GCU9002

Web Enabled Network Control Unit

Features Description

Embedded Web Server. The GCU9002 is a 7” Touch Screen Web enabled network control
unit that uses Ethernet and TCP/IP networking technologies. It
Easy control & monitor via web browser
incorporates an embedded web server that can deliver
complete with security protection. user-specific web pages to any PC or mobile terminal running
Ethernet 10/100 Mbps connection and internet browser software. A user with an appropriate security
codes can made adjustment or monitor the network control unit
use TCP/IP networking technologies. form any internet access point in the world.
Support Standard Multi Protocols –
It is also provides network management, integration and process
BACnet & Modbus
control functions for any existing or new building controllers and
Telnet support for uploading and microprocessor based equipments or system in buildings.
downloading of database & online The management function provided by the GCU9002 such as
trend log and alarm generation improves building controllers and
modification. microprocessor based equipments or system management and
Support Multi-System For Seamless audit trail capabilities.
Integration or Router function.
The integration function provided by the GCU9002 allows
Built-in soft ladder logic for process seamless integration such as information sharing (read/write)
control. between building controllers and microprocessor based
equipments or system without any need of major upgrade or
Support time schedule & holiday
equipments replacement and allow cost saving.
function.
Support trend (real-time & historical) The process control functions provided by the GCU9002 allow
global control action to be implemented across any building
logging and storage function. controllers and microprocessor based equipments or system to
Support real-time alarm generation and allow full building control.
storage function.
The GCU9002 provide a truly cost effective solution for any
Support E-mail, SMS and voice building automation or high-level integration application. A truly
notification based on alarm/change of Ethernet network compliant feature allows the GCU9002 to be
install anywhere in the building.
state condition.
7” Capacitive Touch Screen
Resolution – 800 x 480 pixels

Pegasus reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

GCU9002 Data Sheet Issue 3.0 12/8/17 1


Firmware Specifications
Can be access at anytime & anywhere via internet browser.
Allow platform cross over development and code pot over for new software
Web based compliant application features.
Building automation or high level integration data can be co-exist on existing
IT Ethernet networks.
Allows graphics pages navigation from one page to another page.
Allows simple mouse click to operate command or viewing.
Built GUI Interface
No additional software required (all require programs have been embedded
in the firmware).
Standard Web Programming
Use Java Scripts, Java Applets, and CGI Scripts programming.
Languages
Support Protocols For High Level
BACnet/IP, BACnet/MSTP, Modbus/IP, Modbus RTU, UDP and URL.
Integration
FTP Support A file size can be upload or download via FTP command
I/O Database Capacities Support up to 1023 I/O points capacities with full functions.
Unlimited Time schedule configuration up to 5 years in advance for all I/O
Time Scheduling Function
points.
Unlimited Holiday schedule configuration up to 5 years in advance for all I/O
Holiday Scheduling Function
points.
All I/O points can be configured for trend log function with log sample size of
1,000,000 (max.) samples for each I/O point.
Allow more than a year storage space for data samples for each point with
sample rate of 1 minutes interval.
Trend Logging Function
Built-in real-time or historical line chart into firmware.
All log data samples are fully self-contained into the unit flash memory.
All trend log data samples can be converted into CSV file format
automatically upon up loading from the unit (Data format is Excel ready).
All I/O points can be configured for alarm with up to 5 alarm stages (out of
range, high, high high, low & low low) for each I/O point.
Alarm Management Function
All alarms are fully self-contained into the unit flash memory up to 1,000,000
(max.) alarms history.
All I/O points can be configured to sent out messages via E-mail, SMS or
Voice based on alarm state (normal to alarm), return to normal state (alarm
to normal), any change of state, rate of change and time based. Each
Alarm Notification Function message has complete details of the alarm/event with point ID, event,
condition, additional user configure information, time and date stamp.
All message can be received by mobile phone any where in the world via
standard Internet gateways
Support Pegasus logic (soft logic) programming for process control. All I/O
points can be use as input (source) or output (destination) by the ladder
Process Control Function
logic program. Built-in function such as PID, Gate, Logic, Comparator, etc
will simplify, speed up user programming time and learning curve.

Pegasus reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

GCU9002 Data Sheet Issue 3.0 12/8/17 2


Hardware Specifications
Power Supply: 24VDC
Power Consumption: 18 Watt
Microprocessor: 32 Bits – i.MX6 Quad Core 1 GHz
SDRAM Memory: 2 GB DDR-III
eMMC Flash Memory: 8 GB
MicroSD Storage Disk Memory: 128 GB
Main Network: Ethernet (TCP/IP) – support 10/100 MBPS connection (auto detect)
Wireless Network: Optional – WiFi 802.11ac 300Mbit
Sub Network: 3 x RS-485
Sub Network Baud Rate: 50 ~ 230.4 KBPS
Sub Network Cable Length: Maximum Length: 1000 meters using screened twisted pair 24AWG
Yes, allows configuration of a predefine tasks/events to run based on time
Real Time Clock & Calendar:
and date automatically
LCD Screen Size: 7” capacitive touch screen
LCD Screen Resolution: 800 x 480 pixels
LCD Proximity Sensor: Radar sensor (Detect any object in front of the LCD (Range : 0 – 2m)
Optional – HD camera support 2D/3D image acceleration and H264
LCD Front Camera:
format
LCD Audio Support: Optional – 2 watt speaker and microphone
Storage Condition: -20 to 70 Deg C / 0% - 90% RH, Non - Condensing
Operating Condition: -5 to 65 Deg C / 0% - 90% RH, Non - Condensing
Surge Protection: 15KV ESD for serial port
Magnetic Isolation: 1.5KV for Ethernet
Mounting: Panel mounting with loose flange
Protection: IP40
Weight: 350 g

LCD Dimension