E Series Specification Catalog

Geothermal/Water Source Heat Pumps


• R-410A Refrigerant
• 2, 2.5, 3, 3.5, 4, 5, 6 Ton Single Speed
• 3, 4, 5, 6 Ton Dual Capacity

Design Features

Factory Options

Accessories

Dimensional Data

Physical Data

Performance Data

Engineering Guide Specifications

WaterFurnace

SP1461 09/04
E SERIES SPECIFICATION CATALOG

WaterFurnace E Series products set the industry standard for efficiency,


performance, reliability and quiet operation. Available in seven single speed
sizes and four dual capacity sizes, the E Series units provide exceptional
efficiency throughout a wide range of entering water temperatures (25º to
110º F).

All E Series units utilize the ozone-safe R-410A refrigerant to meet the most stringent EPA requirements now and for
many years to come. Coated air coils add durability and longer life. A sophisticated microprocessor control sequences all
components during operation for optimum performance, and provides easy-to-use troubleshooting features with fault lights
and on-board diagnostics. Unit configurations include horizontal, vertical top discharge and vertical bottom discharge.
Heavy-gauge metal cabinets are coated with durable poly paint for long lasting protection. Single speed units are available
with either ECM2 or PSC blower motors. Dual capacity units feature the Bristol Twin Single compressor and include ECM2
blower motors.

E Series products are performance-certified to ARI ISO 13256-1 standards, are ETL listed, and are
ENERGYSTAR® qualified.

As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit
built is exposed to a wide range of quality control procedures throughout the assembly process and is then subjected to
a rigorous battery of computerized run tests to certify that it meets or exceeds performance standards for efficiency and
safety, and will perform flawlessly at startup. As further affirmation of our quality standards, each unit carries our exclusive
Quality Assurance emblem, signed by the final test technician.

WaterFurnace International’s corporate headquarters and manufacturing facility is located in Fort Wayne, IN. A scenic
three-acre pond located in front of the building serves as our geothermal heating and cooling source to comfort-condition
our 110,000 square feet of manufacturing and office space. As a pioneer, and now a leader in the industry, the team of
WaterFurnace engineers, customer support staff and skilled assembly technicians is dedicated to providing the finest com-
fort systems available.

By choosing or specifying WaterFurnace E Series products, you can be assured that your customer is investing in the ulti-
mate comfort system and peace of mind for many years to come.

2
E SERIES SPECIFICATION CATALOG

Table of Contents

Ground Loop Performance Ratings 4


Model Nomenclature 5
Design Features 6-7
Vertical Features 8-10
Horizontal Features 11
Vertical Dimensional Data 12-13
Horizontal Dimensional Data 14
Optional Filter Rack/Duct Collar 15
Physical Data 16
Unit Electrical Data 17
Auxiliary Heat Ratings 18
Auxiliary Electrical Data 18
Fan Performance Data 19-20
Reference Calculations 21
Legends and Notes 21
Entering Air Correction Factors 21
Capacity Data 22-65
Microprocessor Control Features and Operation 66
Description of Operation 67
Operation Logic Data Table 68
Logic Board Physical Layout 69
Engineering Guide Specifications 70-71

3
E SERIES SPECIFICATION CATALOG

Ground Loop Performance Ratings


SINGLE SPEED
COOLING HEATING
UNIT
CFM GPM 77º F EWT 32º F EWT
SIZE
BTU/HR EER BTU/HR COP
024 700 6.0 24,500 19.2 15,600 3.7
030 900 7.0 29,500 17.5 20,600 3.7
035 1100 9.0 35,000 16.7 25,000 3.5
040 1300 11.0 40,000 19.1 29,000 3.8
047 1500 12.0 50,000 18.0 37,800 3.6
058 2000 14.0 60,000 16.1 46,500 3.5
066 2200 16.0 66,200 16.3 53,500 3.4
Notes: Rated in accordance with ARI/ISO Standard 13256-1.
Cooling capacities based on 80.6°F DB, 66.2°F WB entering air temperature.
Heating capacities based on 68°F DB entering air temperature.

DUAL CAPACITY
COOLING HEATING COOLING HEATING
UNIT
SPEED CFM GPM 77º F EWT 32º F EWT 68º F EWT 41º F EWT
SIZE
BTU/HR EER BTU/HR COP BTU/HR EER BTU/HR COP
HIGH 1200 9.0 36,200 16.7 24,700 3.5    
E036
LOW 800 5.0     18,800 24.0 12,800 4.3
HIGH 1500 12.0 48,900 16.1 35,800 3.5    
E048
LOW 1000 6.0     29,800 22.2 21,200 4.2
HIGH 2000 14.0 60,000 17.0 41,800 3.9    
E060
LOW 1200 8.0     33,200 25.9 22,600 4.7
HIGH 2200 16.0 69,000 14.1 51,000 3.7    
E072
LOW 1400 10.0     36,800 24.3 25,700 4.6
Notes: Rated in accordance with ARI/ISO Standard 13256-1.
Cooling capacities based on 80.6°F DB, 66.2°F WB.
Heating capacities based on 68°F DB.

4
E SERIES SPECIFICATION CATALOG

Model Nomenclature
E 048 T L 1 0 1 N B D S S A

Family Vintage
E Series R-410A

Unit Capacity Non-Standard Option Details


MBTUH

Discharge Air Configuration Non-Standard Options


T = Top Discharge Vertical
B = Bottom Discharge Vertical
E = End Discharge Horizontal
S = Side Discharge Horizontal

Return Air Configuration Filter Options


L = Left D = 1" Pleated Disposable
R= Right

Sound Kit
Voltage A = None
1 = 208-230/60/1 B = Blanket
(standard on 024, 030, 035, 036,
048, 060, 072)
Coax Options
N = Cupronickel

Hot Water Option Blower Options


0 = None 0 = PSC Blower
1 = Hot Water Generation 1 = ECM Blower
With Factory Installed Pump (standard on 036, 048, 060, 072)
2 = Oversized ECM Blower Option
(040, 047, 048)

5
E SERIES SPECIFICATION CATALOG

Design Features
Application Flexibility • Utilizes the ozone-friendly R-410A refrigerant which
• Safe, efficient operation in a wide range of liquid produces higher efficiencies and warmer discharge air
temperatures (25° F to 110° F) and flow rates (as low temperatures.
as 1.5 GPM/ton in open loop applications when EWT
>50°F). Service Advantages
• Top or bottom air discharge for upflow or counterflow • Removable panels (three for the compressor compart-
installations in vertical units, side or end discharge for ment and one or two for the air handling compartment)
horizontal units. provide quick access to all internal components with
• True left or right return air locations—vertical units ductwork in place.
include filter rack/duct collar. • Easily accessible thermal expansion valve.
• Variable-speed ECM2 blowers permit various duct ap- • Brass, swivel-type water connections for quick connec-
plications. tion union, and elimination of wrenches and sealants
• Narrow cabinet for easy movement through doorways. during installation.
• Internally trapped condensate piping for neat, compact • Insulated divider and separate air handling/compressor
installation (vertical upflow units only). access panels permit service testing without air bypass.
• Optional field-installed auxiliary electric heater. • Designed for front access in tight applications.
• Corner-located electrical box for field wiring from two • LED fault and status lights with memory for easy diag-
sides. nostics.
• Fuse-protected loop pump power block for easy wiring. • Detachable thermostat connection strip for wiring conve-
nience.
• Loop pump slaving feature allows multiple units to
share one flow center. • Hot water pump shut-off switch for easy startup and
service.
• Relay to control field-mounted accessories.
• Control box and fan motors have quick-attach wiring
• Field-selectable freeze protection setting for well or
plugs for easy removal.
closed loop systems.
• Internal drop-out blower with permanently-lubricated ball
• Field-selectable voltage switch for low voltage applica-
bearing motor.
tions.
• High- and low-pressure service ports in refrigerant cir-
Operating Efficiencies cuit.
• ARI/ISO 13256-1 rating for heating COPs, cooling • Fan and transformer powered from auxiliary heat supply
EERs and low water flow requirements. (when installed) to provide emergency heat with open
• Optional desuperheater with internal pump generates compressor circuit breaker.
hot water at considerable savings while improving over-
all system efficiency. Factory Quality
• All units are computer run-tested, with conditioned
• High-stability expansion valve delivers optimum refrig-
source water, in all modes to insure efficiency and reli-
erant flow over a wide range of conditions and provides
ability.
bidirectional operation without troublesome check
valves. • Heavy-gauge steel cabinets are painted with durable
powder coat paint for long lasting beauty and service.
• Efficient reciprocating and scroll compressors operate
quietly. • All refrigerant brazing is performed in a nitrogen atmo-
sphere.
• Oversized coaxial tube water-to-refrigerant heat ex-
changer operates at low liquid pressure drops. • All units are deep evacuated to less than 150 microns
prior to refrigerant charging.
• Convoluted cupronickel water tube functions efficiently
at low flow rates. • All joints are helium leak-tested to insure an annual leak
rate of less than 1/4 ounce.
• Oversized rifled copper tube/lanced aluminum fin air-to-
refrigerant heat exchanger provides high efficiencies at • Coaxial heat exchanger, refrigerant suction lines, de-
low-face velocity. superheater coil, and all water pipes are fully insulated
to reduce condensation problems in low temperature
• Large, low-RPM blowers with variable-speed motors
operation.
provide quiet and efficient air movement with high static
capability.

6
E SERIES SPECIFICATION CATALOG

Design Features
• Electro-coated air coils for extended life.
• Noise reduction features include isolation mounted com-
pressors and soft starting blower motors; insulated com-
pressor compartment; interior cabinet insulation using 1/2-
inch coated glass fiber. Selected units include compressor
blanket for quiet operation (available on other units as an
option).
• Safety features include high- and low-pressure refrigerant
controls to protect the compressor; condensate overflow
protection; freeze protection sensor to safeguard the co-
axial heat exchanger; fan start detection; hot water high-
limit desuperheater pump shutdown; fault lockout enables
emergency heat and prevents compressor operation until
thermostat or circuit breaker is reset.

Microprocessor Benefits
• Digital auto-changeover thermostat with 3-stage heating/
2-stage cooling holds precise temperature and provides
varying fan speed control.
• Component sequencing delays for quiet startup, shutdown,
and timed staging of auxiliary electric heat.
• ECM2 fan speed control provides higher supply air tem-
perature in heating, better dehumidification in cooling, and
quiet operation at reduced airflows in all modes.
• Hot water limit prevents scalding, and pump shuts down
automatically when full unit capacity is needed for heating.

Options & Accessories


• Optional desuperheater with internally mounted pump and
water heater plumbing connector.
• Electronic auto-changeover thermostat with
3-stage heating/2-stage cooling and indicator LEDs.
• 24 volt 1-inch electronic air cleaner.
• 90% efficient, cleanable electrostatic filters.
• Closed loop flow center.
• Auxiliary electric heater.
• Hose kits.
• Filter rack/duct collar for horizontal units.
• Additional accessory relay.

7
E SERIES SPECIFICATION CATALOG

Vertical Features
Top Air Discharge

Factory mounted
filter rack accepts
standard size
Powder coated, filters
heavy-gauge steel
Drain pan
cabinet
overflow
protection
Optional auxiliary
heater with Insulated access
electronic controls panels

Oversized rifled Optional factory


tube/lanced fin installed water
coated air coil heating system
with built-in coil
Insulated divider and pump
panel
Internally trapped
Fault and status
condensate line
LEDs
Compressor Brass swivel water
connections

8
E SERIES SPECIFICATION CATALOG

Vertical Features
Small Cabinet ▬ Bottom Air Discharge

Compressor
Optional factory
installed water
heating system
Insulation for low with built-in coil
temperature and pump
operation
Reversing
valve
Bidirectional
expansion valve Easily removable
control box

Internally Microprocessor
removable blower control

Internally
insulated cabinet
Variable speed, soft-
starting ECM2 fan
motor (optional)

9
E SERIES SPECIFICATION CATALOG

Vertical Features
Large Cabinet ▬ Bottom Air Discharge

Electronic controls for optional


auxiliary heater
Upper insulated
access panel
Oversized rifled tube/lanced
fin coated air coil

Powder coated, heavy-gauge


steel cabinet
Internally removable blower

Drain pan with overflow


protection

Fault and status LEDs

Optional factory installed


water heating system with
built-in coil and pump

Brass swivel
water connection

Reversing valve

Internally trapped
condensate line

Brass swivel
water connection

Easy Lower Brass swivel water Removeable control Compressor


grip insulated connections box with micropro-
handles access cessor controls
panel

10
E SERIES SPECIFICATION CATALOG

Horizontal Features
Compressor Compartment

Reversing valve

Optional factory
installed water
Filter bracket accepts
heating system
standard size filters
with built-in coil
and pump
Each unit is quality
built and run-tested
Bidirectional
expansion valve
Insulation for low
temperature
Insulated access
operation
panels
Compressor
Brass swivel water
connections
Fault and diagnostic
LEDs
Microprocessor
control Easily removable
control box

Blower Compartment Insulated divider True left or right return


panel
Side or end Oversized rifled
discharge Internally removable tube/lanced fin coated
(field convertible) blower air coil

Optional auxiliary
Auxiliary optional heater with
heater coil assembly electronic controls

Drain pan overflow


Powder coated, protection
heavy-gauge
steel cabinet

Variable speed,
soft starting ECM2
fan motor (optional)

Internally insulated
cabinet

Hanger kit Condensate line


included
11
E SERIES SPECIFICATION CATALOG

Vertical Dimensional Data


Top Air Discharge
LEFT-HAND RIGHT-HAND
SIDE VIEW RETURN AIR RETURN AIR

Supply Air
L E D E
G F D F H
I J 1”

Access Panels
t Fron
Retu Fron t
K rn A
ir rn Air
Line Voltage Retu

DHW Out
C
DHW In

Alternate Drain
Water Out
Water In

Low Voltage
A B B A
Access Panels
Drain

WATER AUX HEAT


MODEL A B C D E F G H I J K L
CONNECTION KNOCKOUTS

E024, E030, E035 1.00" Swivel 1-3/8" 26.2 22.5 52.0 14.0 14.0 6.1 7.5 4.4 2.4 20.8 28.9 1.7
E036, E040, E047, E048,
1.00" Swivel 1-3/8" 31.2 25.5 58.4 18.0 18.0 6.6 6.5 3.7 1.1 27.3 34.0 1.7
E058, E060, E066, E072

12
E SERIES SPECIFICATION CATALOG

Vertical Dimensional Data


Small Cabinet Bottom Air Discharge
LEFT-HAND RIGHT-HAND
SIDE VIEW RETURN AIR RETURN AIR
DHW Out
DHW In

Line Voltage
L
Water Out

Water In
Low Voltage
C Fron
t Aux Htr Knockout t
Fron
K Retu
rn Air Air
Access Panels rn
Retu

Drain

I A B B A
J

H F E D D E F G

Supply Air Supply Air

WATER AUX HEAT


MODEL A B C D E F G H I J K L
CONNECTION KNOCKOUT
E024, E030, E035 1.00" Swivel 1-3/8" 26.2 22.5 54.4 9.3 10.5 8.5 11.4 6.0 2.1 20.7 28.8 20.0

Large Cabinet Bottom Air Discharge


LEFT-HAND RIGHT-HAND
SIDE VIEW RETURN AIR RETURN AIR
L
I J

Access Panels
t Fron
Retu Fron t
K rn A
ir rn Air
Retu

DHW Out
C
Alternate Drain

Water Out
Water In
Line Voltage
Drain
Low Voltage
DHW In
A B B A
Access Panels
G F E D M D E F H
M

Supply Air Supply Air

WATER AUX HEAT


MODEL A B C D E F G H I J K L M
CONNECTION KNOCKOUT
E036, E040, E047, E048,
1.00" Swivel 1-3/8" 32.1 28.0 62.5 12.8 13.0 4.5 6.5 8.4 1.9 27.3 33.9 1.7 6.6
E058, E060, E066, E072

13
E SERIES SPECIFICATION CATALOG

Horizontal Dimensional Data


LEFT-HAND RIGHT-HAND
RETURN AIR RETURN AIR

E E
Line Voltage
D D
F DHW Out F
DHW In
G Water Out G
Water In

Low Voltage B
Return Air B
A Return Air
A
Front
SIDE DISCHARGE SIDE DISCHARGE

Piping End (Front) Piping End (Front)

Return Air
K J K K
J J
C
H C I

I H
Drain
Supply Air Supply Air

END DISCHARGE END DISCHARGE

Piping End (Front) Piping End (Front)


Return Air

K L
L K

H
H

M
Supply Air

WATER
MODEL A B C D E F G H I J K L M
CONNECTION
E024
E030 1.00” Swivel 22.50 63.00 21.25 31.00 3.56 1.00 19.25 10.49 9.1 8.25 9.30 5.75 2.17
E035
E036 1.00” Swivel 25.50 72.00 21.25 31.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E040
E047 1.00” Swivel 25.50 72.00 21.25 36.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E048
E058 1.00” Swivel 25.50 77.00 21.25 41.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E060 1.00” Swivel 25.50 77.00 21.25 41.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E066 1.00” Swivel 25.50 82.00 21.25 41.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E072 1.00” Swivel 25.50 82.00 21.25 46.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
Notes: All low voltage knockouts are 7/8 inch.
Unit line voltage knockouts are 1-1/8 inch.
Filter bracket extends beyond side of cabinet 1-1/8 inch and is removable.
Electric heater power knockouts are 1-1/8 inch and 1-3/8 inch.

14
E SERIES SPECIFICATION CATALOG

Optional Filter Rack/Duct Collar

MODEL A B C D E MODEL NO.


C
A E024
D E030, E035 37.10 20.10 2.20 0.60 5.50 DCH1836
E040, E047
B
E036
37.12 20.08 2.23 0.59 5.50 DCH2037
E048
E058
E Door side mountable 42.12 20.08 2.23 0.59 5.50 DCH2042
on either end E060
E066
47.12 20.08 2.23 0.59 5.50 DCH2048
E072

15
E SERIES SPECIFICATION CATALOG

Physical Data
Vertical
SINGLE SPEED DUAL CAPACITY
MODEL
E024 E030 E035 E040 E047 E058 E066 E036 E048 E060 E072
Fan Wheel
ECM 9x7 9x7 9x7 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
PSC 9x7 9x7 9x7 10 x 10 10 x 10 11 x 10 11 x 10 n.a. n.a. n.a. n.a.
Fan Motor HP
ECM 1/2 1/2 1/2 1/2* 1/2* 1 1 1/2 1/2* 1 1
PSC 1/5 1/3** 1/2 1/2 1/2 1 1 n.a. n.a. n.a. n.a.
Compressor Reciprocating Scroll Dual Capacity (Twin Single)
Refrigerant Charge
R-410A (oz.) 66.0 67.0 72.0 70.0 72.0 90.0 94.0 61.0 77.0 100.0 103.0
Air Coil
Dimensions (in.) 20 x 30 20 x 30 20 x 30 32 x 25 32 x 25 36 x 25 36 x 25 28 x 25 32 x 25 36 x 25 36 x 25
Face Area (sq. ft.) 4.2 4.2 4.2 5.6 5.6 6.6 6.3 4.9 5.6 6.3 6.3
Number of Rows 3 3 3 3 3 3 3 3 3 3 3
Filter (1”)
Disposable 24 x 31 24 x 31 24 x 31 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36
Electrostatic EAF2431 EAF2431 EAF2431 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036
Electronic EAC2431 EAC2431 EAC2431 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036
Weight (lbs.) 300 301 306 365 389 441 447 376 398 460 463
Notes: * E040, 047, 048 available with optional 1 HP ECM motor.
** E030 265 volt unit uses a 1/2 HP PSC motor.

Horizontal
SINGLE SPEED DUAL CAPACITY
MODEL
E024 E030 E035 E040 E047 E058 E066 E036 E048 E060 E072
Fan Wheel
ECM 9x7 9x7 9x7 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
PSC 9x7 9x7 9x7 10 x 10 10 x 10 11 x 10 11 x 10 n.a. n.a. n.a. n.a.
Fan Motor HP
ECM 1/2 1/2 1/2 1/2* 1/2* 1 1 1/2 1/2* 1 1
PSC 1/5 1/3** 1/2 1/2 1/2 1 1 n.a. n.a. n.a. n.a.
Compressor Reciprocating Scroll Dual Capacity (Twin Single)
Refrigerant Charge
R-410A (oz.) 66.0 67.0 72.0 70.0 72.0 90.0 94.0 58.0 81.0 97.0 103.0
Air Coil
Dimensions (in.) 20 x 30 20 x 30 20 x 30 20 x 35 20 x 35 20 x 40 20 x 45 20 x 30 20 x 35 20 x 40 20 x 45
Face Area (sq. ft.) 4.2 4.2 4.2 4.9 5.6 5.6 6.3 4.2 4.9 5.6 6.3
Number of Rows 3 3 3 3 3 3 3 3 3 3 3
Filter (1”)
Disposable 20 x 37 20 x 37 20 x 37 20 x 37 20 x 37 (1) 18 x 20 (2) 20 x 24 20 x 37 20 x 37 (1) 18 x 20 (2) 20 x 24
Disposable (1) 20 x 24 (1) 20 x 24
Electrostatic EAF2037 EAF2037 EAF2037 EAF2037 EAF2037 EAF2042 EAF2048 EAF2037 EAF2037 EAF2042 EAF2048
Electronic EAC2037 EAC2037 EAC2037 EAC2037 EAC2037 EAC2042 EAC2048 EAC2037 EAC2037 EAC2042 EAC2048
Weight (lbs.) 300 301 306 365 389 441 447 376 398 460 463
Notes: * E040, 047, 048 available with optional 1 HP ECM motor.
* E040, 047, 048 available with optional 1 HP ECM motor.

16
E SERIES SPECIFICATION CATALOG

Unit Electrical Data


ECM Motor
COMPRESSOR FAN EXT. INT. TOTAL MIN. MAX.
RATED VOLTAGE MAX.
MODEL MOTOR PUMP PUMP UNIT CIRCUIT HACR
VOLTAGE MIN./MAX. MCC RLA LRA FUSE
FLA FLA FLA FLA AMP BREAKER

SINGLE SPEED
E024 208-230/60/1 197/253 13.0 8.3 48.0 4.0 5.4 0.4 18.1 20.2 25 25
E030 208-230/60/1 197/253 15.5 9.9 55.0 4.0 5.4 0.4 19.7 22.2 30 30
E035 208-230/60/1 197/253 19.0 12.2 66.0 4.0 5.4 0.4 22.0 25.0 35 35
E040 208-230/60/1 197/253 24.0 15.4 83.0 4.0 5.4 0.4 25.2 29.0 40 40
E040* 208-230/60/1 197/253 24.0 15.4 83.0 7.0 5.4 0.4 28.2 32.0 45 45
E047 208-230/60/1 197/253 32.0 20.5 109.0 4.0 5.4 0.4 30.3 35.4 50 50
E047* 208-230/60/1 197/253 32.0 20.5 109.0 7.0 5.4 0.4 33.3 38.4 50 50
E058 208-230/60/1 197/253 42.0 26.9 145.0 7.0 5.4 0.4 39.7 46.4 70 70
E066 208-230/60/1 197/253 47.0 30.1 158.0 7.0 5.4 0.4 42.9 50.4 80 80
DUAL CAPACITY
E036 208-230/60/1 197/253 19.5 12.5 66.0 4.0 5.4 0.4 22.3 25.4 35 35
E048 208-230/60/1 197/253 28.0 17.9 96.0 4.0 5.4 0.4 27.7 32.2 50 50
E048* 208-230/60/1 197/253 28.0 17.9 96.0 7.0 5.4 0.4 30.7 35.2 50 50
E060 208-230/60/1 197/253 38.5 24.7 130.0 7.0 5.4 0.4 37.5 43.6 60 60
E072 208-230/60/1 197/253 41.0 26.3 130.0 7.0 5.4 0.4 39.1 45.7 70 70
Notes: Always refer to unit nameplate data prior to installation.
HACR circuit breaker in United States only. All fuses are class RK-5.
* With optional 1 HP ECM2 motor.

PSC Motor
COMPRESSOR FAN EXT. INT. TOTAL MIN. MAX.
RATED VOLTAGE MAX.
MODEL MOTOR PUMP PUMP UNIT CIRCUIT HACR
VOLTAGE MIN./MAX. MCC RLA LRA FUSE
FLA FLA FLA FLA AMP BREAKER

SINGLE SPEED
E024 208-230/60/1 197/253 13.0 8.3 48.0 1.2 5.4 0.4 15.3 17.4 25 25
E030 208-230/60/1 197/253 15.5 9.9 55.0 1.5 5.4 0.4 17.2 19.7 25 25
E035 208-230/60/1 197/253 19.0 12.2 66.0 2.2 5.4 0.4 20.2 23.2 35 35
E040 208-230/60/1 197/253 24.0 15.4 83.0 2.8 5.4 0.4 24.0 27.8 40 40
E047 208-230/60/1 197/253 32.0 20.5 109.0 3.5 5.4 0.4 29.8 34.9 50 50
E058 208-230/60/1 197/253 42.0 26.9 145.0 5.9 5.4 0.4 38.6 45.3 70 70
E066 208-230/60/1 197/253 47.0 30.1 158.0 5.9 5.4 0.4 41.8 49.3 70 70
Notes: Always refer to unit nameplate data prior to installation.
HACR circuit breaker in United States only. All fuses are class RK-5.

17
E SERIES SPECIFICATION CATALOG

Auxiliary Heat Ratings


KW BTU/HR MIN E MODEL COMPATIBILITY
MODEL
280 V 240 V STAGES 208 V 240 V CFM E024 E030 E035 E036 E040 E047 E048 E058 E060 E066 E072
EAM(H)5 3.6 4.8 1 12300 16300 450 • • •
EAM(H)8 5.7 7.6 2 19400 25900 550 • • •
EAM(H)10 7.2 9.6 2 24600 32700 650 • •

EAL(H)10 7.2 9.6 2 24600 32700 1100 • • • • • • • •


EAL(H)15 10.8 14.4 3 36900 49100 1250 • • • • • • •

EAL(H)20 14.4 19.2 4 49200 65500 1500 • •


• • •

Auxiliary Heat Electrical Data


SUPPLY HEATER AMPS MIN CIRC AMP FUSE (USA) FUSE (CAN) CKT BRK (CAN)
MODEL
CIRC 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V
SINGLE SPEED
EAM(H)5 Single 17.3 20.0 26.7 30.0 30 30 30 30 30 30
EAM(H)8 Single 27.5 31.7 39.3 44.6 40 45 40 45 40 45
EAM(H)10 Single 34.7 40.0 48.3 55.0 50 60 50 60 50 60
EAL(H)10 Single 34.7 40.0 53.3 60.0 60 60 60 60 60 60
Single 52.0 60.0 75.0 85.0 80 90 80 90 80 90
EAL(H)15 L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60
L3/L4 17.3 20.0 21.7 25.0 25 25 25 25 25 25
Single 69.3 80.0 96.7 110.0 100 110 100 110 100 110
EAL(H)20 L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60
L3/L4 34.7 40.0 43.3 50.0 45 50 45 50 40 50
DUAL CAPACITY
EAL(H)10 Single 34.7 40.0 53.3 60.0 60 60 60 60 60 60
Single 52.0 60.0 75.0 85.0 80 90 80 90 80 90
EAL(H)15 L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60
L3/L4 17.3 20.0 21.7 25.0 25 25 25 25 25 25
Single 69.3 80.0 96.7 110.0 100 110 100 110 100 110
EAL(H)20 L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60
L3/L4 34.7 40.0 43.3 50.0 45 50 45 50 40 50
Notes: All heaters rated single phase 60 cycle and include the unit fan load. All fuses type “D” time delay (or HACR
circuit breaker in USA). Supply wire size to be determined by local codes.

