUATE 
7  7.5 ‐ 10  LEG  CHS73.025X5.156  137  0.70  ‐  ‐  ADEQUATE 
8  5 ‐ 7.5  LEG  CHS83.025X10.15  314  0.48  142  1.06  ADEQUATE 
9  2.5 ‐ 5  LEG  CHS83.025X10.15  314  0.59  ‐  ‐  ADEQUATE 
10  0 ‐ 2.5  LEG  CHS83.025X10.15  314  0.69  ‐  ‐  ADEQUATE 
 

TOWER DIAGONAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  BRC  EA40X40X6  52  0.01  27  0.02  ADEQUATE 


2  16 ‐ 17  BRC  EA40X40X6  52  0.02  27  0.04  ADEQUATE 
3  15 ‐ 16  BRC  EA40X40X6  52  0.03  27  0.06  ADEQUATE 
4  13.3 ‐ 15  BRC  EA40X40X6  35  0.33  27  0.43  ADEQUATE 
5  12.5 ‐ 13.3  BRC  EA40X40X6  33  0.33  27  0.42  ADEQUATE 
6  10 ‐ 12.5  XBR  DAE40X40X6  79  0.31  27  0.92  ADEQUATE 
7  7.5 ‐ 10  XBR  DAE40X40X6  81  0.42  53  0.64  ADEQUATE 
8  5 ‐ 7.5  XBR  DAE50X50X6  120  0.20  27  0.92  ADEQUATE 
9  2.5 ‐ 5  XBR  DAE50X50X6  109  0.24  47  0.54  ADEQUATE 
10  0 ‐ 2.5  XBR  DAE50X50X6  98  0.29  47  0.60  ADEQUATE 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

TOWER HORIZONTAL RESULT SUMMARY             
PANEL  MEMBER SIZE  MEMBER  BOLT 
HEIGHT  TYPE  RATIO  RATIO  STATUS 
(m)  (mm)  CAPACITY  CAPACITY 

1  17 ‐ 18  HOR  EA40X40X6  62  0.00  27  0.00  ADEQUATE 


2  16 ‐ 17                      
3  15 ‐ 16                      
4  13.3 ‐ 15  HOR  EA40X40X6  62  0.06  27  0.14  ADEQUATE 
5  12.5 ‐ 13.3                      
6  10 ‐ 12.5  HOR  EA40X40X6  60  0.13  27  0.29  ADEQUATE 
7  7.5 ‐ 10  HOR  EA40X40X6  36  0.40  27  0.55  ADEQUATE 
8  5 ‐ 7.5  HOR  EA40X40X6  22  0.82  27  0.72  ADEQUATE 
9  2.5 ‐ 5  HOR  DAE40X40X6  75  0.26  27  0.77  ADEQUATE 
10  0 ‐ 2.5  HOR  DAE40X40X6  55  0.48  47  0.57  ADEQUATE 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐SST 270KPH_B 

MAXIMUM REACTION SUMMARY

MAX.  REACTIONS ‐ A1 
INDIVIDUAL LEG REACTION  TOWER REACTIONS 
ITEM  LOADING CASE  HORIZONTAL  VERTICAL 
COMPRESSION  UPLIFT  SHEAR  MOMENT  
SHEAR  THRUST 
1  EX  142.33   ‐126.29   25.08   262.43   29.33   16.62  
2  EX+PR  171.99   ‐158.41   29.09   317.75   33.93   18.81  
3  EX+PR+FU  248.18   ‐231.49   39.61   460.82   43.71   23.34  
 

MAX.  REACTIONS ‐ A1 (EXISTING LOADS) 
     
ITEM  LOADING CASE 
FX  FY  FZ  MX  MY  MZ 
MAX 
1  ‐21.69   142.33   ‐12.63   ‐0.04   0.00   0.07  
COMPRESSION 
2  MAX UPLIFT  0.10   ‐126.29   ‐21.60   ‐0.07   0.00   0.00  
3  MAX SHEAR  ‐0.10   142.12   25.08   0.08   0.00   0.00  
 

MAX.  REACTIONS ‐ A1 (EXISTING + PROPOSED LOADS) 
     
ITEM  LOADING CASE 
FX  FY  FZ  MX  MY  MZ 
MAX 
1  ‐21.69   171.99   ‐12.63   ‐0.04   0.00   0.07  
COMPRESSION 
2  MAX UPLIFT  18.64   ‐158.41   10.89   0.04   0.00   ‐0.06  
3  MAX SHEAR  ‐0.10   142.12   29.09   0.08   0.00   0.00  
 

