Design Features
Factory Options
Accessories
Dimensional Data
Physical Data
Performance Data
WaterFurnace
SP1461 09/04
E SERIES SPECIFICATION CATALOG
All E Series units utilize the ozone-safe R-410A refrigerant to meet the most stringent EPA requirements now and for
many years to come. Coated air coils add durability and longer life. A sophisticated microprocessor control sequences all
components during operation for optimum performance, and provides easy-to-use troubleshooting features with fault lights
and on-board diagnostics. Unit configurations include horizontal, vertical top discharge and vertical bottom discharge.
Heavy-gauge metal cabinets are coated with durable poly paint for long lasting protection. Single speed units are available
with either ECM2 or PSC blower motors. Dual capacity units feature the Bristol Twin Single compressor and include ECM2
blower motors.
E Series products are performance-certified to ARI ISO 13256-1 standards, are ETL listed, and are
ENERGYSTAR® qualified.
As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit
built is exposed to a wide range of quality control procedures throughout the assembly process and is then subjected to
a rigorous battery of computerized run tests to certify that it meets or exceeds performance standards for efficiency and
safety, and will perform flawlessly at startup. As further affirmation of our quality standards, each unit carries our exclusive
Quality Assurance emblem, signed by the final test technician.
WaterFurnace International’s corporate headquarters and manufacturing facility is located in Fort Wayne, IN. A scenic
three-acre pond located in front of the building serves as our geothermal heating and cooling source to comfort-condition
our 110,000 square feet of manufacturing and office space. As a pioneer, and now a leader in the industry, the team of
WaterFurnace engineers, customer support staff and skilled assembly technicians is dedicated to providing the finest com-
fort systems available.
By choosing or specifying WaterFurnace E Series products, you can be assured that your customer is investing in the ulti-
mate comfort system and peace of mind for many years to come.
2
E SERIES SPECIFICATION CATALOG
Table of Contents
3
E SERIES SPECIFICATION CATALOG
DUAL CAPACITY
COOLING HEATING COOLING HEATING
UNIT
SPEED CFM GPM 77º F EWT 32º F EWT 68º F EWT 41º F EWT
SIZE
BTU/HR EER BTU/HR COP BTU/HR EER BTU/HR COP
HIGH 1200 9.0 36,200 16.7 24,700 3.5
E036
LOW 800 5.0 18,800 24.0 12,800 4.3
HIGH 1500 12.0 48,900 16.1 35,800 3.5
E048
LOW 1000 6.0 29,800 22.2 21,200 4.2
HIGH 2000 14.0 60,000 17.0 41,800 3.9
E060
LOW 1200 8.0 33,200 25.9 22,600 4.7
HIGH 2200 16.0 69,000 14.1 51,000 3.7
E072
LOW 1400 10.0 36,800 24.3 25,700 4.6
Notes: Rated in accordance with ARI/ISO Standard 13256-1.
Cooling capacities based on 80.6°F DB, 66.2°F WB.
Heating capacities based on 68°F DB.
4
E SERIES SPECIFICATION CATALOG
Model Nomenclature
E 048 T L 1 0 1 N B D S S A
Family Vintage
E Series R-410A
Sound Kit
Voltage A = None
1 = 208-230/60/1 B = Blanket
(standard on 024, 030, 035, 036,
048, 060, 072)
Coax Options
N = Cupronickel
5
E SERIES SPECIFICATION CATALOG
Design Features
Application Flexibility • Utilizes the ozone-friendly R-410A refrigerant which
• Safe, efficient operation in a wide range of liquid produces higher efficiencies and warmer discharge air
temperatures (25° F to 110° F) and flow rates (as low temperatures.
as 1.5 GPM/ton in open loop applications when EWT
>50°F). Service Advantages
• Top or bottom air discharge for upflow or counterflow • Removable panels (three for the compressor compart-
installations in vertical units, side or end discharge for ment and one or two for the air handling compartment)
horizontal units. provide quick access to all internal components with
• True left or right return air locations—vertical units ductwork in place.
include filter rack/duct collar. • Easily accessible thermal expansion valve.
• Variable-speed ECM2 blowers permit various duct ap- • Brass, swivel-type water connections for quick connec-
plications. tion union, and elimination of wrenches and sealants
• Narrow cabinet for easy movement through doorways. during installation.
• Internally trapped condensate piping for neat, compact • Insulated divider and separate air handling/compressor
installation (vertical upflow units only). access panels permit service testing without air bypass.
• Optional field-installed auxiliary electric heater. • Designed for front access in tight applications.
• Corner-located electrical box for field wiring from two • LED fault and status lights with memory for easy diag-
sides. nostics.
• Fuse-protected loop pump power block for easy wiring. • Detachable thermostat connection strip for wiring conve-
nience.
• Loop pump slaving feature allows multiple units to
share one flow center. • Hot water pump shut-off switch for easy startup and
service.
• Relay to control field-mounted accessories.
• Control box and fan motors have quick-attach wiring
• Field-selectable freeze protection setting for well or
plugs for easy removal.
closed loop systems.
• Internal drop-out blower with permanently-lubricated ball
• Field-selectable voltage switch for low voltage applica-
bearing motor.
tions.
• High- and low-pressure service ports in refrigerant cir-
Operating Efficiencies cuit.
• ARI/ISO 13256-1 rating for heating COPs, cooling • Fan and transformer powered from auxiliary heat supply
EERs and low water flow requirements. (when installed) to provide emergency heat with open
• Optional desuperheater with internal pump generates compressor circuit breaker.
hot water at considerable savings while improving over-
all system efficiency. Factory Quality
• All units are computer run-tested, with conditioned
• High-stability expansion valve delivers optimum refrig-
source water, in all modes to insure efficiency and reli-
erant flow over a wide range of conditions and provides
ability.
bidirectional operation without troublesome check
valves. • Heavy-gauge steel cabinets are painted with durable
powder coat paint for long lasting beauty and service.
• Efficient reciprocating and scroll compressors operate
quietly. • All refrigerant brazing is performed in a nitrogen atmo-
sphere.
• Oversized coaxial tube water-to-refrigerant heat ex-
changer operates at low liquid pressure drops. • All units are deep evacuated to less than 150 microns
prior to refrigerant charging.
• Convoluted cupronickel water tube functions efficiently
at low flow rates. • All joints are helium leak-tested to insure an annual leak
rate of less than 1/4 ounce.
• Oversized rifled copper tube/lanced aluminum fin air-to-
refrigerant heat exchanger provides high efficiencies at • Coaxial heat exchanger, refrigerant suction lines, de-
low-face velocity. superheater coil, and all water pipes are fully insulated
to reduce condensation problems in low temperature
• Large, low-RPM blowers with variable-speed motors
operation.
provide quiet and efficient air movement with high static
capability.
6
E SERIES SPECIFICATION CATALOG
Design Features
• Electro-coated air coils for extended life.
• Noise reduction features include isolation mounted com-
pressors and soft starting blower motors; insulated com-
pressor compartment; interior cabinet insulation using 1/2-
inch coated glass fiber. Selected units include compressor
blanket for quiet operation (available on other units as an
option).
• Safety features include high- and low-pressure refrigerant
controls to protect the compressor; condensate overflow
protection; freeze protection sensor to safeguard the co-
axial heat exchanger; fan start detection; hot water high-
limit desuperheater pump shutdown; fault lockout enables
emergency heat and prevents compressor operation until
thermostat or circuit breaker is reset.
Microprocessor Benefits
• Digital auto-changeover thermostat with 3-stage heating/
2-stage cooling holds precise temperature and provides
varying fan speed control.
• Component sequencing delays for quiet startup, shutdown,
and timed staging of auxiliary electric heat.
• ECM2 fan speed control provides higher supply air tem-
perature in heating, better dehumidification in cooling, and
quiet operation at reduced airflows in all modes.
• Hot water limit prevents scalding, and pump shuts down
automatically when full unit capacity is needed for heating.
7
E SERIES SPECIFICATION CATALOG
Vertical Features
Top Air Discharge
Factory mounted
filter rack accepts
standard size
Powder coated, filters
heavy-gauge steel
Drain pan
cabinet
overflow
protection
Optional auxiliary
heater with Insulated access
electronic controls panels
8
E SERIES SPECIFICATION CATALOG
Vertical Features
Small Cabinet ▬ Bottom Air Discharge
Compressor
Optional factory
installed water
heating system
Insulation for low with built-in coil
temperature and pump
operation
Reversing
valve
Bidirectional
expansion valve Easily removable
control box
Internally Microprocessor
removable blower control
Internally
insulated cabinet
Variable speed, soft-
starting ECM2 fan
motor (optional)
9
E SERIES SPECIFICATION CATALOG
Vertical Features
Large Cabinet ▬ Bottom Air Discharge
Brass swivel
water connection
Reversing valve
Internally trapped
condensate line
Brass swivel
water connection
10
E SERIES SPECIFICATION CATALOG
Horizontal Features
Compressor Compartment
Reversing valve
Optional factory
installed water
Filter bracket accepts
heating system
standard size filters
with built-in coil
and pump
Each unit is quality
built and run-tested
Bidirectional
expansion valve
Insulation for low
temperature
Insulated access
operation
panels
Compressor
Brass swivel water
connections
Fault and diagnostic
LEDs
Microprocessor
control Easily removable
control box
Optional auxiliary
Auxiliary optional heater with
heater coil assembly electronic controls
Variable speed,
soft starting ECM2
fan motor (optional)
Internally insulated
cabinet
Supply Air
L E D E
G F D F H
I J 1”
Access Panels
t Fron
Retu Fron t
K rn A
ir rn Air
Line Voltage Retu
DHW Out
C
DHW In
Alternate Drain
Water Out
Water In
Low Voltage
A B B A
Access Panels
Drain
E024, E030, E035 1.00" Swivel 1-3/8" 26.2 22.5 52.0 14.0 14.0 6.1 7.5 4.4 2.4 20.8 28.9 1.7
E036, E040, E047, E048,
1.00" Swivel 1-3/8" 31.2 25.5 58.4 18.0 18.0 6.6 6.5 3.7 1.1 27.3 34.0 1.7
E058, E060, E066, E072
12
E SERIES SPECIFICATION CATALOG
Line Voltage
L
Water Out
Water In
Low Voltage
C Fron
t Aux Htr Knockout t
Fron
K Retu
rn Air Air
Access Panels rn
Retu
Drain
I A B B A
J
H F E D D E F G
Access Panels
t Fron
Retu Fron t
K rn A
ir rn Air
Retu
DHW Out
C
Alternate Drain
Water Out
Water In
Line Voltage
Drain
Low Voltage
DHW In
A B B A
Access Panels
G F E D M D E F H
M
13
E SERIES SPECIFICATION CATALOG
E E
Line Voltage
D D
F DHW Out F
DHW In
G Water Out G
Water In
Low Voltage B
Return Air B
A Return Air
A
Front
SIDE DISCHARGE SIDE DISCHARGE
Return Air
K J K K
J J
C
H C I
I H
Drain
Supply Air Supply Air
K L
L K
H
H
M
Supply Air
WATER
MODEL A B C D E F G H I J K L M
CONNECTION
E024
E030 1.00” Swivel 22.50 63.00 21.25 31.00 3.56 1.00 19.25 10.49 9.1 8.25 9.30 5.75 2.17
E035
E036 1.00” Swivel 25.50 72.00 21.25 31.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E040
E047 1.00” Swivel 25.50 72.00 21.25 36.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E048
E058 1.00” Swivel 25.50 77.00 21.25 41.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E060 1.00” Swivel 25.50 77.00 21.25 41.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E066 1.00” Swivel 25.50 82.00 21.25 41.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
E072 1.00” Swivel 25.50 82.00 21.25 46.00 2.56 1.00 19.25 13.74 5.66 7.77 13.24 5.02 1.85
Notes: All low voltage knockouts are 7/8 inch.
Unit line voltage knockouts are 1-1/8 inch.
Filter bracket extends beyond side of cabinet 1-1/8 inch and is removable.
Electric heater power knockouts are 1-1/8 inch and 1-3/8 inch.
14
E SERIES SPECIFICATION CATALOG
15
E SERIES SPECIFICATION CATALOG
Physical Data
Vertical
SINGLE SPEED DUAL CAPACITY
MODEL
E024 E030 E035 E040 E047 E058 E066 E036 E048 E060 E072
Fan Wheel
ECM 9x7 9x7 9x7 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
PSC 9x7 9x7 9x7 10 x 10 10 x 10 11 x 10 11 x 10 n.a. n.a. n.a. n.a.
Fan Motor HP
ECM 1/2 1/2 1/2 1/2* 1/2* 1 1 1/2 1/2* 1 1
PSC 1/5 1/3** 1/2 1/2 1/2 1 1 n.a. n.a. n.a. n.a.
Compressor Reciprocating Scroll Dual Capacity (Twin Single)
Refrigerant Charge
R-410A (oz.) 66.0 67.0 72.0 70.0 72.0 90.0 94.0 61.0 77.0 100.0 103.0
Air Coil
Dimensions (in.) 20 x 30 20 x 30 20 x 30 32 x 25 32 x 25 36 x 25 36 x 25 28 x 25 32 x 25 36 x 25 36 x 25
Face Area (sq. ft.) 4.2 4.2 4.2 5.6 5.6 6.6 6.3 4.9 5.6 6.3 6.3
Number of Rows 3 3 3 3 3 3 3 3 3 3 3
Filter (1”)
Disposable 24 x 31 24 x 31 24 x 31 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36 30 x 36
Electrostatic EAF2431 EAF2431 EAF2431 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036 EAF3036
Electronic EAC2431 EAC2431 EAC2431 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036 EAC3036
Weight (lbs.) 300 301 306 365 389 441 447 376 398 460 463
Notes: * E040, 047, 048 available with optional 1 HP ECM motor.
** E030 265 volt unit uses a 1/2 HP PSC motor.
Horizontal
SINGLE SPEED DUAL CAPACITY
MODEL
E024 E030 E035 E040 E047 E058 E066 E036 E048 E060 E072
Fan Wheel
ECM 9x7 9x7 9x7 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
PSC 9x7 9x7 9x7 10 x 10 10 x 10 11 x 10 11 x 10 n.a. n.a. n.a. n.a.
Fan Motor HP
ECM 1/2 1/2 1/2 1/2* 1/2* 1 1 1/2 1/2* 1 1
PSC 1/5 1/3** 1/2 1/2 1/2 1 1 n.a. n.a. n.a. n.a.
Compressor Reciprocating Scroll Dual Capacity (Twin Single)
Refrigerant Charge
R-410A (oz.) 66.0 67.0 72.0 70.0 72.0 90.0 94.0 58.0 81.0 97.0 103.0
Air Coil
Dimensions (in.) 20 x 30 20 x 30 20 x 30 20 x 35 20 x 35 20 x 40 20 x 45 20 x 30 20 x 35 20 x 40 20 x 45
Face Area (sq. ft.) 4.2 4.2 4.2 4.9 5.6 5.6 6.3 4.2 4.9 5.6 6.3
Number of Rows 3 3 3 3 3 3 3 3 3 3 3
Filter (1”)
Disposable 20 x 37 20 x 37 20 x 37 20 x 37 20 x 37 (1) 18 x 20 (2) 20 x 24 20 x 37 20 x 37 (1) 18 x 20 (2) 20 x 24
Disposable (1) 20 x 24 (1) 20 x 24
Electrostatic EAF2037 EAF2037 EAF2037 EAF2037 EAF2037 EAF2042 EAF2048 EAF2037 EAF2037 EAF2042 EAF2048
Electronic EAC2037 EAC2037 EAC2037 EAC2037 EAC2037 EAC2042 EAC2048 EAC2037 EAC2037 EAC2042 EAC2048
Weight (lbs.) 300 301 306 365 389 441 447 376 398 460 463
Notes: * E040, 047, 048 available with optional 1 HP ECM motor.
* E040, 047, 048 available with optional 1 HP ECM motor.
16
E SERIES SPECIFICATION CATALOG
SINGLE SPEED
E024 208-230/60/1 197/253 13.0 8.3 48.0 4.0 5.4 0.4 18.1 20.2 25 25
E030 208-230/60/1 197/253 15.5 9.9 55.0 4.0 5.4 0.4 19.7 22.2 30 30
E035 208-230/60/1 197/253 19.0 12.2 66.0 4.0 5.4 0.4 22.0 25.0 35 35
E040 208-230/60/1 197/253 24.0 15.4 83.0 4.0 5.4 0.4 25.2 29.0 40 40
E040* 208-230/60/1 197/253 24.0 15.4 83.0 7.0 5.4 0.4 28.2 32.0 45 45
E047 208-230/60/1 197/253 32.0 20.5 109.0 4.0 5.4 0.4 30.3 35.4 50 50
E047* 208-230/60/1 197/253 32.0 20.5 109.0 7.0 5.4 0.4 33.3 38.4 50 50
E058 208-230/60/1 197/253 42.0 26.9 145.0 7.0 5.4 0.4 39.7 46.4 70 70
E066 208-230/60/1 197/253 47.0 30.1 158.0 7.0 5.4 0.4 42.9 50.4 80 80
DUAL CAPACITY
E036 208-230/60/1 197/253 19.5 12.5 66.0 4.0 5.4 0.4 22.3 25.4 35 35
E048 208-230/60/1 197/253 28.0 17.9 96.0 4.0 5.4 0.4 27.7 32.2 50 50
E048* 208-230/60/1 197/253 28.0 17.9 96.0 7.0 5.4 0.4 30.7 35.2 50 50
E060 208-230/60/1 197/253 38.5 24.7 130.0 7.0 5.4 0.4 37.5 43.6 60 60
E072 208-230/60/1 197/253 41.0 26.3 130.0 7.0 5.4 0.4 39.1 45.7 70 70
Notes: Always refer to unit nameplate data prior to installation.
HACR circuit breaker in United States only. All fuses are class RK-5.
* With optional 1 HP ECM2 motor.
PSC Motor
COMPRESSOR FAN EXT. INT. TOTAL MIN. MAX.
RATED VOLTAGE MAX.
MODEL MOTOR PUMP PUMP UNIT CIRCUIT HACR
VOLTAGE MIN./MAX. MCC RLA LRA FUSE
FLA FLA FLA FLA AMP BREAKER
SINGLE SPEED
E024 208-230/60/1 197/253 13.0 8.3 48.0 1.2 5.4 0.4 15.3 17.4 25 25
E030 208-230/60/1 197/253 15.5 9.9 55.0 1.5 5.4 0.4 17.2 19.7 25 25
E035 208-230/60/1 197/253 19.0 12.2 66.0 2.2 5.4 0.4 20.2 23.2 35 35
E040 208-230/60/1 197/253 24.0 15.4 83.0 2.8 5.4 0.4 24.0 27.8 40 40
E047 208-230/60/1 197/253 32.0 20.5 109.0 3.5 5.4 0.4 29.8 34.9 50 50
E058 208-230/60/1 197/253 42.0 26.9 145.0 5.9 5.4 0.4 38.6 45.3 70 70
E066 208-230/60/1 197/253 47.0 30.1 158.0 5.9 5.4 0.4 41.8 49.3 70 70
Notes: Always refer to unit nameplate data prior to installation.
HACR circuit breaker in United States only. All fuses are class RK-5.
17
E SERIES SPECIFICATION CATALOG
18
E SERIES SPECIFICATION CATALOG
19
E SERIES SPECIFICATION CATALOG
20
E SERIES SPECIFICATION CATALOG
Reference Calculations
Heating Calculations: Cooling Calculations:
HE HR
LWT = EWT - LWT = EWT +
GPM x 500 GPM x 500
HC SC
LAT = EAT + LAT (DB) = EAT (DB) -
CFM x 1.08 CFM x 1.08
LC = TC - SC
TH = HC + HW SC
S/T =
TC
Desuperheater capacity based on 0.4 GPM flow per nominal unit ton at 90°F entering hot water temperature.
Capacity data on pages 22-65 do not include water pumping watts and are based upon 15% (by volume)
methanol antifreeze solution. For non-standard EAT conditions, apply the appropriate correction factors
found below. Interpolation between EWT, GPM and CFM data is permissible. Extrapolation for heating
data down to 25°F is permissible. Catalog illustrations cover the general appearance of products at time of
publication. We reserve the right to make changes in design and construction at any time without notice.