18
E SERIES SPECIFICATION CATALOG

Fan Performance Data


ECM2
AIR FLOW DIP SWITCH SETTINGS
MODEL MAX
ESP 1 2 3 4 5 6 7 8 9 10 11 12
SINGLE SPEED
500 600 700
E024 0.50 300 400 800
L M H
500 700 900
E030 0.50 300 400 600 800 1000
L M H
700 900 1100
E035 0.50 500 600 800 1000 1175 1250
L M H
850 1050 1325
E040 0.50 650 750 950 1150 1250 1375 1475
L M H
1050 1250 1550
E047 0.50 650 750 850 950 1150 1325 1375 1475 1600
L M H
E040 800 1000 1300
0.75 1100 1500
w/1 HP * L M H
E047 1000 1300 1500
0.75 800 1100 1600 1800
w/1 HP * L M H
1200 1400 1850
E058 0.75 750 900 1000 1600 1700 2000 2200 2300 2400
L M H
1400 1700 2200
E066 0.75 750 900 1000 1200 1600 1850 2000 2300 2400
L M H
DUAL CAPACITY
600 800 1200
E036 0.50 700 900 1000 1100 1300 1400 1500 1550 1600
L M H
600 1000 1500
E048 0.50 700 800 900 1100 1200 1300 1400 1550 1600
L M H
E048 750 1000 1600
0.75 900 1200 1400 1700 1850 2000 2200 2300 2400
w/1 HP * L M H
750 1200 2000
E060 0.75 900 1000 1400 1600 1700 1850 2200 2300 2400
L M H
750 1400 2200
E072 0.75 900 1000 1200 1600 1700 1850 2000 2300 2400
L M H
Notes: Factory settings are recommended L-M-H DIP switch locations. M-H settings must be SW1
Off On
located within CFM range (shaded area). CFM is controlled within + 5% up to the maximum ESP.
Max ESP includes allowance for wet coil and standard filter. Lowest and highest dip switch settings 1
are assumed to be L and H respectively.
* With optional 1 HP fan motor available. 2
3
A 12-position DIP switch package on the control allows the airflow levels to be set for low,
medium, and high speed when using the ECM2 blower motor. Only three of the DIP switches 4
can be in the "on" position. 5
• The first "on" switch (the lowest position number) determines the low speed fan setting.
6
• The second "on" switch determines the medium speed fan setting.
• The third "on" switch determines the high speed fan setting. 7
8
The example to the right shows SW1 on the control board configured for the following E036 9
airflow settings.
10
Low Speed Fan: 600 CFM
Medium Speed Fan: 800 CFM 11
High Speed Fan: 1200 CFM 12

19
E SERIES SPECIFICATION CATALOG

Fan Performance Data


PSC
SPEED 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
E024
Max 1020 CFM High* 1020 1003 984 961 940 908 882 845 810 772 717 653 - - - -
Rated 700 Med 801 795 784 776 761 742 714 692 672 628 580 - - - - -
Min 580 CFM Low 713 705 691 694 674 665 645 616 594 - - - - - - -
E030
Max 1275 CFM High* 1275 1252 1230 1210 1179 1152 1108 1079 1030 991 955 849 687 - - -
Rated 900 Med 1052 1042 1034 1027 1001 993 959 940 908 868 836 744 - - - -
Min 720 CFM Low 847 845 844 846 830 829 805 793 768 739 720 - - - - -
E035
Max 1420 CFM High* 1420 1391 1357 1329 1294 1254 1212 1167 1119 1067 1016 892 - - - -
Rated 1100 Med 1214 1199 1185 1152 1127 1096 1056 1031 1002 956 908 - - - - -
Min 890 CFM Low 1077 1070 1058 1046 1034 1006 974 953 925 890 - - - - - -
E040
Max 1610 CFM High* 1610 1588 1568 1536 1498 1469 1427 1388 1360 1293 1229 1128 - - - -
Rated 1300 Med 1397 1374 1360 1344 1302 1298 1269 1237 1189 1162 1105 - - - - -
Min1040 CFM Low 1100 1092 1081 1066 1055 1040 - - - - - - - - - -
E047
Max 1800 CFM High* - 1800 1760 1725 1690 1632 1584 1523 1474 1399 1308 1194 - - - -
Rated 1500 Med 1571 1547 1518 1486 1456 1414 1388 1331 1281 1236 1168 1080 - - - -
Min 1080 CFM Low 1183 1175 1162 1149 1136 1111 1085 - - - - - - - - -
E058
Max 2160 CFM High* - - - - - - 2160 2115 2057 2016 1963 1860 1722 - - -
Rated 2000 Med - - - 2141 2105 2072 2034 1994 1947 1907 1861 1774 1650 - - -
Min 1550 CFM Low 2071 2049 2026 2000 1970 1941 1908 1872 1834 1792 1749 1655 1550 - - -
E066
Max 2300 CFM High* - - - - - 2300 2237 2199 2135 2102 2037 1938 1789 1725 - -
Rated 2200 Med 2282 2249 2224 2198 2157 2134 2091 2056 1995 1964 1915 1817 1676 - - -
Min 1630 CFM Low 2059 2030 2008 1983 1942 1924 1877 1853 1812 1770 1730 1630 - - - -
Notes: All units tested with a wet coil and clean 1-inch filter.
* Indicates factory settings

20
E SERIES SPECIFICATION CATALOG

Reference Calculations
Heating Calculations: Cooling Calculations:
HE HR
LWT = EWT - LWT = EWT +
GPM x 500 GPM x 500

HC SC
LAT = EAT + LAT (DB) = EAT (DB) -
CFM x 1.08 CFM x 1.08

LC = TC - SC
TH = HC + HW SC
S/T =
TC

Legends and Notes


ABBREVIATIONS AND DEFINITIONS:
CFM = airflow, cubic feet/minute HE = total heat of extraction, MBTUH
EWT = entering water temperature, Fahrenheit HW = desuperheater capacity, MBTUH
GPM = water flow in gallons/minute EER = Energy Efficient Ratio
WPD = water pressure drop, PSI and feet of water = BTU output/Watt input
EAT = entering air temperature, Fahrenheit COP = Coefficient of Performance
(dry bulb/wet bulb) = BTU output/BTU input
HC = air heating capacity, MBTUH LWT = leaving water temperature, °F
TC = total cooling capacity, MBTUH LAT = leaving air temperature, °F
SC = sensible cooling capacity, MBTUH TH = total heating capacity, MBTUH
KW = total power unit input, kilowatts LC = latent cooling capacity, MBTUH
HR = total heat of rejection, MBTUH S/T = sensible to total cooling ratio

Desuperheater capacity based on 0.4 GPM flow per nominal unit ton at 90°F entering hot water temperature.
Capacity data on pages 22-65 do not include water pumping watts and are based upon 15% (by volume)
methanol antifreeze solution. For non-standard EAT conditions, apply the appropriate correction factors
found below. Interpolation between EWT, GPM and CFM data is permissible. Extrapolation for heating
data down to 25°F is permissible. Catalog illustrations cover the general appearance of products at time of
publication. We reserve the right to make changes in design and construction at any time without notice.

Entering Air Correction Factors


COOLING HEATING

EAT TC SC KW HR EAT HC KW HE
75/63 0.92 0.96 0.98 0.94 60 1.09 0.95 1.06
80/67 1.00 1.00 1.00 1.00 70 1.00 1.00 1.00
85/71 1.08 1.04 1.02 1.06 80 0.97 1.05 0.94
(ECM Only)

21
E SERIES SPECIFICATION CATALOG

E024
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
600 13.7 1.1 9.9 91.1 3.6 11.4 1.1 10.0 87.6 2.3 3.7
3.0 0.7 1.6
700 13.9 1.1 10.1 88.4 3.6 11.9 1.1 10.1 85.8 1.9 3.7
600 14.4 1.1 10.5 92.2 3.7 12.0 1.1 10.6 88.6 2.4 3.8
30 4.5 1.4 3.2
700 14.7 1.2 10.7 89.4 3.7 12.6 1.1 10.7 86.7 2.0 3.8
600 14.7 1.2 10.7 92.6 3.7 12.2 1.1 10.8 88.9 2.4 3.9
6.0 2.4 5.6
700 14.9 1.2 11.0 89.7 3.8 12.8 1.1 11.0 87.0 2.0 3.8
600 19.9 1.4 15.1 100.7 4.2 17.0 1.3 15.3 96.2 2.8 4.4
3.0 0.7 1.6
700 20.3 1.4 15.6 96.9 4.3 17.9 1.4 15.6 93.6 2.4 4.4
600 20.9 1.4 16.0 102.2 4.3 17.9 1.4 16.2 97.6 2.9 4.5
50 4.5 1.4 3.2
700 21.3 1.4 16.5 98.2 4.4 18.8 1.4 16.6 94.9 2.5 4.5
600 21.2 1.4 16.3 102.8 4.3 18.2 1.4 16.5 98.1 3.0 4.5
6.0 2.4 5.6
700 21.7 1.4 16.8 98.7 4.4 19.2 1.4 16.9 95.3 2.5 4.6
600 25.1 1.5 19.8 108.7 4.8 21.6 1.4 20.0 103.3 3.4 5.1
3.0 0.7 1.6
700 25.7 1.5 20.6 104.0 5.0 22.9 1.5 20.8 100.3 2.8 5.2
600 26.2 1.6 20.9 110.4 4.9 22.6 1.5 21.1 104.8 3.5 5.2
70 4.5 1.4 3.2
700 27.0 1.5 21.7 105.7 5.1 24.0 1.5 21.9 101.8 2.9 5.4
600 26.7 1.6 21.3 111.2 4.9 23.0 1.5 21.5 105.4 3.6 5.2
6.0 2.4 5.6
700 27.4 1.6 22.2 106.3 5.2 24.5 1.5 22.4 102.4 3.0 5.4
600 30.0 1.7 24.4 116.3 5.3 25.9 1.5 24.6 110.0 4.0 5.7
3.0 0.6 1.4
700 31.0 1.6 25.5 111.0 5.7 27.8 1.5 25.9 106.8 3.3 5.9
600 31.3 1.7 25.5 118.2 5.4 27.0 1.6 25.7 111.6 4.1 5.8
90 4.5 1.3 3.0
700 32.4 1.6 26.8 112.8 5.8 29.1 1.6 27.1 108.4 3.4 6.1
600 31.8 1.7 25.9 119.1 5.4 27.4 1.6 26.2 112.3 4.2 5.8
6.0 2.3 5.3
700 33.0 1.7 27.3 113.6 5.8 29.6 1.6 27.7 109.2 3.5 6.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

22
E SERIES SPECIFICATION CATALOG

E024
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
600 28.8 17.7 1.0 32.2 28.7 28.8 17.7 1.0 30.5 1.7 29.3
3.0 0.7 1.6
700 29.4 19.3 1.0 32.9 28.1 29.4 19.3 1.0 31.2 1.7 28.7
600 29.1 17.9 1.0 32.3 30.7 29.1 17.9 0.9 30.7 1.5 31.2
50 4.5 1.4 3.2
700 29.7 19.5 1.0 33.0 30.1 29.7 19.5 1.0 31.4 1.6 30.5
600 29.4 17.9 0.9 32.5 31.9 29.4 17.9 0.9 31.1 1.4 32.2
6.0 2.4 5.6
700 30.0 19.5 1.0 33.2 31.3 30.0 19.5 1.0 31.8 1.4 31.6
600 25.6 16.5 1.3 29.9 20.1 25.7 16.5 1.2 27.0 2.9 20.7
3.0 0.7 1.6
700 26.1 17.9 1.3 30.6 19.8 26.2 18.0 1.3 27.6 3.0 20.4
600 25.8 16.6 1.2 29.9 21.5 26.0 16.7 1.2 27.3 2.7 22.0
70 4.5 1.4 3.2
700 26.4 18.1 1.3 30.6 21.1 26.5 18.1 1.2 27.9 2.8 21.6
600 26.1 16.6 1.2 30.1 22.3 26.2 16.7 1.2 27.7 2.5 22.7
6.0 2.4 5.6
700 26.6 18.1 1.2 30.8 22.0 26.8 18.1 1.2 28.3 2.6 22.3
600 21.9 15.1 1.6 27.2 14.1 22.1 15.2 1.5 23.1 4.2 14.7
3.0 0.6 1.4
700 22.4 16.4 1.6 27.8 14.0 22.6 16.5 1.6 23.6 4.3 14.6
600 22.1 15.3 1.5 27.2 15.1 22.4 15.4 1.4 23.4 3.9 15.6
90 4.5 1.3 3.0
700 22.6 16.6 1.5 27.8 14.9 22.8 16.7 1.5 23.9 4.0 15.4
600 22.4 15.3 1.4 27.2 15.7 22.6 15.4 1.4 23.8 3.6 16.0
6.0 2.3 5.3
700 22.8 16.6 1.5 27.8 15.6 23.1 16.7 1.5 24.3 3.7 15.9
600 19.4 13.7 1.8 25.5 10.7 19.7 13.8 1.7 20.1 5.5 11.3
3.0 0.6 1.3
700 19.8 14.9 1.9 26.1 10.7 20.1 15.0 1.8 20.6 5.6 11.2
600 19.6 13.8 1.7 25.4 11.5 19.9 13.9 1.7 20.4 5.1 11.9
110 4.5 1.3 2.9
700 20.0 15.0 1.8 25.9 11.4 20.3 15.1 1.7 20.9 5.2 11.9
600 19.8 13.8 1.7 25.4 12.0 20.1 13.9 1.6 20.9 4.7 12.3
6.0 2.2 5.2
700 20.2 15.0 1.7 26.0 11.9 20.5 15.1 1.7 21.4 4.9 12.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

23
E SERIES SPECIFICATION CATALOG

E024
Heating Capacity Data (700 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 14.6 1.1 10.7 79.2 3.8 12.5 1.1 10.7 76.5 1.8 3.8
3.0 0.7 1.6 70 14.1 1.2 10.1 88.7 3.5 12.1 1.2 10.1 86.0 1.9 3.6
80 13.7 1.2 9.5 98.1 3.2 11.7 1.2 9.5 95.4 2.0 3.3
60 15.2 1.1 11.3 80.2 3.9 13.2 1.1 11.3 77.5 1.9 4.0
30 4.5 1.4 3.2 70 14.8 1.2 10.7 89.6 3.6 12.7 1.2 10.7 86.8 2.0 3.7
80 14.4 1.3 10.1 99.0 3.3 12.2 1.2 10.1 96.2 2.1 3.4
60 15.6 1.2 11.7 80.6 4.0 13.6 1.1 11.7 78.0 1.9 4.0
6.0 2.4 5.6 70 15.1 1.2 11.0 90.0 3.7 13.1 1.2 11.0 87.3 2.0 3.7
80 14.7 1.3 10.3 99.4 3.4 12.5 1.3 10.3 96.6 2.1 3.4
60 21.2 1.4 16.5 88.0 4.5 18.7 1.3 16.5 84.8 2.3 4.6
3.0 0.7 1.6 70 20.5 1.4 15.6 97.1 4.2 18.0 1.4 15.6 93.8 2.4 4.3
80 19.8 1.5 14.7 106.2 3.8 17.2 1.5 14.7 102.8 2.5 3.9
60 22.3 1.4 17.5 89.4 4.7 19.8 1.4 17.6 86.2 2.4 4.8
50 4.5 1.4 3.2 70 21.5 1.5 16.5 98.5 4.3 19.0 1.4 16.6 95.1 2.5 4.4
80 20.8 1.5 15.5 107.5 3.9 18.2 1.5 15.6 104.0 2.6 4.0
60 22.6 1.4 17.8 89.9 4.7 20.2 1.4 17.9 86.7 2.4 4.8
6.0 2.4 5.6 70 21.9 1.5 16.8 98.9 4.3 19.3 1.4 16.9 95.5 2.5 4.4
80 21.1 1.6 15.8 107.9 4.0 18.5 1.5 15.9 104.4 2.6 4.1
60 26.9 1.5 21.8 95.5 5.3 24.2 1.4 22.0 92.0 2.7 5.5
3.0 0.7 1.6 70 25.9 1.6 20.6 104.2 4.9 23.1 1.5 20.8 100.6 2.8 5.1
80 24.9 1.6 19.4 113.0 4.5 22.0 1.6 19.6 109.2 2.9 4.6
60 28.2 1.5 23.0 97.2 5.5 25.4 1.5 23.2 93.5 2.8 5.7
70 4.5 1.4 3.2 70 27.1 1.6 21.7 105.9 5.0 24.2 1.5 21.9 102.0 2.9 5.2
80 26.1 1.7 20.4 114.5 4.6 23.1 1.6 20.6 110.5 3.0 4.8
60 28.7 1.5 23.5 98.0 5.5 25.8 1.5 23.7 94.2 2.9 5.8
6.0 2.4 5.6 70 27.7 1.6 22.2 106.6 5.1 24.7 1.5 22.4 102.6 3.0 5.3
80 26.6 1.7 20.9 115.2 4.6 23.5 1.6 21.1 111.1 3.1 4.8
60 32.4 1.6 27.0 102.9 6.0 29.4 1.5 27.5 98.9 3.2 6.3
3.0 0.6 1.4 70 31.2 1.7 25.5 111.2 5.5 28.0 1.6 25.9 107.1 3.3 5.8
80 29.9 1.7 24.0 119.6 5.0 26.6 1.7 24.3 115.2 3.4 5.3
60 33.9 1.6 28.4 104.8 6.2 30.6 1.5 28.7 100.5 3.3 6.5
90 4.5 1.3 3.0 70 32.6 1.7 26.8 113.1 5.6 29.2 1.6 27.1 108.6 3.4 5.9
80 31.2 1.8 25.2 121.3 5.2 27.7 1.7 25.5 116.7 3.5 5.4
60 34.5 1.6 28.9 105.6 6.2 31.3 1.5 29.4 101.3 3.4 6.6
6.0 2.3 5.3 70 33.1 1.7 27.3 113.8 5.7 29.8 1.6 27.7 109.4 3.5 6.0
80 31.8 1.8 25.7 122.1 5.2 28.3 1.7 26.0 117.4 3.6 5.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

24
E SERIES SPECIFICATION CATALOG

E024
Cooling Capacity Data (700 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 27.0 18.5 1.1 31.1 25.3 27.0 18.5 1.0 31.0 1.6 25.8
3.0 0.7 1.6 80/67 29.4 19.3 1.1 33.1 26.9 29.4 19.3 1.1 33.0 1.7 27.4
85/71 31.7 20.1 1.1 35.1 28.5 31.7 20.1 1.1 35.0 1.8 29.0
75/63 27.3 18.7 1.0 31.2 26.8 27.3 18.7 1.0 31.1 1.6 27.3
50 4.5 1.4 3.2 80/67 29.7 19.5 1.0 33.2 28.5 29.7 19.5 1.0 33.1 1.6 29.1
85/71 32.0 20.3 1.1 35.2 30.2 32.0 20.3 1.0 35.1 1.6 30.8
75/63 27.6 18.7 1.0 31.4 27.8 27.6 18.7 1.0 31.4 1.4 28.1
6.0 2.4 5.6 80/67 30.0 19.5 1.0 33.4 29.7 30.0 19.5 1.0 33.4 1.4 30.0
85/71 32.3 20.3 1.0 35.4 31.4 32.3 20.3 1.0 35.4 1.4 31.7
75/63 24.0 17.2 1.3 28.9 17.9 24.1 17.3 1.3 28.9 2.9 18.3
3.0 0.7 1.6 80/67 26.1 17.9 1.4 30.7 19.0 26.2 18.0 1.3 30.7 3.0 19.5
85/71 28.1 18.6 1.4 32.6 20.1 28.2 18.7 1.4 32.6 3.1 20.7
75/63 24.2 17.4 1.3 28.9 19.0 24.3 17.4 1.2 28.9 2.7 19.6
70 4.5 1.4 3.2 80/67 26.4 18.1 1.3 30.8 20.3 26.5 18.1 1.3 30.8 2.8 20.8
85/71 28.5 18.8 1.3 32.6 21.5 28.6 18.8 1.3 32.6 2.9 22.1
75/63 24.4 17.4 1.2 29.0 19.8 24.6 17.4 1.2 29.2 2.5 20.1
6.0 2.4 5.6 80/67 26.6 18.1 1.3 30.9 21.1 26.8 18.1 1.3 31.0 2.6 21.4
85/71 28.7 18.8 1.3 32.7 22.3 28.9 18.8 1.3 32.9 2.7 22.7
75/63 20.6 15.7 1.6 26.3 12.7 20.7 15.8 1.6 26.3 4.2 13.2
3.0 0.6 1.4 80/67 22.4 16.4 1.7 28.0 13.5 22.6 16.5 1.6 28.0 4.3 14.1
85/71 24.1 17.1 1.7 29.7 14.3 24.4 17.2 1.6 29.7 4.4 14.9
75/63 20.7 15.9 1.5 26.2 13.6 20.9 16.0 1.5 26.3 3.9 14.0
90 4.5 1.3 3.0 80/67 22.6 16.6 1.6 27.9 14.5 22.8 16.7 1.5 28.0 4.0 14.9
85/71 24.4 17.3 1.6 29.5 15.3 24.6 17.4 1.6 29.6 4.1 15.7
75/63 20.9 15.9 1.5 26.3 14.1 21.2 16.0 1.5 26.5 3.6 14.4
6.0 2.3 5.3 80/67 22.8 16.6 1.5 27.9 15.0 23.1 16.7 1.5 28.2 3.7 15.4
85/71 24.6 17.3 1.6 29.6 15.8 24.9 17.4 1.5 29.9 3.8 16.3
75/63 18.2 14.3 1.9 24.7 9.8 18.4 14.4 1.8 24.7 5.4 10.3
3.0 0.6 1.3 80/67 19.8 14.9 1.9 26.2 10.4 20.1 15.0 1.8 26.3 5.6 11.0
85/71 21.3 15.5 1.9 27.8 11.0 21.7 15.6 1.9 27.9 5.8 11.6
75/63 18.4 14.4 1.8 24.5 10.4 18.6 14.5 1.7 24.7 5.0 10.8
110 4.5 1.3 2.9 80/67 20.0 15.0 1.8 26.1 11.1 20.3 15.1 1.8 26.3 5.2 11.5
85/71 21.5 15.6 1.8 27.7 11.7 21.9 15.7 1.8 27.8 5.4 12.2
75/63 18.5 14.4 1.7 24.6 10.8 18.8 14.5 1.7 24.8 4.8 11.1
6.0 2.2 5.2 80/67 20.2 15.0 1.8 26.1 11.5 20.5 15.1 1.7 26.4 4.9 11.8
85/71 21.8 15.6 1.8 27.7 12.2 22.1 15.7 1.8 27.9 5.0 12.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

25
E SERIES SPECIFICATION CATALOG

E030
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
700 17.9 1.6 12.6 93.7 3.3 15.3 1.5 12.7 90.2 2.6 3.4
4.0 1.2 2.8
900 18.3 1.6 12.8 88.8 3.3 15.9 1.6 12.8 86.4 2.3 3.4
700 18.5 1.6 13.1 94.4 3.4 15.7 1.5 13.2 90.8 2.7 3.5
30 5.5 2.1 4.9
900 18.8 1.6 13.3 89.4 3.4 16.4 1.6 13.3 86.9 2.3 3.5
700 18.9 1.6 13.5 95.0 3.5 16.1 1.6 13.6 91.3 2.8 3.6
7.0 3.2 7.5
900 19.3 1.6 13.8 89.9 3.5 16.8 1.6 13.8 87.3 2.4 3.5
700 24.9 1.8 18.8 102.9 4.1 21.1 1.7 19.0 97.9 3.7 4.3
4.0 1.2 2.7
900 25.5 1.8 19.4 96.2 4.2 22.1 1.7 19.4 92.8 3.2 4.3
700 25.7 1.8 19.6 104.0 4.2 21.8 1.7 19.8 98.8 3.9 4.4
50 5.5 2.0 4.7
900 26.3 1.8 20.2 97.1 4.3 22.9 1.8 20.3 93.5 3.4 4.4
700 26.3 1.8 20.1 104.7 4.3 22.2 1.7 20.3 99.4 3.9 4.4
7.0 3.1 7.2
900 26.9 1.8 20.7 97.7 4.3 23.4 1.8 20.8 94.1 3.4 4.5
700 31.0 2.0 24.3 111.0 4.6 26.1 1.9 24.6 104.5 4.8 4.9
4.0 1.1 2.5
900 31.9 1.9 25.3 102.8 4.8 27.7 1.9 25.5 98.5 4.2 5.0
700 32.1 2.0 25.3 112.4 4.7 27.0 1.9 25.6 105.7 5.0 5.0
70 5.5 2.0 4.5
900 33.0 2.0 26.3 104.0 4.9 28.6 1.9 26.6 99.5 4.4 5.1
700 32.6 2.0 25.8 113.2 4.8 27.4 1.9 26.1 106.2 5.1 5.1
7.0 3.0 6.9
900 33.7 2.0 26.9 104.6 5.0 29.2 1.9 27.2 100.0 4.5 5.2
700 36.5 2.0 29.6 118.3 5.3 30.4 1.9 29.9 110.3 5.9 5.6
4.0 1.1 2.5
900 37.8 2.0 31.0 108.9 5.6 32.7 1.9 31.4 103.7 5.2 5.8
700 37.8 2.1 30.8 120.1 5.3 31.5 1.9 31.1 111.7 6.1 5.7
90 5.5 1.9 4.4
900 39.3 2.0 32.3 110.4 5.7 34.0 1.9 32.8 105.0 5.4 6.0
700 38.4 2.1 31.2 120.7 5.4 31.9 1.9 31.5 112.2 6.3 5.8
7.0 2.9 6.7
900 39.8 2.1 32.8 111.0 5.7 34.4 2.0 33.3 105.4 5.6 6.0
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

26
E SERIES SPECIFICATION CATALOG

E030
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
700 34.1 20.6 1.2 38.3 27.7 34.1 20.6 1.2 36.4 1.9 28.1
4.0 1.2 2.7
900 35.2 23.1 1.3 39.7 26.9 35.2 23.1 1.3 37.6 2.0 27.3
700 34.2 20.7 1.2 38.3 28.9 34.2 20.7 1.2 36.5 1.8 29.2
50 5.5 2.0 4.7
900 35.3 23.3 1.3 39.6 28.0 35.3 23.3 1.3 37.7 1.9 28.3
700 34.6 20.7 1.2 38.6 29.8 34.6 20.7 1.2 36.9 1.6 30.0
7.0 3.1 7.2
900 35.7 23.3 1.2 39.9 28.9 35.7 23.3 1.2 38.2 1.7 29.0
700 30.8 19.4 1.5 35.8 21.1 31.0 19.5 1.4 32.3 3.6 21.7
4.0 1.1 2.5
900 31.8 21.7 1.5 37.0 20.7 31.9 21.8 1.5 33.4 3.7 21.2
700 30.9 19.5 1.4 35.7 22.0 31.1 19.5 1.4 32.5 3.3 22.5
70 5.5 2.0 4.5
900 31.9 21.8 1.5 36.9 21.5 32.1 21.9 1.5 33.6 3.5 22.0
700 31.2 19.5 1.4 36.0 22.7 31.4 19.6 1.4 33.0 3.1 23.0
7.0 3.0 6.9
900 32.2 21.9 1.5 37.2 22.2 32.4 21.9 1.4 34.1 3.2 22.5
700 26.1 17.9 1.9 32.7 13.6 26.4 17.9 1.9 27.5 5.2 14.2
4.0 1.1 2.5
900 26.9 19.9 2.0 33.8 13.5 27.2 20.0 1.9 28.4 5.4 14.0
700 26.3 17.9 1.8 32.6 14.2 26.5 18.0 1.8 27.8 4.9 14.7
90 5.5 1.9 4.4
900 27.1 20.0 1.9 33.6 14.1 27.4 20.1 1.9 28.7 5.1 14.5
700 26.5 17.9 1.8 32.7 14.7 26.8 18.0 1.8 28.4 4.6 15.0
7.0 2.9 6.7
900 27.4 20.0 1.9 33.8 14.5 27.6 20.1 1.9 29.3 4.7 14.8
700 21.8 16.3 2.2 29.4 9.8 22.1 16.4 2.2 22.6 6.9 10.3
4.0 1.1 2.5
900 22.5 18.2 2.3 30.3 9.8 22.8 18.3 2.2 23.3 7.1 10.3
700 21.9 16.3 2.2 29.3 10.2 22.3 16.4 2.1 23.0 6.5 10.6
110 5.5 1.8 4.3
900 22.6 18.2 2.2 30.2 10.2 23.0 18.3 2.2 23.7 6.7 10.6
700 22.2 16.4 2.1 29.4 10.5 22.5 16.5 2.1 23.6 6.0 10.8
7.0 2.8 6.5
900 22.8 18.3 2.2 30.3 10.5 23.2 18.4 2.2 24.3 6.2 10.8
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