MAX.  REACTIONS ‐ A1 (EXISTING + PROPOSED + FUTURE LOADS) 
     
ITEM  LOADING CASE 
FX  FY  FZ  MX  MY  MZ 
MAX 
1  ‐34.53   248.18   ‐20.41   ‐0.04   0.00   0.08  
COMPRESSION 
2  MAX UPLIFT  ‐31.32   ‐231.49   18.15   0.04   0.00   0.07  
3  MAX SHEAR  ‐0.06   244.51   39.61   0.09   0.00   0.00  

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

ANTENNA LOADING SUMMARY

EXISTING LOADS 

ACCESS ANTENNA
Leg  Type  Dimension  Qty. Height Azimuth Remarks  
A  12‐Ports  2769x429x196  1  10.00  60  Pre‐Installed 
B  12‐Ports  2769x429x196  1  10.00  180  Pre‐Installed 
C  12‐Ports  2769x429x196  1  10.00  280  Pre‐Installed 
A  BTS  750x300x120  1  11.00  60  For Dismantling 
B  BTS  750x300x120  1  11.00  180  For Dismantling 
C  BTS  750x300x120  1  11.00  280  For Dismantling 
 
 
FEEDER CABLE  
Loaded Width (Mm)  Loaded Depth  Type Comments 

400  50  1.5m From Floor to Top   


 
 
PROPOSED LOADS 
ACCESS ANTENNA
Leg  Type  Dimension  Qty. Height Azimuth Remarks  
2.3 MM 
A  860x520x170  1  11.00  60  Proposed 
(MIMO) 
2.3 MM 
B  860x520x170  1  11.00  180  Proposed 
(MIMO) 
2.3 MM 
C  860x520x170  1  11.00  280  Proposed 
(MIMO) 
 
 
MICROWAVE ANTENNA
Leg  Type  Diameter   Qty. Height Azimuth Remarks  
C  Shroud  1200  1  13.00  280  Proposed 
 
 
FEEDER CABLE  
Loaded Width (Mm)  Loaded Depth  Type Comments 

450  50  1.5m From Floor to Top   


 
   

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

 
 
 
 
FUTURE LOADS 

ACCESS ANTENNA
Leg  Type  Dimension  Qty. Height Azimuth Remarks  
2.6G MM 
A  860x520x170  1  15.00  60  Reserve 
(MIMO) 
2.6G MM 
B  860x520x170  1  15.00  180  Reserve 
(MIMO) 
2.6G MM 
C  860x520x170  1  15.00  280  Reserve 
(MIMO) 
3.5G MM 
A  795x395x220  1  15.00  60  Reserve 
(MIMO) 
3.5G MM 
B  795x395x220  1  15.00  180  Reserve 
(MIMO) 
3.5G MM 
C  795x395x220  1  15.00  280  Reserve 
(MIMO) 
 
 
MICROWAVE ANTENNA
Leg  Type  Diameter   Qty. Height Azimuth Remarks  
B  Shroud  1200  1  13.00  180  Reserve 
 
FEEDER CABLE  
Loaded Width (Mm)  Loaded Depth  Type Comments 

500  50  1.5m From Floor to Top   

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

RETROFITTING SCHEME

2
1. PROVIDE 5MM THICK STEEL
PLATE JACKET
PANEL 5 TO PANEL 7

3 2. PROVIDE ANGLE BAR ON


DIAGONAL TO MAKE DOUBLE
ANGLE (SAME AS EXISTING)
PANEL 3 TO PANEL 7

4 3. PROVIDE ANGLE BAR ON


HORIZONTAL TO MAKE DOUBLE
ANGLE
PANEL 6 TO PANEL 7

5 4. PROVIDE CLAMP ON LEG TO


LEG CONNECTION
PANEL 5

EFB GEOSTRUKT INC. 
I.  TOWER STRUCTURAL EVALUATION 
I.A. Executive Summary
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

1. INTRODUCTION

The structural design review of the existing 18sm 3-Legged SST located at Felisa Bldg.,
Pres. Quirino Ave., Malate, Manila conducted by the undersigned upon the commission
of SMART Communication Inc.
The main objective of the design review and appraisal is to determine the structural
integrity of the existing tower and foundation affected by the proposed antenna upgrade.

