You are on page 1of 26

KSB Know-how, Volume 8

Planning Information for Fire-fighting Water Systems


Contents

Page
Foreword 3

1. Standards 4

2. Requirements to be met by fire-fighting water systems 5


2.1 Legal basis 5
2.2 Issues to be clarified 5
2.3 General requirements 6
2.4 Pipes and valves 6
2.5 Pipe sizing 7
2.6 Pressure control valve to DIN 14462 Supplement 1 7
2.7 Flow rate and flow pressure 7
2.8 Drainage 8
2.9 Break tank 8
2.10 Pressure booster systems – Minimum requirements for fire-fighting
applications to DIN 14462 8
2.10.1 General 8
2.10.2 Minimum requirements for PBS control 9
2.10.3 PBS connection to power supply 9

3. Overview of fire-fighting water systems 10


3.1 Fire-fighting water hand-over point 10
3.2 Wet-type fire-fighting water systems to DIN 14462 11
3.3 Wet/dry-type fire-fighting water systems to DIN 14462 12
3.4 Drinking water installation with wall hydrant type S (DIN 14462) 13
3.5 Planning and installation to DIN 14462 14

4. Calculating the hydraulic data of a fire-fighting PBS for


wall hydrants 15
4.1 Calculation example 1 16
4.2 Calculation example 2 17
4.3 Calculation example 3 18

5. Break tank selection 19


5.1. Break tank with a type AB air gap to DIN EN 1717 and
DIN EN 13077 19

6. Selection chart for automatic flushing equipment 20

7. Continued use
7.1 Excerpt from the Drinking Water Ordinance 21
7.2 Excerpt from DIN 1988-600 21

8. Log book 21

9. Products offered by KSB 21

Appendices 22
Foreword event of a fire either by building for fire-fighting systems and
occupants or by professional fire-fighting water systems.
This brochure is intended for all firefighters, depending on their KSB's systems comply with all
involved with the planning and design. Prior to planning fire- requirements to be met by
design of fire-fighting systems fighting and fire protection pressure booster systems for
in general and fire-fighting systems, it is necessary to fire-fighting applications
water systems in particular. consult the fire protection plan in accordance with DIN 14462
This brochure specifically deals and take into account accepted and DIN 1988-600.
with wall hydrant systems. Fire- technical rules and regional
fighting systems and fire- building regulations including
fighting water systems are used laws, regulations and directives
in preventive fire protection and applicable for specific building
are not intended for domestic types (e.g. directives and
use (see DIN EN 1717). They regulations relating to high-rise
serve to save and protect the buildings, assembly rooms,
lives of persons and to fight garages etc.). The fire
fires. Their piping systems protection plan provides
convey either potable or non- information on the required
potable water. When directly fire-fighting water quantity, the
connected to the drinking water location and arrangement of
grid, they are subject to strict building services installations
hygienic requirements to avoid (piping system in particular)
impairment of drinking water and documentation confirming
quality. Wall hydrant systems fire-fighting water supply.
are stationary fire-fighting Should such a plan not be
installations equipped with available, information must be
specialised fire hose obtained from the bodies
connections which require responsible, e.g. fire protection
manual operation. Their authorities, fire service. This
purpose is to be used in the brochure offers design guidance

3
1 Fire-fighting water supply

1.
Standards

Fundamental European standard


DIN EN 806 Technical rules for drinking water installations
Part 1: General
Part 2: Planning
Part 3: Calculation of inside pipe diameters
Part 4: Installation
Part 5: Operation and maintenance

Standards for drinking water and fire-fighting installations


• DIN EN 1717
Protection against pollution of potable water installations and general requirements of devices to
prevent pollution by backflow

• DIN 14462
Planning, installation, operation and maintenance of fire hose systems and pillar fire hydrant and
underground fire systems

National supplements
DIN 1988-100: Protection of drinking water, drinking water quality control
DIN 1988-200: Installation, planning
DIN 1988-300: Pipe sizing
DIN 1988-500: Pressure boosting stations with RPM-regulated pumps
DIN 1988-600: Drinking water installations in connection with fire-fighting and fire protection
installations

4
Fire-fighting water supply
2

standards.

