You are on page 1of 5

ComFlor 60/1.

2/S350 Eurocodes Page 1 of 4

SCI Tata Steel v9.0.34.24751


Job Reference: Date: 29/4/2019
Deck Reference: CF60/1.2_350 Time: 16:44:06
Company Name: Job No:
Client Name: Calcs By:
Checked By: File Name:

Full Output
Note: Section Designed to Eurocodes, United Kingdom National Annex
Construction Stage: PASS Max Unity Factor: 0.42
Normal Stage: PASS Max Unity Factor: 0.57
Fire Condition: PASS Max Unity Factor: 0.62
Serviceability: SATISFACTORY Max Unity Factor: 0.54
*** Section Adequate ***
Floor Plan Data (unpropped composite construction with ComFlor 60/1.2/S350 decking)
Beam centres - unequal 3.00 m, 3.20 m Profile span type Double
Beam or wall width 150 mm Propping None
Concrete span type Internal
Profile Data (ComFlor 60/1.2/S350 decking.)
Depth 60 mm Pitch of deck ribs 300 mm
Trough width 120 mm Crest width 130.7 mm
Nominal sheet thickness 1.20 mm Design sheet thickness 1.16 mm
Deck weight 0.14 kN/m² Yield strength 350 N/mm²
Concrete Slab (Normal Weight Concrete ; Grade C30/37; Mesh : A252)
Overall slab depth 150 mm
Concrete characteristic strength 30 N/mm² Concrete wet density 2550 kg/m³
Modular ratio 10 Concrete dry density 2450 kg/m³
Bar reinforcement None
Mesh reinforcement :
Mesh A252 Yield strength 500 N/mm²
Cover to Mesh 25 mm Mesh Layers Single
Account for End Anchorage No Shear connectors per rib N/A
Diameter of Shear Connectors N/A
Screed depth 50 mm Screed density 2200 kg/m³
Section Properties
*** Note - 1: All values of inertia are expressed in steel units
*** Note - 2: Average inertia is used for deflection calculations for the composite stage
*** Note - 3: Cracked dynamic inertia is used for natural frequency calculations
Deck Profile
Sagging Inertia, Iy 132.910 cm4/m Area of profile (Net), Ap 1721 mm²/m
Hogging Inertia, Iy 121.600 cm4/m Effective area of profile 1576.00 mm²/m
Composite
Inertia, Iy - Uncracked 2430 cm4/m Inertia, Iy - Cracked 1301 cm4/m
Average inertia 1865 cm4/m Cracked inertia (dynamic) 1466 cm4/m
Shear bond coefficients - Tau 0.26
Concrete volume 0.117 m³/m/m
Loads Acting on Slab (Actions)
*** Note: Slab subjected to uniformly distributed loads (UDL) ONLY
Imposed (occupancy) 5.00 kN/m² Partitions 0.00 kN/m²
Ceilings and services 0.50 kN/m² Finishes 2.05 kN/m²
Self weight of concrete slab (wet) 2.94 kN/m² Self weight of decking 0.14 kN/m²
Self weight of concrete slab (dry) 2.82 kN/m² Self weight of screeds 1.08 kN/m²
Construction load 1.50 kN/m²
Line Loads Perpendicular to Deck Span (Actions)
None
Line Loads Parallel to Deck Span (Actions)
None

File Name: v9.0.34.24751


ComFlor 60/1.2/S350 Eurocodes Page 2 of 4

Fire Data
Design method Mesh + Deck Method Fire resistance period 60 mins
Non-permanent imposed loads N/A
Partial Safety Factors
Actions Materials
Permanent, gamma G 1.35 Structural steel - elastic, gamma M0 1.00
Permanent - accidental, gamma GA N/A Structural steel - buckling, gamma M1 1.00
Variable, gamma Q 1.50 Concrete, gamma C 1.50
Combination factor - Fire, psi 1 0.70 Reinforcement, gamma S 1.15
Combination factor, psi 0 0.70 Combination factor, psi 2 0.60

Construction Stage

Loadings @ SLS (kN/m²) @ ULS (kN/m²)


