GENERAL NOTES

1. Drawings to be read in conjunction with all relevant Architect's,


Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site.
Any discrepancies must be brought to the engineer's attention
prior to construction.
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in
accordance with the relevant provisions of
“The Application of the National Building Regulations”
(SANS 10400), Building Standards act (Act103)
and the relevant parts of SABS 1200.
5. The works will be inspected form time to time by the
consulting engineer to ascertain that the contractor is carrying
out the work in general conformity with the engineering
drawings and documents.
Such inspections are not for the contractors benefit and do not
relieve him of the responsibility for the proper construction
of the works in accordance with the engineering drawings,
documents and good building practice.
6. The signed original copy of this drawing is kept at the
engineer's office.

13 14 15 16 17 18 19 20
685 2000 6850 1900 2600 6450 1750

230mm BRICK WALL


ON 750 x 250 dp STRIP FOOTING

E E
RC RAFT SLAB
125mm THK, 30MPa
T.O.C. = 0 185
155mm

4800

4800
STEP 155mm
STEP
280 x 280mm
RC COLUMN

G G

T.O.C. = 0 030
155mm

1720

1720
STEP RC RAFT BEAM
350 x 515mm dp, 30MPa 195x195x6.0
H SHS POST H
155mm

350 x 515mm dp, 30MPa


STEP
B

RC RAFT BEAM
155mm - A

5375

5375
STEP
-
RC RAFT BEAM
350 x 600mm dp, 30MPa 195x195x6.0
SHS POST
RC RAFT BEAM
350 x 600mm dp, 30MPa
195x195x6.0
J SHS POST J

350 x 600mm dp, 30MPa


350 x 600mm dp, 30MPa

350 x 515mm dp, 30MPa


RC RAFT BEAM
RC RAFT BEAM

RC RAFT BEAM
70mm
STEP
195x195x6.0

6440

6440
SHS POST
RC RAFT SLAB
125mm THK, 30MPa
T.O.C. = 0 100

RC RAFT BEAM
350 x 600mm dp, 30MPa 195x195x6.0
K RC RAFT BEAM
350 x 515mm dp, 30MPa
SHS POST
K
RC RAFT SLAB 85mm
01 02 03 04 05 06 07 08 09 10 11 12 125mm THK, 30MPa STEP
21 22 23 24

350 x 600mm dp, 30MPa


T.O.C. = 0 185
195x195x6.0

RC RAFT BEAM
3000 6000 685 4680 1320 4679 1320 4680 1320 4680 1320 SHS POST
2000 6880 3780

STEEL COLUMN STEEL COLUMN STEEL COLUMN STEEL COLUMN


203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION

350 x 600mm dp, 30MPa


RC RAFT BEAM 155mm
A 350 x 600mm dp, 30MPa STEP

350 x 600mm dp, 30MPa

RC RAFT BEAM
350 x 600mm dp, 30MPa

EJ
350 x 600mm dp, 30MPa

EJ
85mm

RC RAFT BEAM
STEP
RC RAFT BEAM

RC RAFT BEAM

RC RAFT SLAB
RC RAFT BEAM RC RAFT BEAM
125mm THK, 30MPa
350 x 700mm dp, 30MPa 350 x 700mm dp, 30MPa C T.O.C. = 0 100
4473

280 x 280mm
1000

1000

1000

1000

1000
CONTINUES AS ON

-
ARCHITECTURAL

RC COLUMN 85mm
TOC 85mm STEP
LAYOUT

2320 2320 2320 2320 0.1m STEP


RC BASE RC BASE RC BASE RC BASE
B 2320 x 1000 x 700mm dp 2320 x 1000 x 700mm dp 2320 x 1000 x 700mm dp 2320 x 1000 x 700mm dp STEEL COLUMN

EJ
EJ

RC RAFT BEAM 203 x 203 x 46 H-SECTION RC RAFT BEAM


350 x 600mm dp, 30MPa 350 x 600mm dp, 30MPa
G
- RC RAFT BEAM M
350 x 700mm dp, 30MPa 155mm

350 x 600mm dp, 30MPa

350 x 600mm dp, 30MPa


STEP

RC RAFT BEAM
350 x 700mm dp, 30MPa

RC RAFT BEAM

350 x 600mm dp, 30MPa


RC RAFT BEAM
RC RAFT SLAB 350 x 700mm dp, 30MPa
RC RAFT BEAM

RC RAFT BEAM
125mm THK, 30MPa RC RAFT SLAB
350 x 600mm dp, 30MPa

T.O.C. = 0 185 RC RAFT SLAB - 125mm THK, 30MPa


EJ
RC RAFT BEAM

175mm THK, 30MPa T.O.C. = 0 185

EJ
1800mm HIGH PERIMETER WALL
ON 750 x 230 dp STRIP FOOTING

T.O.C. = 0 100
RC RAFT BEAM 155mm RC RAFT SLAB

8920
RC RAFT BEAM 125mm THK, 30MPa
F 350 x 600mm dp, 30MPa
12995

STEP
350 x 700mm dp, 30MPa T.O.C. = 0 100
-
85mm
350 x 700mm dp, 30MPa

350 x 600mm dp, 30MPa


RC RAFT BEAM 85mm 85mm STEP
RC RAFT BEAM

STEP

RC RAFT BEAM
350 x 600mm dp, 30MPa STEP
0 11-11-'16 ISSUED FOR INFORMATION

EJ
350 x 600mm dp, 30MPa

EJ

RC RAFT BEAM
RC RAFT BEAM

NO. DATE AMENDMENT


350 x 600mm dp, 30MPa
85mm RC RAFT BEAM RC RAFT BEAM
STEP RC RAFT SLAB 350 x 700mm dp, 30MPa 350 x 700mm dp, 30MPa N Client
125mm THK, 30MPa

1855
T.O.C. = 0 185 SLOPE DOWN TO 155mm RC RAFT BEAM
T.O.C = 100mm RC RAFT BEAM
STEP 350 x 600mm dp, 30MPa

350 x 600mm dp, 30MPa


350 x 600mm dp, 30MPa
O

RC RAFT BEAM
C 1800mm HIGH PERIMETER WALL
EJ

EJ

1800mm HIGH PERIMETER WALL ON 750 x 230 dp STRIP FOOTING


RC BASE RC BASE RC BASE RC BASE

3600
ON 750 x 250 dp STRIP FOOTING
2866

300mm THICK 2320 x 1000 x 700mm dp 2320 x 1000 x 700mm dp 2320 x 1000 x 700mm dp 2320 x 1000 x 700mm dp
RC WALL 2320 2320 2320 2320
85mm RC RAFT BEAM 155mm
STEP 350 x 600mm dp, 30MPa STEP
D
1000

1000

1000

1000

1000

P
RC RAFT BEAM STEEL COLUMN Consultant
EJ

350 x 700mm dp, 30MPa 203 x 203 x 46 H-SECTION


EJ

155mm
RC RAFT SLAB
STEP
125mm THK, 30MPa
STEEL COLUMN STEEL COLUMN STEEL COLUMN STEEL COLUMN T.O.C. = 0 030
STEEL COLUMN 280 x 280mm
203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION 203 x 203 x 46 H-SECTION
RC COLUMN
230 x 230mm Tel: +27(0) 861 878 252
BRICK COLUMN
www.csmeng.co.za
E
- Discipline
STRUCTURAL
Project

GROUND FLOOR - RC FOUNDATION LAYOUT EKURHULENI: KATLEHONG


SCALE 1 : 100 FIRE STATION

Drawing title
GROUND FLOOR
RC FOUNDATIONS
LAYOUT & SECTIONS
Signed by

Engineer:
S.A. Engelbrecht Reg. no:20140036
Date Designed
NOVEMBER 2016 DV
Size Drawn
A0 JS
Scale Checked
- SE
Building Occupancy Climate Zone
- -
Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 01 00
FOR:
INFORMATION
GENERAL NOTES
1. Drawings to be read in conjunction with all relevant Architect's,
Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site.
Any discrepancies must be brought to the engineer's attention
prior to construction.
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in
accordance with the relevant provisions of
“The Application of the National Building Regulations”
(SANS 10400), Building Standards act (Act103)
and the relevant parts of SABS 1200.
5. The works will be inspected form time to time by the
consulting engineer to ascertain that the contractor is carrying

01 02 03 out the work in general conformity with the engineering


drawings and documents.
Such inspections are not for the contractors benefit and do not
relieve him of the responsibility for the proper construction
of the works in accordance with the engineering drawings,
3000 6000 documents and good building practice.
6. The signed original copy of this drawing is kept at the
engineer's office.

