Column Design Check Summary G/F Column/ B-5

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 22.12 2.08 1.55 D Dead Load Self weight
Live Load, L 0.9 0.13 0.003 L Live load Imposed load
Plant Load, P -1.14 0.002 0.001 P Plant load Roof load due to a/c unit
Wind Load, W 4.5 2.99 0.06 W Wind load Wind Pressure
Seismic Load, S 47 33.58 0.47 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 640 Plan of
Or 1.2D+1.2L+1.2W 640 Column C5
Or 1.1(1.2D+0.5L±1.0S) 3731
With Plant Load
Either 1.4D+1.6L 640
Or 1.2D+1.2L+1.2W 640
Or 1.1(1.2D+0.5L±1.0S) 3761

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ B-6

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 90.3 1.8 4.72 D Dead Load Self weight
Live Load, L 11.97 0.23 0.59 L Live load Imposed load
Plant Load, P -0.69 0.0139 0.00053 P Plant load Roof load due to a/c unit
Wind Load, W 3.9 0.09 0.79 W Wind load Wind Pressure
Seismic Load, S 47.94 1.29 10.86 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 928 Plan of
Or 1.2D+1.2L+1.2W 640 Column C5
Or 1.1(1.2D+0.5L±1.0S) 10339
With Plant Load
Either 1.4D+1.6L 894
Or 1.2D+1.2L+1.2W 640
Or 1.1(1.2D+0.5L±1.0S) 10294

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ C-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 62.43 1.25 7.37 D Dead Load Self weight
Live Load, L 14.2 0.4 2 L Live load Imposed load
Plant Load, P 0.55 0.01 0.04 P Plant load Roof load due to a/c unit
Wind Load, W 3.2 2.9 0.37 W Wind load Wind Pressure
Seismic Load, S 47.5 40.3 5.5 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 110.1 2.2 13.4
1.2D+1.2L+1.2W 95.8 3.06 11.6
1.1(1.2D+0.5L±1.0S) 142.46 44.27 16.77
With Plant Load
1.4D+1.6L 110.9 2.2 13.5
1.2D+1.2L+1.2W 96.46 3.06 11.65
1.1(1.2D+0.5L±1.0S) 143.19 44.27 16.85

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 5205 Plan of
Or 1.2D+1.2L+1.2W 4089 Column C5
Or 1.1(1.2D+0.5L±1.0S) 12423
With Plant Load
Either 1.4D+1.6L 5280
Or 1.2D+1.2L+1.2W 4125
Or 1.1(1.2D+0.5L±1.0S) 12480

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ C-3

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 81.3 1.63 10.3 D Dead Load Self weight
Live Load, L 20.4 0.41 2.9 L Live load Imposed load
Plant Load, P -0.03 0.015 0.001 P Plant load Roof load due to a/c unit
Wind Load, W 0.2 0.67 0.05 W Wind load Wind Pressure
Seismic Load, S 7.2 40.45 0.47 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 146.55 2.93 19.15
1.2D+1.2L+1.2W 122.71 5.27 16.03
1.1(1.2D+0.5L±1.0S) 126.51 44.85 16.76
With Plant Load
1.4D+1.6L 146.52 2.93 19.15
1.2D+1.2L+1.2W 122.68 5.28 16.03
1.1(1.2D+0.5L±1.0S) 126.48 44.87 16.76

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 10357 Plan of
Or 1.2D+1.2L+1.2W 7799 Column C5
Or 1.1(1.2D+0.5L±1.0S) 12287
With Plant Load
Either 1.4D+1.6L 10355
Or 1.2D+1.2L+1.2W 7799
Or 1.1(1.2D+0.5L±1.0S) 12287

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ C-4

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 90.91 1.82 10.96 D Dead Load Self weight
Live Load, L 19.68 0.39 2.66 L Live load Imposed load
Plant Load, P 1.96 0.045 0.19 P Plant load Roof load due to a/c unit
Wind Load, W 1.29 2.66 0.16 W Wind load Wind Pressure
Seismic Load, S 19.55 3.67 2.45 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 158.76 3.18 19.58
1.2D+1.2L+1.2W 134.25 4.64 16.52
1.1(1.2D+0.5L±1.0S) 152.33 41.66 18.56
With Plant Load
1.4D+1.6L 161.51 3.23 19.86
1.2D+1.2L+1.2W 136.61 4.62 16.76
1.1(1.2D+0.5L±1.0S) 154.93 41.64 18.82