EAT TC SC KW HR EAT HC KW HE
75/63 0.92 0.96 0.98 0.94 60 1.09 0.95 1.06
80/67 1.00 1.00 1.00 1.00 70 1.00 1.00 1.00
85/71 1.08 1.04 1.02 1.06 80 0.97 1.05 0.94
(ECM Only)
21
E SERIES SPECIFICATION CATALOG
E024
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
600 13.7 1.1 9.9 91.1 3.6 11.4 1.1 10.0 87.6 2.3 3.7
3.0 0.7 1.6
700 13.9 1.1 10.1 88.4 3.6 11.9 1.1 10.1 85.8 1.9 3.7
600 14.4 1.1 10.5 92.2 3.7 12.0 1.1 10.6 88.6 2.4 3.8
30 4.5 1.4 3.2
700 14.7 1.2 10.7 89.4 3.7 12.6 1.1 10.7 86.7 2.0 3.8
600 14.7 1.2 10.7 92.6 3.7 12.2 1.1 10.8 88.9 2.4 3.9
6.0 2.4 5.6
700 14.9 1.2 11.0 89.7 3.8 12.8 1.1 11.0 87.0 2.0 3.8
600 19.9 1.4 15.1 100.7 4.2 17.0 1.3 15.3 96.2 2.8 4.4
3.0 0.7 1.6
700 20.3 1.4 15.6 96.9 4.3 17.9 1.4 15.6 93.6 2.4 4.4
600 20.9 1.4 16.0 102.2 4.3 17.9 1.4 16.2 97.6 2.9 4.5
50 4.5 1.4 3.2
700 21.3 1.4 16.5 98.2 4.4 18.8 1.4 16.6 94.9 2.5 4.5
600 21.2 1.4 16.3 102.8 4.3 18.2 1.4 16.5 98.1 3.0 4.5
6.0 2.4 5.6
700 21.7 1.4 16.8 98.7 4.4 19.2 1.4 16.9 95.3 2.5 4.6
600 25.1 1.5 19.8 108.7 4.8 21.6 1.4 20.0 103.3 3.4 5.1
3.0 0.7 1.6
700 25.7 1.5 20.6 104.0 5.0 22.9 1.5 20.8 100.3 2.8 5.2
600 26.2 1.6 20.9 110.4 4.9 22.6 1.5 21.1 104.8 3.5 5.2
70 4.5 1.4 3.2
700 27.0 1.5 21.7 105.7 5.1 24.0 1.5 21.9 101.8 2.9 5.4
600 26.7 1.6 21.3 111.2 4.9 23.0 1.5 21.5 105.4 3.6 5.2
6.0 2.4 5.6
700 27.4 1.6 22.2 106.3 5.2 24.5 1.5 22.4 102.4 3.0 5.4
600 30.0 1.7 24.4 116.3 5.3 25.9 1.5 24.6 110.0 4.0 5.7
3.0 0.6 1.4
700 31.0 1.6 25.5 111.0 5.7 27.8 1.5 25.9 106.8 3.3 5.9
600 31.3 1.7 25.5 118.2 5.4 27.0 1.6 25.7 111.6 4.1 5.8
90 4.5 1.3 3.0
700 32.4 1.6 26.8 112.8 5.8 29.1 1.6 27.1 108.4 3.4 6.1
600 31.8 1.7 25.9 119.1 5.4 27.4 1.6 26.2 112.3 4.2 5.8
6.0 2.3 5.3
700 33.0 1.7 27.3 113.6 5.8 29.6 1.6 27.7 109.2 3.5 6.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
22
E SERIES SPECIFICATION CATALOG
E024
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
600 28.8 17.7 1.0 32.2 28.7 28.8 17.7 1.0 30.5 1.7 29.3
3.0 0.7 1.6
700 29.4 19.3 1.0 32.9 28.1 29.4 19.3 1.0 31.2 1.7 28.7
600 29.1 17.9 1.0 32.3 30.7 29.1 17.9 0.9 30.7 1.5 31.2
50 4.5 1.4 3.2
700 29.7 19.5 1.0 33.0 30.1 29.7 19.5 1.0 31.4 1.6 30.5
600 29.4 17.9 0.9 32.5 31.9 29.4 17.9 0.9 31.1 1.4 32.2
6.0 2.4 5.6
700 30.0 19.5 1.0 33.2 31.3 30.0 19.5 1.0 31.8 1.4 31.6
600 25.6 16.5 1.3 29.9 20.1 25.7 16.5 1.2 27.0 2.9 20.7
3.0 0.7 1.6
700 26.1 17.9 1.3 30.6 19.8 26.2 18.0 1.3 27.6 3.0 20.4
600 25.8 16.6 1.2 29.9 21.5 26.0 16.7 1.2 27.3 2.7 22.0
70 4.5 1.4 3.2
700 26.4 18.1 1.3 30.6 21.1 26.5 18.1 1.2 27.9 2.8 21.6
600 26.1 16.6 1.2 30.1 22.3 26.2 16.7 1.2 27.7 2.5 22.7
6.0 2.4 5.6
700 26.6 18.1 1.2 30.8 22.0 26.8 18.1 1.2 28.3 2.6 22.3
600 21.9 15.1 1.6 27.2 14.1 22.1 15.2 1.5 23.1 4.2 14.7
3.0 0.6 1.4
700 22.4 16.4 1.6 27.8 14.0 22.6 16.5 1.6 23.6 4.3 14.6
600 22.1 15.3 1.5 27.2 15.1 22.4 15.4 1.4 23.4 3.9 15.6
90 4.5 1.3 3.0
700 22.6 16.6 1.5 27.8 14.9 22.8 16.7 1.5 23.9 4.0 15.4
600 22.4 15.3 1.4 27.2 15.7 22.6 15.4 1.4 23.8 3.6 16.0
6.0 2.3 5.3
700 22.8 16.6 1.5 27.8 15.6 23.1 16.7 1.5 24.3 3.7 15.9
600 19.4 13.7 1.8 25.5 10.7 19.7 13.8 1.7 20.1 5.5 11.3
3.0 0.6 1.3
700 19.8 14.9 1.9 26.1 10.7 20.1 15.0 1.8 20.6 5.6 11.2
600 19.6 13.8 1.7 25.4 11.5 19.9 13.9 1.7 20.4 5.1 11.9
110 4.5 1.3 2.9
700 20.0 15.0 1.8 25.9 11.4 20.3 15.1 1.7 20.9 5.2 11.9
600 19.8 13.8 1.7 25.4 12.0 20.1 13.9 1.6 20.9 4.7 12.3
6.0 2.2 5.2
700 20.2 15.0 1.7 26.0 11.9 20.5 15.1 1.7 21.4 4.9 12.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
23
E SERIES SPECIFICATION CATALOG
E024
Heating Capacity Data (700 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 14.6 1.1 10.7 79.2 3.8 12.5 1.1 10.7 76.5 1.8 3.8
3.0 0.7 1.6 70 14.1 1.2 10.1 88.7 3.5 12.1 1.2 10.1 86.0 1.9 3.6
80 13.7 1.2 9.5 98.1 3.2 11.7 1.2 9.5 95.4 2.0 3.3
60 15.2 1.1 11.3 80.2 3.9 13.2 1.1 11.3 77.5 1.9 4.0
30 4.5 1.4 3.2 70 14.8 1.2 10.7 89.6 3.6 12.7 1.2 10.7 86.8 2.0 3.7
80 14.4 1.3 10.1 99.0 3.3 12.2 1.2 10.1 96.2 2.1 3.4
60 15.6 1.2 11.7 80.6 4.0 13.6 1.1 11.7 78.0 1.9 4.0
6.0 2.4 5.6 70 15.1 1.2 11.0 90.0 3.7 13.1 1.2 11.0 87.3 2.0 3.7
80 14.7 1.3 10.3 99.4 3.4 12.5 1.3 10.3 96.6 2.1 3.4
60 21.2 1.4 16.5 88.0 4.5 18.7 1.3 16.5 84.8 2.3 4.6
3.0 0.7 1.6 70 20.5 1.4 15.6 97.1 4.2 18.0 1.4 15.6 93.8 2.4 4.3
80 19.8 1.5 14.7 106.2 3.8 17.2 1.5 14.7 102.8 2.5 3.9
60 22.3 1.4 17.5 89.4 4.7 19.8 1.4 17.6 86.2 2.4 4.8
50 4.5 1.4 3.2 70 21.5 1.5 16.5 98.5 4.3 19.0 1.4 16.6 95.1 2.5 4.4
80 20.8 1.5 15.5 107.5 3.9 18.2 1.5 15.6 104.0 2.6 4.0
60 22.6 1.4 17.8 89.9 4.7 20.2 1.4 17.9 86.7 2.4 4.8
6.0 2.4 5.6 70 21.9 1.5 16.8 98.9 4.3 19.3 1.4 16.9 95.5 2.5 4.4
80 21.1 1.6 15.8 107.9 4.0 18.5 1.5 15.9 104.4 2.6 4.1
60 26.9 1.5 21.8 95.5 5.3 24.2 1.4 22.0 92.0 2.7 5.5
3.0 0.7 1.6 70 25.9 1.6 20.6 104.2 4.9 23.1 1.5 20.8 100.6 2.8 5.1
80 24.9 1.6 19.4 113.0 4.5 22.0 1.6 19.6 109.2 2.9 4.6
60 28.2 1.5 23.0 97.2 5.5 25.4 1.5 23.2 93.5 2.8 5.7
70 4.5 1.4 3.2 70 27.1 1.6 21.7 105.9 5.0 24.2 1.5 21.9 102.0 2.9 5.2
80 26.1 1.7 20.4 114.5 4.6 23.1 1.6 20.6 110.5 3.0 4.8
60 28.7 1.5 23.5 98.0 5.5 25.8 1.5 23.7 94.2 2.9 5.8
6.0 2.4 5.6 70 27.7 1.6 22.2 106.6 5.1 24.7 1.5 22.4 102.6 3.0 5.3
80 26.6 1.7 20.9 115.2 4.6 23.5 1.6 21.1 111.1 3.1 4.8
60 32.4 1.6 27.0 102.9 6.0 29.4 1.5 27.5 98.9 3.2 6.3
3.0 0.6 1.4 70 31.2 1.7 25.5 111.2 5.5 28.0 1.6 25.9 107.1 3.3 5.8
80 29.9 1.7 24.0 119.6 5.0 26.6 1.7 24.3 115.2 3.4 5.3
60 33.9 1.6 28.4 104.8 6.2 30.6 1.5 28.7 100.5 3.3 6.5
90 4.5 1.3 3.0 70 32.6 1.7 26.8 113.1 5.6 29.2 1.6 27.1 108.6 3.4 5.9
80 31.2 1.8 25.2 121.3 5.2 27.7 1.7 25.5 116.7 3.5 5.4
60 34.5 1.6 28.9 105.6 6.2 31.3 1.5 29.4 101.3 3.4 6.6
6.0 2.3 5.3 70 33.1 1.7 27.3 113.8 5.7 29.8 1.6 27.7 109.4 3.5 6.0
80 31.8 1.8 25.7 122.1 5.2 28.3 1.7 26.0 117.4 3.6 5.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
24
E SERIES SPECIFICATION CATALOG
E024
Cooling Capacity Data (700 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 27.0 18.5 1.1 31.1 25.3 27.0 18.5 1.0 31.0 1.6 25.8
3.0 0.7 1.6 80/67 29.4 19.3 1.1 33.1 26.9 29.4 19.3 1.1 33.0 1.7 27.4
85/71 31.7 20.1 1.1 35.1 28.5 31.7 20.1 1.1 35.0 1.8 29.0
75/63 27.3 18.7 1.0 31.2 26.8 27.3 18.7 1.0 31.1 1.6 27.3
50 4.5 1.4 3.2 80/67 29.7 19.5 1.0 33.2 28.5 29.7 19.5 1.0 33.1 1.6 29.1
85/71 32.0 20.3 1.1 35.2 30.2 32.0 20.3 1.0 35.1 1.6 30.8
75/63 27.6 18.7 1.0 31.4 27.8 27.6 18.7 1.0 31.4 1.4 28.1
6.0 2.4 5.6 80/67 30.0 19.5 1.0 33.4 29.7 30.0 19.5 1.0 33.4 1.4 30.0
85/71 32.3 20.3 1.0 35.4 31.4 32.3 20.3 1.0 35.4 1.4 31.7
75/63 24.0 17.2 1.3 28.9 17.9 24.1 17.3 1.3 28.9 2.9 18.3
3.0 0.7 1.6 80/67 26.1 17.9 1.4 30.7 19.0 26.2 18.0 1.3 30.7 3.0 19.5
85/71 28.1 18.6 1.4 32.6 20.1 28.2 18.7 1.4 32.6 3.1 20.7
75/63 24.2 17.4 1.3 28.9 19.0 24.3 17.4 1.2 28.9 2.7 19.6
70 4.5 1.4 3.2 80/67 26.4 18.1 1.3 30.8 20.3 26.5 18.1 1.3 30.8 2.8 20.8
85/71 28.5 18.8 1.3 32.6 21.5 28.6 18.8 1.3 32.6 2.9 22.1
75/63 24.4 17.4 1.2 29.0 19.8 24.6 17.4 1.2 29.2 2.5 20.1
6.0 2.4 5.6 80/67 26.6 18.1 1.3 30.9 21.1 26.8 18.1 1.3 31.0 2.6 21.4
85/71 28.7 18.8 1.3 32.7 22.3 28.9 18.8 1.3 32.9 2.7 22.7
75/63 20.6 15.7 1.6 26.3 12.7 20.7 15.8 1.6 26.3 4.2 13.2
3.0 0.6 1.4 80/67 22.4 16.4 1.7 28.0 13.5 22.6 16.5 1.6 28.0 4.3 14.1
85/71 24.1 17.1 1.7 29.7 14.3 24.4 17.2 1.6 29.7 4.4 14.9
75/63 20.7 15.9 1.5 26.2 13.6 20.9 16.0 1.5 26.3 3.9 14.0
90 4.5 1.3 3.0 80/67 22.6 16.6 1.6 27.9 14.5 22.8 16.7 1.5 28.0 4.0 14.9
85/71 24.4 17.3 1.6 29.5 15.3 24.6 17.4 1.6 29.6 4.1 15.7
75/63 20.9 15.9 1.5 26.3 14.1 21.2 16.0 1.5 26.5 3.6 14.4
6.0 2.3 5.3 80/67 22.8 16.6 1.5 27.9 15.0 23.1 16.7 1.5 28.2 3.7 15.4
85/71 24.6 17.3 1.6 29.6 15.8 24.9 17.4 1.5 29.9 3.8 16.3
75/63 18.2 14.3 1.9 24.7 9.8 18.4 14.4 1.8 24.7 5.4 10.3
3.0 0.6 1.3 80/67 19.8 14.9 1.9 26.2 10.4 20.1 15.0 1.8 26.3 5.6 11.0
85/71 21.3 15.5 1.9 27.8 11.0 21.7 15.6 1.9 27.9 5.8 11.6
75/63 18.4 14.4 1.8 24.5 10.4 18.6 14.5 1.7 24.7 5.0 10.8
110 4.5 1.3 2.9 80/67 20.0 15.0 1.8 26.1 11.1 20.3 15.1 1.8 26.3 5.2 11.5
85/71 21.5 15.6 1.8 27.7 11.7 21.9 15.7 1.8 27.8 5.4 12.2
75/63 18.5 14.4 1.7 24.6 10.8 18.8 14.5 1.7 24.8 4.8 11.1
6.0 2.2 5.2 80/67 20.2 15.0 1.8 26.1 11.5 20.5 15.1 1.7 26.4 4.9 11.8
85/71 21.8 15.6 1.8 27.7 12.2 22.1 15.7 1.8 27.9 5.0 12.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
25
E SERIES SPECIFICATION CATALOG
E030
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
700 17.9 1.6 12.6 93.7 3.3 15.3 1.5 12.7 90.2 2.6 3.4
4.0 1.2 2.8
900 18.3 1.6 12.8 88.8 3.3 15.9 1.6 12.8 86.4 2.3 3.4
700 18.5 1.6 13.1 94.4 3.4 15.7 1.5 13.2 90.8 2.7 3.5
30 5.5 2.1 4.9
900 18.8 1.6 13.3 89.4 3.4 16.4 1.6 13.3 86.9 2.3 3.5
700 18.9 1.6 13.5 95.0 3.5 16.1 1.6 13.6 91.3 2.8 3.6
7.0 3.2 7.5
900 19.3 1.6 13.8 89.9 3.5 16.8 1.6 13.8 87.3 2.4 3.5
700 24.9 1.8 18.8 102.9 4.1 21.1 1.7 19.0 97.9 3.7 4.3
4.0 1.2 2.7
900 25.5 1.8 19.4 96.2 4.2 22.1 1.7 19.4 92.8 3.2 4.3
700 25.7 1.8 19.6 104.0 4.2 21.8 1.7 19.8 98.8 3.9 4.4
50 5.5 2.0 4.7
900 26.3 1.8 20.2 97.1 4.3 22.9 1.8 20.3 93.5 3.4 4.4
700 26.3 1.8 20.1 104.7 4.3 22.2 1.7 20.3 99.4 3.9 4.4
7.0 3.1 7.2
900 26.9 1.8 20.7 97.7 4.3 23.4 1.8 20.8 94.1 3.4 4.5
700 31.0 2.0 24.3 111.0 4.6 26.1 1.9 24.6 104.5 4.8 4.9
4.0 1.1 2.5
900 31.9 1.9 25.3 102.8 4.8 27.7 1.9 25.5 98.5 4.2 5.0
700 32.1 2.0 25.3 112.4 4.7 27.0 1.9 25.6 105.7 5.0 5.0
70 5.5 2.0 4.5
900 33.0 2.0 26.3 104.0 4.9 28.6 1.9 26.6 99.5 4.4 5.1
700 32.6 2.0 25.8 113.2 4.8 27.4 1.9 26.1 106.2 5.1 5.1
7.0 3.0 6.9
900 33.7 2.0 26.9 104.6 5.0 29.2 1.9 27.2 100.0 4.5 5.2
700 36.5 2.0 29.6 118.3 5.3 30.4 1.9 29.9 110.3 5.9 5.6
4.0 1.1 2.5
900 37.8 2.0 31.0 108.9 5.6 32.7 1.9 31.4 103.7 5.2 5.8
700 37.8 2.1 30.8 120.1 5.3 31.5 1.9 31.1 111.7 6.1 5.7
90 5.5 1.9 4.4
900 39.3 2.0 32.3 110.4 5.7 34.0 1.9 32.8 105.0 5.4 6.0
700 38.4 2.1 31.2 120.7 5.4 31.9 1.9 31.5 112.2 6.3 5.8
7.0 2.9 6.7
900 39.8 2.1 32.8 111.0 5.7 34.4 2.0 33.3 105.4 5.6 6.0
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
26
E SERIES SPECIFICATION CATALOG
E030
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
700 34.1 20.6 1.2 38.3 27.7 34.1 20.6 1.2 36.4 1.9 28.1
4.0 1.2 2.7
900 35.2 23.1 1.3 39.7 26.9 35.2 23.1 1.3 37.6 2.0 27.3
700 34.2 20.7 1.2 38.3 28.9 34.2 20.7 1.2 36.5 1.8 29.2
50 5.5 2.0 4.7
900 35.3 23.3 1.3 39.6 28.0 35.3 23.3 1.3 37.7 1.9 28.3
700 34.6 20.7 1.2 38.6 29.8 34.6 20.7 1.2 36.9 1.6 30.0
7.0 3.1 7.2
900 35.7 23.3 1.2 39.9 28.9 35.7 23.3 1.2 38.2 1.7 29.0
700 30.8 19.4 1.5 35.8 21.1 31.0 19.5 1.4 32.3 3.6 21.7
4.0 1.1 2.5
900 31.8 21.7 1.5 37.0 20.7 31.9 21.8 1.5 33.4 3.7 21.2
700 30.9 19.5 1.4 35.7 22.0 31.1 19.5 1.4 32.5 3.3 22.5
70 5.5 2.0 4.5
900 31.9 21.8 1.5 36.9 21.5 32.1 21.9 1.5 33.6 3.5 22.0
700 31.2 19.5 1.4 36.0 22.7 31.4 19.6 1.4 33.0 3.1 23.0
7.0 3.0 6.9
900 32.2 21.9 1.5 37.2 22.2 32.4 21.9 1.4 34.1 3.2 22.5
700 26.1 17.9 1.9 32.7 13.6 26.4 17.9 1.9 27.5 5.2 14.2
4.0 1.1 2.5
900 26.9 19.9 2.0 33.8 13.5 27.2 20.0 1.9 28.4 5.4 14.0
700 26.3 17.9 1.8 32.6 14.2 26.5 18.0 1.8 27.8 4.9 14.7
90 5.5 1.9 4.4
900 27.1 20.0 1.9 33.6 14.1 27.4 20.1 1.9 28.7 5.1 14.5
700 26.5 17.9 1.8 32.7 14.7 26.8 18.0 1.8 28.4 4.6 15.0
7.0 2.9 6.7
900 27.4 20.0 1.9 33.8 14.5 27.6 20.1 1.9 29.3 4.7 14.8
700 21.8 16.3 2.2 29.4 9.8 22.1 16.4 2.2 22.6 6.9 10.3
4.0 1.1 2.5
900 22.5 18.2 2.3 30.3 9.8 22.8 18.3 2.2 23.3 7.1 10.3
700 21.9 16.3 2.2 29.3 10.2 22.3 16.4 2.1 23.0 6.5 10.6
110 5.5 1.8 4.3
900 22.6 18.2 2.2 30.2 10.2 23.0 18.3 2.2 23.7 6.7 10.6
700 22.2 16.4 2.1 29.4 10.5 22.5 16.5 2.1 23.6 6.0 10.8
7.0 2.8 6.5
900 22.8 18.3 2.2 30.3 10.5 23.2 18.4 2.2 24.3 6.2 10.8
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
27
E SERIES SPECIFICATION CATALOG
E030
Heating Capacity Data (900 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 19.0 1.6 13.6 79.5 3.6 16.5 1.5 13.6 77.0 2.2 3.6
4.0 1.2 2.8 70 18.4 1.6 12.8 88.9 3.3 16.0 1.6 12.8 86.5 2.3 3.3
80 17.9 1.7 12.0 98.4 3.0 15.5 1.7 12.0 95.9 2.4 3.1
60 19.4 1.6 14.1 80.0 3.6 17.1 1.5 14.1 77.6 2.2 3.7
30 5.5 2.1 4.9 70 18.9 1.6 13.3 89.5 3.4 16.5 1.6 13.3 87.0 2.3 3.4
80 18.4 1.7 12.5 98.9 3.1 15.9 1.7 12.5 96.4 2.4 3.2
60 20.0 1.6 14.6 80.6 3.7 17.6 1.5 14.6 78.1 2.3 3.8
7.0 3.2 7.5 70 19.5 1.7 13.8 90.0 3.4 16.9 1.6 13.8 87.4 2.4 3.5
80 18.9 1.7 13.0 99.5 3.2 16.3 1.7 13.0 96.8 2.5 3.2
60 26.5 1.7 20.6 87.2 4.5 23.2 1.7 20.6 83.9 3.1 4.6
4.0 1.2 2.8 70 25.6 1.8 19.4 96.4 4.1 22.3 1.8 19.4 92.9 3.2 4.2
80 24.8 1.9 18.2 105.5 3.8 21.3 1.9 18.2 101.9 3.3 3.9
60 27.4 1.7 21.4 88.2 4.6 24.0 1.7 21.5 84.7 3.3 4.7
50 5.5 2.1 4.9 70 26.5 1.8 20.2 97.2 4.2 23.0 1.8 20.3 93.7 3.4 4.3
80 25.6 1.9 19.0 106.3 3.9 22.0 1.9 19.1 102.6 3.5 4.0
60 28.0 1.8 21.9 88.8 4.7 24.6 1.7 22.0 85.3 3.3 4.8
7.0 3.2 7.5 70 27.0 1.9 20.7 97.8 4.3 23.5 1.8 20.8 94.2 3.4 4.4
80 26.1 1.9 19.5 106.9 3.9 22.5 1.9 19.6 103.1 3.5 4.0
60 33.2 1.9 26.8 94.2 5.2 29.1 1.8 27.0 90.0 4.1 5.4
4.0 1.2 2.8 70 32.0 2.0 25.3 103.0 4.8 27.8 1.9 25.5 98.6 4.2 4.9
80 30.9 2.1 23.8 111.7 4.4 26.5 2.0 24.0 107.2 4.3 4.5
60 34.3 1.9 27.9 95.3 5.3 30.2 1.8 28.2 91.0 4.3 5.5
70 5.5 2.1 4.9 70 33.1 2.0 26.3 104.1 4.9 28.8 1.9 26.6 99.6 4.4 5.1
80 31.9 2.1 24.7 112.8 4.5 27.4 2.0 25.0 108.2 4.5 4.6
60 35.0 1.9 28.5 96.1 5.4 30.7 1.8 28.8 91.6 4.4 5.6
7.0 3.2 7.5 70 33.8 2.0 26.9 104.8 4.9 29.3 1.9 27.2 100.1 4.5 5.1
80 32.5 2.1 25.3 113.4 4.5 27.9 2.0 25.6 108.7 4.6 4.7
60 39.5 1.9 32.9 100.6 6.0 34.5 1.8 33.3 95.5 5.0 6.3
4.0 1.2 2.8 70 37.9 2.0 31.0 109.0 5.5 32.8 1.9 31.4 103.8 5.2 5.8
80 36.4 2.1 29.1 117.5 5.0 31.1 2.0 29.5 112.0 5.4 5.3
60 40.9 2.0 34.2 102.1 6.1 35.9 1.9 34.8 96.9 5.2 6.5
90 5.5 2.1 4.9 70 39.3 2.1 32.3 110.5 5.6 34.1 2.0 32.8 105.1 5.4 5.9
80 37.8 2.2 30.4 118.9 5.1 32.3 2.1 30.8 113.2 5.6 5.4
60 41.5 2.0 34.8 102.7 6.1 36.3 1.9 35.3 97.3 5.4 6.5
7.0 3.2 7.5 70 39.9 2.1 32.8 111.1 5.6 34.5 2.0 33.3 105.5 5.6 5.9
80 38.3 2.2 30.8 119.4 5.1 32.6 2.1 31.3 113.6 5.8 5.4
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
28
E SERIES SPECIFICATION CATALOG
E030
Cooling Capacity Data (900 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 32.4 22.2 1.32 37.4 24.5 32.4 22.2 1.30 37.3 1.9 24.9
4.0 1.2 2.7 80/67 35.2 23.1 1.35 39.8 26.1 35.2 23.1 1.33 39.7 2.0 26.5
85/71 38.0 24.0 1.37 42.1 27.7 38.0 24.0 1.35 42.1 2.1 28.1
75/63 32.4 22.4 1.27 37.3 25.6 32.4 22.4 1.26 37.3 1.8 25.8
50 5.5 2.0 4.7 80/67 35.3 23.3 1.30 39.7 27.2 35.3 23.3 1.29 39.7 1.9 27.4
85/71 38.1 24.2 1.32 42.1 28.8 38.1 24.2 1.31 42.0 2.0 29.1
75/63 32.8 22.4 1.25 37.6 26.3 32.8 22.4 1.24 37.6 1.6 26.5
7.0 3.1 7.2 80/67 35.7 23.3 1.28 40.0 28.0 35.7 23.3 1.27 40.0 1.7 28.2
85/71 38.5 24.2 1.30 42.4 29.6 38.5 24.2 1.29 42.4 1.8 29.9
75/63 29.2 20.8 1.54 34.9 18.9 29.3 20.9 1.50 34.9 3.6 19.5
4.0 1.1 2.5 80/67 31.8 21.7 1.58 37.1 20.2 31.9 21.8 1.54 37.1 3.7 20.8
85/71 34.3 22.6 1.61 39.4 21.4 34.4 22.7 1.57 39.3 3.8 22.0
75/63 29.3 20.9 1.48 34.8 19.7 29.5 21.0 1.47 34.9 3.4 20.1
70 5.5 2.0 4.5 80/67 31.9 21.8 1.52 37.0 21.0 32.1 21.9 1.50 37.2 3.5 21.4
85/71 34.4 22.7 1.55 39.3 22.3 34.6 22.8 1.52 39.4 3.6 22.7
75/63 29.6 21.0 1.46 35.0 20.3 29.8 21.0 1.45 35.2 3.1 20.6
7.0 3.0 6.9 80/67 32.2 21.9 1.49 37.2 21.7 32.4 21.9 1.48 37.4 3.2 21.9
85/71 34.7 22.8 1.51 39.5 22.9 35.0 22.8 1.50 39.6 3.3 23.2
75/63 24.7 19.1 1.99 31.8 12.4 25.0 19.2 1.94 31.9 5.2 12.9
4.0 1.1 2.5 80/67 26.9 19.9 2.04 33.8 13.2 27.2 20.0 1.98 33.9 5.4 13.8
85/71 29.0 20.7 2.08 35.8 14.0 29.3 20.8 2.01 35.9 5.6 14.6
75/63 24.9 19.2 1.92 31.7 13.0 25.2 19.3 1.88 31.9 4.9 13.4
90 5.5 1.9 4.4 80/67 27.1 20.0 1.96 33.7 13.8 27.4 20.1 1.92 33.9 5.1 14.3
85/71 29.2 20.8 1.99 35.8 14.7 29.6 20.9 1.95 35.9 5.3 15.1
