You are on page 1of 10

PRELIMINARY - NOT

FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\1. 138KV_13820-13825_13811_WOOD POLE


H-FRAME\1.138KV_13820-13825_13811_WOOD POLE H-FRAME.DWG 1/3/2014 4:13 PM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\2. 230KV_DOUBLE CIRCUIT_LATTICE STEEL TOWER\2.230KV_DOUBLE


CIRCUIT_LATTICE STEEL TOWER.DWG 1/3/2014 1:04 PM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\3. 230KV_DOUBLE CIRCUIT_TUBULAR STEEL POLE\3.230KV_DOUBLE


CIRCUIT_TUBULAR STEEL POLE.DWG 1/3/2014 10:38 AM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\4. 138KV_(13804) WOOD POLE H-FRAME\4.138KV_(13804) WOOD POLE


H-FRAME.DWG 1/3/2014 10:38 AM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\5. 69KV_WOOD POLE H-FRAMES\5.69KV_WOOD POLE H-FRAMES.DWG 1/3/2014


10:38 AM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\6. 230KV_DOUBLE CIRCUIT TUBULAR STEEL POLE\6.230KV_DOUBLE CIRCUIT


TUBULAR STEEL POLE.DWG 1/3/2014 10:39 AM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\7. 69KV_DOUBLE CIRCUIT TUBULAR STEEL POLE\7.69KV_DOUBLE CIRCUIT


TUBULAR STEEL POLE.DWG 1/3/2014 10:39 AM KCORBETT
PRELIMINARY - NOT
FOR CONSTRUCTION
2014

\\BRE-FPS-001\DATA\USERS\KCORBETT\SDG&E\8. 230KV_DOUBLE CIRCUIT UNDERGROUND CABLE POLE\8.230KV_DOUBLE


CIRCUIT UNDERGROUND CABLE POLE.DWG 1/3/2014 10:39 AM KCORBETT
THERMAL DUCTBANK
CONCRETE ENVELOPE
5'-0" MAX (TYP) FIRST POUR
QUAD 2" SECOND POUR
DUCT
12" 8"
MIN MIN
8" SCH 40 PVC
CONDUIT (TYP) MATCH EXISTING A.C. PAVEMENT THICKNESS
SAWCUT EXISTING A.C. PAVEMENT
SEE TRENCH RESURFACING PER
G24-A, COUNTY OF SAN DIEGO
DIRECTION OF 45° STANDARD DRAWINGS EXISTING A.C. PAVEMENT EXISTING DIRT SURFACE
CABLE PULL

