Professional Documents
Culture Documents
6, NOVEMBER 2006
A Line-Interactive Single-Phase to
Three-Phase Converter System
Ricardo Quadros Machado, Simone Buso, Member, IEEE, and José Antenor Pomilio, Senior Member, IEEE
Abstract—This paper describes a line-interactive single-phase to some upgrades to improve performance aspects such as: mini-
three-phase converter. A typical application is in rural areas sup- mization of the number of power switches; cost reduction; im-
plied by a single-wire with earth return system. The traditional ob- provement of the power factor to the single-phase feeder; guar-
jective of feeding a three-phase induction motor is not anymore
the main concern for such conversion. Due to the evolution of the antee of good voltage quality to the load; etc.
farm technology, some of the local loads (as electronic power con- Besides the motors, even in rural applications, there is an
verters, computers, communication equipments, etc) require high increase in the use of electric and electronic loads that are sen-
power quality that is intended as sinusoidal, symmetrical, and bal- sitive to the power quality as, for example, power electronics
anced three-phase voltage. Additionally, to maximize the power converters, computers, etc. Some of these are nonlinear, single-
from the feeder, the system provides a unity power factor to the
grid. A three-phase voltage source inverter–pulsewidth modulation phase loads with low power factor. The single-phase feeder
converter is used for this purpose. The power converter processes could directly feed these loads. However, considering the power
a fraction of the load power and the energy necessary to regulate limitation of the feeder, it is interesting to maximize the active
the dc link voltage. As it does not need to supply active power, it power availability, which can be achieved with a unity power
is not necessary to have a source at the dc side. However, if island factor. This improvement could be done using some kind of
mode operation is needed, a dc source must be available at the dc
link to supply the load. The control strategy, design criteria, and power factor corrector or active power filter.
experimental results are presented. This paper presents a single-phase to three-phase conversion
system that improves the local power quality for linear and non-
Index Terms—Digital control, pulsewidth modulation (PWM)
inverter, single-phase to three-phase conversion, uninterrupted linear loads, and guarantees unity power factor at the single-
power supplies (UPS). phase feeder. The system is shown in Fig. 1. The single-phase
feeder is connected to the local three-phase bus through an
inductor. A three-phase static power converter (SPC) is con-
I. INTRODUCTION nected to the bus through a low-pass filter . The
inverter controls the local power quality, producing three-phase
VEN if the distribution of electric power is typically three-
E phase, in some situations the consumer can have access
only to a single-phase grid. This happens in residential, light in-
balanced, symmetrical and sinusoidal voltages. It also controls
the single-phase power flow, by adjusting the local voltage am-
plitude and phase angle. Harmonic currents of the load flow lo-
dustrial, and rural areas. Sometimes, a specific appliance needs cally, so that the resulting feeder current is sinusoidal, except for
three-phase power, requiring some kind of power conversion the harmonic components already present in the single-phase
[1]. In rural areas, the use of a single wire feeder with earth voltage. In this sense, the converter also works as an active filter
return is common. The power quality is normally very poor in for the current harmonics and as a reactive power compensator
terms of voltage regulation and distortion. [9]. Additionally, part of the load power is not processed by the
In a typical situation, the load is a three-phase induction motor converter, and flows directly from the grid, which can improve
and the conversion is made using some kind of pulsewidth mod- the overall efficiency.
ulation (PWM) converter [2]–[8]. For such an application, it is As this SPC does not deliver active power to the load in other
not important to filter out the switching high-frequency com- words, it only processes a fraction of the load power and the
ponents produced by the converter, because the load naturally energy necessary to regulate the dc link, a dc power source is
acts as a low-pass filter. In the conventional conversion system, not necessary. However, the system could operate also as an
the load power is processed twice: by a single-phase rectifier uninterrupted power supply (UPS) if a dc source is available on
and a three-phase inverter. The topologies presented in [2]–[8] the dc side, since then the islanding situation can be adequately
also have a rectifier followed by an inverter, but they incorporate managed. After grid failure, the solid state relay must be opened
and fixed voltage amplitude must be produced by the SPC [10].
Manuscript received September 9, 2004; revised October 17, 2005. The paper
was presented at the Power Electronics Specialists Conference (PESC), Aachen,
Germany, June 2004. This work was supported by CAPES and FAPESP Projects
BEX0277/02-9 and 00/11038-9. Recommended by Associate Editor A. von
II. BASIC SYSTEM OPERATION
Jouanne.
