BT 125

Series general data BT


Backward centrifugal, external rotor motor

MANUFACTURING FEATURES:

• Galvanised steel sheet housing.


• Galvanised steel impeller.
• External wiring box.
• Asynchronous external rotor , IP-44 protection and rated class B insulation according to the DIN 40.050 h1
Standard and ball bearings permanently greased. Manufactured with standard voltages 230V 50Hz.

APPLICATIONS:

Designed for inline installation, they are suitable for:


• Air renewal in bathrooms and small enclosed environments.
• Maximum working temperature: 50ºC.
• Not suitable to conduct gases in hazardous areas.

Series accessories BT

JE-45 INT PE REG CPM

Characteristic curve
Design point
Q (m3/h) 348.42
Ps(Pa) 3.65

Service point
Impeller rpm 2400
Max. temp.(ºC) 60
Q (m3/h) 348.25
Ps(Pa) 3.64
Pd(Pa) 37.27
Pt(Pa) 40.91
Air speed(m/s) 7.88
SWL dB(A) 76 (INDUCT)
SPL dB(A) 55 (INDUCT)
Distance(m) 3

Technical data
Impeller rpm 2400 Power(kW) 0,09
Motor rpm 2400 Imax 230V(A) 0,42
Approx. weight(kg) 3 Imax 400V(A) -
Maximum flow rate(m3/h) 350 Imax 690V(A) -

This report data could change without any previous advise v4.0.5
BT 125
Acoustics to the service point (INDUCT)
Power dB(A)
63 Hz 52
125 Hz 68
250 Hz 72
500 Hz 72
1000 Hz 63
2000 Hz 62
4000 Hz 58
8000 Hz 48
Total dB(A) 76

Pressure dB(A) [3 m]
63 Hz 31
125 Hz 47
250 Hz 51
500 Hz 51
1000 Hz 42
2000 Hz 41
4000 Hz 37
8000 Hz 27
Total dB(A) 55

dimensions diagram

Dimensions (mm)
A=125 B=243 C=25 D=189 E=22

Wiring diagram

This report data could change without any previous advise v4.0.5