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 10914 Plan of
Or 1.2D+1.2L+1.2W 8286 Column C5
Or 1.1(1.2D+0.5L±1.0S) 13833
With Plant Load
Either 1.4D+1.6L 11182
Or 1.2D+1.2L+1.2W 8504
Or 1.1(1.2D+0.5L±1.0S) 14090

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ D-5

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 141 6.18 5.11 D Dead Load Self weight
Live Load, L 27.97 1.89 1.04 L Live load Imposed load
Plant Load, P 8.63 0.22 0.06 P Plant load Roof load due to a/c unit
Wind Load, W 1 0.47 0.05 W Wind load Wind Pressure
Seismic Load, S 12.14 1.96 7.49 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 240 11.63 8.82
1.2D+1.2L+1.2W 206.17 7.52 11.09
1.1(1.2D+0.5L±1.0S) 216.05 10.39 18.57
With Plant Load
1.4D+1.6L 252.15 11.95 9.19
1.2D+1.2L+1.2W 216.52 7.56 1.16
1.1(1.2D+0.5L±1.0S) 227.43 10.46 19.13

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 4185 Plan of
Or 1.2D+1.2L+1.2W 4829 Column C5
Or 1.1(1.2D+0.5L±1.0S) 11554
With Plant Load
Either 1.4D+1.6L 4715
Or 1.2D+1.2L+1.2W 5477
Or 1.1(1.2D+0.5L±1.0S) 12131

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ D-6

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 96.5 1.93 7.22 D Dead Load Self weight
Live Load, L 22.71 2.49 0.12 L Live load Imposed load
Plant Load, P 4.49 0.17 0.23 P Plant load Roof load due to a/c unit
Wind Load, W 0.76 0.17 0.39 W Wind load Wind Pressure
Seismic Load, S -7.44 1.34 6.41 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
1.4D+1.6L 171.45 3.43 12.78
1.2D+1.2L+1.2W 142.32 2.85 11.17
1.1(1.2D+0.5L±1.0S) 133.6 3.06 16.81
With Plant Load
1.4D+1.6L 177.73 3.55 13.23
1.2D+1.2L+1.2W 147.7 2.95 11.56
1.1(1.2D+0.5L±1.0S) 137.62 2.75 17.35

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm
For Axial load column
area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Either 1.4D+1.6L 5493 Plan of
Or 1.2D+1.2L+1.2W 3834 Column C5
Or 1.1(1.2D+0.5L±1.0S) 8399
With Plant Load
Either 1.4D+1.6L 5965
Or 1.2D+1.2L+1.2W 4201
Or 1.1(1.2D+0.5L±1.0S) 8799

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ E-7

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 66.49 1.39 4.91 D Dead Load Self weight
Live Load, L 13.2 1.21 0.88 L Live load Imposed load
Plant Load, P 2.99 0.26 0.2 P Plant load Roof load due to a/c unit
Wind Load, W 1.2 1.36 0.11 W Wind load Wind Pressure
Seismic Load, S 14.79 18.24 1.47 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 114.22 2.65 8.41
1.2D+1.2L+1.2W 93.53 6.37 6.75
1.1(1.2D+0.5L±1.0S) 108.96 26.66 7.82
With Plant Load
1.4D+1.6L 118.42 2.76 8.74
1.2D+1.2L+1.2W 99.22 2.41 7.43
1.1(1.2D+0.5L±1.0S) 112.92 27.06 8.05

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 1395 Plan of
Or 1.2D+1.2L+1.2W 1043 Column C2
Or 1.1(1.2D+0.5L±1.0S) 3585
With Plant Load
Either 1.4D+1.6L 1646
Or 1.2D+1.2L+1.2W 1033
Or 1.1(1.2D+0.5L±1.0S) 3780