4473

B RC RING BEAM
280 x 450mm dp, 30MPa 70x70x6 ∠ RUNNERS
13 14 15 16 17 18 19 20

685 2000 6850 1900 2600 6450 1750


RC RING BEAM
280 x 450mm dp, 30MPa
E E
280 x 450mm dp, 30MPa

TRUSS TYPE 01
TRUSS TYPE 12

TRUSS TYPE 12

TRUSS TYPE 12
100x100x3.0
RC RING BEAM
12995

SHS POST

70x70x6 ∠ RUNNERS

4800

4800
70x70x6 ∠ RUNNERS
TRUSS TYPE 01

280 x 450mm dp, 30MPa STEEL PURLINS


150 x 75 x 20 x 3.0mm CFLC RC RING BEAM RC RING BEAM
RC RING BEAM

@ 1500mm c/c MAX. 280 x 450mm dp, 30MPa 280 x 450mm dp, 30MPa
G TRUSS TYPE 02
G
TRUSS TYPE 07

1720

1720
H H

280 x 450mm dp, 30MPa


TRUSS TYPE 08 TRUSS TYPE 02

RC RING BEAM
C

5375

5375
300mm THICK
3005

RC WALL TRUSS TYPE 08 TRUSS TYPE 03

RC RING BEAM
280 x 450mm dp, 30MPa
D 50x50x3 ∠ VERTICAL CROSS BRACING

J TRUSS TYPE 08 TRUSS TYPE 02 J


50x50x3 ∠ CROSS BRACING

280 x 450mm dp, 30MPa


6440

6440
RC RING BEAM
TRUSS TYPE 05
UPPER EAVES LEVEL - RC BEAM LAYOUT TRUSS TYPE 08

SCALE 1 : 100
50x50x3 ∠ CROSS BRACING

280 x 450mm dp, 30MPa


RC RING BEAM
H TRUSS TYPE 08 TRUSS TYPE 04
195x195x6.0 SHS POST
-
K RAFTER TYPE 01 K
01 02 03 04 05 06 07 08 09 10 11 12 TRUSS TYPE 08 TRUSS TYPE 06

280 x 450mm dp, 30MPa

280 x 450mm dp, 30MPa


RC RING BEAM

RC RING BEAM
3000 6000 685 4680 1320 4679 1320 4680 1320 4680 1320 50x50x3 ∠ VERTICAL CROSS BRACING 195x195x6.0 SHS POST
STEEL PURLIN RAFTER TYPE 01
75 x 50 x 20 x 3.0mm CFLC

TRUSS TYPE 08 TRUSS TYPE 02

280 x 450mm dp, 30MPa


70x70x6 ∠ RUNNER STEEL HORIZONTAL STEEL HORIZONTAL
RC RING BEAM CROSS-BRACING CROSS-BRACING

RC RING BEAM
280 x 450mm dp, 30MPa 50 x 50 x 3mm ∠ 50 x 50 x 3mm ∠
A
21 22 23 24
280 x 450mm dp, 30MPa

280 x 450mm dp, 30MPa

TRUSS TYPE 11
RC RING BEAM

RC RING BEAM

TRUSS TYPE 08 TRUSS TYPE 03


TRUSS TYPE 11 2000 6880 3780
4473

K
TRUSS TYPE 11 -
RC RING BEAM
TRUSS TYPE 08 280 x 450mm dp, 30MPa TRUSS TYPE 03
TRUSS TYPE 11
B RC RING BEAM , 30MPa
50x50x3 ∠ CROSS BRACING 280 x 450mm dp, 30MPa STEEL HORIZONTAL 170mm RC FLAT SLAB 280 x 305mm dp
CROSS-BRACING
G o/a US BEAM

-
50 x 50 x 3mm ∠
RC RING BEAM
M
280 x 450mm dp, 30MPa

a
MP
280 x 305mm dp
o/a US BEAM

30
STEEL HORIZONTAL

280 x 450mm dp, 30MPa

B,
280 x 450mm dp, 30MPa
CROSS-BRACING

280 x 305mm dp
LA
50 x 50 x 3mm ∠

TS
RC RING BEAM

o/a US BEAM
RC RING BEAM

A
FL
a

0 11-11-'16 ISSUED FOR INFORMATION

TRUSS TYPE 09

TRUSS TYPE 10
MP

TRUSS TYPE 09

TRUSS TYPE 09

TRUSS TYPE 09

TRUSS TYPE 09

TRUSS TYPE 09

TRUSS TYPE 09

TRUSS TYPE 09

RC

8920
30

280 x 450mm dp, 30MPa

100x100x3.0
12995

m
NO. DATE AMENDMENT
B,

0m
280 x 450mm dp, 30MPa

SHS POST
A

RC RING BEAM
SL

17
RC RING BEAM

Client
U
SIT
IN-

280 x 305mm dp
RC

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

TYPICAL TRUSS

o/a US BEAM
mm

280 x 450mm dp, 30MPa


170

RC RING BEAM
N

1855
RC RING BEAM
280 x 450mm dp, 30MPa
O
85mm STEP

C Pa
Consultant

30M 50x50x3 ∠ CROSS BRACING


B ,

3600
A
SL 300mm THICK J
2866

RAFTER TYPE 02

RAFTER TYPE 02

RAFTER TYPE 02

RAFTER TYPE 02

RAFTER TYPE 02
TU

Pa
SI RC WALL
IN- - 70x70x6 ∠ RUNNERS

280 x 305mm dp

0M
RC

o/a US BEAM

280 x 305mm dp
,3
m
0m

o/a US BEAM
50x50x3 ∠ VERTICAL CROSS BRACING

AB
17
D P

SL
AT
RC RING BEAM

FL
280 x 450mm dp, 30MPa Tel: +27(0) 861 878 252

RC
www.csmeng.co.za

m
0m
17
RC RING BEAM Discipline
280 x 450mm dp, 30MPa STRUCTURAL
280 x 305mm dp
o/a US BEAM Project

EKURHULENI: KATLEHONG
FIRE STATION

Drawing title
EAVES LEVELS RC
H STEEL PURLINS AND STEELWORK
150 x 75 x 20 x 3.0mm CFLC LAYOUT
- @ 1500mm c/c MAX.
EAVES LEVEL - RC & STEEL LAYOUT Signed by

SCALE 1 : 100
Engineer:
S.A. Engelbrecht Reg. no:20140036
Date Designed
NOVEMBER 2016 DV
Size Drawn
A0 JS
Scale Checked
- SE
Building Occupancy Climate Zone
- -
Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 02 00
FOR:
INFORMATION
GENERAL NOTES
1. Drawings to be read in conjunction with all relevant Architect's,
STIFFENERS TO BE PLACED IN ALL 230mm Consultant's, and Specialist's drawings and specifications.
AND 110mm THICK MASONRY WALLS, 2. All details and dimensions subject to confirmation on site.
WHICH DO NOT SUPPORT THE RING BEAM, Any discrepancies must be brought to the engineer's attention
AT A MAXIMUM SPACING OF 6m c/c. prior to construction.
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in
accordance with the relevant provisions of
200 100 “The Application of the National Building Regulations”
TOC
(SANS 10400), Building Standards act (Act103)
0.185 TOC 2615 1200 and the relevant parts of SABS 1200.
125mm RC GROUND SLAB, 30MPa 0.100 5. The works will be inspected form time to time by the
FILLET WELD FILLET WELD

85
consulting engineer to ascertain that the contractor is carrying
125

125mm RC GROUND SLAB, 30MPa


out the work in general conformity with the engineering

85
125
drawings and documents.
Such inspections are not for the contractors benefit and do not

600
relieve him of the responsibility for the proper construction

515

415
of the works in accordance with the engineering drawings,
250µ DPC LAYER documents and good building practice.
6. The signed original copy of this drawing is kept at the
100 450 350 2065 350 R8 BARS - 500mm R8 BARS - 500mm engineer's office.
SOIL MATTRESS AS TOC LONG @ 510mm c/c LONG @ 510mm c/c

510
PER CIVIL ENGINEER NGL 0.100
SPECIFICATION 350 x 515mm dp 350 0.000 175mm RC GROUND SLAB, 30MPa
350 350 x 600mm dp 300
RAFT BEAM, 30MPa RAFT BEAM, 30MPa
50mm BLINDING LAYER
15MPa

