You are on page 1of 6

EQUIPMENT

Computech
CLOSE CONTROL A/C UNITS (MAIN DATA CENTRE)

UNIFLAIR
SDA0601

UNIFLAIR
CAL0801

Uniflair

FOURIER - DATANET SYSTEM

SEVEN SEAS DESIGN


SECTION NO. 1
JUBILEE DATA CENTRE
ELEMENT NO. 1
AIR CONDITIONING SYSTEMS
1 (CONVERTABLE A/C UNITS )
(Supply and install Convertible AC units Model:
CARRIER /TOSHIBA or equivalent and approved
48,000 BTU )
(Supply and install matching condensing unit for
(a ) the
(20above units.
mm dia. )
copper refrigerant pipes for liquid
(b ) line. )
c 25 mm dia.copper refrigerant pipes for suction line
d 20 mm dia. Armflex insulation 10 mm thick.
e 25 mm dia. Armflex insulation 12.5 mm thick.
f Pressure test pipework at 250 PSI for 24 Hrs.using
(Dry Nitrogen) to hold for 24 Hrs.
g Allow for vacuuming and dehydration of the whole
system.
h Refrigerant change as recommended by the
Manufacturer.
i Testing and Commissioning.
HIGH TEMPERATURE SENSOR SYSTEM
1.2 Supply and install High Temperature sensor Panel
with Visual and audial alarms to be installed near
the Data Centre Entry Door
DEHUMIDIFIER SYSTEM
1.3 Supply and install Dehumidifier Unity at the
Data Centre
Carried to Collection
GAS EXTRACT SYSTEM
1.4 Supply and install gas extract system complete
with the following:
a.) Woods fan 800 m3/hr at 200pa3phase 415v
b.)Flexible Ducting with 300mm diameter 15
meters
c.)Motorized damper 1no.
d)External alluminium grill 1no.
e)Internal alluminium grill 2no.
HVAC PANEL
1.5 supply and install Hvac panel for the control of the
gas extract system and interfacing of the Air
Conditoning systems with fire system.
1.6 Fresh air alluminium transfer pair 400mm x
400mm with insect screed
Carried to Collection

COLLECTION
From Page No. 1
From Page No. 2
SECTION NO. 1 TO MAIN SUMMARY
AIR CONDITIONING
MAIN SUMMARY
SECTION

1 PRELIMINARIES
2 JUBILEE DATA CENTRE
3 TESTING AND COMMISSIONING
4 TRAINING & MAINTENANCE MANUALS
TENDER CORRECTED SUM

TENDER SUM
DESCRIPTION QUANTITY
UNIT PRICE

MAIN DATA CENTRE)

Supply ofl Close Control down flow A/C unit 3 15,630.00


each having a cooling capacity of
17 KW at 35Deg.C complete with Electric Heating.
Units to be EPOXY baked powder coated.
Condensate tray to be stainless steel. System
to have micro-processor control compatible to BMS with
digital display/touch pad and alert for alarms. Provision
for fire alarm interface, water detection alarm. System
to have floor and stand adjustable +/- 25mm

Supply of matching condensing units for the 3 4200


above indoor units Model CUS 6 including main isolators.
Units to have EPOXY baked powder coated
weather proof finish, and micro-processor controls

Floor stands 3 250

Water detection with sensor 2

Water detection with sensor 2 600

Floor and griils 40 290

EMU INC. 2 LOGGERS, 1 RECIVER, GSM MODEM 1 5265.75


AND INSTALLATION

Allow for preparation of shop drawings, & As Built Drawings" 1 601.80


Relocating the old units not included at this stage

SUB-TOTAL

Unit Qty (Rate )


(Dimensions )

NO 2 2,101,954.80

LM 2 696,000.00
LM 30 -
LM 30 11,600.00
LM 30 23,200.00
LM 30 23,200.00

ITEM 1 0.00

ITEM 1 0.00

ITEM 1 0.00
ITEM 1 255,200.00
-

ITEM 1 53,592.00
-

NO 1 88,160.00
-
-
-

-
-

-
-
ITEM 1 214,368.00
-

ITEM 1 23,200.00

18,560.00
NO 1

Kshs.

PAGE
NO

2
ITEM
ITEM
Ksh
TOTAL

46,890.00

12,600.00

750.00

1,200.00

11,600.00

5,265.75

601.80

###

(Rate ) (Amount )
(Air Tech ) (Air Tech )

180,786.00 361,572.00
406,000.00
203,000.00
1,682.00 50,460.00
2,088.00 62,640.00
406.00 12,180.00
638.00 19,140.00

25,000.00 25,000.00
7,500.00
7,500.00
24,000.00
24,000.00
20,000.00 20,000.00
-
-

-
- -
-
-
- 988,492.00
-
-

-
-

-
-
322,248.00 322,248.00
- -
139,200.00

139,200.00
17,400.00 17,400.00

478,848.00

988,492.00
478,848.00

###

AMOUNT
KSHS
150,000.00
###
25,000.00

###

###