Technical Data Bulletin


TS 30198

Main to Reserve Transfer Station

The Main to Reserve Transfer Station is supplied


with the following standard features:

C Installs quickly
C Helps prevent accidental discharge
of reserve cylinder bank
C Fits standard single gang electrical boxes
C UL listed

Description

The Chemetron Fire Systems Main to Reserve Transfer ARCHITECT/ENGINEER SPECIFICATIONS


Station is a manually-activated, electric device designed to A Chemetron Fire Systems Main to Reserve Transfer
let the user switch the fire suppression system to its reserve Station, stock number 20100145, shall be provided. It shall
cylinders until the primary cylinders are back in place and be used to switch the suppression system from the main
operating normally. Its distinctive appearance and operation agent supply to the reserve, back-up supply.
make it easy to differentiate from other types of system
Operating instructions shall be in raised letters, stamped
controls.
into the faceplate. The raised letters shall be silkscreened
Normally mounted near the suppression agent storage in a contrasting color.
location, the transfer station is operated by pulling the
The unit shall consist of a two-pole switch that shall
protective pin, which breaks the seal and allows the toggle
accommodate two independently supervised releasing
switch to be pushed into the Reserve position. The toggle
solenoids. The switch shall be fitted with a protective guard
switch has a double-pole, double-throw contact arrange-
and pin with a seal to prevent misuse or tampering. To
ment for two independently supervised releasing solenoids.
guard against locking out all actuators, the switch shall have
The faceplate is constructed of formed steel and painted no middle position.
red. For permanence, all operating instructions are in raised
letters, stamped into the faceplate. For added clarity, the
letters are silkscreened in a contrasting color. Instructions
are arranged in an easy-to-read format. A back box is
available for surface-mounted installations.

Ordering Information

Shipping Weight
Stock Number Description lbs (kg)

20100145 Main to Reserve Transfer Station .5 (.23)

30100207 Back Box for Surface Mounting .5 (.23)


Technical Data Bulletin
TS 30198

Distributed by

The seller makes no warranties, express or implied, including,


but not limited to, the implied warranties of merchantability
and fitness for a particular purpose, except as expressly stated
in seller's sales contract or sales acknowledgment form.