27
E SERIES SPECIFICATION CATALOG

E030
Heating Capacity Data (900 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 19.0 1.6 13.6 79.5 3.6 16.5 1.5 13.6 77.0 2.2 3.6
4.0 1.2 2.8 70 18.4 1.6 12.8 88.9 3.3 16.0 1.6 12.8 86.5 2.3 3.3
80 17.9 1.7 12.0 98.4 3.0 15.5 1.7 12.0 95.9 2.4 3.1
60 19.4 1.6 14.1 80.0 3.6 17.1 1.5 14.1 77.6 2.2 3.7
30 5.5 2.1 4.9 70 18.9 1.6 13.3 89.5 3.4 16.5 1.6 13.3 87.0 2.3 3.4
80 18.4 1.7 12.5 98.9 3.1 15.9 1.7 12.5 96.4 2.4 3.2
60 20.0 1.6 14.6 80.6 3.7 17.6 1.5 14.6 78.1 2.3 3.8
7.0 3.2 7.5 70 19.5 1.7 13.8 90.0 3.4 16.9 1.6 13.8 87.4 2.4 3.5
80 18.9 1.7 13.0 99.5 3.2 16.3 1.7 13.0 96.8 2.5 3.2
60 26.5 1.7 20.6 87.2 4.5 23.2 1.7 20.6 83.9 3.1 4.6
4.0 1.2 2.8 70 25.6 1.8 19.4 96.4 4.1 22.3 1.8 19.4 92.9 3.2 4.2
80 24.8 1.9 18.2 105.5 3.8 21.3 1.9 18.2 101.9 3.3 3.9
60 27.4 1.7 21.4 88.2 4.6 24.0 1.7 21.5 84.7 3.3 4.7
50 5.5 2.1 4.9 70 26.5 1.8 20.2 97.2 4.2 23.0 1.8 20.3 93.7 3.4 4.3
80 25.6 1.9 19.0 106.3 3.9 22.0 1.9 19.1 102.6 3.5 4.0
60 28.0 1.8 21.9 88.8 4.7 24.6 1.7 22.0 85.3 3.3 4.8
7.0 3.2 7.5 70 27.0 1.9 20.7 97.8 4.3 23.5 1.8 20.8 94.2 3.4 4.4
80 26.1 1.9 19.5 106.9 3.9 22.5 1.9 19.6 103.1 3.5 4.0
60 33.2 1.9 26.8 94.2 5.2 29.1 1.8 27.0 90.0 4.1 5.4
4.0 1.2 2.8 70 32.0 2.0 25.3 103.0 4.8 27.8 1.9 25.5 98.6 4.2 4.9
80 30.9 2.1 23.8 111.7 4.4 26.5 2.0 24.0 107.2 4.3 4.5
60 34.3 1.9 27.9 95.3 5.3 30.2 1.8 28.2 91.0 4.3 5.5
70 5.5 2.1 4.9 70 33.1 2.0 26.3 104.1 4.9 28.8 1.9 26.6 99.6 4.4 5.1
80 31.9 2.1 24.7 112.8 4.5 27.4 2.0 25.0 108.2 4.5 4.6
60 35.0 1.9 28.5 96.1 5.4 30.7 1.8 28.8 91.6 4.4 5.6
7.0 3.2 7.5 70 33.8 2.0 26.9 104.8 4.9 29.3 1.9 27.2 100.1 4.5 5.1
80 32.5 2.1 25.3 113.4 4.5 27.9 2.0 25.6 108.7 4.6 4.7
60 39.5 1.9 32.9 100.6 6.0 34.5 1.8 33.3 95.5 5.0 6.3
4.0 1.2 2.8 70 37.9 2.0 31.0 109.0 5.5 32.8 1.9 31.4 103.8 5.2 5.8
80 36.4 2.1 29.1 117.5 5.0 31.1 2.0 29.5 112.0 5.4 5.3
60 40.9 2.0 34.2 102.1 6.1 35.9 1.9 34.8 96.9 5.2 6.5
90 5.5 2.1 4.9 70 39.3 2.1 32.3 110.5 5.6 34.1 2.0 32.8 105.1 5.4 5.9
80 37.8 2.2 30.4 118.9 5.1 32.3 2.1 30.8 113.2 5.6 5.4
60 41.5 2.0 34.8 102.7 6.1 36.3 1.9 35.3 97.3 5.4 6.5
7.0 3.2 7.5 70 39.9 2.1 32.8 111.1 5.6 34.5 2.0 33.3 105.5 5.6 5.9
80 38.3 2.2 30.8 119.4 5.1 32.6 2.1 31.3 113.6 5.8 5.4

Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
28
E SERIES SPECIFICATION CATALOG

E030
Cooling Capacity Data (900 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 32.4 22.2 1.32 37.4 24.5 32.4 22.2 1.30 37.3 1.9 24.9
4.0 1.2 2.7 80/67 35.2 23.1 1.35 39.8 26.1 35.2 23.1 1.33 39.7 2.0 26.5
85/71 38.0 24.0 1.37 42.1 27.7 38.0 24.0 1.35 42.1 2.1 28.1
75/63 32.4 22.4 1.27 37.3 25.6 32.4 22.4 1.26 37.3 1.8 25.8
50 5.5 2.0 4.7 80/67 35.3 23.3 1.30 39.7 27.2 35.3 23.3 1.29 39.7 1.9 27.4
85/71 38.1 24.2 1.32 42.1 28.8 38.1 24.2 1.31 42.0 2.0 29.1
75/63 32.8 22.4 1.25 37.6 26.3 32.8 22.4 1.24 37.6 1.6 26.5
7.0 3.1 7.2 80/67 35.7 23.3 1.28 40.0 28.0 35.7 23.3 1.27 40.0 1.7 28.2
85/71 38.5 24.2 1.30 42.4 29.6 38.5 24.2 1.29 42.4 1.8 29.9
75/63 29.2 20.8 1.54 34.9 18.9 29.3 20.9 1.50 34.9 3.6 19.5
4.0 1.1 2.5 80/67 31.8 21.7 1.58 37.1 20.2 31.9 21.8 1.54 37.1 3.7 20.8
85/71 34.3 22.6 1.61 39.4 21.4 34.4 22.7 1.57 39.3 3.8 22.0
75/63 29.3 20.9 1.48 34.8 19.7 29.5 21.0 1.47 34.9 3.4 20.1
70 5.5 2.0 4.5 80/67 31.9 21.8 1.52 37.0 21.0 32.1 21.9 1.50 37.2 3.5 21.4
85/71 34.4 22.7 1.55 39.3 22.3 34.6 22.8 1.52 39.4 3.6 22.7
75/63 29.6 21.0 1.46 35.0 20.3 29.8 21.0 1.45 35.2 3.1 20.6
7.0 3.0 6.9 80/67 32.2 21.9 1.49 37.2 21.7 32.4 21.9 1.48 37.4 3.2 21.9
85/71 34.7 22.8 1.51 39.5 22.9 35.0 22.8 1.50 39.6 3.3 23.2
75/63 24.7 19.1 1.99 31.8 12.4 25.0 19.2 1.94 31.9 5.2 12.9
4.0 1.1 2.5 80/67 26.9 19.9 2.04 33.8 13.2 27.2 20.0 1.98 33.9 5.4 13.8
85/71 29.0 20.7 2.08 35.8 14.0 29.3 20.8 2.01 35.9 5.6 14.6
75/63 24.9 19.2 1.92 31.7 13.0 25.2 19.3 1.88 31.9 4.9 13.4
90 5.5 1.9 4.4 80/67 27.1 20.0 1.96 33.7 13.8 27.4 20.1 1.92 33.9 5.1 14.3
85/71 29.2 20.8 1.99 35.8 14.7 29.6 20.9 1.95 35.9 5.3 15.1
75/63 25.2 19.2 1.88 31.9 13.4 25.4 19.3 1.87 32.0 4.6 13.6
7.0 2.9 6.7 80/67 27.4 20.0 1.92 33.9 14.3 27.6 20.1 1.91 34.1 4.7 14.5
85/71 29.6 20.8 1.95 35.9 15.1 29.8 20.9 1.94 36.1 4.8 15.3
75/63 20.7 17.5 2.29 28.6 9.0 20.9 17.6 2.21 28.6 6.9 9.5
4.0 1.1 2.5 80/67 22.5 18.2 2.34 30.4 9.6 22.8 18.3 2.26 30.5 7.1 10.1
85/71 24.3 18.9 2.38 32.3 10.2 24.6 19.0 2.30 32.3 7.3 10.7
75/63 20.8 17.5 2.21 28.4 9.4 21.1 17.6 2.15 28.6 6.5 9.8
110 5.5 1.8 4.3 80/67 22.6 18.2 2.26 30.3 10.0 23.0 18.3 2.20 30.5 6.7 10.5
85/71 24.4 18.9 2.30 32.1 10.6 24.8 19.0 2.24 32.3 6.9 11.1
75/63 20.9 17.6 2.16 28.5 9.7 21.3 17.7 2.14 28.8 6.0 10.0
7.0 2.8 6.5 80/67 22.8 18.3 2.21 30.3 10.3 23.2 18.4 2.19 30.6 6.2 10.6
85/71 24.6 19.0 2.25 32.1 10.9 25.0 19.1 2.23 32.5 6.4 11.2

Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
29
E SERIES SPECIFICATION CATALOG

E035
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
900 22.4 1.97 15.7 93.1 3.34 18.9 1.91 15.9 89.5 3.5 3.43
5.0 2.2 5.0
1100 22.9 2.01 16.0 89.2 3.33 19.6 1.98 16.0 86.5 3.1 3.37
900 23.1 1.97 16.4 93.8 3.43 19.5 1.91 16.5 90.1 3.5 3.53
30 7.0 3.6 8.4
1100 23.6 2.01 16.7 89.8 3.43 20.3 1.97 16.7 87.1 3.2 3.48
900 23.7 1.99 16.9 94.3 3.48 20.0 1.93 17.0 90.6 3.6 3.58
9.0 5.7 13.2
1100 24.1 2.03 17.2 90.3 3.48 20.8 1.99 17.2 87.5 3.2 3.53
900 30.6 2.25 23.0 101.5 3.99 26.1 2.15 23.2 96.9 4.4 4.15
5.0 2.1 4.7
1100 31.3 2.27 23.6 96.4 4.05 27.4 2.20 23.7 93.1 3.8 4.15
900 31.6 2.26 23.9 102.5 4.09 27.0 2.16 24.1 97.8 4.5 4.27
50 7.0 3.4 7.9
1100 32.4 2.28 24.6 97.3 4.17 28.3 2.21 24.7 93.9 3.9 4.28
900 32.3 2.29 24.5 103.2 4.14 27.6 2.19 24.7 98.4 4.6 4.32
9.0 5.4 12.4
1100 33.1 2.30 25.3 97.9 4.22 29.0 2.23 25.4 94.4 4.0 4.33
900 38.1 2.47 29.6 109.2 4.51 32.6 2.34 29.9 103.5 5.3 4.75
5.0 1.9 4.3
1100 39.2 2.46 30.8 103.0 4.67 34.5 2.37 31.0 99.1 4.6 4.84
900 39.4 2.51 30.8 110.5 4.60 33.7 2.36 31.1 104.7 5.5 4.87
70 7.0 3.2 7.4
1100 40.6 2.48 32.1 104.1 4.78 35.8 2.39 32.4 100.2 4.7 4.97
900 40.1 2.54 31.4 111.2 4.63 34.3 2.38 31.7 105.3 5.6 4.90
9.0 5.0 11.6
1100 41.3 2.51 32.7 104.8 4.82 36.5 2.41 33.1 100.7 4.8 5.02
900 44.9 2.63 36.0 116.2 5.02 38.4 2.44 36.3 109.5 6.3 5.36
5.0 1.8 4.3
1100 46.5 2.57 37.8 109.2 5.30 41.3 2.45 38.3 104.8 5.3 5.57
900 46.6 2.67 37.4 117.9 5.10 39.8 2.48 37.8 110.9 6.5 5.47
90 7.0 3.1 7.1
1100 48.3 2.61 39.4 110.6 5.41 42.9 2.49 39.9 106.1 5.5 5.71
900 47.2 2.71 38.0 118.5 5.11 40.3 2.50 38.3 111.4 6.6 5.49
9.0 4.8 11.2
1100 49.0 2.64 40.0 111.2 5.44 43.5 2.51 40.6 106.6 5.6 5.74
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

30
E SERIES SPECIFICATION CATALOG

E035
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
900 39.7 23.8 1.58 45.1 25.2 39.7 23.8 1.55 42.5 2.5 25.5
5.0 2.1 4.7
1100 40.9 26.8 1.68 46.7 24.4 40.9 26.8 1.65 44.0 2.6 24.7
900 39.8 24.0 1.52 45.0 26.2 39.8 24.0 1.50 42.6 2.4 26.5
50 7.0 3.4 7.9
1100 41.0 26.9 1.62 46.6 25.4 41.0 26.9 1.60 44.1 2.5 25.7
900 40.2 24.0 1.49 45.3 27.0 40.2 24.0 1.48 43.0 2.2 27.2
9.0 5.4 12.4
1100 41.5 26.9 1.58 46.9 26.2 41.5 26.9 1.57 44.5 2.3 26.3
900 36.1 22.8 1.95 42.7 18.5 36.3 22.9 1.91 38.6 4.2 19.0
5.0 1.9 4.3
1100 37.2 25.6 2.06 44.2 18.1 37.4 25.6 2.01 39.9 4.3 18.6
900 36.2 22.9 1.88 42.6 19.3 36.4 22.9 1.85 38.9 3.9 19.7
70 7.0 3.2 7.4
1100 37.3 25.6 1.98 44.1 18.9 37.5 25.7 1.95 40.2 4.0 19.3
900 36.6 22.9 1.84 42.9 19.9 36.8 23.0 1.83 39.4 3.6 20.1
9.0 5.0 11.6
1100 37.7 25.7 1.94 44.3 19.4 37.9 25.7 1.92 40.8 3.7 19.7
900 31.7 21.3 2.39 39.9 13.3 32.0 21.4 2.32 34.1 5.8 13.8
5.0 1.8 4.3
1100 32.7 23.8 2.49 41.2 13.1 33.0 23.9 2.41 35.3 6.0 13.7
900 31.9 21.3 2.30 39.7 13.9 32.2 21.4 2.25 34.5 5.4 14.3
90 7.0 3.1 7.1
1100 32.9 23.8 2.39 41.0 13.7 33.2 23.9 2.35 35.7 5.6 14.2
900 32.2 21.4 2.25 39.9 14.3 32.5 21.5 2.23 35.2 4.9 14.6
9.0 4.8 11.2
1100 33.2 23.9 2.35 41.2 14.1 33.5 24.0 2.32 36.4 5.1 14.4
900 26.7 19.4 2.80 36.3 9.5 27.1 19.5 2.70 28.8 7.5 10.0
5.0 1.8 4.1
1100 27.5 21.6 2.89 37.4 9.5 27.9 21.7 2.78 29.7 7.7 10.0
900 26.9 19.4 2.70 36.1 10.0 27.3 19.5 2.63 29.3 6.9 10.4
110 7.0 3.0 6.9
1100 27.7 21.6 2.78 37.2 10.0 28.1 21.8 2.71 30.2 7.1 10.4
900 27.1 19.5 2.64 36.1 10.3 27.5 19.6 2.61 30.1 6.3 10.5
9.0 4.7 10.8
1100 28.0 21.7 2.72 37.3 10.3 28.4 21.9 2.69 31.1 6.5 10.5

Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

31
E SERIES SPECIFICATION CATALOG

E035
Heating Capacity Data (1100 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 23.6 1.9 17.0 79.9 3.6 20.3 1.9 17.0 77.1 3.0 3.6
5.0 2.2 5.0 70 22.9 2.0 16.0 89.3 3.3 19.7 2.0 16.0 86.6 3.1 3.3
80 22.2 2.1 15.0 98.7 3.1 19.0 2.1 15.0 96.0 3.2 3.1
60 24.3 1.9 17.7 80.4 3.7 21.1 1.9 17.7 77.7 3.1 3.7
30 7.0 3.6 8.4 70 23.6 2.0 16.7 89.9 3.4 20.3 2.0 16.7 87.1 3.2 3.5
80 23.0 2.1 15.7 99.3 3.2 19.5 2.1 15.7 96.4 3.3 3.2
60 24.9 1.9 18.2 80.9 3.7 21.6 1.9 18.2 78.2 3.1 3.8
9.0 5.7 13.2 70 24.2 2.1 17.2 90.4 3.5 20.9 2.0 17.2 87.6 3.2 3.5
80 23.5 2.2 16.2 99.8 3.2 20.1 2.1 16.2 96.9 3.3 3.2
60 32.4 2.2 25.0 87.3 4.4 28.6 2.1 25.1 84.1 3.7 4.5
5.0 2.1 4.7 70 31.4 2.3 23.6 96.4 4.0 27.5 2.2 23.7 93.1 3.8 4.1
80 30.4 2.4 22.2 105.6 3.7 26.3 2.3 22.3 102.2 3.9 3.8
60 33.5 2.2 26.1 88.2 4.5 29.6 2.1 26.2 84.9 3.8 4.6
50 7.0 3.4 7.9 70 32.5 2.3 24.6 97.3 4.1 28.4 2.2 24.7 93.9 3.9 4.2
80 31.4 2.4 23.1 106.4 3.8 27.2 2.3 23.2 102.9 4.0 3.9
60 34.3 2.2 26.8 88.9 4.6 30.3 2.1 26.9 85.5 3.9 4.7
9.0 5.4 12.4 70 33.2 2.3 25.3 98.0 4.2 29.1 2.3 25.4 94.5 4.0 4.3
80 32.1 2.4 23.8 107.0 3.9 27.8 2.4 23.9 103.4 4.1 4.0
60 40.7 2.4 32.6 94.3 5.1 36.1 2.3 32.9 90.4 4.5 5.2
5.0 1.9 4.3 70 39.3 2.5 30.8 103.1 4.6 34.6 2.4 31.0 99.1 4.6 4.8
80 37.8 2.6 29.0 111.9 4.3 33.0 2.5 29.1 107.8 4.7 4.4
60 42.1 2.4 34.0 95.5 5.2 37.6 2.3 34.3 91.7 4.6 5.4
70 7.0 3.2 7.4 70 40.6 2.5 32.1 104.2 4.8 35.9 2.4 32.4 100.2 4.7 4.9
80 39.1 2.6 30.2 112.9 4.4 34.3 2.5 30.5 108.8 4.8 4.5
60 42.9 2.4 34.7 96.1 5.2 38.3 2.3 35.1 92.2 4.7 5.5
9.0 5.0 11.6 70 41.3 2.5 32.7 104.8 4.8 36.6 2.4 33.1 100.8 4.8 5.0
80 39.8 2.7 30.7 113.5 4.4 34.9 2.6 31.1 109.4 4.9 4.6
60 48.5 2.5 40.1 100.8 5.8 43.5 2.3 40.6 96.6 5.1 6.1
5.0 1.8 4.3 70 46.6 2.6 37.8 109.3 5.3 41.4 2.5 38.3 104.9 5.3 5.5
80 44.8 2.7 35.5 117.7 4.8 39.4 2.6 36.0 113.2 5.5 5.1
60 50.3 2.5 41.8 102.3 5.9 45.1 2.4 42.3 98.0 5.3 6.2
90 7.0 3.1 7.1 70 48.4 2.6 39.4 110.7 5.4 43.0 2.5 39.9 106.2 5.5 5.7
80 46.5 2.8 37.0 119.1 4.9 40.8 2.6 37.5 114.4 5.7 5.2
60 51.0 2.5 42.4 103.0 5.9 45.8 2.4 43.0 98.6 5.4 6.2
9.0 4.8 11.2 70 49.1 2.7 40.0 111.3 5.4 43.6 2.5 40.6 106.7 5.6 5.7
80 47.1 2.8 37.6 119.7 4.9 41.5 2.7 38.2 114.9 5.8 5.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

32
E SERIES SPECIFICATION CATALOG

E035
Cooling Capacity Data (1100 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 37.6 25.7 1.67 43.9 22.6 37.6 25.7 1.64 43.8 2.5 23.0
5.0 2.1 4.7 80/67 40.9 26.8 1.70 46.7 24.0 40.9 26.8 1.67 46.6 2.6 24.5
85/71 44.2 27.9 1.73 49.5 25.5 44.2 27.9 1.70 49.4 2.7 25.9
75/63 37.7 25.8 1.61 43.8 23.5 37.7 25.8 1.59 43.7 2.4 23.7
50 7.0 3.4 7.9 80/67 41.0 26.9 1.64 46.6 25.0 41.0 26.9 1.62 46.5 2.5 25.3
85/71 44.3 28.0 1.67 49.4 26.5 44.3 28.0 1.65 49.3 2.6 26.8
75/63 38.2 25.8 1.57 44.1 24.3 38.2 25.8 1.56 44.1 2.2 24.5
9.0 5.4 12.4 80/67 41.5 26.9 1.60 46.9 25.9 41.5 26.9 1.59 46.9 2.3 26.1
85/71 44.8 28.0 1.63 49.8 27.5 44.8 28.0 1.62 49.7 2.4 27.6
75/63 34.2 24.6 2.04 41.6 16.8 34.4 24.6 1.99 41.6 4.2 17.3
5.0 1.9 4.3 80/67 37.2 25.6 2.08 44.3 17.9 37.4 25.6 2.03 44.3 4.3 18.4
85/71 40.2 26.6 2.12 46.9 18.9 40.4 26.6 2.07 47.0 4.4 19.5
75/63 34.3 24.6 1.96 41.5 17.5 34.5 24.7 1.93 41.6 3.9 17.9
70 7.0 3.2 7.4 80/67 37.3 25.6 2.00 44.1 18.6 37.5 25.7 1.97 44.2 4.0 19.0
85/71 40.3 26.6 2.04 46.8 19.7 40.5 26.7 2.01 46.9 4.1 20.1
75/63 34.7 24.7 1.92 41.7 18.0 34.9 24.7 1.90 41.8 3.6 18.3
9.0 5.0 11.6 80/67 37.7 25.7 1.96 44.4 19.2 37.9 25.7 1.94 44.5 3.7 19.5
85/71 40.7 26.7 2.00 47.0 20.4 40.9 26.7 1.98 47.2 3.8 20.7
75/63 30.1 22.8 2.46 38.8 12.2 30.3 22.9 2.38 38.8 5.8 12.7
5.0 1.8 4.3 80/67 32.7 23.8 2.51 41.2 13.0 33.0 23.9 2.43 41.3 6.0 13.6
85/71 35.3 24.8 2.56 43.7 13.8 35.6 24.9 2.48 43.7 6.2 14.4
75/63 30.3 22.8 2.36 38.6 12.8 30.5 22.9 2.32 38.8 5.4 13.1
90 7.0 3.1 7.1 80/67 32.9 23.8 2.41 41.1 13.6 33.2 23.9 2.37 41.3 5.6 14.0
85/71 35.5 24.8 2.46 43.6 14.4 35.8 24.9 2.42 43.7 5.8 14.8
75/63 30.5 22.9 2.32 38.8 13.1 30.8 23.0 2.29 39.0 4.9 13.4
9.0 4.8 11.2 80/67 33.2 23.9 2.37 41.3 14.0 33.5 24.0 2.34 41.5 5.1 14.3
85/71 35.8 24.9 2.42 43.7 14.8 36.2 25.0 2.39 44.0 5.3 15.2
75/63 25.3 20.7 2.85 35.2 8.9 25.7 20.8 2.74 35.2 7.5 9.3
5.0 1.8 4.1 80/67 27.5 21.6 2.91 37.4 9.4 27.9 21.7 2.80 37.4 7.7 10.0
85/71 29.7 22.5 2.97 39.7 10.0 30.1 22.6 2.86 39.7 7.9 10.5
75/63 25.5 20.7 2.74 35.0 9.3 25.8 20.9 2.68 35.2 6.9 9.7
110 7.0 3.0 6.9 80/67 27.7 21.6 2.80 37.2 9.9 28.1 21.8 2.73 37.4 7.1 10.3
85/71 29.9 22.5 2.86 39.5 10.5 30.3 22.7 2.78 39.6 7.3 10.9
75/63 25.7 20.8 2.69 35.1 9.6 26.1 21.0 2.66 35.4 6.3 9.8
9.0 4.7 10.8 80/67 28.0 21.7 2.74 37.3 10.2 28.4 21.9 2.71 37.6 6.5 10.5
85/71 30.2 22.6 2.79 39.6 10.8 30.7 22.8 2.76 39.9 6.7 11.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

33
E SERIES SPECIFICATION CATALOG

E036
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
800 22.9 1.91 16.4 96.5 3.52 20.0 1.88 17.1 93.2 3.4 3.67
5.0 1.6 3.6 1000 23.6 1.92 17.0 91.8 3.59 20.7 1.89 17.5 89.1 3.3 3.71
1200 24.3 1.99 17.5 88.8 3.58 21.3 1.95 17.7 86.5 3.1 3.66
800 23.5 1.94 16.9 97.2 3.55 20.5 1.90 17.6 93.8 3.5 3.70
30 7.0 2.9 6.8 1000 24.2 1.95 17.5 92.4 3.64 21.2 1.91 18.0 89.6 3.3 3.76
1200 24.9 2.01 18.1 89.2 3.64 21.8 1.97 18.3 86.9 3.2 3.72
800 24.0 1.97 17.2 97.7 3.56 20.9 1.93 17.9 94.2 3.6 3.72
9.0 4.7 10.8 1000 24.6 1.97 17.9 92.8 3.66 21.5 1.93 18.3 89.9 3.4 3.78
1200 25.4 2.03 18.4 89.6 3.66 22.2 1.99 18.6 87.1 3.2 3.74
800 29.3 2.28 21.5 103.9 3.77 25.3 2.19 22.3 99.3 4.4 3.98
5.0 1.5 3.5 1000 30.1 2.18 22.7 97.9 4.05 26.1 2.11 23.1 94.2 4.1 4.21
1200 31.0 2.21 23.5 93.9 4.11 27.0 2.15 23.5 90.8 3.9 4.20
800 30.4 2.34 22.4 105.2 3.80 26.3 2.25 23.2 100.4 4.6 4.02
50 7.0 2.8 6.5 1000 31.2 2.23 23.6 98.9 4.10 27.1 2.15 24.0 95.1 4.3 4.27
1200 32.2 2.26 24.5 94.8 4.17 28.0 2.19 24.5 91.6 4.0 4.27
800 31.0 2.38 22.9 105.9 3.82 26.9 2.28 23.7 101.1 4.6 4.05
9.0 4.5 10.4 1000 31.9 2.25 24.2 99.5 4.15 27.7 2.17 24.6 95.7 4.3 4.32
1200 32.9 2.28 25.1 95.4 4.22 28.6 2.21 25.1 92.1 4.0 4.32
800 39.5 2.64 30.5 115.7 4.38 34.6 2.50 31.4 110.1 5.3 4.69
5.0 1.4 3.3 1000 40.8 2.42 32.6 107.8 4.94 35.9 2.31 33.0 103.3 4.9 5.18
1200 42.2 2.42 33.9 102.5 5.11 37.1 2.33 33.7 98.6 4.6 5.23
800 41.4 2.75 32.0 117.9 4.41 36.3 2.59 33.0 112.1 5.5 4.73
70 7.0 2.6 6.1 1000 42.9 2.50 34.3 109.7 5.02 37.7 2.38 34.7 104.9 5.1 5.27
1200 44.3 2.50 35.8 104.2 5.20 38.9 2.40 35.4 100.0 4.7 5.33
800 42.5 2.80 32.9 119.2 4.45 37.3 2.63 33.9 113.2 5.6 4.78
9.0 4.2 9.7 1000 44.0 2.53 35.4 110.7 5.09 38.7 2.41 35.7 105.9 5.2 5.35
1200 45.5 2.52 36.9 105.1 5.28 40.0 2.42 36.5 100.8 4.8 5.42
800 45.9 3.04 35.6 123.1 4.43 39.8 2.81 36.5 116.0 6.3 4.81
5.0 1.4 3.1 1000 47.7 2.66 38.7 114.2 5.26 41.6 2.50 38.9 108.5 5.8 5.55
1200 49.4 2.62 40.5 108.1 5.53 43.0 2.49 39.8 103.2 5.3 5.68
800 48.7 3.20 37.7 126.3 4.46 42.3 2.95 38.7 118.9 6.5 4.84
90 7.0 2.5 5.8 1000 50.7 2.78 41.2 116.9 5.34 44.2 2.61 41.3 110.9 6.0 5.64
1200 52.5 2.73 43.2 110.5 5.64 45.7 2.59 42.3 105.3 5.5 5.78
800 50.1 3.25 39.0 128.0 4.51 43.6 2.99 40.0 120.4 6.6 4.91
9.0 4.0 9.3 1000 52.3 2.82 42.6 118.4 5.44 45.6 2.63 42.7 112.2 6.1 5.76
1200 54.1 2.75 44.7 111.8 5.76 47.1 2.62 43.8 106.4 5.6 5.91
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
34
E SERIES SPECIFICATION CATALOG

