Professional Documents
Culture Documents
A.L.P.I.
e-mail alp@ysi.es
Web site http://www.caneco.es
edition 27/07/2009
Training Manual for CANECO BT 5.3 3
Contents
GENERAL ........................................................................................................................................ 7
CERTIFICATE OF COMPLIANCE .................................................................................................................... 7
DESIGN CALCULATION METHODS FOR LV ELECTRICAL INSTALLATIONS ................................................................. 10
Method 1: from Downstream to Upstream .............................................................................................. 10
Method 2: from Upstream to Downstream .............................................................................................. 10
Method 2: from Upstream to Downstream .............................................................................................. 11
PARTICULAR FUNCTIONALITIES OF CANECO BT .................................................................................................. 11
PARTICULAR FUNCTIONALITIES OF CANECO BT .................................................................................................. 12
An "Expert Design Engine" ..................................................................................................................... 12
Three Tools for Entering Circuits ............................................................................................................ 12
Automatic Design of Power Circuits ....................................................................................................... 13
Generation of a Customisable Technical Folder..................................................................................... 13
OVERVIEW OF THE APPLICATION INTERFACE........................................................................................................ 14
DATA ENTRY TOOLS .......................................................................................................................................... 17
Network Single-Line Diagram ................................................................................................................. 18
Board Single-line Diagram ...................................................................................................................... 19
Spreadsheet ............................................................................................................................................ 20
CREATING A SOURCE ......................................................................................................................................... 21
The Source Window ................................................................................................................................ 21
The Different Types of Source ................................................................................................................ 21
Setting the Source .................................................................................................................................. 22
Source Section ........................................................................................................................................ 22
Network Section ...................................................................................................................................... 23
Link Section............................................................................................................................................. 24
Board Source by lk .................................................................................................................................. 25
Description .............................................................................................................................................. 25
Calculation of an LV Source by Ik ........................................................................................................... 26
Board Source by R and X ....................................................................................................................... 27
This source allows an installation to be extended .................................................................................. 27
SCHEMATIC ................................................................................................................................... 73
PRINTING ....................................................................................................................................... 83
PRINT CONFIGURATION ...................................................................................................................................... 83
Composition of a Caneco BT print folder ................................................................................................ 83
Entering data for your project.................................................................................................................. 84
Inserting the LOGO ................................................................................................................................. 85
Creating a print folder ............................................................................................................................. 85
Creating a new Document model ........................................................................................................... 86
STANDARD CANECO BT DOCUMENT MODELS ................................................................................................... 88
Training Manual for CANECO BT 5.3 5
« Flyleaf » ...................................................................................................................................... 88
« List of folios » .............................................................................................................................. 88
Supply calculation sheet: ............................................................................................................... 89
« Network single-line diagram » ..................................................................................................... 89
Circuit calculation sheet ................................................................................................................. 90
« Cables list » ................................................................................................................................. 90
Protection settings: ......................................................................................................................... 91
Consumer list: ................................................................................................................................ 91
Cable nomenclature: ...................................................................................................................... 92
Protection nomenclature: « Nomenclature prot. » ......................................................................... 92
Site single-line diagram 8 circuits per folio: .................................................................................... 93
Operator single-line diagram 8 circuits per folio: ............................................................................ 93
Panel builder single-line diagram 8 circuits per folio ...................................................................... 94
Industrial single-line diagram 8 circuits per folio ............................................................................ 94
GENERAL
CERTIFICATE OF COMPLIANCE
Caneco BT has got certificates of compliance from various software certification organisations which confirm
that its calculations comply with electrical standard rules:
France UTE: (Union Technique de l’Electricité), certificate of compliance with NFC 15-100.
UK : certificatre of compliance with the British Standard: BS7671 from IEE member
Belgium : certificatre of compliance with the RGIE
Notes
Training Manual for CANECO BT 5.3 8
Notes
Training Manual for CANECO BT 5.3 9
Notes
Training Manual for CANECO BT 5.3 10
This involves sizing the distribution circuits i.e. defining their design currents according to the equipment
supplied.
This Downstream (equipment supplied) to Upstream (distributions and Source) approach is called Power
requirement
It cannot be carried out until the equipment has been defined.
TD1
Downstream
Outlet 1 Outlet 2
Notes
Training Manual for CANECO BT 5.3 11
When the design currents in the distribution circuits have been defined, we have to define the protections
and busbar trunking systems from the source to the final circuits.
Sizing is performed by calculating among other parameters the accumulated voltage drops from the
beginning of the installation, together with the short-circuit currents, which require knowledge of the
impedances upstream of the circuit being designed.
The method becomes Upstream (Source, then distribution circuits) to Downstream (terminal equipment).
Upstream
MSB
TD1
Downstream
Notes
Training Manual for CANECO BT 5.3 12
Notes
Training Manual for CANECO BT 5.3 13
Notes
Training Manual for CANECO BT 5.3 14
The interface is similar to that of most programs running under Windows environment
The menu bar located at the top of the screen. The menu commands enable you to directly trigger an
action or to display a sub-menu or dialog box
The tool bar under this menu bar allows direct access to a command in one of the menus.
Board Single-line
Spreadsheet Diagram Network Single-Line
diagram
Designations of
Length of circuits circuits
Consumption of
Button for creating/modifying circuits
circuits
Main screen:
Example with Network
Single-Line diagram
Calculation
results
Notes
Training Manual for CANECO BT 5.3 15
Calculation report
Fig 2.
Right-click a line to display a pop-up
menu (Fig. 2):
Fig 3.