Column Rebar
provided in the 2060 mm2
SAPL design
Column Design Check Summary G/F Column/ H-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 218.24 4.36 8.74 D Dead Load Self weight
Live Load, L 56.95 2.81 2 L Live load Imposed load
Plant Load, P -2.2 0.044 0.0167 P Plant load Roof load due to a/c unit
Wind Load, W 3.18 1.18 0.59 W Wind load Wind Pressure
Seismic Load, S 46.39 5.41 17.36 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 396.65 7.93 15.61
1.2D+1.2L+1.2W 325.57 6.51 15.76
1.1(1.2D+0.5L±1.0S) 370.43 7.41 26.35
With Plant Load
1.4D+1.6L 393.55 7.87 15.45
1.2D+1.2L+1.2W 322.91 6.46 15.65
1.1(1.2D+0.5L±1.0S) 367.5 7.35 26.29

Rebar Requirements for the necessary load combination


300mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 3533 Plan of
Or 1.2D+1.2L+1.2W 1813 Column C4
Or 1.1(1.2D+0.5L±1.0S) 6613
With Plant Load
Either 1.4D+1.6L 3402
Or 1.2D+1.2L+1.2W 1722
Or 1.1(1.2D+0.5L±1.0S) 6534

Column Rebar
provided in the 2864 mm2
SAPL design
Column Design Check Summary G/F Column/ H-4

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 356.49 7.13 3.07 D Dead Load Self weight
Live Load, L 96 3.27 4.27 L Live load Imposed load
Plant Load, P 32.05 1.14 0.34 P Plant load Roof load due to a/c unit
Wind Load, W 0.31 0.22 0.36 W Wind load Wind Pressure
Seismic Load, S 2.45 31.14 7.77 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L 647.32 21.69 25.86
1.2D+1.2L+1.2W 538.75 17.35 20.63
1.1(1.2D+0.5L±1.0S) 515.58 51.42 28.69
With Plant Load
1.4D+1.6L 692.18 23.28 26.75
1.2D+1.2L+1.2W 576.6 22.72 22.99
1.1(1.2D+0.5L±1.0S) 557.88 52.92 29.53

Rebar Requirements for the necessary load combination


600mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 3806 Plan of
Or 1.2D+1.2L+1.2W 1440 Column C1
Or 1.1(1.2D+0.5L±1.0S) 4990
With Plant Load
Either 1.4D+1.6L 5273
Or 1.2D+1.2L+1.2W 1778
Or 1.1(1.2D+0.5L±1.0S) 6107

Column Rebar
provided in the 4472 mm2
SAPL design
Column Design Check Summary G/F Column/ H-7

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 125.74 2.52 9.07 D Dead Load Self weight
Live Load, L 31.74 0.8 3.72 L Live load Imposed load
Plant Load, P 23.2 0.51 0.96 P Plant load Roof load due to a/c unit
Wind Load, W 0.37 0.19 0.47 W Wind load Wind Pressure
Seismic Load, S 5.48 2.66 6.59 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


290mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 6122 Plan of
Or 1.2D+1.2L+1.2W 4147 Column C1A
Or 1.1(1.2D+0.5L±1.0S) 6175
With Plant Load
Either 1.4D+1.6L 7234
Or 1.2D+1.2L+1.2W 5005
Or 1.1(1.2D+0.5L±1.0S) 7157

Column Rebar
provided in the 3216 mm2
SAPL design
Column Design Check Summary G/F Column/ J-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 121.81 2.44 7.06 D Dead Load Self weight
Live Load, L 27 0.54 3.02 L Live load Imposed load
Plant Load, P -1.35 0.04 0.03 P Plant load Roof load due to a/c unit
Wind Load, W 0.56 0.9 0.55 W Wind load Wind Pressure
Seismic Load, S -6.55 21.21 6.8 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


300mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 1750 Plan of
Or 1.2D+1.2L+1.2W 960 Column C4
Or 1.1(1.2D+0.5L±1.0S) 4351
With Plant Load
Either 1.4D+1.6L 1713
Or 1.2D+1.2L+1.2W 960
Or 1.1(1.2D+0.5L±1.0S) 4323

Column Rebar
provided in the 2864 mm2
SAPL design
Column Design Check Summary G/F Column/ J-4