2. SCOPE OF WORK

The structural review and appraisal involve the following procedures:


Conduct site inspection and determine conduct an as-built of the existing tower. Based
on the preliminary and ocular inspection, make a preliminary assessment of the existing
physical condition.
Evaluate the existing antenna support structure and foundation based on the loading
requirements provided by the client.
To provide design plans for structural strengthening and upgrading works when found
necessary to restore the structural soundness and integrity of the whole structure based
on the new antenna load requirement.

3. EXISTING CELL SITE BRIEF DESCRIPTION

The existing cell site is a roof deck structure. It is an 18m high 3-legged self-supporting
tower that will support the additional antenna upgrade of Smart Communication Inc.
The. The tower is currently supporting 3 – 12 Ports antenna, and 3 –BTS antenna.
The proposed antenna upgrade of the project is installing of 3 – 2.3 MM (MIMO), 1 –
1.2mø microwave antenna and dismantling of 3 –BTS antenna. The reserve antennas
considered are 3 – 2.6G MM(MIMO), 3 – 3.5G MM (MIMO) and 1 – 1.2m ø MW.

4. RESULT OF EVALUATION OF THE EXISTING TOWER

The tower analyzed with the help of MS TOWER software; loads based on the existing
antenna as surveyed and the load consideration provided by the client. The tower
anchorage was also analyzed using PROKON software.
Based on the preceding, the existing 18m 3-legged self-supporting tower is
INADEQUATE to support the current and additional loads of the project. The most
stress member of the tower is the main bracing at panel 7 with demand over the
capacity ratio of 1.98. Nevertheless, tower anchorage and baseplate are ADEQUATE.
The tower is subjected to retrofitting analysis with maximum UR of 82% on horizontal
member. Hence the tower is ADEQUATE.

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

5. RESULT OF EVALUATION OF THE SUPPORTING BUILDING FRAME

The roof deck structural system consists mainly of the concrete member section and
concrete slab carrying the floor loads. The beams are interconnected to the concrete
column sections, thus providing a regular pattern of the beam and column layout. Based
on the analysis, the beams and column directly supporting the antenna supporting
structures have the adequate capacity to support the additional loads of the project and
meets the minimum design requirement for strength and serviceability as specified by
the local code.
Roof beams were evaluated considering the area of reinforcement is not less than the
minimum ACI code requirement and not over the maximum area of reinforcement as
prescribed by the said code. Final assumption of reinforcement shall take into account
that under the original service load, the beam passed the criteria for the allowable
deflection.
The columns were evaluated considering the minimum ACI Code provision having a
steel ratio to the cross-sectional area of the member of not less than 1% and were also

6. CONCLUSION& RECOMMENDATIONS

From the structural investigation of the existing 18m 3-Legged Self-Supporting Tower, it
observed that the tower with retrofitting will be complied with the minimum strength
requirements of the NSCP 2015 (7th Edition) and TIA-222-G.

The existing superstructure needs to be reinforced and modified to comply with the
minimum strength and serviceability requirements by the proponent and related
governing design codes and standards.
Prepared by:

Elizalde S. Cabangon a.asep


Structural Engineer
PRC No : 104270
PTR No : 2429298
Date : 01-08-2019
Place : Plaridel, Bulacan

EFB GEOSTRUKT INC. 
I.B. Design Criteria
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

1. INTRODUCTION 
 
The following presents the structural design criteria, calculations and specifications adopted for the 
investigation of structural adequacy of the existing 18m 3‐Legged Self‐Supporting Tower and its roof 
deck framing system that will support the proposed antenna upgrade of Smart Huawei Project. The 
client,  requested  for  the  assessment  of  existing  structure  in  which  the  scope  includes  a 
comprehensive  structural  analysis  to  assess  the  stability  and  safety  of  the  structure  to  conform  to 
the latest local and international structural codes. 
 