Notes
Training Manual for CANECO BT 5.3 16
Calculation results
Calculated cross-sections
Calculation criterion
Withstand current
Design current
Short-circuit currents
Circuit and overall voltage drop
Discrimination
Coordination
Windows:
"Network graphic"
"Calculation Report"
"Calculation results"
Notes
Training Manual for CANECO BT 5.3 17
Icons and menus remain identical in the three tools. In addition, for the spreadsheet and the Board
Single-Line Diagram, three data entry areas facilitate circuit entry:
Upstream/dow
Spread
Board single-line Network single-line nstream
sheet
distribution
Creation button /
circuit changes circuit styles Consumption length designation
All three tools offer several options for entering and moving circuits:
• Inserting circuits and circuit blocks (in the board single-line diagram)
• copy/pasting one or more circuits
• moving circuits
• multiple entry of circuits
• Use of circuit styles (see section entitled "Circuit Styles")
Notes
Training Manual for CANECO BT 5.3 18
The Network Single-Line diagram allows the user to edit and view the schematic representation of the
complete project or of its main circuits.
Redraw
Rebuild
(refresh)
(refresh)
Distribution
choice Wiring system:
cable or CEP HV/LV transformer:
MSB
Busbars
Notes
Training Manual for CANECO BT 5.3 19
All the circuits to the right of the dotted line in the window are supplied by the
greyed-out distribution in the network graphic. (T_001 in this case), shown by
the feeder to the left of the dotted line
Allows to view:
Ground bar
Symbol attributes
Terminals of equipment
supplied
Terminal numbers
Notes
Training Manual for CANECO BT 5.3 20
SPREADSHEET
The advantage of the spreadsheet is that it gives a representation of data for the present distribution. This
tool allows very fast data entry.
Data entry on the spreadsheet automatically generates a schematic in the board and Network Single-Line
diagrams outlined below.
Notes
Training Manual for CANECO BT 5.3 21
CREATING A SOURCE
THE SOURCE WINDOW
Any creation of a project in Caneco BT starts with the automatic opening of a dialog window entitled
"Normal Source".
This window defines the general characteristics of the network, the source and the Source-MSB wiring
system.
Certain default values are proposed: these must be checked and corrected as required. The mandatory
information to be entered is the power of the source.
Characteristics of the
Source
Characteristics of the
Network
Characteristics of the
Wiring system
1 to 6 transformers
1 to 6 Generating Sets
(identical in parallel)
(identical in parallel)
SOURCE SECTION
Short-circuit voltage
expressed in %
Nominal source power
Characteristics of transformers:
Number of sources: Type of Source: • Files: if standard transformer
Min: trip on Ikmin • Transformer • Ukr: if non-standard
Dielectric type
• Generator transformer
• LV with Ik
Details on dielectric type
SEC95.ZTR : dry transformers, Ukr = 6%
:
UTE95.ZTR oil- transformers 50--630 Ukr = 4%
95.ZTR oil 800--500 Ukr = 6%
Notes
Training Manual for CANECO BT 5.3 23
NETWORK SECTION
Notes
Training Manual for CANECO BT 5.3 24
LINK SECTION
cross-
section of
Fixing
fixing of phase
of number of
conductors cross-section conductor
per phase Number of
conductors per phase
Loaded neutral: a coefficient of 0.84 is applied if
this box is ticked. If TH > 15%, this box is ticked
automatically.
Notes
Training Manual for CANECO BT 5.3 25
BOARD SOURCE BY IK
DESCRIPTION
This is a Low Voltage source for which you define the short-circuit current at the origin.
This applies:
- if you are supplied directly by the electricity company (usually 36 kVA to 250 kVA)
The following characteristics of the origin of the installation are required in order to design such a system:
- current available
The neutral and PE impedances are generally unknown hence the calculations are not very accurate,
particularly in the case of Ik minimum values and If, and therefore the magnetic settings may not be very
accurate.
This type of source is thus not advisable in the following two cases:
Low Voltage supply from an HV-LV transformer belonging to the local distributor and installed close to
the LV delivery point: (this is the case for the EDF yellow rates in France), in which it is preferable to
define in Caneco the characteristics of this transformer and the wiring system up to the delivery point
(Tariff Source 2).
Extension of an existing installation: it is always preferable to describe the existing installation so that all
the impedances upstream of the starting point of your installation are accurately determined.
Notes
Training Manual for CANECO BT 5.3 26
CALCULATION OF AN LV SOURCE BY IK
Caneco BT determines phase-to-phase impedances on the basis of the 3-phase short-circuit current. It is
standard practice to distribute the impedances over the neutral and PE so as to obtain Ik min and If values
equal to Ik3Max/2. This arbitrary convention results in a source characteristic which is unfavourable and
therefore safer.
For a direct supply from the utility boars ( ex EDF Blue Rate connection <= 36 kVA), select a appropriate
catalogue
Notes
Training Manual for CANECO BT 5.3 27
- if the existing project is in the form of a file: ability to copy/paste the impedances at
Board level.
This allows an accurate calculation of the data for the board. (Ik, dU)
Notes
Training Manual for CANECO BT 5.3 28
Supply Contract
Power
Representation in
single-line network
Notes
Training Manual for CANECO BT 5.3 29
In Caneco BT circuit creation is performed automatically using circuit models known as "styles".
A style represents an outlet (protection + wiring system + terminal equipment) having a certain number
of attributes by default (type of cable, type of terminal equipment, polarity, installation method, etc.)