R. Q. Machado and J. A. Pomilio are with the School of Electrical and Com- As explained before, one of the control strategy goals is to
puter Engineering, State University of Campinas, Campinas 13081-970, Brazil produce a grid current that results in unity power factor. As the
(e-mail: ricardom@dsce.fee.unicamp.br; ricardombr2002@yahoo.it). voltage at the single-phase feeder can vary, both amplitude and
S. Buso is with the Department of Information Engineering, University of
Padova, Padova 35131, Italy (e-mail: simone.buso@dei.unipd.it). phase of the ac three-phase bus voltage must be adjusted, as
Digital Object Identifier 10.1109/TPEL.2006.882963 shown in Fig. 2. The limits for the amplitude variation, which
0885-8993/$20.00 © 2006 IEEE
MACHADO et al.: LINE-INTERACTIVE SINGLE-PHASE TO THREE-PHASE CONVERTER SYSTEM 1629
(1)
(2)
A. AC Current Control
Table II presents the design parameters for the PI current
controller shown in the block diagram of Fig. 3. Open loop
gain , closed loop cut-off angular frequency and
phase margin define the proportional and integral con-
stants ( and ) according to the following equations:
(3)
(4)
Fig. 1. Single-phase to three-phase conversion system. An internal current loop employs another PI controller to reduce
the converter output impedance and guarantees a good dynamic
performance to the system. The closed loop cut-off frequency
of the current PI was chosen one decade below the sam-
pling frequency so that the current PI still has a good compen-
sation capability in the frequency range of interest. To improve
this capability, a feedforward of the reference voltage could be
used to compensate the residual error in the closed loop gain at
low frequencies [12], [13].
Fig. 2. Phasorial diagram.
B. AC Voltage Control
Table III presents the design parameters for the PI voltage
TABLE I
THREE-PHASE BUS VOLTAGE RANGE controller. The open loop gain , closed loop cut-off an-
gular frequency and phase margin define the
proportional and integral constants (5) and
(5)
(6)
TABLE II
CURRENT LOOP CONTROL PARAMETERS
TABLE III
VOLTAGE LOOP CONTROL PARAMETERS
component a tuned resonant filter and a feedforward of the ca- from the phasor diagram of Fig. 2, it is possible to obtain the
pacitive current are put in parallel to the conventional voltage power flow at the single-phase feeder, when unity power factor
regulator, so as to boost the loop gain at the fundamental fre- is assumed. This is given by
quency [12], [13].
(8)
C. DC Link Voltage Control
According to (9), the dc link power flow is
When an ac power disturbance is detected, due to a load vari-
(9)
ation or to a grid voltage fluctuation, the control system reacts
adjusting the voltage in order to alter the power flow at the As the dc link voltage should be almost constant, a relatively
single-phase feeder. During such transient, the power unbalance large dc link capacitor was used (4700 F). In other words, we
flows through the inverter, changing the dc link voltage. After can assume that variations only take place in the dc link current,
the transient, whose power demand is supplied by the inverter, according to
the load power is supposed to be constant.
The strategy adopted to regulate the dc link voltage is to ex- (10)
change the necessary power with the single-phase feeder. In
order to maintain the ac bus voltage amplitude constant, this The variation of can then be expressed as in (11).
control circuit adjusts only the angle, based on the dc link Assuming small values (11) can be linearized as in (12) as
voltage error, as illustrated in Fig. 4. follows:
Considering the power balance condition
(11)
(12)
(7)
MACHADO et al.: LINE-INTERACTIVE SINGLE-PHASE TO THREE-PHASE CONVERTER SYSTEM 1631
TABLE IV
DC VOLTAGE CONTROL PARAMETERS
Fig. 6. SPC voltage and angle versus source voltage (nominal power).
(13)
(14)
TABLE V
L DIMENSION
Fig. 12. From top to bottom: load current (10 A/div), ac bus voltage (90 V/div),
single-phase current (10 A/div) and ac bus voltage (250 V/div). Horizontal:
10 ms/div.
Fig. 10. From top to bottom: single-phase current (10 A/div), ac bus voltage
(500 V/div.), dc link voltage (200 V/div) and motor current (5 A/div). Hori- TABLE VI
zontal: 50 ms/div. STEADY-STATE POWER MEASUREMENTS
Fig. 16. From top to bottom: ac bus voltage (250V/div), single-phase current
(10 A/div) and single-phase feeder voltage (90 V/div). Horizontal: 10 ms/div.
Fig. 13. DC link voltage under a load step (45 V/div.) Horizontal: 40 ms/div.
(experimental result).
single-phase voltage is present and waits about 1 s to close the
solid state relay and reconnect the system (Fig. 16).