Property boundary 2.2


Issues to be clarified
– Has a fire protection plan
been obtained from the
responsible body and what
Inside Outside of Water provider
buildings buildings information does is provide?
DIN EN 1717 DIN EN 805 DIN EN 805
DIN EN 806
– Type and design of outlet
Additional scope – DIN1988, 10 0 - 60 0 devices
Fig. 1: Scope of standards – Fire-fighting water system
design
2. types (e.g. directives and – Number and distribution of
Requirements to be met by regulations relating to high-rise outlet devices
fire-fighting water systems buildings, assembly rooms, – Fire-fighting water draw-off
The fire-fighting water system garages etc.). If a plan is not specified
begins at the interface between available, information can be
the fire-fighting/fire protection
obtained from the bodies
system and the drinking water • Max. flow rate when using
responsible for fire protection
installations. This interface is the outlet device, e.g.
such as building inspection,
referred to as the fire-fighting 100 l/ min per hydrant
water hand-over point (HOP) in fire service or fire protection
• Minimum flow pressure at all
accordance with DIN 1988- experts.
outlet devices, e.g. 3 bar
600.
• Number of simultaneously
No further draw-off points Minimum scope of information
other than those for fire- used outlet devices, e.g. 3
provided by a fire protection
fighting water extraction are units
plan:
permitted downstream of this • Required duration of fire-
– Operation: Who is operating
hand-over point. fighting water provision
the systems?
(DIN 14462: min. 2 hours)
– Wall hydrants: Where and at
• Performance data of water
2.1 which distances?
Legal basis supply connection
– Duration of fire-fighting water
• Max. static pressure
Prior to planning and supply
• Nominal supply pipe diameter
constructing fire-fighting and – Emergency power supply
• Max. height difference within
fire protection systems, it is – Functional integrity
the fire-fighting water system
necessary to consult the fire – Redundancy
protection plan and take into
account accepted technical rules Issues of liability require that all
and regional building planners focus not only on
regulations including laws, compliance with fire protection
regulations and directives requirements, but also on
applicable for specific building compliance with hygienic

5
2 Fire-fighting water supply

• Mechanical filters must not 2.4 used, increased hydraulic forces


be installed in the pipe Pipes and valves must be taken into account during
used for both drinking and The pipes and valves must be the filling process. Fire-fighting
fire-fighting water supply as selected in accordance with the water pipes and their valves must
otherwise the water supply to requirements of DIN 1988-600 be designed for a minimum
the wall hydrant system and must be laid and used in nominal pressure of PN 10 and
would not be sufficient in the compliance with this standard and “dry” risers for a nominal pressure
event of a fire. the manufacturer’s specifications. of PN 16, unless higher internal
• Filters must be installed in Valves intended for fitting into the pressures require a higher nominal
the piping which branches off supply pipe of fire-fighting pressure.
to the drinking water supply equipment must be designed in
installation. such a way that the fire-fighting It must be ensured that
• The branch pipe should be equipment’s operating function is impermissible pressures do not
fitted immediately not impaired. If distribution pipes occur as a result of high
downstream of the water meter. and risers of drinking water temperatures in the event of a fire.
• Strainers installed in the pipe installations are made of If required, expansion valves for
used for fire-fighting water flammable materials, it must be water discharge should be
supply must have a mesh size ensured that these pipe sections are provided; see DIN 4753,
of min. 1.0 mm. shut off by valves that close DIN 1988-200 and DIN EN 1509.
automatically when fire-fighting
water is extracted. The pipe materials used must
2.3
General requirements correspond to the table of

It must be ensured that only All shut-off elements provided for DIN 14462.

components complying with the pipes conveying fire-fighting water

applicable standards and other must be installed as centrally as Press-fit, clamp and plug-in

regulations are installed. Any possible. They must be marked and connections in dry- and wet/dry-

deviations from these stipula- secured against unauthorised closing. type fire-fighting water systems are

tions must be agreed with the only permitted if they are suitable

responsible authorities and Except for the inlet valves for this use.

documented in a test log. The (breechings) and outlet valves

standards DIN EN 1717 and (landing valves), installation of any If these connection modes have

DIN 1988-100 and 600 must further shut-off elements into already been inspected and tested

be observed for the connection “dry” fire-fighting water pipes, i.e. for use in fire-fighting water

of fire-fighting water pipes/ risers, is not permitted. systems (i.e. sprinkler and water

wall hydrants to drinking water spray systems) by an inspection

installations. Fire-fighting water pipes must be body1), they are considered suitable
fastened in accordance with for use in dry- and wet/dry-type
DIN 1988-200. When dry- and fire-fighting water systems.
wet/dry-type riser systems are

1
) Information on inspection bodies is provided by NA 031 German fire-fighting standards committee (FNFW) at DIN e. V.,
10772 Berlin (Address: Burggrafenstraße 6, 10787 Berlin).