Caneco BT offers 10 basic default styles, corresponding to standard circuits: Motor, Socket, Lighting,
Heating. Miscellaneous, Board, Busbar Trunking, Capacitor, LV-LV Transformer and Busbar.
These styles may be modified and completed by the user in order to create personal styles.
EXAMPLES OF STYLES
Notes
Training Manual for CANECO BT 5.3 30
STYLE
Protection type
Minimum Rating
Default Indirect contact protection
protection Etc.…
Cable + Protection
Polarity
Type
Core
Length
Default wiring Cable Installation method
system Minimum cross-section
Busbar DU max
Etc.…
trunking system
CIRCUIT
Distribution Type
BOARD Consumption
Default Cos phi
LV/LV Number
Equipment
terminal
Busbar trunk Use Coef
equipment
Etc.…
Equipment
Motor
Lighting
Etc.
Important:
The user can create personalised styles by defining the default diagram and/or parameters.
Notes
Training Manual for CANECO BT 5.3 31
CIRCUIT MARKING
The "Automatic Ref Marks" tab in the "Preferences" window allows the default markings
to be customised.
Notes
Training Manual for CANECO BT 5.3 32
A new circuit can be created in several ways. We shall take the example of creating a distribution board. You can:
1. Either use the "New Circuit" button in the main window 3. Or from the project tree structure, by
right-clicking on the distribution + New Distribution
2. Or by right-clicking from the data entry window 4 – Or from the main menu, by choosing Circuits/New
and selecting New Circuit in the pop-up menu
Training Manual for CANECO BT 5.3 33
3. A window is displayed and prompts you to enter the desired number of outlets.
4. Release the SHIFT key and enter the number of circuits then confirm by OK
Notes
Training Manual for CANECO BT 5.3 34
MOVING CIRCUITS
1. Select the circuit to be moved 2. Drag the selected circuit to the target distribution
2. You can also move a distribution with all the associated outlets
Notes
Training Manual for CANECO BT 5.3 35
DUPLICATING CIRCUITS
After having selected the circuit(s), press the Ctrl key on the keyboard then duplicate the selection on
the desired distribution (in the network diagram or in the network tree)
1. Select and press the Ctrl key 2. Move the selection to the distribution and
release it
Notes
Training Manual for CANECO BT 5.3 36
Additional styles
In order to complete the circuit types in Caneco BT, we offer you 7 additional styles. They appear
automatically in the usual list and automatically manage the diagram and calculation attributes. These styles
can be modified.
C M M
I>
U,f Busbars
with 30 mA
differential
M M M switch M
Ond
Construction principle
Main busbar
Busbar
Supply to downstream
circuits
BOARD
Notes
Training Manual for CANECO BT 5.3 37
Entering busbar
Busbar is available as a style in Caneco BT under the name "Busbar"
⇒ in spreadsheet mode
Understand:
circuits PC1, CH1
and TD1 JB2 are
connected to
busbar TD1 JB1.
Notes
Training Manual for CANECO BT 5.3 38
BOARD
CIRCUITS SUPPLIED
BY THE BUSBARS
Notes
Training Manual for CANECO BT 5.3 39
LV/LV TRANSFORMER
Board isolating
device
MSB
Circuit protection
TRBTBT kOversizing
Example: In our example MERLIN GERIN recommends an NS160N/H/L TM125D for the protection of
LV/LV transformers
fixing
Notes
Training Manual for CANECO BT 5.3 40
Notes
Training Manual for CANECO BT 5.3 41
CAPACITOR
MSB
30 kVar
Ib = 43A
kOversizing
fixing
Notes
Training Manual for CANECO BT 5.3 42
MSB
Cable supplying the busbar trunking system. Its length is defined in the
circuit tab
C-2
T-1
M Trunking length must be entered in the length field of the downstream tab
Notes
Training Manual for CANECO BT 5.3 43
Configurations
Distance
Distance from origin
from origin
Calculation method
Voltage drop
Comb : voltage drop calculated with mean I=IB/2
Transport : voltage drop calculated with IB end
Notes
Training Manual for CANECO BT 5.3 44
SETTING A CIRCUIT
THE CIRCUIT SHEET
This configuration window is displayed when you double-click on a circuit: in this example it is a "Board"
circuit
Protection
section
Equipment
section
Circuit Allows circuit settings to be defined (ref mark, type of protection, consumption, etc.)
Notes
Training Manual for CANECO BT 5.3 45
Allows terminal equipment data to be entered (ref mark, coincidence factor, isolating device,
Board
designation, etc.)
Protection Allows modification of protection-related information
Uninterruptible Power Supply: to connect an inverter (specify ref mark, power and number of
UPS
inverters in parallel).
IK/du Display of short-circuit currents
Currents Information on the various currents: I available, sum of Ib values, I authorised etc.
Schematic Allows you to configure the schematic (earth conductor, terminals, etc.)
Temperature Allows you to define the operating temperatures of the board protections
The Diversisty/Coincidence factor requires detailed knowledge of the installation and experience of the
operating conditions (motors, power sockets).
