FOR CONSTRUCTION
2014
6" MIN.
NATIVE SOIL, 90%
RELATIVE COMPACTION
12" CONSTRUCTION JOINT 18"
CONDUIT SPACER
MIN
PLASTIC WARNING PLASTIC WARNING
UTILITY GRADE BELL END (SEE NOTE 14) TAPE (TYP 2 PLCS)
REBAR (IF REQ'D TO TAPE (TYP 2 PLCS)
STABILIZE SPACERS) FLOWABLE THERMAL
FLOWABLE THERMAL
TYPICAL COUPLING DETAIL BACKFILL (FTB)
BACKFILL (FTB)
FOR DUCT BANK VARIES VARIES PLASTIC SHEET TO SERVE AS
PLASTIC SHEET TO SERVE AS
DETAIL A (3' MIN)
NON-BONDING AGENT BETWEEN
(3' MIN) NON-BONDING AGENT BETWEEN
(FOR CLARITY, GND RETURN CONDUCTOR IS NOT SHOWN) DUCT BANK CONCRETE AND FTB.
DUCT BANK CONCRETE AND FTB.
NOT TO SCALE QUAD 2" DUCT
QUAD 2" DUCT 2 - GROUNDING CONDUIT
2 - GROUNDING CONDUIT FOR INSULATED 4/0
FOR INSULATED 4/0 AWG CONTINUITY & 2 F.O.
AWG CONTINUITY & 2 F.O.
SAWCUT EXISTING A.C. PAVEMENT HOLD DOWN BAR W/ ANCHORS
HOLD DOWN BAR W/ ANCHORS @ 5' SPACING. ANCHOR DEPTH
MATCH EXISTING AC PAVEMENT THICKNESS @ 5' SPACING. ANCHOR DEPTH WILL VARY DEPENDING ON SOIL
SEE TRENCH RESURFACING PER WILL VARY DEPENDING ON SOIL CONDITIONS
G24-A, COUNTY OF SAN DIEGO CONDITIONS
STANDARD DRAWINGS EXISTING A.C. PAVEMENT 11 7/16" 11 7/16" 8" SCH 40 PVC CONDUIT
8" SCH 40 PVC CONDUIT (TYP 8 PLCS)
CL
(TYP 8 PLCS)
A1 S1 C2 A1 S1 C2
6" MIN. TAPE-WARNING U/G THERMAL DUCTBANK
CABLE TX 2417 10 5/8" CONCRETE 10 5/8" THERMAL DUCTBANK
FLOWABLE THERMAL 3'-4" 3'-4" CONCRETE
BACKFILL (FTB) B1 B2 CONDUIT SPACER @ 5' B1 B2
SPACING (TYP) (UNDERGROUND
VARIES PLASTIC SHEET TO SERVE AS 10 5/8" DEVICES, INC. 8W20-3) 10 5/8" CONDUIT SPACER @ 5'
(3' MIN) NON-BONDING AGENT BETWEEN SPACING (TYP) (UNDERGROUND
DUCT BANK CONCRETE AND FTB. C1 S2 A2 C1 S2 A2 DEVICES, INC. 8W20-3)
THERMAL DUCTBANK 7 5/16" 7 5/16"
CONCRETE
CONDUIT SPACER @ 5' NOTE: SPARE CONDUIT
SPACING (TYP) (UNDERGROUND DENOTED AS "S"
4-#4 10 5/8" 4-#4 10 5/8" NOTE: SPARE CONDUIT
DEVICES, INC. 8W20-3)
TYP TYP DENOTED AS "S"
9 5/16" 8" SCH 40 PVC CONDUIT 8 3/8" 1'-9 1/4" 8 3/8" 8 3/8" 1'-9 1/4" 8 3/8"
1'-4 5/8" (TYP 8 PLCS)
A1 B1 C1 S1 S2 C2 B2 A2 3'-2"
3'-2"
7 5/16"
PLASTIC WARNING
NATIVE SOIL, 90% 6" MIN. TAPE (TYP 2 PLCS)
RELATIVE COMPACTION
(MIN)
2'-6"
SEE NOTE 3 (TYP 2 PLCS) FROM SIDE WALL & 6" BELOW CEILING FOR
(TYP)
(SEE NOTE 15) 4/0 CONTINUITY CONDUCTOR EXIT. (TYP)
12"
CONTINUOUS CHANNEL INSERT
1'-7 1/2"
SLO
SL
SUMP PIT, SEE PE
TYP
(TYP)
PE
1'-6"
SLO
E
OP
EMBEDDED FLUSH WITH CEILING
OP
(TYP)
DETAIL A (TYP
SL
6"
2 PLCS) SURFACE (TYP 4 PLCS)
4'-0" (TYP)
PULLING IRON EMBEDDED 1'-8"
IN CONCRETE, SEE DETAIL 4" KNOCKOUT
2'-4 1/2"
B (TYP) (TYP 2 PLCS)
1 1
- - MANHOLE SECTION JOINT WITH
10'-0"
1'-8"
SEALANT, TYP. CON SEAL, 1'-8"
8'-0"
RAM-NEK SEALANT OR
(TYP)
CL MANHOLE
1'-6"
5'-6"
APPROVED EQUAL.
LADDER RUNG
1'-8"
VAULT NECKING AND
(TYP 2 PLCS)
COVER (PRECAST PART
1'-8"
NUMBER 3332) MANHOLE ENTRANCES
(TYP 2 PLCS)
1'-7 1/2"
1'-6"
1'-9"
NOTE: REMOVAL OF
2'-1 1/2"
(TYP)
1'-7 1/2"
SL
TRAFFIC COVER IS 3'-6" 3'-6" 10" 10"
OP
E
E
6'-0"
OP
OPENING SLO
PE PE
SLO
SL
2" CONDUIT
TERMINATOR CAST
INTO MANHOLE END
12'-0" WALL (TYP 4 PLCS) ADD 2" DIA. KNOCKOUT FOR GROUND
(TYP) CONNECTION ON EACH SIDE. PLACE 6"
C
L MANHOLE
NOTE 5
LADDER RUNG
2'-6"
1'-8"
1'-10" 4'-0"
8'-0"
1'-9"
TYP
(TYP) (TYP)
MANHOLE SECTION JOINT WITH
RAM-NEK SEALANT. (JOINT
1'-8"
4" KNOCKOUT
LOCATION AND QUANTITY TO
BE DETERMINED BY MANHOLE
SUPPLIER)
1'-8"
LIFTING LUG RECESSED INTO
1'-9"
8'-0"
SURFACE, SEE NOTE 4 (TYP 4
PLCS, TOP, BOTTOM & WALL
SECTIONS)
1'-8"
8" SCH 40 PVC
#10 REIFORCING BAR, 36" CONDUIT ENTRANCE
LONG, EMBEDDED 6" INTO (TYP 16 PLCS)
OUTER FACE OF MANHOLE 10'-0"
1'-9"
ENDWALL FOR DUCT BANK
INTERFACE. TO BE
INSERTED AT TIME OF
(TYP)
12"
TYP A
2 PLCS -
24'-0" 3'X5' COMM. VAULT CL MANHOLE CONCRETE ENCASED
MH NECKS
SECTION 1 2-2" CONDUITS FOR COMM.
FIBER CABLE
SCALE: 3/8"=1'-0"
GRATING NECESSARY
8" CONDUITS 8" CONDUITS
(MIN)
2"
(MIN)
3/4"
8"
(MIN)
3"
4"
(MIN, TYP)
CONCRETE
3/4"