2. CODES AND REFERENCES 
The design shall be in accordance with all the applicable laws and regulations of the Government of 
the  Philippines  and  with  the  applicable  local  codes  and  ordinances.  A  summary  of  the  codes  and 
industry standards to be used in the design shall be as follows: 
Design Codes and Standards 
1. National Structural Code of the Philippines (NSCP), Volume 1 – Buildings, Towers and Other 
Vertical Structures, Seventh Edition 2015 
2. TIA  /  EIA  ‐  222  ‐  STANDARD:  Structural  Standards  for  Steel  Antenna  Towers  and  Antenna 
Supporting Structures. 
3. American Concrete Institute (ACI) Publications: 
a. ACI 318‐11  Building Code Requirement for Structural Concrete 
b. ACI 315‐99  Manual of Standard Practice for Details and Detailing 
c. ACI 301‐96  Specification for Structural Concrete for Buildings 
4. American Institute of Steel Construction (AISC) Publications: 
5. Manual of Steel Construction, Allowable Stress Design, Thirteenth Edition Detailing of Steel 
Construction  
6. American Iron and Steel Institute (AISI) Publication: 
7. Specification for the Design of Cold‐Formed Steel Structural Members  
8. American Society of Civil Engineers/Structural Engineering Institute – Minimum Design Loads 
for Buildings and other structures ASCE/SEI 7 ‐95 
9. Uniform Building Code, UBC 1997 
10. Material Codes and Standards 
11. American Society for Testing & Materials (ASTM) Publication. 
 
Material Codes and Standard 
1. American Society for Testing & Materials (ASTM) Publication. 
2. Association of Structural Engineers of the Philippines (ASEP) Steel Handbook 
 
3. ENGINEERING SOFTWARES 
1. MS Tower V6.20 
2. Prokon2.6.32 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

 
4. MATERIAL STRENGTH 
The material specification and specified design data for structural design and analysis and detailing 
of  concrete  and  steel  members  shall  be  in  accordance  with  the  following  material  strengths 
specified. 

Structural Steel 
Material strength used for structural steel was assumed to be ASTM A36 (248Mpa) for the 
tapered pole and for the rest of tower members and plates. Connection bolts for leg splices 
used were assumed to be ASTM A325 with yield strength of 628 Mpa (91,000 psi). Anchor 
bolts were assumed to be ASTM A490M type. 
 
Concrete 
The  strength  is  in  accordance  with  the  test  method  using  cylinder  type  test  pieces  as 
PNS/ASTM  C39.  The  specified  compressive  strength  (fc)  at  28th  days  age  and  laboratory 
cured shall be as follows: 
  f’c = 21 MPa (3000 psi) for building frame 
Modulus of Elasticity, Ec = 4700 f’c 
Modulus of Rupture, fr = 0.67 f’c 
Reinforcing Steel 
Reinforcing steel shall be deformed and shall meet ASTM A706. The minimum yield strength 
shall be as follows: 
For ø 12 and smaller 
  fy = 275 MPa (40 ksi) 
For ø 16 and larger 
  fy = 414 MPa (60 ksi) 
Modulus of Elasticity, Es = 200,000 MPa 
ASTM A615 (weldable) shall be permitted if: 
a. The actual yield strength based on mill tests does not exceed fy by more than 125 
MPa(retests shall not exceed this value by more than an additional of 21 MPa); and 
b. The ratio of the actual tensile strength  to the actual yield strength is not less than 
1.25. 
5. ACCESS ANTENNAE, MICROWAVE ANTENNAE AND FEEDER LINES WIND LOADINGS 
Access  Antenna:  Based  on  factory  test  results  of  the  specific  antenna  provided  by  the 
supplier/proponent or determination according to NSCP/TIA‐222‐G. 
 
Microwave Antenna: Based on factory test results NSCP/TIA‐222‐G. 
 
For all antennas loading, the following has been considered and included in the structure model. 
1. Actual orientations of the existing antenna including feeder lines. For proposed antenna 
without confirmed orientation, maximum wind forces were used. 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

2. Antenna eccentricities with respect to their mounting frames. 
3. Antenna mounting frames and brackets. 
4. Cable ladder, feeder cables and man ladder were considered as concentrated loads applied 
at levels of supports and/or member joints. 
5. Shielding of antenna to another antenna, feeder cables, structure members were considered 
in accordance with the provisions of TIA‐222‐G. 
 