In the absence of precise indications, the values can be taken in the table below:
Notes
Training Manual for CANECO BT 5.3 47
CIRCUIT CALCULATION
ELECTRICAL ENGINEERING FORMULAS ON STANDARD CIRCUITS
Data Calculations Diagrams
U = 400 V Ib = S / U. 3
Cos ϕ = 0.8 Ib = 100 / 400. 3
Board
S = 100 kVA
Ib = 144.3 A
U = 400 V P = U . I. 3 ϕ
cos
Cos ϕ = 0.88
Ib = P / U 3 cos ϕ
Motor
Pu = 11 kW
n = 0.86 Ib = 12790 / 0.88. 400 3
(2790 W) according to
Caneco standard Ib = 20.98 A
U = 230 V P = U . I . cos ϕ
Cos ϕ = 0.92
Lighting
2*36 W Ib = P / U cos ϕ
( 90 W with ballast)
Ib = 90 / 0.92. 230
According to Caneco
standard
Ib = 0.425 A
Notes
Training Manual for CANECO BT 5.3 48
In e Ib and Irth e
Maximum current carrying capacity of the wiring systemsystem criterion -
Ib
(IN in Caneco BT)
Notes
Training Manual for CANECO BT 5.3 49
dU max permitted
Length of cable
Design current
Cos. Phi
dU Upstream
Cable cross-section
Notes
Training Manual for CANECO BT 5.3 50
If
chassis
The standard defines a maximum trip time depending on the supply voltage and the neutral point
connection (for ex 400 ms at 400 V under TN according to table 41A)
This time may be as much as 5 seconds for distributions
Note: If the operating time of the protection is greater than the time stipulated in the standard or if the circuit
configuration requires, a suitable device must be used to protect people against indirect contact:
See reminder of rules for using AEB and EQUIPOTENTIALITY appended hereto
Notes
Training Manual for CANECO BT 5.3 51
L1 L2 L3 N PE
Ik3
Ik2
Ik1Min
Ik1Max
If
For thermal stress Short-circuits are calculated at the end of the wiring system
In a short-circuit situation, the thermal stress limited by the protection must meet the following
condition:
k² S² e I² t
For the value of k, please refer to Table 54B and 54D of NFC 15-100
Cable cross-section
Short-circuit
current Coefficient ( depending on each
in the cable insulation family PVC/ XLPE)
Operating time See Table 54B
of the protection
k Copper Alu
PR 143 94
PVC 115 76
table abstract
Practical condition:
Erreur ! Signet non défini. Ik min ≥ IrMg × 1,2Tol. (general purpose circuit-breaker)
Erreur ! Signet non défini. Ik min ≥ IrMg max (modular circuit-breaker) ( IrMagmax = upper
value of operating range)
Notes
Training Manual for CANECO BT 5.3 52
(trip curve)
(the thermal stress curve for the cable must be to the right of the trip curve)
Ikmin is the lowest of the min short-circuit currents (Ik2, Ik1 or If)
Example:
Notes
Training Manual for CANECO BT 5.3 53
Choice of Fuse
In e Ib
Pdf e Ip max
With:
Notes
Training Manual for CANECO BT 5.3 55
Remedy:
- low magnetic, electronic protection
Cross-section chosen to ensure thermal
Thermal stresses following stress for the cable on short-circuit. (on - thermal trip if:
CC
short-circuit. short-circuit) 1. there are no
indirect contacts:
2. we apply the rule "Exemption from
verification of short-circuit tolerance of
conductors"
IF too low or Mg too high
Remedy:
Protection against indirect Cross-section chosen to protect people Differential, equipotential, (distribution
contacts CI against indirect contact circuit) bare copper
(Human protection)
AEB (ending circuit)
Low magnetic or electronic protection
!! It leads to displaying warning C55: Very unfavourable calculation criterion (except for
IN)
Notes
Training Manual for CANECO BT 5.3 56
2. User choice per model: uses the same principles as the "manual" choice in CANECO BT V4.4 but
with more detail.
More enhanced information is included in the manufacturer database if the files originate from
EDIELEC.
In this case, CANECO BT only provides possibilities offered by the manufacturer's catalogue. The
trip unit poles and time delays are specified and CANECO takes them into account.
Protection time delay becomes a selection criterion if the file type is EDIELEC and the "Delayed" box
is ticked.
In this case, the automatic choice looks for the most economical time-delayed protection.
Notes
Training Manual for CANECO BT 5.3 57
3. Off-catalogue choice:
It replaces the previous fixing of all the adjustment values of a protection in previous versions (V4).
Version 5 of Caneco BT clearly states that the product is off-catalogue; a window allows specifying all
the values necessary for a normative calculation except breaking capacity :
Notes
Training Manual for CANECO BT 5.3 58
PROTECTION ADJUSTMENTS
MODULAR CIRCUIT-BREAKER
Modular Circuit-Breaker
Adjustment
Type Thermal adjustment Magnetic adjustment
range
C 5In - 10In Fixed Fixed
Ik min i ≥ 10 × In
Notes
Training Manual for CANECO BT 5.3 59
Notes
Training Manual for CANECO BT 5.3 60
RESULTS WINDOW
Notes
Training Manual for CANECO BT 5.3 61
CALCULATION OPTIONS
DETAILS ON CALCULATION OPTIONS - "CALCULATION" TAB
Human Protection:
Notes
Training Manual for CANECO BT 5.3 62
1 - Use of the
limitation curves
under thermal stress
(I2.t) to calculate
cross-sections.
