DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES

TPG CVT150 - RFQ 001 : 150 KV OUTDOOR CAPACITOR VOLTAGE TRANSFORMER

PROPOSED AND GUARANTEED (FINAL /


NO. DESCRIPTION UNIT REQUIRED
CLARIFIED)

Manufacturer to be mentioned CG Power and Industrial Solutions Limited


Type of Designation to be mentioned CVE 170/750/50
1 Standard IEC 61869-1; IEC 61869-5 IEC 61869-1; IEC 61869-5
2 Service Condition Outdoor, Tropical Area Outdoor, Tropical Area
3 Nominal voltage kV 150 150
4 Highest Voltage for equipment (Um) kV 170 170
5 Rated frequency (Fr) Hz 50 50
6 Rated primary voltage (Upr) kV 150/√3 150/√3
7 Rated secondary voltage (Usr) V 100/√3 100/√3
(110/√3 V especially for East Java and Sulawesi)

RATED INSULATION LEVEL


8 Insulation Class :
- Power frequency withstand voltage kVrms 325 325
- Lightning impulse withstand voltage kVp 750 750
- Switching impulse withstand voltage kVp N.A. N.A.
9 Creepage distance phase to earth (according to degree of
pollution)
Up to Heavy Pollution mm/kV 25 25

GENERAL
10 Rated voltage factor and corresponding rated time, continuous 1.2 1.2
11 Rated voltage factor and corresponding rated time, 30 sec. 1.5 1.5
12 Dissipation factor of capacitor (tan δ) % ≤0.5 ≤0.5
13 Accuracy class :
- for protection 3P 3P
- for instrument and metering (for tariff metering choose 0.2) 0.2 0.2
14 Rated burden :
- for protection VA 15 15
- for instrument and metering VA 15 15
- total simultaneous burden VA 30 30
15 Rated capacitance pF 4000 up to 10000 4400
16 Capacitance tolerance - 5 % to + 10 % - 5 % to + 10 %
17 Ferro resonance :
- Duration of ferro resonance oscillation s ≤0.5 ≤0.5
- Maximum instantaneous error after ferro resonance % ≤10 ≤10
18 oscillation
Suitable for use as coupling capacitor Yes Yes

OTHERS :
19 Insulator material silicon rubber or pocelain Porcelain
Oil compensation corrosion-proof metallic bellow with pressure relief Corrosion-proof Metallic Bellow without
20 device pressure relief device
21 Mechanical characteristics : Suitable for mounting line trap minimum 250 kg Suitable for mounting line trap max. 250 kg
a) Average mechanical breaking load N to be mentioned 10000
b) Minimum failing loads :
- tensile loads N to be mentioned 2500
- torsional loads Nm to be mentioned N/A
- cantilever loads N to be mentioned 2500
- compressive loads N to be mentioned N/A
c) Max. electromechanical failing load to be mentioned N/A
d) Max. operating load N to be mentioned N/A
22 Oil level indicator Direct type Direct type
23 Secondary terminal box Made from corrosion resistant die cast alluminium, Made from corrosion resistant hot dip
min.IP54, removable, undrilled, terminal flange with galvanized mild steel, min.IP54, removable,
drainage undrilled, terminal flange with drainage

24 Earthed terminal one earth terminal One Earth Terminal


25 Sesmic Condition (Earthquake Factor) (according to seismic g ≥ 0,3 0,5
map)