6. DEAD AND LIVE LOADS 
Minimum dead and live loads. 
Dead Load: For all permanent construction, the dry unit weights shown were used in the 
calculation of the dead loads: 
    Structural Steel       77.00 kN/m3 
    Concrete        24.00 kN/m3 
    Soil          16.00 kN/m3 
    Single 7/8” Feeder Cable    0.05 kN/m3 
    Single 1‐5/8” Feeder Cable    0.13 kN/m3 
    Single 1/2” Feeder Cable    0.025 kN/m3 
 
 
Live Load: For all stages of tower model either live load as a minimum can be applied at 
platforms or where required. 
    Area Live Load        2.40 kN/m2 
    Point Live Load        2.00 kN/ 
7. WIND LOADS 
 
7.1. WIND SPEED 
Site basic wind speed is in accordance to Occupancy Category I Buildings and Other Structures at 
exposure B (Urban and suburban areas, wooded areas). The basic wind speed, V, is 240 KPH. 
The above wind speeds represent three (3) second gust at ten (10) meters above ground level 
corresponding to 0.03 annual probabilities (50‐year recurrence interval). 
 
7.2. TOPOGRAPHIC FACTOR 
Topographic factor, Kzt, shall be as per Figure 207A.8‐1 and 207A.8‐2 of the NSCP. A maximum 
1.25 value shall be used if site data is not available. 
 
7.3. EXPOSURE CATEGORY 
Site exposure category is at C, Kz, per Table 207B.3‐1 of the NSCP. 
 
7.4. WIND DIRECTIONALITY FACTOR 
Wind directionality factor, Kd, shall be 0.85 from Table 207A.5‐1c of the NSCP. 
 

EFB GEOSTRUKT INC. 
978_SINGALONG 
18M 3L‐RT SST 270KPH_B 

 
7.5. HEIGHT COEFFCIENTS 
Exposure coefficients corresponding to heights have been considered Table 207B.3‐1 of the 
NSCP. 
7.6. GUST EFFECT FACTOR 
Gust effect factor, G, shall be 0.85 in accordance with the provisions of TIA‐222‐G and NSCP 
Section 207A.9. 
7.7. WIND DIRECTIONS 
The existing  structure was analyzed at eight wind directions i.e.  0°, 45°, 90°, 135°, 180°, 225°,
270°, and 315°.
 
8. SERVICEABILITY CHECKS 
The  serviceability  performance  of  the  existing  structure  shall  be  analyzed  at  critical  structure 
points particular at tower top and antenna locations. Maximum allowable combined “twist and 
sway” is ±1.0°. 
 
9. TYPE OF ANALYSIS 
The existing structure model is to be analyzed using the Ultimate Strength Design/Load and 
Resistance Factor Design (USD/LRFD) 3rd Edition. Design load combinations per section 2.0 of 
the National Structural Code of the Philippines (NSCP), Volume 1: Buildings, Towers and Other 
Vertical Structures, 7th Edition, 2015. 
 
The following load combinations shall be used. (LRFD) 
 
COMBINATION 1 = 1.4DL 
COMBINATION 2 = 1.2DL + 1.6LL ± 1.0WL 
COMBINATION 3 = 1.2DL ± 1.0WL 
COMBINATION 4 = 1.2DL ± 1.0EQ 
COMBINATION 5 = 0.9DL ± 1.0WL 
COMBINATION 6 = 0.9DL ± 1.0EQ 
Where:   DL  =   Dead Load 
             WL  =   Wind load 
             LL  =   Live load 
             EQ  =   Earthquake loads 
 
10. LOADING SCENARIOS 
The following scenarios were used in the performance analysis of the existing tower. 
 
1. Existing Tower Condition with the current antenna loadings. 
2. Existing Tower Condition with the current and proposed antenna loadings. 
3. Existing Tower Condition with the current, proposed, and future antenna loadings. 
4. Retrofitted Tower Condition with the current, proposed, and future antenna loadings. 

EFB GEOSTRUKT INC. 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 

PHILIPPINE MAP 

 
 
  EFB GEOSTRUKT INC. 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 

270 KPH WIND SPEED 
EXPOSURE B 

 
NSCP 2015 WIND ZONE MAP 

 
 
  EFB GEOSTRUKT INC. 
III. ATTACHMENT 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
978_SINGALONG 
18M 3‐LEGGED RT SST 
 
 
 
 
 
 
  EFB GEOSTRUKT INC. 
 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 
 
TYPICAL ANCHORAGE/PEDESTA 

LEG A 

LEG B 

LEG C 
 
 
  EFB GEOSTRUKT INC. 
 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 
 
TOWER SPLICING 

  

   

 
 
  EFB GEOSTRUKT INC. 
 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 
 
EXISTING ANTENNAS 
 
 
 
   
 
 
 
 
 
   
   
   
     
 
  

 
 
 
 
 
 
 
 
 
 
 
  EFB GEOSTRUKT INC. 
 