Notes
Training Manual for CANECO BT 5.3 63
Notes
Training Manual for CANECO BT 5.3 65
DISCRIMINATION -
COORDINATION
DISCRIMINATION - COORDINATION/BACKUP
DISCRIMINATION, SELECTIVITY
If the Upstream and Downstream protections are from different manufacturers, the software calculates
discrimination according to the rule shown below:
Disjoncteur Amont
Disjoncteur Aval
IrMgUpstream 1,2
(- 20%)
≥ = 1,5
IrMg x 0,8 IrMgDownstream 0,8
IrMg IrMg
Aval Amont
Notes
Training Manual for CANECO BT 5.3 66
Discrimination on overload
len
Th
Mg
Current and chronometric discrimination
B (total)
ut
Functional discrimination
Total discrimination
In practice, the most likely short- ensured with a downstream
circuits are at the equipment D1 limiter circuit-breaker
level. IrTh(upstream)
1,5 ≤ )
Discrimination ensured for any Ik Example: IrTh(downstream)
at the end of the circuit. D2
Limit 2 kA
DIFFERENTIAL DISCRIMINATION
1. Total: A
2. Partial:
Discrimination Meaning
Nil the upstream protection trips at the same time as that of the circuit
Uncertain the upstream protection is liable to trip at the same time as that of the circuit
Total the circuit protection trips and the upstream protection does not
Notes
Training Manual for CANECO BT 5.3 68
BACKUP
Backup is the use of the limiting power of the protective devices (fuses or circuit-breakers).
The installation of an upstream limiting device enables the downstream use of circuits-breakers
which do not have a breaking capacity (Icu) sufficient for the presumed short-circuit current (I k) at
the point where they are installed: this arrangement can generate substantial savings.
The current limitation is effective on all the circuits placed downstream and is not merely restricted
to two successive equipment.
Coordination can thus be applied at several stages.
Without means: no
association with upstream
protection
Discrimination reinforced
by coordination
(manufacturer tables)
Breaking capacity
increase by association
with upstream
protection.
Notes
Training Manual for CANECO BT 5.3 69
STANDBY SUPPLY
STANDBY SUPPLY
RULES:
Notes
Training Manual for CANECO BT 5.3 70
15 characters max.
Rated power of generator: 25 to 1000 kVA
Same as normal supply
Notes
Training Manual for CANECO BT 5.3 71
Connection is done by selecting the distribution to which the standby supply will be connected
Notes
Training Manual for CANECO BT 5.3 72
Confirm by YES
Notes
Training Manual for CANECO BT 5.3 73
SCHEMATIC
STYLES BLOCKS
CREATING A CIRCUIT STYLE IN CANECO BT
DESCRIPTION
In Caneco BT, circuits are created based
on templates called "Styles:.
⇒ "Caneco styles"
• These are "standard" styles
• They can not be modified or deleted
• There are 10 of them (in bold characters)
⇒ "Custom styles":
• These are styles created by the user from standard or custom styles
• They can be modified or deleted
Notes
Training Manual for CANECO BT 5.3 74
The Init column allows you to define the initialisation of circuit data: it defines the first initialisation of the
data for a circuit created by its style.
Four options are available:
Init Meaning
Yes means that the parameter will be initialised with the value
specified to the right
No means that this value will not be initialised (e.g. the
designation)
Cond means that initialisation is conditional i.e. determined by the
program (prohibition of PEN conductor in certain cases,
etc.)
Prev means that the parameter will be initialised identically to the
previous circuit (e.g. method of installation)
Choosing to create a new circuit from a style means that CANECO BT identifies the type of equipment
according to the standard style from which the selected style was itself created. On the basis of this
information, CANECO BT performs particular operations e.g.:
- automatic creation of a board if the style was created from the Board style
- choice of particular power values: a circuit having a motor-type equipment gives access to the standard
mechanical power values for motors.
- check of the consistency of circuit data. For example: CANECO BT advises against the use of gG fuse
protection for a circuit with motor-type equipment.
Notes
Training Manual for CANECO BT 5.3 75
Drag/Drop
Notes
Training Manual for CANECO BT 5.3 76
Another method
Notes
Training Manual for CANECO BT 5.3 77
Click on "open:"
Notes
Training Manual for CANECO BT 5.3 78
Dynamic display
Example 2: We want to add one or more data (cable cross-section, Ik, discrimination etc………….)
Double-click
on Cable
Notes
Training Manual for CANECO BT 5.3 79
Ability
- insert disconnection devices in
the calculated circuits (switch,
contactor, etc.)
- create associated circuits which
will not be calculated
- insert blocks (circuits which will
be calculated)
List of styles
List of blocks
created
Notes
Training Manual for CANECO BT 5.3 80
Caneco BT can handle non-calculated circuits, internal or external to the cabinet: non-calculated power
circuits, control-command circuits, measurement and low-current circuits (telephone, alarms, measurements,
home automation) These circuits are often associated with power circuits designed by Caneco BT and are
known as associated circuits. Parameters can be assigned to these circuits, allowing the generation of a
completed board single-line diagram:
Pro te ctio n
Only the board single-line diagram allows you to view the associated circuits, but three tools are available for
creating them: the concept of a style
the insert an image function in the Edit menu
drawing, in the board single-wire diagram, library symbols in a blank associated circuit.
Style-defined associated circuits. When you define a style for a circuit (Styles command in the Options
menu) you can add associated circuits to it. This allows the correct processing of circuits calculated by
Caneco BT associated with non-calculated circuits which are electrically connected to them: motor protected
by aM+thermal with star-delta reverser-starter, lighting with security units. The latter circuits are among the
styles supplied with Caneco BT.
When you create a circuit from a style that includes associated circuits (from the three Caneco BY editors),
these are created automatically. They are only visible, however, in the board single-line diagram:
Example Motor with Varistor
Notes
Training Manual for CANECO BT 5.3 81
The Network Single-Line diagram enables you to see the main circuits and the terminal circuits.