6
Fire-fighting water supply
2

2.5 determined. If the pressures are fitted with its own pump
Pipe sizing lower than 1.2 bar, a throttling system. Alternative: 1 variable
When calculating and selecting orifice should be installed. speed pump system and a
the wall hydrant system, it is second setpoint.
necessary to calculate the • Pressure reducers should be On the basis of the above
pressure loss and determine the installed as centrally as information on pressure
required nominal pipe possible. control, planners must
diameters. A suitable method is • Adjustable flow pressure: 3 to determine whether throttling
stipulated in DIN 1988-300. 8 bar orifices, pressure reducers or
Consult the following table for • They must be capable of multiple pumping systems
information on flow rates and covering a flow rate of 300 to should be used.
minimum flow pressures. 600 litres per minute.

2.6
Pressure control to Their design must ensure that
DIN 14462, Supplement 1 fire protection is not impaired.
A pressure reducer is generally They must be marked and
not required in a fire-fighting secured against unauthorised
water system. Only in cases manipulation. They must be
where the flow pressure at the serviced at least once a year!
wall hydrants exceeds the max. Use of pressure booster systems
permissible level of 8 bar should to control the pressure in the
pressure control devices be pressure zones:
installed and pressure zones e.g.: every pressure zone is

2.7
Flow rate and flow pressure

Required flow rates and pressures at outlet valve (landing valve)


Category Flow rate Simultaneous use Minimum flow Max. flow Max. static
pressure pressure pressure
Wall hydrant type S (for use 24 l/min 2 0.20 MPa
by building occupants)
Wall hydrant type F (for use 100 l/min 3 0.30 MPa
by firefighters 200 l/min 3 0.45 MPa 0.8 MPa 1.2 MPa
Surface hydrant DN 80 800 l/min As per fire
Surface hydrant DN 100 1,600 l/min protection plan 0.15 MPa

Underground hydrant DN 80 800 l/min

Table 1: Required flow rates and pressures at outlet valve (landing valve)

The fire-fighting water available for simultaneous hydrant operation and the required minimum pressure
must be agreed with the responsible fire protection authority or specified in the fire protection plan.

7
2 Fire-fighting water supply

2.8 sufficient fire-fighting water 4. In the case of indirect


Drainage supply. If the fire-fighting water connection, it is important to
Drainage systems must be cannot be supplied in the required provide for external water
installed to drain the water quantity, the break tank must supply by means of an inlet
required for the equipment's be enlarged so that the required device to DIN 14461-2 and an
intended use and for inspection, amount of water can be provided additional check valve for
testing and maintenance for a minimum period of two firefighters, to ensure fire-
purposes; they must be sized and hours. fighting equipment availability
built in accordance with DIN at all times. This equipment is
1986-100 or with the standards not needed for type S wall
of the DIN EN 12056 range. 2.10 hydrant systems.
Pressure booster systems –
This particularly applies to: Minimum requirements for
fire-fighting applications 5. After PBS start-up, the flow
to DIN 14462 pressure developing at the
– Low-point drains, opened fire hose connection
– Fill and drain units, valves must be within the
2.10.1
– Aerators and vents, General required limits. (See table "Flow
– Break tanks, 1. The PBS for fire-fighting rate and flow pressure")
– Fire-fighting water drain outlet applications should be equipped
during flow rate measurement. with a single pump set and be 6. Any devices and controls
exclusively used for supplying fitted outside the pressure
Discharge of the fire-fighting fire-fighting equipment. The booster system's control cabinet
water volumes required for trial connection of further consumers which may compromise the
operation must be provided for is not permitted. The PBS must operational availability/proper
and performed in compliance be selected to ensure reliable functioning of the fire-fighting
with the regulations. operation even if the flow rate equipment must be protected
If the system is installed below falls below the minimum flow. against unauthorised operation
the flood level, it is necessary to and may only be operated by
provide a suitable lifting unit in 2. The fire protection plan authorised persons!
accordance with DIN 1986-100. provides information on the
operating reliability require-
ments (e.g. emergency power
2.9
supply, functional integrity,
Break tank
redundancy, fault indication).
The break tank must have a
Class A air gap which complies
3. If installation of a redundant
with the requirements of DIN
pump set to increase operating
EN 1717, type AB, and DIN EN
reliability is stipulated, then two
13076 or DIN EN 13077. The
pressure booster systems each
break tank may be designed to
capable of providing the required
DIN EN 12845, for example. The
quantity of fire-fighting water
break tank’s design must ensure
must be used, i.e. 2 x 100 %.