75/63 25.2 19.2 1.88 31.9 13.4 25.4 19.3 1.87 32.0 4.6 13.6
7.0 2.9 6.7 80/67 27.4 20.0 1.92 33.9 14.3 27.6 20.1 1.91 34.1 4.7 14.5
85/71 29.6 20.8 1.95 35.9 15.1 29.8 20.9 1.94 36.1 4.8 15.3
75/63 20.7 17.5 2.29 28.6 9.0 20.9 17.6 2.21 28.6 6.9 9.5
4.0 1.1 2.5 80/67 22.5 18.2 2.34 30.4 9.6 22.8 18.3 2.26 30.5 7.1 10.1
85/71 24.3 18.9 2.38 32.3 10.2 24.6 19.0 2.30 32.3 7.3 10.7
75/63 20.8 17.5 2.21 28.4 9.4 21.1 17.6 2.15 28.6 6.5 9.8
110 5.5 1.8 4.3 80/67 22.6 18.2 2.26 30.3 10.0 23.0 18.3 2.20 30.5 6.7 10.5
85/71 24.4 18.9 2.30 32.1 10.6 24.8 19.0 2.24 32.3 6.9 11.1
75/63 20.9 17.6 2.16 28.5 9.7 21.3 17.7 2.14 28.8 6.0 10.0
7.0 2.8 6.5 80/67 22.8 18.3 2.21 30.3 10.3 23.2 18.4 2.19 30.6 6.2 10.6
85/71 24.6 19.0 2.25 32.1 10.9 25.0 19.1 2.23 32.5 6.4 11.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
29
E SERIES SPECIFICATION CATALOG
E035
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
900 22.4 1.97 15.7 93.1 3.34 18.9 1.91 15.9 89.5 3.5 3.43
5.0 2.2 5.0
1100 22.9 2.01 16.0 89.2 3.33 19.6 1.98 16.0 86.5 3.1 3.37
900 23.1 1.97 16.4 93.8 3.43 19.5 1.91 16.5 90.1 3.5 3.53
30 7.0 3.6 8.4
1100 23.6 2.01 16.7 89.8 3.43 20.3 1.97 16.7 87.1 3.2 3.48
900 23.7 1.99 16.9 94.3 3.48 20.0 1.93 17.0 90.6 3.6 3.58
9.0 5.7 13.2
1100 24.1 2.03 17.2 90.3 3.48 20.8 1.99 17.2 87.5 3.2 3.53
900 30.6 2.25 23.0 101.5 3.99 26.1 2.15 23.2 96.9 4.4 4.15
5.0 2.1 4.7
1100 31.3 2.27 23.6 96.4 4.05 27.4 2.20 23.7 93.1 3.8 4.15
900 31.6 2.26 23.9 102.5 4.09 27.0 2.16 24.1 97.8 4.5 4.27
50 7.0 3.4 7.9
1100 32.4 2.28 24.6 97.3 4.17 28.3 2.21 24.7 93.9 3.9 4.28
900 32.3 2.29 24.5 103.2 4.14 27.6 2.19 24.7 98.4 4.6 4.32
9.0 5.4 12.4
1100 33.1 2.30 25.3 97.9 4.22 29.0 2.23 25.4 94.4 4.0 4.33
900 38.1 2.47 29.6 109.2 4.51 32.6 2.34 29.9 103.5 5.3 4.75
5.0 1.9 4.3
1100 39.2 2.46 30.8 103.0 4.67 34.5 2.37 31.0 99.1 4.6 4.84
900 39.4 2.51 30.8 110.5 4.60 33.7 2.36 31.1 104.7 5.5 4.87
70 7.0 3.2 7.4
1100 40.6 2.48 32.1 104.1 4.78 35.8 2.39 32.4 100.2 4.7 4.97
900 40.1 2.54 31.4 111.2 4.63 34.3 2.38 31.7 105.3 5.6 4.90
9.0 5.0 11.6
1100 41.3 2.51 32.7 104.8 4.82 36.5 2.41 33.1 100.7 4.8 5.02
900 44.9 2.63 36.0 116.2 5.02 38.4 2.44 36.3 109.5 6.3 5.36
5.0 1.8 4.3
1100 46.5 2.57 37.8 109.2 5.30 41.3 2.45 38.3 104.8 5.3 5.57
900 46.6 2.67 37.4 117.9 5.10 39.8 2.48 37.8 110.9 6.5 5.47
90 7.0 3.1 7.1
1100 48.3 2.61 39.4 110.6 5.41 42.9 2.49 39.9 106.1 5.5 5.71
900 47.2 2.71 38.0 118.5 5.11 40.3 2.50 38.3 111.4 6.6 5.49
9.0 4.8 11.2
1100 49.0 2.64 40.0 111.2 5.44 43.5 2.51 40.6 106.6 5.6 5.74
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
30
E SERIES SPECIFICATION CATALOG
E035
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
900 39.7 23.8 1.58 45.1 25.2 39.7 23.8 1.55 42.5 2.5 25.5
5.0 2.1 4.7
1100 40.9 26.8 1.68 46.7 24.4 40.9 26.8 1.65 44.0 2.6 24.7
900 39.8 24.0 1.52 45.0 26.2 39.8 24.0 1.50 42.6 2.4 26.5
50 7.0 3.4 7.9
1100 41.0 26.9 1.62 46.6 25.4 41.0 26.9 1.60 44.1 2.5 25.7
900 40.2 24.0 1.49 45.3 27.0 40.2 24.0 1.48 43.0 2.2 27.2
9.0 5.4 12.4
1100 41.5 26.9 1.58 46.9 26.2 41.5 26.9 1.57 44.5 2.3 26.3
900 36.1 22.8 1.95 42.7 18.5 36.3 22.9 1.91 38.6 4.2 19.0
5.0 1.9 4.3
1100 37.2 25.6 2.06 44.2 18.1 37.4 25.6 2.01 39.9 4.3 18.6
900 36.2 22.9 1.88 42.6 19.3 36.4 22.9 1.85 38.9 3.9 19.7
70 7.0 3.2 7.4
1100 37.3 25.6 1.98 44.1 18.9 37.5 25.7 1.95 40.2 4.0 19.3
900 36.6 22.9 1.84 42.9 19.9 36.8 23.0 1.83 39.4 3.6 20.1
9.0 5.0 11.6
1100 37.7 25.7 1.94 44.3 19.4 37.9 25.7 1.92 40.8 3.7 19.7
900 31.7 21.3 2.39 39.9 13.3 32.0 21.4 2.32 34.1 5.8 13.8
5.0 1.8 4.3
1100 32.7 23.8 2.49 41.2 13.1 33.0 23.9 2.41 35.3 6.0 13.7
900 31.9 21.3 2.30 39.7 13.9 32.2 21.4 2.25 34.5 5.4 14.3
90 7.0 3.1 7.1
1100 32.9 23.8 2.39 41.0 13.7 33.2 23.9 2.35 35.7 5.6 14.2
900 32.2 21.4 2.25 39.9 14.3 32.5 21.5 2.23 35.2 4.9 14.6
9.0 4.8 11.2
1100 33.2 23.9 2.35 41.2 14.1 33.5 24.0 2.32 36.4 5.1 14.4
900 26.7 19.4 2.80 36.3 9.5 27.1 19.5 2.70 28.8 7.5 10.0
5.0 1.8 4.1
1100 27.5 21.6 2.89 37.4 9.5 27.9 21.7 2.78 29.7 7.7 10.0
900 26.9 19.4 2.70 36.1 10.0 27.3 19.5 2.63 29.3 6.9 10.4
110 7.0 3.0 6.9
1100 27.7 21.6 2.78 37.2 10.0 28.1 21.8 2.71 30.2 7.1 10.4
900 27.1 19.5 2.64 36.1 10.3 27.5 19.6 2.61 30.1 6.3 10.5
9.0 4.7 10.8
1100 28.0 21.7 2.72 37.3 10.3 28.4 21.9 2.69 31.1 6.5 10.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
31
E SERIES SPECIFICATION CATALOG
E035
Heating Capacity Data (1100 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 23.6 1.9 17.0 79.9 3.6 20.3 1.9 17.0 77.1 3.0 3.6
5.0 2.2 5.0 70 22.9 2.0 16.0 89.3 3.3 19.7 2.0 16.0 86.6 3.1 3.3
80 22.2 2.1 15.0 98.7 3.1 19.0 2.1 15.0 96.0 3.2 3.1
60 24.3 1.9 17.7 80.4 3.7 21.1 1.9 17.7 77.7 3.1 3.7
30 7.0 3.6 8.4 70 23.6 2.0 16.7 89.9 3.4 20.3 2.0 16.7 87.1 3.2 3.5
80 23.0 2.1 15.7 99.3 3.2 19.5 2.1 15.7 96.4 3.3 3.2
60 24.9 1.9 18.2 80.9 3.7 21.6 1.9 18.2 78.2 3.1 3.8
9.0 5.7 13.2 70 24.2 2.1 17.2 90.4 3.5 20.9 2.0 17.2 87.6 3.2 3.5
80 23.5 2.2 16.2 99.8 3.2 20.1 2.1 16.2 96.9 3.3 3.2
60 32.4 2.2 25.0 87.3 4.4 28.6 2.1 25.1 84.1 3.7 4.5
5.0 2.1 4.7 70 31.4 2.3 23.6 96.4 4.0 27.5 2.2 23.7 93.1 3.8 4.1
80 30.4 2.4 22.2 105.6 3.7 26.3 2.3 22.3 102.2 3.9 3.8
60 33.5 2.2 26.1 88.2 4.5 29.6 2.1 26.2 84.9 3.8 4.6
50 7.0 3.4 7.9 70 32.5 2.3 24.6 97.3 4.1 28.4 2.2 24.7 93.9 3.9 4.2
80 31.4 2.4 23.1 106.4 3.8 27.2 2.3 23.2 102.9 4.0 3.9
60 34.3 2.2 26.8 88.9 4.6 30.3 2.1 26.9 85.5 3.9 4.7
9.0 5.4 12.4 70 33.2 2.3 25.3 98.0 4.2 29.1 2.3 25.4 94.5 4.0 4.3
80 32.1 2.4 23.8 107.0 3.9 27.8 2.4 23.9 103.4 4.1 4.0
60 40.7 2.4 32.6 94.3 5.1 36.1 2.3 32.9 90.4 4.5 5.2
5.0 1.9 4.3 70 39.3 2.5 30.8 103.1 4.6 34.6 2.4 31.0 99.1 4.6 4.8
80 37.8 2.6 29.0 111.9 4.3 33.0 2.5 29.1 107.8 4.7 4.4
60 42.1 2.4 34.0 95.5 5.2 37.6 2.3 34.3 91.7 4.6 5.4
70 7.0 3.2 7.4 70 40.6 2.5 32.1 104.2 4.8 35.9 2.4 32.4 100.2 4.7 4.9
80 39.1 2.6 30.2 112.9 4.4 34.3 2.5 30.5 108.8 4.8 4.5
60 42.9 2.4 34.7 96.1 5.2 38.3 2.3 35.1 92.2 4.7 5.5
9.0 5.0 11.6 70 41.3 2.5 32.7 104.8 4.8 36.6 2.4 33.1 100.8 4.8 5.0
80 39.8 2.7 30.7 113.5 4.4 34.9 2.6 31.1 109.4 4.9 4.6
60 48.5 2.5 40.1 100.8 5.8 43.5 2.3 40.6 96.6 5.1 6.1
5.0 1.8 4.3 70 46.6 2.6 37.8 109.3 5.3 41.4 2.5 38.3 104.9 5.3 5.5
80 44.8 2.7 35.5 117.7 4.8 39.4 2.6 36.0 113.2 5.5 5.1
60 50.3 2.5 41.8 102.3 5.9 45.1 2.4 42.3 98.0 5.3 6.2
90 7.0 3.1 7.1 70 48.4 2.6 39.4 110.7 5.4 43.0 2.5 39.9 106.2 5.5 5.7
80 46.5 2.8 37.0 119.1 4.9 40.8 2.6 37.5 114.4 5.7 5.2
60 51.0 2.5 42.4 103.0 5.9 45.8 2.4 43.0 98.6 5.4 6.2
9.0 4.8 11.2 70 49.1 2.7 40.0 111.3 5.4 43.6 2.5 40.6 106.7 5.6 5.7
80 47.1 2.8 37.6 119.7 4.9 41.5 2.7 38.2 114.9 5.8 5.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
32
E SERIES SPECIFICATION CATALOG
E035
Cooling Capacity Data (1100 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 37.6 25.7 1.67 43.9 22.6 37.6 25.7 1.64 43.8 2.5 23.0
5.0 2.1 4.7 80/67 40.9 26.8 1.70 46.7 24.0 40.9 26.8 1.67 46.6 2.6 24.5
85/71 44.2 27.9 1.73 49.5 25.5 44.2 27.9 1.70 49.4 2.7 25.9
75/63 37.7 25.8 1.61 43.8 23.5 37.7 25.8 1.59 43.7 2.4 23.7
50 7.0 3.4 7.9 80/67 41.0 26.9 1.64 46.6 25.0 41.0 26.9 1.62 46.5 2.5 25.3
85/71 44.3 28.0 1.67 49.4 26.5 44.3 28.0 1.65 49.3 2.6 26.8
75/63 38.2 25.8 1.57 44.1 24.3 38.2 25.8 1.56 44.1 2.2 24.5
9.0 5.4 12.4 80/67 41.5 26.9 1.60 46.9 25.9 41.5 26.9 1.59 46.9 2.3 26.1
85/71 44.8 28.0 1.63 49.8 27.5 44.8 28.0 1.62 49.7 2.4 27.6
75/63 34.2 24.6 2.04 41.6 16.8 34.4 24.6 1.99 41.6 4.2 17.3
5.0 1.9 4.3 80/67 37.2 25.6 2.08 44.3 17.9 37.4 25.6 2.03 44.3 4.3 18.4
85/71 40.2 26.6 2.12 46.9 18.9 40.4 26.6 2.07 47.0 4.4 19.5
75/63 34.3 24.6 1.96 41.5 17.5 34.5 24.7 1.93 41.6 3.9 17.9
70 7.0 3.2 7.4 80/67 37.3 25.6 2.00 44.1 18.6 37.5 25.7 1.97 44.2 4.0 19.0
85/71 40.3 26.6 2.04 46.8 19.7 40.5 26.7 2.01 46.9 4.1 20.1
75/63 34.7 24.7 1.92 41.7 18.0 34.9 24.7 1.90 41.8 3.6 18.3
9.0 5.0 11.6 80/67 37.7 25.7 1.96 44.4 19.2 37.9 25.7 1.94 44.5 3.7 19.5
85/71 40.7 26.7 2.00 47.0 20.4 40.9 26.7 1.98 47.2 3.8 20.7
75/63 30.1 22.8 2.46 38.8 12.2 30.3 22.9 2.38 38.8 5.8 12.7
5.0 1.8 4.3 80/67 32.7 23.8 2.51 41.2 13.0 33.0 23.9 2.43 41.3 6.0 13.6
85/71 35.3 24.8 2.56 43.7 13.8 35.6 24.9 2.48 43.7 6.2 14.4
75/63 30.3 22.8 2.36 38.6 12.8 30.5 22.9 2.32 38.8 5.4 13.1
90 7.0 3.1 7.1 80/67 32.9 23.8 2.41 41.1 13.6 33.2 23.9 2.37 41.3 5.6 14.0
85/71 35.5 24.8 2.46 43.6 14.4 35.8 24.9 2.42 43.7 5.8 14.8
75/63 30.5 22.9 2.32 38.8 13.1 30.8 23.0 2.29 39.0 4.9 13.4
9.0 4.8 11.2 80/67 33.2 23.9 2.37 41.3 14.0 33.5 24.0 2.34 41.5 5.1 14.3
85/71 35.8 24.9 2.42 43.7 14.8 36.2 25.0 2.39 44.0 5.3 15.2
75/63 25.3 20.7 2.85 35.2 8.9 25.7 20.8 2.74 35.2 7.5 9.3
5.0 1.8 4.1 80/67 27.5 21.6 2.91 37.4 9.4 27.9 21.7 2.80 37.4 7.7 10.0
85/71 29.7 22.5 2.97 39.7 10.0 30.1 22.6 2.86 39.7 7.9 10.5
75/63 25.5 20.7 2.74 35.0 9.3 25.8 20.9 2.68 35.2 6.9 9.7
110 7.0 3.0 6.9 80/67 27.7 21.6 2.80 37.2 9.9 28.1 21.8 2.73 37.4 7.1 10.3
85/71 29.9 22.5 2.86 39.5 10.5 30.3 22.7 2.78 39.6 7.3 10.9
75/63 25.7 20.8 2.69 35.1 9.6 26.1 21.0 2.66 35.4 6.3 9.8
9.0 4.7 10.8 80/67 28.0 21.7 2.74 37.3 10.2 28.4 21.9 2.71 37.6 6.5 10.5
85/71 30.2 22.6 2.79 39.6 10.8 30.7 22.8 2.76 39.9 6.7 11.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
33
E SERIES SPECIFICATION CATALOG
E036
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
800 22.9 1.91 16.4 96.5 3.52 20.0 1.88 17.1 93.2 3.4 3.67
5.0 1.6 3.6 1000 23.6 1.92 17.0 91.8 3.59 20.7 1.89 17.5 89.1 3.3 3.71
1200 24.3 1.99 17.5 88.8 3.58 21.3 1.95 17.7 86.5 3.1 3.66
800 23.5 1.94 16.9 97.2 3.55 20.5 1.90 17.6 93.8 3.5 3.70
30 7.0 2.9 6.8 1000 24.2 1.95 17.5 92.4 3.64 21.2 1.91 18.0 89.6 3.3 3.76
1200 24.9 2.01 18.1 89.2 3.64 21.8 1.97 18.3 86.9 3.2 3.72
800 24.0 1.97 17.2 97.7 3.56 20.9 1.93 17.9 94.2 3.6 3.72
9.0 4.7 10.8 1000 24.6 1.97 17.9 92.8 3.66 21.5 1.93 18.3 89.9 3.4 3.78
1200 25.4 2.03 18.4 89.6 3.66 22.2 1.99 18.6 87.1 3.2 3.74
800 29.3 2.28 21.5 103.9 3.77 25.3 2.19 22.3 99.3 4.4 3.98
5.0 1.5 3.5 1000 30.1 2.18 22.7 97.9 4.05 26.1 2.11 23.1 94.2 4.1 4.21
1200 31.0 2.21 23.5 93.9 4.11 27.0 2.15 23.5 90.8 3.9 4.20
800 30.4 2.34 22.4 105.2 3.80 26.3 2.25 23.2 100.4 4.6 4.02
50 7.0 2.8 6.5 1000 31.2 2.23 23.6 98.9 4.10 27.1 2.15 24.0 95.1 4.3 4.27
1200 32.2 2.26 24.5 94.8 4.17 28.0 2.19 24.5 91.6 4.0 4.27
800 31.0 2.38 22.9 105.9 3.82 26.9 2.28 23.7 101.1 4.6 4.05
9.0 4.5 10.4 1000 31.9 2.25 24.2 99.5 4.15 27.7 2.17 24.6 95.7 4.3 4.32
1200 32.9 2.28 25.1 95.4 4.22 28.6 2.21 25.1 92.1 4.0 4.32
800 39.5 2.64 30.5 115.7 4.38 34.6 2.50 31.4 110.1 5.3 4.69
5.0 1.4 3.3 1000 40.8 2.42 32.6 107.8 4.94 35.9 2.31 33.0 103.3 4.9 5.18
1200 42.2 2.42 33.9 102.5 5.11 37.1 2.33 33.7 98.6 4.6 5.23
800 41.4 2.75 32.0 117.9 4.41 36.3 2.59 33.0 112.1 5.5 4.73
70 7.0 2.6 6.1 1000 42.9 2.50 34.3 109.7 5.02 37.7 2.38 34.7 104.9 5.1 5.27
1200 44.3 2.50 35.8 104.2 5.20 38.9 2.40 35.4 100.0 4.7 5.33
800 42.5 2.80 32.9 119.2 4.45 37.3 2.63 33.9 113.2 5.6 4.78
9.0 4.2 9.7 1000 44.0 2.53 35.4 110.7 5.09 38.7 2.41 35.7 105.9 5.2 5.35
1200 45.5 2.52 36.9 105.1 5.28 40.0 2.42 36.5 100.8 4.8 5.42
800 45.9 3.04 35.6 123.1 4.43 39.8 2.81 36.5 116.0 6.3 4.81
5.0 1.4 3.1 1000 47.7 2.66 38.7 114.2 5.26 41.6 2.50 38.9 108.5 5.8 5.55
1200 49.4 2.62 40.5 108.1 5.53 43.0 2.49 39.8 103.2 5.3 5.68
800 48.7 3.20 37.7 126.3 4.46 42.3 2.95 38.7 118.9 6.5 4.84
90 7.0 2.5 5.8 1000 50.7 2.78 41.2 116.9 5.34 44.2 2.61 41.3 110.9 6.0 5.64
1200 52.5 2.73 43.2 110.5 5.64 45.7 2.59 42.3 105.3 5.5 5.78
800 50.1 3.25 39.0 128.0 4.51 43.6 2.99 40.0 120.4 6.6 4.91
9.0 4.0 9.3 1000 52.3 2.82 42.6 118.4 5.44 45.6 2.63 42.7 112.2 6.1 5.76
1200 54.1 2.75 44.7 111.8 5.76 47.1 2.62 43.8 106.4 5.6 5.91
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
34
E SERIES SPECIFICATION CATALOG
E036
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
800 38.8 22.0 1.64 44.4 23.6 40.0 21.7 1.63 43.2 2.3 24.6
5.0 1.5 3.5 1000 41.9 25.0 1.73 47.8 24.2 43.2 24.8 1.72 46.6 2.5 25.2
1200 44.1 27.8 1.82 50.3 24.2 45.4 27.5 1.81 49.0 2.6 25.2
800 39.6 22.2 1.54 44.9 25.7 40.8 22.2 1.53 43.9 2.2 26.8
50 7.0 2.8 6.5 1000 42.8 25.3 1.63 48.3 26.3 44.1 25.3 1.61 47.2 2.3 27.4
1200 45.0 28.1 1.71 50.9 26.3 46.4 28.1 1.70 49.7 2.5 27.4
800 40.0 23.7 1.50 45.2 26.6 41.2 23.9 1.49 44.3 2.0 27.7
9.0 4.5 10.4 1000 43.2 27.0 1.59 48.6 27.2 44.5 27.3 1.57 47.7 2.2 28.3
1200 45.5 30.0 1.67 51.2 27.2 46.8 30.3 1.66 50.2 2.3 28.3
800 36.4 21.9 2.02 43.4 18.0 37.4 21.8 2.00 40.3 3.9 18.6
5.0 1.4 3.3 1000 38.6 24.7 2.10 45.8 18.3 39.5 24.6 2.08 42.5 4.1 19.0
1200 40.3 27.5 2.18 47.7 18.5 41.3 27.3 2.16 44.4 4.3 19.1
800 37.4 22.1 1.93 44.0 19.3 38.3 22.2 1.91 41.2 3.6 20.0
70 7.0 2.6 6.1 1000 39.6 25.0 2.01 46.4 19.7 40.6 25.1 1.99 43.5 3.8 20.4
1200 41.3 27.7 2.08 48.4 19.8 42.4 27.9 2.06 45.4 4.0 20.5
800 37.8 23.0 1.89 44.2 20.0 38.7 23.3 1.87 41.7 3.4 20.7
9.0 4.2 9.7 1000 40.0 26.0 1.96 46.7 20.4 41.0 26.3 1.94 44.1 3.5 21.1
1200 41.8 28.8 2.04 48.7 20.5 42.8 29.2 2.02 46.0 3.7 21.2
800 32.6 21.0 2.40 40.8 13.6 33.3 21.0 2.38 35.8 5.6 14.0
5.0 1.4 3.1 1000 33.9 23.5 2.45 42.2 13.8 34.5 23.5 2.43 37.0 5.8 14.2
1200 35.1 26.1 2.51 43.7 14.0 35.8 26.1 2.48 38.3 6.0 14.4
800 33.6 21.2 2.33 41.6 14.4 34.3 21.4 2.31 37.0 5.2 14.9
90 7.0 2.5 5.8 1000 34.9 23.8 2.38 43.1 14.6 35.6 24.0 2.36 38.3 5.4 15.1
1200 36.2 26.4 2.44 44.5 14.8 36.9 26.6 2.41 39.6 5.6 15.3
800 34.0 21.4 2.28 41.8 14.9 34.6 21.9 2.26 37.6 4.8 15.3
9.0 4.0 9.3 1000 35.3 24.0 2.34 43.3 15.1 36.0 24.5 2.31 38.9 4.9 15.5
1200 36.6 26.6 2.39 44.7 15.3 37.3 27.2 2.37 40.3 5.1 15.8
800 27.6 20.1 2.80 37.1 9.8 28.0 20.2 2.77 30.1 7.4 10.1
5.0 1.3 2.9 1000 28.1 22.3 2.82 37.8 10.0 28.5 22.4 2.80 30.6 7.5 10.2
1200 28.9 24.7 2.85 38.6 10.2 29.4 24.8 2.82 31.3 7.7 10.4
800 28.6 20.3 2.77 38.0 10.3 29.0 20.6 2.74 31.6 6.8 10.6
110 7.0 2.3 5.4 1000 29.2 22.5 2.79 38.7 10.4 29.6 22.9 2.76 32.1 6.9 10.7
1200 30.0 25.0 2.81 39.6 10.7 30.4 25.3 2.79 32.8 7.1 10.9
800 28.9 19.9 2.72 38.2 10.6 29.3 20.4 2.69 32.3 6.2 10.9
9.0 3.7 8.6 1000 29.5 22.2 2.74 38.8 10.7 29.9 22.7 2.72 32.8 6.4 11.0
1200 30.3 24.5 2.77 39.7 11.0 30.7 25.1 2.74 33.6 6.5 11.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
35
E SERIES SPECIFICATION CATALOG
E036
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
600 9.5 0.85 6.6 92.6 3.27 8.7 0.84 6.8 88.9 1.0 3.38
3.0 0.7 1.5 700 9.8 0.85 6.9 89.0 3.38 9.0 0.84 7.1 86.2 0.9 3.47
800 10.2 0.87 7.2 86.2 3.43 9.5 0.86 7.4 84.0 0.9 3.50
600 9.8 0.86 6.8 93.5 3.33 8.9 0.84 7.0 89.7 1.0 3.45
30 4.0 1.1 2.5 700 10.0 0.85 7.1 89.8 3.45 9.2 0.84 7.3 86.9 0.9 3.55
800 10.5 0.88 7.5 86.9 3.50 9.7 0.87 7.6 84.6 0.9 3.58
600 10.4 0.88 7.4 93.8 3.46 9.5 0.86 7.6 89.9 1.0 3.58
5.0 1.6 3.7 700 10.7 0.87 7.7 90.0 3.58 9.9 0.86 7.9 87.0 0.9 3.69
800 11.1 0.90 8.1 87.1 3.64 10.4 0.89 8.2 84.8 0.9 3.72
600 14.3 0.92 11.2 100.5 4.59 13.1 0.88 11.6 95.3 1.4 4.84
3.0 0.6 1.4 700 14.8 0.90 11.7 95.5 4.79 13.7 0.88 11.9 91.8 1.2 4.98
800 15.2 0.91 12.1 91.9 4.88 14.3 0.90 12.2 89.2 1.0 4.99
600 14.8 0.92 11.7 101.8 4.74 13.6 0.88 12.1 96.5 1.5 5.01
50 4.0 1.0 2.2 700 15.3 0.90 12.2 96.6 4.96 14.2 0.88 12.4 92.8 1.3 5.16
800 15.7 0.91 12.6 92.8 5.05 14.8 0.90 12.8 90.0 1.1 5.17
600 15.5 0.94 12.3 102.4 4.85 14.3 0.90 12.7 96.9 1.5 5.13
5.0 1.5 3.4 700 16.0 0.92 12.8 97.0 5.07 14.9 0.90 13.1 93.2 1.3 5.28
800 16.5 0.94 13.3 93.2 5.16 15.5 0.92 13.4 90.4 1.1 5.29
600 19.9 0.98 16.5 108.1 5.96 18.3 0.92 17.0 101.4 1.9 6.41
3.0 0.5 1.2 700 20.5 0.95 17.2 101.6 6.28 19.0 0.91 17.5 97.0 1.5 6.60
800 20.9 0.96 17.6 97.3 6.40 19.6 0.93 17.6 94.0 1.2 6.57
