You are on page 1of 9

Downloaded from http://iranpaper.

ir
http://www.itrans24.com/landing1.html

1700 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 4, APRIL 2013

Multiple Distributed Generator Placement in Primary


Distribution Networks for Loss Reduction
Duong Quoc Hung, Student Member, IEEE, and Nadarajah Mithulananthan, Senior Member, IEEE

Abstract—This paper investigates the problem of multiple dis- them in an optimal way such that it will increase reliability,
tributed generator (DG units) placement to achieve a high loss reduce system losses, and hence improve the voltage profile
reduction in large-scale primary distribution networks. An im- while serving the primary goal of energy injection.
proved analytical (IA) method is proposed in this paper. This
method is based on IA expressions to calculate the optimal size DG units are modeled as synchronous generators for small
of four different DG types and a methodology to identify the best hydro, geothermal, and combined cycles; combustion turbines;
location for DG allocation. A technique to get the optimal power and wind turbines with power electronics. Induction genera-
factor is presented for DG capable of delivering real and reactive tors are used in wind and small hydropower generation. DG
power. Moreover, loss sensitivity factor (LSF) and exhaustive load units are considered as power electronics inverter generators
flow (ELF) methods are also introduced. IA method was tested and
validated on three distribution test systems with varying sizes and or static generators for technologies such as photovoltaic (PV)
complexity. Results show that IA method is effective as compared plants and fuel cells [7], [8]. For instance, DG using a PV
with LSF and ELF solutions. Some interesting results are also grid-connected converter is controlled on the basis of the
discussed in this paper. droop-control technique presented in [9]–[17]. The converter is
Index Terms—Analytical expression, loss reduction, loss sensi- capable of providing active power to local loads and injecting
tivity factor (LSF), multiple DG, optimal location, optimal power reactive power to stabilize load voltages. Furthermore, the type
factor, optimal size. of DG technology adopted will have a significant bearing on
the solution approach. For example, in [18], the installation of
I. I NTRODUCTION synchronous machine-based DG units that are close to the loads
can lead to a gain in the system voltage stability margin; on the

I N RECENT YEARS, the penetration of distributed gen-


erator (DG) into distribution systems has been increasing
rapidly in many parts of the world. The main reasons for
other hand, in the case with an induction generator, the system
stability margin is reduced. Given the choice, DG units should
be placed in appropriate locations with suitable sizes and types
the increase in penetration are the liberalization of electricity to enjoy system-wide benefit.
markets, constraints on building new transmission and distribu- It is evident that any loss reduction is beneficial to distri-
tion lines, and environmental concerns [1]–[3]. Technological bution utilities, which is generally the entity responsible to
advances in small generators, power electronics, and energy keep losses at low levels. Loss reduction is, therefore, the
storage devices for transient backup have also accelerated the most important factor to be considered in the planning and
penetration of DG into electric power generation plants [4]. operation of DG [19], [20]. For instance, multiobjective index
At present, there are several technologies used for DG appli- for performance calculation of distribution systems for single
cations that range from traditional to nontraditional technolo- DG size and location planning has been proposed [19]. For this
gies. The former is nonrenewable technologies such as internal analysis, the active and reactive power losses receive significant
combustion engines, combined cycles, combustion turbines, weights of 0.40 and 0.20, respectively. The current capacity
and microturbines. The latter is renewable technologies such as receives a weight of 0.25, leaving the behavior of voltage profile
solar, photovoltaic, wind, geothermal, ocean, and fuel cell. The at 0.15.
main advantages of using renewable-energy-based DG sources In a radial feeder, depending on the technology, DG units
are the elimination of harmful emissions and inexhaustible can deliver a portion of the total real and/or reactive power to
resources of the primary energy. However, the main disadvan- loads so that the feeder current reduces from the source to the
tages are relative low efficiency, high costs, and intermittency location of DG units. However, studies [21]–[23] have indicated
[5], [6]. that if DG units are improperly allocated and sized, the reverse
As the penetration of DG units increases in the distribution power flow from larger DG units can lead to higher system
system, it is in the best interest of all players involved to allocate losses. Hence, to minimize losses, it is important to find the best
location and size given the option of resource availability. A
technique for DG placement using “2/3 rule” which is tradition-
ally applied to capacitor allocation in distribution systems with
Manuscript received June 18, 2010; revised November 18, 2010; accepted
December 12, 2010. Date of publication February 4, 2011; date of current uniformly distributed loads has been presented [22]. Although
version November 22, 2012. simple and easy to apply, this technique cannot be applied
The authors are with the School of Information Technology and Electrical directly to a feeder with other types of load distribution or to
Engineering, the University of Queensland, Brisbane, Qld. 4072, Australia
(e-mail: hung.duong@uq.edu.au; mithulan@itee.uq.edu.au). a meshed distribution system. In [24], an analytical approach
Digital Object Identifier 10.1109/TIE.2011.2112316 has been presented to identify the location to optimally place