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 314.29 6.29 7.82 D Dead Load Self weight
Live Load, L 82.74 3.47 0.99 L Live load Imposed load
Plant Load, P 22.72 0.87 0.52 P Plant load Roof load due to a/c unit
Wind Load, W 0.14 0.8 0.33 W Wind load Wind Pressure
Seismic Load, S 1.99 22.51 8.39 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


600mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 1440 Plan of
Or 1.2D+1.2L+1.2W 1440 Column C1
Or 1.1(1.2D+0.5L±1.0S) 1440
With Plant Load
Either 1.4D+1.6L 1641
Or 1.2D+1.2L+1.2W 1440
Or 1.1(1.2D+0.5L±1.0S) 2081

Column Rebar
provided in the 4472 mm2
SAPL design
Column Design Check Summary G/F Column/ J-7

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 129.64 2.98 9.47 D Dead Load Self weight
Live Load, L 32.55 0.65 3.86 L Live load Imposed load
Plant Load, P 15.33 0.44 0.65 P Plant load Roof load due to a/c unit
Wind Load, W 0.39 0.23 0.35 W Wind load Wind Pressure
Seismic Load, S 5.58 3.01 5.15 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


290mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 6452 Plan of
Or 1.2D+1.2L+1.2W 4364 Column C1A
Or 1.1(1.2D+0.5L±1.0S) 6127
With Plant Load
Either 1.4D+1.6L 7181
Or 1.2D+1.2L+1.2W 4943
Or 1.1(1.2D+0.5L±1.0S) 6844

Column Rebar
provided in the 3216 mm2
SAPL design
Column Design Check Summary G/F Column/ K-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 216.51 4.33 9.39 D Dead Load Self weight
Live Load, L 56.85 2.9 2.02 L Live load Imposed load
Plant Load, P -0.61 0.03 0.006 P Plant load Roof load due to a/c unit
Wind Load, W 1.87 1.19 0.31 W Wind load Wind Pressure
Seismic Load, S -4.59 15.54 0.56 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


300mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 3796 Plan of
Or 1.2D+1.2L+1.2W 1670 Column C4
Or 1.1(1.2D+0.5L±1.0S) 3391
With Plant Load
Either 1.4D+1.6L 3759
Or 1.2D+1.2L+1.2W 1643
Or 1.1(1.2D+0.5L±1.0S) 3363

Column Rebar
provided in the 2864 mm2
SAPL design
Column Design Check Summary G/F Column/ K-4

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 341.88 8.37 5.57 D Dead Load Self weight
Live Load, L 93.02 4.01 2.68 L Live load Imposed load
Plant Load, P 6.99 0.22 0.27 P Plant load Roof load due to a/c unit
Wind Load, W 0.34 0.72 0.14 W Wind load Wind Pressure
Seismic Load, S -6.78 7.68 14.29 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


600mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 2588 Plan of
Or 1.2D+1.2L+1.2W 1440 Column C1
Or 1.1(1.2D+0.5L±1.0S) 1440
With Plant Load
Either 1.4D+1.6L 2865
Or 1.2D+1.2L+1.2W 1440
Or 1.1(1.2D+0.5L±1.0S) 1440

Column Rebar
provided in the 4472 mm2
SAPL design
Column Design Check Summary G/F Column/ K-7

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 119.69 2.53 8.44 D Dead Load Self weight
Live Load, L 30 1.01 3.43 L Live load Imposed load
Plant Load, P 1.49 0.09 0.08 P Plant load Roof load due to a/c unit
Wind Load, W 0.29 0.24 0.24 W Wind load Wind Pressure
Seismic Load, S 0.58 9.72 0.27 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


290mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 5255 Plan of
Or 1.2D+1.2L+1.2W 3402 Column C1A
Or 1.1(1.2D+0.5L±1.0S) 4657
With Plant Load
Either 1.4D+1.6L 5361
Or 1.2D+1.2L+1.2W 3486
Or 1.1(1.2D+0.5L±1.0S) 4729

Column Rebar
provided in the 3216 mm2
SAPL design
Column Design Check Summary G/F Column/ L-5