600 20.7 0.97 17.4 109.8 6.24 19.1 0.92 17.9 102.8 2.0 6.73
70 4.0 0.8 1.8 700 21.3 0.95 18.1 103.0 6.58 19.9 0.91 18.4 98.2 1.6 6.93
800 21.7 0.95 18.5 98.6 6.71 20.4 0.92 18.5 95.2 1.2 6.88
600 21.3 1.00 17.9 110.9 6.26 19.6 0.94 18.4 103.7 2.0 6.77
5.0 1.4 3.3 700 21.9 0.97 18.6 103.9 6.61 20.4 0.93 18.9 98.9 1.6 6.96
800 22.3 0.97 19.0 99.4 6.74 20.9 0.94 19.0 95.9 1.3 6.91
600 24.4 1.01 21.0 113.1 7.10 22.4 0.93 21.6 104.6 2.4 7.79
3.0 0.4 0.9 700 25.1 0.98 21.8 105.6 7.53 23.3 0.92 22.0 99.8 1.9 8.00
800 25.3 0.96 22.0 100.9 7.69 23.6 0.93 21.8 97.0 1.4 7.89
600 25.6 1.00 22.2 115.1 7.52 23.6 0.92 22.9 106.2 2.4 8.28
90 4.0 0.7 1.6 700 26.4 0.97 23.1 107.2 7.99 24.5 0.91 23.3 101.1 1.9 8.50
800 26.5 0.95 23.3 102.4 8.15 24.8 0.92 23.1 98.2 1.4 8.38
600 25.8 1.02 22.3 116.7 7.40 23.6 0.94 23.0 107.6 2.5 8.17
5.0 1.3 3.0 700 26.5 0.99 23.1 108.5 7.87 24.5 0.93 23.4 102.3 2.0 8.38
800 26.6 0.97 23.3 103.6 8.03 24.8 0.93 23.1 99.3 1.4 8.25
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
36
E SERIES SPECIFICATION CATALOG
E036
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
600 21.2 13.7 0.64 23.4 33.1 21.4 13.7 0.63 22.9 0.7 33.8
3.0 0.6 1.4 700 21.8 14.9 0.65 24.0 33.8 22.0 14.9 0.64 23.5 0.7 34.4
800 22.4 16.5 0.66 24.6 34.0 22.6 16.5 0.65 24.1 0.7 34.7
600 21.4 13.8 0.62 23.5 34.3 21.5 13.8 0.62 23.1 0.5 34.8
50 4.0 1.0 2.2 700 22.0 15.0 0.63 24.1 35.0 22.1 15.0 0.62 23.7 0.5 35.5
800 22.6 16.6 0.64 24.8 35.2 22.7 16.6 0.63 24.3 0.6 35.8
600 21.8 14.2 0.62 23.9 35.2 21.8 14.2 0.61 23.5 0.4 35.5
5.0 1.5 3.4 700 22.3 15.4 0.62 24.5 35.9 22.3 15.4 0.62 24.0 0.4 36.2
800 23.0 17.0 0.64 25.1 36.1 23.0 17.0 0.63 24.7 0.4 36.5
600 19.1 13.5 0.84 22.0 22.9 19.4 13.4 0.82 20.2 2.0 23.6
3.0 0.5 1.2 700 19.6 14.6 0.84 22.5 23.3 19.9 14.5 0.83 20.7 2.0 24.0
800 20.2 16.2 0.86 23.1 23.5 20.5 16.0 0.85 21.3 2.1 24.2
600 19.3 13.6 0.81 22.1 23.7 19.5 13.6 0.80 20.5 1.7 24.2
70 4.0 0.8 1.8 700 19.8 14.7 0.82 22.6 24.2 20.0 14.7 0.81 21.0 1.8 24.7
800 20.4 16.3 0.84 23.2 24.4 20.6 16.3 0.83 21.6 1.8 24.9
600 19.6 13.9 0.81 22.4 24.3 19.7 14.0 0.80 21.0 1.5 24.7
5.0 1.4 3.3 700 20.1 15.1 0.81 22.9 24.8 20.2 15.2 0.81 21.5 1.5 25.1
800 20.7 16.7 0.83 23.5 25.0 20.8 16.8 0.82 22.1 1.6 25.4
600 16.2 12.5 1.02 19.7 15.9 16.5 12.2 1.00 16.6 3.3 16.5
3.0 0.4 0.9 700 16.6 13.5 1.03 20.1 16.2 16.9 13.3 1.01 17.0 3.4 16.8
800 17.1 15.0 1.05 20.6 16.3 17.4 14.7 1.03 17.4 3.5 17.0
600 16.3 12.6 0.99 19.7 16.4 16.6 12.5 0.98 16.9 3.0 16.9
90 4.0 0.7 1.6 700 16.7 13.6 1.00 20.2 16.7 17.0 13.6 0.99 17.3 3.0 17.2
800 17.2 15.1 1.02 20.7 16.9 17.5 15.0 1.00 17.8 3.1 17.4
600 16.6 12.9 0.99 19.9 16.8 16.8 13.0 0.98 17.5 2.6 17.2
5.0 1.3 3.0 700 17.0 14.0 0.99 20.4 17.2 17.2 14.1 0.98 17.9 2.6 17.5
800 17.5 15.5 1.01 20.9 17.3 17.7 15.6 1.00 18.4 2.7 17.7
600 12.9 10.5 1.19 16.9 10.8 13.2 10.2 1.16 12.5 4.7 11.4
3.0 0.3 0.6 700 13.2 11.4 1.20 17.3 11.0 13.5 11.0 1.17 12.8 4.8 11.6
800 13.6 12.6 1.22 17.7 11.1 13.9 12.2 1.19 13.1 4.9 11.7
600 13.0 10.6 1.16 16.9 11.2 13.2 10.5 1.14 13.0 4.2 11.6
110 4.0 0.6 1.4 700 13.3 11.5 1.17 17.3 11.4 13.6 11.4 1.15 13.2 4.3 11.9
800 13.7 12.7 1.19 17.8 11.5 14.0 12.6 1.17 13.6 4.4 11.9
600 13.2 10.8 1.15 17.1 11.5 13.4 11.0 1.14 13.6 3.7 11.8
5.0 1.2 2.8 700 13.6 11.7 1.16 17.5 11.7 13.8 11.9 1.15 13.9 3.8 12.0
800 13.9 13.0 1.18 18.0 11.8 14.1 13.2 1.17 14.3 3.9 12.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
37
E SERIES SPECIFICATION CATALOG
E040
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1000 27.4 2.37 19.3 95.4 3.39 23.1 2.28 19.5 91.4 4.2 3.51
5.0 1.7 3.9
1300 27.7 2.35 19.7 89.7 3.45 23.6 2.29 19.7 86.8 3.9 3.52
1000 28.3 2.40 20.1 96.2 3.46 23.8 2.30 20.3 92.0 4.4 3.59
30 8.0 3.5 8.0
1300 28.6 2.38 20.5 90.4 3.53 24.3 2.31 20.5 87.3 4.0 3.61
1000 28.7 2.40 20.5 96.6 3.51 24.1 2.30 20.7 92.3 4.5 3.64
11.0 4.9 11.4
1300 29.0 2.38 20.9 90.7 3.58 24.7 2.30 20.9 87.6 4.1 3.66
1000 35.7 2.50 27.2 103.1 4.18 30.2 2.39 27.5 98.0 5.4 4.37
5.0 1.6 3.7
1300 36.3 2.45 28.0 95.9 4.34 31.4 2.36 28.1 92.4 4.7 4.48
1000 37.2 2.56 28.5 104.5 4.25 31.4 2.44 28.7 99.1 5.7 4.46
50 8.0 3.3 7.7
1300 37.9 2.50 29.3 97.0 4.43 32.7 2.41 29.4 93.3 4.9 4.59
1000 38.0 2.58 29.2 105.2 4.31 32.0 2.45 29.5 99.7 5.8 4.52
11.0 4.7 10.9
1300 38.7 2.52 30.1 97.5 4.50 33.5 2.42 30.2 93.8 5.0 4.66
1000 43.2 2.67 34.0 110.0 4.74 36.4 2.52 34.4 103.7 6.6 5.00
5.0 1.5 3.5
1300 44.1 2.58 35.3 101.4 5.01 38.5 2.46 35.6 97.4 5.6 5.24
1000 45.2 2.76 35.8 111.9 4.80 38.1 2.60 36.2 105.3 6.9 5.08
70 8.0 3.2 7.4
1300 46.3 2.66 37.2 103.0 5.10 40.4 2.53 37.6 98.8 5.8 5.35
1000 46.4 2.79 36.9 113.0 4.87 39.1 2.63 37.2 106.2 7.1 5.15
11.0 4.5 10.5
1300 47.6 2.69 38.4 103.9 5.19 41.6 2.55 38.8 99.6 5.9 5.45
1000 50.1 2.83 40.4 116.4 5.18 42.0 2.65 40.8 108.9 7.8 5.51
5.0 1.5 3.5
1300 51.5 2.70 42.3 106.7 5.59 45.2 2.55 42.9 102.2 6.4 5.92
1000 52.8 2.97 42.7 118.9 5.22 44.3 2.76 43.1 111.0 8.2 5.57
90 8.0 3.1 7.2
1300 54.5 2.82 44.9 108.8 5.67 47.9 2.65 45.5 104.1 6.7 6.03
1000 54.5 3.02 44.2 120.4 5.29 45.8 2.81 44.6 112.4 8.4 5.66
11.0 4.4 10.2
1300 56.3 2.86 46.5 110.1 5.76 49.6 2.69 47.2 105.3 6.8 6.15
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
38
E SERIES SPECIFICATION CATALOG
E040
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1000 42.0 27.2 1.62 47.5 26.0 42.0 27.2 1.58 43.8 3.5 26.5
5.0 1.6 3.7
1300 43.7 30.5 1.70 49.5 25.7 43.7 30.5 1.67 45.7 3.7 26.2
1000 42.4 27.4 1.54 47.7 27.5 42.4 27.4 1.52 44.2 3.4 27.9
50 8.0 3.3 7.7
1300 44.2 30.8 1.62 49.7 27.2 44.2 30.8 1.60 46.1 3.5 27.6
1000 42.8 27.4 1.50 47.9 28.6 42.8 27.4 1.49 44.7 3.2 28.8
11.0 4.7 10.9
1300 44.6 30.8 1.58 50.0 28.3 44.6 30.8 1.57 46.7 3.3 28.5
1000 39.3 26.4 2.03 46.2 19.3 39.5 26.4 1.98 40.7 5.5 19.9
5.0 1.5 3.5
1300 40.7 29.6 2.13 47.9 19.1 40.9 29.7 2.07 42.2 5.8 19.7
1000 39.9 26.6 1.93 46.5 20.7 40.1 26.7 1.90 41.4 5.2 21.1
70 8.0 3.2 7.4
1300 41.3 29.9 2.02 48.2 20.5 41.5 30.0 1.98 42.9 5.4 20.9
1000 40.3 26.6 1.87 46.7 21.5 40.5 26.7 1.86 42.0 4.8 21.8
11.0 4.5 10.5
1300 41.7 29.9 1.96 48.4 21.3 41.9 30.0 1.94 43.6 5.0 21.6
1000 35.7 25.3 2.58 44.5 13.9 36.1 25.5 2.50 37.1 7.6 14.4
5.0 1.5 3.5
1300 36.8 28.5 2.69 46.0 13.7 37.2 28.6 2.61 38.3 7.8 14.3
1000 36.5 25.6 2.44 44.8 15.0 36.8 25.7 2.39 37.9 7.0 15.4
90 8.0 3.1 7.2
1300 37.6 28.8 2.54 46.2 14.8 38.0 28.9 2.49 39.2 7.3 15.3
1000 36.8 25.6 2.37 44.9 15.6 37.2 25.7 2.34 38.7 6.5 15.9
11.0 4.4 10.2
1300 38.0 28.8 2.46 46.4 15.4 38.3 28.9 2.44 40.0 6.7 15.7
1000 31.2 23.9 3.32 42.6 9.4 31.7 24.1 3.20 33.1 9.6 9.9
5.0 1.5 3.5
1300 32.0 26.9 3.44 43.8 9.3 32.5 27.1 3.32 34.0 9.9 9.8
1000 32.0 24.1 3.12 42.7 10.3 32.5 24.3 3.05 34.1 8.9 10.7
110 8.0 3.0 6.9
1300 32.9 27.1 3.24 43.9 10.2 33.4 27.3 3.16 35.0 9.1 10.6
1000 32.4 24.1 3.03 42.7 10.7 32.9 24.3 3.00 34.9 8.2 11.0
11.0 4.3 9.9
1300 33.2 27.1 3.14 43.9 10.6 33.7 27.3 3.10 35.9 8.4 10.9
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
39
E SERIES SPECIFICATION CATALOG
E040
Heating Capacity Data (1300 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 28.6 2.25 20.9 80.4 3.72 24.3 2.19 20.8 77.3 3.8 3.76
5.0 1.7 3.9 70 27.8 2.37 19.7 89.8 3.43 23.6 2.31 19.7 86.8 3.9 3.50
80 26.9 2.49 18.5 99.2 3.17 22.7 2.42 18.5 96.2 4.0 3.24
60 29.5 2.28 21.7 81.0 3.80 25.4 2.21 21.7 78.1 3.9 3.88
30 8.0 3.5 8.0 70 28.7 2.40 20.5 90.4 3.51 24.4 2.33 20.5 87.4 4.0 3.58
80 27.9 2.51 19.3 99.8 3.25 23.5 2.44 19.3 96.7 4.2 3.31
60 30.0 2.28 22.2 81.3 3.86 25.7 2.21 22.2 78.3 4.0 3.95
11.0 4.9 11.4 70 29.1 2.40 20.9 90.7 3.56 24.8 2.32 20.9 87.6 4.1 3.64
80 28.3 2.51 19.7 100.1 3.29 23.8 2.44 19.7 96.9 4.2 3.36
60 37.7 2.35 29.6 86.8 4.70 32.9 2.26 29.7 83.4 4.6 4.85
5.0 1.6 3.7 70 36.4 2.47 28.0 95.9 4.31 31.5 2.38 28.1 92.4 4.7 4.45
80 35.1 2.60 26.3 105.0 3.97 30.1 2.50 26.4 101.4 4.9 4.09
60 39.3 2.40 31.1 88.0 4.80 34.3 2.30 31.2 84.4 4.8 4.97
50 8.0 3.3 7.7 70 37.9 2.52 29.3 97.0 4.40 32.8 2.43 29.4 93.4 4.9 4.56
80 36.6 2.65 27.6 106.1 4.05 31.3 2.55 27.7 102.3 5.1 4.18
60 40.1 2.41 31.9 88.6 4.88 35.1 2.31 32.0 85.0 4.8 5.06
11.0 4.7 11.4 70 38.7 2.54 30.1 97.6 4.47 33.5 2.44 30.2 93.9 5.0 4.64
80 37.3 2.66 28.3 106.6 4.11 32.0 2.56 28.4 102.8 5.1 4.26
60 45.9 2.47 37.4 92.7 5.45 40.4 2.36 37.7 88.8 5.4 5.70
5.0 1.5 3.5 70 44.2 2.60 35.3 101.5 4.98 38.5 2.48 35.6 97.4 5.6 5.21
80 42.5 2.73 33.2 110.3 4.57 36.6 2.60 33.5 106.1 5.7 4.77
60 48.2 2.55 39.5 94.3 5.55 42.5 2.42 39.9 90.3 5.6 5.82
70 8.0 3.2 7.4 70 46.4 2.68 37.2 103.0 5.08 40.5 2.55 37.6 98.9 5.8 5.32
80 44.6 2.81 35.0 111.8 4.65 38.5 2.68 35.3 107.4 6.0 4.87
60 49.5 2.57 40.7 95.2 5.64 43.7 2.44 41.1 91.1 5.7 5.93
11.0 4.5 10.5 70 47.6 2.71 38.4 103.9 5.16 41.7 2.57 38.8 99.7 5.9 5.42
80 45.8 2.84 36.1 112.6 4.72 39.6 2.70 36.5 108.2 6.1 4.96
60 53.7 2.59 44.9 98.2 6.08 47.6 2.44 45.4 93.9 6.2 6.45
5.0 1.5 3.5 70 51.6 2.72 42.3 106.8 5.56 45.3 2.57 42.9 102.2 6.4 5.88
80 49.5 2.86 39.8 115.3 5.08 42.9 2.70 40.3 110.6 6.6 5.37
60 56.8 2.70 47.6 100.4 6.17 50.4 2.54 48.3 95.9 6.5 6.57
90 8.0 3.1 7.2 70 54.6 2.84 44.9 108.9 5.64 48.0 2.67 45.5 104.2 6.7 5.99
80 52.4 2.98 42.2 117.3 5.15 45.5 2.81 42.8 112.4 6.9 5.47
60 58.6 2.74 49.3 101.8 6.28 52.2 2.57 50.0 97.2 6.6 6.70
11.0 4.4 10.2 70 56.3 2.88 46.5 110.1 5.73 49.6 2.71 47.2 105.4 6.8 6.11
80 54.0 3.02 43.7 118.5 5.24 47.1 2.84 44.4 113.5 7.0 5.57
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
40
E SERIES SPECIFICATION CATALOG
E040
Cooling Capacity Data (1300 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 40.2 29.3 1.69 46.6 23.8 40.2 29.3 1.65 46.5 3.6 24.3
5.0 1.6 3.7 80/67 43.7 30.5 1.72 49.6 25.4 43.7 30.5 1.69 49.5 3.7 25.9
85/71 47.2 31.7 1.76 52.5 26.9 47.2 31.7 1.72 52.4 3.8 27.4
75/63 40.6 29.6 1.61 46.8 25.2 40.6 29.6 1.59 46.7 3.4 25.5
50 8.0 3.3 7.7 80/67 44.1 30.8 1.64 49.8 26.9 44.1 30.8 1.62 49.7 3.5 27.2
85/71 47.7 32.1 1.68 52.7 28.4 47.7 32.1 1.65 52.7 3.6 28.8
75/63 41.0 29.6 1.56 47.0 26.2 41.0 29.6 1.55 47.0 3.2 26.4
11.0 4.7 10.9 80/67 44.6 30.8 1.60 50.0 27.9 44.6 30.8 1.59 50.0 3.3 28.1
85/71 48.2 32.1 1.63 53.0 29.6 48.2 32.1 1.62 53.0 3.4 29.8
75/63 37.4 28.5 2.10 45.1 17.8 37.6 28.5 2.05 45.1 5.6 18.3
5.0 1.6 3.7 80/67 40.7 29.6 2.15 48.0 19.0 40.9 29.7 2.09 48.0 5.8 19.5
85/71 43.9 30.8 2.19 50.9 20.1 44.1 30.9 2.13 50.9 5.9 20.7
75/63 38.0 28.7 2.00 45.4 19.0 38.2 28.8 1.96 45.4 5.2 19.4
70 8.0 3.3 7.7 80/67 41.3 29.9 2.04 48.3 20.3 41.5 30.0 2.00 48.3 5.4 20.7
85/71 44.6 31.1 2.08 51.1 21.5 44.8 31.2 2.04 51.2 5.5 21.9
75/63 38.4 28.7 1.94 45.6 19.8 38.6 28.8 1.92 45.7 4.9 20.0
11.0 4.7 10.9 80/67 41.7 29.9 1.98 48.5 21.1 41.9 30.0 1.96 48.6 5.0 21.4
85/71 45.1 31.1 2.02 51.4 22.3 45.3 31.2 2.00 51.5 5.2 22.6
75/63 33.9 27.3 2.65 43.3 12.8 34.2 27.5 2.57 43.4 7.6 13.3
5.0 1.5 3.7 80/67 36.8 28.5 2.71 46.0 13.6 37.2 28.6 2.63 46.1 7.8 14.2
85/71 39.7 29.6 2.76 48.8 14.4 40.1 29.8 2.68 48.9 8.0 15.0
75/63 34.6 27.6 2.51 43.5 13.8 34.9 27.8 2.46 43.7 7.0 14.2
90 8.0 3.1 7.2 80/67 37.6 28.8 2.56 46.3 14.7 37.9 28.9 2.51 46.5 7.3 15.1
85/71 40.6 29.9 2.61 49.1 15.5 41.0 30.1 2.56 49.3 7.5 16.0
75/63 34.9 27.6 2.43 43.6 14.3 35.3 27.8 2.41 43.9 6.5 14.6
11.0 4.4 10.2 80/67 37.9 28.8 2.48 46.4 15.3 38.3 28.9 2.46 46.7 6.7 15.6
85/71 41.0 29.9 2.53 49.2 16.2 41.4 30.1 2.51 49.5 6.9 16.5
75/63 29.5 25.8 3.39 41.2 8.7 29.9 26.0 3.27 41.3 9.6 9.1
5.0 1.5 3.5 80/67 32.0 26.9 3.46 43.8 9.3 32.5 27.1 3.34 43.9 9.9 9.7
85/71 34.6 27.9 3.53 46.5 9.8 35.1 28.1 3.41 46.5 10.1 10.3
75/63 30.2 26.0 3.19 41.3 9.5 30.7 26.2 3.12 41.5 8.9 9.8
110 8.0 3.0 6.9 80/67 32.8 27.1 3.26 44.0 10.1 33.3 27.3 3.18 44.2 9.1 10.5
85/71 35.5 28.2 3.32 46.6 10.7 36.0 28.4 3.24 46.8 9.4 11.1
75/63 30.5 26.0 3.10 41.3 9.9 31.0 26.2 3.06 41.7 8.1 10.1
11.0 4.3 9.9 80/67 33.2 27.1 3.16 44.0 10.5 33.7 27.3 3.12 44.3 8.4 10.8
85/71 35.8 28.2 3.23 46.6 11.1 36.4 28.4 3.19 47.0 8.7 11.4
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
41
E SERIES SPECIFICATION CATALOG
E047
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1200 34.3 3.09 23.8 96.5 3.25 29.3 2.97 24.0 92.6 4.8 3.37
6.0 2.0 4.6
1500 34.7 3.07 24.2 91.4 3.31 29.9 2.98 24.2 88.4 4.5 3.38
1200 35.4 3.13 24.8 97.3 3.32 30.2 3.00 25.0 93.3 5.0 3.44
30 9.0 3.7 8.5
1500 35.8 3.10 25.2 92.1 3.39 30.9 3.01 25.2 89.1 4.6 3.46
1200 35.9 3.13 25.2 97.7 3.36 30.6 3.00 25.5 93.6 5.1 3.49
12.0 5.9 13.6
1500 36.3 3.10 25.8 92.4 3.44 31.3 3.01 25.8 89.3 4.7 3.51
1200 44.1 3.28 32.9 104.0 3.94 37.9 3.12 33.2 99.2 6.0 4.12
6.0 1.9 4.4
1500 44.8 3.21 33.8 97.6 4.09 39.2 3.09 33.9 94.2 5.3 4.22
1200 45.9 3.36 34.4 105.4 4.01 39.4 3.19 34.8 100.4 6.3 4.19
50 9.0 3.5 8.2
1500 46.7 3.28 35.5 98.8 4.17 40.9 3.15 35.6 95.2 5.5 4.31
1200 46.8 3.38 35.3 106.1 4.06 40.2 3.21 35.6 101.0 6.4 4.25
12.0 5.6 12.9
1500 47.6 3.30 36.4 99.4 4.23 41.8 3.16 36.6 95.8 5.6 4.39
1200 53.2 3.53 41.1 111.0 4.41 45.7 3.33 41.5 105.2 7.3 4.65
6.0 1.8 3.9
1500 54.3 3.41 42.7 103.5 4.66 48.0 3.26 43.0 99.6 6.2 4.87
1200 55.7 3.66 43.3 113.0 4.47 47.9 3.44 43.7 107.0 7.5 4.72
70 9.0 3.3 7.6
1500 57.0 3.52 45.0 105.2 4.74 50.5 3.35 45.4 101.2 6.4 4.97
1200 57.2 3.70 44.5 114.1 4.53 49.2 3.48 45.0 107.9 7.7 4.79
12.0 5.3 12.2
1500 58.5 3.56 46.4 106.1 4.82 51.9 3.38 46.9 102.0 6.5 5.06
1200 60.8 3.75 48.0 116.9 4.75 51.9 3.50 48.5 110.1 8.5 5.06
6.0 1.7 3.9
1500 62.5 3.57 50.3 108.6 5.13 55.5 3.37 51.0 104.2 7.0 5.43
1200 64.2 3.92 50.8 119.5 4.79 54.9 3.65 51.3 112.4 8.8 5.11
90 9.0 3.3 7.6
1500 66.1 3.73 53.4 110.8 5.20 58.8 3.51 54.2 106.3 7.3 5.52
1200 66.2 3.99 52.5 121.1 4.86 56.7 3.71 53.1 113.8 9.0 5.19
12.0 5.2 12.0
1500 68.2 3.78 55.3 112.1 5.29 60.9 3.55 56.2 107.6 7.4 5.63
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
42
E SERIES SPECIFICATION CATALOG
E047
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM CFM
PSI FT TC SC KW HR EER TC SC KW HR HW EER
1200 50.6 31.4 2.23 58.2 22.6 50.6 31.4 2.19 54.0 4.0 23.1
6.0 1.9 4.4
1500 52.7 35.3 2.35 60.7 22.4 52.7 35.3 2.31 56.4 4.2 22.9
1200 51.1 31.7 2.13 58.4 24.0 51.1 31.7 2.10 54.5 3.8 24.3
50 9.0 3.5 8.2
1500 53.2 35.6 2.24 60.9 23.7 53.2 35.6 2.21 56.8 4.0 24.0
1200 51.6 31.7 2.07 58.7 25.0 51.6 31.7 2.06 55.0 3.6 25.1
12.0 5.6 12.9
1500 53.8 35.6 2.18 61.2 24.7 53.8 35.6 2.17 57.4 3.8 24.8
1200 47.7 30.8 2.70 56.9 17.7 47.9 30.9 2.63 51.1 5.9 18.2
6.0 1.8 3.9
1500 49.4 34.6 2.83 59.1 17.5 49.7 34.7 2.76 53.0 6.1 18.0
1200 48.4 31.1 2.57 57.2 18.9 48.7 31.2 2.52 51.7 5.6 19.3
70 9.0 3.3 7.6
1500 50.2 35.0 2.69 59.4 18.7 50.4 35.1 2.64 53.6 5.9 19.1
1200 48.9 31.1 2.49 57.4 19.6 49.2 31.2 2.47 52.2 5.4 19.9
12.0 5.3 12.2
1500 50.7 35.0 2.61 59.6 19.4 51.0 35.1 2.59 54.2 5.6 19.7
1200 43.6 29.6 3.35 55.1 13.0 44.1 29.7 3.25 47.4 7.7 13.6
6.0 1.7 3.9
1500 45.0 33.2 3.49 56.9 12.9 45.4 33.4 3.38 49.0 8.0 13.4
1200 44.5 29.9 3.16 55.3 14.1 45.0 30.0 3.10 48.1 7.5 14.5
90 9.0 3.3 7.6
1500 45.9 33.6 3.30 57.2 13.9 46.4 33.7 3.23 49.7 7.7 14.4
1200 45.0 29.9 3.07 55.5 14.6 45.4 30.0 3.04 48.7 7.2 14.9
12.0 5.2 12.0
1500 46.4 33.6 3.20 57.3 14.5 46.8 33.7 3.17 50.3 7.4 14.8
1200 38.3 27.7 4.21 52.6 9.1 38.9 27.9 4.06 43.1 9.6 9.6
6.0 1.6 3.9
1500 39.3 31.1 4.36 54.1 9.0 39.9 31.3 4.21 44.3 9.9 9.5
1200 39.3 28.0 3.96 52.8 9.9 39.9 28.2 3.86 43.8 9.3 10.3
110 9.0 3.0 6.9
1500 40.3 31.4 4.10 54.3 9.8 40.9 31.6 4.01 45.0 9.6 10.2
1200 39.7 28.0 3.84 52.8 10.3 40.3 28.2 3.80 44.3 8.9 10.6
12.0 4.8 11.1
1500 40.7 31.4 3.98 54.3 10.2 41.3 31.6 3.93 45.5 9.2 10.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
43
