Professional Documents
Culture Documents
13
Shares
13
SPONSORED SEARCHES
ASCE 7-10 provides two methods for wind load calculation: a simplified procedure and an analytical procedure.
The simplified procedure is for building with simple diaphragm, roof slope less than 10 degree, mean roof height
less than 30 feet (9 meters), regular shape rigid building, no expansion joints, flat terrain and not subjected to
special wind condition. The analytical procedure is for all buildings and non-building structures. Each
procedure has two categories: wind for main wind force-resisting system (MWFRS) and wind for component
and claddings (C&C).
Since most of our wind design considerations are for buildings other than the simplified procedure stated above,
let us tackled the Analytical Procedure approach that can be applied both for buildings and non-building
structure.
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 1/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
The objective of this article is to help you decide which wind load criteria is appropriate for your design as per
the analytical procedure; here are the summaries of wind load analytical procedure approach as specified in
ASCE 7-10. You are going to need a copy of the ASCE 7-10 code for sections, figures and table references.
SPONSORED SEARCHES
13
qz = 0.613 Kz Kzt Kd V2 (N/m2); V=m/s
where:
Velocity pressure exposure coefficients, Kz are listed Table 27.3-1 of ASCE 7-10 or can be calculated as
Kz = 2.01 (z/zg)2/α
from which, z is the height above ground and should not be less than 15 feet (4.5 meters) except that z shall not
be less than 30 feet (9 meters) for exposure B for low rise building and for component and cladding. The
parameters, α and zg are taken as follows:
B 7 1200 365.76
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 2/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
Kzt = (1 + K1K2K3)2
where:
K1, K2, K3 are determined from Figure 26.8-1 of ASCE 7-10 based on ridge, escarpment and hill. If site
conditions and locations of structures do not meet all the conditions specified in section 26.8.1 then Kzt =1.0
Wind Directionality Factor; Kd shall be determine from Table 26.6-1 and the basic wind speed, V is according to
Figure 26.5-1 of ASCE 7-10.
where:
q = qh for Leeward walls, side walls, and roof evaluated at mean roof height h above ground.
Cp is the external pressure coefficient from Figures 27.4-1, 27.4-2 and 27.4-3 of ASCE 7-10.
Figure 27.4-1 is for gable, hip roof, mono-slope roof, and mansard roof
Enclosed building:
qi = qh evaluated for windward walls, leeward walls, and side walls, and roof.
qi = qh for negative internal pressure, qi= qz for positive internal pressure at height z at the level of highest
opening.
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 3/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
Note: The internal pressure shall be applied simultaneously on windward and leeward walls and both positive
and negative pressures need to be considered. Therefore, it cancels each other for enclosed building except for
roof. For partially enclosed building, internal pressure shall be added to leeward wall at the height of opening.
Wall pressure coefficient Cp for Gable, Hip roof (from figures 27.4-1, 27.4-2 and 27.4-3 of ASCE 7-10):
2 -0.3
≥4 -0.2
13
Shares
Side Wall All values -0.7 qh
where:
Note: For wind pressures at edges and corners of walls and roof are higher than interior zone. Wind pressure at
each zone needs to be calculated separately.
1 2 3 4 1E 2E 3E 4E
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 4/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
1.3 Parapets
The design wind pressure for the effect of parapets on MWFRS of rigid or flexible buildings shall be calculated
as
where
Pp is the combined net pressure on the parapet due to the combination of net pressure from front and back
surfaces; ± signs signify net pressure toward and away from the exterior side of the parapet
13GCpn is combined net pressure coefficient, +1.5 for windward parapet, -1.0 for leeward parapet.
Shares
13
Case 1: Full wind loads in two perpendicular directions considered separately.
Case 2: 75% wind loads in two perpendicular directions with 15% eccentricity considered separately.
Case 4: 56.3% (75%x75%) of wind load in two perpendicular directions with 15% eccentricity
simultaneously.
where:
Figures 30.4-2A to 30.4-2C (flat roofs, gable roofs, and hip roofs)
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 5/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
13
where:
Shares
q = qh for Leeward walls, side walls, and roof evaluated at mean roof height h above ground.
13
qi is internal pressure evaluated as follows:
Enclosed building:
qi = qh evaluated at mean roof height for windward, leeward, and side walls, and roof.
qi = qh for negative internal pressure, qi = qz for positive internal pressure at height z at the level of highest
opening.
Note: The internal pressure shall be applied simultaneously on windward and leeward walls and both positive
and negative pressures need to be considered. Therefore, it cancels each other for enclosed building except for
roof. For partially enclosed building, internal pressure shall be added to leeward wall at the height of opening.
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 6/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
where
Figures 30.4-1, 30.4-2A to 30.4-2C, 30.4-3, 30.4-4, 30.4-5A and 30-5B, 30.4-6, 30.4-7, 30.6-1, 27.4-3
and 27.4-3 (footnote 4).
13
GCpi
Shares is internal pressure coefficient from Table 26.11-1 based on the porosity of the parapet envelope.
Note: Two load cases shall be considered as per Figure 30.9-1 of ASCE 7-10.
P = qhG CN (30.8-1)
where
qh= velocity pressure at mean roof height h using the exposure defined in Section 26.7.3
CN is net pressure coefficients include from top and bottom surfaces given in
To Sum Up:
The above wind load provisions are according to ASCE 7-10 Chapters that Sum Up as follows:
A recommended reference book Guide to the Wind Load Provisions of ASCE 7-10 by Kishor C. Metha and
William L. Coulbourne containing different wind analysis examples problems is worth to try.
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 7/8
4/1/2019 Guide to Wind Load Analytical Procedure of ASCE 7-10 | | The Structural World
What do you think of the above article? Tell us your thoughts! Leave your message in the comment section
below. Feel free to share this article, subscribe to our newsletter and follow us on our social media pages.
SPONSORED SEARCHES
13
https://www.thestructuralworld.com/2019/02/07/guide-to-wind-load-analytical-procedure-of-asce-7-10/ 8/8