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 153.02 3.06 9.94 D Dead Load Self weight
Live Load, L 27.12 0.71 1.07 L Live load Imposed load
Plant Load, P -0.07 0.007 0.0015 P Plant load Roof load due to a/c unit
Wind Load, W 1.1 0.35 0.02 W Wind load Wind Pressure
Seismic Load, S -11.32 6.9 0.43 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 9290 Plan of
Or 1.2D+1.2L+1.2W 6698 Column C5
Or 1.1(1.2D+0.5L±1.0S) 9492
With Plant Load
Either 1.4D+1.6L 9283
Or 1.2D+1.2L+1.2W 6692
Or 1.1(1.2D+0.5L±1.0S) 9485

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ L-6

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 86.43 2.38 13.39 D Dead Load Self weight
Live Load, L 14.69 0.29 2.55 L Live load Imposed load
Plant Load, P -0.045 0.011 0.0024 P Plant load Roof load due to a/c unit
Wind Load, W 0.12 0.059 0.027 W Wind load Wind Pressure
Seismic Load, S 1.25 9.94 0.023 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 13311 Plan of
Or 1.2D+1.2L+1.2W 10062 Column C5
Or 1.1(1.2D+0.5L±1.0S) 11411
With Plant Load
Either 1.4D+1.6L 13307
Or 1.2D+1.2L+1.2W 10059
Or 1.1(1.2D+0.5L±1.0S) 11402

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ L-7

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 43.55 2.38 2.58 D Dead Load Self weight
Live Load, L 7.28 0.6 0.53 L Live load Imposed load
Plant Load, P -0.27 0.06 0.03 P Plant load Roof load due to a/c unit
Wind Load, W 0.54 0.21 0.16 W Wind load Wind Pressure
Seismic Load, S 6.24 2.39 3.05 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


290mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 696 Plan of
Or 1.2D+1.2L+1.2W 696 Column C1A
Or 1.1(1.2D+0.5L±1.0S) 855
With Plant Load
Either 1.4D+1.6L 696
Or 1.2D+1.2L+1.2W 696
Or 1.1(1.2D+0.5L±1.0S) 696

Column Rebar
provided in the 3216 mm2
SAPL design
Column Design Check Summary G/F Column/ M-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 59.15 1.88 0.25 D Dead Load Self weight
Live Load, L 13.55 0.49 1.84 L Live load Imposed load
Plant Load, P 0.13 0.0026 0.009 P Plant load Roof load due to a/c unit
Wind Load, W 0.35 0.12 0.009 W Wind load Wind Pressure
Seismic Load, S 10.34 4.93 1.93 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 4651 Plan of
Or 1.2D+1.2L+1.2W 3390 Column C5
Or 1.1(1.2D+0.5L±1.0S) 4427
With Plant Load
Either 1.4D+1.6L 4659
Or 1.2D+1.2L+1.2W 3400
Or 1.1(1.2D+0.5L±1.0S) 4435

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ M-3

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 81.75 1.64 0.19 D Dead Load Self weight
Live Load, L 20.59 0.41 2.87 L Live load Imposed load
Plant Load, P -0.026 0.0084 0.00042 P Plant load Roof load due to a/c unit
Wind Load, W 0.13 0.11 0.009 W Wind load Wind Pressure
Seismic Load, S -3.33 2.26 1.22 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 9749 Plan of
Or 1.2D+1.2L+1.2W 6954 Column C5
Or 1.1(1.2D+0.5L±1.0S) 7792
With Plant Load
Either 1.4D+1.6L 9745
Or 1.2D+1.2L+1.2W 6951
Or 1.1(1.2D+0.5L±1.0S) 7789

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ M-4

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 87.92 4.49 6.09 D Dead Load Self weight
Live Load, L 18.41 0.38 1.48 L Live load Imposed load
Plant Load, P -0.056 0.0057 0.0002 P Plant load Roof load due to a/c unit
Wind Load, W 0.15 0.006 0.033 W Wind load Wind Pressure
Seismic Load, S 3.74 1.91 2.77 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 3655 Plan of
Or 1.2D+1.2L+1.2W 2204 Column C5
Or 1.1(1.2D+0.5L±1.0S) 4883
With Plant Load
Either 1.4D+1.6L 3654
Or 1.2D+1.2L+1.2W 2202
Or 1.1(1.2D+0.5L±1.0S) 4879