978_SINGALONG 
   
18M 3L‐RT SST 270KPH_B 
   
 
 
 
SITE DEVELOPMENT 

    

 
 

 
 
  EFB GEOSTRUKT INC. 
 
Software Download and Licensing Information

Site Information Order Information

EFB GeoStrukt, Inc. Order Number : 44913870


Unit 805 Cityland 10 Tower II, Customer PO Number : Service Request:
H.V. Dela Costa Street, Customer Number : 1002289290
1224 MAKATI CITY Date : 16 DEC 16 16:25
PHILIPPINES

Contact Name : Elizalde Cabangon


Telephone : (63) 2817 0022
Email : elizalde_cabangon@outlook.com

Thank you for your recent purchase of Bentley software!

We understand your continued success depends on efficient deployment of your new software. As such, we have created this web-based
document with instructions for obtaining your Bentley product(s) and license(s).

Export Control:

You acknowledge that these commodities, technology or software are subject to the export control laws, rules, regulations, restrictions and national
security controls of the United States and other agencies or authorities based outside of the United States (the "Export Controls").

You must not export, re-export or transfer, whether directly or indirectly, the commodities, technology or software, or any portion thereof, or any
system containing such commodities, technology or software or portion thereof, without first complying strictly and fully with all Export Controls that
may be imposed on them.

The countries subject to restriction by action of the United States Government or any other governmental agency or authority based outside of the
United States, are subject to change, and it is your responsibility to comply with the applicable United States Government requirements, or those of
any other governmental agency or authority based outside of the United States, as they may be amended from time to time. For additional
information, see http://www.bis.doc.gov

Bentley is subject to the United States Department of the Treasury Office of Foreign Assets Control (OFAC) Sanctions Programs regulations.
Those regulations require Bentley not engage in transactions (1) with designated persons and entities set forth on OFAC's Specially Designated
Nationals List ("SDN List"), see http://www.treasury.gov/ofac/downloads/ctrylst.txt , or (2) where a customer intends to finance a purchase of
Bentley software and/or technology through new debt or equity by or for entities identified on OFAC's Sectoral Sanctions Identifications List ("SSI
List"), see http://www.treasury.gov/ofac/downloads/ssi/ssi_ctrylst.txt. Accordingly, Bentley will not engage in such transactions.

Order Summary:

Item Product Serial Number


10 MStower 30000000279755
Authentication Key: http://appsnet.bentley.com/productdownload/default.aspx?guid=005056A15EFE1ED6B0ED272CAC1A6812
20 MStower Design Code US 30000000279756
Authentication Key: http://appsnet.bentley.com/productdownload/default.aspx?guid=005056A15EFE1ED6B0ED27EC529F2812

Steps To Activating Your Product:

To follow these steps please ensure that you are connected to the internet.

Download And Activate My Bentley Products


Software Download and Licensing Information

- Links to download your recently purchased Bentley Products are provided individually in
the order summary above.

- Launch the downloaded product and enter the information below below into the Product
Activation Wizard:.

Server Name ProductActivation.bentley.com

Site Activation Key DF30D6A1B04A78F1BDFE001422FE5B2E

Bentley Systems International Limited, Second Floor, Block 2, Park Place, Upper Hatch Street, Dublin 2, D02 NP94, Ireland
VAT # IE 9729353D Tel.: +353 (1) 436 4600 Fax.:+353 (1) 416 1261 Email: asia.Orders@bentley.com
http://www.bentley.com/contact
Directors: Heidi Koston, Gabriel Keating, Damien Mulligan
Software Download and Licensing Information

Additional Notes

1. For additional product activation assistance, please click here:


www.bentley.com/activate
2. SELECTServices Online Login and Password information:
- If you know your email address and want to know your password (or have forgotten your
password), click here: http://www.bentley.com/forgotpassword/
3. Obtain Information on becoming a SELECT subscriber click here
www.bentley.com/en-US/Services/Bentley+SELECT
4. Electronic Help Documentation is included with the download of each product.
5. To obtain further Technical support for your products:
- click here: http://www.bentley.com/servicerequestmanager/

Thank you for choosing Bentley Systems. Please do not hesitate to contact your Account Manager or Bentley representative in your local Bentley
office should you have any questions about this document.

Yours Sincerely,

Bentley Systems Inc.