8
Fire-fighting water supply
2

2.10.2 2.10.3
Minimum requirements for PBS connection to power
PBS control supply
1
1. In addition to automatic 1. The power cable to the
operation, it must be possible to pump's control cabinet must be
manually activate the PBS. The used for power supply to the PBS 2 3

use of emergency-OFF switches only; it must be separated from 4 5

is not permitted. all other connections.

2. Faults must be visually 2. Connection to power supply 6 7


indicated at the pump's control must be performed in such a
Fig. 2: Example for the connec-
cabinet. Volt-free contacts must way that the power supply to the tion of a hydrant system at the
be provided for the transmission pump’s control cabinet is not cut low-voltage distribution board
of faults. Fault messages can be off when other consumers are
transmitted as a general fault disconnected. Key:
message. 1. Main fuse
3. A residual current device must 2. Fuse for hydrant connection
3. Motor protection devices in not be installed in the circuit. 3. Main fuse for other
the pump’s circuit may trigger The power cable leading to the consumers
fault signals, but must not trip PBS control cabinet must be 4. Load-break switch for
the pump set. The motor protected via the low-voltage hydrant systems
protection devices must only be distribution board. 5. Master switch for other
active during trial operation. In consumers
the event of a fire or when the 4. The electrical cables to the 6. To control cabinet/hydrant
PBS is in use, the motor motor’s terminal board or to the connection
protection device must not be power cable of submersible 7. To other consumers
active! borehole pumps must consist of
a single length of cable. Only
4. Transmission paths between one consumer (control cabinet,
the system and external motor etc.) may be connected to
commands triggering pump one cable.
start-up when fire-fighting water
supply is required, must be 5. Electrical cables for PBS
monitored for broken wire and power supply must remain fully
short circuits. Broken wire and functional in the event of a fire.
short circuits must be indicated
as a fault and must result in the
pump being started up.

9
3 Fire-fighting water supply

3.
Overview of fire-fighting water systems

Fire-fighting water systems

Wall hydrant systems

No frost Frost

Wet-type fire-fighting Wet/dry-type fire-fighting Drinking water supply Dry-type fire-fighting


water system water system system with wall hydrants water system

Wall hydrant type "F" Wall hydrant type "S"


(F = firefighters use) Inlet and outlet devices
(S = occupant use) in dry-type systems
3 x 100 l/min at 3 bar
3 x 200 l/min at 4.5 bar 2 x 24 l/min at 2 bar

For firefighters and


For occupant use only For firefighters' use only
building occupants

Fig. 3: Overview of fire-fighting water systems

3.1 provide appropriate automatic supply pipe to the fire-fighting


Fire-fighting water hand- flushing devices at the fire- water hand-over point must not
over point fighting water hand-over point exceed the calculated flow
The fire-fighting water hand- to ensure that sufficient water velocity of 5 m/s. The common
over point should be located as flows through the pipe. The supply pipe must be sized in
close to the water meter as flushing devices must be sized to accordance with the drinking
possible. The fire-fighting water ensure that a flow velocity of water peak flow rate.
hand-over point starts with a min. 0.2 m/s is reached at
shut-off valve. The fire-fighting DN 50 (referred to nominal
water hand-over point must not diameter) and 0.1 m/s in pipes
be located in rooms liable to greater than DN 50.
flooding. Individual supply pipes The automatic flushing device
to the fire-fighting water hand- must be operated in such a way
over point must not exceed a that at least 3 times the water
length of 10 × DN and a volume volume of the individual supply
of 1.5 litres. If this requirement pipe is exchanged once a week.
cannot be met, it is necessary to The peak flow in the individual

10
Fire-fighting water supply
3

3.2 Wall hydrants type F 8. Break tank with a type AB


Wet-type fire-fighting 1. Wall hydrant to DIN 14461-1, air gap to DIN EN 1717
water systems to DIN 14462 DIN 14461-6 and DIN EN 9. Strainers
Wet-type fire-fighting water 671-1 (with valve to 10. Flushing equipment, if
systems may only be indirectly DIN 14461-3) necessary
connected to the drinking water 2. Fire-fighting water pipe to
grid DIN 1988-600 and in
accordance with this
– Wall hydrants type F, with standard
semi-rigid hose 3. Water supply (optional) is
– Water supply to break tank: permitted with indirect
Class A air gap, vertical connection
(downward) inflow, minimum 4. PBS, e.g. to new DIN 14462
distance 2 cm or 2 x inside (fire-fighting PBS)
diameter to the water surface F 5. Continuous consumers
– The tank must be selected to 6. Domestic water filter
ensure sufficient fire-fighting 7. Water meter
water supply.