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary G/F Column/ N-5

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 77.82 5.45 6.44 D Dead Load Self weight
Live Load, L 7.45 0.226 0.079 L Live load Imposed load
Plant Load, P -0.227 0.005 0.001 P Plant load Roof load due to a/c unit
Wind Load, W 2.1 0.3 0.12 W Wind load Wind Pressure
Seismic Load, S 25.7 0.56 2.73 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


200mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 4274 Plan of
Or 1.2D+1.2L+1.2W 2734 Column C5
Or 1.1(1.2D+0.5L±1.0S) 6248
With Plant Load
Either 1.4D+1.6L 4261
Or 1.2D+1.2L+1.2W 2727
Or 1.1(1.2D+0.5L±1.0S) 6235

Column Rebar
provided in the 4372 mm2
SAPL design
Column Design Check Summary F/F Column/ H-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 142.92 18.09 10.45 D Dead Load Self weight
Live Load, L 32.57 1.77 0.89 L Live load Imposed load
Plant Load, P -2.4 0.055 0.027 P Plant load Roof load due to a/c unit
Wind Load, W 1.13 0.32 0.24 W Wind load Wind Pressure
Seismic Load, S 16.99 2.63 11.67 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


300mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 4159 Plan of
Or 1.2D+1.2L+1.2W 2522 Column C4
Or 1.1(1.2D+0.5L±1.0S) 5837
With Plant Load
Either 1.4D+1.6L 4122
Or 1.2D+1.2L+1.2W 2511
Or 1.1(1.2D+0.5L±1.0S) 5827

Column Rebar
provided in the 2864 mm2
SAPL design
Column Design Check Summary F/F Column/ J-4

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 209.5 16.06 4.93 D Dead Load Self weight
Live Load, L 49.7 2.73 0.29 L Live load Imposed load
Plant Load, P 22.72 2.93 0.45 P Plant load Roof load due to a/c unit
Wind Load, W 0.075 0.88 0.065 W Wind load Wind Pressure
Seismic Load, S 0.033 3.78 30.44 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


600mm
Column steel are needed Y
Extra to resist
Total Steel
600 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 1440 Plan of
Or 1.2D+1.2L+1.2W 1440 Column C1
Or 1.1(1.2D+0.5L±1.0S) 1440
With Plant Load
Either 1.4D+1.6L 1440
Or 1.2D+1.2L+1.2W 1440
Or 1.1(1.2D+0.5L±1.0S) 1440

Column Rebar
provided in the 4472 mm2
SAPL design
Column Design Check Summary F/F Column/ K-2

Action on Column (Characteristic Loads)

Vertical Load
(Axial load) Sway Moment
Primary Load Case
X-X Y-Y
Ton Ton-M Ton-M Legend
Dead Load, D 141.49 16.39 11.07 D Dead Load Self weight
Live Load, L 32.43 1.72 0.93 L Live load Imposed load
Plant Load, P -0.66 0.12 0.006 P Plant load Roof load due to a/c unit
Wind Load, W 0.9 0.2 0.52 W Wind load Wind Pressure
Seismic Load, S -1.98 22.05 0.1 S Seismic load Earthquake load

Vertical Load Sway Moment


ULS load combination (Axial load) X-X Y-Y
Ton Ton-M Ton-M
Without Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)
With Plant Load
1.4D+1.6L
1.2D+1.2L+1.2W
1.1(1.2D+0.5L±1.0S)

Rebar Requirements for the necessary load combination


300mm
Column steel are needed Y
Extra to resist
Total Steel
800 mm

For Axial load column


area
ULS load combination only (Vertical bending due to x x
actually
load) horizontal
needed
sway
steel, mm2 steel, mm2 steel, mm2 Y
Without Plant Load
Either 1.4D+1.6L 4263 Plan of
Or 1.2D+1.2L+1.2W 2613 Column C4
Or 1.1(1.2D+0.5L±1.0S) 4714
With Plant Load
Either 1.4D+1.6L 4232
Or 1.2D+1.2L+1.2W 2581
Or 1.1(1.2D+0.5L±1.0S) 4680

Column Rebar
provided in the 2864 mm2
SAPL design