VI. CONCLUSION
A line-interactive single-phase to three-phase conversion
system was presented. It is suitable for sensitive loads be-
cause it guarantees the three-phase power quality that means:
sinusoidal, balanced, and symmetrical voltages even with
nonlinear and unbalanced loads. A three-phase inverter is
controlled in order to stabilize the three-phase voltage while
absorbing current from the single-phase feeder, under unity
power factor. Experimental results on a 3-kVA system confirm
the expectations.
REFERENCES
[1] W. A. Moncrief, “Practical application and selection of single-phase
to three-phase converters,” in Proc. 39th IEEE Rural Electric Power
Conf., Apr. 1996, pp. D3-1–D3-9.
Fig. 14. DC link voltage under a load step (50 V/div.) Horizontal: 50 ms/div. [2] P. Enjeti and A. Rahman, “A new single-phase to three-phase converter
(simulation result). with active input current shaping for low cost ac motor drives,” IEEE
Trans. Ind. Appl., vol. 29, no. 4, pp. 806–813, Jul./Aug. 1993.
[3] D.-C. Lee, T.-Y. Kim, G.-M. Lee, and J.-K. Seok, “Low-cost
single-phase to three-phase PWM AC/DC/AC converters without
source voltage sensor,” in Proc. IEEE ICIT’02, 2002, pp. 792–797.
[4] G. A. Covic, G. L. Peters, and J. T. Boys, “An improved single phase
to three phase converter for low cost ac motor drives,” in Proc. IEEE
PEDS Conf., Feb. 1995, pp. 549–554.
[5] E. R. C. da Silva, S. B. de Souza, and F. A. Coelho, “A single phase
to three phase soft-switched converter, isolated and with active input
current shape,” in Proc. IEEE PESC, Jun. 1995, pp. 1252–1257.
[6] T. Ohnishi, “PWM control method for single-phase to three-phase
converter with a three-phase switching power module,” in Proc. IEEE
PESC, May 1998, pp. 464–469.
[7] E. N. Tshivhilinge and M. Malengret, “A practical control of a cost
reduced single-phase to there-phase converter,” in Proc. IEEE ISIE, Jul.
1998, pp. 445–449.
[8] H. Douglas and M. Malengret, “Symmetrical PWM with a split-capac-
itor single-phase to three-phase converter for rural electrification,” in
Proc. IEEE ISIE, Jul. 1998, pp. 289–293.
[9] E. G. Marra and J. A. Pomilio, “Induction generator based system pro-
viding regulated voltage with constant frequency,” IEEE Trans. Ind.
Electron., vol. 47, no. 4, pp. 908–914, Aug. 2000.
Fig. 15. From top to bottom: ac bus voltage (250V/div), single-phase current [10] S. B. Bekiarov and A. Emadi, “A new on-line single-phase to three-
(10 A/div), Single-phase feeder voltage (90 V/div) and failure bit detector of the phase UPS topology with reduced number of switches,” in Proc. IEEE
single-phase voltage. Horizontal: 10 ms/div. PESC, 2003, pp. 451–456.
1636 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 21, NO. 6, NOVEMBER 2006
[11] Standard for Power Delivery Using the Single Wire Earth Return Simone Buso (M’97) received the M.S. degree
System (Norma Para Fornecimento de Energia Elétrica Pelo Sistema in electronic engineering and the Ph.D. degree
Monofásico com Retorno por Terra—MRT), NE 08. CELPE, Cia. de in industrial electronics and informatics from the
Eletricidade do Pernambuco, 1978. University of Padova, Padova, Italy, in 1992 and
[12] R. Q. Machado, S. Buso, J. A. Pomilio, and F. P. Marafão, “Three- 1997, respectively.
phase to single-phase direct connection for rural co-generation sys- Since 1993, he has worked with the Power Elec-
tems,” in Proc. IEEE APEC, Feb. 2004, pp. 753–758. tronics Research Group, Department of Information
[13] R. Q. Machado, J. A. Pomilio, S. Buso, and F. P. Marafão, “Eletronic Engineering (DEI), University of Padova, where he is
control of a three-phase induction generator directly connected to a currently a Scientific Researcher. His main research
single-phase feeder,” in Proc. COBEP onf., Brazil, Sep. 2003, pp. interests are in the industrial and power electronics
fields and are specifically related to: dc/dc and ac/dc
651–656.
converters, smart power integrated circuits, digital control and robust control of
[14] L. Rossetto and S. Buso, “PWM line voltage regulator with integrated
power converters, solid state lighting, electromagnetic compatibility applied to
PFC,” in Proc. IEEE PESC, 2003, pp. 1254–1259.
integrated circuits, and switch mode power supplies.