Professional Documents
Culture Documents
Page
Foreword 3
1. Standards 4
7. Continued use
7.1 Excerpt from the Drinking Water Ordinance 21
7.2 Excerpt from DIN 1988-600 21
8. Log book 21
Appendices 22
Foreword event of a fire either by building for fire-fighting systems and
occupants or by professional fire-fighting water systems.
This brochure is intended for all firefighters, depending on their KSB's systems comply with all
involved with the planning and design. Prior to planning fire- requirements to be met by
design of fire-fighting systems fighting and fire protection pressure booster systems for
in general and fire-fighting systems, it is necessary to fire-fighting applications
water systems in particular. consult the fire protection plan in accordance with DIN 14462
This brochure specifically deals and take into account accepted and DIN 1988-600.
with wall hydrant systems. Fire- technical rules and regional
fighting systems and fire- building regulations including
fighting water systems are used laws, regulations and directives
in preventive fire protection and applicable for specific building
are not intended for domestic types (e.g. directives and
use (see DIN EN 1717). They regulations relating to high-rise
serve to save and protect the buildings, assembly rooms,
lives of persons and to fight garages etc.). The fire
fires. Their piping systems protection plan provides
convey either potable or non- information on the required
potable water. When directly fire-fighting water quantity, the
connected to the drinking water location and arrangement of
grid, they are subject to strict building services installations
hygienic requirements to avoid (piping system in particular)
impairment of drinking water and documentation confirming
quality. Wall hydrant systems fire-fighting water supply.
are stationary fire-fighting Should such a plan not be
installations equipped with available, information must be
specialised fire hose obtained from the bodies
connections which require responsible, e.g. fire protection
manual operation. Their authorities, fire service. This
purpose is to be used in the brochure offers design guidance
3
1 Fire-fighting water supply
1.
Standards
• DIN 14462
Planning, installation, operation and maintenance of fire hose systems and pillar fire hydrant and
underground fire systems
National supplements
DIN 1988-100: Protection of drinking water, drinking water quality control
DIN 1988-200: Installation, planning
DIN 1988-300: Pipe sizing
DIN 1988-500: Pressure boosting stations with RPM-regulated pumps
DIN 1988-600: Drinking water installations in connection with fire-fighting and fire protection
installations
4
Fire-fighting water supply
2
standards.
5
2 Fire-fighting water supply
It must be ensured that only All shut-off elements provided for DIN 14462.
applicable standards and other must be installed as centrally as Press-fit, clamp and plug-in
regulations are installed. Any possible. They must be marked and connections in dry- and wet/dry-
deviations from these stipula- secured against unauthorised closing. type fire-fighting water systems are
tions must be agreed with the only permitted if they are suitable
responsible authorities and Except for the inlet valves for this use.
standards DIN EN 1717 and (landing valves), installation of any If these connection modes have
DIN 1988-100 and 600 must further shut-off elements into already been inspected and tested
be observed for the connection “dry” fire-fighting water pipes, i.e. for use in fire-fighting water
of fire-fighting water pipes/ risers, is not permitted. systems (i.e. sprinkler and water
installations. Fire-fighting water pipes must be body1), they are considered suitable
fastened in accordance with for use in dry- and wet/dry-type
DIN 1988-200. When dry- and fire-fighting water systems.
wet/dry-type riser systems are
1
) Information on inspection bodies is provided by NA 031 German fire-fighting standards committee (FNFW) at DIN e. V.,
10772 Berlin (Address: Burggrafenstraße 6, 10787 Berlin).
6
Fire-fighting water supply
2
2.5 determined. If the pressures are fitted with its own pump
Pipe sizing lower than 1.2 bar, a throttling system. Alternative: 1 variable
When calculating and selecting orifice should be installed. speed pump system and a
the wall hydrant system, it is second setpoint.
necessary to calculate the • Pressure reducers should be On the basis of the above
pressure loss and determine the installed as centrally as information on pressure
required nominal pipe possible. control, planners must
diameters. A suitable method is • Adjustable flow pressure: 3 to determine whether throttling
stipulated in DIN 1988-300. 8 bar orifices, pressure reducers or
Consult the following table for • They must be capable of multiple pumping systems
information on flow rates and covering a flow rate of 300 to should be used.
minimum flow pressures. 600 litres per minute.
2.6
Pressure control to Their design must ensure that
DIN 14462, Supplement 1 fire protection is not impaired.