E036
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
800 38.8 22.0 1.64 44.4 23.6 40.0 21.7 1.63 43.2 2.3 24.6
5.0 1.5 3.5 1000 41.9 25.0 1.73 47.8 24.2 43.2 24.8 1.72 46.6 2.5 25.2
1200 44.1 27.8 1.82 50.3 24.2 45.4 27.5 1.81 49.0 2.6 25.2
800 39.6 22.2 1.54 44.9 25.7 40.8 22.2 1.53 43.9 2.2 26.8
50 7.0 2.8 6.5 1000 42.8 25.3 1.63 48.3 26.3 44.1 25.3 1.61 47.2 2.3 27.4
1200 45.0 28.1 1.71 50.9 26.3 46.4 28.1 1.70 49.7 2.5 27.4
800 40.0 23.7 1.50 45.2 26.6 41.2 23.9 1.49 44.3 2.0 27.7
9.0 4.5 10.4 1000 43.2 27.0 1.59 48.6 27.2 44.5 27.3 1.57 47.7 2.2 28.3
1200 45.5 30.0 1.67 51.2 27.2 46.8 30.3 1.66 50.2 2.3 28.3
800 36.4 21.9 2.02 43.4 18.0 37.4 21.8 2.00 40.3 3.9 18.6
5.0 1.4 3.3 1000 38.6 24.7 2.10 45.8 18.3 39.5 24.6 2.08 42.5 4.1 19.0
1200 40.3 27.5 2.18 47.7 18.5 41.3 27.3 2.16 44.4 4.3 19.1
800 37.4 22.1 1.93 44.0 19.3 38.3 22.2 1.91 41.2 3.6 20.0
70 7.0 2.6 6.1 1000 39.6 25.0 2.01 46.4 19.7 40.6 25.1 1.99 43.5 3.8 20.4
1200 41.3 27.7 2.08 48.4 19.8 42.4 27.9 2.06 45.4 4.0 20.5
800 37.8 23.0 1.89 44.2 20.0 38.7 23.3 1.87 41.7 3.4 20.7
9.0 4.2 9.7 1000 40.0 26.0 1.96 46.7 20.4 41.0 26.3 1.94 44.1 3.5 21.1
1200 41.8 28.8 2.04 48.7 20.5 42.8 29.2 2.02 46.0 3.7 21.2
800 32.6 21.0 2.40 40.8 13.6 33.3 21.0 2.38 35.8 5.6 14.0
5.0 1.4 3.1 1000 33.9 23.5 2.45 42.2 13.8 34.5 23.5 2.43 37.0 5.8 14.2
1200 35.1 26.1 2.51 43.7 14.0 35.8 26.1 2.48 38.3 6.0 14.4
800 33.6 21.2 2.33 41.6 14.4 34.3 21.4 2.31 37.0 5.2 14.9
90 7.0 2.5 5.8 1000 34.9 23.8 2.38 43.1 14.6 35.6 24.0 2.36 38.3 5.4 15.1
1200 36.2 26.4 2.44 44.5 14.8 36.9 26.6 2.41 39.6 5.6 15.3
800 34.0 21.4 2.28 41.8 14.9 34.6 21.9 2.26 37.6 4.8 15.3
9.0 4.0 9.3 1000 35.3 24.0 2.34 43.3 15.1 36.0 24.5 2.31 38.9 4.9 15.5
1200 36.6 26.6 2.39 44.7 15.3 37.3 27.2 2.37 40.3 5.1 15.8
800 27.6 20.1 2.80 37.1 9.8 28.0 20.2 2.77 30.1 7.4 10.1
5.0 1.3 2.9 1000 28.1 22.3 2.82 37.8 10.0 28.5 22.4 2.80 30.6 7.5 10.2
1200 28.9 24.7 2.85 38.6 10.2 29.4 24.8 2.82 31.3 7.7 10.4
800 28.6 20.3 2.77 38.0 10.3 29.0 20.6 2.74 31.6 6.8 10.6
110 7.0 2.3 5.4 1000 29.2 22.5 2.79 38.7 10.4 29.6 22.9 2.76 32.1 6.9 10.7
1200 30.0 25.0 2.81 39.6 10.7 30.4 25.3 2.79 32.8 7.1 10.9
800 28.9 19.9 2.72 38.2 10.6 29.3 20.4 2.69 32.3 6.2 10.9
9.0 3.7 8.6 1000 29.5 22.2 2.74 38.8 10.7 29.9 22.7 2.72 32.8 6.4 11.0
1200 30.3 24.5 2.77 39.7 11.0 30.7 25.1 2.74 33.6 6.5 11.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
35
E SERIES SPECIFICATION CATALOG

E036
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
600 9.5 0.85 6.6 92.6 3.27 8.7 0.84 6.8 88.9 1.0 3.38
3.0 0.7 1.5 700 9.8 0.85 6.9 89.0 3.38 9.0 0.84 7.1 86.2 0.9 3.47
800 10.2 0.87 7.2 86.2 3.43 9.5 0.86 7.4 84.0 0.9 3.50
600 9.8 0.86 6.8 93.5 3.33 8.9 0.84 7.0 89.7 1.0 3.45
30 4.0 1.1 2.5 700 10.0 0.85 7.1 89.8 3.45 9.2 0.84 7.3 86.9 0.9 3.55
800 10.5 0.88 7.5 86.9 3.50 9.7 0.87 7.6 84.6 0.9 3.58
600 10.4 0.88 7.4 93.8 3.46 9.5 0.86 7.6 89.9 1.0 3.58
5.0 1.6 3.7 700 10.7 0.87 7.7 90.0 3.58 9.9 0.86 7.9 87.0 0.9 3.69
800 11.1 0.90 8.1 87.1 3.64 10.4 0.89 8.2 84.8 0.9 3.72
600 14.3 0.92 11.2 100.5 4.59 13.1 0.88 11.6 95.3 1.4 4.84
3.0 0.6 1.4 700 14.8 0.90 11.7 95.5 4.79 13.7 0.88 11.9 91.8 1.2 4.98
800 15.2 0.91 12.1 91.9 4.88 14.3 0.90 12.2 89.2 1.0 4.99
600 14.8 0.92 11.7 101.8 4.74 13.6 0.88 12.1 96.5 1.5 5.01
50 4.0 1.0 2.2 700 15.3 0.90 12.2 96.6 4.96 14.2 0.88 12.4 92.8 1.3 5.16
800 15.7 0.91 12.6 92.8 5.05 14.8 0.90 12.8 90.0 1.1 5.17
600 15.5 0.94 12.3 102.4 4.85 14.3 0.90 12.7 96.9 1.5 5.13
5.0 1.5 3.4 700 16.0 0.92 12.8 97.0 5.07 14.9 0.90 13.1 93.2 1.3 5.28
800 16.5 0.94 13.3 93.2 5.16 15.5 0.92 13.4 90.4 1.1 5.29
600 19.9 0.98 16.5 108.1 5.96 18.3 0.92 17.0 101.4 1.9 6.41
3.0 0.5 1.2 700 20.5 0.95 17.2 101.6 6.28 19.0 0.91 17.5 97.0 1.5 6.60
800 20.9 0.96 17.6 97.3 6.40 19.6 0.93 17.6 94.0 1.2 6.57
600 20.7 0.97 17.4 109.8 6.24 19.1 0.92 17.9 102.8 2.0 6.73
70 4.0 0.8 1.8 700 21.3 0.95 18.1 103.0 6.58 19.9 0.91 18.4 98.2 1.6 6.93
800 21.7 0.95 18.5 98.6 6.71 20.4 0.92 18.5 95.2 1.2 6.88
600 21.3 1.00 17.9 110.9 6.26 19.6 0.94 18.4 103.7 2.0 6.77
5.0 1.4 3.3 700 21.9 0.97 18.6 103.9 6.61 20.4 0.93 18.9 98.9 1.6 6.96
800 22.3 0.97 19.0 99.4 6.74 20.9 0.94 19.0 95.9 1.3 6.91
600 24.4 1.01 21.0 113.1 7.10 22.4 0.93 21.6 104.6 2.4 7.79
3.0 0.4 0.9 700 25.1 0.98 21.8 105.6 7.53 23.3 0.92 22.0 99.8 1.9 8.00
800 25.3 0.96 22.0 100.9 7.69 23.6 0.93 21.8 97.0 1.4 7.89
600 25.6 1.00 22.2 115.1 7.52 23.6 0.92 22.9 106.2 2.4 8.28
90 4.0 0.7 1.6 700 26.4 0.97 23.1 107.2 7.99 24.5 0.91 23.3 101.1 1.9 8.50
800 26.5 0.95 23.3 102.4 8.15 24.8 0.92 23.1 98.2 1.4 8.38
600 25.8 1.02 22.3 116.7 7.40 23.6 0.94 23.0 107.6 2.5 8.17
5.0 1.3 3.0 700 26.5 0.99 23.1 108.5 7.87 24.5 0.93 23.4 102.3 2.0 8.38
800 26.6 0.97 23.3 103.6 8.03 24.8 0.93 23.1 99.3 1.4 8.25
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
36
E SERIES SPECIFICATION CATALOG

E036
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
600 21.2 13.7 0.64 23.4 33.1 21.4 13.7 0.63 22.9 0.7 33.8
3.0 0.6 1.4 700 21.8 14.9 0.65 24.0 33.8 22.0 14.9 0.64 23.5 0.7 34.4
800 22.4 16.5 0.66 24.6 34.0 22.6 16.5 0.65 24.1 0.7 34.7
600 21.4 13.8 0.62 23.5 34.3 21.5 13.8 0.62 23.1 0.5 34.8
50 4.0 1.0 2.2 700 22.0 15.0 0.63 24.1 35.0 22.1 15.0 0.62 23.7 0.5 35.5
800 22.6 16.6 0.64 24.8 35.2 22.7 16.6 0.63 24.3 0.6 35.8
600 21.8 14.2 0.62 23.9 35.2 21.8 14.2 0.61 23.5 0.4 35.5
5.0 1.5 3.4 700 22.3 15.4 0.62 24.5 35.9 22.3 15.4 0.62 24.0 0.4 36.2
800 23.0 17.0 0.64 25.1 36.1 23.0 17.0 0.63 24.7 0.4 36.5
600 19.1 13.5 0.84 22.0 22.9 19.4 13.4 0.82 20.2 2.0 23.6
3.0 0.5 1.2 700 19.6 14.6 0.84 22.5 23.3 19.9 14.5 0.83 20.7 2.0 24.0
800 20.2 16.2 0.86 23.1 23.5 20.5 16.0 0.85 21.3 2.1 24.2
600 19.3 13.6 0.81 22.1 23.7 19.5 13.6 0.80 20.5 1.7 24.2
70 4.0 0.8 1.8 700 19.8 14.7 0.82 22.6 24.2 20.0 14.7 0.81 21.0 1.8 24.7
800 20.4 16.3 0.84 23.2 24.4 20.6 16.3 0.83 21.6 1.8 24.9
600 19.6 13.9 0.81 22.4 24.3 19.7 14.0 0.80 21.0 1.5 24.7
5.0 1.4 3.3 700 20.1 15.1 0.81 22.9 24.8 20.2 15.2 0.81 21.5 1.5 25.1
800 20.7 16.7 0.83 23.5 25.0 20.8 16.8 0.82 22.1 1.6 25.4
600 16.2 12.5 1.02 19.7 15.9 16.5 12.2 1.00 16.6 3.3 16.5
3.0 0.4 0.9 700 16.6 13.5 1.03 20.1 16.2 16.9 13.3 1.01 17.0 3.4 16.8
800 17.1 15.0 1.05 20.6 16.3 17.4 14.7 1.03 17.4 3.5 17.0
600 16.3 12.6 0.99 19.7 16.4 16.6 12.5 0.98 16.9 3.0 16.9
90 4.0 0.7 1.6 700 16.7 13.6 1.00 20.2 16.7 17.0 13.6 0.99 17.3 3.0 17.2
800 17.2 15.1 1.02 20.7 16.9 17.5 15.0 1.00 17.8 3.1 17.4
600 16.6 12.9 0.99 19.9 16.8 16.8 13.0 0.98 17.5 2.6 17.2
5.0 1.3 3.0 700 17.0 14.0 0.99 20.4 17.2 17.2 14.1 0.98 17.9 2.6 17.5
800 17.5 15.5 1.01 20.9 17.3 17.7 15.6 1.00 18.4 2.7 17.7
600 12.9 10.5 1.19 16.9 10.8 13.2 10.2 1.16 12.5 4.7 11.4
3.0 0.3 0.6 700 13.2 11.4 1.20 17.3 11.0 13.5 11.0 1.17 12.8 4.8 11.6
800 13.6 12.6 1.22 17.7 11.1 13.9 12.2 1.19 13.1 4.9 11.7
600 13.0 10.6 1.16 16.9 11.2 13.2 10.5 1.14 13.0 4.2 11.6
110 4.0 0.6 1.4 700 13.3 11.5 1.17 17.3 11.4 13.6 11.4 1.15 13.2 4.3 11.9
800 13.7 12.7 1.19 17.8 11.5 14.0 12.6 1.17 13.6 4.4 11.9
600 13.2 10.8 1.15 17.1 11.5 13.4 11.0 1.14 13.6 3.7 11.8
5.0 1.2 2.8 700 13.6 11.7 1.16 17.5 11.7 13.8 11.9 1.15 13.9 3.8 12.0
800 13.9 13.0 1.18 18.0 11.8 14.1 13.2 1.17 14.3 3.9 12.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
37
E SERIES SPECIFICATION CATALOG

E040
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1000 27.4 2.37 19.3 95.4 3.39 23.1 2.28 19.5 91.4 4.2 3.51
5.0 1.7 3.9
1300 27.7 2.35 19.7 89.7 3.45 23.6 2.29 19.7 86.8 3.9 3.52
1000 28.3 2.40 20.1 96.2 3.46 23.8 2.30 20.3 92.0 4.4 3.59
30 8.0 3.5 8.0
1300 28.6 2.38 20.5 90.4 3.53 24.3 2.31 20.5 87.3 4.0 3.61
1000 28.7 2.40 20.5 96.6 3.51 24.1 2.30 20.7 92.3 4.5 3.64
11.0 4.9 11.4
1300 29.0 2.38 20.9 90.7 3.58 24.7 2.30 20.9 87.6 4.1 3.66
1000 35.7 2.50 27.2 103.1 4.18 30.2 2.39 27.5 98.0 5.4 4.37
5.0 1.6 3.7
1300 36.3 2.45 28.0 95.9 4.34 31.4 2.36 28.1 92.4 4.7 4.48
1000 37.2 2.56 28.5 104.5 4.25 31.4 2.44 28.7 99.1 5.7 4.46
50 8.0 3.3 7.7
1300 37.9 2.50 29.3 97.0 4.43 32.7 2.41 29.4 93.3 4.9 4.59
1000 38.0 2.58 29.2 105.2 4.31 32.0 2.45 29.5 99.7 5.8 4.52
11.0 4.7 10.9
1300 38.7 2.52 30.1 97.5 4.50 33.5 2.42 30.2 93.8 5.0 4.66
1000 43.2 2.67 34.0 110.0 4.74 36.4 2.52 34.4 103.7 6.6 5.00
5.0 1.5 3.5
1300 44.1 2.58 35.3 101.4 5.01 38.5 2.46 35.6 97.4 5.6 5.24
1000 45.2 2.76 35.8 111.9 4.80 38.1 2.60 36.2 105.3 6.9 5.08
70 8.0 3.2 7.4
1300 46.3 2.66 37.2 103.0 5.10 40.4 2.53 37.6 98.8 5.8 5.35
1000 46.4 2.79 36.9 113.0 4.87 39.1 2.63 37.2 106.2 7.1 5.15
11.0 4.5 10.5
1300 47.6 2.69 38.4 103.9 5.19 41.6 2.55 38.8 99.6 5.9 5.45
1000 50.1 2.83 40.4 116.4 5.18 42.0 2.65 40.8 108.9 7.8 5.51
5.0 1.5 3.5
1300 51.5 2.70 42.3 106.7 5.59 45.2 2.55 42.9 102.2 6.4 5.92
1000 52.8 2.97 42.7 118.9 5.22 44.3 2.76 43.1 111.0 8.2 5.57
90 8.0 3.1 7.2
1300 54.5 2.82 44.9 108.8 5.67 47.9 2.65 45.5 104.1 6.7 6.03
1000 54.5 3.02 44.2 120.4 5.29 45.8 2.81 44.6 112.4 8.4 5.66
11.0 4.4 10.2
1300 56.3 2.86 46.5 110.1 5.76 49.6 2.69 47.2 105.3 6.8 6.15
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

38
E SERIES SPECIFICATION CATALOG

E040
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1000 42.0 27.2 1.62 47.5 26.0 42.0 27.2 1.58 43.8 3.5 26.5
5.0 1.6 3.7
1300 43.7 30.5 1.70 49.5 25.7 43.7 30.5 1.67 45.7 3.7 26.2
1000 42.4 27.4 1.54 47.7 27.5 42.4 27.4 1.52 44.2 3.4 27.9
50 8.0 3.3 7.7
1300 44.2 30.8 1.62 49.7 27.2 44.2 30.8 1.60 46.1 3.5 27.6
1000 42.8 27.4 1.50 47.9 28.6 42.8 27.4 1.49 44.7 3.2 28.8
11.0 4.7 10.9
1300 44.6 30.8 1.58 50.0 28.3 44.6 30.8 1.57 46.7 3.3 28.5
1000 39.3 26.4 2.03 46.2 19.3 39.5 26.4 1.98 40.7 5.5 19.9
5.0 1.5 3.5
1300 40.7 29.6 2.13 47.9 19.1 40.9 29.7 2.07 42.2 5.8 19.7
1000 39.9 26.6 1.93 46.5 20.7 40.1 26.7 1.90 41.4 5.2 21.1
70 8.0 3.2 7.4
1300 41.3 29.9 2.02 48.2 20.5 41.5 30.0 1.98 42.9 5.4 20.9
1000 40.3 26.6 1.87 46.7 21.5 40.5 26.7 1.86 42.0 4.8 21.8
11.0 4.5 10.5
1300 41.7 29.9 1.96 48.4 21.3 41.9 30.0 1.94 43.6 5.0 21.6
1000 35.7 25.3 2.58 44.5 13.9 36.1 25.5 2.50 37.1 7.6 14.4
5.0 1.5 3.5
1300 36.8 28.5 2.69 46.0 13.7 37.2 28.6 2.61 38.3 7.8 14.3
1000 36.5 25.6 2.44 44.8 15.0 36.8 25.7 2.39 37.9 7.0 15.4
90 8.0 3.1 7.2
1300 37.6 28.8 2.54 46.2 14.8 38.0 28.9 2.49 39.2 7.3 15.3
1000 36.8 25.6 2.37 44.9 15.6 37.2 25.7 2.34 38.7 6.5 15.9
11.0 4.4 10.2
1300 38.0 28.8 2.46 46.4 15.4 38.3 28.9 2.44 40.0 6.7 15.7
1000 31.2 23.9 3.32 42.6 9.4 31.7 24.1 3.20 33.1 9.6 9.9
5.0 1.5 3.5
1300 32.0 26.9 3.44 43.8 9.3 32.5 27.1 3.32 34.0 9.9 9.8
1000 32.0 24.1 3.12 42.7 10.3 32.5 24.3 3.05 34.1 8.9 10.7
110 8.0 3.0 6.9
1300 32.9 27.1 3.24 43.9 10.2 33.4 27.3 3.16 35.0 9.1 10.6
1000 32.4 24.1 3.03 42.7 10.7 32.9 24.3 3.00 34.9 8.2 11.0
11.0 4.3 9.9
1300 33.2 27.1 3.14 43.9 10.6 33.7 27.3 3.10 35.9 8.4 10.9
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

39
E SERIES SPECIFICATION CATALOG

E040
Heating Capacity Data (1300 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 28.6 2.25 20.9 80.4 3.72 24.3 2.19 20.8 77.3 3.8 3.76
5.0 1.7 3.9 70 27.8 2.37 19.7 89.8 3.43 23.6 2.31 19.7 86.8 3.9 3.50
80 26.9 2.49 18.5 99.2 3.17 22.7 2.42 18.5 96.2 4.0 3.24
60 29.5 2.28 21.7 81.0 3.80 25.4 2.21 21.7 78.1 3.9 3.88
30 8.0 3.5 8.0 70 28.7 2.40 20.5 90.4 3.51 24.4 2.33 20.5 87.4 4.0 3.58
80 27.9 2.51 19.3 99.8 3.25 23.5 2.44 19.3 96.7 4.2 3.31
60 30.0 2.28 22.2 81.3 3.86 25.7 2.21 22.2 78.3 4.0 3.95
11.0 4.9 11.4 70 29.1 2.40 20.9 90.7 3.56 24.8 2.32 20.9 87.6 4.1 3.64
80 28.3 2.51 19.7 100.1 3.29 23.8 2.44 19.7 96.9 4.2 3.36
60 37.7 2.35 29.6 86.8 4.70 32.9 2.26 29.7 83.4 4.6 4.85
5.0 1.6 3.7 70 36.4 2.47 28.0 95.9 4.31 31.5 2.38 28.1 92.4 4.7 4.45
80 35.1 2.60 26.3 105.0 3.97 30.1 2.50 26.4 101.4 4.9 4.09
60 39.3 2.40 31.1 88.0 4.80 34.3 2.30 31.2 84.4 4.8 4.97
50 8.0 3.3 7.7 70 37.9 2.52 29.3 97.0 4.40 32.8 2.43 29.4 93.4 4.9 4.56
80 36.6 2.65 27.6 106.1 4.05 31.3 2.55 27.7 102.3 5.1 4.18
60 40.1 2.41 31.9 88.6 4.88 35.1 2.31 32.0 85.0 4.8 5.06
11.0 4.7 11.4 70 38.7 2.54 30.1 97.6 4.47 33.5 2.44 30.2 93.9 5.0 4.64
80 37.3 2.66 28.3 106.6 4.11 32.0 2.56 28.4 102.8 5.1 4.26
60 45.9 2.47 37.4 92.7 5.45 40.4 2.36 37.7 88.8 5.4 5.70
5.0 1.5 3.5 70 44.2 2.60 35.3 101.5 4.98 38.5 2.48 35.6 97.4 5.6 5.21
80 42.5 2.73 33.2 110.3 4.57 36.6 2.60 33.5 106.1 5.7 4.77
60 48.2 2.55 39.5 94.3 5.55 42.5 2.42 39.9 90.3 5.6 5.82
70 8.0 3.2 7.4 70 46.4 2.68 37.2 103.0 5.08 40.5 2.55 37.6 98.9 5.8 5.32
80 44.6 2.81 35.0 111.8 4.65 38.5 2.68 35.3 107.4 6.0 4.87
60 49.5 2.57 40.7 95.2 5.64 43.7 2.44 41.1 91.1 5.7 5.93
11.0 4.5 10.5 70 47.6 2.71 38.4 103.9 5.16 41.7 2.57 38.8 99.7 5.9 5.42
80 45.8 2.84 36.1 112.6 4.72 39.6 2.70 36.5 108.2 6.1 4.96
60 53.7 2.59 44.9 98.2 6.08 47.6 2.44 45.4 93.9 6.2 6.45
5.0 1.5 3.5 70 51.6 2.72 42.3 106.8 5.56 45.3 2.57 42.9 102.2 6.4 5.88
80 49.5 2.86 39.8 115.3 5.08 42.9 2.70 40.3 110.6 6.6 5.37
60 56.8 2.70 47.6 100.4 6.17 50.4 2.54 48.3 95.9 6.5 6.57
90 8.0 3.1 7.2 70 54.6 2.84 44.9 108.9 5.64 48.0 2.67 45.5 104.2 6.7 5.99
80 52.4 2.98 42.2 117.3 5.15 45.5 2.81 42.8 112.4 6.9 5.47
60 58.6 2.74 49.3 101.8 6.28 52.2 2.57 50.0 97.2 6.6 6.70
11.0 4.4 10.2 70 56.3 2.88 46.5 110.1 5.73 49.6 2.71 47.2 105.4 6.8 6.11
80 54.0 3.02 43.7 118.5 5.24 47.1 2.84 44.4 113.5 7.0 5.57
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
40
E SERIES SPECIFICATION CATALOG

E040
Cooling Capacity Data (1300 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 40.2 29.3 1.69 46.6 23.8 40.2 29.3 1.65 46.5 3.6 24.3
5.0 1.6 3.7 80/67 43.7 30.5 1.72 49.6 25.4 43.7 30.5 1.69 49.5 3.7 25.9
85/71 47.2 31.7 1.76 52.5 26.9 47.2 31.7 1.72 52.4 3.8 27.4
75/63 40.6 29.6 1.61 46.8 25.2 40.6 29.6 1.59 46.7 3.4 25.5
50 8.0 3.3 7.7 80/67 44.1 30.8 1.64 49.8 26.9 44.1 30.8 1.62 49.7 3.5 27.2
85/71 47.7 32.1 1.68 52.7 28.4 47.7 32.1 1.65 52.7 3.6 28.8
75/63 41.0 29.6 1.56 47.0 26.2 41.0 29.6 1.55 47.0 3.2 26.4
11.0 4.7 10.9 80/67 44.6 30.8 1.60 50.0 27.9 44.6 30.8 1.59 50.0 3.3 28.1
85/71 48.2 32.1 1.63 53.0 29.6 48.2 32.1 1.62 53.0 3.4 29.8
75/63 37.4 28.5 2.10 45.1 17.8 37.6 28.5 2.05 45.1 5.6 18.3
5.0 1.6 3.7 80/67 40.7 29.6 2.15 48.0 19.0 40.9 29.7 2.09 48.0 5.8 19.5
85/71 43.9 30.8 2.19 50.9 20.1 44.1 30.9 2.13 50.9 5.9 20.7
75/63 38.0 28.7 2.00 45.4 19.0 38.2 28.8 1.96 45.4 5.2 19.4
70 8.0 3.3 7.7 80/67 41.3 29.9 2.04 48.3 20.3 41.5 30.0 2.00 48.3 5.4 20.7
85/71 44.6 31.1 2.08 51.1 21.5 44.8 31.2 2.04 51.2 5.5 21.9
75/63 38.4 28.7 1.94 45.6 19.8 38.6 28.8 1.92 45.7 4.9 20.0
11.0 4.7 10.9 80/67 41.7 29.9 1.98 48.5 21.1 41.9 30.0 1.96 48.6 5.0 21.4
85/71 45.1 31.1 2.02 51.4 22.3 45.3 31.2 2.00 51.5 5.2 22.6
75/63 33.9 27.3 2.65 43.3 12.8 34.2 27.5 2.57 43.4 7.6 13.3
5.0 1.5 3.7 80/67 36.8 28.5 2.71 46.0 13.6 37.2 28.6 2.63 46.1 7.8 14.2
85/71 39.7 29.6 2.76 48.8 14.4 40.1 29.8 2.68 48.9 8.0 15.0
75/63 34.6 27.6 2.51 43.5 13.8 34.9 27.8 2.46 43.7 7.0 14.2
90 8.0 3.1 7.2 80/67 37.6 28.8 2.56 46.3 14.7 37.9 28.9 2.51 46.5 7.3 15.1
85/71 40.6 29.9 2.61 49.1 15.5 41.0 30.1 2.56 49.3 7.5 16.0
75/63 34.9 27.6 2.43 43.6 14.3 35.3 27.8 2.41 43.9 6.5 14.6
11.0 4.4 10.2 80/67 37.9 28.8 2.48 46.4 15.3 38.3 28.9 2.46 46.7 6.7 15.6
85/71 41.0 29.9 2.53 49.2 16.2 41.4 30.1 2.51 49.5 6.9 16.5
75/63 29.5 25.8 3.39 41.2 8.7 29.9 26.0 3.27 41.3 9.6 9.1
5.0 1.5 3.5 80/67 32.0 26.9 3.46 43.8 9.3 32.5 27.1 3.34 43.9 9.9 9.7
85/71 34.6 27.9 3.53 46.5 9.8 35.1 28.1 3.41 46.5 10.1 10.3
75/63 30.2 26.0 3.19 41.3 9.5 30.7 26.2 3.12 41.5 8.9 9.8
110 8.0 3.0 6.9 80/67 32.8 27.1 3.26 44.0 10.1 33.3 27.3 3.18 44.2 9.1 10.5
85/71 35.5 28.2 3.32 46.6 10.7 36.0 28.4 3.24 46.8 9.4 11.1
75/63 30.5 26.0 3.10 41.3 9.9 31.0 26.2 3.06 41.7 8.1 10.1
11.0 4.3 9.9 80/67 33.2 27.1 3.16 44.0 10.5 33.7 27.3 3.12 44.3 8.4 10.8
85/71 35.8 28.2 3.23 46.6 11.1 36.4 28.4 3.19 47.0 8.7 11.4
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
41
E SERIES SPECIFICATION CATALOG

E047
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1200 34.3 3.09 23.8 96.5 3.25 29.3 2.97 24.0 92.6 4.8 3.37
6.0 2.0 4.6
1500 34.7 3.07 24.2 91.4 3.31 29.9 2.98 24.2 88.4 4.5 3.38
1200 35.4 3.13 24.8 97.3 3.32 30.2 3.00 25.0 93.3 5.0 3.44
30 9.0 3.7 8.5
1500 35.8 3.10 25.2 92.1 3.39 30.9 3.01 25.2 89.1 4.6 3.46
1200 35.9 3.13 25.2 97.7 3.36 30.6 3.00 25.5 93.6 5.1 3.49
12.0 5.9 13.6
1500 36.3 3.10 25.8 92.4 3.44 31.3 3.01 25.8 89.3 4.7 3.51
1200 44.1 3.28 32.9 104.0 3.94 37.9 3.12 33.2 99.2 6.0 4.12
6.0 1.9 4.4
1500 44.8 3.21 33.8 97.6 4.09 39.2 3.09 33.9 94.2 5.3 4.22
1200 45.9 3.36 34.4 105.4 4.01 39.4 3.19 34.8 100.4 6.3 4.19
50 9.0 3.5 8.2
1500 46.7 3.28 35.5 98.8 4.17 40.9 3.15 35.6 95.2 5.5 4.31
1200 46.8 3.38 35.3 106.1 4.06 40.2 3.21 35.6 101.0 6.4 4.25
12.0 5.6 12.9
1500 47.6 3.30 36.4 99.4 4.23 41.8 3.16 36.6 95.8 5.6 4.39
1200 53.2 3.53 41.1 111.0 4.41 45.7 3.33 41.5 105.2 7.3 4.65
6.0 1.8 3.9
1500 54.3 3.41 42.7 103.5 4.66 48.0 3.26 43.0 99.6 6.2 4.87
1200 55.7 3.66 43.3 113.0 4.47 47.9 3.44 43.7 107.0 7.5 4.72
70 9.0 3.3 7.6
1500 57.0 3.52 45.0 105.2 4.74 50.5 3.35 45.4 101.2 6.4 4.97
1200 57.2 3.70 44.5 114.1 4.53 49.2 3.48 45.0 107.9 7.7 4.79
12.0 5.3 12.2
1500 58.5 3.56 46.4 106.1 4.82 51.9 3.38 46.9 102.0 6.5 5.06
1200 60.8 3.75 48.0 116.9 4.75 51.9 3.50 48.5 110.1 8.5 5.06
6.0 1.7 3.9
1500 62.5 3.57 50.3 108.6 5.13 55.5 3.37 51.0 104.2 7.0 5.43
1200 64.2 3.92 50.8 119.5 4.79 54.9 3.65 51.3 112.4 8.8 5.11
90 9.0 3.3 7.6
1500 66.1 3.73 53.4 110.8 5.20 58.8 3.51 54.2 106.3 7.3 5.52
1200 66.2 3.99 52.5 121.1 4.86 56.7 3.71 53.1 113.8 9.0 5.19
12.0 5.2 12.0
1500 68.2 3.78 55.3 112.1 5.29 60.9 3.55 56.2 107.6 7.4 5.63
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