E SERIES SPECIFICATION CATALOG
E047
Heating Capacity Data (1500 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 35.8 2.93 25.7 82.1 3.58 30.8 2.85 25.6 79.0 4.4 3.62
6.0 2.0 4.6 70 34.8 3.09 24.2 91.5 3.30 29.9 3.00 24.2 88.5 4.5 3.36
80 33.7 3.24 22.8 100.8 3.05 28.8 3.15 22.7 97.8 4.7 3.11
60 36.9 2.96 26.8 82.8 3.65 32.1 2.88 26.7 79.8 4.5 3.73
30 9.0 3.7 8.5 70 35.9 3.12 25.2 92.2 3.37 30.9 3.03 25.2 89.1 4.6 3.44
80 34.9 3.28 23.7 101.5 3.12 29.8 3.18 23.7 98.4 4.8 3.19
60 37.4 2.96 27.3 83.1 3.70 32.6 2.87 27.3 80.1 4.6 3.78
12.0 5.9 13.6 70 36.4 3.12 25.8 92.5 3.42 31.4 3.03 25.8 89.4 4.7 3.49
80 35.4 3.28 24.2 101.8 3.17 30.2 3.18 24.2 98.7 4.8 3.23
60 46.3 3.07 35.9 88.6 4.42 40.9 2.96 36.0 85.2 5.2 4.57
6.0 1.9 4.4 70 44.9 3.23 33.8 97.7 4.07 39.2 3.11 33.9 94.2 5.3 4.20
80 43.4 3.39 31.8 106.8 3.75 37.6 3.27 31.9 103.2 5.5 3.86
60 48.3 3.13 37.6 89.8 4.52 42.7 3.01 37.8 86.4 5.3 4.67
50 9.0 3.5 8.2 70 46.7 3.30 35.5 98.8 4.15 40.9 3.17 35.6 95.3 5.5 4.29
80 45.2 3.46 33.3 107.9 3.82 39.2 3.33 33.5 104.2 5.7 3.95
60 49.3 3.15 38.6 90.4 4.59 43.6 3.02 38.7 86.9 5.4 4.76
12.0 5.6 13.6 70 47.7 3.32 36.4 99.4 4.22 41.8 3.18 36.6 95.8 5.6 4.37
80 46.1 3.48 34.2 108.4 3.88 40.0 3.34 34.4 104.7 5.8 4.01
60 56.4 3.26 45.3 94.8 5.06 50.2 3.11 45.6 91.0 6.0 5.30
6.0 1.8 3.9 70 54.4 3.43 42.7 103.6 4.64 48.0 3.28 43.0 99.7 6.2 4.85
80 52.4 3.61 40.1 112.4 4.26 45.8 3.44 40.5 108.3 6.4 4.45
60 59.2 3.36 47.7 96.5 5.16 52.9 3.20 48.2 92.6 6.2 5.41
70 9.0 3.3 7.6 70 57.1 3.54 45.0 105.2 4.73 50.5 3.37 45.4 101.2 6.4 4.95
80 55.0 3.72 42.3 114.0 4.33 48.2 3.54 42.7 109.8 6.6 4.54
60 60.8 3.40 49.2 97.5 5.24 54.4 3.23 49.7 93.6 6.3 5.51
12.0 5.3 12.2 70 58.6 3.58 46.4 106.2 4.80 52.0 3.40 46.9 102.1 6.5 5.04
80 56.4 3.76 43.6 114.8 4.40 49.5 3.57 44.1 110.6 6.7 4.62
60 65.0 3.41 53.4 100.1 5.58 58.2 3.22 54.1 95.9 6.8 5.91
6.0 1.7 3.9 70 62.6 3.59 50.3 108.6 5.11 55.5 3.39 51.0 104.3 7.0 5.40
80 60.2 3.77 47.3 117.2 4.68 52.9 3.56 47.9 112.6 7.3 4.94
60 68.7 3.56 56.6 102.4 5.66 61.8 3.35 57.4 98.1 7.1 6.02
90 9.0 3.3 7.6 70 66.2 3.75 53.4 110.8 5.18 58.9 3.53 54.2 106.4 7.3 5.50
80 63.6 3.93 50.2 119.3 4.74 56.0 3.70 50.9 114.6 7.5 5.03
60 71.0 3.61 58.6 103.8 5.76 63.9 3.40 59.5 99.5 7.2 6.14
12.0 5.2 12.0 70 68.3 3.80 55.3 112.2 5.27 60.9 3.57 56.2 107.6 7.4 5.60
80 65.6 3.99 52.0 120.5 4.82 58.0 3.75 52.8 115.8 7.6 5.12
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
44
E SERIES SPECIFICATION CATALOG
E047
Cooling Capacity Data (1500 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 48.5 33.9 2.32 57.1 20.9 48.5 33.9 2.28 57.0 4.1 21.3
6.0 1.9 4.4 80/67 52.7 35.3 2.37 60.8 22.2 52.7 35.3 2.33 60.6 4.2 22.7
85/71 56.9 36.7 2.42 64.4 23.5 56.9 36.7 2.37 64.3 4.3 24.0
75/63 49.0 34.2 2.22 57.3 22.1 49.0 34.2 2.19 57.2 3.9 22.4
50 9.0 3.5 8.2 80/67 53.2 35.6 2.26 60.9 23.5 53.2 35.6 2.23 60.9 4.0 23.8
85/71 57.5 37.0 2.31 64.6 24.9 57.5 37.0 2.28 64.5 4.1 25.2
75/63 49.5 34.2 2.15 57.6 23.0 49.5 34.2 2.14 57.5 3.7 23.1
12.0 5.6 12.9 80/67 53.8 35.6 2.20 61.3 24.5 53.8 35.6 2.19 61.2 3.8 24.6
85/71 58.1 37.0 2.24 64.9 25.9 58.1 37.0 2.23 64.9 3.9 26.1
75/63 45.5 33.3 2.79 55.6 16.3 45.7 33.3 2.72 55.6 5.9 16.8
6.0 1.9 4.4 80/67 49.4 34.6 2.85 59.1 17.3 49.7 34.7 2.78 59.1 6.1 17.9
85/71 53.4 36.0 2.91 62.7 18.4 53.6 36.1 2.83 62.7 6.3 18.9
75/63 46.2 33.6 2.65 55.8 17.4 46.4 33.7 2.61 55.9 5.7 17.8
70 9.0 3.5 8.2 80/67 50.2 35.0 2.71 59.4 18.5 50.4 35.1 2.66 59.5 5.9 18.9
85/71 54.2 36.4 2.76 63.0 19.6 54.5 36.5 2.72 63.1 6.0 20.1
75/63 46.6 33.6 2.58 56.1 18.1 46.9 33.7 2.56 56.2 5.4 18.3
12.0 5.6 12.9 80/67 50.7 35.0 2.63 59.7 19.3 50.9 35.1 2.61 59.8 5.6 19.5
85/71 54.7 36.4 2.68 63.2 20.4 55.0 36.5 2.66 63.4 5.8 20.7
75/63 41.4 31.9 3.44 53.5 12.0 41.8 32.1 3.34 53.6 7.8 12.5
6.0 1.7 4.4 80/67 45.0 33.2 3.51 56.9 12.8 45.4 33.4 3.40 57.0 8.0 13.3
85/71 48.6 34.6 3.58 60.4 13.6 49.1 34.7 3.47 60.5 8.2 14.1
75/63 42.2 32.2 3.25 53.8 13.0 42.6 32.4 3.19 54.0 7.5 13.4
90 9.0 3.3 7.6 80/67 45.9 33.6 3.32 57.2 13.8 46.4 33.7 3.25 57.4 7.7 14.3
85/71 49.6 34.9 3.38 60.6 14.7 50.1 35.1 3.32 60.9 7.9 15.1
75/63 42.7 32.2 3.16 53.9 13.5 43.1 32.4 3.12 54.2 7.2 13.8
12.0 5.2 12.0 80/67 46.4 33.6 3.22 57.3 14.4 46.8 33.7 3.19 57.7 7.4 14.7
85/71 50.1 34.9 3.28 60.8 15.2 50.6 35.1 3.25 61.2 7.6 15.6
75/63 36.1 29.9 4.29 50.9 8.4 36.6 30.1 4.14 51.0 9.6 8.8
6.0 1.6 3.9 80/67 39.2 31.1 4.38 54.2 9.0 39.8 31.3 4.23 54.3 9.9 9.4
85/71 42.4 32.3 4.47 57.4 9.5 43.0 32.6 4.31 57.5 10.2 10.0
75/63 37.0 30.2 4.04 51.1 9.2 37.6 30.4 3.94 51.3 9.3 9.5
110 9.0 3.0 6.9 80/67 40.3 31.4 4.12 54.3 9.8 40.9 31.6 4.03 54.6 9.6 10.2
85/71 43.5 32.7 4.20 57.6 10.3 44.1 32.9 4.11 57.9 9.8 10.8
75/63 37.4 30.2 3.92 51.1 9.5 38.0 30.4 3.88 51.5 8.9 9.8
12.0 4.8 11.1 80/67 40.7 31.4 4.00 54.3 10.2 41.3 31.6 3.95 54.8 9.2 10.4
85/71 43.9 32.7 4.08 57.6 10.8 44.6 32.9 4.03 58.1 9.5 11.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
45
E SERIES SPECIFICATION CATALOG
E048
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
900 30.9 2.77 21.5 101.8 3.27 26.0 2.72 22.3 96.7 5.7 3.40
6.0 2.0 4.6 1200 31.8 2.80 22.2 94.5 3.33 26.8 2.75 22.8 90.7 5.4 3.43
1500 32.8 2.89 22.9 90.2 3.32 27.9 2.84 23.2 87.2 5.0 3.39
900 31.7 2.82 22.1 102.6 3.29 26.5 2.77 23.0 97.2 6.0 3.43
30 9.0 3.7 8.5 1200 32.6 2.83 22.9 95.1 3.37 27.4 2.78 23.5 91.1 5.6 3.48
1500 33.6 2.92 23.6 90.7 3.36 28.4 2.87 23.8 87.6 5.2 3.44
900 32.3 2.86 22.5 103.2 3.30 26.9 2.81 23.4 97.6 6.1 3.44
12.0 5.9 13.6 1200 33.1 2.86 23.4 95.6 3.39 27.8 2.81 23.9 91.5 5.7 3.50
1500 34.2 2.95 24.1 91.1 3.39 28.9 2.89 24.3 87.8 5.3 3.46
900 42.3 3.39 30.7 113.5 3.66 34.7 3.26 31.8 105.7 8.2 3.86
6.0 1.9 4.4 1200 43.4 3.22 32.5 103.5 3.96 36.3 3.11 33.0 98.0 7.4 4.11
1500 44.8 3.26 33.6 97.6 4.02 37.7 3.17 33.6 93.3 6.7 4.11
900 43.9 3.46 32.1 115.1 3.72 36.3 3.32 33.2 107.4 8.2 3.93
50 9.0 3.5 8.1 1200 45.1 3.28 33.8 104.8 4.02 38.0 3.17 34.5 99.3 7.3 4.18
1500 46.4 3.33 35.1 98.7 4.09 39.4 3.23 35.1 94.3 6.7 4.18
900 44.8 3.49 32.9 116.1 3.76 37.3 3.35 34.0 108.4 8.2 3.98
12.0 5.6 12.9 1200 46.0 3.32 34.7 105.5 4.07 39.0 3.20 35.4 100.1 7.3 4.23
1500 47.5 3.36 36.0 99.3 4.13 40.4 3.26 36.0 95.0 6.7 4.23
900 53.3 4.05 39.5 124.9 3.86 43.2 3.80 40.7 114.4 10.5 4.13
6.0 1.8 4.2 1200 55.0 3.65 42.5 112.4 4.41 45.7 3.47 42.9 105.2 9.1 4.62
1500 56.7 3.64 44.3 105.0 4.57 47.5 3.49 43.8 99.3 8.3 4.68
900 55.9 4.17 41.7 127.5 3.93 45.9 3.92 42.9 117.2 10.4 4.21
70 9.0 3.3 7.6 1200 57.7 3.76 44.8 114.5 4.49 48.5 3.58 45.3 107.4 9.1 4.70
1500 59.5 3.75 46.7 106.7 4.65 50.3 3.60 46.2 101.0 8.2 4.76
900 57.3 4.21 43.0 129.0 3.99 47.4 3.96 44.3 118.7 10.4 4.28
12.0 5.3 12.2 1200 59.2 3.81 46.2 115.7 4.55 49.7 3.62 46.6 108.3 9.3 4.77
1500 61.1 3.79 48.1 107.7 4.72 51.9 3.64 47.7 102.0 8.2 4.84
900 62.6 4.69 46.6 134.4 3.91 49.6 4.30 47.7 121.0 12.8 4.25
6.0 1.7 3.9 1200 64.8 4.03 51.1 120.0 4.71 53.2 3.77 51.2 111.0 10.9 4.98
1500 67.0 3.95 53.5 111.4 4.97 55.3 3.74 52.4 104.2 9.8 5.10
900 66.3 4.88 49.7 138.3 3.99 53.5 4.48 50.9 125.0 12.7 4.33
90 9.0 3.3 7.6 1200 68.8 4.20 54.5 123.1 4.80 57.2 3.93 54.7 114.2 10.9 5.07
1500 71.1 4.11 57.1 113.9 5.07 59.4 3.90 55.9 106.7 9.8 5.19
900 68.3 4.92 51.5 140.3 4.07 55.6 4.52 52.8 127.2 12.7 4.42
12.0 5.2 12.0 1200 70.9 4.24 56.4 124.7 4.90 59.4 3.97 56.7 115.8 10.8 5.18
1500 73.3 4.16 59.1 115.3 5.17 61.7 3.95 57.9 108.1 9.7 5.30
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
46
E SERIES SPECIFICATION CATALOG
E048
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
900 49.5 30.2 2.42 57.8 20.5 51.0 29.9 2.40 54.9 4.3 21.3
6.0 1.9 4.4 1200 53.5 34.4 2.55 62.2 20.9 55.1 34.1 2.53 59.0 4.7 21.8
1500 56.3 38.2 2.69 65.4 20.9 58.0 37.9 2.66 62.1 4.9 21.8
900 50.1 30.7 2.26 57.9 22.2 51.6 30.7 2.24 55.4 3.9 23.1
50 9.0 3.5 8.1 1200 54.1 34.9 2.39 62.3 22.7 55.7 34.9 2.36 59.6 4.2 23.6
1500 57.0 38.8 2.51 65.5 22.7 58.7 38.8 2.49 62.7 4.5 23.6
900 50.6 30.7 2.18 58.1 23.2 52.2 31.0 2.16 56.0 3.5 24.1
12.0 5.6 12.9 1200 54.7 35.0 2.30 62.5 23.7 56.3 35.4 2.28 60.3 3.8 24.7
1500 57.5 38.9 2.42 65.8 23.7 59.3 39.3 2.40 63.5 4.0 24.7
900 46.4 28.9 2.93 56.4 15.8 47.6 28.7 2.90 50.9 6.6 16.4
6.0 1.8 4.2 1200 49.1 32.6 3.05 59.5 16.1 50.4 32.4 3.02 53.7 6.9 16.7
1500 51.3 36.2 3.16 62.1 16.2 52.6 36.0 3.13 56.0 7.3 16.8
900 47.4 29.2 2.80 57.0 17.0 48.6 29.4 2.77 52.0 6.0 17.6
70 9.0 3.3 7.6 1200 50.2 33.0 2.90 60.1 17.3 51.5 33.2 2.87 54.9 6.4 17.9
1500 52.4 36.6 3.01 62.7 17.4 53.7 36.8 2.98 57.3 6.7 18.0
900 47.9 29.4 2.72 57.2 17.6 49.1 29.8 2.69 52.8 5.5 18.2
12.0 5.3 12.2 1200 50.7 33.2 2.82 60.4 18.0 52.0 33.7 2.80 55.7 5.8 18.6
1500 53.0 36.9 2.93 63.0 18.1 54.3 37.4 2.90 58.1 6.1 18.7
900 41.8 27.1 3.46 53.6 12.1 42.6 27.1 3.42 45.3 9.0 12.4
6.0 1.7 3.9 1200 43.4 30.4 3.54 55.5 12.3 44.3 30.4 3.50 46.9 9.3 12.6
1500 45.0 33.7 3.62 57.3 12.4 45.9 33.7 3.58 48.5 9.6 12.8
900 43.1 27.4 3.36 54.5 12.8 43.9 27.7 3.32 47.0 8.3 13.2
90 9.0 3.3 7.6 1200 44.7 30.7 3.44 56.5 13.0 45.6 31.0 3.40 48.7 8.6 13.4
1500 46.4 34.0 3.51 58.4 13.2 47.3 34.4 3.48 50.3 8.9 13.6
900 43.5 27.7 3.29 54.7 13.2 44.4 28.2 3.26 47.9 7.6 13.6
12.0 5.2 12.0 1200 45.2 31.0 3.37 56.7 13.4 46.1 31.6 3.33 49.6 7.8 13.8
1500 46.8 34.4 3.44 58.6 13.6 47.8 35.1 3.41 51.3 8.1 14.0
900 37.1 25.4 3.98 50.7 9.3 37.7 25.5 3.94 39.6 11.5 9.6
6.0 1.6 3.7 1200 37.9 28.2 4.01 51.6 9.4 38.4 28.4 3.97 40.3 11.7 9.7
1500 38.9 31.3 4.04 52.7 9.6 39.5 31.4 4.00 41.2 12.0 9.9
900 38.7 25.6 3.94 52.1 9.8 39.2 26.0 3.90 41.9 10.6 10.0
110 9.0 3.0 6.9 1200 39.4 28.5 3.98 53.0 9.9 40.0 28.9 3.94 42.6 10.8 10.2
1500 40.5 31.5 4.01 54.2 10.1 41.1 32.0 3.97 43.6 11.1 10.4
900 39.0 26.0 3.90 52.3 10.0 39.6 26.6 3.86 43.0 9.8 10.3
12.0 4.8 11.1 1200 39.8 28.9 3.93 53.2 10.1 40.4 29.6 3.89 43.8 9.9 10.4
1500 40.9 32.0 3.96 54.5 10.3 41.6 32.8 3.92 44.8 10.2 10.6
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
47
E SERIES SPECIFICATION CATALOG
E048
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
600 14.5 1.33 9.9 92.6 3.18 11.8 1.31 10.2 88.9 2.9 3.28
3.0 1.4 3.2 800 15.0 1.34 10.5 89.0 3.28 12.5 1.33 10.7 86.2 2.8 3.37
1000 15.5 1.36 10.9 86.2 3.34 13.1 1.35 11.1 84.0 2.7 3.42
600 15.6 1.40 10.8 93.5 3.27 12.7 1.37 11.2 89.7 3.1 3.38
30 6.0 2.0 4.6 800 16.2 1.40 11.4 89.8 3.40 13.5 1.38 11.7 86.9 2.9 3.50
1000 16.7 1.41 11.9 86.9 3.47 14.2 1.40 12.2 84.6 2.8 3.55
600 16.0 1.42 11.2 93.8 3.31 13.1 1.39 11.5 89.8 3.2 3.43
9.0 3.7 8.5 800 16.6 1.41 11.8 90.0 3.45 13.8 1.39 12.1 87.0 3.0 3.54
1000 17.2 1.43 12.3 87.1 3.52 14.6 1.41 12.5 84.8 2.8 3.60
600 21.1 1.58 15.7 100.5 3.90 17.4 1.53 16.1 95.3 4.0 4.09
3.0 1.3 3.0 800 21.8 1.53 16.5 95.5 4.16 18.5 1.49 16.9 91.8 3.6 4.31
1000 22.5 1.53 17.3 91.9 4.31 19.5 1.51 17.5 89.2 3.1 4.41
600 22.8 1.64 17.2 101.8 4.07 18.8 1.58 17.7 96.5 4.3 4.29
50 6.0 1.9 4.4 800 23.5 1.58 18.2 96.6 4.38 20.0 1.53 18.5 92.8 3.8 4.55
1000 24.4 1.57 19.0 92.8 4.55 21.2 1.54 19.2 90.0 3.3 4.66
600 23.6 1.67 17.9 102.4 4.15 19.5 1.60 18.5 96.9 4.4 4.38
9.0 3.5 8.1 800 24.4 1.59 18.9 97.0 4.48 20.7 1.55 19.3 93.2 3.9 4.66
1000 25.2 1.59 19.8 93.2 4.66 22.0 1.55 20.0 90.4 3.4 4.77
600 27.4 1.82 21.2 108.1 4.42 22.7 1.73 21.9 101.4 5.0 4.71
3.0 1.2 2.8 800 28.2 1.70 22.4 101.6 4.86 24.1 1.64 22.8 97.0 4.3 5.08
1000 29.3 1.68 23.5 97.3 5.10 25.6 1.64 23.7 94.0 3.6 5.23
600 29.8 1.87 23.4 109.8 4.67 24.7 1.76 24.1 102.8 5.4 5.01
70 6.0 1.8 4.2 800 30.6 1.73 24.7 103.0 5.19 26.1 1.65 25.1 98.2 4.6 5.45
1000 31.8 1.70 26.0 98.6 5.49 27.8 1.65 26.0 95.2 3.8 5.63
600 31.1 1.90 24.6 110.9 4.79 25.9 1.79 25.4 103.7 5.6 5.16
9.0 3.3 7.6 800 32.0 1.75 26.0 103.9 5.36 27.3 1.67 26.4 98.9 4.8 5.63
1000 33.2 1.71 27.4 99.4 5.68 29.1 1.66 27.4 95.9 3.9 5.82
600 32.5 2.03 25.6 113.1 4.70 26.7 1.89 26.4 104.6 6.1 5.09
3.0 1.2 2.8 800 33.3 1.83 27.0 105.6 5.32 28.2 1.74 27.4 99.8 5.1 5.61
1000 34.6 1.79 28.5 100.9 5.68 30.2 1.73 28.4 97.0 4.1 5.82
600 35.4 2.07 28.4 115.1 5.02 29.1 1.91 29.2 106.2 6.6 5.49
90 6.0 1.7 3.9 800 36.2 1.84 29.9 107.2 5.77 30.7 1.73 30.3 101.1 5.5 6.12
1000 37.7 1.78 31.7 102.4 6.21 32.9 1.71 31.4 98.2 4.4 6.37
600 37.3 2.10 30.1 116.7 5.20 30.8 1.93 31.0 107.6 6.8 5.71
9.0 3.3 7.6 800 38.2 1.86 31.8 108.5 6.01 32.5 1.75 32.1 102.3 5.6 6.38
1000 39.8 1.80 33.7 103.6 6.49 34.8 1.73 33.3 99.3 4.5 6.66
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
48
E SERIES SPECIFICATION CATALOG
E048
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
600 30.3 18.5 1.20 34.4 25.3 30.6 18.5 1.19 33.4 1.2 25.8
3.0 1.3 3.0 800 32.2 20.1 1.19 36.3 27.1 32.6 20.1 1.18 35.3 1.3 27.7
1000 33.2 23.7 1.24 37.5 26.8 33.6 23.7 1.23 36.4 1.3 27.4
600 30.9 18.7 1.04 34.5 29.7 31.1 18.7 1.03 33.7 0.9 30.1
50 6.0 1.9 4.4 800 32.9 20.2 1.03 36.5 31.9 33.1 20.2 1.02 35.7 0.9 32.4
1000 33.9 23.8 1.08 37.6 31.6 34.1 23.8 1.07 36.8 1.0 32.0
600 31.1 18.7 0.98 34.4 31.6 31.1 18.7 0.97 33.9 0.5 32.0
9.0 3.5 8.1 800 33.1 20.2 0.97 36.4 34.0 33.1 20.2 0.96 35.8 0.6 34.3
1000 34.1 23.8 1.02 37.6 33.6 34.1 23.8 1.00 36.9 0.6 34.0
600 26.9 17.4 1.49 32.0 18.0 27.3 17.2 1.47 29.1 3.2 18.5
3.0 1.2 2.8 800 28.6 19.2 1.49 33.7 19.1 29.0 19.0 1.47 30.7 3.3 19.7
1000 29.5 22.6 1.56 34.8 18.9 29.9 22.4 1.53 31.7 3.5 19.5
600 27.2 17.5 1.35 31.8 20.1 27.4 17.5 1.34 29.3 2.7 20.5
70 6.0 1.8 4.2 800 28.9 19.4 1.35 33.5 21.4 29.2 19.3 1.33 30.9 2.9 21.9
1000 29.8 22.8 1.41 34.6 21.2 30.1 22.7 1.39 31.9 3.0 21.6
600 27.6 17.6 1.29 32.0 21.5 27.8 17.7 1.28 29.9 2.2 21.8
9.0 3.3 7.6 800 29.4 19.5 1.29 33.8 22.8 29.5 19.6 1.27 31.5 2.4 23.2
1000 30.3 22.9 1.34 34.9 22.6 30.5 23.0 1.33 32.5 2.5 22.9
600 23.6 15.8 1.73 29.5 13.7 24.1 15.5 1.69 24.7 5.2 14.2
3.0 1.2 2.8 800 25.1 17.8 1.74 31.0 14.4 25.6 17.4 1.71 26.0 5.4 15.0
1000 25.9 20.9 1.81 32.0 14.3 26.4 20.5 1.78 26.8 5.6 14.8
600 23.6 16.0 1.63 29.2 14.4 23.9 15.9 1.61 24.9 4.6 14.9
90 6.0 1.7 3.9 800 25.1 18.0 1.65 30.7 15.2 25.4 17.9 1.62 26.2 4.8 15.7
1000 25.8 21.2 1.71 31.7 15.1 26.2 21.1 1.69 27.0 5.0 15.5
600 24.3 16.2 1.57 29.7 15.5 24.6 16.3 1.55 25.9 4.0 15.8
9.0 3.3 7.6 800 25.8 18.2 1.58 31.2 16.3 26.1 18.4 1.57 27.3 4.2 16.7
1000 26.6 21.4 1.65 32.2 16.2 26.9 21.6 1.63 28.2 4.3 16.5
600 19.9 14.1 1.91 26.4 10.4 20.4 13.7 1.87 19.6 7.1 10.9
3.0 1.1 2.5 800 21.1 16.2 1.94 27.7 10.9 21.6 15.7 1.90 20.6 7.5 11.4
1000 21.7 19.0 2.02 28.7 10.7 22.3 18.5 1.97 21.3 7.8 11.3
600 19.6 14.4 1.90 26.1 10.4 20.0 14.3 1.86 20.0 6.4 10.7
110 6.0 1.6 3.7 800 20.8 16.4 1.93 27.4 10.8 21.3 16.3 1.89 21.0 6.7 11.2
1000 21.5 19.3 2.01 28.3 10.7 21.9 19.2 1.97 21.7 7.0 11.1
600 20.5 14.6 1.84 26.8 11.1 20.8 14.8 1.82 21.4 5.7 11.4
9.0 3.0 6.9 800 21.8 16.7 1.87 28.1 11.6 22.1 16.9 1.85 22.5 6.0 11.9
1000 22.4 19.6 1.95 29.1 11.5 22.8 19.9 1.93 23.2 6.2 11.8
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
49
E SERIES SPECIFICATION CATALOG
E058
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1800 44.9 3.79 32.0 93.1 3.47 40.2 3.72 32.4 90.7 4.8 3.55
8.0 2.1 4.9
2000 45.8 3.86 32.6 91.2 3.48 41.3 3.78 33.0 89.1 4.6 3.56
1800 45.3 3.83 32.3 93.3 3.47 40.4 3.75 32.6 90.8 5.0 3.54
30 11.0 3.1 7.2
2000 46.2 3.90 32.9 91.4 3.47 41.5 3.82 33.3 89.2 4.8 3.55
1800 46.7 3.93 33.3 94.0 3.48 41.7 3.85 33.7 91.5 5.1 3.56
14.0 5.5 12.7
2000 47.7 4.00 34.0 92.1 3.49 42.8 3.92 34.3 89.8 4.9 3.57
1800 58.3 4.17 44.1 100.0 4.10 51.9 4.08 44.2 96.7 6.2 4.18
8.0 2.0 4.6
2000 58.9 4.21 44.6 97.3 4.10 53.5 4.17 45.0 94.8 5.7 4.16
1800 59.0 4.16 44.8 100.3 4.16 52.2 4.07 44.8 96.9 6.5 4.22
