Professional Documents
Culture Documents
Within the context of Annex 24, a comparison is presented between two types of cooling systems: one
using an electrical compression chiller and the other using an absorption chiller. The absorption chillers
considered are all driven by heat from CHP (Combined Heat and Power) units. The comparison focuses on
the relative levels of primary energy consumption and CO2 emission. A spreadsheet program is used to
calculate these relative levels.
elimination of an equivalent amount equivalent amount of electricity The efficiency of most power plants in
of public grid electricity production production elsewhere in the grid. the Netherlands is 42% or more.
capacity. The electrical efficiency of The amount of extra fossil fuel Modern gas-fired power plants can
the CHP (36%) is lower than that of needed to compensate for this achieve an efficiency of 54%. In future,
the public power plants in the lowering of the electrical output by the average efficiency of power plants
various reference scenarios. An extra generating the electricity by another is expected to increase further. At
amount of fossil fuel is needed to plant in the grid is the energy cost of present, the useful life span of an
compensate for the lower electrical generating the useful heat supplied absorption cooling plant is almost
efficiency of the CHP unit in by the CHP unit, and is used as such 15 years. Decisions on whether or not to
comparison to the public grid. This in the calculations. For CO2 install absorption chillers for cooling
extra amount of fossil fuel is the emissions, a similar procedure is should be based on energy efficiencies
energy cost of generating the useful applied. at present as well as in the future.
heat supplied by the CHP unit, and is
used as such in the calculations. For The remaining data in Table 2 are Figure 3 presents the results of the
CO2 emissions, the same procedure needed to calculate the conversion calculated relative CO2 emissions for
is applied. However, the power efficiencies of the two cooling systems the two cooling systems.
plants in two reference scenarios in Figure 1 and the energy distribution
emit more CO2 than the CHP unit. losses in the system. The amount of CO2 emissions depends
Therefore, a reduction of CO2 not only on the energy efficiency of the
emissions is the cost of the generated power plant but also on the type of fuel
heat in these cases; Results and discussion used (see Table 1). As different types of
• when using an electricity-focused Heat-focused CHPs fuel are used in the reference scenarios,
CHP to produce heat for an The results calculated for the energy the results are given separately for each
absorption chiller: Heat is the by- comparison of compression cooling and scenario. As expected, the CO2
product. Eliminating some potential absorption cooling driven by a heat- emissions per unit of cooling capacity
production capacity at the focused CHP are presented in Figure 2. for electrical compression cooling
“electricity-focused” CHP plant in decrease as the COP of the cooling
order to produce heat necessitates an The solid curve passes through those system increases. For absorption
points at which the energy efficiency of cooling, two scenarios (POP, ANG)
both cooling systems is equal. At these result in negative CO2 emissions. The
24 points, the values for the efficiency of reason is that the gas-fired CHP unit
▼ Table 1: Efficiency of electricity the power plant used as a reference and produces less CO2 than the coal- or oil-
generation in three “standardised” types of for the COP (Coefficient Of fired reference power plants in these
public power plants in the Netherlands Performance = cooling capacity/ cases. This causes negative “CO2
electrical input) of the compression emission cost” for the heat to drive the
code fuel efficiency CO2 chiller are such that both cooling absorption chiller, and therefore
emission
% kg/GJ
systems are equally efficient. The red negative CO2 emissions for absorption
Best available area above and to the right of the solid cooling. Figure 3 shows that in the POP
technology BAT gas 55.0 56 line represents those combinations of reference scenario this reduction would
Average
national grid ANG mix 42.0 73
values in which compression cooling is be considerable. In the BAT scenario all
Phase-out more efficient. The blue area below and power plants are gas-fired. As a matter
power plant POP coal 37.0 98 to the left of the solid line defines the of fact, if the COP of the electrical
range of values in which absorption chiller is greater than 1.6, compression
▼ Table 2: Energy conversion efficiencies cooling is more efficient. cooling produces less CO2 emissions
and energy losses for the various steps in than absorption cooling in this scenario.
Figure 1 Modern technologies make it possible
to achieve a COP of 5 for electrical Electricity-focused CHPs
Heat-focused CHP: compression cooling. Modern cooling Figure 4 summarises the spreadsheet
CHP elect. eff. 36 %
CHP overall eff. 85 %
plants used in the food industry and for calculations for the energy comparison
Electricity-focused CHP with heat drawn off: cooling buildings can even achieve a when the absorption chiller is driven by
CHP elec. eff. 52 % COP higher than 5. Assuming a COP of heat from an electricity-focused CHP.
CHP overall eff. 85 %
Absorption cooling COPth* 0.70 -
5 or higher, Figure 2 shows that if the
Absorption cooling Rel ** 40 - efficiency of the reference power plant The PER (Primary Energy Ratio) on the
Distribution loss electricity grid 5 % exceeds 42%, then the energy efficiency Y-axis is equal to the cooling capacity
Distribution loss heat distribution 10 %
* COPth = cooling capacity/thermal energy input
of electrical compression cooling is delivered by the system per unit of
** Rel = cooling capacity/auxiliary electrical input higher than that of absorption cooling. primary energy input to the system.
18
16
Again, results are presented for each same as in the energy comparison
COP electric cooling
50 the power delivered by the CHP to the 42% or greater. From the perspective of
CO2 emission
2
Therefore, there is only one COP perspective of energy efficiency as well
of the compression cooler where the as CO2 emissions and regardless of
1 efficiencies of both cooling systems are which reference scenario is chosen for
0
equal, regardless of the efficiency of the the electricity grid.
0 1 2 3 4 5 6 7 8 reference power plant.
COP electric cooling
40
break-even point is a COP of 6.1.
CO2 emission
30
The results calculated for CO2
20 emissions are summarised in Figure 5. Harry Hondeman
10 Gastec N.V.
0 Figure 5 shows a comparable result for PO Box 137
0 1 2 3 4 5 6 7 8 CO2 emissions as for energy efficiency. 7300 AC Apeldoorn
COP electric cooling
The break-even point, regardless of the The Netherlands
▲ Figure 5: Comparison of CO 2 emissions scenario chosen, is a COP of 6.1. At Tel: +31-55 5 393 299
for electrical compression cooling and COP values higher than 6.1, Fax: +31-55 5 393 223
absorption cooling driven by electricity- compression cooling becomes more E-mail: HMN@gastec.nl
focused CHP. favourable. The reasoning here is the Internet: http://www.gastec.nl