6" MIN.
NATIVE SOIL, 90%
RELATIVE COMPACTION
12" CONSTRUCTION JOINT 18"
CONDUIT SPACER
MIN
PLASTIC WARNING PLASTIC WARNING
UTILITY GRADE BELL END (SEE NOTE 14) TAPE (TYP 2 PLCS)
REBAR (IF REQ'D TO TAPE (TYP 2 PLCS)
STABILIZE SPACERS) FLOWABLE THERMAL
FLOWABLE THERMAL
TYPICAL COUPLING DETAIL BACKFILL (FTB)
BACKFILL (FTB)
FOR DUCT BANK VARIES VARIES PLASTIC SHEET TO SERVE AS
PLASTIC SHEET TO SERVE AS
DETAIL A (3' MIN)
NON-BONDING AGENT BETWEEN
(3' MIN) NON-BONDING AGENT BETWEEN
(FOR CLARITY, GND RETURN CONDUCTOR IS NOT SHOWN) DUCT BANK CONCRETE AND FTB.
DUCT BANK CONCRETE AND FTB.
NOT TO SCALE QUAD 2" DUCT
QUAD 2" DUCT 2 - GROUNDING CONDUIT
2 - GROUNDING CONDUIT FOR INSULATED 4/0
FOR INSULATED 4/0 AWG CONTINUITY & 2 F.O.
AWG CONTINUITY & 2 F.O.
SAWCUT EXISTING A.C. PAVEMENT HOLD DOWN BAR W/ ANCHORS
HOLD DOWN BAR W/ ANCHORS @ 5' SPACING. ANCHOR DEPTH
MATCH EXISTING AC PAVEMENT THICKNESS @ 5' SPACING. ANCHOR DEPTH WILL VARY DEPENDING ON SOIL
SEE TRENCH RESURFACING PER WILL VARY DEPENDING ON SOIL CONDITIONS
G24-A, COUNTY OF SAN DIEGO CONDITIONS
STANDARD DRAWINGS EXISTING A.C. PAVEMENT 11 7/16" 11 7/16" 8" SCH 40 PVC CONDUIT
8" SCH 40 PVC CONDUIT (TYP 8 PLCS)
CL
(TYP 8 PLCS)
A1 S1 C2 A1 S1 C2
6" MIN. TAPE-WARNING U/G THERMAL DUCTBANK
CABLE TX 2417 10 5/8" CONCRETE 10 5/8" THERMAL DUCTBANK
FLOWABLE THERMAL 3'-4" 3'-4" CONCRETE
BACKFILL (FTB) B1 B2 CONDUIT SPACER @ 5' B1 B2
SPACING (TYP) (UNDERGROUND
VARIES PLASTIC SHEET TO SERVE AS 10 5/8" DEVICES, INC. 8W20-3) 10 5/8" CONDUIT SPACER @ 5'
(3' MIN) NON-BONDING AGENT BETWEEN SPACING (TYP) (UNDERGROUND
DUCT BANK CONCRETE AND FTB. C1 S2 A2 C1 S2 A2 DEVICES, INC. 8W20-3)
THERMAL DUCTBANK 7 5/16" 7 5/16"
CONCRETE
CONDUIT SPACER @ 5' NOTE: SPARE CONDUIT
SPACING (TYP) (UNDERGROUND DENOTED AS "S"
4-#4 10 5/8" 4-#4 10 5/8" NOTE: SPARE CONDUIT
DEVICES, INC. 8W20-3)
TYP TYP DENOTED AS "S"
9 5/16" 8" SCH 40 PVC CONDUIT 8 3/8" 1'-9 1/4" 8 3/8" 8 3/8" 1'-9 1/4" 8 3/8"
1'-4 5/8" (TYP 8 PLCS)
A1 B1 C1 S1 S2 C2 B2 A2 3'-2"
3'-2"
7 5/16"

QUAD 2" DUCT


DUCT BANK DETAIL 1 DUCT BANK DETAIL 2
6-#4
NOTE: SPARE CONDUIT
10 1/8" 10 5/8"
2 - GROUNDING CONDUIT
10 1/8" DENOTED AS "S"
PAVEMENT SECTION DIRT SURFACE (ROW SECTION)
FOR INSULATED 4/0 NOT TO SCALE
TYP NOT TO SCALE
AWG CONTINUITY & 2 F.O.
8'-9 1/4"

DUCT BANK DETAIL 5


SAWCUT EXISTING A.C. PAVEMENT
SIX CABLES IN EIGHT INCH CONDUIT (HORZ.)
MATCH EXISTING A.C. PAVEMENT THICKNESS
PAVEMENT SECTION AREA EXISTING A.C. PAVEMENT
NOT TO SCALE SEE TRENCH RESURFACING PER
SAWCUT EXISTING A.C. PAVEMENT G24-A, COUNTY OF SAN DIEGO
SEE TRENCH RESURFACING PER STANDARD DRAWINGS EXISTING A.C. PAVEMENT
G24-A, COUNTY OF SAN DIEGO
STANDARD DRAWINGS
EXISTING NATIVE MATCH EXISTING A.C. PAVEMENT 6" MIN.
SOIL GROUND THICKNESS
CL CL