0278-0046/$26.00 © 2011 IEEE


Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

HUNG AND MITHULANANTHAN: MULTIPLE DG PLACEMENT IN PRIMARY DISTRIBUTION NETWORKS FOR LOSS REDUCTION 1701

single DG with unity power factor in radial as well as meshed in calculation; however, it can lead to a completely optimal
networks to minimize losses. However, in this approach, the solution. Its numerical results are presented in Section III.
optimal sizing is not considered. The genetic algorithm (GA)-
based method has been presented to determine the size and
A. Power Losses
location of DG [25], [26]. GA is suitable for multiobjective
problems and can lead to a near optimal solution but demand The total real power loss in a power system is represented by
higher computational time. An analytical approach based on an an exact loss formula [28]
exact loss formula has been presented to find the optimal size
and location of single DG [21]. In this method, a new methodol- 
N 
N
PL = [αij (Pi Pj + Qi Qj ) + βij (Qi Pj − Pi Qj )] (1)
ogy has been proposed to quickly calculate approximate losses i=1 j=1
for identifying the best location; the load flow is required to be
performed only twice. In the first time, it is applied to calculate where
the loss of the base case, and in the second time, it is used rij rij
to find the minimum total loss after DG placement. Although αij = cos(δi − δj ); βij = sin(δi − δj )
Vi Vj Vi Vj
this method requires less computation, single DG capable of
delivering real power only is considered. A probabilistic-based Vi ∠δi complex voltage at the bus ith;
planning technique has been proposed for determining the rij + jxij = Zij ijth element of [Zbus] impedance matrix;
optimal fuel mix of different types of renewable DG units Pi and Pj active power injections at the ith and jth
(i.e., wind, solar, and biomass) in order to minimize the annual buses, respectively;
energy losses in the distribution system [23]; however, DG Qi and Qj reactive power injections at the ith and jth
units capable of delivering real power only is considered in this buses, respectively;
paper. Recently, the authors in [27] have presented an effective N number of buses.
method based on improved analytical (IA) expressions to place
four different types of single DG for loss reduction. However,
multiple DG unit placement has not been addressed in this B. IA Method
paper. To overcome limitations in previous works, this paper In this paper, an effective methodology is proposed to find the
proposes an IA method for allocating four types of multiple optimal location, size, and power factor of multiple DG units in
DG units for loss reduction in primary distribution networks. distribution networks. A brief description of the IA expressions
This method is based on IA expressions in [27] to calculate and optimal power factors for single DG allocation is presented
the optimal size of four different DG types and a methodology as follows [27]:
to identify the best location for multiple DG allocation. The 1) IA Expressions: Type 1 DG (i.e., 0 < P FDG < 1) is
importance of DG operation (i.e., real and reactive power capable of injecting both real and reactive power (e.g., syn-
dispatch) for loss minimization along with a “fast approach” chronous generators). The optimal size of DG at each bus i for
as a simple way to quickly select the power factor of DG minimizing losses can be given by (2) and (3)
units that is close to the optimal power factor is also presented.
The proposed methodology is computationally less demanding. αii (PDi + aQDi ) − Xi − aYi
PDGi = (2)
Moreover, voltage profile enhancement is also examined. a2 αii + αii
The remainder of this paper is organized as follows: QDGi = aPDGi (3)
Section II explains the proposed IA method. Procedure for mul-
tiple DG placement using IA method and loss sensitivity factor in which
(LSF) method is also elaborated in this section. Section III  
portrays the test distribution systems and numerical results a = (sign) tan cos−1 (P FDG )
along with some observations and discussions for multiple DG
placement. Finally, the major contributions and conclusions are sign = +1 DG injecting reactive power
summarized in Section IV. 
n 
n
Xi = (αij Pj − βij Qj ) Yi = (αij Qj + βij Pj ).
j=1 j=1
j=i j=1

