Capacitor VoltageTransformer
Transformer type
type CPA
CPA / CPB
System voltage 72.5 - 550 kV
Installation Outdoor
Voltage Transformers type CPA and CPB
ABBs capacitor voltage transfor- Electromagnetic Unit
mers (CVT:s) and coupling capa-
A capacitor voltage transformer with an electromagnetic
citors are intended for connection unit (EMU), type EOA is called CPA and with an electro-
between phase and ground in net- magnetic unit (EMU), type EOB is called CPB. The design
of the EOA and EOB is basically identical, however the
works with isolated or earthed EOB has a larger tank and core, with space for larger
neutral. windings, therefore it’s capable of withstanding higher
burdens.
The design corresponds to the requirements of IEC and The voltage divider and the transformer are connected by
all national standards based on IEC. Special designs to internal bushings, which is necessary for applications with
meet other standards and customer specifications are also high accuracy.
available.
Due to the design of the capacitor elements, described The EMU has double enamelled copper windings and
below, CPA and CPB are, with regard to temperature an iron core, made of high quality steel sheet and is oil
stability and accuracy equivalent to inductive voltage trans- insulated in a hermetically sealed aluminium tank with
formers. standard transformer oil.
Capacitior Voltage Divider The primary coil is divided into a main winding, and a
set of trimming windings available externally. The nominal
The capacitor voltage divider (CVD) consists of one or intermediate voltage is approx. 22/√3 kV.
two capacitor units, assembled on top of each other. Each
unit contains a large number of series connected, oil insu- EOA and EOB have a reactor, which is connected in
lated capacitor elements. The units are completely filled series between the voltage divider and the high voltage
with the syntetic oil, which is kept under a slight overpres- end of the primary winding. This reactor compensates for
sure by the design of the expansion system. O-ring seals the shift in phase angle caused by the capacitive voltage
are used throughout our design. divider. The capacitive and inductive reactances are tuned
individually on each transformer before accuracy testing.
The capacitor elements are designed with respect to the
demands made by revenue metering, and their active part For special applicationes, HVDC stations, metering of har-
consists of aluminium foil, insulated with paper / poly- monics etc. there is another type of EMU available, the
propylene film, impregnated by a PCB-free synthetic oil, EOAL. EOAL is basically an EOA but without a separate
which has better insulating properties than normal mineral compensating reactor. In the EOAL the compensating
oil. Due to it’s unique proportions between paper and reactor and transformer is combined into one piece which
polypropylene film, this dielectric has proven itself virtu- gives several advantages.
ally insensitive to temperature changes. The useful frequency range is wider since the internal
resonance frequency of the EMU is higher than for an
Our standard voltage divider, type designation CSA (high EOA or EOB. The already excellent tranisent response of
capacitance) or CSB (extra high capacitance) is mounted the EOA and EOB is improved even further.
on an electromagnetic unit (EMU), making up a complete However the EOAL is limited to burdens lower than the
capacitor voltage transformer. EOA.
A coupling capacitor (without an EMU) is called CCA
(high capacitance) or CCB (extra high capacitance).
222
2
Advantages of the CPA and CPB
Climate 4
These transformers are designed for, and have been instal-
led in widely varying conditions, from Arctic to desert
climate, on every continent. 1
Ferroresonance
The low induction (0.35-0.45 T at rated voltage), combi-
ned with an efficient damping circuit, gives a safe and
stable damping of ferroresonance at all frequencies and
voltages up to rated voltage factor, see page 4.
Life Time 2
The low voltage stress within the capacitor elements ensu-
res a safe product with a long lifetime. 3
6 5
Transient properties
The high intermediate voltage and high capacitance result
in transient properties that are far better than required by 7
current international standards.
8 12
Adjustment 9
The adjustment windings for ratio adjustment are acces-
sible in the terminal box, and can thus be used by the 10
customer to optimise the accuracy, as described on page 4.
11
Power Line Carrier
CPA and CPB have the compensating reactor connected
on the high voltage side of the primary winding, resulting Capacitor Voltage Divider CSA or CSB
in the possibility of using also higher frequencies (> 400
kHz) for power line carrier transmission.
1 Expansion system
2 Capacitor elements
3 Intermediate voltage bushing
Stray Capacitance 4 Primary terminal, flat 4 hole Al-pad
The design with the compensating reactor on the high 5 Low voltage terminal
voltage side of the main winding ensures less than 200 pF (for carrier frequency use)
stray capacitance, which is the most stringent requirement
in the IEC standard for carrier properties.