A pressure reducer is generally They must be marked and
not required in a fire-fighting secured against unauthorised
water system. Only in cases manipulation. They must be
where the flow pressure at the serviced at least once a year!
wall hydrants exceeds the max. Use of pressure booster systems
permissible level of 8 bar should to control the pressure in the
pressure control devices be pressure zones:
installed and pressure zones e.g.: every pressure zone is
2.7
Flow rate and flow pressure
Table 1: Required flow rates and pressures at outlet valve (landing valve)
The fire-fighting water available for simultaneous hydrant operation and the required minimum pressure
must be agreed with the responsible fire protection authority or specified in the fire protection plan.
7
2 Fire-fighting water supply
8
Fire-fighting water supply
2
2.10.2 2.10.3
Minimum requirements for PBS connection to power
PBS control supply
1
1. In addition to automatic 1. The power cable to the
operation, it must be possible to pump's control cabinet must be
manually activate the PBS. The used for power supply to the PBS 2 3
9
3 Fire-fighting water supply
3.
Overview of fire-fighting water systems
No frost Frost
10
Fire-fighting water supply
3
5 2
6
FIL
000
∑m3
9
7
8
10 4 3
Fig. 4: Wet-type fire-fighting water system with type F wall hydrant; fire-fighting water hand-over point; air gap
11
3 Fire-fighting water supply
3.3
Wet/dry-type fire-fighting
Wet/dry-type fire-fighting water system
water systems to DIN 14462
Drinking water
Wet/dry-type fire-fighting water
1
systems may be directly or
5 3
indirectly connected to the
drinking water grid. In the case
2
of direct connection, external
water supply, e.g. by 6
FIL
firefighters, is not permitted via
8 4
000
∑m3
11
– a fire-fighting water inlet 7 10
12
device 9
semi-rigid hose
• Fire-fighting water with QFfw 2
and p supplied after a
maximum of 60 s
6
FIL
000
continuous consumers and ∑m3
11
the centre of the solenoid Water meter
valve is ≤ 10 · DN or ≤ 1.5l of 12
3.4
Drinking water installation
2
with wall hydrant type S 1
(DIN 14462)
If the drinking water demand is 1
1. Continuous consumers
2. Wall hydrant type S to
DIN 14461-1 (fire hose Fig. 7: Drinking water installation with wall hydrant type S; fire-fighting
connection valve to water hand-over point: wall hydrant type S with safety combination
13
3 Fire-fighting water supply
3.5
Planning and installation
to DIN 14462
DIN 14462: Wall hydrant
systems
According to DIN 14462, wall
hydrants for occupant use must
be provided in conjunction with
wet/dry-type fire-fighting water
systems. The wall hydrants
installed for this purpose
should preferably be equipped
with semi-rigid hose types to
DIN 14461-1.
DIN 14461-1
Firefighter use (may also be
used by occupants to combat
incipient fires)
Fire-fighting water flow rate:
3 x 100 l/min (= 18 m³/h) at a
minimum flow pressure of 3 bar
14
Fire-fighting water supply
4
500
400
100
300
Max. flow pressure
8.0 bar
200
2B 4B 6B 10 B 15 B 25 B 45 65 90 B
50
40
30 100
ft
20
50
40
10
30
H
[m]
20
5
1 Q[m³/h] 2 3 4 5 10 20 30 40 50 100 200
0.3 0.4 0.5 l/s 1 2 3 4 5 10 20 30 40 50
2 type S 3 type F 3 type F
wall hydrants wall hydrants wall hydrants
24 l/min 3 x 100 l/min 3 x 200 l/min
(2,88 m3/h) (18 m3/h) (36 m3/h)
15
4 Fire-fighting water supply
4.1
Calculation example 1
Office and administration building
– 5 floors, each with a height of 3.0 m
– Type F wall hydrants
> 3.0 bar
100 l/min at 3 bar
– Remotest hydrant 40 m (15 mbar/m)
– Single-pump PBS
∑ HV= 0.6 bar
15 m
Δpp = Δpgeo+ Σ(R · l +Z)discharge+pmin,hydr (3)
0 bar
= 1.5 bar + 0.6 bar + 3.0 bar
= 5.1 bar VB PBS
0 20 US.gpm 40 60 80 100
0 20 IM.gpm 40 60 80
270 Q min *)
250 15/17 15 kW
800
15/15 15 kW