II. M ETHODOLOGY
The aforementioned equations give the optimum size of DG
This section focuses on a detailed description of IA method. for each bus i, for the loss to be minimum. Any size of DG
To check the effectiveness and applicability of the proposed other than PDGi placed at bus i will lead to a higher loss.
method, LSF and exhaustive load flow (ELF) methods for This loss, however, is a function of loss coefficients α and β.
allocating multiple DG units are used. LSF method has been When DG is installed in the system, the values of loss co-
employed to select the candidate locations for single DG place- efficients will change, as it depends on voltage and angle.
ment to reduce the search space. A brief description of LSF al- Updating the values of α and β again requires another load
gorithm for multiple DG units is given at the end of this section. flow calculation. However, numerical results showed that the
ELF method, known as a repeated load flow solution, demands accuracy gained in the size of DG by updating α and β is small
excessive computational time since all buses are considered and negligible [21]. With this assumption, the optimum size of
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1702 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 4, APRIL 2013

repeated approach is also introduced to check the effectiveness


of the fast approach. It is interesting to note that, in all the three
test systems used in this paper, the optimal power factor of DG
units placed for loss reduction is found to be closer to the power
factor of the combined load of respective systems.
a) Fast Approach: The power factor of the combined load
Fig. 1. Simple distribution system with single DG. of the system (P FD ) can be expressed by (6). The total active
and reactive power of the load demand is expressed as
DG for each bus, given by the aforementioned relations, can be

N 
N
calculated from the base case load flow (i.e., without DG case). PD = PDi QD = QDi .
This methodology requires the load flow to be carried out only i=1 i=1
two times for single DG allocation, one for the base case and
another at the end with DG included to obtain the final solution The “possible minimum” total loss can be achieved if the
[21], [27]. power factor of DG (P FDG ) is selected to be equal to that of
Type 2 DG (i.e., 0 < P FDG < 1) is capable of injecting the combined load (P FD ). That can be expressed as
real power but consuming reactive power (sign = −1) (e.g.,
induction generators). Similar to type 1 DG, the optimal size
P FDG = P FD . (8)
of type 2 DG at each bus i for the minimum loss is given by
(2) and (3).
Type 3 DG (i.e., P FDG = 1, a = 0) is capable of injecting b) Repeated Method: In this method, the optimal power
real power only (e.g., PV, microturbines, and fuel cells which factor is selected by calculating a few power factors of DG units
are integrated to the main grid with the help of converters/ (change in a small step of 0.01) that are near to the power factor
inverters). The optimal size of DG at each bus i for the mini- of the combined load. The sizes and locations of DG units at
mum loss is given by reduced (4) various power factors with respect to losses are identified from
(2) and (3). The losses are compared, and the optimal power
1  factor of DG units at which the total loss is at minimum is
N
PDGi = PDi − (αij Pj − βij Qj ). (4) determined.
αii j=1
j=i
3) Optimization Algorithm for Multiple DG Allocation:
This algorithm is made on the basis of the IA expressions [27]
Type 4 DG (i.e., P FDG = 0, a = ∞) is capable of delivering to find the optimal buses at which the losses are the lowest and
reactive power only (e.g., synchronous compensators). The where multiple DG units are best placed. The IA expressions
optimal size of DG at each bus i for the minimum loss is given help reduce the solution space. Fig. 2 illustrates the flowchart of
by reduced (5) IA method for multiple DG allocation. The descriptions of each
step in detail are given as follows. In this paper, based on an idea
of updating the load data after each time of DG placement, the
1 
N
QDGi = QDi − (αij Qj + βij Pj ). (5) algorithm is proposed to solve optimal multiple DG placement.
αii j=1
j=i
First, a single DG is added in the system. After that, the load
data are updated with the first DG placed and then another DG
2) Power Factor Selection: Consider a simple distribution is added. Similarly, the algorithm continues to allocate other
system with two buses, a source, a load, and a DG connected DG units until it does not satisfy at least one of the constraints
through a transmission line as shown in Fig. 1. in step 7 as described as follows.
The power factor of the single load (P FD ) is given as The computational procedure to allocate multiple DG units
on the basis of the IA expressions is described in detail as
PD follows.
P FD =  2
. (6)
PD + Q2D Step 1) Enter the number of DG units to be installed.
Step 2) Run the load flow for the base case and find losses
The power factor of the single DG injected (P FDG ) is using (1).
given as Step 3) Calculate the power factor of DG using (8) or enter
the power factor of DG.
PDG Step 4) Find the optimal location of DG using the following
P FDG =  . (7)
PDG + Q2DG
2
steps.
a) Calculate the optimal size of DG at each bus
It is obvious that the minimum loss occurs when the power using (2) and (3).
factor of the single DG as (6) is equal to that of the single load b) Place the DG with the optimal size, as mentioned
as (7). earlier, at each bus one at a time. Calculate the
To find the optimal power factor of DG units for a radial approximate loss for each case using (1) with the
complex distribution system, a fast approach is proposed. A values α and β of the base case.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