42
E SERIES SPECIFICATION CATALOG

E047
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM CFM
PSI FT TC SC KW HR EER TC SC KW HR HW EER
1200 50.6 31.4 2.23 58.2 22.6 50.6 31.4 2.19 54.0 4.0 23.1
6.0 1.9 4.4
1500 52.7 35.3 2.35 60.7 22.4 52.7 35.3 2.31 56.4 4.2 22.9
1200 51.1 31.7 2.13 58.4 24.0 51.1 31.7 2.10 54.5 3.8 24.3
50 9.0 3.5 8.2
1500 53.2 35.6 2.24 60.9 23.7 53.2 35.6 2.21 56.8 4.0 24.0
1200 51.6 31.7 2.07 58.7 25.0 51.6 31.7 2.06 55.0 3.6 25.1
12.0 5.6 12.9
1500 53.8 35.6 2.18 61.2 24.7 53.8 35.6 2.17 57.4 3.8 24.8
1200 47.7 30.8 2.70 56.9 17.7 47.9 30.9 2.63 51.1 5.9 18.2
6.0 1.8 3.9
1500 49.4 34.6 2.83 59.1 17.5 49.7 34.7 2.76 53.0 6.1 18.0
1200 48.4 31.1 2.57 57.2 18.9 48.7 31.2 2.52 51.7 5.6 19.3
70 9.0 3.3 7.6
1500 50.2 35.0 2.69 59.4 18.7 50.4 35.1 2.64 53.6 5.9 19.1
1200 48.9 31.1 2.49 57.4 19.6 49.2 31.2 2.47 52.2 5.4 19.9
12.0 5.3 12.2
1500 50.7 35.0 2.61 59.6 19.4 51.0 35.1 2.59 54.2 5.6 19.7
1200 43.6 29.6 3.35 55.1 13.0 44.1 29.7 3.25 47.4 7.7 13.6
6.0 1.7 3.9
1500 45.0 33.2 3.49 56.9 12.9 45.4 33.4 3.38 49.0 8.0 13.4
1200 44.5 29.9 3.16 55.3 14.1 45.0 30.0 3.10 48.1 7.5 14.5
90 9.0 3.3 7.6
1500 45.9 33.6 3.30 57.2 13.9 46.4 33.7 3.23 49.7 7.7 14.4
1200 45.0 29.9 3.07 55.5 14.6 45.4 30.0 3.04 48.7 7.2 14.9
12.0 5.2 12.0
1500 46.4 33.6 3.20 57.3 14.5 46.8 33.7 3.17 50.3 7.4 14.8
1200 38.3 27.7 4.21 52.6 9.1 38.9 27.9 4.06 43.1 9.6 9.6
6.0 1.6 3.9
1500 39.3 31.1 4.36 54.1 9.0 39.9 31.3 4.21 44.3 9.9 9.5
1200 39.3 28.0 3.96 52.8 9.9 39.9 28.2 3.86 43.8 9.3 10.3
110 9.0 3.0 6.9
1500 40.3 31.4 4.10 54.3 9.8 40.9 31.6 4.01 45.0 9.6 10.2
1200 39.7 28.0 3.84 52.8 10.3 40.3 28.2 3.80 44.3 8.9 10.6
12.0 4.8 11.1
1500 40.7 31.4 3.98 54.3 10.2 41.3 31.6 3.93 45.5 9.2 10.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

43
E SERIES SPECIFICATION CATALOG

E047
Heating Capacity Data (1500 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 35.8 2.93 25.7 82.1 3.58 30.8 2.85 25.6 79.0 4.4 3.62
6.0 2.0 4.6 70 34.8 3.09 24.2 91.5 3.30 29.9 3.00 24.2 88.5 4.5 3.36
80 33.7 3.24 22.8 100.8 3.05 28.8 3.15 22.7 97.8 4.7 3.11
60 36.9 2.96 26.8 82.8 3.65 32.1 2.88 26.7 79.8 4.5 3.73
30 9.0 3.7 8.5 70 35.9 3.12 25.2 92.2 3.37 30.9 3.03 25.2 89.1 4.6 3.44
80 34.9 3.28 23.7 101.5 3.12 29.8 3.18 23.7 98.4 4.8 3.19
60 37.4 2.96 27.3 83.1 3.70 32.6 2.87 27.3 80.1 4.6 3.78
12.0 5.9 13.6 70 36.4 3.12 25.8 92.5 3.42 31.4 3.03 25.8 89.4 4.7 3.49
80 35.4 3.28 24.2 101.8 3.17 30.2 3.18 24.2 98.7 4.8 3.23
60 46.3 3.07 35.9 88.6 4.42 40.9 2.96 36.0 85.2 5.2 4.57
6.0 1.9 4.4 70 44.9 3.23 33.8 97.7 4.07 39.2 3.11 33.9 94.2 5.3 4.20
80 43.4 3.39 31.8 106.8 3.75 37.6 3.27 31.9 103.2 5.5 3.86
60 48.3 3.13 37.6 89.8 4.52 42.7 3.01 37.8 86.4 5.3 4.67
50 9.0 3.5 8.2 70 46.7 3.30 35.5 98.8 4.15 40.9 3.17 35.6 95.3 5.5 4.29
80 45.2 3.46 33.3 107.9 3.82 39.2 3.33 33.5 104.2 5.7 3.95
60 49.3 3.15 38.6 90.4 4.59 43.6 3.02 38.7 86.9 5.4 4.76
12.0 5.6 13.6 70 47.7 3.32 36.4 99.4 4.22 41.8 3.18 36.6 95.8 5.6 4.37
80 46.1 3.48 34.2 108.4 3.88 40.0 3.34 34.4 104.7 5.8 4.01
60 56.4 3.26 45.3 94.8 5.06 50.2 3.11 45.6 91.0 6.0 5.30
6.0 1.8 3.9 70 54.4 3.43 42.7 103.6 4.64 48.0 3.28 43.0 99.7 6.2 4.85
80 52.4 3.61 40.1 112.4 4.26 45.8 3.44 40.5 108.3 6.4 4.45
60 59.2 3.36 47.7 96.5 5.16 52.9 3.20 48.2 92.6 6.2 5.41
70 9.0 3.3 7.6 70 57.1 3.54 45.0 105.2 4.73 50.5 3.37 45.4 101.2 6.4 4.95
80 55.0 3.72 42.3 114.0 4.33 48.2 3.54 42.7 109.8 6.6 4.54
60 60.8 3.40 49.2 97.5 5.24 54.4 3.23 49.7 93.6 6.3 5.51
12.0 5.3 12.2 70 58.6 3.58 46.4 106.2 4.80 52.0 3.40 46.9 102.1 6.5 5.04
80 56.4 3.76 43.6 114.8 4.40 49.5 3.57 44.1 110.6 6.7 4.62
60 65.0 3.41 53.4 100.1 5.58 58.2 3.22 54.1 95.9 6.8 5.91
6.0 1.7 3.9 70 62.6 3.59 50.3 108.6 5.11 55.5 3.39 51.0 104.3 7.0 5.40
80 60.2 3.77 47.3 117.2 4.68 52.9 3.56 47.9 112.6 7.3 4.94
60 68.7 3.56 56.6 102.4 5.66 61.8 3.35 57.4 98.1 7.1 6.02
90 9.0 3.3 7.6 70 66.2 3.75 53.4 110.8 5.18 58.9 3.53 54.2 106.4 7.3 5.50
80 63.6 3.93 50.2 119.3 4.74 56.0 3.70 50.9 114.6 7.5 5.03
60 71.0 3.61 58.6 103.8 5.76 63.9 3.40 59.5 99.5 7.2 6.14
12.0 5.2 12.0 70 68.3 3.80 55.3 112.2 5.27 60.9 3.57 56.2 107.6 7.4 5.60
80 65.6 3.99 52.0 120.5 4.82 58.0 3.75 52.8 115.8 7.6 5.12
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
44
E SERIES SPECIFICATION CATALOG

E047
Cooling Capacity Data (1500 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 48.5 33.9 2.32 57.1 20.9 48.5 33.9 2.28 57.0 4.1 21.3
6.0 1.9 4.4 80/67 52.7 35.3 2.37 60.8 22.2 52.7 35.3 2.33 60.6 4.2 22.7
85/71 56.9 36.7 2.42 64.4 23.5 56.9 36.7 2.37 64.3 4.3 24.0
75/63 49.0 34.2 2.22 57.3 22.1 49.0 34.2 2.19 57.2 3.9 22.4
50 9.0 3.5 8.2 80/67 53.2 35.6 2.26 60.9 23.5 53.2 35.6 2.23 60.9 4.0 23.8
85/71 57.5 37.0 2.31 64.6 24.9 57.5 37.0 2.28 64.5 4.1 25.2
75/63 49.5 34.2 2.15 57.6 23.0 49.5 34.2 2.14 57.5 3.7 23.1
12.0 5.6 12.9 80/67 53.8 35.6 2.20 61.3 24.5 53.8 35.6 2.19 61.2 3.8 24.6
85/71 58.1 37.0 2.24 64.9 25.9 58.1 37.0 2.23 64.9 3.9 26.1
75/63 45.5 33.3 2.79 55.6 16.3 45.7 33.3 2.72 55.6 5.9 16.8
6.0 1.9 4.4 80/67 49.4 34.6 2.85 59.1 17.3 49.7 34.7 2.78 59.1 6.1 17.9
85/71 53.4 36.0 2.91 62.7 18.4 53.6 36.1 2.83 62.7 6.3 18.9
75/63 46.2 33.6 2.65 55.8 17.4 46.4 33.7 2.61 55.9 5.7 17.8
70 9.0 3.5 8.2 80/67 50.2 35.0 2.71 59.4 18.5 50.4 35.1 2.66 59.5 5.9 18.9
85/71 54.2 36.4 2.76 63.0 19.6 54.5 36.5 2.72 63.1 6.0 20.1
75/63 46.6 33.6 2.58 56.1 18.1 46.9 33.7 2.56 56.2 5.4 18.3
12.0 5.6 12.9 80/67 50.7 35.0 2.63 59.7 19.3 50.9 35.1 2.61 59.8 5.6 19.5
85/71 54.7 36.4 2.68 63.2 20.4 55.0 36.5 2.66 63.4 5.8 20.7
75/63 41.4 31.9 3.44 53.5 12.0 41.8 32.1 3.34 53.6 7.8 12.5
6.0 1.7 4.4 80/67 45.0 33.2 3.51 56.9 12.8 45.4 33.4 3.40 57.0 8.0 13.3
85/71 48.6 34.6 3.58 60.4 13.6 49.1 34.7 3.47 60.5 8.2 14.1
75/63 42.2 32.2 3.25 53.8 13.0 42.6 32.4 3.19 54.0 7.5 13.4
90 9.0 3.3 7.6 80/67 45.9 33.6 3.32 57.2 13.8 46.4 33.7 3.25 57.4 7.7 14.3
85/71 49.6 34.9 3.38 60.6 14.7 50.1 35.1 3.32 60.9 7.9 15.1
75/63 42.7 32.2 3.16 53.9 13.5 43.1 32.4 3.12 54.2 7.2 13.8
12.0 5.2 12.0 80/67 46.4 33.6 3.22 57.3 14.4 46.8 33.7 3.19 57.7 7.4 14.7
85/71 50.1 34.9 3.28 60.8 15.2 50.6 35.1 3.25 61.2 7.6 15.6
75/63 36.1 29.9 4.29 50.9 8.4 36.6 30.1 4.14 51.0 9.6 8.8
6.0 1.6 3.9 80/67 39.2 31.1 4.38 54.2 9.0 39.8 31.3 4.23 54.3 9.9 9.4
85/71 42.4 32.3 4.47 57.4 9.5 43.0 32.6 4.31 57.5 10.2 10.0
75/63 37.0 30.2 4.04 51.1 9.2 37.6 30.4 3.94 51.3 9.3 9.5
110 9.0 3.0 6.9 80/67 40.3 31.4 4.12 54.3 9.8 40.9 31.6 4.03 54.6 9.6 10.2
85/71 43.5 32.7 4.20 57.6 10.3 44.1 32.9 4.11 57.9 9.8 10.8
75/63 37.4 30.2 3.92 51.1 9.5 38.0 30.4 3.88 51.5 8.9 9.8
12.0 4.8 11.1 80/67 40.7 31.4 4.00 54.3 10.2 41.3 31.6 3.95 54.8 9.2 10.4
85/71 43.9 32.7 4.08 57.6 10.8 44.6 32.9 4.03 58.1 9.5 11.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
45
E SERIES SPECIFICATION CATALOG

E048
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
900 30.9 2.77 21.5 101.8 3.27 26.0 2.72 22.3 96.7 5.7 3.40
6.0 2.0 4.6 1200 31.8 2.80 22.2 94.5 3.33 26.8 2.75 22.8 90.7 5.4 3.43
1500 32.8 2.89 22.9 90.2 3.32 27.9 2.84 23.2 87.2 5.0 3.39
900 31.7 2.82 22.1 102.6 3.29 26.5 2.77 23.0 97.2 6.0 3.43
30 9.0 3.7 8.5 1200 32.6 2.83 22.9 95.1 3.37 27.4 2.78 23.5 91.1 5.6 3.48
1500 33.6 2.92 23.6 90.7 3.36 28.4 2.87 23.8 87.6 5.2 3.44
900 32.3 2.86 22.5 103.2 3.30 26.9 2.81 23.4 97.6 6.1 3.44
12.0 5.9 13.6 1200 33.1 2.86 23.4 95.6 3.39 27.8 2.81 23.9 91.5 5.7 3.50
1500 34.2 2.95 24.1 91.1 3.39 28.9 2.89 24.3 87.8 5.3 3.46
900 42.3 3.39 30.7 113.5 3.66 34.7 3.26 31.8 105.7 8.2 3.86
6.0 1.9 4.4 1200 43.4 3.22 32.5 103.5 3.96 36.3 3.11 33.0 98.0 7.4 4.11
1500 44.8 3.26 33.6 97.6 4.02 37.7 3.17 33.6 93.3 6.7 4.11
900 43.9 3.46 32.1 115.1 3.72 36.3 3.32 33.2 107.4 8.2 3.93
50 9.0 3.5 8.1 1200 45.1 3.28 33.8 104.8 4.02 38.0 3.17 34.5 99.3 7.3 4.18
1500 46.4 3.33 35.1 98.7 4.09 39.4 3.23 35.1 94.3 6.7 4.18
900 44.8 3.49 32.9 116.1 3.76 37.3 3.35 34.0 108.4 8.2 3.98
12.0 5.6 12.9 1200 46.0 3.32 34.7 105.5 4.07 39.0 3.20 35.4 100.1 7.3 4.23
1500 47.5 3.36 36.0 99.3 4.13 40.4 3.26 36.0 95.0 6.7 4.23
900 53.3 4.05 39.5 124.9 3.86 43.2 3.80 40.7 114.4 10.5 4.13
6.0 1.8 4.2 1200 55.0 3.65 42.5 112.4 4.41 45.7 3.47 42.9 105.2 9.1 4.62
1500 56.7 3.64 44.3 105.0 4.57 47.5 3.49 43.8 99.3 8.3 4.68
900 55.9 4.17 41.7 127.5 3.93 45.9 3.92 42.9 117.2 10.4 4.21
70 9.0 3.3 7.6 1200 57.7 3.76 44.8 114.5 4.49 48.5 3.58 45.3 107.4 9.1 4.70
1500 59.5 3.75 46.7 106.7 4.65 50.3 3.60 46.2 101.0 8.2 4.76
900 57.3 4.21 43.0 129.0 3.99 47.4 3.96 44.3 118.7 10.4 4.28
12.0 5.3 12.2 1200 59.2 3.81 46.2 115.7 4.55 49.7 3.62 46.6 108.3 9.3 4.77
1500 61.1 3.79 48.1 107.7 4.72 51.9 3.64 47.7 102.0 8.2 4.84
900 62.6 4.69 46.6 134.4 3.91 49.6 4.30 47.7 121.0 12.8 4.25
6.0 1.7 3.9 1200 64.8 4.03 51.1 120.0 4.71 53.2 3.77 51.2 111.0 10.9 4.98
1500 67.0 3.95 53.5 111.4 4.97 55.3 3.74 52.4 104.2 9.8 5.10
900 66.3 4.88 49.7 138.3 3.99 53.5 4.48 50.9 125.0 12.7 4.33
90 9.0 3.3 7.6 1200 68.8 4.20 54.5 123.1 4.80 57.2 3.93 54.7 114.2 10.9 5.07
1500 71.1 4.11 57.1 113.9 5.07 59.4 3.90 55.9 106.7 9.8 5.19
900 68.3 4.92 51.5 140.3 4.07 55.6 4.52 52.8 127.2 12.7 4.42
12.0 5.2 12.0 1200 70.9 4.24 56.4 124.7 4.90 59.4 3.97 56.7 115.8 10.8 5.18
1500 73.3 4.16 59.1 115.3 5.17 61.7 3.95 57.9 108.1 9.7 5.30
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
46
E SERIES SPECIFICATION CATALOG

E048
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
900 49.5 30.2 2.42 57.8 20.5 51.0 29.9 2.40 54.9 4.3 21.3
6.0 1.9 4.4 1200 53.5 34.4 2.55 62.2 20.9 55.1 34.1 2.53 59.0 4.7 21.8
1500 56.3 38.2 2.69 65.4 20.9 58.0 37.9 2.66 62.1 4.9 21.8
900 50.1 30.7 2.26 57.9 22.2 51.6 30.7 2.24 55.4 3.9 23.1
50 9.0 3.5 8.1 1200 54.1 34.9 2.39 62.3 22.7 55.7 34.9 2.36 59.6 4.2 23.6
1500 57.0 38.8 2.51 65.5 22.7 58.7 38.8 2.49 62.7 4.5 23.6
900 50.6 30.7 2.18 58.1 23.2 52.2 31.0 2.16 56.0 3.5 24.1
12.0 5.6 12.9 1200 54.7 35.0 2.30 62.5 23.7 56.3 35.4 2.28 60.3 3.8 24.7
1500 57.5 38.9 2.42 65.8 23.7 59.3 39.3 2.40 63.5 4.0 24.7
900 46.4 28.9 2.93 56.4 15.8 47.6 28.7 2.90 50.9 6.6 16.4
6.0 1.8 4.2 1200 49.1 32.6 3.05 59.5 16.1 50.4 32.4 3.02 53.7 6.9 16.7
1500 51.3 36.2 3.16 62.1 16.2 52.6 36.0 3.13 56.0 7.3 16.8
900 47.4 29.2 2.80 57.0 17.0 48.6 29.4 2.77 52.0 6.0 17.6
70 9.0 3.3 7.6 1200 50.2 33.0 2.90 60.1 17.3 51.5 33.2 2.87 54.9 6.4 17.9
1500 52.4 36.6 3.01 62.7 17.4 53.7 36.8 2.98 57.3 6.7 18.0
900 47.9 29.4 2.72 57.2 17.6 49.1 29.8 2.69 52.8 5.5 18.2
12.0 5.3 12.2 1200 50.7 33.2 2.82 60.4 18.0 52.0 33.7 2.80 55.7 5.8 18.6
1500 53.0 36.9 2.93 63.0 18.1 54.3 37.4 2.90 58.1 6.1 18.7
900 41.8 27.1 3.46 53.6 12.1 42.6 27.1 3.42 45.3 9.0 12.4
6.0 1.7 3.9 1200 43.4 30.4 3.54 55.5 12.3 44.3 30.4 3.50 46.9 9.3 12.6
1500 45.0 33.7 3.62 57.3 12.4 45.9 33.7 3.58 48.5 9.6 12.8
900 43.1 27.4 3.36 54.5 12.8 43.9 27.7 3.32 47.0 8.3 13.2
90 9.0 3.3 7.6 1200 44.7 30.7 3.44 56.5 13.0 45.6 31.0 3.40 48.7 8.6 13.4
1500 46.4 34.0 3.51 58.4 13.2 47.3 34.4 3.48 50.3 8.9 13.6
900 43.5 27.7 3.29 54.7 13.2 44.4 28.2 3.26 47.9 7.6 13.6
12.0 5.2 12.0 1200 45.2 31.0 3.37 56.7 13.4 46.1 31.6 3.33 49.6 7.8 13.8
1500 46.8 34.4 3.44 58.6 13.6 47.8 35.1 3.41 51.3 8.1 14.0
900 37.1 25.4 3.98 50.7 9.3 37.7 25.5 3.94 39.6 11.5 9.6
6.0 1.6 3.7 1200 37.9 28.2 4.01 51.6 9.4 38.4 28.4 3.97 40.3 11.7 9.7
1500 38.9 31.3 4.04 52.7 9.6 39.5 31.4 4.00 41.2 12.0 9.9
900 38.7 25.6 3.94 52.1 9.8 39.2 26.0 3.90 41.9 10.6 10.0
110 9.0 3.0 6.9 1200 39.4 28.5 3.98 53.0 9.9 40.0 28.9 3.94 42.6 10.8 10.2
1500 40.5 31.5 4.01 54.2 10.1 41.1 32.0 3.97 43.6 11.1 10.4
900 39.0 26.0 3.90 52.3 10.0 39.6 26.6 3.86 43.0 9.8 10.3
12.0 4.8 11.1 1200 39.8 28.9 3.93 53.2 10.1 40.4 29.6 3.89 43.8 9.9 10.4
1500 40.9 32.0 3.96 54.5 10.3 41.6 32.8 3.92 44.8 10.2 10.6
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
47
E SERIES SPECIFICATION CATALOG

E048
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
600 14.5 1.33 9.9 92.6 3.18 11.8 1.31 10.2 88.9 2.9 3.28
3.0 1.4 3.2 800 15.0 1.34 10.5 89.0 3.28 12.5 1.33 10.7 86.2 2.8 3.37
1000 15.5 1.36 10.9 86.2 3.34 13.1 1.35 11.1 84.0 2.7 3.42
600 15.6 1.40 10.8 93.5 3.27 12.7 1.37 11.2 89.7 3.1 3.38
30 6.0 2.0 4.6 800 16.2 1.40 11.4 89.8 3.40 13.5 1.38 11.7 86.9 2.9 3.50
1000 16.7 1.41 11.9 86.9 3.47 14.2 1.40 12.2 84.6 2.8 3.55
600 16.0 1.42 11.2 93.8 3.31 13.1 1.39 11.5 89.8 3.2 3.43
9.0 3.7 8.5 800 16.6 1.41 11.8 90.0 3.45 13.8 1.39 12.1 87.0 3.0 3.54
1000 17.2 1.43 12.3 87.1 3.52 14.6 1.41 12.5 84.8 2.8 3.60
600 21.1 1.58 15.7 100.5 3.90 17.4 1.53 16.1 95.3 4.0 4.09
3.0 1.3 3.0 800 21.8 1.53 16.5 95.5 4.16 18.5 1.49 16.9 91.8 3.6 4.31
1000 22.5 1.53 17.3 91.9 4.31 19.5 1.51 17.5 89.2 3.1 4.41
600 22.8 1.64 17.2 101.8 4.07 18.8 1.58 17.7 96.5 4.3 4.29
50 6.0 1.9 4.4 800 23.5 1.58 18.2 96.6 4.38 20.0 1.53 18.5 92.8 3.8 4.55
1000 24.4 1.57 19.0 92.8 4.55 21.2 1.54 19.2 90.0 3.3 4.66
600 23.6 1.67 17.9 102.4 4.15 19.5 1.60 18.5 96.9 4.4 4.38
9.0 3.5 8.1 800 24.4 1.59 18.9 97.0 4.48 20.7 1.55 19.3 93.2 3.9 4.66
1000 25.2 1.59 19.8 93.2 4.66 22.0 1.55 20.0 90.4 3.4 4.77
600 27.4 1.82 21.2 108.1 4.42 22.7 1.73 21.9 101.4 5.0 4.71
3.0 1.2 2.8 800 28.2 1.70 22.4 101.6 4.86 24.1 1.64 22.8 97.0 4.3 5.08
1000 29.3 1.68 23.5 97.3 5.10 25.6 1.64 23.7 94.0 3.6 5.23
600 29.8 1.87 23.4 109.8 4.67 24.7 1.76 24.1 102.8 5.4 5.01
70 6.0 1.8 4.2 800 30.6 1.73 24.7 103.0 5.19 26.1 1.65 25.1 98.2 4.6 5.45
1000 31.8 1.70 26.0 98.6 5.49 27.8 1.65 26.0 95.2 3.8 5.63
600 31.1 1.90 24.6 110.9 4.79 25.9 1.79 25.4 103.7 5.6 5.16
9.0 3.3 7.6 800 32.0 1.75 26.0 103.9 5.36 27.3 1.67 26.4 98.9 4.8 5.63
1000 33.2 1.71 27.4 99.4 5.68 29.1 1.66 27.4 95.9 3.9 5.82
600 32.5 2.03 25.6 113.1 4.70 26.7 1.89 26.4 104.6 6.1 5.09
3.0 1.2 2.8 800 33.3 1.83 27.0 105.6 5.32 28.2 1.74 27.4 99.8 5.1 5.61
1000 34.6 1.79 28.5 100.9 5.68 30.2 1.73 28.4 97.0 4.1 5.82
600 35.4 2.07 28.4 115.1 5.02 29.1 1.91 29.2 106.2 6.6 5.49
90 6.0 1.7 3.9 800 36.2 1.84 29.9 107.2 5.77 30.7 1.73 30.3 101.1 5.5 6.12
1000 37.7 1.78 31.7 102.4 6.21 32.9 1.71 31.4 98.2 4.4 6.37
600 37.3 2.10 30.1 116.7 5.20 30.8 1.93 31.0 107.6 6.8 5.71
9.0 3.3 7.6 800 38.2 1.86 31.8 108.5 6.01 32.5 1.75 32.1 102.3 5.6 6.38
1000 39.8 1.80 33.7 103.6 6.49 34.8 1.73 33.3 99.3 4.5 6.66
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
48
E SERIES SPECIFICATION CATALOG