You can add labels (ref marks, rating, length, etc.)
Select from the drop-down menu: Tools / Preferences
Labels
Notes
Training Manual for CANECO BT 5.3 82
Printing labels
Select from the drop-down menu: Tools / Printing models / Document models
If ticked: print
labels
Notes
Training Manual for CANECO BT 5.3 83
PRINTING
PRINT CONFIGURATION
COMPOSITION OF A CANECO BT PRINT FOLDER
Calculation notes
Transfer of documents to
Flyleaf
The user selects the document models which he wants to include in his print folder, from the menu: Tools /
Printing models
Notes
Training Manual for CANECO BT 5.3 84
"Client" tab
"Project" tab
Select custom Logo in the Tools menu, then
Preferences thenprint and select
company logo.
Notes
Training Manual for CANECO BT 5.3 85
To insert a logo:
1. Go to Tools – Preferences
2. Select the "Print" tab
3. Select the LOGO in the FOLIOS folder
4. Confirm by "OPEN" Click on three points to open
“FOLIOS” folder
Notes
Training Manual for CANECO BT 5.3 86
1. Click on "New"
2. Specify the document name
Notes
Training Manual for CANECO BT 5.3 87
The newly-created document model is empty. The next stage will be to specify the file to be associated with
the document model.
The procedure to be followed is detailed below:
Right-click
browse
Notes
Training Manual for CANECO BT 5.3 88
« LIST OF FOLIOS »
Notes
Training Manual for CANECO BT 5.3 89
TGBT
POMPE1
POMPE2
COND1
ASC1
ASC2
TD0
TD1
TD2
TD3
TD4
1F01
ECL FM
1E02
1E03
1E04
1E05
1E06
1E07
1E08
1E09
1E10
1E11
1F02
1F03
1F04
1F05
1F06
EXTERT
Folio
A bon pour exécution AFFAIRE N° 123AH2A
6
Ind. MODIFICATIONS
Unifilaire général Date : 22/05/97 Fichier : EXTERT PLAN N° 48
Notes
Training Manual for CANECO BT 5.3 90
« CABLES LIST »
Notes
Training Manual for CANECO BT 5.3 91
PROTECTION SETTINGS:
CONSUMER LIST:
Notes
Training Manual for CANECO BT 5.3 92
CABLE NOMENCLATURE:
Notes
Training Manual for CANECO BT 5.3 93
Notes
Training Manual for CANECO BT 5.3 94
Notes
Training Manual for CANECO BT 5.3 95
PRACTICAL WORKSHOPS
Notes
Training Manual for CANECO BT 5.3 96
WORKSHOP 1: FAMILIARISATION WITH DATA ENTRY TOOLS
A B C
Standby direct on Normal feeding MSB
distribution board Standby feeding standby MSB
Normal and standby on MSB
MSB MSB
Standby
MSB
APPENDICES
FACTS ABOUT CABLES
Cables
Op. temp.: : maximum temperature of conductor cores for operation at continuous rating.
S-C temp: maximum core temperature in short-circuit condition
Separating
tape
Protective sheath
Filler
Maximum allowable thermal stresses on conductors depend on the nature of the insulation in direct
contact with the core.
3 2
2 3 2 3 2
N
1 1 3
PE N 1 PE N
1
PE
5G10 3X70+G50 Multi +PE
with integrated PE 4X10 with reduced integrated PE 4X10 + separate PE 1X6
Not reduced
Wiring systems using single-core cables:
λ: (mΩ / m)
Multicore cables
0,08
or single-core cables in trefoils
Touching single-core cables in layers 0,09
Separate single-core cables 0,13
Training Manual for CANECO BT 5.3 104
Non-compliance with the specified symmetry conditions for 2 and 4 cables per phase or the use of 3 cables
per phase requires the application of a coefficient fs equal to 0.8.
Applying the symmetry coefficient fs does not remove the need to take grouping into account, which means
that when a circuit uses several single-core cables per phase, account should be taken of as many circuits
as there are cables per phase.
If Caneco detects the installation of several cables in parallel, the user can choose whether or not to apply
the symmetry factor. The default value of the symmetry coefficient is 1 (symmetrical arrangement of
conductors).
1st case: 2 or 4 cables per phase: the user may or may not apply the symmetry coefficient
If the number of conductors is greater than 4, message indicating non-compliance with
the standard requirements, but the calculation can nevertheless be performed.
2nd case: 3 cables per phase: Caneco applies the mandatory coefficient of 0.8.
Symmetry is not possible
installation is symmetrical
3 2 2 3 Fs = 1
and touching by default or separated by 2 diameters.
1 1
A protective device must automatically disconnect from the power supply the circuit or equipment
protected by this device against indirect contacts in such a manner that, following a fault between a live part
and an earth in the circuit or equipment, a presumed contact voltage greater than 50 Volts for A.C. or 120
Volts for smoothed D.C. cannot persist for a time sufficient to be physiopathologically dangerous for a person
in contact simultaneously with accessible conducting parts.
Without taking into account the contact voltage, a disconnection time of not more than 5 seconds is
permitted in certain circumstances, depending on the earth connections diagram (distribution circuits)
If the protection conditions defined in paragraph 411.3.2.1 cannot be met in an installation or part of
an installation, a local wiring system said additional equipotential bonding (see paragraph 415.2) must
be created.
Creating additional equipotential bondings avoids the hazards caused by indirect contacts if, in the
event of a fault, disconnection is not fast enough.