700

510
600
SECTION A - A

3200

3200
SCALE 1:20
SOIL MATTRESS AS
PER CIVIL ENGINEER 200x10.0mm THICK 100x18.0mm THICK
250µ DPC LAYER
SPECIFICATION STIFFENER PLATE STIFFENER PLATE

TOC TOC
SECTION E - E FILLET WELD FILLET WELD
SCALE 1:20
0.185 0.185
TOC
0.030
125

125
155

200x150x12.0mm 150x100x18.0mm
THICK PLATE THICK PLATE
600

600

125mm RC SLAB,
30MPa
50mm BLINDING LAYER 4 No. M12 CHEMICAL ANCHORS 4 No. M12 CHEMICAL ANCHORS
250µ DPC LAYER 15MPa INSTALLED IN ACCORDANCE INSTALLED IN ACCORDANCE
WITH THE MANUFACTURER'S WITH THE MANUFACTURER'S
350 920 350 350 x 600mm dp INSTRUCTIONS INSTRUCTIONS
SOIL MATTRESS AS
350 x 600mm dp
RAFT BEAM, 30MPa 230mm WALL STIFFENER 110mm WALL STIFFENER
PER CIVIL ENGINEER
SPECIFICATION
RAFT BEAM, 30MPa PLATE DETAILS PLATE DETAILS
SCALE 1:20 SCALE 1:20
SECTION B - B EXPANSION JOINT (EJ)
SCALE 1:20 20mm JOINTEX PRIMED AND SEALED
WITH POLYURETHANE SEALANT
TOC
0.185 TOC
125mm RC GROUND SLAB, 30MPa 0.100

85
125
175mm RC GROUND SLAB, 30MPa

175
600
TOC
10 80
0.185

700
SOIL MATTRESS AS

30 40 10

30 35 15
125

155

PER CIVIL ENGINEER

80

80
SPECIFICATION 6mm FILLET WELD
250µ DPC LAYER
250µ DPC LAYER
COMPACTED MATERIAL 14mm diam HOLE
415

(REFER TO SPECIAL NOTES) COMPACTED MATERIAL SLOTTED TO 20mm


125mm RC SLAB, (REFER TO SPECIAL NOTES)
30MPa SOIL MATTRESS AS 350 x 600mm dp 350 350
PER CIVIL ENGINEER RAFT BEAM, 30MPa 350 x 700mm dp 14mm diam HOLE
250µ DPC LAYER SPECIFICATION RAFT BEAM, 30MPa
300 x 415mm dp
SECTION F - F
RAFT BEAM, 30MPa SCALE 1:20
350 900 300
350 x 600mm dp 150
50mm BLINDING LAYER
RAFT BEAM, 30MPa 15MPa

SECTION C - C
SCALE 1:20

280 1653 280


TOC
3.035

TOC

280
TOC 2.755

450
145 170 135 205

3.035 TOC
TOC
SLAB US BEAM BEHIND 2.585

170
2.900
EXPANSION JOINT (EJ) 35 35 10 50 30
20mm JOINTEX PRIMED AND SEALED
80
450

WITH POLYURETHANE SEALANT TOC 150


TOC
TOC 0.185 2.585
1702
0.100 125mm RC GROUND SLAB, 30MPa
85

125

175mm RC GROUND SLAB, 30MPa


280
175

TOP AND BOTTOM PLATE STIFFENER


600

SECTION J - J 230
CONNECTION CLEAT DETAILS
SECTION K - K
700

SOIL MATTRESS AS SCALE 1:20 SCALE 1:5


PER CIVIL ENGINEER SCALE 1:20 280x450mm DP RC RING BEAM
SPECIFICATION
250µ DPC LAYER
250µ DPC LAYER
COMPACTED MATERIAL 100mm LONG,10mm DIAM STUD WELDED TO
(REFER TO SPECIAL NOTES) PLATE AND CAST INTO RING BEAM
350 350
350 x 700mm dp 350 x 600mm dp
RAFT BEAM, 30MPa RAFT BEAM, 30MPa
SECTION D - D SLIP JOINT WITH STUD PUNCHED THROUGH JOINT
SCALE 1:20
120x30x10mm PLATE

0 11-11-'16 ISSUED FOR INFORMATION

Y20 BAR WELDED TO PLATE


NO. DATE AMENDMENT

Client

FISHTAIL ANCHOR

350
1520 COMPONENTS TO BE
GALVANISED FOR
280 x 450mm dp RC BEAM CORROSION PROTECTION
TOC 30MPa
280 x 450mm dp RC BEAM 2.905
145 170 135

30MPa 270 170mm RC IN-SITU SLAB, 30MPa


450

450
151

280 Consultant
280
17
0

280
50
ANCHORS TO BE PROVIDED IN ALL
LOAD BEARING MASONRY WALLS
BELOW RING BEAMS AT INTERVALS Tel: +27(0) 861 878 252
170mm RC LANDING SLAB, 30MPa
NOT EXCEEDING 1.5m c/c
www.csmeng.co.za
FISHTAIL ANCHOR
2405

Discipline

270
STRUCTURAL
Y20 BAR WELDED TO PLATE
Project

EKURHULENI: KATLEHONG
151
0
17

120x30x10mm PLATE
FIRE STATION
EXPANSION JOINT (EJ)
20mm JOINTEX PRIMED AND SEALED
WITH POLYURETHANE SEALANT
1200 M8 CONCRETE ANCHOR INSTALLED Drawing title
TOC IN ACCORDANCE WITH THE
TOC
GROUND FLOOR
0.185 MANUFACTURER'S INSTRUCTIONS
FINISH TO ARCHITECT'S 125mm RC GROUND SLAB, 30MPa 125mm RC GROUND SLAB, 30MPa 0.100 AND EAVES LEVEL SECTIONS
85
125

125

SPECIFICATION 175mm RC GROUND SLAB, 30MPa


155

Signed by
175
600

600

25 75
700

Engineer:
200 x 250mm dp 20
1 LAYER MESH REF. 500 PLATFORM AS 1 LAYER MESH REF. 500 S.A. Engelbrecht Reg. no:20140036
EDGE THICKENING PER CIVIL ENGINEER Date Designed
TOP & BOTTOM TOP & BOTTOM
SPECIFICATION OF NOVEMBER 2016 DV
250µ DPC LAYER "REFER TO TYPICAL DETAIL" 250µ DPC LAYER Size Drawn
300
50mm BLINDING LAYER
350 x 600mm dp
SOIL MATERIAL AS PER
250µ DPC LAYER
TYPICAL BRICK WALL A0 JS
RAFT BEAM, 30MPa 350 SOIL MATERIAL AS PER Scale Checked
15MPa CIVIL ENGINEER'S SPEC.
SECTION G - G CIVIL ENGINEER'S SPEC. ANCHORING DETAIL - SE
350 x 600mm dp 350 350 Building Occupancy Climate Zone
SCALE 1:5
SCALE 1:20 RAFT BEAM, 30MPa 350 x 700mm dp - -
RAFT BEAM, 30MPa Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 03 00
FOR:
INFORMATION
GENERAL NOTES
1. Drawings to be read in conjunction with all relevant Architect's,
Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site.
Any discrepancies must be brought to the engineer's attention
prior to construction.
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in
accordance with the relevant provisions of
“The Application of the National Building Regulations”
1899 (SANS 10400), Building Standards act (Act103)

05 and the relevant parts of SABS 1200.


5. The works will be inspected form time to time by the
consulting engineer to ascertain that the contractor is carrying
out the work in general conformity with the engineering
1913 DETAIL 03 drawings and documents.
Such inspections are not for the contractors benefit and do not
relieve him of the responsibility for the proper construction
of the works in accordance with the engineering drawings,
1500mm documents and good building practice.
c/c MAX.
6. The signed original copy of this drawing is kept at the
engineer's office.