PLASTIC WARNING
NATIVE SOIL, 90% 6" MIN. TAPE (TYP 2 PLCS)
RELATIVE COMPACTION

18" FLOWABLE THERMAL


TAPE-WARNING U/G TAPE-WARNING U/G BACKFILL (FTB)
CABLE TX 2417 CABLE TX 2417
79.71'
3'-0" MIN. PLASTIC SHEET TO SERVE AS
FLOWABLE THERMAL FLOWABLE THERMAL NON-BONDING AGENT BETWEEN
VARIES VARIES A1,B1,C1 A1
BACKFILL (FTB) BACKFILL (FTB) DUCT BANK CONCRETE AND FTB. B1
(3' MIN) (3' MIN) C1
S1
PLASTIC SHEET TO SERVE PLASTIC SHEET TO SERVE S2
AS NON-BONDING AGENT AS NON-BONDING AGENT C2,B2,A2 C2
B2
A2
HOLD DOWN BAR W/ ANCHORS
HOLD DOWN BAR W/ ANCHORS HOLD DOWN BAR W/ ANCHORS
@ 5' SPACING. ANCHOR DEPTH 400'R, TYP.
@ 5' SPACING. ANCHOR DEPTH @ 5' SPACING. ANCHOR DEPTH
WILL VARY DEPENDING ON SOIL
WILL VARY DEPENDING ON SOIL WILL VARY DEPENDING ON SOIL
CONDITIONS
CONDITIONS 11 7/16" CONDITIONS 11 7/16" PLAN
THERMAL DUCTBANK
2-2" DUCT 2-2" DUCT 400'R, TYP.
A1 A1 CONCRETE
1 - GROUNDING CONDUIT 1 - GROUNDING CONDUIT C2 C2,B2,A2
FOR INSULATED 4/0 FOR INSULATED 4/0 11 7/16" B2
CONDUIT SPACER @ 5' A2
AWG CONTINUITY & 1 F.O. AWG CONTINUITY & 1 F.O.
3'-4" 3'-4" A1 S1 C2 B2 SPACING (TYP) (UNDERGROUND
B1 S1 B1 S1 DEVICES, INC. 8W20-3) 53.20'
2'-5 3/8"
10 5/8"
10 5/8" (TYP) CONDUIT SPACER @ 5' 10 5/8" (TYP) CONDUIT SPACER @ 5' QUAD 2" DUCT
SPACING (TYP 6 PLCS) SPACING (TYP 6 PLCS) 2 - GROUNDING CONDUIT
B1 C1 S2 A2
C1 (UNDERGROUND DEVICES, C1 (UNDERGROUND DEVICES, FOR INSULATED 4/0 ELEVATION RIGHT
INC. 8W20-3) INC. 8W20-3) 7 5/16" AWG CONTINUITY & 2 F.O.
7 5/16" 7 5/16"
400'R, TYP.
8" SCH 40 PVC CONDUIT A1 A1,B1,C1
THERMAL DUCTBANK 4-#4 THERMAL DUCTBANK 4-#4 (TYP 8 PLCS) B1
C1
CONCRETE CONCRETE 4-#4
2'-4 5/8" 2'-4 5/8" 8 3/8" 10 5/8" 10 5/8" 10 5/8" 10 5/8" 8 3/8"
8" SCH 40 PVC CONDUIT 8" SCH 40 PVC CONDUIT 53.20'
NOTE: SPARE CONDUIT
(TYP 4 PLCS) (TYP 4 PLCS)
NOTE: SPARE CONDUIT NOTE: SPARE CONDUIT DENOTED AS "S"
DENOTED AS "S" DENOTED AS "S" 4'-11 1/4" ELEVATION LEFT

DUCT BANK DETAIL 3 DUCT BANK DETAIL 4


DUCT BANK TRANSITION DETAIL
NOT TO SCALE
3 CABLES IN EIGHT INCH CONDUIT (VERTICAL) 3 CABLES IN EIGHT INCH CONDUIT (VERTICAL) DUCT BANK DETAIL 7
DIRT SURFACE (ROW SECTION) PAVEMENT (ROW SECTION) PAVEMENT SECTION
NOT TO SCALE NOT TO SCALE NOT TO SCALE