Notes 1. - This additional equipotential bonding may serve the whole installation, part of it, an equipment
or a location
2. - The use of additional equipotential bondings does not eliminate the need to disconnect the
supply for other reasons, such as fire prevention, equipment thermal stress, etc.
3. - Additional requirements may be necessary for specific locations.
However, other harmful events may occur, such as heating of an equipotentiality conductor, increased earth electrode
resistance due to drought, etc. This is valid both in the case of a first fault in TT and TN installations and for a
second fault in IT installations.
Training Manual for CANECO BT 5.3 106
- Between two exposed conductive parts: - Between an exposed conductive part and a
structure:
Si S PE1 ≤ S PE2
SPE1
SLS = (*)
S LS = S PE1
2
M1 M2 M
Conductors not incorporated into a cable are mechanically protected if they are installed in ducts,
raceways or mouldings or are protected in a similar way.
There is no need to use equipotential bonds for conductive parts which are not liable to propagate an
external voltage, e.g. certain metal fittings, ventilation grills, stair rails, etc.
Bonding of the reinforced concrete armature is limited to a loop at the base of the foundations under
the conditions defined in the Standard when the appropriate bonds are established when the building is
constructed.
Note:
If the AEB option is chosen in CANECO BT, cable wording will be printed as: 3 * 70 +G50 +
AEB, if an AEB is necessary
Equipotental bonding : Means that the equipment conductive part is bonded to the general
conductive part equipotentiality.
Training Manual for CANECO BT 5.3 107
(STANDARD))
The main equipotential bonding conductors must have a cross-section of not less than half that of the largest
protective conductor in the installation, with a minimum of 6 mm². Their cross-section may however be limited to 25 mm²
if they are copper, or an equivalent cross-section for another metal.
(COMMENTS)
1 The general main equipotential bonding is that specified in paragraph 411.3.1.1 of NF C15-100 in each
building
2 The local equipotential bonding allows a disconnection time of 5 seconds without taking account of the value
of the contact voltage.
1 General main equipotential bonding (411.3.1.1) created at the origin of the installation and at least in every
building if the installation involves more than one building.
If a metal pipe penetrates into a building at a point far from the main distribution board of the installation, and if that
pipe is connected locally to a protective conductor, it is not necessary to connect the pipe to the main equipotential
bonding. The bond between the pipe and the protective conductor is then considered as an additional equipotential
bonding (415.2.1).
This local equipotential bonding is intended to create a reference point such that its potential in the event of a fault
can be considered as broadly identical to that of the general main equipotential bonding (1).
Training Manual for CANECO BT 5.3 108
GLOSSARY
Source Glossary
Power Source standardized Power in KVA. (1 to 2500 kVA)
File Dry95.ZTR : File for dry transformers
Oil95.ZTR : File for oil transformers
Ukr Short circuit voltage in %
Xd Transient direct Reactance in % (standard 30%)
Xo Steady state direct Reactance in % (standard 6%)
Network
LV Voltage Source operating voltage, between phases, on load (default 400V).
No load voltage is equal to 1.05 times operating voltage
Frequency Network frequency 50Hz or 60Hz
Funct. T. Prot HV Operating time for HV protective device at transformer HV/LV primary level.
Pcc. HV Min High voltage Min short circuit Power (default 500 MV
Pcc. HV Max High voltage Max short circuit Power (default 500 MV
Factors
Temperature (K T) Temperature factor downgrading Cable current carrying capacity.
Group (K prox) Conductors group factor
Symetrical fs fs Symetrical factor according to standard (0.8)
Conductors
Phase Phase conductor cross-section
PEN Neutral/PEN conductor cross-section
Po Protective conductor cross-section
Loaded Neutral
Results
IB Transformer Nominal intensity calculated with on load voltage (between phases)
STH Theoretical cross-section calculated according to overload condition
dU total Voltage drop % at MSB level from transformer
Ik2/3 Max Max short-circuit current two-phase or three-phase on MSB (in A)
Ik1 Max Max short-circuit current single-phase on MSB (in A)
Ik1/2 Min Mini short-circuit current on MSB (in A) (Single with Neutral, two-phase without
Neutral)
If Default short circuit current (phase - PE), at MSB level (in A)
Training Manual for CANECO BT 5.3 109
Circuit Glossary
Circuit
Upstream Distribution upstream reference mark
Ref Mark Circuit reference mark (15 characters maximum)
Style Circuit style (model)
D/Origin Connecting distance from the beginning of the Busbar trunking system
Bus Bar Upstream sub-busbar Ref Mark
Supply Circuit supply (Normal, Standby, N and S)
Content Wiring system distribution (3P+N+PE, P+N+PE…)
Designation Circuit designation (36 characters maximum)
Index Circuit modification index
Protection
Type Type of protective device used (General purpose Breaker, C curve breaker, B curve
breaker…)
Indirect Contacts Protection against indirect contacts
Rating Circuit breakers rating or support rating (Switch, disconnector or Disconnector switch)
or fuse rating
K on C Oversizing factor for overload setting
Thermal relay Thermal relay reference
In/Irth/IrLR Circuit-breaker thermal setting or fuse rating insuring protection against overload.