17931

STEEL PURLINS
150 x 75 x 20 x 3.0mm CFLC
@ 1500mm c/c MAX. 01
STEEL TR
406 x 178 USS
STEEL PURLIN STEEL PURLINS FOR CLADDING x 54 I-SE
CTION
300 x 75 x 20 x 3.0mm CFLC 150 x 75 x 20 x 3.0mm CFLC
@ 750mm c/c MAX.
STEEL PURLIN FOR CLADDING

2281
STEEL PURLIN
250 x 75 x 20 x 3.0mm CFLC 150 x 75 x 20 x 3.0mm CFLC

STEEL PURLIN STEEL PURLINS


200 x 75 x 20 x 3.0mm CFLC 150 x 75 x 20 x 3.0mm CFLC
@ 1500mm c/c MAX.
STEEL PURLIN STEEL PURLIN
100 x 75 x 20 x 3.0mm CFLC 75 x 50 x 20 x 3.0mm CFLC
STEEL TR

406 x 178 USS


x 54 I-SEC
TION

STEEL BEAM STEEL BEAM STEEL BEAM


406 x 178 x 54 I-SECTION 406 x 178 x 54 I-SECTION 406 x 178 x 54 I-SECTION

STEEL PURLIN DETAIL 04

450

450
150 x 75 x 20 x 3.0mm CFLC DETAIL 02

STEEL PURLIN
125 x 75 x 20 x 3.0mm CFLC

1200 3699 17797 3699 1200

203 x 203 x 46 H-SECTION


203 x 203 x 46 H-SECTION

STEEL COLUMN
STEEL COLUMN
5734

DETAIL 01 DETAIL 01

TOC TOC TOC RC BASE F01


NGL 100 450 350 0.100 0.100 0.100 2320 x 1000 x 700mm dp 350 450 100 NGL
0.000 175mm RC GROUND SLAB, 30MPa 175mm RC GROUND SLAB, 30MPa 175mm RC GROUND SLAB, 30MPa 0.000
175

175

175
700

700

700

700
250µ DPC LAYER 50mm BLINDING LAYER 50mm BLINDING LAYER 50mm BLINDING LAYER 250µ DPC LAYER
350 x 700mm dp 15MPa 350 x 700mm dp 15MPa 15MPa
350 x 700mm dp
1000 RC BASE F01 RAFT BEAM, 30MPa RAFT BEAM, 30MPa RAFT BEAM, 30MPa
350 350 350 1000
2320 x 1000 x 700mm dp SOIL MATERIAL AS PER
CIVIL ENGINEER'S SPEC.

SOIL MATERIAL AS PER


CIVIL ENGINEER'S SPEC.
SECTION F - F
SCALE 1:25

0 11-11-'16 ISSUED FOR INFORMATION

NO. DATE AMENDMENT

Client

STIFFENER PLATE
181 x 97 x 8mm
6mm FILLET WELD
6mm FILLET WELD (WAR)
ALONG EDGES OF STIFFENER PLATE
EXCEPT ON CHAMFERS
STEEL COLUMN STIFFENER PLATE
203 x 203 x 46 H-SECTION 181 x 97 x 8mm
6mm FILLET WELD (WAR)
6mm FILLET WELD
6mm FILLET WELD (WAR)
ALONG EDGES OF STIFFENER PLATE
7° SLOPE EXCEPT ON CHAMFERS Consultant
BASE PLATE
250 x 250 x 20mm
STEEL TR
406 x 178 USS
x 54 I-SEC 7° SLOPE
TION
4No. M16 ANCHORS STEEL TR
406 x 178 USS
x 54 I-SE
CTION STEEL TR
END PLATES 6mm FILLET WELD (WAR) USS
203 x 203 x 46 H-SECTION

406 x 178
x 54 I-SEC
350

70 x 70 x 10mm FOR EACH ANCHOR TION Tel: +27(0) 861 878 252
STEEL COLUMN

6mm FILLET WELD (WAR) www.csmeng.co.za

462
STEEL BEAM STEEL BEAM 82 15
406 x 178 x 54 I-SECTION 406 x 178 x 54 I-SECTION
Discipline
6mm FILLET WELD (WAR) STRUCTURAL

151 15
6mm FILLET WELD (WAR) 6mm FILLET WELD (WAR)

181
Project

DETAIL 01

15

203 x 203 x 46 H-SECTION


SCALE 1:10 EKURHULENI: KATLEHONG
203 x 203 x 46 H-SECTION

97 STEEL BEAM STEEL BEAM

STEEL COLUMN
406 x 178 x 54 I-SECTION 406 x 178 x 54 I-SECTION FIRE STATION
STEEL COLUMN

250 STIFFENER PLATE DETAIL 6mm FILLET WELD (WAR)


80 90 80 DETAIL 03 SCALE 1:10
6mm FILLET WELD (WAR)
Drawing title

SCALE 1:10 FOUNDATIONS LAYOUT


35

& SECTIONS
250
180

Signed by
35

18mm Ø HOLES Engineer:

DETAIL 01 DETAIL 02 Date


S.A. Engelbrecht
Designed
Reg. no:20140036

NOVEMBER 2016 DV
SECTION SCALE 1:10 DETAIL 03 Size Drawn
SCALE 1:10
SECTION DETAIL 04 Scale
A0
Checked
JS

SCALE 1:10 SCALE 1:10 - SE


Building Occupancy Climate Zone
- -
Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 04 00
FOR:
INFORMATION
N.G.L. = 0 000
STEEL PURLINS
150 x 50 x 20 x 3.0mm CFLC
RC RAFT BEAM STIFFENER PLATE @ 1500mm c/c MAX.
1200 300 x 700mm dp, 30MPa 382 x 80 x 8mm 6mm FILLET WELD (WAR)
RC RAFT SLAB 6mm FILLET WELD
175mm THK, 30MPa ALONG EDGES OF STIFFENER PLATE
c/c MAX.
T.O.C. = 0 100 EXCEPT ON CHAMFERS 1500mm
STEEL COLUMN
406 x 178 x 67 I-SECTION
RC RAFT BEAM USS
STEEL TR

350 x 700mm dp, 30MPa


6mm FILLET WELD (WAR)
CTION

350 x 700mm dp, 30MPa


x 54 I-SE

1483

1483
350 x 700mm dp, 30MPa
17 7° SLOPE 406 x 178

RC RAFT BEAM
DETAIL 03
BASE PLATE

RC RAFT BEAM

750

750
450 x 220 x 20mm
USS
STEEL TR TION
750
RC RAFT SLAB
750 06 x 1 7 8 x 54 I-SEC
175mm THK, 30MPa 4
4No. M16 ANCHORS
1500 T.O.C. = 0 100 1293

85mm STEP
DETAIL 04

350 x 700mm dp, 30MPa


END PLATES STEEL SIDE CLADDING PURLINS
150 x 50 x 20 x 2.0mm CFLC

350
RC RAFT BEAM

1200mm c/c MAX.


70 x 70 x 10mm FOR EACH ANCHOR
STEEL SIDE CLADDING PURLINS @ 1200mm c/c MAX.

406 x 178 x 54 I-SECTION


350 x 785mm dp, 30MPa
150 x 50 x 20 x 2.0mm CFLC
5000

STEEL COLUMN STEEL COLUMN @ 1200mm c/c MAX.

STEEL COLUMN
RC RAFT BEAM
406 x 178 x 54 I-SECTION 406 x 178 x 54 I-SECTION
300 x 700mm dp, 30MPa

RC RAFT SLAB
RC RAFT BEAM

175mm THK, 30MPa


T.O.C. = 0 185
1293 DETAIL 01

406 x 178 x 54 I-SECTION


750 SCALE 1:10

STEEL COLUMN
RC RAFT BEAM RC RAFT BEAM

750

750
350 x 785mm dp, 30MPa 350 x 700mm dp, 30MPa

1500

1500
16 B 750
B 450

750
- -

175mm THK, 30MPa


80 290 80

RC RAFT SLAB

T.O.C. = 0 100

35
400 x 220 x 85mm

7567
750 750
CONCRETE SCREED INFILL DETAIL 04

406 x 178 x 54 I-SECTION


220
150
1500 AT COLUMN BASE PLATE
175mm THK, 30MPa

350 x 785mm dp, 30MPa

SCALE 1:10
350 x 785mm dp, 30MPa

350 x 700mm dp, 30MPa


RC RAFT SLAB

T.O.C. = 0 100

STEEL COLUMN
N.G.L. = 0 000
STEEL BEAM
RC RAFT BEAM
N.G.L. = 0 000

35

6666
RC RAFT BEAM

RC RAFT BEAM
RC RAFT SLAB 254 x 146 x 31 I-SECTION
175mm THK, 30MPa
18mm Ø HOLES
16365

T.O.C. = 0 100
5000

DETAIL 01 6mm FILLET WELD (WAR)


SECTION
SCALE 1:10

406 x 178 x 54 I-SECTION


85mm STEP
RC RAFT BEAM RC RAFT BEAM STEEL RAFTERS
350 x 785mm dp, 30MPa 350 x 700mm dp, 30MPa 150 x 50 x 20 x 2.0mm CFLC