5 2

6
FIL

000
∑m3
9
7
8
10 4 3

Fig. 4: Wet-type fire-fighting water system with type F wall hydrant; fire-fighting water hand-over point; air gap

11
3 Fire-fighting water supply

3.3
Wet/dry-type fire-fighting
Wet/dry-type fire-fighting water system
water systems to DIN 14462
Drinking water
Wet/dry-type fire-fighting water
1
systems may be directly or
5 3
indirectly connected to the
drinking water grid. In the case
2
of direct connection, external
water supply, e.g. by 6

FIL
firefighters, is not permitted via
8 4
000
∑m3
11
– a fire-fighting water inlet 7 10
12
device 9

– wall hydrants with foaming


additives.
Fig. 5: Directly connected wet/dry-type fire-fighting water system;
fire-fighting water hand-over point: fill and drain unit

Wet/dry-type fire-fighting water system

• Wall hydrants type F, with Drinking water


5 1

semi-rigid hose
• Fire-fighting water with QFfw 2
and p supplied after a
maximum of 60 s
6
FIL

• Maximum pressure p = 8 bar <10·DN


or max. 1.5 l 3
(holding pressure)
7
• If the pipe length between the 4

000
continuous consumers and ∑m3
11
the centre of the solenoid Water meter

valve is ≤ 10 · DN or ≤ 1.5l of 12

pipe content, no flushing


equipment is necessary. Fig. 6: Indirectly connected wet/dry-type fire-fighting water system;
• If this distance is > 10 · DN, fire-fighting water hand-over point: air gap

then flushing equipment is


Key: 5. Continuous consumers
necessary: flush once a week, 1. Pipe aerators and vents to 6. Domestic water filter
3 times the pipe content at a DIN 14463-3 7. Water meter
flow rate of 2. Wall hydrant to DIN 14461-1, 8. E.g. membrane-type
0.2 m/s up to DN 50 DIN 14461-6 and DIN EN accumulator (optional)
671-1 (fire hose valve to DIN 9. Pressure booster system (PBS)
0.1 m/s above DN 50
14461-3 with limit switch) 10. Break tank with a type AB
3. Fire-fighting water pipe to air gap to DIN EN 1717
DIN 14463-1, DIN 1988- 11. Strainer
600 and in accordance with 12. Flushing equipment, if
this standard necessary
4. Fill and drain unit, e.g. to
DIN 14463-1
12
Fire-fighting water supply
3

3.4
Drinking water installation
2
with wall hydrant type S 1
(DIN 14462)
If the drinking water demand is 1

higher than the demand for


fire-fighting water, direct 1
3
connection is permitted under
the condition that piping ≤ 10 x
DN or max. 1.5 l pipe content
is observed. 1
6 7
5 4
000
Key: ∑m3
FIL

1. Continuous consumers
2. Wall hydrant type S to
DIN 14461-1 (fire hose Fig. 7: Drinking water installation with wall hydrant type S; fire-fighting
connection valve to water hand-over point: wall hydrant type S with safety combination

DIN 14461-3 with safety


combination)
3. Drinking water pipe to
DIN 1988 and DIN EN 806
4. Drain
5. Domestic water filter
6. Water meter
7. PBS to DIN 1988-500

13
3 Fire-fighting water supply

3.5
Planning and installation
to DIN 14462
DIN 14462: Wall hydrant
systems
According to DIN 14462, wall
hydrants for occupant use must
be provided in conjunction with
wet/dry-type fire-fighting water
systems. The wall hydrants
installed for this purpose
should preferably be equipped
with semi-rigid hose types to
DIN 14461-1.

Wall hydrants with a flat hose


may only be used where
specially trained personnel are
continuously available. 100
100

Wall hydrants type S to


DIN 14461-1
Occupant use, not intended for
use by firefighters
Fire-fighting water flow rate:
2 x 24 l/min (= 2.88 m3/h) at a
flow pressure of 2 bar
Fig. 8: Type S wall hydrant 100
Wall hydrants type F to 100

DIN 14461-1
Firefighter use (may also be
used by occupants to combat
incipient fires)
Fire-fighting water flow rate:
3 x 100 l/min (= 18 m³/h) at a
minimum flow pressure of 3 bar

Fire-fighting water flow rate: Fig. 9: Type F wall hydrant

3 x 200 l/min (= 36 m³/h) at a


minimum flow pressure of 4.5 bar The max. permissible flow
pressure or holding pressure of
8 bar must not be exceeded!