E048
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
600 30.3 18.5 1.20 34.4 25.3 30.6 18.5 1.19 33.4 1.2 25.8
3.0 1.3 3.0 800 32.2 20.1 1.19 36.3 27.1 32.6 20.1 1.18 35.3 1.3 27.7
1000 33.2 23.7 1.24 37.5 26.8 33.6 23.7 1.23 36.4 1.3 27.4
600 30.9 18.7 1.04 34.5 29.7 31.1 18.7 1.03 33.7 0.9 30.1
50 6.0 1.9 4.4 800 32.9 20.2 1.03 36.5 31.9 33.1 20.2 1.02 35.7 0.9 32.4
1000 33.9 23.8 1.08 37.6 31.6 34.1 23.8 1.07 36.8 1.0 32.0
600 31.1 18.7 0.98 34.4 31.6 31.1 18.7 0.97 33.9 0.5 32.0
9.0 3.5 8.1 800 33.1 20.2 0.97 36.4 34.0 33.1 20.2 0.96 35.8 0.6 34.3
1000 34.1 23.8 1.02 37.6 33.6 34.1 23.8 1.00 36.9 0.6 34.0
600 26.9 17.4 1.49 32.0 18.0 27.3 17.2 1.47 29.1 3.2 18.5
3.0 1.2 2.8 800 28.6 19.2 1.49 33.7 19.1 29.0 19.0 1.47 30.7 3.3 19.7
1000 29.5 22.6 1.56 34.8 18.9 29.9 22.4 1.53 31.7 3.5 19.5
600 27.2 17.5 1.35 31.8 20.1 27.4 17.5 1.34 29.3 2.7 20.5
70 6.0 1.8 4.2 800 28.9 19.4 1.35 33.5 21.4 29.2 19.3 1.33 30.9 2.9 21.9
1000 29.8 22.8 1.41 34.6 21.2 30.1 22.7 1.39 31.9 3.0 21.6
600 27.6 17.6 1.29 32.0 21.5 27.8 17.7 1.28 29.9 2.2 21.8
9.0 3.3 7.6 800 29.4 19.5 1.29 33.8 22.8 29.5 19.6 1.27 31.5 2.4 23.2
1000 30.3 22.9 1.34 34.9 22.6 30.5 23.0 1.33 32.5 2.5 22.9
600 23.6 15.8 1.73 29.5 13.7 24.1 15.5 1.69 24.7 5.2 14.2
3.0 1.2 2.8 800 25.1 17.8 1.74 31.0 14.4 25.6 17.4 1.71 26.0 5.4 15.0
1000 25.9 20.9 1.81 32.0 14.3 26.4 20.5 1.78 26.8 5.6 14.8
600 23.6 16.0 1.63 29.2 14.4 23.9 15.9 1.61 24.9 4.6 14.9
90 6.0 1.7 3.9 800 25.1 18.0 1.65 30.7 15.2 25.4 17.9 1.62 26.2 4.8 15.7
1000 25.8 21.2 1.71 31.7 15.1 26.2 21.1 1.69 27.0 5.0 15.5
600 24.3 16.2 1.57 29.7 15.5 24.6 16.3 1.55 25.9 4.0 15.8
9.0 3.3 7.6 800 25.8 18.2 1.58 31.2 16.3 26.1 18.4 1.57 27.3 4.2 16.7
1000 26.6 21.4 1.65 32.2 16.2 26.9 21.6 1.63 28.2 4.3 16.5
600 19.9 14.1 1.91 26.4 10.4 20.4 13.7 1.87 19.6 7.1 10.9
3.0 1.1 2.5 800 21.1 16.2 1.94 27.7 10.9 21.6 15.7 1.90 20.6 7.5 11.4
1000 21.7 19.0 2.02 28.7 10.7 22.3 18.5 1.97 21.3 7.8 11.3
600 19.6 14.4 1.90 26.1 10.4 20.0 14.3 1.86 20.0 6.4 10.7
110 6.0 1.6 3.7 800 20.8 16.4 1.93 27.4 10.8 21.3 16.3 1.89 21.0 6.7 11.2
1000 21.5 19.3 2.01 28.3 10.7 21.9 19.2 1.97 21.7 7.0 11.1
600 20.5 14.6 1.84 26.8 11.1 20.8 14.8 1.82 21.4 5.7 11.4
9.0 3.0 6.9 800 21.8 16.7 1.87 28.1 11.6 22.1 16.9 1.85 22.5 6.0 11.9
1000 22.4 19.6 1.95 29.1 11.5 22.8 19.9 1.93 23.2 6.2 11.8
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
49
E SERIES SPECIFICATION CATALOG

E058
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1800 44.9 3.79 32.0 93.1 3.47 40.2 3.72 32.4 90.7 4.8 3.55
8.0 2.1 4.9
2000 45.8 3.86 32.6 91.2 3.48 41.3 3.78 33.0 89.1 4.6 3.56
1800 45.3 3.83 32.3 93.3 3.47 40.4 3.75 32.6 90.8 5.0 3.54
30 11.0 3.1 7.2
2000 46.2 3.90 32.9 91.4 3.47 41.5 3.82 33.3 89.2 4.8 3.55
1800 46.7 3.93 33.3 94.0 3.48 41.7 3.85 33.7 91.5 5.1 3.56
14.0 5.5 12.7
2000 47.7 4.00 34.0 92.1 3.49 42.8 3.92 34.3 89.8 4.9 3.57
1800 58.3 4.17 44.1 100.0 4.10 51.9 4.08 44.2 96.7 6.2 4.18
8.0 2.0 4.6
2000 58.9 4.21 44.6 97.3 4.10 53.5 4.17 45.0 94.8 5.7 4.16
1800 59.0 4.16 44.8 100.3 4.16 52.2 4.07 44.8 96.9 6.5 4.22
50 11.0 2.9 6.7
2000 60.5 4.26 46.0 98.0 4.16 55.0 4.21 46.4 95.4 5.9 4.23
1800 60.4 4.24 46.0 101.1 4.18 53.5 4.16 46.0 97.5 6.6 4.24
14.0 4.6 10.6
2000 61.6 4.30 46.9 98.5 4.20 55.8 4.21 47.4 95.8 5.9 4.29
1800 70.6 4.51 55.2 106.3 4.59 62.2 4.42 54.8 102.0 7.7 4.64
8.0 2.0 4.4
2000 72.0 4.53 56.6 103.4 4.66 65.4 4.53 56.6 100.3 6.7 4.66
1800 73.1 4.55 57.5 107.6 4.70 64.3 4.46 57.1 103.1 8.0 4.75
70 11.0 2.8 6.5
2000 73.4 4.58 57.8 104.0 4.70 66.4 4.53 57.8 100.7 6.9 4.74
1800 74.5 4.62 58.7 108.3 4.72 65.5 4.53 58.2 103.7 8.2 4.76
14.0 4.4 10.2
2000 76.1 4.67 60.2 105.3 4.78 69.0 4.62 60.2 101.9 7.0 4.82
1800 83.6 4.84 67.1 113.0 5.06 73.1 4.74 66.1 107.6 9.2 5.08
8.0 1.9 4.4
2000 84.9 4.83 68.4 109.3 5.15 76.6 4.83 67.8 105.5 7.7 5.11
1800 88.0 4.95 71.1 115.3 5.21 77.0 4.85 69.9 109.6 9.5 5.22
90 11.0 2.7 6.2
2000 89.1 4.83 72.6 111.2 5.40 79.7 4.83 71.1 106.9 7.9 5.32
1800 89.2 5.00 72.1 115.9 5.23 77.8 4.90 70.8 110.0 9.7 5.23
14.0 4.2 9.7
2000 90.8 5.03 73.6 112.0 5.29 81.2 4.98 72.1 107.6 7.9 5.24
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

50
E SERIES SPECIFICATION CATALOG

E058
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1800 64.6 42.5 2.83 74.3 22.8 64.6 42.5 2.80 69.7 4.5 23.1
8.0 2.0 4.6
2000 64.8 44.2 3.17 75.7 20.5 64.8 44.2 3.14 70.9 4.6 20.7
1800 64.8 42.6 2.73 74.1 23.7 64.8 42.5 2.70 69.7 4.4 24.0
50 11.0 2.9 6.7
2000 64.8 44.6 3.11 75.5 20.9 64.8 44.6 3.08 70.8 4.5 21.1
1800 65.4 42.8 2.72 74.7 24.1 65.5 42.7 2.69 70.4 4.3 24.4
14.0 4.6 10.6
2000 65.5 44.6 2.96 75.6 22.1 65.5 44.6 2.93 71.1 4.4 22.4
1800 59.2 39.8 3.48 71.0 17.0 59.4 40.1 3.44 63.9 7.3 17.2
8.0 2.0 4.4
2000 61.8 43.3 3.75 74.6 16.5 61.8 43.7 3.71 67.0 7.5 16.7
1800 59.4 40.1 3.35 70.9 17.8 59.6 40.2 3.31 64.0 6.9 18.0
70 11.0 2.8 6.5
2000 62.4 43.3 3.61 74.7 17.3 62.4 43.3 3.57 67.5 7.1 17.5
1800 60.0 40.4 3.31 71.3 18.2 60.1 40.3 3.26 64.8 6.5 18.5
14.0 4.4 10.2
2000 62.4 43.7 3.50 74.3 17.8 62.4 43.7 3.47 69.4 6.7 18.0
1800 55.6 39.3 4.43 70.7 12.6 56.0 39.8 4.38 61.0 10.0 12.8
8.0 1.9 4.4
2000 56.1 41.4 4.69 72.1 12.0 56.6 41.8 4.64 62.2 10.3 12.2
1800 56.1 39.7 4.25 70.6 13.2 56.3 40.0 4.19 61.3 9.4 13.5
90 11.0 2.7 6.2
2000 56.6 41.4 4.43 71.7 12.8 56.6 41.8 4.34 61.8 9.6 13.0
1800 56.6 40.1 4.17 70.9 13.6 56.7 40.1 4.09 62.0 8.7 13.9
14.0 4.2 9.7
2000 57.2 41.8 4.30 71.9 13.3 57.2 41.8 4.21 62.7 8.9 13.6
1800 49.7 37.7 5.55 68.6 8.9 50.2 38.4 5.49 56.2 12.8 9.1
8.0 1.8 4.2
2000 50.2 39.2 5.61 69.3 8.9 51.2 39.6 5.61 57.2 13.2 9.1
1800 50.2 38.2 5.32 68.3 9.4 50.5 38.6 5.23 56.5 11.8 9.7
110 11.0 2.6 6.0
2000 50.7 39.8 5.37 69.0 9.4 50.7 40.6 5.21 56.3 12.2 9.7
1800 50.7 38.7 5.19 68.4 9.8 50.8 38.8 5.06 57.2 10.9 10.1
14.0 4.1 9.5
2000 51.2 40.3 5.24 69.1 9.8 51.4 40.4 5.11 57.6 11.2 10.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

51
E SERIES SPECIFICATION CATALOG

E058
Heating Capacity Data (2000 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 47.0 3.62 34.6 81.8 3.81 42.4 3.55 35.0 79.6 4.5 3.87
8.0 2.1 4.9 70 45.6 3.81 32.6 91.1 3.51 41.2 3.73 33.0 89.1 4.6 3.59
80 44.3 4.00 30.7 100.5 3.24 39.7 3.92 31.0 98.4 4.7 3.32
60 47.4 3.66 34.9 81.9 3.80 42.8 3.58 35.3 79.8 4.7 3.88
30 11.0 3.1 7.2 70 46.1 3.85 32.9 91.3 3.51 41.3 3.77 33.3 89.1 4.8 3.58
80 44.7 4.04 30.9 100.7 3.24 39.8 3.96 31.3 98.4 5.0 3.31
60 48.8 3.75 36.0 82.6 3.82 44.2 3.68 36.4 80.5 4.8 3.90
14.0 5.5 12.7 70 47.5 3.95 34.0 92.0 3.52 42.6 3.87 34.3 89.7 4.9 3.60
80 46.1 4.15 32.0 101.4 3.26 41.1 4.06 32.3 99.0 5.0 3.33
60 60.7 3.96 47.2 88.1 4.50 55.5 3.92 47.7 85.7 5.5 4.57
8.0 2.0 4.6 70 58.8 4.16 44.6 97.2 4.14 53.4 4.12 45.0 94.7 5.7 4.20
80 56.8 4.37 41.9 106.3 3.81 51.2 4.33 42.3 103.7 5.9 3.86
60 62.4 4.00 48.7 88.9 4.57 57.0 3.96 49.2 86.4 5.7 4.65
50 11.0 2.9 6.7 70 60.3 4.21 46.0 97.9 4.20 54.8 4.16 46.4 95.4 5.9 4.27
80 58.3 4.42 43.2 107.0 3.87 52.5 4.37 43.6 104.3 6.0 3.93
60 63.5 4.04 49.7 89.4 4.61 58.0 3.96 50.2 86.8 5.8 4.72
14.0 4.6 10.6 70 61.4 4.25 46.9 98.4 4.23 55.6 4.16 47.4 95.8 5.9 4.33
80 59.3 4.46 44.1 107.5 3.90 53.3 4.37 44.5 104.7 6.1 3.99
60 74.5 4.26 60.0 94.5 5.13 68.0 4.26 60.0 91.5 6.5 5.13
8.0 2.0 4.4 70 71.9 4.48 56.6 103.3 4.70 65.2 4.48 56.6 100.2 6.7 4.70
80 69.2 4.70 53.2 112.1 4.31 62.4 4.70 53.2 108.9 6.9 4.31
60 75.9 4.30 61.3 95.2 5.18 69.1 4.26 61.3 92.0 6.7 5.22
70 11.0 2.8 6.5 70 73.2 4.53 57.8 103.9 4.74 66.2 4.48 57.8 100.7 6.9 4.78
80 70.5 4.75 54.3 112.7 4.35 63.3 4.70 54.3 109.3 7.1 4.38
60 78.8 4.39 63.8 96.5 5.26 71.9 4.34 63.8 93.3 6.8 5.31
14.0 4.4 10.2 70 76.0 4.62 60.2 105.2 4.82 68.8 4.57 60.2 101.9 7.0 4.86
80 73.1 4.85 56.6 113.9 4.42 65.8 4.80 56.6 110.4 7.2 4.45
60 88.1 4.54 72.6 100.8 5.68 79.9 4.54 71.8 97.0 7.4 5.64
8.0 1.9 4.4 70 84.8 4.78 68.4 109.2 5.20 76.4 4.78 67.8 105.4 7.7 5.16
80 81.5 5.02 64.3 117.7 4.76 72.9 5.02 63.7 113.8 7.9 4.72
60 92.4 4.54 76.9 102.8 5.97 83.2 4.54 75.4 98.5 7.7 5.87
90 11.0 2.7 6.2 70 88.9 4.78 72.6 111.1 5.45 79.5 4.78 71.1 106.8 7.9 5.36
80 85.3 5.02 68.2 119.5 4.98 75.8 5.02 66.9 115.1 8.1 4.91
60 94.2 4.73 78.0 103.6 5.83 84.7 4.68 76.5 99.2 7.7 5.79
14.0 4.2 9.7 70 90.6 4.98 73.6 111.9 5.33 81.0 4.93 72.1 107.5 7.9 5.29
80 87.0 5.23 69.2 120.3 4.88 77.3 5.18 67.8 115.8 8.2 4.84
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
52
E SERIES SPECIFICATION CATALOG

E058
Cooling Capacity Data (2000 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 59.7 42.4 3.05 71.0 19.5 59.7 42.4 3.02 70.9 4.5 19.7
8.0 2.0 4.6 80/67 64.9 44.2 3.12 75.5 20.8 64.9 44.2 3.09 75.4 4.6 21.0
85/71 70.1 45.9 3.18 80.1 22.0 70.1 45.9 3.15 79.9 4.7 22.3
75/63 59.7 42.8 3.00 70.8 19.9 59.7 42.8 2.97 70.7 4.4 20.1
50 11.0 2.9 6.7 80/67 64.9 44.6 3.06 75.3 21.2 64.9 44.6 3.03 75.2 4.5 21.4
85/71 70.1 46.4 3.12 79.8 22.5 70.1 46.4 3.09 79.7 4.6 22.7
75/63 60.3 42.8 2.85 71.0 21.1 60.3 42.8 2.82 70.9 4.3 21.4
14.0 4.6 10.6 80/67 65.6 44.6 2.91 75.5 22.5 65.6 44.6 2.88 75.4 4.4 22.8
85/71 70.8 46.4 2.97 80.0 23.9 70.8 46.4 2.94 79.9 4.5 24.1
75/63 56.9 41.5 3.62 70.0 15.7 56.9 41.9 3.58 69.8 7.2 15.9
8.0 2.0 4.4 80/67 61.8 43.3 3.70 74.4 16.7 61.8 43.7 3.66 74.3 7.5 16.9
85/71 66.8 45.0 3.77 78.9 17.7 66.8 45.4 3.73 78.8 7.7 17.9
75/63 57.5 41.5 3.48 70.1 16.5 57.5 41.5 3.45 70.0 6.8 16.7
70 11.0 2.8 6.5 80/67 62.5 43.3 3.56 74.6 17.6 62.5 43.3 3.52 74.5 7.1 17.7
85/71 67.4 45.0 3.63 79.1 18.6 67.4 45.0 3.59 78.9 7.3 18.8
75/63 57.5 42.0 3.38 69.8 17.0 57.5 42.0 3.35 69.7 6.5 17.2
14.0 4.4 10.2 80/67 62.5 43.7 3.45 74.2 18.1 62.5 43.7 3.42 74.1 6.7 18.3
85/71 67.4 45.4 3.52 78.7 19.2 67.4 45.4 3.48 78.5 6.9 19.4
75/63 51.6 39.7 4.54 67.6 11.4 52.1 40.1 4.50 68.0 10.0 11.6
8.0 1.9 4.4 80/67 56.1 41.4 4.64 71.9 12.1 56.7 41.8 4.59 72.3 10.3 12.3
85/71 60.6 43.0 4.73 76.2 12.8 61.2 43.5 4.68 76.7 10.6 13.1
75/63 52.1 39.7 4.29 67.3 12.2 52.1 40.1 4.20 67.0 9.3 12.4
90 11.0 2.7 6.2 80/67 56.7 41.4 4.38 71.6 12.9 56.7 41.8 4.29 71.3 9.6 13.2
85/71 61.2 43.0 4.47 75.9 13.7 61.2 43.5 4.38 75.6 9.9 14.0
75/63 52.7 40.1 4.17 67.4 12.6 52.7 40.1 4.08 67.2 8.6 12.9
14.0 4.2 6.2 80/67 57.3 41.8 4.25 71.8 13.5 57.3 41.8 4.16 71.5 8.9 13.7
85/71 61.8 43.5 4.34 76.1 14.3 61.8 43.5 4.25 75.7 9.2 14.6
75/63 46.2 37.7 5.45 65.0 8.5 47.1 38.0 5.45 66.0 12.8 8.7
8.0 1.8 4.2 80/67 50.2 39.2 5.56 69.2 9.0 51.2 39.6 5.56 70.2 13.2 9.2
85/71 54.2 40.8 5.67 73.3 9.6 55.3 41.2 5.67 74.4 13.5 9.8
75/63 46.7 38.2 5.22 64.8 8.9 46.7 39.0 5.06 64.3 11.8 9.2
110 11.0 2.6 6.0 80/67 50.7 39.8 5.32 68.9 9.5 50.7 40.6 5.16 68.4 12.2 9.8
85/71 54.8 41.4 5.43 73.0 10.1 54.8 42.2 5.27 72.5 12.5 10.4
75/63 47.2 38.7 5.09 64.8 9.3 47.3 38.8 4.96 64.5 10.8 9.5
14.0 4.1 9.5 80/67 51.3 40.3 5.19 69.0 9.9 51.4 40.4 5.06 68.7 11.2 10.2
85/71 55.4 41.9 5.29 73.1 10.5 55.5 42.0 5.16 72.8 11.5 10.8
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
53
E SERIES SPECIFICATION CATALOG

E060
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1000 29.2 2.99 19.0 97.0 2.86 21.8 2.94 19.4 90.2 7.7 2.93
8.0 2.1 4.9 1700 34.1 3.09 23.5 88.6 3.23 27.2 3.03 23.9 84.8 7.1 3.31
2000 34.9 3.25 23.8 86.2 3.15 28.3 3.19 24.1 83.1 6.7 3.21
1000 31.1 2.98 20.9 98.8 3.05 23.5 2.93 21.3 91.8 7.8 3.13
30 11.0 3.1 7.0 1700 36.5 3.12 25.9 89.9 3.43 29.5 3.06 26.3 86.0 7.3 3.52
2000 37.5 3.32 26.2 87.4 3.31 30.8 3.25 26.5 84.2 6.8 3.38
1000 31.1 2.91 21.1 98.8 3.12 23.4 2.86 21.6 91.7 7.9 3.21
14.0 4.8 11.0 1700 37.0 3.20 26.1 90.2 3.40 29.8 3.13 26.5 86.2 7.4 3.48
2000 37.9 3.35 26.5 87.5 3.31 31.0 3.28 26.7 84.4 6.9 3.38
1000 44.4 3.43 32.7 111.1 3.80 34.1 3.27 32.9 101.5 10.0 3.95
8.0 2.0 4.7 1700 51.7 3.58 39.4 98.1 4.23 42.3 3.45 39.6 93.0 9.1 4.36
2000 52.8 3.69 40.2 94.4 4.19 44.1 3.58 40.1 90.4 8.2 4.28
1000 47.1 3.51 35.1 113.6 3.93 36.4 3.34 35.3 103.7 10.3 4.10
50 11.0 2.9 6.7 1700 54.7 3.65 42.2 99.8 4.39 44.9 3.51 42.3 94.5 9.3 4.53
2000 55.8 3.74 43.0 95.8 4.37 46.8 3.63 42.9 91.7 8.4 4.46
1000 48.0 3.56 35.9 114.5 3.95 37.1 3.38 36.0 104.3 10.5 4.12
14.0 4.6 10.6 1700 55.6 3.69 43.0 100.3 4.42 45.6 3.55 43.0 94.8 9.5 4.56
2000 56.8 3.78 43.9 96.3 4.40 47.6 3.67 43.7 92.1 8.6 4.49
1000 60.3 4.21 45.9 125.8 4.20 46.5 3.90 45.6 113.0 12.5 4.42
8.0 2.0 4.5 1700 68.2 4.20 53.9 107.2 4.76 55.8 3.97 53.3 100.4 11.1 4.94
2000 69.7 4.22 55.3 102.3 4.84 58.6 4.07 54.5 97.1 9.8 4.92
1000 62.7 4.30 48.0 128.1 4.27 48.3 3.97 47.6 114.7 12.9 4.52
70 11.0 2.8 6.4 1700 70.7 4.26 56.1 108.5 4.86 57.6 4.01 55.4 101.4 11.5 5.05
2000 72.3 4.27 57.7 103.5 4.96 60.5 4.10 56.6 98.0 10.1 5.05
1000 64.5 4.37 49.6 129.8 4.33 49.8 4.02 49.1 116.1 13.1 4.58
14.0 4.4 10.1 1700 72.5 4.31 57.8 109.5 4.93 59.1 4.05 56.9 102.2 11.7 5.12
2000 74.2 4.31 59.5 104.4 5.04 62.1 4.14 58.3 98.8 10.3 5.13
1000 75.8 4.94 58.9 140.1 4.49 58.0 4.45 57.7 123.7 14.9 4.80
8.0 1.9 4.3 1700 83.4 4.72 67.3 115.4 5.18 67.4 4.37 65.6 106.7 13.1 5.39
2000 85.4 4.65 69.6 109.6 5.38 71.3 4.43 67.5 103.0 11.4 5.46
1000 77.3 5.04 60.1 141.6 4.49 58.6 4.50 58.7 124.3 15.4 4.82
90 11.0 2.7 6.1 1700 84.5 4.77 68.2 116.0 5.19 67.6 4.40 66.2 106.8 13.6 5.41
2000 86.6 4.67 70.7 110.1 5.43 71.7 4.44 68.3 103.2 11.8 5.50
1000 80.2 5.13 62.7 144.3 4.58 61.0 4.56 61.1 126.5 15.7 4.93
14.0 4.2 9.6 1700 87.4 4.83 70.9 117.6 5.30 70.1 4.44 68.8 108.2 13.9 5.54
2000 89.7 4.72 73.6 111.5 5.57 74.3 4.48 71.0 104.4 12.0 5.64
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
54
E SERIES SPECIFICATION CATALOG

E060
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1000 61.0 34.1 2.73 70.3 22.4 61.6 33.8 2.70 64.0 6.9 22.8
8.0 2.0 4.7 1700 68.8 43.6 2.98 78.9 23.1 69.4 43.1 2.95 71.8 7.7 23.5
2000 70.2 47.4 3.17 81.0 22.1 70.9 46.9 3.14 73.7 7.9 22.6
1000 61.7 34.5 2.67 70.8 23.1 62.0 34.3 2.64 64.3 6.7 23.5
50 11.0 2.9 6.7 1700 69.5 44.0 2.92 79.4 23.8 69.8 43.8 2.89 72.1 7.5 24.2
2000 70.9 47.9 3.10 81.5 22.8 71.2 47.6 3.07 74.0 7.7 23.2
1000 62.3 34.8 2.62 71.2 23.7 62.3 34.8 2.60 64.6 6.5 24.0
14.0 4.6 10.6 1700 70.2 44.5 2.87 79.9 24.5 70.2 44.5 2.84 72.5 7.3 24.7
2000 71.6 48.3 3.05 82.0 23.5 71.6 48.3 3.02 74.4 7.5 23.7
1000 54.8 32.5 3.26 65.9 16.8 55.4 32.5 3.21 57.4 8.9 17.3
8.0 2.0 4.5 1700 61.2 41.6 3.56 73.3 17.2 61.8 41.6 3.51 63.9 9.9 17.6
2000 63.1 45.2 3.79 76.1 16.6 63.8 45.2 3.74 66.3 10.3 17.1
1000 55.4 32.8 3.19 66.3 17.4 55.7 32.8 3.15 57.8 8.6 17.7
70 11.0 2.8 6.4 1700 61.8 42.0 3.49 73.7 17.7 62.1 42.0 3.44 64.3 9.6 18.0
2000 63.8 45.6 3.71 76.4 17.2 64.1 45.6 3.67 66.7 9.9 17.5
1000 55.9 33.1 3.13 66.6 17.9 55.9 33.1 3.10 58.2 8.3 18.0
14.0 4.4 10.1 1700 62.4 42.4 3.43 74.1 18.2 62.4 42.4 3.39 64.8 9.3 18.4
2000 64.4 46.1 3.65 76.9 17.6 64.4 46.1 3.61 67.1 9.6 17.8
1000 47.1 29.9 3.77 60.0 12.5 47.6 30.2 3.69 49.3 10.9 12.9
8.0 1.9 4.3 1700 51.9 38.3 4.12 66.0 12.6 52.5 38.6 4.04 54.2 12.0 13.0
2000 54.2 41.6 4.39 69.2 12.3 54.7 42.0 4.31 56.8 12.6 12.7
1000 47.6 30.2 3.69 60.2 12.9 47.9 30.4 3.63 49.7 10.5 13.2
90 11.0 2.7 6.1 1700 52.5 38.6 4.04 66.3 13.0 52.7 38.8 3.98 54.7 11.6 13.3
2000 54.7 42.0 4.30 69.4 12.7 55.0 42.2 4.24 57.3 12.2 13.0
1000 47.9 30.4 3.63 60.3 13.2 47.9 30.4 3.59 50.1 10.1 13.4
14.0 4.2 9.6 1700 53.0 39.1 3.97 66.6 13.4 53.0 39.1 3.93 55.2 11.2 13.5
2000 55.3 42.4 4.23 69.7 13.1 55.3 42.4 4.19 57.9 11.7 13.2
1000 38.6 30.6 4.20 52.9 9.2 39.0 31.2 4.09 40.1 12.9 9.5
8.0 1.8 4.1 1700 42.3 39.4 4.60 58.0 9.2 42.7 40.2 4.48 43.9 14.1 9.5
2000 44.6 42.8 4.90 61.4 9.1 45.1 43.7 4.78 46.4 15.0 9.4
1000 39.0 30.9 4.11 53.0 9.5 39.2 31.2 4.04 40.6 12.4 9.7
110 11.0 2.6 5.9 1700 42.8 39.8 4.50 58.1 9.5 43.0 40.2 4.42 44.5 13.6 9.7
2000 45.1 43.2 4.80 61.5 9.4 45.3 43.7 4.72 47.0 14.4 9.6
1000 39.4 31.2 4.04 53.2 9.8 39.4 31.2 4.00 41.2 11.9 9.9
14.0 3.9 9.0 1700 43.2 40.2 4.42 58.3 9.8 43.2 40.2 4.38 45.1 13.0 9.9
2000 45.5 43.7 4.72 61.7 9.6 45.5 43.7 4.67 47.7 13.8 9.7
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
55
E SERIES SPECIFICATION CATALOG