Self weight of decking 0.14 0.18
Self weight of concrete slab (wet) 2.94 4.41
Reinforcement 0.04 0.06
Total weight of slab 3.12 4.65
Construction live load 0.75 1.13
Construction live load patch 0.75 1.13
Note: Critical span is longer span
Effective Span of Deck
Effective span Le, is the smaller of
1) c/c of supports = 3.20 m
2) clear span + deck depth = 3.05 + 60.0 / 1000
= 3.11 m
Therefore Le = 3.11 m
Shear Resistance Check (BS EN 1993-1-3 Clause 6.1.5 and 6.1.7.3)
Applied shear 12.69 kN/m
Web shear resistance, Pv 100.15 kN/m Unity Factor 0.13 PASS
Applied reaction 20.02 kN/m
Web crushing resistance, Pw 60.38 kN/m Unity Factor 0.33 PASS
Bending Resistance Check (BS EN 1993-1-3 Clause 6.1.4.1)
*** Note: Redistribution of hogging moment is applied, based on equilibrium of the continuous decking as the sagging moment
does not exceed design resistance.
Sagging
Max applied moment is at 1.37 m from support in longer span
Max applied moment 6.46 kNm/m
Moment resistance 15.21 kNm/m Unity Factor 0.42 PASS
Hogging
Applied moment 0.00 kNm/m
Moment resistance 13.07 kNm/m Unity Factor 0.00 PASS
Combined Effects
Bending and Web Crushing (BS EN 1993-1-3 Clause 6.1.11)
*** Note: Redistribution of hogging moment is applied, based on equilibrium of the continuous decking as the sagging moment
does not exceed design resistance.
Design unity factor is the worst case of
1. Maximum hogging:
(11.08 / 60.38 + 0.00 / 13.07) / 1.25 = 0.15
2. Maximum reaction:
(20.02 / 60.38 + 0.00 / 13.07) / 1.25 = 0.27
Design unity factor 0.27 PASS
Bending and Shear (BS EN 1993-1-3 Clause 6.1.10)
*** Note: Low shear - This check is not required
Uplift
2. Uplift force -1.10
Support Interaction Check at Serviceability Limit State (BS EN 1993-1-3 Clause 7.2)

File Name: v9.0.34.24751


ComFlor 60/1.2/S350 Eurocodes Page 3 of 4

Design unity factor is the worst case of


1. Maximum hogging:
(16.26 / 60.38 + 4.45 / 13.07) / (0.9 * 1.25) = 0.54
2. Maximum reaction:
(16.26 / 60.38 + 4.45 / 13.07) / (0.9 * 1.25) = 0.54
Design unity factor 0.54 PASS
Deflection
Allowable deflection is the lesser of
1) Effective span / deflection limit without ponding 17.28 mm
2) Deflection limit without ponding, absolute maximum value 20.00 mm
3) Slab depth / 10 15.00 mm
Max deflection is at 1.37 m from support in longer span.
Max self weight deflection = 6.54mm <= 15.00mm SATISFACTORY

Normal Stage

Span
The effective composite span is 3.17 m
Loadings @ SLS (kN/m²) @ ULS (kN/m²)
Dead (Profile, concrete, reinforcement) 3.00 4.05
Imposed 5.00 7.50
Superimp (Ceiling, services, screed, finishes) 3.63 4.90
Total 11.63 16.45
All line and point described above in 'Loading Details' are applied at the Normal stage
Shear Resistance Check
Shear Bond (BS EN 1994-1-1 Clause 9.7.3)
Shear span 0.79 m
Applied bond shear 20.23 kN/m
Bond resistance = (1000 * 116.15/1.25) * [178.39 * 1721.00/(1000 * [0.79 * 1000]) + 0.10] / 1000 + 0.00)/1000 = 45.28 kN/m
Unity Factor = 20.23/45.28 = 0.45 < 1 PASS
Vertical Shear (BS EN 1992-1-1 Clause 6.2.2)
Maximum applied shear 24.98 kN/m
Shear resistance of end diaphragm (ComFlor 225 only) 0.00 kN/m ***test value
Vertical shear resistance is the greater of:
1. (0.54 * 400.00 * 116.15) / 1000 + 0.00
2. (0.12 * 2.00 * (100 * 0.02 * 30.00)^1/3) * 400.00 * 116.15) / 1000 + 0.00
= 43.65 kN/m
Unity Factor = 24.98/43.65 = 0.57 < 1 PASS
Punching Shear (BS EN 1994-1-1 Clause 9.7.6)
N/A - no concentrated loads have been applied
Bending Resistance Check (BS EN 1994-1-1 Clause 9.7.2)
Applied bending moment 19.78 kNm/m
Depth of concrete stress block 32.45 mm
Lever arm 99.93 mm
Compression in concrete 551.60 kN/m
Moment Resistance 55.12 kNm/m
Unity Factor = 19.78/55.12 = 0.36 < 1 PASS
Fire Resistance
Effective span in fire 3.05 m
Fire total UDL 10.26 kN/m²
Fire free moment 11.93 kNm/m
Moment resistance 9.33 kNm/m
Total moment resistance 19.29 kNm/m
Unity Factor 0.62 PASS
Deflection
Properties
Modular ratio 10.00
Uncracked section inertia 24299250.00 mm4
Cracked section inertia 13007650.00 mm4
File Name: v9.0.34.24751
ComFlor 60/1.2/S350 Eurocodes Page 4 of 4

Deflection Checks
Imposed load deflection 1.66 mm
Allowable deflection (20 mm max) 20.00 mm SATISFACTORY
Total deflection 2.86 mm
Allowable deflection 12.66 mm PASS
Dynamic Sensitivity
Dynamic inertia (cracked section) 1465.75 cm4
Maximum deflection 3.01 mm
Frequency 10.38 Hz
Unity Factor = 5.00/10.38 = 0.48 < 1 PASS

File Name: v9.0.34.24751

You might also like