2CDC231001S0010
Description Order data
–– Overload protection – trip class 10 T16 screw terminal
–– Phase loss sensitivity For B6/B7/VB6/VB7 mini contactors
–– Temperature compensation from -25 … +60 °C For AS block contactors
–– Adjustable current setting for overload protection
–– Automatic or manual reset selectable
–– Suitable for three- and single-phase application Setting range Type Order code Packing Weight
unit per PCE
–– Trip-free mechanism
A PCE kg
–– Status indication
0.10 ... 0.13 T16-0.13 1SAZ711201R1005 1 0.100
–– STOP and TEST function 0.13 ... 0.17 T16-0.17 1SAZ711201R1008 1 0.100
–– Direct mounting onto mini contactors or block contactors 0.17 ... 0.23 T16-0.23 1SAZ711201R1009 1 0.100
0.23 ... 0.31 T16-0.31 1SAZ711201R1013 1 0.100
0.31 ... 0.41 T16-0.41 1SAZ711201R1014 1 0.100
0.41 ... 0.55 T16-0.55 1SAZ711201R1017 1 0.100
Approvals Marks 0.55 ... 0.74 T16-0.74 1SAZ711201R1021 1 0.100
0.74 ... 1.00 T16-1.0 1SAZ711201R1023 1 0.100
A cULus UL 508 a CE
1.00 ... 1.30 T16-1.3 1SAZ711201R1025 1 0.100
K CB scheme 1.30 ... 1.70 T16-1.7 1SAZ711201R1028 1 0.100
1.70 ... 2.30 T16-2.3 1SAZ711201R1031 1 0.100
E CCC 2.30 ... 3.10 T16-3.1 1SAZ711201R1033 1 0.100
3.10 ... 4.20 T16-4.2 1SAZ711201R1035 1 0.100
ABS 4.20 ... 5.70 T16-5.7 1SAZ711201R1038 1 0.100
5.70 ... 7.60 T16-7.6 1SAZ711201R1040 1 0.100
RINA 7.60 ... 10.0 T16-10 1SAZ711201R1043 1 0.104
10.0 ... 13.0 T16-13 1SAZ711201R1045 1 0.104
DNV
13.0 ... 16.0 T16-16 1SAZ711201R1047 1 0.104
P Lloyd’s Register
2 3 Status indication
3
4 RESET button
2CDC231001S0010
4
Automatic or manual reset selectable
5
Operation mode
1~ 3~
2CDC232001F0010
Wiring diagram
A
RESET 95 97
M
2CDC232001F0009
TEST
2T1 4T2 6T3 STOP 96 98
2 - 2CDC106020D0201
Resistance and power loss per pole and short-circuit protection device
Technical diagrams
Intermittent periodic duty
(s)
40
(Op/h)
140
20
120
11
switching frequency
10
100
ta =
6
80
0.5
tripping time
4
ta
60 3
=
1
ta =
s
1.5 2
40 ta = s
3s
20 ta = 5
s
1
ABB827833
ABB836246
0 3 4 5 6 7 8
0 20 40 60 80 100 (%) 7.4
duty ratio multiple of setting current
Dimensions
in mm and inches
8.6 0.34" 9.1 0.36"
1.2 0.05" 36.9 1.45" 2.4 0.09"
3.02"
76.7
2CDC232008F0008
2CDC106020D0201 - 3
Technical data IEC/EN
Data at TA = 40 °C and at rated values, if nothing else indicated
Main circuit
2T1-4T2-6T3
Rated operational voltage Ue 690 V a.c.
- V d.c.
Setting range - thermal overload protection see table on page 1
Rated operational current AC-3 Ie see upper value of setting range, see table on page 3
Trip class 10
Rated frequency 50/60 Hz
Number of poles 3
Resistance per pole see table on page 3
Power loss per pole see table on page 3
Short-circuit protection device see table on page 3
4 - 2CDC106020D0201
Auxiliary circuit
95-96, 97-98
Rated operational voltage Ue 600 V
Conventional free air thermal current Ith NC, 95-96 6A
NO, 97-98 4A
Rated frequency d.c., 50/60 Hz
Number of poles 1NC + 1NO
Rated operational current Ie
acc. to IEC/EN 60947-5-1 for utilization category
at AC15 at 110-120 V NC, 95-96 3.00 A
NO, 97-98 0.75 A
at AC15 at 220-230-240 V NC, 95-96 3.00 A
NO, 97-98 0.75 A
at AC15 at 440 V NC, 95-96 0.75 A
NO, 97-98 0.75 A
at AC15 at 480-500 V NC, 95-96 0.75 A
NO, 97-98 0.75 A
at DC13 at 24 V NC, 95-96 1.25 A
NO, 97-98 1.25 A
at DC13 at 110-120-125 V NC, 95-96 0.55 A
NO, 97-98 0.55 A
at DC13 at 250 V NC, 95-96 0.27 A
NO, 97-98 0.27 A
at DC13 at 500 V NC, 95-96 0.15 A
NO, 97-98 0.15 A
Minimum switching capacity 17 V / 3 mA
Short-circuit protection device NC, 95-96 6 A, Type gG
NO, 97-98 4 A, Type gG
2CDC106020D0201 - 5
General data
Electromagnetic compatibility
Environmental data
Standards / directives
6 - 2CDC106020D0201
Technical data UL/CSA
Main circuit
Max. operational voltage 600 V a.c.
Trip rating 125 % of FLA
Full load amps (FLA) see table above
Short-circuit rating RMS symmetrical see table above
Short-circuit protection device see table above
Electrical connection
Connecting capacity stranded 1/2 x AWG 18 ... 10
flexible without ferrule 1/2 x AWG 18 ... 10
Stripping length 12 mm
Tightening torque 9 ... 13 Ib-in
Auxiliary circuit
Conventional thermal current NC, 95-96 5A
NO, 97-98 2.5 A
Making and breaking capacity NC, 95-96 B600, Q300
NO, 97-98 D300, Q300
Electrical connection
Connecting capacity stranded 1/2 x AWG 18 ... 12
flexible without ferrule 1/2 x AWG 18 ... 12
Stripping length 9 mm
Tightening torque 9 ... 13 Ib-in
2CDC106020D0201 - 7