HUNG AND MITHULANANTHAN: MULTIPLE DG PLACEMENT IN PRIMARY DISTRIBUTION NETWORKS FOR LOSS REDUCTION 1703

Fig. 3. Flow chart of LSF method to allocate multiple DG units.

C. LSF Method

Fig. 2. Flow chart of IA method to allocate multiple DG units. In this paper, the sensitivity factor of active power loss is em-
ployed to find the most sensitive buses to place DG units which
c) Locate the optimal bus at which the loss is at are capable of injecting active power only (i.e., type 3 DG).
minimum. The sensitivity factor method is based on the principle of lin-
Step 5) Find the optimal size of DG and calculate losses earization of the original nonlinear equation around the initial
using the following steps. operating point, which helps reduce the number of solution
a) Place a DG at the optimal bus obtained in step 4, space. The LSF at the ith bus is derived from (1) with respect
change this DG size in “small” step, update the to active power injection at that bus, which is given as [21]
values α and β, and calculate the loss for each N
∂PL
case using (1) by running the load flow. αi = =2 (αij Pj − βij Qj ). (9)
b) Select and store the optimal size of the DG that ∂Pi j=1
gives the minimum loss.
Step 6) Update load data after placing the DG with the Fig. 3 shows the flow chart of LSF method for multiple DG
optimal size obtained in step 5 to allocate the placement. Similar to IA method, the procedure to find the
next DG. optimal locations and sizes of multiple DG units using the LSF
Step 7) Stop if either the following occurs: is described in detail as follows.
a) the voltage at a particular bus is over the upper Step 1) Enter the number of DG units to be installed.
limit; Step 2) Run the load flow for the base case and find losses
b) the total size of DG units is over the total load using (1).
plus loss; Step 3) Find the optimal location of DG using the following
c) the maximum number of DG units is unavailable; steps.
d) the new iteration loss is greater than the previous a) Find LSF using (9). Rank buses in descending
iteration loss. order of the values of their LSFs to form a
The previous iteration loss is retained; otherwise, priority list.
repeat steps 2 to 6. b) Locate the highest priority bus.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1704 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 4, APRIL 2013

Step 4) Find the optimal size of DG and calculate losses TABLE I


DG P LACEMENT BY VARIOUS T ECHNIQUES FOR 16-B US S YSTEM
using the following steps.
a) Place a DG at the bus with the highest priority
obtained in step 3, change this DG size in “small”
step, update the values α and β, and calculate the
loss for each case using (1) by running the load
flow.
b) Select and store the optimal size of the DG that
gives the minimum loss.
Step 5) Update load data after placing the DG with the
optimal size obtained in step 4 to allocate the
next DG.
Step 6) Stop if either the following occurs:
a) the voltage at a particular bus is over the upper
limit;
b) the total size of DG units is over the total load
plus loss;
c) the maximum number of DG units is unavailable;
d) the new iteration loss is greater than the previous
iteration loss.
The previous iteration loss is retained; otherwise,
repeat steps 2 to 5.