STEEL COLUMN
@ 900mm c/c MAX.
902

902

300 x 700mm dp, 30MPa


1652

1652

RC RAFT BEAM
15
750

750

750

750 750 750


1217 1500 1293
A A
350 x 700mm dp, 30MPa

350 x 700mm dp, 30MPa

350 x 700mm dp, 30MPa

400 x 220 x 85mm


RC RAFT BEAM

RC RAFT BEAM

RC RAFT BEAM

- STEEL COLUMN
406 x 178 x 54 I-SECTION
- DETAIL 02 CONCRETE SCREED INFILL
AT COLUMN BASE PLATE
STEEL COLUMN SCALE 1:10
5000

406 x 178 x 54 I-SECTION DETAIL 01 400


1200 3195 7305 1200
TOC
STEEL COLUMN 1 LAYER MESH REF. 500
FINISH TO ARCHITECT'S TOC 0.185 TOC DETAIL 01
406 x 178 x 54 I-SECTION 0.100 TOP & BOTTOM 0.100
SPECIFICATION

85

85
1217 1500 RC RAFT SLAB 1293 175mm RC GROUND SLAB, 30MPa

175

175
750 750 175mm THK, 30MPa 750
T.O.C. = 0 100

785

785
700

700

700

700
525

525
6534 250µ DPC LAYER
750

750

750
1378

1378

RC RAFT BEAM
14 350 x 700mm dp, 30MPa
300 x 700mm dp SOIL MATERIAL AS PER 1293 x 700mm dp
STEEL TRUSS 350 x 785mm dp 1500 x 700/785mm dp
RAFT BEAM, 30MPa CIVIL ENGINEER'S SPEC. RAFT BASE, 30MPa
406 x 178 x 54 I-SECTION 300 350 RAFT BEAM, 30MPa 1500 1293 300
RAFT BASE, 30MPa
RC RAFT SLAB SECTION B - B
175mm THK, 30MPa
1200

SCALE 1:25
T.O.C. = 0 100
RC RAFT BEAM
300 x 700mm dp, 30MPa STEEL COLUMN
406 x 178 x 54 I-SECTION
2877 6940
STEEL RAFTERS
N.G.L. = 0 000 150 x 50 x 20 x 2.0mm CFLC
1200
X V 10500
W 1200
@ 900mm c/c MAX.

SAG BAR 2440


WASH BAY - RC FOUNDATION LAYOUT

5000
50 x 50 x 3mm ∠
SCALE 1 : 50 STEEL COLUMN STEEL PURLINS
406 x 178 x 54 I-SECTION 150 x 50 x 20 x 3.0mm CFLC
@ 1500mm c/c MAX.

STIFFENER PLATE c/c MAX.


382 x 80 x 8mm 1500mm
STEEL RAFTERS
6mm FILLET WELD
150 x 50 x 20 x 2.0mm CFLC
ALONG EDGES OF STIFFENER PLATE
@ 900mm c/c MAX. USS
EXCEPT ON CHAMFERS STEEL TRUSS WATER TANK STEEL TR CTION
x 54 I-SE
406 x 178 x 54 I-SECTION 406 x 178 DETAIL 03
B B
- -
7° SLOPE
STEEL PURLINS DETAIL 04
STEEL SIDE CLADDING PURLINS

3660
150 x 50 x 20 x 3.0mm CFLC 150 x 50 x 20 x 2.0mm CFLC

1200mm c/c MAX.


STEEL SIDE CLADDING PURLINS @ 1200mm c/c MAX.
USS
STEEL TR CTION 150 x 50 x 20 x 2.0mm CFLC
x 54 I-SE
406 x 178 x 54 I-SECTION

406 x 178 SAG BAR @ 1200mm c/c MAX.

5000
50 x 50 x 3mm ∠
STEEL COLUMN

6mm FILLET WELD (WAR)

STEEL VERTICAL
15 65 CROSS-BRACING
60 x 60 x 4mm ∠ STEEL COLUMN
15

406 x 178 x 54 I-SECTION STEEL COLUMN


STEEL COLUMN 1131 1131 383
406 x 178 x 54 I-SECTION
406 x 178 x 54 I-SECTION STEEL TRUSS
STEEL BEAM
254 x 146 x 31 I-SECTION 406 x 178 x 54 I-SECTION
352

382

STEEL VERTICAL
STEEL BEAMS CROSS-BRACING
DETAIL 03 356 x 171 x 57 I-SECTION 60 x 60 x 4mm ∠ STEEL BEAMS

7567
SCALE 1:10 356 x 171 x 57 I-SECTION
15

STEEL BEAM
80 254 x 146 x 31 I-SECTION
A A

6666
STIFFENER PLATE DETAIL - - 2850
DETAIL 02
SCALE 1:10 SAG BAR
5146

5000

50 x 50 x 3mm ∠
STEEL HORIZONTAL
DETAIL 03 CROSS-BRACING
60 x 60 x 4mm ∠
SECTION

406 x 178 x 54 I-SECTION


STEEL COLUMN
406 x 178 x 54 I-SECTION
SCALE 1:10

406 x 178 x 54 I-SECTION


STEEL HORIZONTAL
GENERAL NOTES CROSS-BRACING

STEEL COLUMN

STEEL COLUMN
1. Drawings to be read in conjunction with all relevant Architect's, 60 x 60 x 4mm ∠
Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site. STEEL VERTICAL
3693

Any discrepancies must be brought to the engineer's attention CROSS-BRACING


prior to construction. 60 x 60 x 4mm ∠
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in STEEL BEAM STEEL TRUSS
accordance with the relevant provisions of 254 x 146 x 31 I-SECTION 406 x 178 x 54 I-SECTION
“The Application of the National Building Regulations” STEEL COLUMN
(SANS 10400), Building Standards act (Act103) 406 x 178 x 54 I-SECTION 1131 1131 STEEL COLUMN STEEL COLUMN
and the relevant parts of SABS 1200. 406 x 178 x 54 I-SECTION 406 x 178 x 54 I-SECTION
5. The works will be inspected form time to time by the 2850 6940
consulting engineer to ascertain that the contractor is carrying
out the work in general conformity with the engineering
drawings and documents.
Such inspections are not for the contractors benefit and do not
relieve him of the responsibility for the proper construction
of the works in accordance with the engineering drawings,
documents and good building practice.
6. The signed original copy of this drawing is kept at the
engineer's office.
WASH BAY - STEELWORK LAYOUT 1200 2845 7655 1200
SCALE 1 : 50 TOC
FINISH TO ARCHITECT'S 1 LAYER MESH REF. 500
0.100
SPECIFICATION TOP & BOTTOM
Client Consultant Discipline Drawing title Date Designed 175mm RC GROUND SLAB, 30MPa
175

175
STRUCTURAL OCTOBER 2016 DV
Size Drawn
Project WASH BAY A0 JS
700

700

700

700

700
525
CONCRETE AND STEELWORK
525

Scale Checked
- SE
250µ DPC LAYER
LAYOUTS Building Occupancy Climate Zone
EKURHULENI: KATLEHONG - -

Tel: +27(0) 861 878 252 FIRE STATION Signed by Project #: Discipline: Stage: Drawing #: Rev:
300 x 700mm dp 350 x 700mm dp 350 x 700mm dp
SOIL MATERIAL AS PER
CIVIL ENGINEER'S SPEC.
RAFT BEAM, 30MPa 300 350 RAFT BEAM, 30MPa 350 RAFT BEAM, 30MPa 350 300
www.csmeng.co.za 0373107C S T 05 00
FOR:
SECTION A - A
Engineer:
INFORMATION SCALE 1:25
S.A. Engelbrecht Reg. no:20140036
GENERAL NOTES
1. Drawings to be read in conjunction with all relevant Architect's,
Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site.
Any discrepancies must be brought to the engineer's attention
STEEL PURLINS prior to construction.
100 x 75 x 20 x 2.5mm CFLC 3. Drawings are not to be scaled.
STEEL PURLINS NOTE: @ 2000mm c/c MAX. 4. All construction workmanship and materials to be in
100 x 75 x 20 x 2.5mm CFLC accordance with the relevant provisions of
1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL “The Application of the National Building Regulations”
@ 2000mm c/c MAX. 2000 c/c M
CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS AX. (SANS 10400), Building Standards act (Act103)
and the relevant parts of SABS 1200.
WITH 8mm FILLET WELD (WAR). 5. The works will be inspected form time to time by the
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED TOP CO consulting engineer to ascertain that the contractor is carrying
2000 c/c M RD
AX. BEFORE MANUFACTURING. IPE 140 U out the work in general conformity with the engineering
B
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES drawings and documents.