14
Fire-fighting water supply
4

4. The simultaneous-use factor Based on the head calculation


Calculating the hydraulic defined by DIN 14 462 is f = 3 for drinking water, the
data of a fire-fighting PBS wall hydrants. discharge pressure and head of
for wall hydrants the fire-fighting PBS is
The peak flow (V· ) for a fire- peak established as follows:
· ·
fighting water supply Vpeak = Vdesign,hydr · f = QD [m3/h]
application is exclusively (1)
calculated on the basis of the Δpp = Δpgeo+ Σ(R · l +Z)discharge +pmin,hydr
design flow rate per wall
(2)
hydrant x simultaneous-use Key:
factor (f). V·
peak
= Peak flow rate of a
For a type F wall hydrant, the PBS Key:
·
design flow rate per wall Vdesign,hydr = Design flow rate of Δpgeo = Pressure loss from
hydrant is as follows: a wall hydrant geodetic head difference
f = Simultaneous-use Σ(R · l+Z)discharge = Pipe friction and individual
·
Vdesign = 100 l/min = 6 m3/h or factor losses downstream of PBS

design
= 200 l/min = 12 m3/h QD = PBS design flow rate pmin,hydr = Minimum flow pressure
at the hydraulically least
favourable hydrant

5 US.gpm 10 20 30 40 50 100 200 300 400 500


4 5 IM.gpm 10 20 30 40 50 100 200 300 400 500
200

500

400

100
300
Max. flow pressure
8.0 bar
200
2B 4B 6B 10 B 15 B 25 B 45 65 90 B
50

40

30 100

ft
20

50

40

10
30
H
[m]

20

5
1 Q[m³/h] 2 3 4 5 10 20 30 40 50 100 200
0.3 0.4 0.5 l/s 1 2 3 4 5 10 20 30 40 50
2 type S 3 type F 3 type F
wall hydrants wall hydrants wall hydrants
24 l/min 3 x 100 l/min 3 x 200 l/min
(2,88 m3/h) (18 m3/h) (36 m3/h)

Fig. 10: Performance chart of Hya-Solo and Hya-Duo D FL

15
4 Fire-fighting water supply

4.1
Calculation example 1
Office and administration building
– 5 floors, each with a height of 3.0 m
– Type F wall hydrants
> 3.0 bar
100 l/min at 3 bar
– Remotest hydrant 40 m (15 mbar/m)
– Single-pump PBS
∑ HV= 0.6 bar

15 m
Δpp = Δpgeo+ Σ(R · l +Z)discharge+pmin,hydr (3)

0 bar

= 1.5 bar + 0.6 bar + 3.0 bar
= 5.1 bar VB PBS

V· peak = V· design,hydr · f (4)


V· peak = 100 l/min x 3


= 300 l/min Fig. 11: System diagram
=^ 18 m3/h

0 20 US.gpm 40 60 80 100
0 20 IM.gpm 40 60 80
270 Q min *)
250 15/17 15 kW
800

15/15 15 kW

200
15/13 15 kW
600

15/11 11 kW

150 15/10 11 kW
15/9 11 kW

15/8 7,5 kW 400

15/7 7,5 kW
100
15/6 5,5 kW ft
15/5 5,5 kW

15/4 4 kW 200
55
50 15/3 3 kW

15/2 2,2 kW
m
15/1 1,1 kW

0 0
0 5 m3/h 10 15 18 20 25
0 2 l/ s 4 6

Fig. 12: Characteristic curve of Hya-Solo D FL 1/1505 Fig. 13: Hya- Solo D FL

16
Fire-fighting water supply
4

4.2
Calculation example 2
> 4.5 bar
Office building
– Building height > 22 m; directives and
regulations relating to standard high-rise
buildings are applied ∑ HV= 0.3 bar

– Type F wall hydrant 30 m


200 l/min at 4.5 bar
– Simultaneous-use factor: 3 wall hydrants
0 bar
– Dual-pump PBS 2 x 100%

VB PBS
Δpp = Δpgeo+ Σ(R · l +Z)discharge+pmin,hydr (5)

Fig. 14: System diagram

= 3.0 bar + 0.3 bar + 4.5 bar
= 7.8 bar

V· peak = V· design,hydr · f (6)


V· peak = 200 l/min x 3


= 600 l/min
^ 36 m3/h
=

Fig. 15: Hya-Duo D FL Compact

When one or two wall hydrants are H [m]