III. N UMERICAL R ESULTS


A. Test Systems
The proposed methodology is tested on three test systems of the base case and three cases with DG numbers ranging
with varying sizes and complexities. The first system used in from one to three are compared. The results include the optimal
this paper is a 16-bus test radial distribution system with a sizes and locations of DG units with respect to the total losses
total load of 28.7 MW and 5.9 MVAr [29]. The second one by each technique. The loss reduction, computational time,
is a 33-bus test radial distribution system with a total load of and schedule of installed DG units of each technique are also
3.7 MW and 2.3 MVAr [30]. The last one is a 69-bus test presented in the table.
radial distribution system with a total load of 3.8 MW and For all the cases, IA leads to a completely optimal solution
2.69 MVAr [31]. as compared with ELF, i.e., the optimal locations and sizes of
Based on the proposed methodology, an analytical software DG units by IA is the same as those by ELF. Among all the
tool has been developed in MATLAB environment to run the cases, LSF yields the lowest loss reduction due to poor choice
load flow, calculate power losses, and identify the optimal size of locations. For instance, placing single DG by IA, ELF, and
and location of multiple DG units. Although the tool can handle LSF yields loss reductions of 67.06%, 67.06%, and 62.15%,
four different DG types and various load levels, the results of respectively.
type 3 DG and type 1 DG at the peak load level, respectively, IA demands shorter computational time compared to ELF as
are presented. expected. However, LSF is the quickest among all methods.
2) 33-Bus Test System: Similar to 16-bus system, Table II
presents the results of the optimal sizes and locations of DG
B. Assumptions and Constraints units by various techniques.
The following are the assumptions and constraints for this For single DG, the loss reduction by IA, at 47.39%, is the
paper: same as that by ELF. Among all the cases, LSF produces a loss
reduction of only 30.48%. For two DG units, the loss reduction
1) The lower and upper voltage thresholds are set at 0.90 and by IA, at 56.61%, is slightly lower than that by ELF, at 58.51%.
1.05 pu, respectively. In contrast, it is higher than the loss reduction by LSF at only
2) The maximum number of DG units is three, with the size 52.32%. For three DG units, IA achieves a loss reduction of
each from 250 kW to the total load plus loss, and the 61.62%, compared with ELF at 64.83%. However, it is better
maximum DG penetration is 100%. than LSF that yields a loss reduction of 59.72%. In general,
for this system, IA method can lead to an optimal solution
for single DG and a near optimal solution for two and three
C. Type 3 DG Placement
DG units.
1) 16-Bus Test System: Table I presents the simulation re- IA needs a short computational time. Particularly, for three
sults of placing DG units by various techniques. The results DG units, the time by IA is 0.40 s, nearly twice longer than that
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

HUNG AND MITHULANANTHAN: MULTIPLE DG PLACEMENT IN PRIMARY DISTRIBUTION NETWORKS FOR LOSS REDUCTION 1705

TABLE II TABLE IV
DG P LACEMENT BY VARIOUS T ECHNIQUES FOR 33-B US S YSTEM DG P LACEMENT AT O PTIMAL AND C OMBINED
L OAD P OWER FACTORS FOR 16-B US S YSTEM

and sizes of DG units. However, it is better than ELF in terms of


computational time. Particularly, for three DG units, the time by
IA is 0.71 s, nearly 33 times shorter than that by ELF at 23.16 s.
It is quite longer than the time by LSF at 0.52 s. In addition, IA
achieves better loss reduction than LSF. For instance, for two
TABLE III
DG P LACEMENT BY VARIOUS T ECHNIQUES FOR 69-B US S YSTEM DG units, IA reaches a loss reduction of 67.94%, while LSF
obtains that of 54.97%.

D. Type 1 DG Placement
1) 16-Bus Test System: Table IV shows the simulation re-
sults of the optimal sizes, locations, and power factors of DG
units by IA for this system. The results of the base case and
three cases with DG units at the optimal and combined load
power factors are compared. The power factor of the combined
load is 0.98 lagging. The optimal power factor of DG units
is identified at 0.99 lagging. In all the cases, the results of
loss reduction at the optimal power factor are slightly higher
compared to those at the combined load factor power. As a
result, selection of the power factor of DG units can be based
on combined load power factor.
Among the cases, three DG units at the optimal power factor
yield a maximum loss reduction of 86.70%, while one DG at
this power factor obtains a minimum loss reduction of only
68.21%. As the number of DG units is increased, the loss
reduction becomes more effective.
These results are obtained with the help of the proposed
method and verified by ELF solutions.
2) 33-Bus Test System: Table V shows the simulation results
of the optimal sizes, locations, and power factors of DG units by
by LSF at 0.23 s. In contrast, it is approximately eight times IA. The power factor of the combined load is 0.85 lagging. The
shorter than the time by ELF at 3.06 s. optimal power factor of DG units is identified at 0.82 lagging.
3) 69-Bus Test System: Table III presents the results of In all the cases, the results of loss reduction at the optimal
optimal sizes and locations of DG units by various techniques. power factor are slightly higher as compared with those at the
For all the cases, IA leads to a globally optimal solution as combined load factor power. Therefore, selection of the power
compared with ELF; particularly, the results by IA are the same factor of DG units that is equal to that of the combined load is
as those by ELF in terms of loss reduction, optimal locations, feasible for this case.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1706 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 4, APRIL 2013