VERTICAL CORD
WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN. Such inspections are not for the contractors benefit and do not
RAFTER

VERTICAL CORD
relieve him of the responsibility for the proper construction
RD

60 x 60 x 4mm ∠
IPE 140 UB
IPE 200 U O of the works in accordance with the engineering drawings,
B C m∠

VERTICAL CORD
RD

60 x 60 x 4mm ∠
documents and good building practice.

VERTICAL CORD
L m O RD
NA x 4 ∠ 6. The signed original copy of this drawing is kept at the

450
C
m CO ∠

IPE 140 UB
O 0 L
A 4 m m engineer's office.
AG x 6 L
I
D 60 G ON 0 x O NA x 4m
RC RING BEAM, 30MPa 6
A
DI 0 x AG 60
280 x 450mm dp 6 DI 0 x
6
5294 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠
2 No. M16 BOLTS

STEEL COLUMN
195 x 195 x 6mm SHS
BOTTOM CORD STEEL RUNNER
IPE 160 UB 70 x 70 x 6mm ∠

450

450
1593 1453 1593
2 No. M16 HD BOLTS
STEEL RAFTER - TYPE 01 RC RING BEAM, 30MPa
280 x 450mm dp
RC RING BEAM, 30MPa
280 x 450mm dp
TYPICAL
SCALE 1:25 STEEL TRUSS - TYPE 01
NOTE: TYPICAL
1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL SCALE 1:25
CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
WITH 8mm FILLET WELD (WAR).
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
BEFORE MANUFACTURING. NOTE:
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES STEEL PURLINS
WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN. 100 x 75 x 20 x 2.5mm CFLC 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL
STEEL PURLINS @ 2000mm c/c MAX. CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
100 x 75 x 20 x 2.5mm CFLC WITH 8mm FILLET WELD (WAR).
@ 2000mm c/c MAX. 2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
BEFORE MANUFACTURING.
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
2000 c/c M WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.
AX.

VERTICAL CORD
.
2000 c/c MAX 70 x 70 x 6mm ∠ TOP CO

VERTICAL CORD
RD RD

IPE 140 UB
IPE 140 U
RAFTER CO ∠

VERTICAL CORD
IPE 140 UB
B

60 x 60 x 4mm ∠
L m
IPE 200 UB NA x 4m RD

IPE 140 UB

VERTICAL CORD
O CO ∠ RD

60 x 60 x 4mm ∠
AG 60

POST
DI 0 x CO ∠

VERTICAL CORD
L m
NA x 4m

60 x 60 x 4mm ∠
6 O AL m RD

VERTICAL CORD
AG 60 ON x 4m CO ∠

60 x 60 x 4mm ∠
DI 0 x G L ORD

VERTICAL CORD
I A
x6
0 NA m AL C ∠

60 x 60 x 4mm ∠
6 D GO x 4m N
60 IA O m
D x 60 DIAG 60 x 4m AL COR
D
60 60 x DIAGON 4mm ∠
x
60 x 60
450

450
5400
STEEL RUNNER BOTTOM CORD STEEL RUNNER STEEL RUNNER
RC RING BEAM, 30MPa STEEL RAFTER - TYPE 02 RC RING BEAM, 30MPa 70 x 70 x 6mm ∠ IPE 160 UB 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠

450

450

450
280 x 450mm dp 280 x 450mm dp RC RING BEAM, 30MPa RC RING BEAM, 30MPa
TYPICAL 280 x 450mm dp 280 x 450mm dp
SCALE 1:25 RC RING BEAM, 30MPa
2040 1788 1788 1788 1788 1788 1724 280 x 450mm dp

STEEL TRUSS - TYPE 02


TYPICAL
SCALE 1:25

NOTE:
NOTE:
STEEL PURLINS 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL
100 x 75 x 20 x 2.5mm CFLC 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
STEEL PURLINS
@ 2000mm c/c MAX. CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS WITH 8mm FILLET WELD (WAR).
100 x 75 x 20 x 2.5mm CFLC
WITH 8mm FILLET WELD (WAR). @ 2000mm c/c MAX. 2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED BEFORE MANUFACTURING.
BEFORE MANUFACTURING. 3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
2000 c/c M 3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.
A X. WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.

VERTICAL CORD
2000 c/c M

VERTICAL CORD
TOP CO AX.

IPE 140 UB

60 x 60 x 4mm ∠
RD
VERTICAL CORD

VERTICAL CORD

RD
60 x 60 x 4mm ∠

TOP COR IPE 140 U


RD D CO ∠

VERTICAL CORD
B
RD
IPE 140 UB

60 x 60 x 4mm ∠
CO ∠ IPE 140 U L
VERTICAL CORD

A mm

VERTICAL CORD
RD B CO ∠
60 x 60 x 4mm ∠

AL mm ON x 4

60 x 60 x 4mm ∠
CO ∠
VERTICAL CORD

ON x 4 G AL m D
60 x 60 x 4mm ∠

VERTICAL CORD
AL A
DI 0 x 6 ON x 4m OR

60 x 60 x 4mm ∠
G m RD L C m∠
VERTICAL CORD

0 G RD

450 VERTICAL CORD


A ON x 4 m CO ∠
DI 0 x 6 DIA x 60
60 x 60 x 4mm ∠

G L ORD
6
GO
A
N 4m A L CO ∠

VERTICAL CORD
6 DIA x 60 NA 4mm AL C ∠ 60 O N
DIA x 60 x

60 x 60 x 4mm ∠
m
GO DIAG 60 x 4m D

IPE 140 UB
60 DIA x 60 x O N
DIAG 60 x 4mm AL COR
AL COR
D 60 0 x DIAGON ∠
60 60 x DIAGON 4mm ∠ 6
60 x 60 x
4mm
x
60 x 60

STEEL RUNNER STEEL RUNNER BOTTOM CORD STEEL RUNNER


STEEL RUNNER STEEL RUNNER BOTTOM CORD STEEL RUNNER 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ IPE 160 UB 70 x 70 x 6mm ∠

450
70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ IPE 160 UB 70 x 70 x 6mm ∠
450

450
1928 1788 1788 1788 1893 2107
RC RING BEAM, 30MPa
RC RING BEAM, 30MPa
280 x 450mm dp RC RING BEAM, 30MPa RC RING BEAM, 30MPa
280 x 450mm dp
1928 1788 1788 1788 1788 1849 280 x 450mm dp STEEL TRUSS - TYPE 04 280 x 450mm dp

STEEL TRUSS - TYPE 03 TYPICAL


SCALE 1:25
TYPICAL
SCALE 1:25

NOTE:
STEEL PURLINS
100 x 75 x 20 x 2.5mm CFLC 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL
@ 2000mm c/c MAX. CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
WITH 8mm FILLET WELD (WAR).
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
BEFORE MANUFACTURING.
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
2000 c/c M WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.
VERTICAL CORD

AX.
70 x 70 x 6mm ∠ TOP CO
RD
IPE 140 UB

RD IPE 140 U
VERTICAL CORD

0 11-11-'16 ISSUED FOR INFORMATION


VERTICAL CORD

CO ∠ B
60 x 60 x 4mm ∠

L
IPE 140 UB

m RD
NA x 4m

VERTICAL CORD
O CO ∠ RD

60 x 60 x 4mm ∠
NO. DATE AMENDMENT
AG 60 L CO ∠

VERTICAL CORD
m
DI 0 x NA 4m

60 x 60 x 4mm ∠
O A L m
x RD

VERTICAL CORD
6 G 0 ON x 4m CO ∠

60 x 60 x 4mm ∠
A
DI 0 x 6 G
DIA x 60
L
NA 4mm ORD Client

VERTICAL CORD
6 GO N AL C ∠
60 DIA x 60 x O
DIAG 60 x 4m
m D
AL COR

IPE 140 UB
60 60 x DIAGON m ∠
4m
60 x 60 x

STEEL RUNNER STEEL RUNNER BOTTOM CORD STEEL RUNNER


70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ IPE 160 UB 70 x 70 x 6mm ∠

450
450

450

2040 1788 1788 1788 1788 1893 2107

RC RING BEAM, 30MPa


280 x 450mm dp
RC RING BEAM, 30MPa
280 x 450mm dp
STEEL TRUSS - TYPE 05 RC RING BEAM, 30MPa
280 x 450mm dp
TYPICAL Consultant