CARMEL VALLEY ROAD


SCALE: AS SHOWN
-
15070 AVENUE OF SCIENCE, SUITE 100 SAN DIEGO, CA. 92128
858.385.0500 TEL 858.385.0400 FAX WWW.NV5.COM CONST CONST
TRENCH SECTION DETAILS
REV BUDGET CHANGE DRAWN CHK'D APPV'D DATE REV BUDGET CHANGE DRAWN CHK'D APPV'D DATE
ORDER ORDER
230XX 1 - 1 UG1
2 3
CONTINUOUS CHANNEL INSERT
- - EMBEDDED FLUSH WITH SURFACE,
ADD 2" DIA. KNOCKOUT FOR 24'-0" HOT DIPPED GALVANIZED (TYP 4 2" SCH 40 PVC CONDUIT
GROUND CONNECTION PLCS, 2 OPPOSITE FACE) ENTRANCE FOR CONTINUITY
(TYP 2 PLCS) CONDUCTOR (TYP 4 PLCS)
2" 2" DEEP RECESS IN
CONDUIT 4" KNOCKOUT MANHOLE END WALL FOR ADD 2" DIA. KNOCKOUT FOR GROUND
(TYP) C
L MANHOLE
ENTRANCES, (TYP 2 PLCS) DUCT CONCRETE. CONNECTION ON EACH SIDE. PLACE 6"

(MIN)
2'-6"
SEE NOTE 3 (TYP 2 PLCS) FROM SIDE WALL & 6" BELOW CEILING FOR

(TYP)
(SEE NOTE 15) 4/0 CONTINUITY CONDUCTOR EXIT. (TYP)

12"
CONTINUOUS CHANNEL INSERT

1'-7 1/2"
SLO

SL
SUMP PIT, SEE PE

TYP

(TYP)
PE

1'-6"
SLO

E
OP
EMBEDDED FLUSH WITH CEILING

OP

(TYP)
DETAIL A (TYP

SL

6"
2 PLCS) SURFACE (TYP 4 PLCS)

4'-0" (TYP)
PULLING IRON EMBEDDED 1'-8"
IN CONCRETE, SEE DETAIL 4" KNOCKOUT

2'-4 1/2"
B (TYP) (TYP 2 PLCS)
1 1
- - MANHOLE SECTION JOINT WITH

10'-0"

1'-8"
SEALANT, TYP. CON SEAL, 1'-8"

8'-0"
RAM-NEK SEALANT OR

(TYP)
CL MANHOLE

1'-6"

5'-6"
APPROVED EQUAL.
LADDER RUNG

1'-8"
VAULT NECKING AND
(TYP 2 PLCS)
COVER (PRECAST PART

1'-8"
NUMBER 3332) MANHOLE ENTRANCES
(TYP 2 PLCS)

1'-7 1/2"
1'-6"

1'-9"
NOTE: REMOVAL OF

2'-1 1/2"
(TYP)

1'-7 1/2"
SL
TRAFFIC COVER IS 3'-6" 3'-6" 10" 10"

OP
E

REQUIRED FOR MANHOLE

E
6'-0"
OP

OPENING SLO
PE PE
SLO
SL

ENTRANCE (TYP) 8" SCH 40 PVC


CONDUIT ENTRANCE
(TYP 16 PLCS)
LIFTING LUG RECESSED INTO PULLING IRON, TYP
SURFACE, SEE NOTE 4 (TYP 4 (SEE DETAIL B)
10'-0"
PLCS, TOP, BOTTOM & WALL
SECTIONS) 2 PLAN VIEW 3
- STANDARD MANHOLE - SECTION 2
SCALE: 3/8"=1'-0" SCALE: 3/8"=1'-0"

2" CONDUIT
TERMINATOR CAST
INTO MANHOLE END
12'-0" WALL (TYP 4 PLCS) ADD 2" DIA. KNOCKOUT FOR GROUND
(TYP) CONNECTION ON EACH SIDE. PLACE 6"
C
L MANHOLE
NOTE 5