50 11.0 2.9 6.7
2000 60.5 4.26 46.0 98.0 4.16 55.0 4.21 46.4 95.4 5.9 4.23
1800 60.4 4.24 46.0 101.1 4.18 53.5 4.16 46.0 97.5 6.6 4.24
14.0 4.6 10.6
2000 61.6 4.30 46.9 98.5 4.20 55.8 4.21 47.4 95.8 5.9 4.29
1800 70.6 4.51 55.2 106.3 4.59 62.2 4.42 54.8 102.0 7.7 4.64
8.0 2.0 4.4
2000 72.0 4.53 56.6 103.4 4.66 65.4 4.53 56.6 100.3 6.7 4.66
1800 73.1 4.55 57.5 107.6 4.70 64.3 4.46 57.1 103.1 8.0 4.75
70 11.0 2.8 6.5
2000 73.4 4.58 57.8 104.0 4.70 66.4 4.53 57.8 100.7 6.9 4.74
1800 74.5 4.62 58.7 108.3 4.72 65.5 4.53 58.2 103.7 8.2 4.76
14.0 4.4 10.2
2000 76.1 4.67 60.2 105.3 4.78 69.0 4.62 60.2 101.9 7.0 4.82
1800 83.6 4.84 67.1 113.0 5.06 73.1 4.74 66.1 107.6 9.2 5.08
8.0 1.9 4.4
2000 84.9 4.83 68.4 109.3 5.15 76.6 4.83 67.8 105.5 7.7 5.11
1800 88.0 4.95 71.1 115.3 5.21 77.0 4.85 69.9 109.6 9.5 5.22
90 11.0 2.7 6.2
2000 89.1 4.83 72.6 111.2 5.40 79.7 4.83 71.1 106.9 7.9 5.32
1800 89.2 5.00 72.1 115.9 5.23 77.8 4.90 70.8 110.0 9.7 5.23
14.0 4.2 9.7
2000 90.8 5.03 73.6 112.0 5.29 81.2 4.98 72.1 107.6 7.9 5.24
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
50
E SERIES SPECIFICATION CATALOG
E058
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1800 64.6 42.5 2.83 74.3 22.8 64.6 42.5 2.80 69.7 4.5 23.1
8.0 2.0 4.6
2000 64.8 44.2 3.17 75.7 20.5 64.8 44.2 3.14 70.9 4.6 20.7
1800 64.8 42.6 2.73 74.1 23.7 64.8 42.5 2.70 69.7 4.4 24.0
50 11.0 2.9 6.7
2000 64.8 44.6 3.11 75.5 20.9 64.8 44.6 3.08 70.8 4.5 21.1
1800 65.4 42.8 2.72 74.7 24.1 65.5 42.7 2.69 70.4 4.3 24.4
14.0 4.6 10.6
2000 65.5 44.6 2.96 75.6 22.1 65.5 44.6 2.93 71.1 4.4 22.4
1800 59.2 39.8 3.48 71.0 17.0 59.4 40.1 3.44 63.9 7.3 17.2
8.0 2.0 4.4
2000 61.8 43.3 3.75 74.6 16.5 61.8 43.7 3.71 67.0 7.5 16.7
1800 59.4 40.1 3.35 70.9 17.8 59.6 40.2 3.31 64.0 6.9 18.0
70 11.0 2.8 6.5
2000 62.4 43.3 3.61 74.7 17.3 62.4 43.3 3.57 67.5 7.1 17.5
1800 60.0 40.4 3.31 71.3 18.2 60.1 40.3 3.26 64.8 6.5 18.5
14.0 4.4 10.2
2000 62.4 43.7 3.50 74.3 17.8 62.4 43.7 3.47 69.4 6.7 18.0
1800 55.6 39.3 4.43 70.7 12.6 56.0 39.8 4.38 61.0 10.0 12.8
8.0 1.9 4.4
2000 56.1 41.4 4.69 72.1 12.0 56.6 41.8 4.64 62.2 10.3 12.2
1800 56.1 39.7 4.25 70.6 13.2 56.3 40.0 4.19 61.3 9.4 13.5
90 11.0 2.7 6.2
2000 56.6 41.4 4.43 71.7 12.8 56.6 41.8 4.34 61.8 9.6 13.0
1800 56.6 40.1 4.17 70.9 13.6 56.7 40.1 4.09 62.0 8.7 13.9
14.0 4.2 9.7
2000 57.2 41.8 4.30 71.9 13.3 57.2 41.8 4.21 62.7 8.9 13.6
1800 49.7 37.7 5.55 68.6 8.9 50.2 38.4 5.49 56.2 12.8 9.1
8.0 1.8 4.2
2000 50.2 39.2 5.61 69.3 8.9 51.2 39.6 5.61 57.2 13.2 9.1
1800 50.2 38.2 5.32 68.3 9.4 50.5 38.6 5.23 56.5 11.8 9.7
110 11.0 2.6 6.0
2000 50.7 39.8 5.37 69.0 9.4 50.7 40.6 5.21 56.3 12.2 9.7
1800 50.7 38.7 5.19 68.4 9.8 50.8 38.8 5.06 57.2 10.9 10.1
14.0 4.1 9.5
2000 51.2 40.3 5.24 69.1 9.8 51.4 40.4 5.11 57.6 11.2 10.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
51
E SERIES SPECIFICATION CATALOG
E058
Heating Capacity Data (2000 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 47.0 3.62 34.6 81.8 3.81 42.4 3.55 35.0 79.6 4.5 3.87
8.0 2.1 4.9 70 45.6 3.81 32.6 91.1 3.51 41.2 3.73 33.0 89.1 4.6 3.59
80 44.3 4.00 30.7 100.5 3.24 39.7 3.92 31.0 98.4 4.7 3.32
60 47.4 3.66 34.9 81.9 3.80 42.8 3.58 35.3 79.8 4.7 3.88
30 11.0 3.1 7.2 70 46.1 3.85 32.9 91.3 3.51 41.3 3.77 33.3 89.1 4.8 3.58
80 44.7 4.04 30.9 100.7 3.24 39.8 3.96 31.3 98.4 5.0 3.31
60 48.8 3.75 36.0 82.6 3.82 44.2 3.68 36.4 80.5 4.8 3.90
14.0 5.5 12.7 70 47.5 3.95 34.0 92.0 3.52 42.6 3.87 34.3 89.7 4.9 3.60
80 46.1 4.15 32.0 101.4 3.26 41.1 4.06 32.3 99.0 5.0 3.33
60 60.7 3.96 47.2 88.1 4.50 55.5 3.92 47.7 85.7 5.5 4.57
8.0 2.0 4.6 70 58.8 4.16 44.6 97.2 4.14 53.4 4.12 45.0 94.7 5.7 4.20
80 56.8 4.37 41.9 106.3 3.81 51.2 4.33 42.3 103.7 5.9 3.86
60 62.4 4.00 48.7 88.9 4.57 57.0 3.96 49.2 86.4 5.7 4.65
50 11.0 2.9 6.7 70 60.3 4.21 46.0 97.9 4.20 54.8 4.16 46.4 95.4 5.9 4.27
80 58.3 4.42 43.2 107.0 3.87 52.5 4.37 43.6 104.3 6.0 3.93
60 63.5 4.04 49.7 89.4 4.61 58.0 3.96 50.2 86.8 5.8 4.72
14.0 4.6 10.6 70 61.4 4.25 46.9 98.4 4.23 55.6 4.16 47.4 95.8 5.9 4.33
80 59.3 4.46 44.1 107.5 3.90 53.3 4.37 44.5 104.7 6.1 3.99
60 74.5 4.26 60.0 94.5 5.13 68.0 4.26 60.0 91.5 6.5 5.13
8.0 2.0 4.4 70 71.9 4.48 56.6 103.3 4.70 65.2 4.48 56.6 100.2 6.7 4.70
80 69.2 4.70 53.2 112.1 4.31 62.4 4.70 53.2 108.9 6.9 4.31
60 75.9 4.30 61.3 95.2 5.18 69.1 4.26 61.3 92.0 6.7 5.22
70 11.0 2.8 6.5 70 73.2 4.53 57.8 103.9 4.74 66.2 4.48 57.8 100.7 6.9 4.78
80 70.5 4.75 54.3 112.7 4.35 63.3 4.70 54.3 109.3 7.1 4.38
60 78.8 4.39 63.8 96.5 5.26 71.9 4.34 63.8 93.3 6.8 5.31
14.0 4.4 10.2 70 76.0 4.62 60.2 105.2 4.82 68.8 4.57 60.2 101.9 7.0 4.86
80 73.1 4.85 56.6 113.9 4.42 65.8 4.80 56.6 110.4 7.2 4.45
60 88.1 4.54 72.6 100.8 5.68 79.9 4.54 71.8 97.0 7.4 5.64
8.0 1.9 4.4 70 84.8 4.78 68.4 109.2 5.20 76.4 4.78 67.8 105.4 7.7 5.16
80 81.5 5.02 64.3 117.7 4.76 72.9 5.02 63.7 113.8 7.9 4.72
60 92.4 4.54 76.9 102.8 5.97 83.2 4.54 75.4 98.5 7.7 5.87
90 11.0 2.7 6.2 70 88.9 4.78 72.6 111.1 5.45 79.5 4.78 71.1 106.8 7.9 5.36
80 85.3 5.02 68.2 119.5 4.98 75.8 5.02 66.9 115.1 8.1 4.91
60 94.2 4.73 78.0 103.6 5.83 84.7 4.68 76.5 99.2 7.7 5.79
14.0 4.2 9.7 70 90.6 4.98 73.6 111.9 5.33 81.0 4.93 72.1 107.5 7.9 5.29
80 87.0 5.23 69.2 120.3 4.88 77.3 5.18 67.8 115.8 8.2 4.84
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
52
E SERIES SPECIFICATION CATALOG
E058
Cooling Capacity Data (2000 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 59.7 42.4 3.05 71.0 19.5 59.7 42.4 3.02 70.9 4.5 19.7
8.0 2.0 4.6 80/67 64.9 44.2 3.12 75.5 20.8 64.9 44.2 3.09 75.4 4.6 21.0
85/71 70.1 45.9 3.18 80.1 22.0 70.1 45.9 3.15 79.9 4.7 22.3
75/63 59.7 42.8 3.00 70.8 19.9 59.7 42.8 2.97 70.7 4.4 20.1
50 11.0 2.9 6.7 80/67 64.9 44.6 3.06 75.3 21.2 64.9 44.6 3.03 75.2 4.5 21.4
85/71 70.1 46.4 3.12 79.8 22.5 70.1 46.4 3.09 79.7 4.6 22.7
75/63 60.3 42.8 2.85 71.0 21.1 60.3 42.8 2.82 70.9 4.3 21.4
14.0 4.6 10.6 80/67 65.6 44.6 2.91 75.5 22.5 65.6 44.6 2.88 75.4 4.4 22.8
85/71 70.8 46.4 2.97 80.0 23.9 70.8 46.4 2.94 79.9 4.5 24.1
75/63 56.9 41.5 3.62 70.0 15.7 56.9 41.9 3.58 69.8 7.2 15.9
8.0 2.0 4.4 80/67 61.8 43.3 3.70 74.4 16.7 61.8 43.7 3.66 74.3 7.5 16.9
85/71 66.8 45.0 3.77 78.9 17.7 66.8 45.4 3.73 78.8 7.7 17.9
75/63 57.5 41.5 3.48 70.1 16.5 57.5 41.5 3.45 70.0 6.8 16.7
70 11.0 2.8 6.5 80/67 62.5 43.3 3.56 74.6 17.6 62.5 43.3 3.52 74.5 7.1 17.7
85/71 67.4 45.0 3.63 79.1 18.6 67.4 45.0 3.59 78.9 7.3 18.8
75/63 57.5 42.0 3.38 69.8 17.0 57.5 42.0 3.35 69.7 6.5 17.2
14.0 4.4 10.2 80/67 62.5 43.7 3.45 74.2 18.1 62.5 43.7 3.42 74.1 6.7 18.3
85/71 67.4 45.4 3.52 78.7 19.2 67.4 45.4 3.48 78.5 6.9 19.4
75/63 51.6 39.7 4.54 67.6 11.4 52.1 40.1 4.50 68.0 10.0 11.6
8.0 1.9 4.4 80/67 56.1 41.4 4.64 71.9 12.1 56.7 41.8 4.59 72.3 10.3 12.3
85/71 60.6 43.0 4.73 76.2 12.8 61.2 43.5 4.68 76.7 10.6 13.1
75/63 52.1 39.7 4.29 67.3 12.2 52.1 40.1 4.20 67.0 9.3 12.4
90 11.0 2.7 6.2 80/67 56.7 41.4 4.38 71.6 12.9 56.7 41.8 4.29 71.3 9.6 13.2
85/71 61.2 43.0 4.47 75.9 13.7 61.2 43.5 4.38 75.6 9.9 14.0
75/63 52.7 40.1 4.17 67.4 12.6 52.7 40.1 4.08 67.2 8.6 12.9
14.0 4.2 6.2 80/67 57.3 41.8 4.25 71.8 13.5 57.3 41.8 4.16 71.5 8.9 13.7
85/71 61.8 43.5 4.34 76.1 14.3 61.8 43.5 4.25 75.7 9.2 14.6
75/63 46.2 37.7 5.45 65.0 8.5 47.1 38.0 5.45 66.0 12.8 8.7
8.0 1.8 4.2 80/67 50.2 39.2 5.56 69.2 9.0 51.2 39.6 5.56 70.2 13.2 9.2
85/71 54.2 40.8 5.67 73.3 9.6 55.3 41.2 5.67 74.4 13.5 9.8
75/63 46.7 38.2 5.22 64.8 8.9 46.7 39.0 5.06 64.3 11.8 9.2
110 11.0 2.6 6.0 80/67 50.7 39.8 5.32 68.9 9.5 50.7 40.6 5.16 68.4 12.2 9.8
85/71 54.8 41.4 5.43 73.0 10.1 54.8 42.2 5.27 72.5 12.5 10.4
75/63 47.2 38.7 5.09 64.8 9.3 47.3 38.8 4.96 64.5 10.8 9.5
14.0 4.1 9.5 80/67 51.3 40.3 5.19 69.0 9.9 51.4 40.4 5.06 68.7 11.2 10.2
85/71 55.4 41.9 5.29 73.1 10.5 55.5 42.0 5.16 72.8 11.5 10.8
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
53
E SERIES SPECIFICATION CATALOG
E060
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1000 29.2 2.99 19.0 97.0 2.86 21.8 2.94 19.4 90.2 7.7 2.93
8.0 2.1 4.9 1700 34.1 3.09 23.5 88.6 3.23 27.2 3.03 23.9 84.8 7.1 3.31
2000 34.9 3.25 23.8 86.2 3.15 28.3 3.19 24.1 83.1 6.7 3.21
1000 31.1 2.98 20.9 98.8 3.05 23.5 2.93 21.3 91.8 7.8 3.13
30 11.0 3.1 7.0 1700 36.5 3.12 25.9 89.9 3.43 29.5 3.06 26.3 86.0 7.3 3.52
2000 37.5 3.32 26.2 87.4 3.31 30.8 3.25 26.5 84.2 6.8 3.38
1000 31.1 2.91 21.1 98.8 3.12 23.4 2.86 21.6 91.7 7.9 3.21
14.0 4.8 11.0 1700 37.0 3.20 26.1 90.2 3.40 29.8 3.13 26.5 86.2 7.4 3.48
2000 37.9 3.35 26.5 87.5 3.31 31.0 3.28 26.7 84.4 6.9 3.38
1000 44.4 3.43 32.7 111.1 3.80 34.1 3.27 32.9 101.5 10.0 3.95
8.0 2.0 4.7 1700 51.7 3.58 39.4 98.1 4.23 42.3 3.45 39.6 93.0 9.1 4.36
2000 52.8 3.69 40.2 94.4 4.19 44.1 3.58 40.1 90.4 8.2 4.28
1000 47.1 3.51 35.1 113.6 3.93 36.4 3.34 35.3 103.7 10.3 4.10
50 11.0 2.9 6.7 1700 54.7 3.65 42.2 99.8 4.39 44.9 3.51 42.3 94.5 9.3 4.53
2000 55.8 3.74 43.0 95.8 4.37 46.8 3.63 42.9 91.7 8.4 4.46
1000 48.0 3.56 35.9 114.5 3.95 37.1 3.38 36.0 104.3 10.5 4.12
14.0 4.6 10.6 1700 55.6 3.69 43.0 100.3 4.42 45.6 3.55 43.0 94.8 9.5 4.56
2000 56.8 3.78 43.9 96.3 4.40 47.6 3.67 43.7 92.1 8.6 4.49
1000 60.3 4.21 45.9 125.8 4.20 46.5 3.90 45.6 113.0 12.5 4.42
8.0 2.0 4.5 1700 68.2 4.20 53.9 107.2 4.76 55.8 3.97 53.3 100.4 11.1 4.94
2000 69.7 4.22 55.3 102.3 4.84 58.6 4.07 54.5 97.1 9.8 4.92
1000 62.7 4.30 48.0 128.1 4.27 48.3 3.97 47.6 114.7 12.9 4.52
70 11.0 2.8 6.4 1700 70.7 4.26 56.1 108.5 4.86 57.6 4.01 55.4 101.4 11.5 5.05
2000 72.3 4.27 57.7 103.5 4.96 60.5 4.10 56.6 98.0 10.1 5.05
1000 64.5 4.37 49.6 129.8 4.33 49.8 4.02 49.1 116.1 13.1 4.58
14.0 4.4 10.1 1700 72.5 4.31 57.8 109.5 4.93 59.1 4.05 56.9 102.2 11.7 5.12
2000 74.2 4.31 59.5 104.4 5.04 62.1 4.14 58.3 98.8 10.3 5.13
1000 75.8 4.94 58.9 140.1 4.49 58.0 4.45 57.7 123.7 14.9 4.80
8.0 1.9 4.3 1700 83.4 4.72 67.3 115.4 5.18 67.4 4.37 65.6 106.7 13.1 5.39
2000 85.4 4.65 69.6 109.6 5.38 71.3 4.43 67.5 103.0 11.4 5.46
1000 77.3 5.04 60.1 141.6 4.49 58.6 4.50 58.7 124.3 15.4 4.82
90 11.0 2.7 6.1 1700 84.5 4.77 68.2 116.0 5.19 67.6 4.40 66.2 106.8 13.6 5.41
2000 86.6 4.67 70.7 110.1 5.43 71.7 4.44 68.3 103.2 11.8 5.50
1000 80.2 5.13 62.7 144.3 4.58 61.0 4.56 61.1 126.5 15.7 4.93
14.0 4.2 9.6 1700 87.4 4.83 70.9 117.6 5.30 70.1 4.44 68.8 108.2 13.9 5.54
2000 89.7 4.72 73.6 111.5 5.57 74.3 4.48 71.0 104.4 12.0 5.64
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
54
E SERIES SPECIFICATION CATALOG
E060
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1000 61.0 34.1 2.73 70.3 22.4 61.6 33.8 2.70 64.0 6.9 22.8
8.0 2.0 4.7 1700 68.8 43.6 2.98 78.9 23.1 69.4 43.1 2.95 71.8 7.7 23.5
2000 70.2 47.4 3.17 81.0 22.1 70.9 46.9 3.14 73.7 7.9 22.6
1000 61.7 34.5 2.67 70.8 23.1 62.0 34.3 2.64 64.3 6.7 23.5
50 11.0 2.9 6.7 1700 69.5 44.0 2.92 79.4 23.8 69.8 43.8 2.89 72.1 7.5 24.2
2000 70.9 47.9 3.10 81.5 22.8 71.2 47.6 3.07 74.0 7.7 23.2
1000 62.3 34.8 2.62 71.2 23.7 62.3 34.8 2.60 64.6 6.5 24.0
14.0 4.6 10.6 1700 70.2 44.5 2.87 79.9 24.5 70.2 44.5 2.84 72.5 7.3 24.7
2000 71.6 48.3 3.05 82.0 23.5 71.6 48.3 3.02 74.4 7.5 23.7
1000 54.8 32.5 3.26 65.9 16.8 55.4 32.5 3.21 57.4 8.9 17.3
8.0 2.0 4.5 1700 61.2 41.6 3.56 73.3 17.2 61.8 41.6 3.51 63.9 9.9 17.6
2000 63.1 45.2 3.79 76.1 16.6 63.8 45.2 3.74 66.3 10.3 17.1
1000 55.4 32.8 3.19 66.3 17.4 55.7 32.8 3.15 57.8 8.6 17.7
70 11.0 2.8 6.4 1700 61.8 42.0 3.49 73.7 17.7 62.1 42.0 3.44 64.3 9.6 18.0
2000 63.8 45.6 3.71 76.4 17.2 64.1 45.6 3.67 66.7 9.9 17.5
1000 55.9 33.1 3.13 66.6 17.9 55.9 33.1 3.10 58.2 8.3 18.0
14.0 4.4 10.1 1700 62.4 42.4 3.43 74.1 18.2 62.4 42.4 3.39 64.8 9.3 18.4
2000 64.4 46.1 3.65 76.9 17.6 64.4 46.1 3.61 67.1 9.6 17.8
1000 47.1 29.9 3.77 60.0 12.5 47.6 30.2 3.69 49.3 10.9 12.9
8.0 1.9 4.3 1700 51.9 38.3 4.12 66.0 12.6 52.5 38.6 4.04 54.2 12.0 13.0
2000 54.2 41.6 4.39 69.2 12.3 54.7 42.0 4.31 56.8 12.6 12.7
1000 47.6 30.2 3.69 60.2 12.9 47.9 30.4 3.63 49.7 10.5 13.2
90 11.0 2.7 6.1 1700 52.5 38.6 4.04 66.3 13.0 52.7 38.8 3.98 54.7 11.6 13.3
2000 54.7 42.0 4.30 69.4 12.7 55.0 42.2 4.24 57.3 12.2 13.0
1000 47.9 30.4 3.63 60.3 13.2 47.9 30.4 3.59 50.1 10.1 13.4
14.0 4.2 9.6 1700 53.0 39.1 3.97 66.6 13.4 53.0 39.1 3.93 55.2 11.2 13.5
2000 55.3 42.4 4.23 69.7 13.1 55.3 42.4 4.19 57.9 11.7 13.2
1000 38.6 30.6 4.20 52.9 9.2 39.0 31.2 4.09 40.1 12.9 9.5
8.0 1.8 4.1 1700 42.3 39.4 4.60 58.0 9.2 42.7 40.2 4.48 43.9 14.1 9.5
2000 44.6 42.8 4.90 61.4 9.1 45.1 43.7 4.78 46.4 15.0 9.4
1000 39.0 30.9 4.11 53.0 9.5 39.2 31.2 4.04 40.6 12.4 9.7
110 11.0 2.6 5.9 1700 42.8 39.8 4.50 58.1 9.5 43.0 40.2 4.42 44.5 13.6 9.7
2000 45.1 43.2 4.80 61.5 9.4 45.3 43.7 4.72 47.0 14.4 9.6
1000 39.4 31.2 4.04 53.2 9.8 39.4 31.2 4.00 41.2 11.9 9.9
14.0 3.9 9.0 1700 43.2 40.2 4.42 58.3 9.8 43.2 40.2 4.38 45.1 13.0 9.9
2000 45.5 43.7 4.72 61.7 9.6 45.5 43.7 4.67 47.7 13.8 9.7
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
55
E SERIES SPECIFICATION CATALOG
E060
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
700 16.2 1.50 11.0 91.4 3.16 12.8 1.49 11.5 86.9 3.8 3.27
5.0 1.1 2.5 900 16.9 1.52 11.7 87.4 3.27 13.6 1.50 12.0 84.0 3.5 3.34
1100 17.5 1.54 12.3 84.7 3.34 14.3 1.52 12.4 82.0 3.3 3.39
700 16.1 1.53 10.8 91.2 3.08 12.5 1.51 11.3 86.5 3.9 3.19
30 8.0 2.1 4.9 900 16.8 1.54 11.5 87.3 3.18 13.4 1.53 11.8 83.7 3.7 3.26
1100 17.4 1.56 12.0 84.6 3.26 14.1 1.54 12.2 81.8 3.4 3.31
700 16.7 1.53 11.5 92.1 3.20 13.1 1.51 11.9 87.3 4.0 3.31
11.0 3.1 7.0 900 17.4 1.54 12.2 87.9 3.31 14.0 1.53 12.5 84.4 3.7 3.39
1100 18.0 1.56 12.7 85.2 3.39 14.7 1.54 12.8 82.4 3.4 3.44
700 24.7 1.63 19.2 102.7 4.45 19.9 1.58 19.8 96.4 5.3 4.68
5.0 1.0 2.3 900 25.9 1.62 20.4 96.6 4.67 21.6 1.59 20.8 92.2 4.6 4.84
1100 26.6 1.62 21.1 92.4 4.81 22.6 1.59 21.1 89.0 3.9 4.88
700 25.1 1.66 19.4 103.2 4.43 20.0 1.60 20.1 96.5 5.5 4.67
50 8.0 2.0 4.6 900 26.3 1.65 20.6 97.0 4.67 21.7 1.61 21.0 92.3 4.8 4.83
1100 26.9 1.64 21.3 92.6 4.80 22.7 1.61 21.3 89.1 4.1 4.88
700 25.9 1.67 20.2 104.2 4.54 20.7 1.61 20.9 97.4 5.7 4.79
11.0 2.9 6.7 900 27.1 1.66 21.4 97.9 4.79 22.4 1.61 21.8 93.1 4.9 4.96
1100 27.7 1.65 22.1 93.3 4.92 23.5 1.62 22.1 89.8 4.1 5.00
700 33.6 1.82 27.4 114.4 5.42 27.3 1.72 28.3 106.2 6.8 5.81
5.0 0.9 2.2 900 35.2 1.78 29.2 106.3 5.79 29.7 1.71 29.5 100.6 5.7 6.05
1100 35.8 1.75 29.8 100.1 5.98 30.9 1.71 29.6 96.0 4.6 6.08
700 34.9 1.85 28.6 116.2 5.54 28.3 1.74 29.5 107.4 7.1 5.97
70 8.0 2.0 4.6 900 36.7 1.81 30.5 107.7 5.95 30.8 1.73 30.8 101.7 5.9 6.23
1100 37.1 1.77 31.1 101.2 6.13 31.9 1.72 30.8 96.9 4.7 6.24
700 35.6 1.87 29.3 117.1 5.58 28.8 1.76 30.1 108.1 7.3 6.02
11.0 2.8 6.4 900 37.4 1.83 31.2 108.5 6.00 31.4 1.75 31.5 102.3 6.1 6.28
1100 37.8 1.79 31.7 101.8 6.19 32.5 1.74 31.4 97.4 4.8 6.29
700 41.0 1.97 34.3 124.3 6.10 33.1 1.82 35.2 113.8 8.3 6.67
5.0 0.9 2.1 900 43.1 1.90 36.6 114.3 6.63 36.2 1.80 36.8 107.2 6.8 6.99
1100 43.2 1.85 36.9 106.4 6.85 37.2 1.78 36.3 101.3 5.2 6.97
700 43.8 2.00 37.0 128.0 6.42 35.5 1.84 37.9 116.9 8.7 7.06
90 8.0 1.9 4.4 900 46.0 1.93 39.5 117.4 7.00 38.7 1.81 39.6 109.8 7.1 7.41
1100 46.0 1.86 39.7 108.7 7.24 39.6 1.79 38.9 103.4 5.4 7.37
700 44.1 2.04 37.2 128.4 6.34 35.5 1.86 38.1 116.9 9.0 6.99
11.0 2.7 6.1 900 46.3 1.96 39.7 117.7 6.93 38.8 1.84 39.8 109.9 7.2 7.34
1100 46.2 1.89 39.8 108.9 7.17 39.7 1.81 39.0 103.4 5.5 7.30
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
56
E SERIES SPECIFICATION CATALOG
E060
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
700 35.3 20.6 1.07 38.9 32.8 35.6 20.8 1.06 37.2 2.0 33.5