SCALE 1:25

NOTE:
Tel: +27(0) 861 878 252
STEEL PURLINS
100 x 75 x 20 x 2.5mm CFLC 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL www.csmeng.co.za
@ 2000mm c/c MAX. CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
WITH 8mm FILLET WELD (WAR).
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED Discipline
BEFORE MANUFACTURING. STRUCTURAL
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
2000 c/c M WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN. Project
AX.
70 x 70 x 6mm ∠ TOP CO
VERTICAL CORD

RD RD
VERTICAL CORD

IPE 140 U
CO ∠
VERTICAL CORD

B
IPE 140 UB

60 x 60 x 4mm ∠

L m EKURHULENI: KATLEHONG
IPE 140 UB

ONA x 4m RD
VERTICAL CORD

AG 60 CO ∠ RD
60 x 60 x 4mm ∠

DI 0 x L CO ∠
FIRE STATION
VERTICAL CORD

m
NA x 4m
60 x 60 x 4mm ∠

6 O AL mm D VERTICAL CORD
AG 0 N OR
DI 0 x 6 GO x 4 L C m∠ 60 x 60 x 4mm ∠

VERTICAL CORD
RD
6 DIA x 60 A
N 4m L CO ∠
60 GO O N A

IPE 140 UB
DIA x 60 x DIAG 60 x 4mm AL COR
D Drawing title
60 6 0 x DIAGON ∠
4mm
60 x 60 x EAVES LEVELS SECTIONS
1 OF 2
STEEL RUNNER BOTTOM CORD STEEL RUNNER STEEL RUNNER Signed by
70 x 70 x 6mm ∠ IPE 160 UB 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠

450
450

450

2040 1788 1788 1788 1788 1893 Engineer:


S.A. Engelbrecht Reg. no:20140036
RC RING BEAM, 30MPa
Date Designed
RC RING BEAM, 30MPa
280 x 450mm dp
RC RING BEAM, 30MPa
280 x 450mm dp
STEEL TRUSS - TYPE 06 280 x 450mm dp
NOVEMBER 2016 DV
Size Drawn
TYPICAL A0 JS

SCALE 1:25 Scale Checked


- SE
Building Occupancy Climate Zone
- -
Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 06 00
FOR:
INFORMATION
GENERAL NOTES
1. Drawings to be read in conjunction with all relevant Architect's,
Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site.
Any discrepancies must be brought to the engineer's attention
prior to construction.
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in
accordance with the relevant provisions of
“The Application of the National Building Regulations”
(SANS 10400), Building Standards act (Act103)
and the relevant parts of SABS 1200.
5. The works will be inspected form time to time by the
consulting engineer to ascertain that the contractor is carrying
out the work in general conformity with the engineering
drawings and documents.
NOTE: NOTE:
Such inspections are not for the contractors benefit and do not
relieve him of the responsibility for the proper construction
1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL of the works in accordance with the engineering drawings,
CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS documents and good building practice.
WITH 8mm FILLET WELD (WAR). WITH 8mm FILLET WELD (WAR). 6. The signed original copy of this drawing is kept at the
engineer's office.
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED 2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
BEFORE MANUFACTURING. BEFORE MANUFACTURING.
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES 3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN. WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.
STEEL PURLINS
100 x 75 x 20 x 2.5mm CFLC STEEL PURLINS
@ 2000mm c/c MAX. 100 x 75 x 20 x 2.5mm CFLC
@ 2000mm c/c MAX.

VERTICAL CORD
VERTICAL CORD
.
2000 c/c MAX

VERTICAL CORD
VERTICAL CORD
60 x 60 x 4mm ∠

VERTICAL CORD
60 x 60 x 4mm ∠
IPE 140 UB
TOP CORD TOP CORD

IPE 140 UB
.
DIAGON 2000 c/c MAX DIAG

IPE 140 UB
IPE 140 UB AL O
60 x 60 x CORD IPE 140 UB 60 x NAL CO
4mm ∠ DIAGON 60 x R
AL COR
D 4mm D
60 x 60 ∠
x 4mm ∠

STEEL RUNNER BOTTOM CORD STEEL RUNNER


70 x 70 x 6mm ∠ IPE 160 UB
450

450
70 x 70 x 6mm ∠ STEEL RUNNER BOTTOM CORD STEEL RUNNER
RC RING BEAM, 30MPa 70 x 70 x 6mm ∠ IPE 160 UB

450

450
450
70 x 70 x 6mm ∠
280 x 450mm dp
RC RING BEAM, 30MPa RC RING BEAM, 30MPa
RC RING BEAM, 30MPa 4209 2632 RC RING BEAM, 30MPa 280 x 450mm dp 280 x 450mm dp
280 x 450mm dp 280 x 450mm dp
4209 2492 2040
STEEL TRUSS - TYPE 07
TYPICAL STEEL TRUSS - TYPE 08
SCALE 1:25
TYPICAL
SCALE 1:25

NOTE:
NOTE: 1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL
CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL WITH 8mm FILLET WELD (WAR).
CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS 2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
WITH 8mm FILLET WELD (WAR). BEFORE MANUFACTURING.
STEEL PURLINS
100 x 75 x 20 x 2.5mm CFLC 2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED 3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
BEFORE MANUFACTURING. WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.
@ 2000mm c/c MAX.
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES STEEL PURLINS
WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN. 100 x 75 x 20 x 2.5mm CFLC
@ 2000mm c/c MAX.

2000 c/c M
TOP CO AX.
RD 2000 c/c M
IPE 140 U
VERTICAL CORD

B AX.
TOP CO
RD

VERTICAL CORD
IPE 140 UB

m RD

IPE 140 U
RD B

IPE 140 UB
4m CO

CO ∠

RD

VERTICAL CORD
VERTICAL CORD

VERTICAL CORD

60 x 60 x 4mm ∠
60 x 60 x 4mm ∠

L m
CO ∠
60 x 60 x 4mm ∠

NA x 4m
60 L

RD

VERTICAL CORD
RD

VERTICAL CORD
VERTICAL CORD
x NA

60 x 60 x 4mm ∠
m O

60 x 60 x 4mm ∠
60 x 60 x 4mm ∠

VERTICAL CORD
AL 4m CO ∠ CO ∠
x

RD AG 60
60 GO

N DI 0 x L ORD
VERTICAL CORD

x L m NA m
O 0 CO ∠ L C ∠
60 x 60 x 4mm ∠
NA x 4m GO 0 x 4m

IPE 140 UB
A

AG 6 L 6 N A
DI

O m IA GO mm

VERTICAL CORD
DI 0 x AG 60 NA 4m D x6 DIA 60 x 4

60 x 60 x 4mm ∠
O D
DI 0 x OR 60

VERTICAL CORD
6 G 0 x x
DIA 0 x 6
C 60
6 AL m∠
ON x 4m

IPE 140 UB
6 G
DIA x 60
60
STEEL RUNNER BOTTOM CORD STEEL RUNNER
RC RING BEAM
IPE 160 UB

450
70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠

450
280 x 450mm dp, 30MPa
1492 1833 1833 958
STEEL RUNNER STEEL RUNNER BOTTOM CORD STEEL RUNNER
70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ IPE 160 UB 70 x 70 x 6mm ∠ RC RING BEAM, 30MPa
450

450
170mm RC SLAB, 30MPa RC RING BEAM, 30MPa 280 x 450mm dp
280 x 450mm dp
1509 1833 1833 1833 1833 2100

STEEL TRUSS - TYPE 09 STEEL TRUSS - TYPE 10


TYPICAL TYPICAL
SCALE 1:25
SCALE 1:25

NOTE:

1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL


CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS
WITH 8mm FILLET WELD (WAR).
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
BEFORE MANUFACTURING.
STEEL PURLINS
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
100 x 75 x 20 x 2.5mm CFLC
WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.
@ 2000mm c/c MAX.