160
opened at the lower floors, the max. 150
45/6
permissible flow pressure of 8 bar is 140
130 45/6-1
exceeded. The following separate
120 45/5
solutions are available: 110
45/5-1
100 45/4
90
- Installation of a variable speed 45/4-1 Max. flow
80 pressure
pressure booster system with a fixed 70 8.0 bar

setpoint of below 8 bar. 60


50
40
- Reduction of the flow pressure 30

through the installation of throttling 20


10
orifices at the lower floors. 0
0 5 10 15 20 25 30 35 40 45 50 55 60 Q [m3/h]

Fig.16: Characteristic curve of Hya-Duo D FL 2/4504

17
4 Fire-fighting water supply

4.3
Calculation example 3
> 4.5 bar
Office building
– Building height > 22 m; directives and
regulations relating to standard high-
rise buildings are applied ∑ HV= 0.3 bar
– Type F wall hydrant
30 m
200 l/min at 4.5 bar
– Simultaneous-use factor: 3 wall hydrants
– Dual-pump PBS 2 x 100% 0 bar

VB PBS
Δpp = Δpgeo+ Σ(R · l +Z)discharge+pmin,hydr (7)

Fig. 17: System diagram

= 4.0 bar + 0.5 bar + 4.5 bar
= 9.0 bar

V· peak = V· design,hydr · f (8)


V· peak = 200 l/min x 3


= ^ 600 l/min
^ 36 m3/h
=

Fig. 18: Hya-Duo DV FL Compact

H [m]
When wall hydrants are opened, the 160
max. permissible flow pressure of 8 150
45/6
bar is generally exceeded. To prevent 140
130 45/6-1
this, the following options are 120 45/5
available: 110
45/5-1
100 45/4
90
Max. flow
- Installation of a variable speed 80
45/4-1
pressure
pressure booster system with two 70 8.0 bar
60
fixed setpoints, e.g. high pressure via
50
pressure control and low pressure via 40

limit switch 30
20
10
- Throttling orifices at the lower 0
0 5 10 15 20 25 30 35 40 45 50 55 60 Q [m3/h]
floors.

Fig. 19: Characteristic curve of Hya-Duo D FL 2/4505

18
Fire-fighting water supply
5

5. 5.1
Break tank selection Break tank with a type AB
As per DIN 14462, the effective air gap to DIN EN 1717 and
volume must be established in DIN EN13077
accordance with DIN 1988-500 The break tanks and their
or its operating reliability must be accessories must comply with
demonstrated individually. the hygienic standards
regarding the following:
The effective volume must there-
fore be calculated as follows: – Non-circular overflow to
DIN EN 1717, type AB
Optional: automatic flushing
V BT ≥ 0.03 · Qpeak device with timer to DIN 14462
(9)

where
V BT = Effective volume in m3
Qpeak = Peak flow rate in m3/h

Calculation:
V BT = 0.03 · 18 m3/h = 540 l or
V BT = 0.03 · 36 m3/h = 1080 l

Selected:

Volume flow Total Effective Inlet valve Outlet pipe


rate volume in l volume in l connection connection
18 m³/h 850 600 R1 1/2“ DN 50
36 m³/h 1800 1080 2 x R2“ DN 80

Up to an effective volume From an effective volume


of 600 l = round tank of 800 l = rectangular tank

Fig. 20: Break tank selection

19
6 Fire-fighting water supply

Fig. 21: Hya-Duo D FL with


break tank

6.
Selection chart for auto-
matic flushing device
In order to comply with the
requirements for drinking water
80
hygiene, an automatic flushing
device must be provided for a 1½" solenoid valve
70
branch pipe larger than 10x DN
or a 1.5 l pipe content. 60

50
Selection chart for solenoid
valves 40
Q m3/h
30
Nominal Flow velocity 1" solenoid valve
diameter 20
18
≥ DN 50 min. 0.2 m/s
10 ½" solenoid valve
< DN 50 min. 0.1 m/s
0
At least 3 times the pipe content 0 1 2 3 4 5 6
Pinl [bar]
must be flushed once a week!

Fig. 22: Selection diagram for flushing device

20
Fire-fighting water supply
7

7. repaired these systems must not 9.