Web: http://www.bentley.com/licensing

Bentley Systems International Limited, Second Floor, Block 2, Park Place, Upper Hatch Street, Dublin 2, D02 NP94, Ireland
VAT # IE 9729353D Tel.: +353 (1) 436 4600 Fax.:+353 (1) 416 1261 Email: asia.Orders@bentley.com
http://www.bentley.com/contact
Directors: Heidi Koston, Gabriel Keating, Damien Mulligan
Invoice
Page 1 of 2

Bill to party Summary


Invoice Number 47893147
EFB Geostrukt, Inc. (Projects Div) Invoice Date 08/02/2018
H.V. Dela Costa Street, PO Number SIGNED CSS ORDER
Unit 805 Cityland 10 Tower II, Customer Number 1005058253
1224 Makati City, Philippines Currency USD

Remittance Information Cloud Services Subscription Period 01/02/2018 - 31/01/2019


Payment Terms: Net 30 Days
Account holder: Bentley Systems International Ltd Please reference your customer and invoice number with your
Bank: Deutsche Bank A.G., The Netherlands payment.
SWIFT/BIC: DEUTNL2A CSS : 0104830122
IBAN: NL26 DEUT 0265 0477 65

Intermediary Bank: Deutsche Bank Trust, USA


SWIFT/BIC: BKTRUS33 VAT Identification Number

Only payment by electronic transfer

Item Description Qty Total


10 Cloud Services Subscription Voucher 1 7,000.00

Total Amount 7,000.00


Total Invoice Amount 7,000.00

Bentley Systems International Limited, Second Floor, Block 2, Park Place, Upper Hatch Street, Dublin 2, Ireland
VAT # IE 9729353D Tel.: +353 (1) 436 4600 Fax.:+353 (1) 416 1261 Email: asia.Orders@bentley.com
http://www.bentley.com/contact
Directors: Heidi Koston, Gabriel Keating, Damien Mulligan
Details
Page 2 of 2

Invoice Number 47893147

Ship to:
EFB Geostrukt, Inc. (Projects Div)
H.V. Dela Costa Street,
Unit 805 Cityland 10 Tower II,
1224 Makati City, Philippines

Description Qty Unit Price Gross Price Discount/Surcharge Total


Cloud Services Subscription Voucher
01/02/2018 - 31/01/2019 1 7,000.00 7,000.00 0.00 7,000.00
Site Total 7,000.00

All products and/or SELECT Program subscriptions set forth herein shall be delivered pursuant to the terms of your Bentley SELECT Program
Agreement and/or Bentley End User License Agreement as applicable. Any additional or different terms or conditions shall not be binding on the parties
and shall not apply.

Export Control:

You acknowledge that these commodities, technology or software are subject to the export control laws, rules, regulations, restrictions and national
security controls of the United States and other agencies or authorities based outside of the United States (the "Export Controls").

You must not export, re-export or transfer, whether directly or indirectly, the commodities, technology or software, or any portion thereof, or any system
containing such commodities, technology or software or portion thereof, without first complying strictly and fully with all Export Controls that may be
imposed on them.

The countries subject to restriction by action of the United States Government or any other governmental agency or authority based outside of the
United States, are subject to change, and it is your responsibility to comply with the applicable United States Government requirements, or those of any
other governmental agency or authority based outside of the United States, as they may be amended from time to time. For additional information, see
http://www.bis.doc.gov

Bentley is subject to the United States Department of the Treasury Office of Foreign Assets Control (OFAC) Sanctions Programs regulations. Those
regulations require Bentley not engage in transactions (1) with designated persons and entities set forth on OFAC's Specially Designated Nationals List
("SDN List"), see http://www.treasury.gov/ofac/downloads/ctrylst.txt , or (2) where a customer intends to finance a purchase of Bentley software and/or
technology through new debt or equity by or for entities identified on OFAC's Sectoral Sanctions Identifications List ("SSI List"), see
http://www.treasury.gov/ofac/downloads/ssi/ssi_ctrylst.txt. Accordingly, Bentley will not engage in such transactions.

Bentley Systems International Limited, Second Floor, Block 2, Park Place, Upper Hatch Street, Dublin 2, Ireland
VAT # IE 9729353D Tel.: +353 (1) 436 4600 Fax.:+353 (1) 416 1261 Email: asia.Orders@bentley.com
http://www.bentley.com/contact
Directors: Heidi Koston, Gabriel Keating, Damien Mulligan

You might also like