5.0 1.0 2.3 900 37.6 23.6 1.10 41.3 34.2 38.0 23.8 1.09 39.5 2.1 34.9
1100 38.7 26.8 1.16 42.7 33.5 39.1 27.0 1.14 40.8 2.2 34.2
700 35.3 20.8 1.03 38.9 34.2 35.7 21.0 1.02 37.3 1.8 34.9
50 8.0 2.0 4.6 900 37.7 23.8 1.06 41.3 35.6 38.0 24.0 1.05 39.7 1.9 36.4
1100 38.8 27.0 1.11 42.6 34.9 39.2 27.3 1.10 41.0 2.0 35.6
700 35.4 20.8 1.01 38.9 35.0 35.8 21.0 1.00 37.6 1.6 35.7
11.0 2.9 6.7 900 37.8 23.8 1.04 41.3 36.5 38.1 24.0 1.03 39.9 1.7 37.2
1100 38.9 27.0 1.09 42.7 35.7 39.3 27.3 1.08 41.2 1.8 36.4
700 30.8 19.9 1.41 35.6 21.9 31.6 19.7 1.39 32.2 4.1 22.7
5.0 0.9 2.2 900 32.3 22.3 1.43 37.2 22.6 33.1 22.1 1.41 33.6 4.3 23.4
1100 33.3 25.0 1.49 38.4 22.4 34.1 24.8 1.47 34.7 4.5 23.1
700 31.0 20.1 1.36 35.6 22.7 31.6 20.2 1.35 32.4 3.8 23.4
70 8.0 2.0 4.6 900 32.5 22.5 1.39 37.2 23.4 33.1 22.6 1.37 33.8 4.0 24.1
1100 33.5 25.3 1.45 38.4 23.2 34.2 25.4 1.43 34.9 4.1 23.9
700 31.2 20.2 1.34 35.7 23.3 31.6 20.5 1.33 32.6 3.5 23.9
11.0 2.8 6.4 900 32.7 22.6 1.36 37.3 24.0 33.2 23.0 1.35 34.1 3.7 24.6
1100 33.7 25.4 1.42 38.5 23.7 34.2 25.8 1.41 35.2 3.8 24.3
700 26.2 19.0 1.74 32.1 15.1 27.2 18.4 1.72 26.8 6.3 15.8
5.0 0.9 2.1 900 27.0 20.8 1.76 33.0 15.3 28.1 20.2 1.74 27.5 6.5 16.1
1100 27.8 23.1 1.81 34.0 15.3 28.9 22.4 1.80 28.4 6.7 16.1
700 26.4 19.2 1.70 32.2 15.5 27.2 19.1 1.69 27.1 5.9 16.2
90 8.0 1.9 4.4 900 27.3 21.0 1.72 33.2 15.8 28.1 20.9 1.71 27.9 6.1 16.5
1100 28.1 23.4 1.78 34.2 15.8 29.0 23.2 1.76 28.7 6.3 16.5
700 26.7 19.4 1.68 32.4 15.9 27.2 19.8 1.66 27.4 5.5 16.4
11.0 2.7 6.1 900 27.5 21.2 1.70 33.3 16.2 28.1 21.7 1.68 28.2 5.6 16.7
1100 28.4 23.6 1.75 34.4 16.2 29.0 24.1 1.73 29.1 5.8 16.7
700 21.7 17.8 2.02 28.6 10.7 22.9 16.9 2.00 21.1 8.6 11.4
5.0 0.9 2.0 900 22.0 19.2 2.04 29.0 10.8 23.2 18.2 2.02 21.4 8.7 11.5
1100 22.7 21.1 2.08 29.8 10.9 23.9 20.0 2.06 22.0 9.0 11.6
700 22.0 18.0 2.00 28.8 11.0 22.9 17.8 1.98 21.6 8.0 11.5
110 8.0 1.8 4.2 900 22.3 19.4 2.02 29.2 11.1 23.2 19.1 2.00 21.9 8.1 11.6
1100 23.0 21.3 2.06 30.0 11.2 23.9 21.0 2.04 22.5 8.4 11.7
700 22.3 18.3 1.97 29.0 11.3 22.8 18.8 1.95 22.0 7.5 11.7
11.0 2.6 5.9 900 22.6 19.7 1.99 29.4 11.4 23.2 20.2 1.97 22.3 7.6 11.8
1100 23.3 21.6 2.03 30.3 11.5 23.9 22.2 2.01 23.0 7.8 11.9
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
57
E SERIES SPECIFICATION CATALOG
E066
Heating Capacity Data
ECM Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1700 52.3 4.90 35.6 98.5 3.13 46.4 4.74 35.5 95.3 5.3 3.19
10.0 2.7 6.2
2200 53.6 5.01 36.5 92.6 3.13 48.3 4.95 36.5 90.3 5.1 3.16
1700 52.6 4.91 35.9 98.7 3.14 46.3 4.74 35.7 95.2 5.5 3.21
30 13.0 4.3 9.9
2200 53.9 5.01 36.8 92.7 3.15 48.4 4.94 36.8 90.4 5.3 3.18
1700 52.8 4.93 36.0 98.8 3.14 46.4 4.76 35.8 95.2 5.7 3.21
16.0 6.1 14.1
2200 54.1 5.03 36.9 92.8 3.15 48.5 4.95 37.0 90.4 5.4 3.19
1700 67.0 5.31 48.9 106.5 3.70 57.6 5.05 48.5 101.4 8.1 3.82
10.0 2.6 6.0
2200 68.6 5.33 50.4 98.9 3.77 61.2 5.19 50.5 95.8 7.1 3.85
1700 68.3 5.36 50.1 107.2 3.74 58.5 5.08 49.6 101.9 8.5 3.86
50 13.0 4.1 9.5
2200 70.0 5.37 51.7 99.5 3.82 62.3 5.23 51.8 96.2 7.3 3.91
1700 68.9 5.40 50.5 107.6 3.74 58.8 5.11 50.1 102.0 8.7 3.87
16.0 5.8 13.4
2200 70.7 5.40 52.2 99.7 3.84 62.8 5.25 52.4 96.4 7.5 3.92
1700 81.6 5.89 61.5 114.4 4.06 68.5 5.50 60.7 107.3 11.0 4.24
10.0 2.4 5.5
2200 83.7 5.80 63.9 105.2 4.23 74.1 5.58 64.1 101.2 9.1 4.36
1700 84.5 5.99 64.1 116.0 4.13 70.9 5.58 63.3 108.6 11.4 4.32
70 13.0 3.8 8.8
2200 86.8 5.89 66.7 106.5 4.31 76.9 5.66 66.9 102.4 9.4 4.47
1700 85.7 6.05 65.1 116.7 4.15 71.7 5.62 64.2 109.1 11.7 4.35
16.0 5.4 12.5
2200 88.0 5.94 67.8 107.0 4.35 77.9 5.69 68.0 102.8 9.6 4.50
1700 94.0 6.39 72.2 121.2 4.31 77.1 5.85 71.0 112.0 13.9 4.56
10.0 2.3 5.3
2200 96.8 6.18 75.7 110.7 4.59 85.0 5.87 76.0 105.8 11.1 4.80
1700 99.0 6.56 76.6 123.9 4.42 81.4 5.99 75.4 114.4 14.4 4.69
90 13.0 3.6 8.3
2200 102.0 6.33 80.4 112.9 4.72 89.9 5.99 80.8 107.8 11.4 4.95
1700 100.7 6.63 78.1 124.9 4.45 82.7 6.04 76.7 115.0 14.7 4.72
16.0 5.1 11.8
2200 104.0 6.38 82.2 113.8 4.77 91.6 6.04 82.6 108.6 11.7 5.01
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
58
E SERIES SPECIFICATION CATALOG
E066
Cooling Capacity Data
ECM Motor
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1700 69.3 43.4 3.18 80.1 21.8 69.9 43.6 3.16 75.3 5.5 22.1
10.0 2.6 6.0
2200 73.2 49.7 3.62 85.6 20.2 73.9 49.8 3.60 80.4 5.8 20.5
1700 69.6 43.7 3.08 80.1 22.6 70.1 43.7 3.05 75.7 4.9 23.0
50 13.0 4.1 9.5
2200 73.6 49.9 3.51 85.6 21.0 74.1 50.0 3.47 80.8 5.2 21.3
1700 70.3 43.9 3.05 80.7 23.0 70.7 43.9 3.00 76.6 4.3 23.5
16.0 5.8 13.4
2200 74.3 50.2 3.47 86.2 21.4 74.7 50.2 3.42 81.8 4.6 21.8
1700 64.8 40.8 3.88 78.0 16.7 65.4 41.1 3.82 70.4 8.1 17.1
10.0 2.4 5.5
2200 67.9 46.7 4.32 82.7 15.7 68.6 47.0 4.25 74.5 8.6 16.1
1700 65.0 40.9 3.77 77.9 17.3 65.5 41.1 3.71 70.7 7.5 17.6
70 13.0 3.8 8.8
2200 68.2 46.8 4.20 82.5 16.3 68.7 47.0 4.13 74.9 7.9 16.6
1700 66.0 41.8 3.71 78.7 17.8 66.3 41.9 3.65 71.9 6.9 18.2
16.0 5.4 12.5
2200 69.2 47.8 4.13 83.3 16.8 69.5 48.0 4.07 76.1 7.3 17.1
1700 59.3 38.3 4.86 75.8 12.2 59.9 38.7 4.73 65.2 10.8 12.6
10.0 2.3 5.3
2200 61.6 43.9 5.28 79.7 11.7 62.3 44.4 5.15 68.5 11.4 12.1
1700 59.4 38.2 4.73 75.5 12.6 59.8 38.6 4.63 65.5 10.2 12.9
90 13.0 3.6 8.3
2200 61.8 43.8 5.14 79.4 12.0 62.2 44.2 5.04 68.8 10.7 12.3
1700 60.6 39.8 4.62 76.3 13.1 60.8 40.1 4.55 66.8 9.5 13.4
16.0 5.1 11.8
2200 63.0 45.6 5.02 80.2 12.5 63.3 45.9 4.95 70.2 10.0 12.8
1700 52.2 35.1 6.13 73.1 8.5 52.7 35.5 5.92 59.3 13.6 8.9
10.0 2.2 5.1
2200 53.9 40.2 6.53 76.2 8.2 54.4 40.8 6.30 61.8 14.1 8.6
1700 52.3 34.9 5.98 72.7 8.7 52.6 35.3 5.84 59.6 12.9 9.0
110 13.0 3.4 7.9
2200 53.9 40.0 6.37 75.7 8.5 54.3 40.5 6.21 62.1 13.4 8.7
1700 53.6 36.9 5.80 73.4 9.2 53.7 37.3 5.72 61.0 12.3 9.4
16.0 4.8 11.1
2200 55.3 42.4 6.18 76.4 8.9 55.5 42.8 6.09 63.5 12.8 9.1
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
59
E SERIES SPECIFICATION CATALOG
E066
Heating Capacity Data (2200 CFM)
PSC Motor
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT EA HC KW HE LAT COP HC KW HE LAT HW COP
60 55.4 4.81 38.7 83.3 3.37 49.9 4.75 38.7 81.0 4.9 3.39
10.0 2.7 6.2 70 53.8 5.06 36.5 92.6 3.11 48.5 5.00 36.5 90.4 5.1 3.14
80 52.2 5.32 34.3 102.0 2.88 47.0 5.25 34.3 99.8 5.3 2.92
60 55.4 4.81 39.0 83.3 3.38 50.1 4.74 39.0 81.1 5.1 3.41
30 13.0 4.3 9.9 70 54.0 5.06 36.8 92.7 3.13 48.6 4.99 36.8 90.4 5.3 3.16
80 52.7 5.32 34.6 102.2 2.91 47.0 5.24 34.6 99.8 5.4 2.93
60 55.6 4.82 39.1 83.4 3.38 50.2 4.75 39.2 81.1 5.2 3.42
16.0 6.1 14.1 70 54.3 5.08 36.9 92.8 3.13 48.6 5.00 37.0 90.5 5.4 3.17
80 52.9 5.33 34.7 102.3 2.91 47.1 5.25 34.7 99.8 5.6 2.94
60 70.9 5.11 53.5 89.8 4.07 63.7 4.98 53.6 86.8 6.9 4.15
10.0 2.6 6.0 70 68.8 5.38 50.4 99.0 3.75 61.4 5.24 50.5 95.8 7.1 3.82
80 66.7 5.65 47.4 108.1 3.46 59.0 5.51 47.5 104.8 7.3 3.53
60 72.4 5.15 54.8 90.5 4.12 64.9 5.01 54.9 87.3 7.1 4.21
50 13.0 4.1 9.5 70 70.2 5.42 51.7 99.5 3.80 62.5 5.28 51.8 96.3 7.3 3.88
80 68.0 5.69 48.6 108.6 3.50 60.1 5.54 48.7 105.3 7.5 3.58
60 73.0 5.18 55.4 90.7 4.14 65.4 5.03 55.5 87.5 7.3 4.23
16.0 5.8 13.4 70 70.8 5.45 52.2 99.8 3.81 63.0 5.30 52.4 96.5 7.5 3.90
80 68.6 5.72 49.1 108.9 3.52 60.5 5.56 49.2 105.5 7.7 3.59
60 86.7 5.56 67.7 96.5 4.57 77.5 5.35 68.0 92.6 8.8 4.72
10.0 2.4 5.5 70 83.9 5.85 63.9 105.3 4.20 74.3 5.63 64.1 101.3 9.1 4.34
80 81.0 6.15 60.1 114.1 3.86 71.1 5.92 60.3 109.9 9.3 3.99
60 89.9 5.65 70.7 97.9 4.67 80.4 5.42 71.0 93.8 9.1 4.83
70 13.0 3.8 8.8 70 87.0 5.94 66.7 106.6 4.29 77.1 5.71 66.9 102.4 9.4 4.44
80 84.0 6.24 62.7 115.3 3.94 73.7 5.99 62.9 111.0 9.6 4.08
60 91.2 5.69 71.8 98.4 4.70 81.5 5.45 72.1 94.3 9.3 4.88
16.0 5.4 12.5 70 88.2 5.99 67.8 107.1 4.32 78.1 5.74 68.0 102.9 9.6 4.47
80 85.1 6.28 63.7 115.8 3.97 74.7 6.03 64.0 111.4 9.9 4.11
60 100.4 5.92 80.2 102.3 4.97 89.0 5.62 80.6 97.5 10.8 5.20
10.0 2.3 5.3 70 96.9 6.23 75.7 110.8 4.56 85.1 5.92 76.0 105.8 11.1 4.77
80 93.4 6.54 71.1 119.3 4.19 81.3 6.22 71.5 114.2 11.4 4.37
60 105.9 6.06 85.2 104.6 5.12 94.2 5.74 85.7 99.6 11.1 5.37
90 13.0 3.6 8.3 70 102.2 6.38 80.4 113.0 4.70 90.0 6.04 80.8 107.9 11.4 4.92
80 98.4 6.69 75.6 121.4 4.31 85.9 6.35 76.0 116.1 11.8 4.51
60 108.0 6.11 87.1 105.4 5.18 96.0 5.78 87.6 100.4 11.3 5.44
16.0 5.1 11.8 70 104.1 6.43 82.2 113.8 4.75 91.8 6.09 82.6 108.6 11.7 4.98
80 100.3 6.75 77.3 122.2 4.35 87.5 6.39 77.7 116.8 12.0 4.56
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
60
E SERIES SPECIFICATION CATALOG
E066
Cooling Capacity Data (2200 CFM)
PSC Motor
WPD EA COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT DB/WB TC SC KW HR EER TC SC KW HR HW EER
75/63 67.3 47.7 3.59 80.5 18.7 68.0 47.8 3.58 81.2 5.7 19.0
10.0 2.6 6.0 80/67 73.2 49.7 3.67 85.7 20.0 73.9 49.8 3.65 86.3 5.8 20.2
85/71 79.0 51.7 3.74 90.8 21.1 79.8 51.8 3.72 91.5 6.0 21.4
75/63 67.6 47.9 3.49 80.5 19.4 68.2 48.0 3.45 80.9 5.0 19.7
50 13.0 4.1 9.5 80/67 73.5 49.9 3.56 85.7 20.7 74.1 50.0 3.52 86.1 5.2 21.0
85/71 79.4 51.9 3.63 90.8 21.9 80.0 52.0 3.60 91.3 5.4 22.3
75/63 68.3 48.2 3.45 81.1 19.8 68.7 48.2 3.40 81.3 4.4 20.2
16.0 5.8 13.4 80/67 74.3 50.2 3.52 86.3 21.1 74.6 50.2 3.47 86.5 4.6 21.5
85/71 80.2 52.2 3.59 91.5 22.3 80.6 52.2 3.54 91.7 4.7 22.8
75/63 62.5 44.9 4.28 77.8 14.6 63.1 45.2 4.22 78.3 8.3 15.0
10.0 2.4 5.5 80/67 67.9 46.7 4.37 82.8 15.5 68.6 47.0 4.30 83.3 8.6 15.9
85/71 73.3 48.6 4.46 87.8 16.5 74.1 48.9 4.39 88.2 8.9 16.9
75/63 62.7 44.9 4.16 77.7 15.1 63.1 45.2 4.10 77.9 7.7 15.4
70 13.0 3.8 8.8 80/67 68.1 46.8 4.25 82.6 16.0 68.6 47.0 4.18 82.9 7.9 16.4
85/71 73.6 48.7 4.33 87.6 17.0 74.1 48.9 4.27 87.9 8.2 17.4
75/63 63.6 45.9 4.09 78.4 15.5 63.9 46.1 4.03 78.5 7.1 15.8
16.0 5.4 12.5 80/67 69.2 47.8 4.18 83.4 16.6 69.5 48.0 4.12 83.5 7.3 16.9
85/71 74.7 49.8 4.26 88.4 17.5 75.0 49.9 4.20 88.5 7.5 17.9
75/63 56.7 42.2 5.23 75.0 10.8 57.2 42.6 5.10 75.2 11.0 11.2
10.0 2.3 5.3 80/67 61.6 43.9 5.33 79.8 11.5 62.2 44.4 5.20 80.0 11.4 12.0
85/71 66.5 45.7 5.44 84.6 12.2 67.2 46.2 5.31 84.8 11.7 12.7
75/63 56.8 42.1 5.09 74.7 11.2 57.2 42.4 4.99 74.8 10.4 11.5
90 13.0 3.6 8.3 80/67 61.8 43.8 5.19 79.5 11.9 62.2 44.2 5.09 79.6 10.7 12.2
85/71 66.7 45.6 5.30 84.2 12.6 67.2 46.0 5.20 84.3 11.0 12.9
75/63 57.9 43.8 4.97 75.5 11.7 58.2 44.1 4.90 75.5 9.7 11.9
16.0 5.1 8.3 80/67 63.0 45.6 5.07 80.3 12.4 63.2 45.9 5.00 80.3 10.0 12.6
85/71 68.0 47.4 5.17 85.1 13.1 68.3 47.8 5.10 85.1 10.3 13.4
75/63 49.5 38.6 6.45 71.7 7.7 50.0 39.1 6.22 71.5 13.7 8.0
10.0 2.2 5.1 80/67 53.8 40.2 6.58 76.3 8.2 54.4 40.8 6.35 76.0 14.1 8.6
85/71 58.1 41.8 6.71 80.9 8.7 58.7 42.4 6.48 80.6 14.6 9.1
75/63 49.6 38.4 6.29 71.2 7.9 49.9 38.9 6.14 71.1 13.0 8.1
110 13.0 3.4 7.9 80/67 53.9 40.0 6.42 75.8 8.4 54.3 40.5 6.26 75.6 13.4 8.7
85/71 58.2 41.6 6.55 80.3 8.9 58.6 42.1 6.39 80.2 13.8 9.2
75/63 50.8 40.7 6.10 71.9 8.3 51.0 41.1 6.02 71.8 12.4 8.5
16.0 4.8 11.1 80/67 55.2 42.4 6.23 76.5 8.9 55.4 42.8 6.14 76.4 12.8 9.0
85/71 59.6 44.0 6.35 81.1 9.4 59.8 44.5 6.27 81.0 13.1 9.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
61
E SERIES SPECIFICATION CATALOG
E072
Heating Capacity Data
High Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
1200 41.3 3.88 28.0 101.8 3.11 34.0 3.82 28.6 96.2 7.7 3.19
10.0 2.7 6.2 1850 45.0 4.01 31.3 92.5 3.29 38.1 3.94 31.8 89.1 7.2 3.37
2200 46.5 4.22 32.1 89.6 3.23 39.9 4.14 32.5 86.8 6.7 3.30
1200 44.1 3.88 30.8 104.0 3.33 36.7 3.81 31.5 98.3 7.8 3.42
30 13.0 4.3 9.9 1850 48.3 4.05 34.4 94.2 3.49 41.3 3.97 35.0 90.6 7.3 3.58
2200 50.0 4.31 35.3 91.0 3.40 43.3 4.23 35.7 88.2 6.8 3.47
1200 44.7 3.96 31.2 104.5 3.31 37.1 3.88 31.8 98.7 7.9 3.40
16.0 6.1 14.1 1850 48.7 4.09 34.8 94.4 3.49 41.6 4.01 35.3 90.8 7.4 3.58
2200 50.5 4.35 35.7 91.3 3.40 43.7 4.27 36.0 88.4 6.9 3.47
1200 58.8 4.79 42.4 115.4 3.59 48.2 4.57 42.7 107.2 10.1 3.74
10.0 2.6 6.0 1850 62.5 4.77 46.2 101.3 3.84 52.8 4.59 46.3 96.4 9.2 3.95
2200 64.6 4.94 47.7 97.2 3.83 55.6 4.80 47.6 93.4 8.3 3.90
1200 62.2 4.90 45.5 118.0 3.72 51.3 4.66 45.8 109.6 10.3 3.88
50 13.0 4.1 9.5 1850 66.0 4.86 49.4 103.0 3.98 56.0 4.67 49.5 98.0 9.4 4.11
2200 68.2 5.02 51.1 98.7 3.98 59.0 4.87 50.9 94.8 8.5 4.06
1200 63.5 4.97 46.5 119.0 3.74 52.3 4.72 46.7 110.4 10.5 3.90
16.0 5.8 13.4 1850 67.2 4.92 50.4 103.6 4.01 57.0 4.72 50.4 98.5 9.6 4.13
2200 69.4 5.07 52.1 99.2 4.01 60.0 4.92 51.9 95.3 8.6 4.09
1200 79.5 5.86 59.5 131.4 3.97 65.1 5.43 59.1 120.2 12.5 4.19
10.0 2.4 5.5 1850 82.4 5.62 63.2 111.2 4.29 69.4 5.31 62.4 104.7 11.2 4.44
2200 85.0 5.66 65.7 105.8 4.40 73.3 5.45 64.6 100.9 9.9 4.47
1200 82.6 5.97 62.2 133.8 4.05 67.6 5.51 61.7 122.2 12.9 4.28
70 13.0 3.8 8.8 1850 85.3 5.71 65.8 112.7 4.38 71.8 5.37 64.9 105.9 11.5 4.54
2200 88.0 5.72 68.5 107.1 4.51 75.9 5.50 67.2 101.9 10.1 4.58
1200 85.0 6.07 64.3 135.6 4.10 69.6 5.58 63.6 123.7 13.1 4.34
16.0 5.4 12.5 1850 87.5 5.78 67.8 113.8 4.44 73.6 5.43 66.8 106.9 11.7 4.60
2200 90.4 5.78 70.6 108.0 4.58 77.9 5.55 69.2 102.8 10.3 4.65
1200 99.5 6.94 75.8 146.8 4.20 80.5 6.24 74.2 132.1 15.0 4.49
10.0 2.3 5.3 1850 100.4 6.44 78.4 120.2 4.56 83.5 5.97 76.4 111.8 13.2 4.75
2200 103.7 6.31 82.1 113.6 4.81 88.7 6.01 79.6 107.3 11.5 4.88
1200 101.4 7.06 77.3 148.2 4.21 81.5 6.30 75.5 132.9 15.4 4.51
90 13.0 3.6 8.3 1850 101.8 6.51 79.5 120.9 4.58 84.1 6.00 77.3 112.1 13.6 4.77
2200 105.1 6.34 83.4 114.2 4.85 89.4 6.03 80.6 107.6 11.8 4.92
1200 105.1 7.17 80.6 151.1 4.29 84.7 6.38 78.6 135.4 15.7 4.61
16.0 5.1 11.8 1850 105.3 6.60 82.8 122.7 4.67 87.1 6.07 80.3 113.6 13.9 4.87
2200 108.8 6.41 86.9 115.8 4.98 92.6 6.08 83.9 109.0 12.0 5.04
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
62
E SERIES SPECIFICATION CATALOG
E072
Cooling Capacity Data
High Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
1200 68.7 39.5 3.40 80.3 20.2 69.4 39.1 3.37 73.9 7.0 20.6
10.0 2.6 6.0 1850 75.6 48.5 3.72 88.3 20.3 76.4 48.0 3.68 81.2 7.7 20.8
2200 77.2 52.7 3.95 90.7 19.5 77.9 52.2 3.91 83.4 7.9 19.9
1200 69.4 39.9 3.33 80.7 20.8 69.7 39.7 3.29 74.1 6.8 21.2
50 13.0 4.1 9.5 1850 76.4 49.0 3.64 88.8 21.0 76.8 48.7 3.60 81.6 7.5 21.3
2200 77.9 53.3 3.87 91.2 20.1 78.3 53.0 3.83 83.7 7.7 20.4
1200 72.4 40.9 3.27 83.6 22.1 72.4 40.9 3.24 76.7 6.8 22.4
16.0 5.8 13.4 1850 77.2 50.0 3.58 89.4 21.6 77.2 50.0 3.54 81.9 7.3 21.8
2200 78.7 53.8 3.81 91.7 20.7 78.7 53.8 3.77 84.1 7.5 20.9
1200 67.6 39.0 4.05 81.4 16.7 68.3 39.0 3.99 72.6 9.3 17.1
10.0 2.4 5.5 1850 72.0 47.7 4.43 87.1 16.3 72.7 47.7 4.36 77.6 10.0 16.7
2200 73.5 51.3 4.71 89.6 15.6 74.2 51.3 4.64 79.8 10.3 16.0
1200 68.3 39.4 3.97 81.8 17.2 68.6 39.4 3.92 73.0 9.0 17.5
70 13.0 3.8 8.8 1850 72.7 48.2 4.34 87.5 16.8 73.1 48.2 4.28 78.1 9.7 17.1
2200 74.2 51.8 4.61 90.0 16.1 74.6 51.8 4.55 80.2 9.9 16.4
1200 69.0 39.8 3.90 82.3 17.7 69.0 39.8 3.86 73.4 8.7 17.9
16.0 5.4 12.5 1850 73.5 48.7 4.26 88.0 17.2 73.5 48.7 4.22 78.5 9.3 17.4
2200 75.0 52.4 4.54 90.4 16.5 75.0 52.4 4.49 80.7 9.6 16.7
1200 56.8 35.7 4.72 72.9 12.1 57.4 36.1 4.62 62.0 11.1 12.4
10.0 2.3 5.3 1850 62.6 43.9 5.15 80.2 12.1 63.2 44.3 5.05 68.2 12.2 12.5
2200 63.9 47.7 5.48 82.6 11.6 64.5 48.1 5.37 70.2 12.6 12.0
1200 57.4 36.1 4.62 73.2 12.4 57.7 36.3 4.55 62.5 10.7 12.7
90 13.0 3.6 8.3 1850 63.2 44.3 5.04 80.4 12.5 63.5 44.5 4.97 68.7 11.8 12.8
2200 64.5 48.1 5.37 82.8 12.0 64.8 48.4 5.29 70.7 12.2 12.3
1200 59.9 37.0 4.54 75.4 13.2 59.9 37.0 4.49 64.7 10.6 13.3
16.0 5.1 11.8 1850 63.9 45.2 4.96 80.8 12.9 63.9 45.2 4.91 69.2 11.4 13.0
2200 65.2 48.6 5.28 83.2 12.3 65.2 48.6 5.22 71.3 11.7 12.5