AX.
2000 c/c M

VERTICAL CORD
RD
TOP CO

IPE 140 UB
B
IPE 140 U

VERTICAL CORD
60 x 60 x 4mm ∠
DI
A

VERTICAL CORD
60 GON

60 x 60 x 4mm ∠
DIA

VERTICAL CORD
G x 6 AL

60 x 60 x 4mm ∠
60 ONAL 0x C
DIAG x6 4m OR

VERTICAL CORD
O 0 x COR

60 x 60 x 4mm ∠
60 x NAL C 4m m D
DIAGO
NA 60 x O m D ∠ ∠
60 x 6 L CORD 4mm RD
0 x 4m ∠
m∠
450

450
STEEL RUNNER BOTTOM CORD
70 x 70 x 6mm ∠ IPE 160 UB 0 11-11-'16 ISSUED FOR INFORMATION
1275 1885 1885 1885 1650
NO. DATE AMENDMENT
RC RING BEAM, 30MPa RC RING BEAM, 30MPa
NOTE: 280 x 450mm dp 280 x 450mm dp
Client
STEEL TRUSS - TYPE 11
1. ALL GUSSET PLATES FOR VERTICAL AND DIAGONAL
CORD CONNECTIONS TO BE 5mm THICK AND WELDED TO MAIN CORDS TYPICAL
WITH 8mm FILLET WELD (WAR).
SCALE 1:25
2. HEIGHT AND WIDTH DIMENSIONS OF GUSSET PLATES TO BE VERIFIED
BEFORE MANUFACTURING.
3. VERTICAL AND DIAGONAL CORDS WELDED TO GUSSET PLATES
WITH 8mm FILLET WELDS (WAR). BEARING OF CORDS TO BE 60mm MIN.

Consultant
TOP COR
D
IPE 140 U
B STEEL PURLINS
100 x 75 x 20 x 2.5mm CFLC
@ 2000mm c/c MAX.

2000 c/c M Tel: +27(0) 861 878 252


TOP CO AX.
VERTICAL CORD

RD
IPE 140 U www.csmeng.co.za
B
IPE 140 UB

m RD

VERTICAL CORD
4m CO

60 x 60 x 4mm ∠

VERTICAL CORD
60 x 60 x 4mm ∠
m RD
60 L

Discipline
RD
x NA

∠ STRUCTURAL
4m CO

VERTICAL CORD
x

60 x 60 x 4mm ∠

O
60 GO

C m∠
RD
60 AL

VERTICAL CORD

L
A

60 x 60 x 4mm ∠

m
NA 4 CO ∠
DI

x N

Project
x

RD
VERTICAL CORD
60 GO

O 0x
60 x 60 x 4mm ∠

m
AG 6 AL 4m CO ∠
IA

VERTICAL CORD
N
DI 60 x L

60 x 60 x 4mm ∠
O x m RD
D

I AG x 60 O NA x 4m CO ∠
TOP CO
RD
EKURHULENI: KATLEHONG

VERTICAL CORD
D 0 G 60 A L m IPE 140 U

60 x 60 x 4mm ∠
A D
6 DI 0 x ON x 4m OR B
6 G
DIA x 60 A L C m∠ FIRE STATION
N 4m ORD

VERTICAL CORD
60 GO AL C ∠
DIA x 60 x O N
60 DIAG 60 x 4mm

IPE 140 UB
BOTTOM CORD BOTTOM CORD 60 x BOTTOM CORD
IPE 160 UB Drawing title
IPE 160 UB IPE 160 UB
EAVES LEVELS SECTIONS
STEEL RUNNER STEEL RUNNER STEEL RUNNER STEEL RUNNER STEEL RUNNER 2 OF 2
450

450
70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠ 70 x 70 x 6mm ∠
2089 1989 1989 1989 1989 1989 1989 2132 Signed by

RC RING BEAM, 30MPa RC RING BEAM, 30MPa


280 x 450mm dp STEEL TRUSS - TYPE 12 280 x 450mm dp
Engineer:

TYPICAL Date
S.A. Engelbrecht
Designed
Reg. no:20140036

SCALE 1:25 NOVEMBER 2016 DV


Size Drawn
A0 JS
Scale Checked
- SE
Building Occupancy Climate Zone
- -
Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 07 00
FOR:
INFORMATION
GENERAL NOTES
1. Drawings to be read in conjunction with all relevant Architect's,
Consultant's, and Specialist's drawings and specifications.
2. All details and dimensions subject to confirmation on site.
Any discrepancies must be brought to the engineer's attention
prior to construction.
3. Drawings are not to be scaled.
4. All construction workmanship and materials to be in
accordance with the relevant provisions of
“The Application of the National Building Regulations”
(SANS 10400), Building Standards act (Act103)
and the relevant parts of SABS 1200.
5. The works will be inspected form time to time by the
consulting engineer to ascertain that the contractor is carrying
out the work in general conformity with the engineering
5000 5000 5000 drawings and documents.
Such inspections are not for the contractors benefit and do not
relieve him of the responsibility for the proper construction
D E F G H I J K L M of the works in accordance with the engineering drawings,
documents and good building practice.
4680 1320 4680 1320 4680 1320 4680 1320 4680 6. The signed original copy of this drawing is kept at the
engineer's office.
5mm CABLES 5mm CABLES 5mm CABLES 5mm CABLES
VERTICAL SAG BARS VERTICAL SAG BARS VERTICAL SAG BARS
50 x 50 x 3mm ∠ 50 x 50 x 3mm ∠ 50 x 50 x 3mm ∠
BETWEEN PURLINS BETWEEN PURLINS BETWEEN PURLINS

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION


STEEL COLUMN

STEEL COLUMN

STEEL COLUMN
VERTICAL CROSS BRACING
80 x 80 x 6mm ∠

203 x 203 x 46 H-SECTION

7567
STEEL COLUMN
DIAGONAL TIES DIAGONAL TIES DIAGONAL TIES
50 x 50 x 3mm ∠ 50 x 50 x 3mm ∠ 50 x 50 x 3mm ∠
SHEETING
OMITTED FOR CLARITY
VERTICAL CROSS BRACING
STEEL PURLINS FOR CLADDING
5mm CABLES 5mm CABLES 80 x 80 x 6mm ∠
5mm CABLES 150 x 50 x 20 x 2.0mm CFLC
5mm CABLES @ 1200mm c/c MAX.

5734
203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION


STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN
WASH BAY - EAST ELEVATION
SCALE 1 : 50

ENGINE BAY - SOUTH ELEVATION


SCALE 1 : 50
5000 5000 5000

203 x 203 x 46 H-SECTION


STEEL COLUMN
203 x 203 x 46 H-SECTION
VERTICAL SAG BARS VERTICAL SAG BARS

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION


VERTICAL SAG BARS

STEEL COLUMN
50 x 50 x 3mm ∠ 50 x 50 x 3mm ∠
50 x 50 x 3mm ∠ BETWEEN PURLINS BETWEEN PURLINS

STEEL COLUMN

STEEL COLUMN
BETWEEN PURLINS

DIAGONAL TIES
50 x 50 x 3mm ∠
VERTICAL CROSS BRACING
WATER TANK 80 x 80 x 6mm ∠
STEEL BEAM OMITTED FOR CLARITY
254 x 146 x 31 I-SECTION
STEEL BEAM
254 x 146 x 31 I-SECTION
DIAGONAL TIES STEEL BEAM

6666
50 x 50 x 3mm ∠ 356 x 171 x 57 I-SECTION
STEEL PURLINS FOR CLADDING

203 x 203 x 46 H-SECTION


150 x 50 x 20 x 2.0mm CFLC

203 x 203 x 46 H-SECTION


M L K J I H G F E D @ 1200mm c/c MAX.

STEEL COLUMN
STEEL COLUMN
4680 1320 4680 1320 4680 1320 4680 1320 4680

4100
VERTICAL CROSS BRACING
80 x 80 x 6mm ∠

WASH BAY - WEST ELEVATION


5mm CABLES 5mm CABLES SCALE 1 : 50
5mm CABLES 5mm CABLES
5734

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION

203 x 203 x 46 H-SECTION


STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN

STEEL COLUMN
0 11-11-'16 ISSUED FOR INFORMATION

NO. DATE AMENDMENT

Client

ENGINE BAY - NORTH ELEVATION


SCALE 1 : 50

Consultant

Tel: +27(0) 861 878 252

www.csmeng.co.za

Discipline
STRUCTURAL
Project

EKURHULENI: KATLEHONG
FIRE STATION

Drawing title

ENGINE BAY & WASH BAY


ELEVATIONS
Signed by

Engineer:
S.A. Engelbrecht Reg. no:20140036
Date Designed
NOVEMBER 2016 DV
Size Drawn
A0 JS
Scale Checked
- SE
Building Occupancy Climate Zone
- -
Project #: Discipline: Stage: Drawing #: Rev:
0373107C S T 08 00
FOR:
INFORMATION