IrMg/In Circuit-breaker magnetic setting insuring protection against short-circuits or fuses
rating value
Cal. gG Fuse rating
Delay (SC CC) Circuit breakers magnetic delay in ms
Differential protection Circuit breakers residual current (differential) setting in mA
setting
Delay (Prot. Diff) Time delay on RCD relay in ms
Cable
Type Type of cable (PVC, XLPE, PRC…)
Core Core nature (Copper or Aluminium)
Pole Single-core or multi-core cables
Instal method Installation method according to standard
Length(m) the cable length in meters
1st Equip(m) Distance from protective device to nearest equipment
K Temp Temperature factor on IZ (from 0.4 to 1.3 - 1.0 for 30°C)
K Group Group factor on IZ (from 0.2 to 1.3) according to installation method and number of
cables
K Additional Additional downgrading factor on IZ (explosive atmosphere 0.85, unbalanced neutral
0.84…)
Symetrical factor fs Symetrical factor (0.8) for wiring systems with cables in parallel
Total Correction Total correction factor (K Temp x K Group x K Addit x fs x Neutral factor)
Phase Phase cross-section
Neutral Neutral cross-section
PE/PEN PE or PEN cross-section
Loaded Neutral apply an additional factor of 0.84 to current carrying capacity if Neutral is loaded
Equipment
Nb Equipment number for final circuits
Consumption Consumption for each equipment (in A, W, kW, VA, kVA and kVAR)
Location Circuit Geographical location (used in cable tracks module)
TH<= 15% Level of 3rd order harmonics < 15%
15% < TH <= 33% Level of 3rd order harmonics between 15% and 33%
Use factor Circuit use factor
Coincidence factor Coincidence factor (Diversity, simultaneity) of equipments fed by same circuit
Cos phi Equipment Cosinus phi (Circuit Power Factor)
Cos phi (start) Cosinus phi at start
ID/IN Starting current, ratio between Starting current and steady current
dU max Maximum admissible voltage drop in %from beginning of installation
Training Manual for CANECO BT 5.3 110
Results window
Cable Multicore cable conventional writing, or phase conductors if the wiring system is of
single-core type
Examples :
4G1,5 means 4 conductors out of which 1 is earth (yellow-green) (G = ground
3*50+N35 means 3 phase conductors + 1 N conductor of 35 mm2
Neutral Neutral conductors conventional writing if the wiring system is of single-core type.
PE or PEN PE/PEN conductors conventional writing if the wiring system is of single-core type.
Criterion Criterion for the phase cross-section calculation
MINI: Minimal cross-section (ex 1.5mm2 for Light, 2.5mm2 for Socket motors…)
IN : overload condition
DU : Voltage drop
IC : Indirect contacts, Human protection against electrical shocks
SC : Thermal stress after Short-Circuit
FIXED : Fixed value by user
Max Length Cable maximal length to keep protection and circuit design conditions
IB (A) Circuit design current directly deducted from consumption in A
STH (mm²) Theoretical cross-section calculated in mm2, according to overload condition.
IZ (A) Current carrying capacity of the wiring system, adjusted with correction factors
This value gives the maximum protection thermal setting.
dU circuit (%) Circuit voltage drop in % on the cable length
dU total (%) Total Voltage drop in % from source supply
dU start Voltage drop at start (motors) or when switching on (lights)
Ik2/3 Max Maximum two-phase or three-phase short-circuit current (in A) at the end of the circuit
Ik1 Max Maximum single-phase short-circuit current (in A) at the end of the circuit
Ik2 Min Maximum two-phase short-circuit current (in A) at the end of the circuit
Ik1 Min Minimum single-phase short-circuit current (in A)at the end of the circuit
If Fault current (phase/PE) or double fault in case of IT system (in A) at the end of the
circuit
IrMg Max Maximum magnetic setting of protective device.
Ik UpStr/DwnStr IK Max Upstream / Downstream the wiring system in kA.
Discrimination Discrimination (selectivity) with upstream on short-circuit.
Backup Back-up protection (IEC 60947-2 Annex A) with or without association (coordination)
with upstream protective device.
Magnetic Standard, low or electronic according to chosen device.
L Track (m) Track length
Link Price Cable price (material)
Circuit state OK
To recalculate : circuit must be re-calculated (change in some data)
Cable not correct : circuit in which cable cross-section ahs been fixed to a value too
small
Protection not correct : protective device with settings not correct
Training Manual for CANECO BT 5.3 112
Board Glossary
Ref mark Board Downstream Ref mark.
Designation Board designation
Coincidence factor t Diversity/Simultaneity factor for circuits fed by the considered board.
Geographical location Equipment geographical location.
Earthing system Board Earthing system : TT, TNC, TNS, IT
Voltage between phase and neutral, in a single phase board (Phase-Neutral),
between phases in other cases
No load voltage No load voltage in V, used to calculate Ik3 Max.
Upstream circuit ref Circuit Upstream ref mark. (feeding board)
mark
Breaking device Board breaking device (generally a switching device in distribution
boards).
IC Protection Nature of the human protection against electrical shock (RCD…)
I Allowed Allowed current downstream board.
I available Available current downstream board.
S Intensities Design current IB sum of all circuits issued from the board multiplied
by the board diversity/simultaneity factor.
Mean cos phi Mean cosinus phi at board level, taking into account downstream
circuits and eventual capacitors
R=S IZ cables / Irth Ration between :
board Sum of IZ of downstream circuits (IZ calculated without taking into
account group factor) and upstream thermal relay setting.
UPS Glossary
Power Power in kVA
Tsc sustaining time of the UPS in ms
Ik3 Maximum three-phase short-circuit current (in A)
Ik2 Maximum two-phase short-circuit current (in A)
Ik1 Maximum single-phase short-circuit current (in A)
If Fault current (phase/PE) (in A)