E060
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
700 16.2 1.50 11.0 91.4 3.16 12.8 1.49 11.5 86.9 3.8 3.27
5.0 1.1 2.5 900 16.9 1.52 11.7 87.4 3.27 13.6 1.50 12.0 84.0 3.5 3.34
1100 17.5 1.54 12.3 84.7 3.34 14.3 1.52 12.4 82.0 3.3 3.39
700 16.1 1.53 10.8 91.2 3.08 12.5 1.51 11.3 86.5 3.9 3.19
30 8.0 2.1 4.9 900 16.8 1.54 11.5 87.3 3.18 13.4 1.53 11.8 83.7 3.7 3.26
1100 17.4 1.56 12.0 84.6 3.26 14.1 1.54 12.2 81.8 3.4 3.31
700 16.7 1.53 11.5 92.1 3.20 13.1 1.51 11.9 87.3 4.0 3.31
11.0 3.1 7.0 900 17.4 1.54 12.2 87.9 3.31 14.0 1.53 12.5 84.4 3.7 3.39
1100 18.0 1.56 12.7 85.2 3.39 14.7 1.54 12.8 82.4 3.4 3.44
700 24.7 1.63 19.2 102.7 4.45 19.9 1.58 19.8 96.4 5.3 4.68
5.0 1.0 2.3 900 25.9 1.62 20.4 96.6 4.67 21.6 1.59 20.8 92.2 4.6 4.84
1100 26.6 1.62 21.1 92.4 4.81 22.6 1.59 21.1 89.0 3.9 4.88
700 25.1 1.66 19.4 103.2 4.43 20.0 1.60 20.1 96.5 5.5 4.67
50 8.0 2.0 4.6 900 26.3 1.65 20.6 97.0 4.67 21.7 1.61 21.0 92.3 4.8 4.83
1100 26.9 1.64 21.3 92.6 4.80 22.7 1.61 21.3 89.1 4.1 4.88
700 25.9 1.67 20.2 104.2 4.54 20.7 1.61 20.9 97.4 5.7 4.79
11.0 2.9 6.7 900 27.1 1.66 21.4 97.9 4.79 22.4 1.61 21.8 93.1 4.9 4.96
1100 27.7 1.65 22.1 93.3 4.92 23.5 1.62 22.1 89.8 4.1 5.00
700 33.6 1.82 27.4 114.4 5.42 27.3 1.72 28.3 106.2 6.8 5.81
5.0 0.9 2.2 900 35.2 1.78 29.2 106.3 5.79 29.7 1.71 29.5 100.6 5.7 6.05
1100 35.8 1.75 29.8 100.1 5.98 30.9 1.71 29.6 96.0 4.6 6.08
700 34.9 1.85 28.6 116.2 5.54 28.3 1.74 29.5 107.4 7.1 5.97
70 8.0 2.0 4.6 900 36.7 1.81 30.5 107.7 5.95 30.8 1.73 30.8 101.7 5.9 6.23
1100 37.1 1.77 31.1 101.2 6.13 31.9 1.72 30.8 96.9 4.7 6.24
700 35.6 1.87 29.3 117.1 5.58 28.8 1.76 30.1 108.1 7.3 6.02
11.0 2.8 6.4 900 37.4 1.83 31.2 108.5 6.00 31.4 1.75 31.5 102.3 6.1 6.28
1100 37.8 1.79 31.7 101.8 6.19 32.5 1.74 31.4 97.4 4.8 6.29
700 41.0 1.97 34.3 124.3 6.10 33.1 1.82 35.2 113.8 8.3 6.67
5.0 0.9 2.1 900 43.1 1.90 36.6 114.3 6.63 36.2 1.80 36.8 107.2 6.8 6.99
1100 43.2 1.85 36.9 106.4 6.85 37.2 1.78 36.3 101.3 5.2 6.97
700 43.8 2.00 37.0 128.0 6.42 35.5 1.84 37.9 116.9 8.7 7.06
90 8.0 1.9 4.4 900 46.0 1.93 39.5 117.4 7.00 38.7 1.81 39.6 109.8 7.1 7.41
1100 46.0 1.86 39.7 108.7 7.24 39.6 1.79 38.9 103.4 5.4 7.37
700 44.1 2.04 37.2 128.4 6.34 35.5 1.86 38.1 116.9 9.0 6.99
11.0 2.7 6.1 900 46.3 1.96 39.7 117.7 6.93 38.8 1.84 39.8 109.9 7.2 7.34
1100 46.2 1.89 39.8 108.9 7.17 39.7 1.81 39.0 103.4 5.5 7.30
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
56
E SERIES SPECIFICATION CATALOG

E060
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
700 35.3 20.6 1.07 38.9 32.8 35.6 20.8 1.06 37.2 2.0 33.5
5.0 1.0 2.3 900 37.6 23.6 1.10 41.3 34.2 38.0 23.8 1.09 39.5 2.1 34.9
1100 38.7 26.8 1.16 42.7 33.5 39.1 27.0 1.14 40.8 2.2 34.2
700 35.3 20.8 1.03 38.9 34.2 35.7 21.0 1.02 37.3 1.8 34.9
50 8.0 2.0 4.6 900 37.7 23.8 1.06 41.3 35.6 38.0 24.0 1.05 39.7 1.9 36.4
1100 38.8 27.0 1.11 42.6 34.9 39.2 27.3 1.10 41.0 2.0 35.6
700 35.4 20.8 1.01 38.9 35.0 35.8 21.0 1.00 37.6 1.6 35.7
11.0 2.9 6.7 900 37.8 23.8 1.04 41.3 36.5 38.1 24.0 1.03 39.9 1.7 37.2
1100 38.9 27.0 1.09 42.7 35.7 39.3 27.3 1.08 41.2 1.8 36.4
700 30.8 19.9 1.41 35.6 21.9 31.6 19.7 1.39 32.2 4.1 22.7
5.0 0.9 2.2 900 32.3 22.3 1.43 37.2 22.6 33.1 22.1 1.41 33.6 4.3 23.4
1100 33.3 25.0 1.49 38.4 22.4 34.1 24.8 1.47 34.7 4.5 23.1
700 31.0 20.1 1.36 35.6 22.7 31.6 20.2 1.35 32.4 3.8 23.4
70 8.0 2.0 4.6 900 32.5 22.5 1.39 37.2 23.4 33.1 22.6 1.37 33.8 4.0 24.1
1100 33.5 25.3 1.45 38.4 23.2 34.2 25.4 1.43 34.9 4.1 23.9
700 31.2 20.2 1.34 35.7 23.3 31.6 20.5 1.33 32.6 3.5 23.9
11.0 2.8 6.4 900 32.7 22.6 1.36 37.3 24.0 33.2 23.0 1.35 34.1 3.7 24.6
1100 33.7 25.4 1.42 38.5 23.7 34.2 25.8 1.41 35.2 3.8 24.3
700 26.2 19.0 1.74 32.1 15.1 27.2 18.4 1.72 26.8 6.3 15.8
5.0 0.9 2.1 900 27.0 20.8 1.76 33.0 15.3 28.1 20.2 1.74 27.5 6.5 16.1
1100 27.8 23.1 1.81 34.0 15.3 28.9 22.4 1.80 28.4 6.7 16.1
700 26.4 19.2 1.70 32.2 15.5 27.2 19.1 1.69 27.1 5.9 16.2
90 8.0 1.9 4.4 900 27.3 21.0 1.72 33.2 15.8 28.1 20.9 1.71 27.9 6.1 16.5
1100 28.1 23.4 1.78 34.2 15.8 29.0 23.2 1.76 28.7 6.3 16.5
700 26.7 19.4 1.68 32.4 15.9 27.2 19.8 1.66 27.4 5.5 16.4
11.0 2.7 6.1 900 27.5 21.2 1.70 33.3 16.2 28.1 21.7 1.68 28.2 5.6 16.7
1100 28.4 23.6 1.75 34.4 16.2 29.0 24.1 1.73 29.1 5.8 16.7
700 21.7 17.8 2.02 28.6 10.7 22.9 16.9 2.00 21.1 8.6 11.4
5.0 0.9 2.0 900 22.0 19.2 2.04 29.0 10.8 23.2 18.2 2.02 21.4 8.7 11.5
1100 22.7 21.1 2.08 29.8 10.9 23.9 20.0 2.06 22.0 9.0 11.6
700 22.0 18.0 2.00 28.8 11.0 22.9 17.8 1.98 21.6 8.0 11.5
110 8.0 1.8 4.2 900 22.3 19.4 2.02 29.2 11.1 23.2 19.1 2.00 21.9 8.1 11.6
1100 23.0 21.3 2.06 30.0 11.2 23.9 21.0 2.04 22.5 8.4 11.7
700 22.3 18.3 1.97 29.0 11.3 22.8 18.8 1.95 22.0 7.5 11.7
11.0 2.6 5.9 900 22.6 19.7 1.99 29.4 11.4 23.2 20.2 1.97 22.3 7.6 11.8
1100 23.3 21.6 2.03 30.3 11.5 23.9 22.2 2.01 23.0 7.8 11.9
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
57
E SERIES SPECIFICATION CATALOG

E066
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1700 52.3 4.90 35.6 98.5 3.13 46.4 4.74 35.5 95.3 5.3 3.19
10.0 2.7 6.2
2200 53.6 5.01 36.5 92.6 3.13 48.3 4.95 36.5 90.3 5.1 3.16
1700 52.6 4.91 35.9 98.7 3.14 46.3 4.74 35.7 95.2 5.5 3.21
30 13.0 4.3 9.9
2200 53.9 5.01 36.8 92.7 3.15 48.4 4.94 36.8 90.4 5.3 3.18
1700 52.8 4.93 36.0 98.8 3.14 46.4 4.76 35.8 95.2 5.7 3.21
16.0 6.1 14.1
2200 54.1 5.03 36.9 92.8 3.15 48.5 4.95 37.0 90.4 5.4 3.19
1700 67.0 5.31 48.9 106.5 3.70 57.6 5.05 48.5 101.4 8.1 3.82
10.0 2.6 6.0
2200 68.6 5.33 50.4 98.9 3.77 61.2 5.19 50.5 95.8 7.1 3.85
1700 68.3 5.36 50.1 107.2 3.74 58.5 5.08 49.6 101.9 8.5 3.86
50 13.0 4.1 9.5
2200 70.0 5.37 51.7 99.5 3.82 62.3 5.23 51.8 96.2 7.3 3.91
1700 68.9 5.40 50.5 107.6 3.74 58.8 5.11 50.1 102.0 8.7 3.87
16.0 5.8 13.4
2200 70.7 5.40 52.2 99.7 3.84 62.8 5.25 52.4 96.4 7.5 3.92
1700 81.6 5.89 61.5 114.4 4.06 68.5 5.50 60.7 107.3 11.0 4.24
10.0 2.4 5.5
2200 83.7 5.80 63.9 105.2 4.23 74.1 5.58 64.1 101.2 9.1 4.36
1700 84.5 5.99 64.1 116.0 4.13 70.9 5.58 63.3 108.6 11.4 4.32
70 13.0 3.8 8.8
2200 86.8 5.89 66.7 106.5 4.31 76.9 5.66 66.9 102.4 9.4 4.47
1700 85.7 6.05 65.1 116.7 4.15 71.7 5.62 64.2 109.1 11.7 4.35
16.0 5.4 12.5
2200 88.0 5.94 67.8 107.0 4.35 77.9 5.69 68.0 102.8 9.6 4.50
1700 94.0 6.39 72.2 121.2 4.31 77.1 5.85 71.0 112.0 13.9 4.56
10.0 2.3 5.3
2200 96.8 6.18 75.7 110.7 4.59 85.0 5.87 76.0 105.8 11.1 4.80
1700 99.0 6.56 76.6 123.9 4.42 81.4 5.99 75.4 114.4 14.4 4.69
90 13.0 3.6 8.3
2200 102.0 6.33 80.4 112.9 4.72 89.9 5.99 80.8 107.8 11.4 4.95
1700 100.7 6.63 78.1 124.9 4.45 82.7 6.04 76.7 115.0 14.7 4.72
16.0 5.1 11.8
2200 104.0 6.38 82.2 113.8 4.77 91.6 6.04 82.6 108.6 11.7 5.01
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

58
E SERIES SPECIFICATION CATALOG

E066
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1700 69.3 43.4 3.18 80.1 21.8 69.9 43.6 3.16 75.3 5.5 22.1
10.0 2.6 6.0
2200 73.2 49.7 3.62 85.6 20.2 73.9 49.8 3.60 80.4 5.8 20.5
1700 69.6 43.7 3.08 80.1 22.6 70.1 43.7 3.05 75.7 4.9 23.0
50 13.0 4.1 9.5
2200 73.6 49.9 3.51 85.6 21.0 74.1 50.0 3.47 80.8 5.2 21.3
1700 70.3 43.9 3.05 80.7 23.0 70.7 43.9 3.00 76.6 4.3 23.5
16.0 5.8 13.4
2200 74.3 50.2 3.47 86.2 21.4 74.7 50.2 3.42 81.8 4.6 21.8
1700 64.8 40.8 3.88 78.0 16.7 65.4 41.1 3.82 70.4 8.1 17.1
10.0 2.4 5.5
2200 67.9 46.7 4.32 82.7 15.7 68.6 47.0 4.25 74.5 8.6 16.1
1700 65.0 40.9 3.77 77.9 17.3 65.5 41.1 3.71 70.7 7.5 17.6
70 13.0 3.8 8.8
2200 68.2 46.8 4.20 82.5 16.3 68.7 47.0 4.13 74.9 7.9 16.6
1700 66.0 41.8 3.71 78.7 17.8 66.3 41.9 3.65 71.9 6.9 18.2
16.0 5.4 12.5
2200 69.2 47.8 4.13 83.3 16.8 69.5 48.0 4.07 76.1 7.3 17.1
1700 59.3 38.3 4.86 75.8 12.2 59.9 38.7 4.73 65.2 10.8 12.6
10.0 2.3 5.3
2200 61.6 43.9 5.28 79.7 11.7 62.3 44.4 5.15 68.5 11.4 12.1
1700 59.4 38.2 4.73 75.5 12.6 59.8 38.6 4.63 65.5 10.2 12.9
90 13.0 3.6 8.3
2200 61.8 43.8 5.14 79.4 12.0 62.2 44.2 5.04 68.8 10.7 12.3
1700 60.6 39.8 4.62 76.3 13.1 60.8 40.1 4.55 66.8 9.5 13.4
16.0 5.1 11.8
2200 63.0 45.6 5.02 80.2 12.5 63.3 45.9 4.95 70.2 10.0 12.8
1700 52.2 35.1 6.13 73.1 8.5 52.7 35.5 5.92 59.3 13.6 8.9
10.0 2.2 5.1
2200 53.9 40.2 6.53 76.2 8.2 54.4 40.8 6.30 61.8 14.1 8.6
1700 52.3 34.9 5.98 72.7 8.7 52.6 35.3 5.84 59.6 12.9 9.0
110 13.0 3.4 7.9
2200 53.9 40.0 6.37 75.7 8.5 54.3 40.5 6.21 62.1 13.4 8.7
1700 53.6 36.9 5.80 73.4 9.2 53.7 37.3 5.72 61.0 12.3 9.4
16.0 4.8 11.1
2200 55.3 42.4 6.18 76.4 8.9 55.5 42.8 6.09 63.5 12.8 9.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

59
E SERIES SPECIFICATION CATALOG

E066
Heating Capacity Data (2200 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 55.4 4.81 38.7 83.3 3.37 49.9 4.75 38.7 81.0 4.9 3.39
10.0 2.7 6.2 70 53.8 5.06 36.5 92.6 3.11 48.5 5.00 36.5 90.4 5.1 3.14
80 52.2 5.32 34.3 102.0 2.88 47.0 5.25 34.3 99.8 5.3 2.92
60 55.4 4.81 39.0 83.3 3.38 50.1 4.74 39.0 81.1 5.1 3.41
30 13.0 4.3 9.9 70 54.0 5.06 36.8 92.7 3.13 48.6 4.99 36.8 90.4 5.3 3.16
80 52.7 5.32 34.6 102.2 2.91 47.0 5.24 34.6 99.8 5.4 2.93
60 55.6 4.82 39.1 83.4 3.38 50.2 4.75 39.2 81.1 5.2 3.42
16.0 6.1 14.1 70 54.3 5.08 36.9 92.8 3.13 48.6 5.00 37.0 90.5 5.4 3.17
80 52.9 5.33 34.7 102.3 2.91 47.1 5.25 34.7 99.8 5.6 2.94
60 70.9 5.11 53.5 89.8 4.07 63.7 4.98 53.6 86.8 6.9 4.15
10.0 2.6 6.0 70 68.8 5.38 50.4 99.0 3.75 61.4 5.24 50.5 95.8 7.1 3.82
80 66.7 5.65 47.4 108.1 3.46 59.0 5.51 47.5 104.8 7.3 3.53
60 72.4 5.15 54.8 90.5 4.12 64.9 5.01 54.9 87.3 7.1 4.21
50 13.0 4.1 9.5 70 70.2 5.42 51.7 99.5 3.80 62.5 5.28 51.8 96.3 7.3 3.88
80 68.0 5.69 48.6 108.6 3.50 60.1 5.54 48.7 105.3 7.5 3.58
60 73.0 5.18 55.4 90.7 4.14 65.4 5.03 55.5 87.5 7.3 4.23
16.0 5.8 13.4 70 70.8 5.45 52.2 99.8 3.81 63.0 5.30 52.4 96.5 7.5 3.90
80 68.6 5.72 49.1 108.9 3.52 60.5 5.56 49.2 105.5 7.7 3.59
60 86.7 5.56 67.7 96.5 4.57 77.5 5.35 68.0 92.6 8.8 4.72
10.0 2.4 5.5 70 83.9 5.85 63.9 105.3 4.20 74.3 5.63 64.1 101.3 9.1 4.34
80 81.0 6.15 60.1 114.1 3.86 71.1 5.92 60.3 109.9 9.3 3.99
60 89.9 5.65 70.7 97.9 4.67 80.4 5.42 71.0 93.8 9.1 4.83
70 13.0 3.8 8.8 70 87.0 5.94 66.7 106.6 4.29 77.1 5.71 66.9 102.4 9.4 4.44
80 84.0 6.24 62.7 115.3 3.94 73.7 5.99 62.9 111.0 9.6 4.08
60 91.2 5.69 71.8 98.4 4.70 81.5 5.45 72.1 94.3 9.3 4.88
16.0 5.4 12.5 70 88.2 5.99 67.8 107.1 4.32 78.1 5.74 68.0 102.9 9.6 4.47
80 85.1 6.28 63.7 115.8 3.97 74.7 6.03 64.0 111.4 9.9 4.11
60 100.4 5.92 80.2 102.3 4.97 89.0 5.62 80.6 97.5 10.8 5.20
10.0 2.3 5.3 70 96.9 6.23 75.7 110.8 4.56 85.1 5.92 76.0 105.8 11.1 4.77
80 93.4 6.54 71.1 119.3 4.19 81.3 6.22 71.5 114.2 11.4 4.37
60 105.9 6.06 85.2 104.6 5.12 94.2 5.74 85.7 99.6 11.1 5.37
90 13.0 3.6 8.3 70 102.2 6.38 80.4 113.0 4.70 90.0 6.04 80.8 107.9 11.4 4.92
80 98.4 6.69 75.6 121.4 4.31 85.9 6.35 76.0 116.1 11.8 4.51
60 108.0 6.11 87.1 105.4 5.18 96.0 5.78 87.6 100.4 11.3 5.44
16.0 5.1 11.8 70 104.1 6.43 82.2 113.8 4.75 91.8 6.09 82.6 108.6 11.7 4.98
80 100.3 6.75 77.3 122.2 4.35 87.5 6.39 77.7 116.8 12.0 4.56
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

60
E SERIES SPECIFICATION CATALOG

E066
Cooling Capacity Data (2200 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 67.3 47.7 3.59 80.5 18.7 68.0 47.8 3.58 81.2 5.7 19.0
10.0 2.6 6.0 80/67 73.2 49.7 3.67 85.7 20.0 73.9 49.8 3.65 86.3 5.8 20.2
85/71 79.0 51.7 3.74 90.8 21.1 79.8 51.8 3.72 91.5 6.0 21.4
75/63 67.6 47.9 3.49 80.5 19.4 68.2 48.0 3.45 80.9 5.0 19.7
50 13.0 4.1 9.5 80/67 73.5 49.9 3.56 85.7 20.7 74.1 50.0 3.52 86.1 5.2 21.0
85/71 79.4 51.9 3.63 90.8 21.9 80.0 52.0 3.60 91.3 5.4 22.3
75/63 68.3 48.2 3.45 81.1 19.8 68.7 48.2 3.40 81.3 4.4 20.2
16.0 5.8 13.4 80/67 74.3 50.2 3.52 86.3 21.1 74.6 50.2 3.47 86.5 4.6 21.5
85/71 80.2 52.2 3.59 91.5 22.3 80.6 52.2 3.54 91.7 4.7 22.8
75/63 62.5 44.9 4.28 77.8 14.6 63.1 45.2 4.22 78.3 8.3 15.0
10.0 2.4 5.5 80/67 67.9 46.7 4.37 82.8 15.5 68.6 47.0 4.30 83.3 8.6 15.9
85/71 73.3 48.6 4.46 87.8 16.5 74.1 48.9 4.39 88.2 8.9 16.9
75/63 62.7 44.9 4.16 77.7 15.1 63.1 45.2 4.10 77.9 7.7 15.4
70 13.0 3.8 8.8 80/67 68.1 46.8 4.25 82.6 16.0 68.6 47.0 4.18 82.9 7.9 16.4
85/71 73.6 48.7 4.33 87.6 17.0 74.1 48.9 4.27 87.9 8.2 17.4
75/63 63.6 45.9 4.09 78.4 15.5 63.9 46.1 4.03 78.5 7.1 15.8
16.0 5.4 12.5 80/67 69.2 47.8 4.18 83.4 16.6 69.5 48.0 4.12 83.5 7.3 16.9
85/71 74.7 49.8 4.26 88.4 17.5 75.0 49.9 4.20 88.5 7.5 17.9
75/63 56.7 42.2 5.23 75.0 10.8 57.2 42.6 5.10 75.2 11.0 11.2
10.0 2.3 5.3 80/67 61.6 43.9 5.33 79.8 11.5 62.2 44.4 5.20 80.0 11.4 12.0
85/71 66.5 45.7 5.44 84.6 12.2 67.2 46.2 5.31 84.8 11.7 12.7
75/63 56.8 42.1 5.09 74.7 11.2 57.2 42.4 4.99 74.8 10.4 11.5
90 13.0 3.6 8.3 80/67 61.8 43.8 5.19 79.5 11.9 62.2 44.2 5.09 79.6 10.7 12.2
85/71 66.7 45.6 5.30 84.2 12.6 67.2 46.0 5.20 84.3 11.0 12.9
75/63 57.9 43.8 4.97 75.5 11.7 58.2 44.1 4.90 75.5 9.7 11.9
16.0 5.1 8.3 80/67 63.0 45.6 5.07 80.3 12.4 63.2 45.9 5.00 80.3 10.0 12.6
85/71 68.0 47.4 5.17 85.1 13.1 68.3 47.8 5.10 85.1 10.3 13.4
75/63 49.5 38.6 6.45 71.7 7.7 50.0 39.1 6.22 71.5 13.7 8.0
10.0 2.2 5.1 80/67 53.8 40.2 6.58 76.3 8.2 54.4 40.8 6.35 76.0 14.1 8.6
85/71 58.1 41.8 6.71 80.9 8.7 58.7 42.4 6.48 80.6 14.6 9.1
75/63 49.6 38.4 6.29 71.2 7.9 49.9 38.9 6.14 71.1 13.0 8.1
110 13.0 3.4 7.9 80/67 53.9 40.0 6.42 75.8 8.4 54.3 40.5 6.26 75.6 13.4 8.7
85/71 58.2 41.6 6.55 80.3 8.9 58.6 42.1 6.39 80.2 13.8 9.2
75/63 50.8 40.7 6.10 71.9 8.3 51.0 41.1 6.02 71.8 12.4 8.5
16.0 4.8 11.1 80/67 55.2 42.4 6.23 76.5 8.9 55.4 42.8 6.14 76.4 12.8 9.0
85/71 59.6 44.0 6.35 81.1 9.4 59.8 44.5 6.27 81.0 13.1 9.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.

61
E SERIES SPECIFICATION CATALOG

E072
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1200 41.3 3.88 28.0 101.8 3.11 34.0 3.82 28.6 96.2 7.7 3.19
10.0 2.7 6.2 1850 45.0 4.01 31.3 92.5 3.29 38.1 3.94 31.8 89.1 7.2 3.37
2200 46.5 4.22 32.1 89.6 3.23 39.9 4.14 32.5 86.8 6.7 3.30
1200 44.1 3.88 30.8 104.0 3.33 36.7 3.81 31.5 98.3 7.8 3.42
30 13.0 4.3 9.9 1850 48.3 4.05 34.4 94.2 3.49 41.3 3.97 35.0 90.6 7.3 3.58
2200 50.0 4.31 35.3 91.0 3.40 43.3 4.23 35.7 88.2 6.8 3.47
1200 44.7 3.96 31.2 104.5 3.31 37.1 3.88 31.8 98.7 7.9 3.40
16.0 6.1 14.1 1850 48.7 4.09 34.8 94.4 3.49 41.6 4.01 35.3 90.8 7.4 3.58
2200 50.5 4.35 35.7 91.3 3.40 43.7 4.27 36.0 88.4 6.9 3.47
1200 58.8 4.79 42.4 115.4 3.59 48.2 4.57 42.7 107.2 10.1 3.74
10.0 2.6 6.0 1850 62.5 4.77 46.2 101.3 3.84 52.8 4.59 46.3 96.4 9.2 3.95
2200 64.6 4.94 47.7 97.2 3.83 55.6 4.80 47.6 93.4 8.3 3.90
1200 62.2 4.90 45.5 118.0 3.72 51.3 4.66 45.8 109.6 10.3 3.88
50 13.0 4.1 9.5 1850 66.0 4.86 49.4 103.0 3.98 56.0 4.67 49.5 98.0 9.4 4.11
2200 68.2 5.02 51.1 98.7 3.98 59.0 4.87 50.9 94.8 8.5 4.06
1200 63.5 4.97 46.5 119.0 3.74 52.3 4.72 46.7 110.4 10.5 3.90
16.0 5.8 13.4 1850 67.2 4.92 50.4 103.6 4.01 57.0 4.72 50.4 98.5 9.6 4.13
2200 69.4 5.07 52.1 99.2 4.01 60.0 4.92 51.9 95.3 8.6 4.09
1200 79.5 5.86 59.5 131.4 3.97 65.1 5.43 59.1 120.2 12.5 4.19
10.0 2.4 5.5 1850 82.4 5.62 63.2 111.2 4.29 69.4 5.31 62.4 104.7 11.2 4.44
2200 85.0 5.66 65.7 105.8 4.40 73.3 5.45 64.6 100.9 9.9 4.47
1200 82.6 5.97 62.2 133.8 4.05 67.6 5.51 61.7 122.2 12.9 4.28
70 13.0 3.8 8.8 1850 85.3 5.71 65.8 112.7 4.38 71.8 5.37 64.9 105.9 11.5 4.54
2200 88.0 5.72 68.5 107.1 4.51 75.9 5.50 67.2 101.9 10.1 4.58
1200 85.0 6.07 64.3 135.6 4.10 69.6 5.58 63.6 123.7 13.1 4.34
16.0 5.4 12.5 1850 87.5 5.78 67.8 113.8 4.44 73.6 5.43 66.8 106.9 11.7 4.60
2200 90.4 5.78 70.6 108.0 4.58 77.9 5.55 69.2 102.8 10.3 4.65
1200 99.5 6.94 75.8 146.8 4.20 80.5 6.24 74.2 132.1 15.0 4.49
10.0 2.3 5.3 1850 100.4 6.44 78.4 120.2 4.56 83.5 5.97 76.4 111.8 13.2 4.75
2200 103.7 6.31 82.1 113.6 4.81 88.7 6.01 79.6 107.3 11.5 4.88
1200 101.4 7.06 77.3 148.2 4.21 81.5 6.30 75.5 132.9 15.4 4.51
90 13.0 3.6 8.3 1850 101.8 6.51 79.5 120.9 4.58 84.1 6.00 77.3 112.1 13.6 4.77
2200 105.1 6.34 83.4 114.2 4.85 89.4 6.03 80.6 107.6 11.8 4.92
1200 105.1 7.17 80.6 151.1 4.29 84.7 6.38 78.6 135.4 15.7 4.61
16.0 5.1 11.8 1850 105.3 6.60 82.8 122.7 4.67 87.1 6.07 80.3 113.6 13.9 4.87
2200 108.8 6.41 86.9 115.8 4.98 92.6 6.08 83.9 109.0 12.0 5.04
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
62
E SERIES SPECIFICATION CATALOG