200
15/13 15 kW
600
15/11 11 kW
150 15/10 11 kW
15/9 11 kW
15/7 7,5 kW
100
15/6 5,5 kW ft
15/5 5,5 kW
15/4 4 kW 200
55
50 15/3 3 kW
15/2 2,2 kW
m
15/1 1,1 kW
0 0
0 5 m3/h 10 15 18 20 25
0 2 l/ s 4 6
Fig. 12: Characteristic curve of Hya-Solo D FL 1/1505 Fig. 13: Hya- Solo D FL
16
Fire-fighting water supply
4
4.2
Calculation example 2
> 4.5 bar
Office building
– Building height > 22 m; directives and
regulations relating to standard high-rise
buildings are applied ∑ HV= 0.3 bar
VB PBS
Δpp = Δpgeo+ Σ(R · l +Z)discharge+pmin,hydr (5)
Fig. 14: System diagram
= 3.0 bar + 0.3 bar + 4.5 bar
= 7.8 bar
17
4 Fire-fighting water supply
4.3
Calculation example 3
> 4.5 bar
Office building
– Building height > 22 m; directives and
regulations relating to standard high-
rise buildings are applied ∑ HV= 0.3 bar
– Type F wall hydrant
30 m
200 l/min at 4.5 bar
– Simultaneous-use factor: 3 wall hydrants
– Dual-pump PBS 2 x 100% 0 bar
VB PBS
Δpp = Δpgeo+ Σ(R · l +Z)discharge+pmin,hydr (7)
Fig. 17: System diagram
= 4.0 bar + 0.5 bar + 4.5 bar
= 9.0 bar
H [m]
When wall hydrants are opened, the 160
max. permissible flow pressure of 8 150
45/6
bar is generally exceeded. To prevent 140
130 45/6-1
this, the following options are 120 45/5
available: 110
45/5-1
100 45/4
90
Max. flow
- Installation of a variable speed 80
45/4-1
pressure
pressure booster system with two 70 8.0 bar
60
fixed setpoints, e.g. high pressure via
50
pressure control and low pressure via 40
limit switch 30
20
10
- Throttling orifices at the lower 0
0 5 10 15 20 25 30 35 40 45 50 55 60 Q [m3/h]
floors.
18
Fire-fighting water supply
5
5. 5.1
Break tank selection Break tank with a type AB
As per DIN 14462, the effective air gap to DIN EN 1717 and
volume must be established in DIN EN13077
accordance with DIN 1988-500 The break tanks and their
or its operating reliability must be accessories must comply with
demonstrated individually. the hygienic standards
regarding the following:
The effective volume must there-
fore be calculated as follows: – Non-circular overflow to
DIN EN 1717, type AB
Optional: automatic flushing
V BT ≥ 0.03 · Qpeak device with timer to DIN 14462
(9)
where
V BT = Effective volume in m3
Qpeak = Peak flow rate in m3/h
Calculation:
V BT = 0.03 · 18 m3/h = 540 l or
V BT = 0.03 · 36 m3/h = 1080 l
Selected:
19
6 Fire-fighting water supply
6.
Selection chart for auto-
matic flushing device
In order to comply with the
requirements for drinking water
80
hygiene, an automatic flushing
device must be provided for a 1½" solenoid valve
70
branch pipe larger than 10x DN
or a 1.5 l pipe content. 60
50
Selection chart for solenoid
valves 40
Q m3/h
30
Nominal Flow velocity 1" solenoid valve
diameter 20
18
≥ DN 50 min. 0.2 m/s
10 ½" solenoid valve
< DN 50 min. 0.1 m/s
0
At least 3 times the pipe content 0 1 2 3 4 5 6
Pinl [bar]
must be flushed once a week!
20
Fire-fighting water supply
7
21
22
Annex
Selection of KSB break tank packaged booster sets for fire-fighting
High-rise building Yes > 22m from the ground floor to the highest occupied floor
No < 22m from the ground floor to the highest occupied floor
Pipe length: m
DN65
DN
At your request, we will be pleased to send you all KSB know-how volumes previously
published. Ordering is easy.
• http://www.ksb.com/ksb-en/contactfinder/
• Choose your country and/or post or ZIP code.
• Simply send an e-mail to the competent sales house or local company, stating the know-how
volumes you require.
2300.023-EN / 03.14 / © KSB Aktiengesellschaft 2013 ·Subject to technical modification without prior notice
The KSB-newsletter –
dont‘ miss out, sign up now
www.ksb.com/newsletter
Your contact:
KSB Aktiengesellschaft
Johann-Klein-Straße 9
67227 Frankenthal (Germany)
www.ksb.com