TABLE V TABLE VII


DG P LACEMENT AT O PTIMAL AND C OMBINED VOLTAGES OF C ASES FOR 16-B US T EST S YSTEM
L OAD P OWER FACTORS FOR 33-B US S YSTEM

TABLE VIII
VOLTAGES OF C ASES FOR 33-B US T EST S YSTEM

TABLE VI
DG P LACEMENT AT O PTIMAL P OWER FACTOR FOR 69-B US S YSTEM

TABLE IX
VOLTAGES OF C ASES FOR 69-B US T EST S YSTEM
Similar to 16-bus test system, three DG units at the optimal
power factor produce a maximum loss reduction of 89.45%,
while one DG at this factor obtains a minimum loss reduction
of only 67.85%. The more the number of DG units is installed,
the better the loss reduction increases.
3) 69-Bus Test System: Table VI shows the simulation re-
sults of the optimal sizes, locations, and power factors of DG
units by IA. The results of the base case and three cases
with DG units at the optimal power factor are compared. The
optimal power factor of DG units is determined to be equal to
the combined load power factor at 0.82 lagging. As a result,
selection of the power factor of DG units that is equal to that reduce significantly while satisfying all the power and voltage
of the combined load can lead to an optimal solution for this constraints. This was checked with exhaustive power flow. It is
system. interesting to note that the voltage profile improves when the
Similar to 16-bus and 33-bus test systems, three DG units at number of DG units installed in the system is increased. Power
the optimal power factor result in a maximum loss reduction of factors of DG units too have an influence on voltage profiles as
97.74%. In contrast, one DG at that factor yields a minimum expected.
loss reduction of only 89.68%. As the number of DG units
becomes larger, the loss reduction increases.
IV. C ONCLUSION
This paper has presented IA method for multiple DG al-
E. Results of Voltages
location for loss reduction in large-scale distribution systems
Tables VII–IX indicate the minimum and maximum voltages while fulfilling the main objective of energy injection. This
for all the cases of 16, 33, and 69-bus test systems, respectively. method is based on IA expressions for finding the size of four
In all the cases, after DG units are added, the total losses can different DG types and an effective methodology to find the
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