1200 49.5 33.0 5.40 67.9 9.2 50.0 33.7 5.27 54.4 13.5 9.5
10.0 2.2 5.1 1850 52.7 40.4 5.90 72.8 8.9 53.2 41.2 5.76 58.4 14.5 9.2
2200 53.8 43.4 6.28 75.2 8.6 54.3 44.3 6.12 60.2 15.0 8.9
1200 50.0 33.3 5.29 68.0 9.5 50.2 33.7 5.19 54.9 13.0 9.7
110 13.0 3.4 7.9 1850 53.2 40.8 5.78 72.9 9.2 53.5 41.2 5.68 58.9 13.9 9.4
2200 54.3 43.9 6.15 75.3 8.8 54.6 44.3 6.04 60.8 14.4 9.0
1200 50.5 33.7 5.20 68.2 9.7 50.5 33.7 5.15 55.6 12.5 9.8
16.0 4.8 11.1 1850 53.8 41.2 5.68 73.1 9.5 53.8 41.2 5.62 59.6 13.4 9.6
2200 54.9 44.3 6.04 75.5 9.1 54.9 44.3 5.98 61.5 13.8 9.2
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
63
E SERIES SPECIFICATION CATALOG
E072
Heating Capacity Data
Low Capacity
WPD HEATING ONLY HEATING WITH HOT WATER
EWT GPM PSI FT CFM HC KW HE LAT COP HC KW HE LAT HW COP
800 18.3 1.61 12.8 91.2 3.34 14.9 1.59 13.3 87.2 3.9 3.45
7.0 1.5 3.4 1000 18.4 1.61 12.9 87.0 3.35 15.1 1.60 13.2 84.0 3.6 3.43
1200 19.3 1.63 13.7 84.9 3.47 16.1 1.61 13.9 82.4 3.3 3.52
800 18.1 1.64 12.5 91.0 3.24 14.6 1.62 13.0 86.9 4.0 3.35
30 10.0 2.7 6.1 1000 18.2 1.64 12.6 86.9 3.26 14.8 1.62 13.0 83.7 3.7 3.34
1200 19.1 1.66 13.5 84.7 3.38 15.8 1.64 13.6 82.2 3.4 3.43
800 18.8 1.64 13.2 91.8 3.36 15.3 1.62 13.8 87.7 4.0 3.48
13.0 4.3 9.9 1000 19.0 1.64 13.4 87.6 3.39 15.5 1.62 13.7 84.4 3.7 3.47
1200 19.9 1.66 14.2 85.3 3.52 16.6 1.64 14.4 82.8 3.4 3.57
800 26.3 1.88 19.9 100.5 4.10 21.4 1.82 20.6 94.7 5.4 4.31
7.0 1.4 3.2 1000 27.0 1.83 20.8 95.0 4.33 22.5 1.78 21.2 90.9 4.7 4.48
1200 28.2 1.81 22.0 91.8 4.56 24.1 1.78 22.0 88.6 4.0 4.63
800 26.6 1.92 20.1 100.8 4.07 21.5 1.85 20.8 94.9 5.6 4.29
50 10.0 2.6 6.0 1000 27.4 1.85 21.0 95.3 4.32 22.7 1.80 21.4 91.0 4.8 4.48
1200 28.5 1.84 22.3 92.0 4.55 24.3 1.80 22.3 88.8 4.1 4.62
800 27.4 1.93 20.8 101.7 4.16 22.2 1.86 21.5 95.7 5.7 4.39
13.0 4.1 9.5 1000 28.2 1.86 21.8 96.1 4.43 23.5 1.81 22.2 91.8 4.9 4.59
1200 29.4 1.85 23.1 92.7 4.67 25.2 1.81 23.1 89.4 4.1 4.74
800 35.1 2.14 27.8 110.6 4.80 28.6 2.02 28.7 103.1 7.0 5.15
7.0 1.3 3.0 1000 37.0 2.02 30.1 104.3 5.38 31.3 1.93 30.5 98.9 5.8 5.62
1200 38.5 1.96 31.8 99.7 5.74 33.4 1.91 31.5 95.8 4.7 5.83
800 36.3 2.18 28.9 112.0 4.89 29.6 2.05 29.7 104.2 7.2 5.25
70 10.0 2.4 5.6 1000 38.4 2.04 31.4 105.6 5.51 32.5 1.95 31.8 100.1 6.0 5.77
1200 39.9 1.98 33.1 100.8 5.89 34.6 1.93 32.8 96.7 4.7 5.99
800 36.9 2.21 29.4 112.7 4.90 30.1 2.07 30.3 104.8 7.3 5.28
13.0 3.8 8.8 1000 39.1 2.07 32.1 106.2 5.55 33.1 1.97 32.4 100.6 6.1 5.82
1200 40.6 2.01 33.8 101.3 5.94 35.3 1.94 33.4 97.2 4.8 6.04
800 41.3 2.38 33.2 117.8 5.08 32.9 2.19 34.0 108.0 8.6 5.55
7.0 1.2 2.8 1000 44.8 2.17 37.4 111.5 6.04 37.6 2.05 37.5 104.8 7.0 6.37
1200 46.3 2.08 39.2 105.7 6.52 40.0 2.00 38.5 100.9 5.3 6.64
800 43.7 2.41 35.5 120.6 5.31 35.1 2.21 36.4 110.6 8.8 5.82
90 10.0 2.3 5.3 1000 47.7 2.20 40.2 114.2 6.37 40.3 2.06 40.3 107.3 7.1 6.73
1200 49.3 2.09 42.1 108.0 6.89 42.8 2.01 41.3 103.0 5.4 7.02
800 43.9 2.46 35.5 120.8 5.23 35.1 2.25 36.4 110.6 9.0 5.74
13.0 3.6 8.3 1000 48.0 2.23 40.4 114.4 6.30 40.4 2.09 40.5 107.4 7.2 6.66
1200 49.5 2.13 42.3 108.2 6.82 42.9 2.04 41.4 103.1 5.5 6.94
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
64
E SERIES SPECIFICATION CATALOG
E072
Cooling Capacity Data
Low Capacity
WPD COOLING ONLY COOLING WITH HOT WATER
EWT GPM PSI FT CFM TC SC KW HR EER TC SC KW HR HW EER
800 36.6 21.6 1.15 40.5 31.9 36.9 21.8 1.14 38.8 2.0 32.6
7.0 1.4 3.2 1000 39.0 24.7 1.17 43.0 33.3 39.4 24.9 1.16 41.2 2.1 34.0
1200 40.2 28.0 1.23 44.4 32.6 40.6 28.3 1.22 42.6 2.2 33.3
800 36.7 21.8 1.10 40.4 33.2 37.0 22.0 1.09 38.9 1.8 33.9
50 10.0 2.6 6.0 1000 39.1 24.9 1.13 42.9 34.7 39.5 25.2 1.12 41.3 1.9 35.4
1200 40.3 28.3 1.19 44.3 34.0 40.7 28.6 1.17 42.7 2.0 34.6
800 36.8 21.8 1.08 40.5 34.0 37.1 22.0 1.07 39.1 1.6 34.7
13.0 4.1 9.5 1000 39.2 24.9 1.10 43.0 35.5 39.6 25.2 1.09 41.6 1.7 36.2
1200 40.4 28.3 1.16 44.4 34.7 40.8 28.6 1.15 42.9 1.8 35.4
800 32.9 21.4 1.53 38.1 21.5 33.7 21.2 1.51 34.7 4.1 22.3
7.0 1.3 3.0 1000 34.5 23.8 1.55 39.7 22.2 35.3 23.6 1.53 36.2 4.3 23.0
1200 35.5 26.8 1.61 41.0 22.1 36.4 26.5 1.59 37.4 4.5 22.9
800 33.1 21.7 1.48 38.1 22.3 33.7 21.7 1.47 34.9 3.8 23.0
70 10.0 2.4 5.6 1000 34.7 24.1 1.50 39.8 23.0 35.4 24.1 1.49 36.4 4.0 23.7
1200 35.7 27.1 1.56 41.1 22.9 36.5 27.1 1.54 37.6 4.1 23.6
800 33.3 21.8 1.46 38.2 22.9 33.8 22.1 1.44 35.2 3.5 23.4
13.0 3.8 8.8 1000 34.9 24.2 1.48 39.9 23.6 35.4 24.6 1.46 36.7 3.7 24.2
1200 36.0 27.2 1.53 41.2 23.5 36.5 27.6 1.52 37.9 3.8 24.1
800 27.9 20.2 1.91 34.4 14.6 29.0 19.6 1.89 29.2 6.3 15.3
7.0 1.2 2.8 1000 28.8 21.9 1.93 35.4 14.9 30.0 21.2 1.91 30.0 6.5 15.7
1200 29.7 24.3 1.97 36.4 15.1 30.9 23.6 1.95 30.8 6.7 15.8
800 28.2 20.4 1.87 34.6 15.1 29.0 20.3 1.85 29.5 5.9 15.7
90 10.0 2.3 5.3 1000 29.1 22.1 1.89 35.6 15.4 30.0 22.0 1.87 30.3 6.1 16.0
1200 30.0 24.6 1.93 36.6 15.5 30.9 24.4 1.91 31.2 6.3 16.2
800 28.5 20.6 1.84 34.8 15.5 29.1 21.0 1.82 29.8 5.5 15.9
13.0 3.6 8.3 1000 29.4 22.3 1.86 35.7 15.8 30.0 22.8 1.84 30.6 5.6 16.3
1200 30.3 24.8 1.90 36.8 15.9 30.9 25.3 1.88 31.5 5.8 16.4
800 22.8 18.4 2.26 30.5 10.1 24.1 17.5 2.23 23.1 8.6 10.8
7.0 1.1 2.7 1000 23.2 19.4 2.27 30.9 10.2 24.5 18.5 2.24 23.4 8.7 10.9
1200 23.9 21.4 2.28 31.7 10.5 25.2 20.3 2.26 24.0 9.0 11.2
800 23.2 18.6 2.23 30.8 10.4 24.1 18.3 2.21 23.6 8.1 10.9
110 10.0 2.2 5.0 1000 23.5 19.6 2.24 31.2 10.5 24.5 19.4 2.22 23.9 8.2 11.0
1200 24.3 21.6 2.25 32.0 10.8 25.2 21.3 2.23 24.5 8.4 11.3
800 23.5 18.8 2.20 31.0 10.7 24.1 19.3 2.18 24.0 7.5 11.1
13.0 3.4 7.8 1000 23.9 19.9 2.21 31.4 10.8 24.5 20.4 2.19 24.3 7.6 11.2
1200 24.6 21.9 2.22 32.2 11.1 25.2 22.5 2.20 24.9 7.8 11.5
Capacity ratings are based upon 80/67°F EAT for Cooling and 70°F EAT for Heating. See chart on page 21 for EAT
correction factors. Multiple Flow Rates (for EWT) are shown in the table above. The lowest flow rate shown is used for
geothermal open loop/well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal
closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for
boiler tower applications.
65
E SERIES SPECIFICATION CATALOG
66
E SERIES SPECIFICATION CATALOG
Description of Operation
Heating Operation Cool, 2nd Stage (Y1, Y2, O) Single Speed Units
Heat, 1st Stage (Y1) The fan changes to high speed (85% of high speed if
The fan motor is started on low speed immediately, the in dehumidification mode) 15 seconds after the “Y2” input.
loop pump is energized 5 seconds after the “Y1” input is Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units
received, and the compressor is energized on low capac- The compressor is de-energized immediately, the
ity 10 seconds after the “Y1” input. The fan is switched to second loop pump is energized 5 seconds after the “Y2”
medium speed 15 seconds after “Y1” input. The hot water input, and the hot water pump is cycled 30 seconds after
pump is cycled 30 seconds after the "Y1" input. the “Y2” input. The fan changes to high speed (85% of
Heat, 2nd Stage (Y1,Y2) Single-Speed Units high speed if in dehumidification mode) 45 seconds after
The hot water pump is de-energized, which directs all the “Y2” input and the compressor is energized on high
heat to satisfying the thermostat, and the fan changes to capacity 60 seconds after the “Y2” input.
high speed 15 seconds after the "Y2" input. Fan (G only)
Heat, 2nd Stage (Y1,Y2) Dual Capacity Units The fan starts on low speed. Regardless of fan input
The compressor is de-energized immediately, the “G” from thermostat, the fan will remain on low speed for
second loop pump is energized 5 seconds after the “Y2” 30 seconds at the end of each heating, cooling or emer-
input, and the hot water pump is cycled 30 seconds after gency heat cycle.
the “Y2” input. The fan changes to high speed 45 seconds
after the “Y2” input and the compressor is energized on
Lockout Conditions
During lockout mode, the appropriate unit and ther-
high capacity 60 seconds after the “Y2” input.
mostat lockout LEDs will illuminate. The compressor, loop
Heat, 3rd Stage (Y1,Y2,W) Single-Speed Units pump, hot water pump, and accessory outputs are de-
The first stage of resistance heat is energized 10 energized. Unless the lockout is caused by an ECM2 low
seconds after “W” input, and with continuous 3rd stage RPM fault, the fan will continue to run on low speed. If the
demand, the additional stages of resistance heat engage thermostat calls for heating, emergency heat operation will
sequentially every 5 minutes. occur.
Lockout modes of any kind can be reset at the thermo-
Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units stat after a 5-second waiting period, which restores normal
The hot water pump is de-energized which directs all operation but keeps the unit lockout LED illuminated.
heat to satisfy the thermostat. The 1st stage of resistance Interruption of power to the unit will reset a lockout without
heat is energized 10 seconds after “W” input, and with a waiting period and clear all lockout LEDs.
continuous 3rd stage demand, the additional stages of
resistance heat engage sequentially every 5 minutes. High Pressure
This lockout mode occurs when the normally closed
Emergency Heat (W only) safety switch is opened momentarily (set at 600 PSI).
The fan is started on high speed, and the first stage of re-
sistance heat is energized 10 seconds after the "W" input. Low Pressure
Continuing demand will engage the additional stages of This lockout mode occurs when the normally closed
resistance heat sequentially every 2 minutes. switch is opened for 30 continuous seconds (set at 40
PSI).
Cooling Operation
In all cooling operations, the reversing valve directly Freeze Protection (Water Flow)
tracks the “O” input. Thus, anytime the “O” input is pres- This lockout mode occurs when the freeze thermistor
ent, the reversing valve will be energized. temperature is at or below the selected freeze protection
point (well 30°F or loop 15°F) for 30 continuous seconds.
Cool, 1st Stage (Y1, 0)
The fan motor is started on low speed immediately, Condensate Overflow
the loop pump is energized 5 seconds after the “Y1” input This lockout mode occurs when the condensate over-
is received, and the compressor is energized 10 seconds flow level has been reached for 30 continuous seconds.
after the “Y1” input. The fan is switched to medium speed Fan RPM
15 seconds after “Y1” input (85% of medium speed if in The control board monitors fan RPM to sense opera-
dehumidification mode). The hot water pump is cycled 30 tion. This lockout mode occurs if the fan RPM falls below
seconds after the “Y1” input. the low RPM limit (100 RPM) for 30 continuous seconds.
67
E SERIES SPECIFICATION CATALOG
68
E SERIES SPECIFICATION CATALOG
240V - L1
240V - L2
Fused L2
Fused L2
240V - L1
Fused L1
240V - L2
Fused L2
Fused L2
F1 F1
69
E SERIES SPECIFICATION CATALOG
Casing & Cabinet - The cabinet shall be fabricated Fan Motor & Assembly - The fan shall be a direct
from heavy-gauge steel and finished with corrosion-resis- drive centrifugal type with a dynamically balanced wheel.
tant powder coating. The interior shall be insulated with The housing and wheel shall be designed for quiet low out-
1/2-inch thick, multi-density, coated glass fiber with edges let velocity operation. The fan housing shall be removable
sealed or tucked under flanges to prevent the introduction from the unit without disconnecting the supply air ductwork
of glass fibers into the discharge air. One to two blower for servicing of the fan motor. The fan motor shall be a
and three compressor compartment access panels shall PSC or variable-speed ECM2 type. The ECM2 fan motor
be removable with supply and return ductwork in place. shall be soft starting, shall maintain constant CFM over its
The internal component layout shall provide for service ac- operating static range, and shall provide 12 CFM settings.
cess from the front side for restricted installations. The fan motor shall be isolated from the housing by rubber
A duct collar shall be provided on the supply air open- grommets. The motor shall be permanently lubricated and
ing. Standard size 1-inch pleated filters shall be provided have thermostatic overload protection. ECM2 motors shall
with each unit. Vertical units shall have a return air filter be long-life ball bearing type.
rack/duct collar; the horizontal units shall have a filter Electrical - A microprocessor-based controller that in-
bracket. The upflow vertical units shall have a removable terfaces with a multi-stage electronic thermostat to monitor
insulated divider panel between the air handling section and control unit operation shall be provided. The control
and the compressor section to minimize the transmission shall provide operational sequencing, fan speed control,
of compressor noise and to permit operational service test- fan failure high and low pressure switch monitoring, freeze
ing without air bypass. Vertical units shall be supplied with protection, hot water limit thermistor sensing, condensate
left or right horizontal air inlet and top or bottom vertical air overflow sensing, auxiliary heat staging, lockout mode
discharge. Horizontal units shall be supplied with left or control, hot water and loop pump control, LED status and
right air inlet and side or end air discharge. fault indicators, fault memory, field selectable options, and
Refrigerant Circuit - All units shall contain a sealed accessory output.
refrigerant circuit including a hermetic motor-compressor, A detachable terminal block with screw terminals will
bidirectional thermostatic expansion valve, finned tube be provided for field control wiring. All units shall have
air-to-refrigerant heat exchanger, reversing valve, coaxial knockouts for entrance of low and line voltage wiring. The
tube water-to-refrigerant heat exchanger, optional desu- fan motor and control box shall be harness plug wired for
perheater coil, and service ports. easy removal.
Compressors shall be high-efficiency single speed
Piping - Supply and return water connections (and
reciprocating or scroll, or dual capacity reciprocating type
optional desuperheater connections) shall be 1-inch FPT
designed for heat pump duty and mounted on vibration
brass swivel fittings, which provide a union and eliminate
isolators. Compressor motors shall be single-phase PSC
the need for pipe wrenches and sealants when making
with overload protection. The electro-coated coil shall
field connections. All water piping shall be insulated to
be sized for low-face velocity and constructed of lanced
prevent condensation at low liquid temperatures, on the
aluminum fins bonded to rifled copper tubes in a staggered
vertical upflow units, the condensate connection shall be a
pattern not less than three rows deep.
3/4-inch PVC socket with internally-trapped hose that can
be routed to front or side locations.
70
E SERIES SPECIFICATION CATALOG
71
Manufactured by WFI
WaterFurnace International, Inc.
9000 Conservation Way
Fort Wayne, IN 46809
www.waterfurnace.com
Product: E Series
Type: Geothermal/Water Source Heat Pumps
Size: 2 thru 6 Ton Single Speed
3 thru 6 Ton Dual Capacity
WFI has a policy of continuous product research Document Type: Specification Catalog
and development and reserves the right to change Part Number: SP1461
design and specifications without notice. Release Date: 09/04
©2004 WFI. Supercedes: SP1461 (08/04)