FROM SIDE WALL & 6" BELOW CEILING FOR


SEE

MANHOLE LID AND FRAME FOR


4/0 CONTINUITY CONDUCTOR EXIT. (TYP)
42" DIA OPENING WITH MINIMUM
8" TRAFFIC COVER (TYP 2 PLCS) 2 SECURITY BOLTS FOR
FASTENING (TYP 2 PLCS)
12" NECKING (TYP 2 PLCS)
2" DEEP x 9'-0" x 5'-4" INDENT
(MIN)

LADDER RUNG
2'-6"

6" INTER SECTION (TYP 2 PLCS) ON OUTSIDE WALL AROUND


(TYP 2 PLCS) 2'-7 1/2"
ENDBELLS (TYPICAL 2 PLCS) 1'-7 1/2"
12" INTER SECTION (TYP 2 PLCS) (TYP) 2'-1 1/2" 4" KNOCKOUT
(SEE NOTE 14)
(TYP 2 PLCS)
7"

1'-8"
1'-10" 4'-0"

8'-0"
1'-9"
TYP

(TYP) (TYP)
MANHOLE SECTION JOINT WITH
RAM-NEK SEALANT. (JOINT

1'-8"
4" KNOCKOUT
LOCATION AND QUANTITY TO
BE DETERMINED BY MANHOLE
SUPPLIER)

1'-8"
LIFTING LUG RECESSED INTO

1'-9"
8'-0"
SURFACE, SEE NOTE 4 (TYP 4
PLCS, TOP, BOTTOM & WALL
SECTIONS)

1'-8"
8" SCH 40 PVC
#10 REIFORCING BAR, 36" CONDUIT ENTRANCE
LONG, EMBEDDED 6" INTO (TYP 16 PLCS)
OUTER FACE OF MANHOLE 10'-0"
1'-9"
ENDWALL FOR DUCT BANK
INTERFACE. TO BE
INSERTED AT TIME OF
(TYP)
12"

MANHOLE INSTALLATION. SECTION 3


(TYP 12 PLCS)
SCALE: 3/8"=1'-0"

TYP A
2 PLCS -
24'-0" 3'X5' COMM. VAULT CL MANHOLE CONCRETE ENCASED
MH NECKS
SECTION 1 2-2" CONDUITS FOR COMM.
FIBER CABLE
SCALE: 3/8"=1'-0"

2-2" CONDUITS FOR COMM.


FIBER CABLE

PULLING IRON PIT GALVANIZED STEEL BAR


DESIGNED TO WITHSTAND
1'-5 1/2" DIA 20,000LB PULL-OUT FORCE 2-2" CONDUITS FOR GCC 2-2" CONDUITS FOR GCC
1'-4" DIA
(MIN)

CONCRETE GALVANIZED REBAR AS


2"

GRATING NECESSARY
8" CONDUITS 8" CONDUITS
(MIN)
2"
(MIN)
3/4"

8"

(MIN)

3"
4"

(MIN, TYP)
CONCRETE
3/4"

DETAIL A DETAIL B DETAIL D


SUMP PIT DETAIL PULLING IRON DETAIL (SEE NOTE 2) COMM. FIBER CABLE DETAIL
SCALE: 1-1/2"=1'-0" SCALE: 1-1/2"=1'-0" SCALE: 3/8"=1'-0"

CARMEL VALLEY ROAD


SCALE: AS SHOWN
-
15070 AVENUE OF SCIENCE, SUITE 100 SAN DIEGO, CA. 92128
858.385.0500 TEL 858.385.0400 FAX WWW.NV5.COM CONST CONST
TRENCH SECTION DETAILS
REV BUDGET CHANGE DRAWN CHK'D APPV'D DATE REV BUDGET CHANGE DRAWN CHK'D APPV'D DATE
ORDER ORDER
230XX 1 - 1 MH