HUNG AND MITHULANANTHAN: MULTIPLE DG PLACEMENT IN PRIMARY DISTRIBUTION NETWORKS FOR LOSS REDUCTION 1707

best location for DG allocation. In this method, a fast approach [14] J. M. Guerrero, L. Hang, and J. Uceda, “Control of distributed uninter-
to obtain an optimal or near optimal power factor has been also ruptible power supply system,” IEEE Trans. Ind. Electron., vol. 56, no. 8,
pp. 2845–2859, Aug. 2008.
presented for placing DG units capable of delivering real and [15] J. M. Guerrero, J. Matas, L. Garcia de Vicuna, M. Castilla, and J. Miret,
reactive power. Moreover, this paper has also introduced the “Decentralized control for parallel operation of distributed generation
LSF and ELF methods. The proposed IA method is effective inverters using resistive output impedance,” IEEE Trans. Ind. Electron.,
vol. 54, no. 2, pp. 994–1004, Apr. 2007.
as corroborated by ELF and LSF solutions in terms of loss [16] J. M. Guerrero, J. Matas, L. G. de Vicuna, M. Castilla, and J. Miret,
reduction and computational time. LSF method may not lead “Wireless-control strategy for parallel operation of distributed-generation
to the best choice for DG placement. The number of DG units inverters,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1461–1470,
Oct. 2006.
with appropriate sizes and locations can reduce the losses to [17] J. M. Guerrero, L. Garcia de Vicuna, J. Matas, M. Castilla, and J. Miret,
a considerable amount. Given the choice, DG(s) should be “Output impedance design of parallel-connected ups inverters with wire-
allocated to enjoy other benefits as well such as loss reduction. less load-sharing control,” IEEE Trans. Ind. Electron., vol. 52, no. 4,
Among different DG types, the DG capable of delivering pp. 1126–1135, Aug. 2005.
[18] W. Freitas, J. C. M. Vieira, A. Morelato, L. C. P. da Silva, V. F. da Costa,
both real and reactive power reduces losses more than that of and F. A. B. Lemos, “Comparative analysis between synchronous and
DG capable of delivering real power only in one or two or three induction machines for distributed generation applications,” IEEE Trans.
DG cases. For DG capable of delivering real and reactive power, Ind. Electron., vol. 21, no. 1, pp. 301–311, Feb. 2006.
[19] D. Singh and K. S. Verma, “Multiobjective optimization for DG planning
their power factors too play a crucial role in loss reduction. with load models,” IEEE Trans. Power Syst., vol. 24, no. 1, pp. 427–436,
In all the test systems used in this paper, the operating power Feb. 2009.
factor of DG units for minimizing losses has been found to be [20] L. F. Ochoa, A. Padilha-Feltrin, and G. P. Harrison, “Evaluating dis-
tributed time-varying generation through a multiobjective index,” IEEE
closer to the power factor of combined load of the respective Trans. Power Del., vol. 23, no. 2, pp. 1132–1138, Apr. 2008.
system. This could be a good guidance for operating DG units [21] N. Acharya, P. Mahat, and N. Mithulananthan, “An analytical approach
that have the capability to deliver both real and reactive power for DG allocation in primary distribution network,” Int. J. Elect. Power
Energy Syst., vol. 28, no. 10, pp. 669–678, Dec. 2006.
for minimizing losses. [22] H. L. Willis, “Analytical methods and rules of thumb for modeling DG-
distribution interaction,” in Proc. IEEE Power Eng. Soc. Summer Meet.,
R EFERENCES 2000, vol. 3, pp. 1643–1644.
[23] Y. M. Atwa, E. F. El-Saadany, M. M. A. Salama, and R. Seethapathy,
[1] D. Singh and R. K. Misra, “Effect of load models in distributed genera- “Optimal renewable resources mix for distribution system energy loss
tion planning,” IEEE Trans. Power Syst., vol. 22, no. 4, pp. 2204–2212, minimization,” IEEE Trans. Power Syst., vol. 25, no. 1, pp. 360–370,
Nov. 2007. Feb. 2010.
[2] I. El-Samahy and E. El-Saadany, “The effect of DG on power quality in [24] C. Wang and M. H. Nehrir, “Analytical approaches for optimal placement
a deregulated environment,” in Proc. IEEE Power Eng. Soc. Gen. Meet., of distributed generation sources in power systems,” IEEE Trans. Power
2005, vol. 3, pp. 2969–2976. Syst., vol. 19, no. 4, pp. 2068–2076, Nov. 2004.
[3] T. Ackermann, G. Andersson, and L. Soder, “Distributed generation: A [25] K. H. Kim, Y. J. Lee, S. B. Rhee, S. K. Lee, and S. K. You, “Dispersed
definition,” Elect. Power Syst. Res., vol. 57, no. 3, pp. 195–204, Apr. 2001. generator placement using fuzzy-GA in distribution systems,” in Proc.
[4] M. N. Marwali, J. W. Jung, and A. Keyhani, “Stability analysis of load IEEE Power Eng. Soc. Summer Meet., 2002, vol. 3, pp. 1148–1153.
sharing control for distributed generation systems,” IEEE Trans. Energy [26] A. Silvestri, A. Berizzi, and S. Buonanno, “Distributed generation plan-