E072
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1200 68.7 39.5 3.40 80.3 20.2 69.4 39.1 3.37 73.9 7.0 20.6
10.0 2.6 6.0 1850 75.6 48.5 3.72 88.3 20.3 76.4 48.0 3.68 81.2 7.7 20.8
2200 77.2 52.7 3.95 90.7 19.5 77.9 52.2 3.91 83.4 7.9 19.9
1200 69.4 39.9 3.33 80.7 20.8 69.7 39.7 3.29 74.1 6.8 21.2
50 13.0 4.1 9.5 1850 76.4 49.0 3.64 88.8 21.0 76.8 48.7 3.60 81.6 7.5 21.3
2200 77.9 53.3 3.87 91.2 20.1 78.3 53.0 3.83 83.7 7.7 20.4
1200 72.4 40.9 3.27 83.6 22.1 72.4 40.9 3.24 76.7 6.8 22.4
16.0 5.8 13.4 1850 77.2 50.0 3.58 89.4 21.6 77.2 50.0 3.54 81.9 7.3 21.8
2200 78.7 53.8 3.81 91.7 20.7 78.7 53.8 3.77 84.1 7.5 20.9
1200 67.6 39.0 4.05 81.4 16.7 68.3 39.0 3.99 72.6 9.3 17.1
10.0 2.4 5.5 1850 72.0 47.7 4.43 87.1 16.3 72.7 47.7 4.36 77.6 10.0 16.7
2200 73.5 51.3 4.71 89.6 15.6 74.2 51.3 4.64 79.8 10.3 16.0
1200 68.3 39.4 3.97 81.8 17.2 68.6 39.4 3.92 73.0 9.0 17.5
70 13.0 3.8 8.8 1850 72.7 48.2 4.34 87.5 16.8 73.1 48.2 4.28 78.1 9.7 17.1
2200 74.2 51.8 4.61 90.0 16.1 74.6 51.8 4.55 80.2 9.9 16.4
1200 69.0 39.8 3.90 82.3 17.7 69.0 39.8 3.86 73.4 8.7 17.9
16.0 5.4 12.5 1850 73.5 48.7 4.26 88.0 17.2 73.5 48.7 4.22 78.5 9.3 17.4
2200 75.0 52.4 4.54 90.4 16.5 75.0 52.4 4.49 80.7 9.6 16.7
1200 56.8 35.7 4.72 72.9 12.1 57.4 36.1 4.62 62.0 11.1 12.4
10.0 2.3 5.3 1850 62.6 43.9 5.15 80.2 12.1 63.2 44.3 5.05 68.2 12.2 12.5
2200 63.9 47.7 5.48 82.6 11.6 64.5 48.1 5.37 70.2 12.6 12.0
1200 57.4 36.1 4.62 73.2 12.4 57.7 36.3 4.55 62.5 10.7 12.7
90 13.0 3.6 8.3 1850 63.2 44.3 5.04 80.4 12.5 63.5 44.5 4.97 68.7 11.8 12.8
2200 64.5 48.1 5.37 82.8 12.0 64.8 48.4 5.29 70.7 12.2 12.3
1200 59.9 37.0 4.54 75.4 13.2 59.9 37.0 4.49 64.7 10.6 13.3
16.0 5.1 11.8 1850 63.9 45.2 4.96 80.8 12.9 63.9 45.2 4.91 69.2 11.4 13.0
2200 65.2 48.6 5.28 83.2 12.3 65.2 48.6 5.22 71.3 11.7 12.5
1200 49.5 33.0 5.40 67.9 9.2 50.0 33.7 5.27 54.4 13.5 9.5
10.0 2.2 5.1 1850 52.7 40.4 5.90 72.8 8.9 53.2 41.2 5.76 58.4 14.5 9.2
2200 53.8 43.4 6.28 75.2 8.6 54.3 44.3 6.12 60.2 15.0 8.9
1200 50.0 33.3 5.29 68.0 9.5 50.2 33.7 5.19 54.9 13.0 9.7
110 13.0 3.4 7.9 1850 53.2 40.8 5.78 72.9 9.2 53.5 41.2 5.68 58.9 13.9 9.4
2200 54.3 43.9 6.15 75.3 8.8 54.6 44.3 6.04 60.8 14.4 9.0
1200 50.5 33.7 5.20 68.2 9.7 50.5 33.7 5.15 55.6 12.5 9.8
16.0 4.8 11.1 1850 53.8 41.2 5.68 73.1 9.5 53.8 41.2 5.62 59.6 13.4 9.6
2200 54.9 44.3 6.04 75.5 9.1 54.9 44.3 5.98 61.5 13.8 9.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
63
E SERIES SPECIFICATION CATALOG

E072
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
800 18.3 1.61 12.8 91.2 3.34 14.9 1.59 13.3 87.2 3.9 3.45
7.0 1.5 3.4 1000 18.4 1.61 12.9 87.0 3.35 15.1 1.60 13.2 84.0 3.6 3.43
1200 19.3 1.63 13.7 84.9 3.47 16.1 1.61 13.9 82.4 3.3 3.52
800 18.1 1.64 12.5 91.0 3.24 14.6 1.62 13.0 86.9 4.0 3.35
30 10.0 2.7 6.1 1000 18.2 1.64 12.6 86.9 3.26 14.8 1.62 13.0 83.7 3.7 3.34
1200 19.1 1.66 13.5 84.7 3.38 15.8 1.64 13.6 82.2 3.4 3.43
800 18.8 1.64 13.2 91.8 3.36 15.3 1.62 13.8 87.7 4.0 3.48
13.0 4.3 9.9 1000 19.0 1.64 13.4 87.6 3.39 15.5 1.62 13.7 84.4 3.7 3.47
1200 19.9 1.66 14.2 85.3 3.52 16.6 1.64 14.4 82.8 3.4 3.57
800 26.3 1.88 19.9 100.5 4.10 21.4 1.82 20.6 94.7 5.4 4.31
7.0 1.4 3.2 1000 27.0 1.83 20.8 95.0 4.33 22.5 1.78 21.2 90.9 4.7 4.48
1200 28.2 1.81 22.0 91.8 4.56 24.1 1.78 22.0 88.6 4.0 4.63
800 26.6 1.92 20.1 100.8 4.07 21.5 1.85 20.8 94.9 5.6 4.29
50 10.0 2.6 6.0 1000 27.4 1.85 21.0 95.3 4.32 22.7 1.80 21.4 91.0 4.8 4.48
1200 28.5 1.84 22.3 92.0 4.55 24.3 1.80 22.3 88.8 4.1 4.62
800 27.4 1.93 20.8 101.7 4.16 22.2 1.86 21.5 95.7 5.7 4.39
13.0 4.1 9.5 1000 28.2 1.86 21.8 96.1 4.43 23.5 1.81 22.2 91.8 4.9 4.59
1200 29.4 1.85 23.1 92.7 4.67 25.2 1.81 23.1 89.4 4.1 4.74
800 35.1 2.14 27.8 110.6 4.80 28.6 2.02 28.7 103.1 7.0 5.15
7.0 1.3 3.0 1000 37.0 2.02 30.1 104.3 5.38 31.3 1.93 30.5 98.9 5.8 5.62
1200 38.5 1.96 31.8 99.7 5.74 33.4 1.91 31.5 95.8 4.7 5.83
800 36.3 2.18 28.9 112.0 4.89 29.6 2.05 29.7 104.2 7.2 5.25
70 10.0 2.4 5.6 1000 38.4 2.04 31.4 105.6 5.51 32.5 1.95 31.8 100.1 6.0 5.77
1200 39.9 1.98 33.1 100.8 5.89 34.6 1.93 32.8 96.7 4.7 5.99
800 36.9 2.21 29.4 112.7 4.90 30.1 2.07 30.3 104.8 7.3 5.28
13.0 3.8 8.8 1000 39.1 2.07 32.1 106.2 5.55 33.1 1.97 32.4 100.6 6.1 5.82
1200 40.6 2.01 33.8 101.3 5.94 35.3 1.94 33.4 97.2 4.8 6.04
800 41.3 2.38 33.2 117.8 5.08 32.9 2.19 34.0 108.0 8.6 5.55
7.0 1.2 2.8 1000 44.8 2.17 37.4 111.5 6.04 37.6 2.05 37.5 104.8 7.0 6.37
1200 46.3 2.08 39.2 105.7 6.52 40.0 2.00 38.5 100.9 5.3 6.64
800 43.7 2.41 35.5 120.6 5.31 35.1 2.21 36.4 110.6 8.8 5.82
90 10.0 2.3 5.3 1000 47.7 2.20 40.2 114.2 6.37 40.3 2.06 40.3 107.3 7.1 6.73
1200 49.3 2.09 42.1 108.0 6.89 42.8 2.01 41.3 103.0 5.4 7.02
800 43.9 2.46 35.5 120.8 5.23 35.1 2.25 36.4 110.6 9.0 5.74
13.0 3.6 8.3 1000 48.0 2.23 40.4 114.4 6.30 40.4 2.09 40.5 107.4 7.2 6.66
1200 49.5 2.13 42.3 108.2 6.82 42.9 2.04 41.4 103.1 5.5 6.94
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
64
E SERIES SPECIFICATION CATALOG

E072
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
800 36.6 21.6 1.15 40.5 31.9 36.9 21.8 1.14 38.8 2.0 32.6
7.0 1.4 3.2 1000 39.0 24.7 1.17 43.0 33.3 39.4 24.9 1.16 41.2 2.1 34.0
1200 40.2 28.0 1.23 44.4 32.6 40.6 28.3 1.22 42.6 2.2 33.3
800 36.7 21.8 1.10 40.4 33.2 37.0 22.0 1.09 38.9 1.8 33.9
50 10.0 2.6 6.0 1000 39.1 24.9 1.13 42.9 34.7 39.5 25.2 1.12 41.3 1.9 35.4
1200 40.3 28.3 1.19 44.3 34.0 40.7 28.6 1.17 42.7 2.0 34.6
800 36.8 21.8 1.08 40.5 34.0 37.1 22.0 1.07 39.1 1.6 34.7
13.0 4.1 9.5 1000 39.2 24.9 1.10 43.0 35.5 39.6 25.2 1.09 41.6 1.7 36.2
1200 40.4 28.3 1.16 44.4 34.7 40.8 28.6 1.15 42.9 1.8 35.4
800 32.9 21.4 1.53 38.1 21.5 33.7 21.2 1.51 34.7 4.1 22.3
7.0 1.3 3.0 1000 34.5 23.8 1.55 39.7 22.2 35.3 23.6 1.53 36.2 4.3 23.0
1200 35.5 26.8 1.61 41.0 22.1 36.4 26.5 1.59 37.4 4.5 22.9
800 33.1 21.7 1.48 38.1 22.3 33.7 21.7 1.47 34.9 3.8 23.0
70 10.0 2.4 5.6 1000 34.7 24.1 1.50 39.8 23.0 35.4 24.1 1.49 36.4 4.0 23.7
1200 35.7 27.1 1.56 41.1 22.9 36.5 27.1 1.54 37.6 4.1 23.6
800 33.3 21.8 1.46 38.2 22.9 33.8 22.1 1.44 35.2 3.5 23.4
13.0 3.8 8.8 1000 34.9 24.2 1.48 39.9 23.6 35.4 24.6 1.46 36.7 3.7 24.2
1200 36.0 27.2 1.53 41.2 23.5 36.5 27.6 1.52 37.9 3.8 24.1
800 27.9 20.2 1.91 34.4 14.6 29.0 19.6 1.89 29.2 6.3 15.3
7.0 1.2 2.8 1000 28.8 21.9 1.93 35.4 14.9 30.0 21.2 1.91 30.0 6.5 15.7
1200 29.7 24.3 1.97 36.4 15.1 30.9 23.6 1.95 30.8 6.7 15.8
800 28.2 20.4 1.87 34.6 15.1 29.0 20.3 1.85 29.5 5.9 15.7
90 10.0 2.3 5.3 1000 29.1 22.1 1.89 35.6 15.4 30.0 22.0 1.87 30.3 6.1 16.0
1200 30.0 24.6 1.93 36.6 15.5 30.9 24.4 1.91 31.2 6.3 16.2
800 28.5 20.6 1.84 34.8 15.5 29.1 21.0 1.82 29.8 5.5 15.9
13.0 3.6 8.3 1000 29.4 22.3 1.86 35.7 15.8 30.0 22.8 1.84 30.6 5.6 16.3
1200 30.3 24.8 1.90 36.8 15.9 30.9 25.3 1.88 31.5 5.8 16.4
800 22.8 18.4 2.26 30.5 10.1 24.1 17.5 2.23 23.1 8.6 10.8
7.0 1.1 2.7 1000 23.2 19.4 2.27 30.9 10.2 24.5 18.5 2.24 23.4 8.7 10.9
1200 23.9 21.4 2.28 31.7 10.5 25.2 20.3 2.26 24.0 9.0 11.2
800 23.2 18.6 2.23 30.8 10.4 24.1 18.3 2.21 23.6 8.1 10.9
110 10.0 2.2 5.0 1000 23.5 19.6 2.24 31.2 10.5 24.5 19.4 2.22 23.9 8.2 11.0
1200 24.3 21.6 2.25 32.0 10.8 25.2 21.3 2.23 24.5 8.4 11.3
800 23.5 18.8 2.20 31.0 10.7 24.1 19.3 2.18 24.0 7.5 11.1
13.0 3.4 7.8 1000 23.9 19.9 2.21 31.4 10.8 24.5 20.4 2.19 24.3 7.6 11.2
1200 24.6 21.9 2.22 32.2 11.1 25.2 22.5 2.20 24.9 7.8 11.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
65
E SERIES SPECIFICATION CATALOG

Microprocessor Control Features and Operation


The E Series control system is a microprocessor- high pressure switch for safety, a low pressure switch to
based printed circuit board conveniently located in the unit prevent loss of charge damage, and a low suction temper-
control box for accessibility. The microprocessor control ature thermistor for freeze protection. Upon a continuous
is specifically designed for the E Series heat pumps 30-second measurement of the fault (immediate for high
which integrate the ECM2 blower motor. All ECM2 airflow pressure), compressor operation is suspended (see Fault
selections are conveniently configured on the control via Retry below), and the appropriate lockout LED begins
DIP switches. The microprocessor provides control of the flashing.
entire unit as well as outputs for status modes, faults, and
diagnostics. Low voltage terminal strips provide all neces- Testing
sary terminals for field connections. LEDs are located on The E Series control allows service personnel to
the front of the unit for quick inspection without removing shorten most timing delays for faster diagnostics.
any access panels. The control offers optimal space con-
Fault Retry
ditioning. The board accepts traditional 24VAC thermostat
All faults (except for low RPM faults with the ECM2 fan
inputs.
motor) are retried twice before finally locking the unit out.
Startup An output signal (10) is made available for a fault LED
The unit will not operate until all the inputs and safety at the thermostat. The “fault retry” feature is designed to
controls are checked for normal conditions. At first power- prevent nuisance service calls.
up, a four-minute delay is employed before the compres- Diagnostics
sor is energized. The E Series control board allows all inputs and
Component Sequencing Delays outputs to be displayed on the LEDs for fast and simple
Components are sequenced and delayed for optimum control board diagnosis.
space conditioning performance.
Resistance Heat Control
Accessory Relay The electric heat control module contains the appropri-
An accessory relay on the control board allows for field ate high-voltage control relays. Control signals energize
connection of solenoid valves, electronic air cleaners, etc. the relays in the proper sequence, and the LED display
The accessory relay has a normally open output and a board indicates which stages are energized.
normally closed output.
Fan Speed Control
Short Cycle Protection A DIP switch on the E Series control allows field
The control employs a minimum “off” time of four min- selection of 15% reduced fan speeds for cooling in the
utes and a minimum “on” time of one minute to provide for dehumidification mode or medium and high fan speeds for
short cycle protection of the compressor. cooling in the normal mode.

Loop Pump Slaving Signals Hot Water High Limit


A signal between multiple E Series control boards at This mode occurs when the hot water input tempera-
the slave inputs and outputs (SL1-In and Out) will provide ture is at or above 130°F for 30 continuous seconds. The
for remote control of the loop pump on any unit. DHW limit status LED on the unit illuminates and the hot
water pump de-energizes. Hot water pump operations
Condensate Overflow Protection resume on the next compressor cycle or after 30 minutes
The E Series control board incorporates an impedance of continuous compressor operation during the current
sensing liquid sensor at the top of the drain pan. Upon a thermostat demand cycle.
continuous 30-second sensing of the condensate, com-
pressor operation is suspended (see Fault Retry), and the Hot Water Pump Switch
condensate overflow lockout LED begins flashing. When the pump switch is engaged, hot water pump
operation is prevented, and the pump status LED on the
Shutdown Input unit illuminates.
A 24VAC common signal to the “shutdown” input on
the control board puts the unit into shutdown mode. Com- ECM2 Airflow Selection DIP Switches (SW1)
pressor, hot water pump and fan operation are suspended. A 12-position DIP switch package on the E Series control-
ler allows the airflow levels to be set for low, medium and
Safety Controls high speed (refer to the Fan Performance Tables on pages
The E Series control receives separate signals for a 19-20).

66
E SERIES SPECIFICATION CATALOG

Description of Operation
Heating Operation Cool, 2nd Stage (Y1, Y2, O) Single Speed Units
Heat, 1st Stage (Y1) The fan changes to high speed (85% of high speed if
The fan motor is started on low speed immediately, the in dehumidification mode) 15 seconds after the “Y2” input.
loop pump is energized 5 seconds after the “Y1” input is Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units
received, and the compressor is energized on low capac- The compressor is de-energized immediately, the
ity 10 seconds after the “Y1” input. The fan is switched to second loop pump is energized 5 seconds after the “Y2”
medium speed 15 seconds after “Y1” input. The hot water input, and the hot water pump is cycled 30 seconds after
pump is cycled 30 seconds after the "Y1" input. the “Y2” input. The fan changes to high speed (85% of
Heat, 2nd Stage (Y1,Y2) Single-Speed Units high speed if in dehumidification mode) 45 seconds after
The hot water pump is de-energized, which directs all the “Y2” input and the compressor is energized on high
heat to satisfying the thermostat, and the fan changes to capacity 60 seconds after the “Y2” input.
high speed 15 seconds after the "Y2" input. Fan (G only)
Heat, 2nd Stage (Y1,Y2) Dual Capacity Units The fan starts on low speed. Regardless of fan input
The compressor is de-energized immediately, the “G” from thermostat, the fan will remain on low speed for
second loop pump is energized 5 seconds after the “Y2” 30 seconds at the end of each heating, cooling or emer-
input, and the hot water pump is cycled 30 seconds after gency heat cycle.
the “Y2” input. The fan changes to high speed 45 seconds
after the “Y2” input and the compressor is energized on
Lockout Conditions
During lockout mode, the appropriate unit and ther-
high capacity 60 seconds after the “Y2” input.
mostat lockout LEDs will illuminate. The compressor, loop
Heat, 3rd Stage (Y1,Y2,W) Single-Speed Units pump, hot water pump, and accessory outputs are de-
The first stage of resistance heat is energized 10 energized. Unless the lockout is caused by an ECM2 low
seconds after “W” input, and with continuous 3rd stage RPM fault, the fan will continue to run on low speed. If the
demand, the additional stages of resistance heat engage thermostat calls for heating, emergency heat operation will
sequentially every 5 minutes. occur.
Lockout modes of any kind can be reset at the thermo-
Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units stat after a 5-second waiting period, which restores normal
The hot water pump is de-energized which directs all operation but keeps the unit lockout LED illuminated.
heat to satisfy the thermostat. The 1st stage of resistance Interruption of power to the unit will reset a lockout without
heat is energized 10 seconds after “W” input, and with a waiting period and clear all lockout LEDs.
continuous 3rd stage demand, the additional stages of
resistance heat engage sequentially every 5 minutes. High Pressure
This lockout mode occurs when the normally closed
Emergency Heat (W only) safety switch is opened momentarily (set at 600 PSI).
The fan is started on high speed, and the first stage of re-
sistance heat is energized 10 seconds after the "W" input. Low Pressure
Continuing demand will engage the additional stages of This lockout mode occurs when the normally closed
resistance heat sequentially every 2 minutes. switch is opened for 30 continuous seconds (set at 40
PSI).
Cooling Operation
In all cooling operations, the reversing valve directly Freeze Protection (Water Flow)
tracks the “O” input. Thus, anytime the “O” input is pres- This lockout mode occurs when the freeze thermistor
ent, the reversing valve will be energized. temperature is at or below the selected freeze protection
point (well 30°F or loop 15°F) for 30 continuous seconds.
Cool, 1st Stage (Y1, 0)
The fan motor is started on low speed immediately, Condensate Overflow
the loop pump is energized 5 seconds after the “Y1” input This lockout mode occurs when the condensate over-
is received, and the compressor is energized 10 seconds flow level has been reached for 30 continuous seconds.
after the “Y1” input. The fan is switched to medium speed Fan RPM
15 seconds after “Y1” input (85% of medium speed if in The control board monitors fan RPM to sense opera-
dehumidification mode). The hot water pump is cycled 30 tion. This lockout mode occurs if the fan RPM falls below
seconds after the “Y1” input. the low RPM limit (100 RPM) for 30 continuous seconds.

67
E SERIES SPECIFICATION CATALOG

Operation Logic Data Table


OPERATION HEATING COOLING
FAN ON SL1 - IN ON SL2 - IN ON
LOGIC TABLE STG1 STG2 STG3 EMERG STG1 STG2
SINGLE SPEED
Compressor On On On Off On On - - -
ECM2 Normal Med High High High Med High Low - -
ECM2 Dehumidify Med High High High 85% Med 85% High Low - -
Rev Valve Off Off Off Off On On - - -
Loop Pump On On On Off On On - On -
DHW Pump On Off Off Off On On - - -
Aux Heater Off Off Staged Staged Off Off - - -
Slave 1- Out On On On Off On On - - -
Emerg LED Off Off Off On Off Off Off - -
T-Stat Signal Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O G
DUAL CAPACITY
Compressor-Lo On Off Off Off On Off - - -
Compressor-Hi Off On On Off Off On - - -
ECM2 Normal Med High High High Med High Low - -
ECM2 Dehumidify Med High High High 85% Med 85% High Low - -
Rev Valve Off Off Off Off On On - - -
Loop Pump-Stg 1 On On On Off On On - On -
Loop Pump-Stg 2 Off On On Off Off On - - On
DHW Pump On On Off Off On On - - -
Aux Heater Off Off Staged Staged Off Off - - -
Slave 1- Out On On On Off On On - - -
Slave 2- Out Off On On Off Off On - - -
Emerg LED Off Off Off On Off Off - - -
T-Stat Signal Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O G - -

68
E SERIES SPECIFICATION CATALOG

Logic Board Physical Layout

240V - L1

240V - L2
Fused L2
Fused L2
240V - L1

Fused L1

240V - L2
Fused L2
Fused L2
F1 F1

N.O. N.O. N.C. N.O.


N.O.
Com Com
CR1- DHW CR2- Loop
Pump Pump CR3- CR4-
CC-GND 9 1
CC 10 2
CCLO Microprocessor 11 3
CCHI 12 4 P6
13 5
SW1 SW2 SW3 14 6
Off On Off On Off On 15 7
1 1 Test / Norm 1 Dual Cap / 1 Speed 16 8
2 2 Loop / Well 2 ECM / ECM2 8 1
3 3 Fan / Comp 3 No RPM / RPM 9 2
4 4 Dehum / Norm 4 EH 10 3
P5
5 5 No Htg3 / Htg3 5 Future Use 11 4
6 6 Inputs / Norm 12 5
7 7 Outputs / Norm 13 6
8 8 24 VAC / TA32E12 14 7
9
10
11
12
P4 P1 P2 P3
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 1 2 3
1 2 3
Shut C C SL1 SL1 SL2 SL2 ACC ACC ACC
Thermostat R C Y1Y2 W O G L Dow IN Out IN Out NO NC COM
R
C
Y1
Y2
W
O
G
L

69
E SERIES SPECIFICATION CATALOG

Engineering Guide Specifications


General - The reverse cycle heating/cooling units The coaxial water-to-refrigerant heat exchanger shall
shall be either suspended type with horizontal air inlet and be designed for low water pressure drop and constructed
discharge or floor mounted type with horizontal air inlet of a convoluted cupronickel inner tube and a steel outer
and vertical upflow/downflow air discharge. Units shall be tube. The thermostatic expansion valve shall provide
ARI/ISO 13256-1 certified and listed by a nationally rec- proper superheat over the entire liquid temperature range
ognized safety-testing laboratory or agency, such as ETL with minimal “hunting.” The valve shall operate bidirection-
Testing Laboratory. Each unit shall be computer run-tested ally without the use of check valves.
at the factory. Each unit shall be mounted on a pallet and The water-to-refrigerant heat exchanger, optional
shipped in a corrugated box or stretch-wrapped. desuperheater coil and refrigerant suction lines shall be
The units shall be designed to operate with entering insulated to prevent condensation at low liquid tempera-
liquid temperature between 25°F and 110°F. tures.

Casing & Cabinet - The cabinet shall be fabricated Fan Motor & Assembly - The fan shall be a direct
from heavy-gauge steel and finished with corrosion-resis- drive centrifugal type with a dynamically balanced wheel.
tant powder coating. The interior shall be insulated with The housing and wheel shall be designed for quiet low out-
1/2-inch thick, multi-density, coated glass fiber with edges let velocity operation. The fan housing shall be removable
sealed or tucked under flanges to prevent the introduction from the unit without disconnecting the supply air ductwork
of glass fibers into the discharge air. One to two blower for servicing of the fan motor. The fan motor shall be a
and three compressor compartment access panels shall PSC or variable-speed ECM2 type. The ECM2 fan motor
be removable with supply and return ductwork in place. shall be soft starting, shall maintain constant CFM over its
The internal component layout shall provide for service ac- operating static range, and shall provide 12 CFM settings.
cess from the front side for restricted installations. The fan motor shall be isolated from the housing by rubber
A duct collar shall be provided on the supply air open- grommets. The motor shall be permanently lubricated and
ing. Standard size 1-inch pleated filters shall be provided have thermostatic overload protection. ECM2 motors shall
with each unit. Vertical units shall have a return air filter be long-life ball bearing type.
rack/duct collar; the horizontal units shall have a filter Electrical - A microprocessor-based controller that in-
bracket. The upflow vertical units shall have a removable terfaces with a multi-stage electronic thermostat to monitor
insulated divider panel between the air handling section and control unit operation shall be provided. The control
and the compressor section to minimize the transmission shall provide operational sequencing, fan speed control,
of compressor noise and to permit operational service test- fan failure high and low pressure switch monitoring, freeze
ing without air bypass. Vertical units shall be supplied with protection, hot water limit thermistor sensing, condensate
left or right horizontal air inlet and top or bottom vertical air overflow sensing, auxiliary heat staging, lockout mode
discharge. Horizontal units shall be supplied with left or control, hot water and loop pump control, LED status and
right air inlet and side or end air discharge. fault indicators, fault memory, field selectable options, and
Refrigerant Circuit - All units shall contain a sealed accessory output.
refrigerant circuit including a hermetic motor-compressor, A detachable terminal block with screw terminals will
bidirectional thermostatic expansion valve, finned tube be provided for field control wiring. All units shall have
air-to-refrigerant heat exchanger, reversing valve, coaxial knockouts for entrance of low and line voltage wiring. The
tube water-to-refrigerant heat exchanger, optional desu- fan motor and control box shall be harness plug wired for
perheater coil, and service ports. easy removal.
Compressors shall be high-efficiency single speed
Piping - Supply and return water connections (and
reciprocating or scroll, or dual capacity reciprocating type
optional desuperheater connections) shall be 1-inch FPT
designed for heat pump duty and mounted on vibration
brass swivel fittings, which provide a union and eliminate
isolators. Compressor motors shall be single-phase PSC
the need for pipe wrenches and sealants when making
with overload protection. The electro-coated coil shall
field connections. All water piping shall be insulated to
be sized for low-face velocity and constructed of lanced
prevent condensation at low liquid temperatures, on the
aluminum fins bonded to rifled copper tubes in a staggered
vertical upflow units, the condensate connection shall be a
pattern not less than three rows deep.
3/4-inch PVC socket with internally-trapped hose that can
be routed to front or side locations.

70
E SERIES SPECIFICATION CATALOG

Engineering Guide Specifications


Hanger Kit (field-installed horizontal units only)
The hanger kit shall consist of galvanized steel brackets,
bolts, lock washers, and isolators and shall be designed
to fasten to the unit bottom panel for suspension from 3/8-
inch threaded rods. Unit sizes 024-035 shall include four
brackets. Unit sizes 036-072 shall include six brackets.

Options & Accessories


Desuperheater - An optional heat reclaiming desu-
perheater coil of vented double-wall copper construction
suitable for potable water shall be provided. The coil and
hot water circulating pump shall be factory mounted inside
the unit.
Thermostat (field-installed) - A multi-stage auto-
changeover electronic digital thermostat shall be provided.
The thermostat shall offer three heating and two cooling
stages with precise temperature control. An OFF-HEAT-
AUTO-COOL-EMERG system switch, OFF-AUTO fan
switch, and indicating LEDs shall be provided. The thermo-
stat shall display in °F or °C. An optional remote outdoor
sensor shall be available.
Electronic Air Cleaner (field-installed) - A 1-inch
electronic air cleaner, cleanable 97% efficiency at 0.3 mi-
crons and larger, shall be provided in lieu of the standard
throwaway filter. The pressure drop across the filter shall
not exceed 0.2-inch w.g. at 300 fpm force velocity.
Earth Loop Flow Center (field-installed) - A self-con-
tained module shall provide all liquid flow, fill and connec-
tion requirements for ground source closed loop systems
up to 20 GPM. The pumps shall be wired to a power block
located in the nearest unit. The heat pump units shall con-
tain low voltage pump slaving control so that two units may
share one flow center.
Auxiliary Heater (field-installed) - An electric resis-
tance heater shall provide supplemental and/or emergency
heating capability. Vertical units shall have the control box
and resistance heater coil assembly mounted internally.
For horizontal units, the control box shall be mounted in-
ternally while the resistance heater coil assembly shall be
mounted externally. A low voltage plug shall be provided
in each unit for quick auxiliary heat connection. The heater
shall operate in sequenced stages as controlled by the
unit’s microprocessor. The heater shall feed line voltage
power to the unit fan and transformer to provide emer-
gency heat capability in the event of an open compressor
circuit breaker.
Filter Rack/Duct Collar (field-installed) - A filter
rack/duct collar shall be provided for each horizontal unit,
to accept standard size 1-inch filters.

71
Manufactured by WFI
WaterFurnace International, Inc.
9000 Conservation Way
Fort Wayne, IN 46809
www.waterfurnace.com

Product: E Series
Type: Geothermal/Water Source Heat Pumps
Size: 2 thru 6 Ton Single Speed
3 thru 6 Ton Dual Capacity

WFI has a policy of continuous product research Document Type: Specification Catalog
and development and reserves the right to change Part Number: SP1461
design and specifications without notice. Release Date: 09/04
©2004 WFI. Supercedes: SP1461 (08/04)