Professional Documents
Culture Documents
Ridwan Septian
Department of Mechanical Engineering,
Faculty of Industrial Technology, Trisakti University,
Jakarta
Email. ridwanseptian01@gmail.com
Abstract -- Laboratory Room is a room that has functions such as Replace sterile
clothes, Preparation, Physical and Chemical Analysis, Chemical storage, Wash tool,
Instrument Analysis, and Sterilization. The cooling load calculation in this building
uses CLTD (Cooling Load Temperature Difference) method. The calculation of cooling
loads based on secondary data is then compared with the installed cooling load
capacity. From the calculation of the above cooling load can be concluded that the
capacity of AHU engine (Air Handling Unit) installed is not sufficient in meeting the
needs of air conditioning system in the laboratory of Quality Control Room of PT Kimia
Farma Sungwun Pharmacopia Production Building.
Abstrak -- Ruang Laboratorium Quality Control adalah ruangan yang memiliki fungsi
diantaranya sebagai ruang Analisa fisik dan kimia, Penyimpanan bahan kimia, Cuci
alat, Analisa Instrumen, Ganti pakaian steril, Preparasi, Sterilisasi, serta Area Kerja.
Perhitungan beban pendinginan pada gedung ini menggunakan metode CLTD
(Cooling Load Temperature Difference). Perhitungan beban pendinginan berdasarkan
data sekunder yang kemudian hasilnya dibandingkan dengan kapasitas beban
pendinginan terpasang. Dari hasil perhitungan beban pendingin di atas dapat
disimpulkan bahwa kapasitas mesin AHU (Air Handling Unit) yang terpasang belum
mencukupi dalam memenuhi kebutuhan sistem tata udara pada ruang Laboratorium
Quality Control Gedung Produksi PT Kimia Farma Sungwun Pharmacopia.
Laboratory Room Quality Control is a room that has functions such as physical and
chemical analysis, Chemical storage, Wash tool, Instrument Analysis, Replace sterile
clothes, Preparation, Sterilization, and Work Area. Reason for re-calculation of coolant
load at Laboratory Room of Quality Control of Production Building of PT Kimia
Farma Sungwun Pharmacopia. this is because the initial condition of the air
conditioning system in this building operates well where the indoor temperature
setpoint can still be achieved in accordance with the conditions in the field. However,
at this time, the temperature conditions in the laboratory room when used at this time
are not in accordance with the expected set point temperature so that the occupants /
users feel less comfortable. This is reinforced by complaints and complaints from the
users of the laboratory space. The purpose of this paper is to recalculate the cooling
load and compare the number of cooling loads calculated with conditions mounted on
the air conditioning system of the laboratory of Quality Control Laboratory of PT
Kimia Farma Sungwun Pharmacopia Production Building.
2. BASIC THEORY
Air Conditioning System
The Air Conditioning System is a process of cooling the air so as to achieve the
temperature and humidity corresponding to that required to the air condition of a given room,
regulating the air flow and cleanliness.
Air Conditioning System Principle
Under the first law of thermodynamics, heat Q1 released from the high temperature
cycle is equal to the amount of heat Q2 released at low temperatures and W.
Q1 = Q2 + W..................................... (1)
The energy input required to remove heat Q2 from low temperature to high temperature
requires mechanical work.
The cooling system can not be removed from the heat transfer process where the heat
produced by the room to be conditioned its temperature will be absorbed by the cooling
system and then will be released into the environment.
Cooling Cycle
The cooling cycle consists of four processes, namely :
1) Evaporation
It is a process of exchanging the room's air heat with refrigerant. At this stage there
is a heat exchange in the evaporator, where the heat of the environment or the cooled
medium is absorbed by the liquid refrigerant in the evaporator so that the liquid refrigerant
derived from the pressurized expansion valve and low temperature changes the phase
from the liquid phase to the vapor having high pressure and temperature. So the great heat
that is absorbed by the refrigerant is:
QC = ṁ (h2 – h1) ............................(2)
Where,
QC : The amount of heat absorbed in the time union evaporator (kJ / s)
ṁ : Mass flow rate of
refrigerant (kg / s)
(h2 – h1) : Effect of refrigeration (kJ/kg)
2) Compression
Compression has two functions, namely : First, to suck the refrigerant from the
evaporator and press it into the condenser. Second, to increase the pressure of refrigerant. At
this stage occurs in the compressor where the vaporized refrigerant with low temperature and
pressure is isotrapically compressed so that the temperature and pressure become high, the
heating capacity can be written by the equation:
QW = ṁ (h3 – h2) ...........................(3)
Where,
Qw : Heating capacity (kJ / s) unity time (kg / s)
ṁ : Mass flow rate of refrigerant (kJ / s)
(h3 – h2) : Compression work (kJ / kg)
3) Condensation (condensation)
Has two functions, namely : First, to remove the heat stored refrigerant on the evaporator.