Continued use only comply with the Drinking Products offered by KSB
7.1 Water Ordinance, but also meet The following KSB systems can
Excerpt from the Drinking the fire protection requirements. be used for these applications:
Water Ordinance
§ 4 The Drinking Water Hya-Solo D FL
Ordinance requirements are 8. - Fully automatic single-pump
complied with if the generally Log book fire-fighting system
accepted technical rules and the A log book must be kept which - Ready-to-connect package
values as per §§ 5-7 are heeded. documents the fire-fighting system on a common
§§ 5 -6 Microbiological and water system. baseplate
chemical concentrations must
be kept as low as possible in The following should be Hya-Solo D FL Compact
accordance with the accepted documented: - Fully automatic single-pump
technical rules. (§ 7 Indicator break tank packaged booster
parameters) a) Property description: set for fire fighting, modular
property's name and address, design
If the drinking water in the owner(s), operator(s), system
network is stagnating it is not installation contractor, Hya-Duo D FL
possible to meet the permissible authorities, i.e. approval - Fully automatic dual-pump
microbiological and chemical authority/fire protection fire-fighting system with
concentration requirements. authority, water and electricity redundant function
providers. - Ready-to-connect package
7.2 system on a common
Excerpt from DIN 1988- 600 b) Building requirements and baseplate
(translation) planning fundamentals:
Dealing with fire-fighting - Design of fire-fighting water Hya-Duo D FL Compact
systems and fire protection pipes and their fire hose - Fully automatic dual-pump
systems in combination with connection equipment: break tank packaged booster
existing drinking water - Wet-type, wet-/dry-type, dry- set for fire-fighting, with
installations in accordance with type fire-fighting water redundant function, modular
DIN 1988-600. systems; drinking water design
installations with wall
If the Drinking Water hydrants. If the fire-fighting water system
Ordinance requirements are not - Fire-fighting water supply calculations reveal that the
met, the continued-use right for max. permissible flow pressure
a drinking water installation c) Technical documentation: of 8 bar will be exceeded, the
used in combination with a fire- plan of wall hydrants installed; above systems can be equipped
fighting/fire protection system acceptance testing result; with a frequency inverter.
will cease. maintenance and inspection/
If existing systems which do not test certificates; evidence of
comply with the regulations are measures taken for drinking
expanded, refurbished or water protection.

21
22
Annex
Selection of KSB break tank packaged booster sets for fire-fighting

High-rise building Yes > 22m from the ground floor to the highest occupied floor
No < 22m from the ground floor to the highest occupied floor

DW pressure pipe Number of floors: Number from location of fire-fighting system


Flammable material? Floor height: m
Yes Hydrant flow rate: l/min (100 l/min or 200 l/min)
No at at
Please tick where applicable Min. flow pressure: bar (3.0bar or 4.5bar)
at the remotest hydrant
DN50

Number of hydrants: simultaneous

Pipe length: m
DN65

DN

Inlet pressure: bar


DN80

Location of Emergency drainage


fire-fighting system:
Selection of KSB break tank packaged booster set for fire-fighting

above flood level


below flood level
Please tick where applicable
Pipe length up to the
remotest hydrant m
Nominal diameter

above flood below flood


level: sewer level: lifting unit
Fire-fighting water supply
How to order the KSB know-how series

At your request, we will be pleased to send you all KSB know-how volumes previously
published. Ordering is easy.

Just get in touch with us via our web site:

• http://www.ksb.com/ksb-en/contactfinder/
• Choose your country and/or post or ZIP code.
• Simply send an e-mail to the competent sales house or local company, stating the know-how
volumes you require.

You may order the following know-how volumes:

PO number Subject Available languages

• 0101.5 “Selecting Centrifugal Pumps“ DE, EN-UK, FR


• 0101.55 “Water Hammer“ DE, EN-UK
• 0508.023 “BOA-Systronic®“
DE, EN-UK
• 2300.02 “Planning Information for Drainage Installations“ DE, EN-UK
• 2300.024 “Pump Control / System Automation“ DE, EN-UK, FR
• 2300.025 “Planning Information for Pressure Booster Systems“ DE, EN-UK
•0118.55 “Planning Information Amacan® Submersible Pumps in
Discharge Tubes“ DE, EN-UK, EN-US, ES
• 2554.025 “KRT Planning Information“ DE, EN-UK, EN-US, ES
• 2300.023 “Planning Information for Fire-Fighting Systems“ DE, EN-UK

Technology that makes its mark

2300.023-EN / 03.14 / © KSB Aktiengesellschaft 2013 ·Subject to technical modification without prior notice
The KSB-newsletter –
dont‘ miss out, sign up now
www.ksb.com/newsletter

Your contact:

KSB Aktiengesellschaft
Johann-Klein-Straße 9
67227 Frankenthal (Germany)
www.ksb.com

You might also like