Electromagnetic unit EOA or EOB
233
Design properties
All external metal surfaces consist of an aluminium alloy, The transformer of the electromagnetic unit has five
resistant to most known environment factors. Bolts, nuts adjustment windings on the earth side of the primary
etc. are made of acid-proof steel. The aluminium surfaces winding. The numbers of turns of these windings have
do not normally need painting. We can, however, offer a been chosen so that the ratio can be adjusted ±6.05% in
protective paint standard, which is light greyish. steps of 0.05%. These windings are externally available in
the secondary terminal box. The CVT is delivered adjusted
Creepage distance for specified burden and class, and normally no further
adjustment is necessary. If needed, the adjustment win-
dings can also be used to extend or improve the accuracy
As standard, CPA and CPB are offered with creepage of the CVT, for example:
distance ≥ 25 mm/kV. Longer creepage distance can be
offered on request. - To maintain or improve the accuracy for a burden range
differing from the rated one.
Silicone rubber insulators
- To minimise the ratio error for a known, fixed burden
The complete ranges of CVT and CC are available with to less than 0.025%.
silicone rubber insulators (SiR). Our SiR insulators are
produced with a patented helical extrusion moulding tech- - To enable exchange of the voltage divider on site, and
nique, which gives completely joint free insulators with readjust the transformer for the new combination of vol-
outstanding performance. All CVT’s and CC’s with this tage divider/electromagnetic unit.
type of insulators have the same flashover distance as por-
celain and the same high creepage distance ≥ 25 mm/kV. Rating plates
Mechanical stability Corrision resistant rating plates with text and wiring dia-
grams. General data can be found on the door of the
The mechanical stability gives sufficient safety margin for terminal box, connection diagram and secondary winding
normal wind loads and conductor forces. In most cases, it data on the inside.
is also possible to mount line traps for power line carrier The capacitors are marked with measured capacitance on
equipment directly on top of the capacitor divider. CPA the lower insulator flange.
and CPB will also withstand most cases of seismic stress.
Primary terminal
CPA and CPB are normally delivered with a flat 4-hole
aluminium pad, suitable for bolt C-C from 40 to 50 mm
and for connecting normal aluminium cable clamps. Other
primary terminals can be offered on request, such as an
aluminium round stud, Ø=30 mm, Maximum force on the
primary terminal is 2000 N in all directions.
Earth terminals
The transformer is normally equipped with an earth clamp
with a cap of nickel-plated brass, for wire diameter 8-15
mm, which can be moved to either mounting foot. An
earth bar, see example right, can also be offered on
request. Earth terminals for the secondary circuits are
placed within the terminal box.
255
Installation and maintenance
Please check the crates and their contents for damage A simple test is to measure the insulation resistance in
during transportion upon receipt. Should there be any mega-ohm (max test voltage 1000V DC) on the secondary
damage, please contact ABB Switchgear for advice. Holt windings.
before the goods are handled further. Any damage should Since the high voltage winding of the transformer is not
be documented (photographed). capacitively graded, a measurement of the loss angle (tan
delta) will give no significant result.
The electromagnetic unit and the capacitor voltage divider What is possible, however, is to take an oil sample, for gas
are delivered as one unit for CVTs with system voltages chromatography analysis from the electromagnetic unit; to
up to 245 kV. assess its condition.
The tank of the electromagnetic unit can, on request,
Assembly be equipped with a sampling valve, and we can deliver
suitable sampling equipment A simple method is to take
CVTs with higher system voltage, having more than one the oil sample from the oil-filling hole.Sampling intervals
CVD part, are delivered with the bottom unit of the CVD will vary, depending on service conditions; generally, no oil
assembled onto the EMU. analysis should be necessary during the first 20 years of
The EMU, with the bottom CVD unit should be installed service of service.
first, before the top part(s) of the CVD is(are) mounted in
place. Lifting instructions are included in each package. Environmental Aspects
Check that the top and the bottom insulator have the same
serial number (for CVDs with more than one capacitor Impregnant
unit.
Both Faradol 600 (the synthetic oil in the voltage dividers),
Maintenance
and Nynäs NYTRO 10 X (the standard transformer oil
in the electromagnetic unit) are free from PCB and other
CPA and CPB are designed for a service life of more than strongly poisonous substances, and pose a low impact to
25 years, and are practically maintenance-free. We recom- the environ-ment.
mend however the following controls and measures.
Destruction
Visual check
After draining the oils, they can be burnt in an appropriate
We recommend a periodical check, to check for oil leaka- plant intended for this purpose. In this way, Faradol has
ges and also to inspect the external insulation for collec- similar combustion properties as normal mineral oil.
tion of dirt on the insulators. The disposal should be carried out in accordance with
local legal provisions, laws and regulations.
Control measurements of the CVD The porcelain can be deposited after it has been crushed.
The metals in the electromagnetic unit, and the housings
Since the voltage dividers are permanently sealed under of the voltage divider can be recycled. Aluminium parts
slight over-pressure it is not possible to take oil samples are labelled with material specification. In order to utilise
from them. the copper in the windings, the oil saturated paper insula-
Under normal service conditions, no noticeable ageing tion should be combusted.
will occur within the capacitors (verified by ageing tests). The aluminium in the capacitor elements, with their com-
However discrepancies between the secondary voltages in bination of aluminium foil, paper and polypropylene film
parallel phases can be an indication of a fault in a capacitor can be reclaimed after the insulation has been combusted;
part of one of the voltage transformers, which is why the plastic film will not emitt any harmful substances
such a comparison is recommended. In such a case a during this process.
further measurement of the capacitance value is recom-
mended. Readings can be taken between the top and the
”L” terminal in the secondary terminal box.