Convers., vol. 22, no. 3, pp. 737–745, Sep. 2007. ning using genetic algorithms,” in Proc. IEEE Int. Conf. Elect. Power
[5] W. Li, G. Joos, and J. Belanger, “Real-time simulation of a wind turbine Eng., PowerTech Budapest, 1999, p. 257.
generator coupled with a battery supercapacitor energy storage system,” [27] D. Q. Hung, N. Mithulananthan, and R. C. Bansal, “Analytical expressions
IEEE Trans. Ind. Electron., vol. 57, no. 4, pp. 1137–1145, Apr. 2010. for DG allocation in primary distribution networks,” IEEE Trans. Energy
[6] A. Pigazo, M. Liserre, R. A. Mastromauro, V. M. Moreno, and Convers., vol. 25, no. 3, pp. 814–820, Sep. 2010.
A. Dell’Aquila, “Wavelet-based islanding detection in grid-connected PV [28] D. P. Kothari and J. S. Dhillon, Power System Optimization. New Delhi:
systems,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4445–4455, Prentice-Hall, India, 2006.
Nov. 2009. [29] S. Civanlar, J. J. Grainger, H. Yin, and S. S. H. Lee, “Distribution feeder
[7] H. B. Puttgen, P. R. MacGregor, and F. C. Lambert, “Distributed genera- reconfiguration for loss reduction,” IEEE Trans. Power Del., vol. 3, no. 3,
tion: Semantic hype or the dawn of a new era?” IEEE Power Energy Mag., pp. 1217–1223, Jul. 1988.
vol. 1, no. 1, pp. 22–29, Jan./Feb. 2003. [30] M. A. Kashem, V. Ganapathy, G. B. Jasmon, and M. I. Buhari, “A novel
[8] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, “Overview method for loss minimization in distribution networks,” in Proc. IEEE
of control and grid synchronization for distributed power generation Int. Conf. Elect. Utility Deregulation Restruct. Power Technol., 2000,
systems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409, pp. 251–256.
Oct. 2006. [31] M. E. Baran and F. F. Wu, “Optimum sizing of capacitor placed on radial
[9] J. C. Vasquez, R. A. Mastromauro, J. M. Guerrero, and M. Liserre, “Volt- distribution systems,” IEEE Trans. Power Del., vol. 4, no. 1, pp. 735–743,
age support provided by a droop-controlled multifunctional inverter,” Jan. 1989.
IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4510–4519, Nov. 2009.
[10] W. Yao, M. Chen, J. Matas, J. M. Guerrero, and Z. Qian, “Design and
analysis of the droop control method for parallel inverters considering the
impact of the complex impedance on the power sharing,” IEEE Trans. Ind.
Electron., vol. 58, no. 2, pp. 576–588, Feb. 2011. Duong Quoc Hung (S’11) received the M.Eng. de-
[11] J. M. Guerrero, J. C. Vasquez, J. Matas, L. Garcia de Vicuna, and gree in electric power system management from the
M. Castilla, “Hierarchical control of droop-controlled AC and DC Asian Institute of Technology, Bangkok, Thailand,
microgrids—A general approach toward standardization,” IEEE Trans. in 2008. He is currently working toward the Ph.D.
Ind. Electron., vol. 58, no. 1, pp. 158–172, Jan. 2011. degree at the School of Information Technol-
[12] J. C. Vasquez, J. M. Guerrero, A. Luna, P. Rodriguez, and R. Teodorescu, ogy and Electrical Engineering, The University of
“Adaptive droop control applied to voltage-source inverters operating in Queensland, Brisbane, Australia.
grid-connected and islanded modes,” IEEE Trans. Ind. Electron., vol. 56, From 1999 to 2006 and from 2008 to 2010, he
no. 10, pp. 4088–4096, Oct. 2009. was with the Technical Department, Southern Power
[13] J. M. Guerrero, J. C. Vasquez, J. Matas, M. Castilla, and L. G. de Vicuna, Corporation, Electricity of Vietnam, Ho Chi Minh
“Control strategy for flexible microgrid based on parallel line-interactive City, Vietnam. His research interests are distribution
ups systems,” IEEE Trans. Ind. Electron., vol. 56, no. 3, pp. 726–736, system design and operations, distributed generation, and application of opti-
Mar. 2009. mization techniques in distribution systems.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1708 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 4, APRIL 2013

Nadarajah Mithulananthan (SM’10) received the


Ph.D. degree in electrical and computer engineer-
ing from the University of Waterloo, Waterloo, ON,
Canada, in 2002, the B.Sc. (Eng.) degree from the
University of Peradeniya, Peradeniya, Sri Lanka,
in May 1993, and the M.Eng. degree from the
Asian Institute of Technology, Bangkok, Thailand, in
August 1997.
He was an Electrical Engineer with the Generation
Planning Branch of the Ceylon Electricity Board and
as a Project Leader with Chulalongkorn University,
Bangkok, Thailand. He is currently a Senior Lecturer with the University of
Queensland (UQ), Brisbane, Australia. Prior to joining UQ, he was an Asso-
ciate Professor with the Asian Institute of Technology. His research interests
are the integration of renewable energy in power systems and power system
stability and dynamics.

You might also like