Second, to change the refrigerant phase from vapor to liquid. At this stage occurs inside the
compressor, where the heat from the vapor refrigerant from the compressor is discharged
into the environment so the refrigerant is condensed. At this stage there is a phase change
from the superheat vapor phase to a saturated aqueous phase, in this saturated liquid phase
the pressure and temperature are still high. The amount of heat released in the condenser is:
qc = h3 – h4 ......................... (4)
where,
qc : Heat released in condenser
(kJ / kg)
h3 : The enthalpy of refrigerant coming out of the compressor (kJ / kg)
h2 : Enthalpi of saturated liquid refrigerant (kJ / kg)
4) Expansion
Changing the hot refrigerant fluid to a cold liquid by lowering the pressure. At this
stage occurs in the expansion valve where the refrigerant is lowered by the pressure
followed by the decrease in the entalphi temperature.
Hot air from room
Liquid
EKSPANSION EVAPORATION
Cool
Liquid Steam Cool Air
Hot
Steam
COMPRESION CONDENSATION
3. METHODOLOGY
This cooling load calculation uses the method of CLTD (Cooling Load Temperature
Difference) method. The calculation of cooling loads based on secondary data is then compared
with the installed cooling load capacity.
• Floor area, building surface area, building volume, glass surface area, each distinguished
between conditioned and not.
• The surface area of the sheath / fasade, consisting of wall and glass area.
• Direct observation for data retrieval in conditioned spaces with cooling systems taking into
account internal and external loads on a theoretical basis on existing literature sources.
• Evaluation of the result of calculating the load on the installed machine with the results of
data field.
results.
4. RESULT AND DISCUSSION
Some data are obtained from secondary data. Table 1 shows the data of the room
analyzed.
Table 1. Data Room
DATA ROOM
Operation time of laboratory room starts at 08.00 WIB until 16.00 WIB.
Lighting for the room uses different types of lights depending on the function and
location of the lamp placement with an operating time of 8 hours or equal to the office hours
of operation. Lighting data is shown in Table 2.
Table 2. Lighting data lamp
LAMP DATA
NO TYPE OF LIGHTS AMOUNT
1 Center Pin Spot Light 20 Watt 2 Units
In space analysis, especially space instrument and physical and chemical analysis
certainly can not be separated from the use of laboratory equipment. The use of such
equipment necessarily produces the heat that must be taken into account in the calculation
of the cooling load. Table 3 shows the equipment data used.
Humans in its activities certainly remove the heat from the body that must be taken into
account in the calculation of the cooling load. Assuming the number of occupants of 12 people
whose details are shown in Table 4.
Table 4. Data Number of Occupants
NO OCCUPANT AMOUNT
1 QC Manager 1 Person
2 Pharmacist 4 People
3 Analyst 4 People
4 QA Inspector 2 Persons
Total 12 People
Engine capacity installed for QC Laboratory room with 1 unit of AHU are : 8.5 TR or
equivalent to 40.1 PK with power of 29.9 kW.
To calculate all loads, especially external loads will be influenced by several factors such as
location and position of the building located that will affect the climate, the type of materials
used in building construction and environmental temperature.
In determining the recovery of heat, the basis used on the hottest loads of the hottest
averaged loads in a year (ASHRAE, 2001) and (Handbook, 1965). Load calculation steps :
Determining the location and position of the building
Determination of the dimensions of the room
Determine the design conditions consisting of :
a. Wet temperature
b. Dry temperature
c. Humidity
Determine the maximum outside temperature as the reference of the load calculation
Maintains load data required for both internal and external loads
Calculates the cooling load
Cooling Charge of laboratory room. The calculation results are shown in Table 5,
Table 6, and Table 7.
Table 5. Amount of Cooling Loads
38.399,570 160.740,619
2 Increase of load by leakage air duct
45,819 191,798
1 The latent engine heat load by incoming outer air
55.769,49 233.451,085
2 Increase of load by leakage air duct
156.904,588 656.802,604
Amount of Calculation Cooling Charges
Total Cooling Charges In Laboratory Room Quality Control Production Building PT Kimia
Farma Sungwun Pharmacopia. obtained are as follows :
Heat load = 156.904,588 kcal / hour
Safety factor = 156.904,588 (kcal/h) x 5%
= 7.845,229 kcal / hour
capacity analysis
BIBLIOGRAPHY
America Society of Heating Refrigerant and Air Conditioning Engineers. ASHRAE
Handbook Fundamental. Atlanta. 2001.
Arismunandar, Wiranto and Heizo Saito., Air Refresher, Cet. 6. Jakarta: PT. Pradnya
Paramita, 2002.
Handbook of Air Conditioning System Design, Carrier Air Conditioning Company.
McGraw Hill Company, 1965.
Pita, Edward.G., Air Conditioning Principles and System an Energy Approach, John
Wiley & Sons, New York, 1981.
Stoecker, W.F and jones, J.W. Refrigeration and Air Conditioning, 2nd Edition. Translation
by Ir. Supratman Hara. Jakarta: Erland, 1989
Sumanto. Fundamentals of Refrigerant. Yogyakarta: Andi., 1994.
Sunarno. Mechanical Electrical, 1st Edition. Yogyakarta: Andi, 2005
Sabaruddin H., Abdul Hamid, dan Imam Hidayat, Perhitungan Ulang Beban
Pendinginan, Jakarta, ISSN : 1410-233