666
6
Technical specifications
Highest voltage for equipment (phase to phase, rms value) Burden and accuracy class
is the maximum operating voltage for which the voltage
transformer is designed. This level should not be exceeded The burden is the external impedance in the secondary
continuously. circuit in ohms at specified power factor. It is usually
expressed as the apparent power – in VA –, which is
Test voltages are specified in the standards in relation to taken up at rated secondary voltage. It is important to
the system voltage. These tests are to show the ability of determine the power consumption of connected meters
the capacitor voltage transformer to withstand the over- and relays. Unnecessary high burdens are often specified
voltages that can occur in the network. Most of the tests for modern equipment. Note that the accuracy for a
are carried out as type tests and are not repeated without measuring windings can be outside the class limit if the
extra charge. The same applies to customer specific tests actual burden is below 25% of the rated burden.
carried out in addition to the requirement in the standard.
The accuracy class for measuring windings is given as
The lightning impulse test is performed with a standardi- 0.2, 0.5 or 1.0 depending on application.The measuring
sed wave shape – 1.2/50 µs – for simulation of lightning class should be fullfilled between 80% to 120% of rated
over-voltage. voltage for the IEC standard. For protection purposes
the class is normally 3P or 6P. Other classes are quoted
A power frequency voltage withstand test is carried out as on request.
a type test under wet conditions for voltages < 300 kV. The cables from the voltage tranformers must be desig-
ned properly, to avoid unnecessary voltage drop and the
actually connected burden must be as low as possible.
Voltage factor
The protection windings must be able to reproduce the
fault voltage without being saturated. The over-voltage
factor for protection cores is called VF.
277
Design data IEC
Nominal capacitance, flashover- and creepage distance
Creepage distance (min.values)
Type Number of High Extra high *) Flashover*)
capacitor capacitance capacitance distance Total *) Protected *)
units pF (+10; -5%) pF (+10; -5%) mm mm mm
Test voltages above are valid for altitudes 1000 m. above sea level. PD = Partial Discharge
*) Standard data for rated voltage factor is 1.5 / 30 s. for effectively earthed systems; and 1.9 / 30 s. for systems without
effective earthing, with automatic earth fault tripping and 1.9 / 8 h. for systems without effective earthing, without automatic
earth fault tripping.
888
8
Schematic diagram of
Capacitor Voltage Transformer
Tests
Routine Tests
As standard, the following tests are performed on
each transformer, according to applicable standard:
Capacitor Voltage Divider/
Electromagnetic unit Coupling Capacitor
IEC 358, § 6.1
IEC 186, § 10.2 a, b Measurement of capacitance and tan-d
a Verification of terminal marking and polarity. (delta) for each capacitor porcelain before
b, c Applied power frequency test on secondary voltage tests.
windings and adjustment windings. c Applied power frequency test between ter
Test voltage 4 kV, 50 Hz, duration one minals, 50 Hz, duration one minute.
minute. d Applied power frequency test between low
d Induced power frequency test on primary voltage terminal and earth. Test voltage 10
winding, kV, 50 Hz, duration one minute.
75 Hz, duration one minute. e Partial discharge test of each capacitor porcelain.
e Partial discharge test f Tightness test of each capacitor porcelain.
a, b Measurement of capacitance and tan-d
IEC 358, § 6.1 (delta) for each capacitor porcelain as final
d Applied power frequency test on L-terminal. test. Calculation of voltage ratio.
Test voltage 10 kV, 50 Hz, duration one
minute. Type Tests:
ABB-specific Tests Type test reports are available for
a Inspection and measurement of damping tests car ried out on transformers of equal or
circuit. similar designs. These reports or report
b Tightness test numbers can be presented on request.
Capacitor Voltage Divider/Coupling Capacitor
299
Dimensions
Capacitor Voltage Transformer CPA
Type Number of Total Flashover Height Mounting hole Earth level
capacitor height A distance B to flange C *) distance D height E
units mm mm mm mm mm
101010
10
Dimensions
CCA 72 1155
CCA 123 1435
CCA145 1645
CCA
CPA/B
Shipping data
S
Type Net weight Oil Shipping Shipping Type Net weight Oil Shipping Shipping
incl.oil weight volume incl.oil kg* weight volume
kg* kg* kg* m3 kg* kg* m3
* The weights for extra high capacitance CVTs are 5 to 10% CPB 170 490 98 525 1.81)
higher, but the shipping volumes are the same as for high capaci- CPB 245 550 100 775 3.12)
tance CVTs. CPB 300 620 112 740 2.43)
21111