You are on page 1of 1

Serial nr.

18010014
TEST REPORT Design FD005001001

Cast Resin Transformer Three-phase Ref. 511.180014

CHARACTERISTICS
(*) Cooling System Primary Secondary
Rating (kVA) 500 500
AN (*)
Current (A) 28,87 721,69
Rating (kVA) 0 0
Current (A) 0,00 0,00
Voltage (V) 10000 0 400 0
MOD 067 (Rev 1) Tappings +2 -2 x 2,5% 0 - 0
Notes Temperature class F F
Temperature rise (K) 100 100
24,0 1,1
Insulation class (kV)
LI 125 AC 50 LI - AC 3
Vector group Dyn5 Freq. (Hz) 60
Altitude service < 1000 m Protection IP00
ROUTINE TESTS
Altitude test <1000 m Standards IEC 60076-11:2004 Tests carried out in IP00
GUARANTEES
Ratio: 10000/400 V Temperature reference: 120 °C
Impedance EFFICIENCY
No-load losses No-load current Load losses Total losses
voltage cos φ
Load
Garanteed values 1450 W 1,20% 6000 W 6,00% 7450 W 0,9 1
Tolerance (%) 15% 30% 15% ± 10,0% 10% 500 kVA
Measured values 1322 W 0,38% - - - 375 kVA
Deviation (%) -8,8% -68,0% - - - 250 kVA
Result Positive Positive - - -
INSULATION TESTS
Induced overvoltage test Separate sourge voltage withstand test

Winding supplied Test voltage Test frequency Duration Result Winding supplied Test voltage Duration Result
Primary 50,0 kV
400 V 800 V 200 Hz 36 '' Positive 60 '' Positive
Secondary 3,0 kV
RESISTANCE MEASUREMENTS (20 °C)
Winding 10000 V Winding 0V Winding 400 V Winding 0V
Phase Ω Phase Ω Phase Ω Phase Ω Room temperature
1U-1V 1,7194 1U-1V 0,0000000 2u-2v 0,002177 3u-3v 0,0000000
1U-1W 1,72 1U-1W 0,0000000 2u-2w 0,0022160 3u-3w 0,0000000
20,0 °C
1V-1W 1,721 1V-1W 0,0000000 2v-2w 0,0021760 3v-3w 0,0000000
PARTIAL DISCHARGES MEASUREMENTS
Un Pre-stress Measure Phase U Phase V Phase W Acceptance level Result
10000 V 18000 V 30 '' 13000 V 3' 2,1 pC 2,6 pC 9,2 pC <10pC Positive
RATIO MEASUREMENTS
(Tolerances: ±0,5% on the guaranteed ratio on all taps)
Ratio 10000 / 400 V. Ratio Ratio Ratio
Tap. step 3,330% Tap. step 0,000% Tap. step 0,000% Tap. step 0,000%
Position Measure Result Position Measure Result Position Measure Result Position Measure Result
0 0 0 0
0 0 0 0
6,660% 46,155 Positive 0,000% 0 0,000% 0 0,000% 0
3,330% 44,754 Positive 0,000% 0 0,000% 0 0,000% 0
0 43,335 Positive 0 0 0
-3,330% 41,925 Positive 0,000% 0 0,000% 0 0,000% 0
-6,660% 40,515 Positive 0,000% 0 0,000% 0 0,000% 0
0 0 0 0
0 0 0 0
DIMENSIONAL CHECK: Dimensions in compliance with the drawing
INSTRUMENTS USED
OHM01 RAP05 TA10 TA11 TA12 TV07 TV08 TV09 MAG02 WBPA02 DMS03
0 0 0 0 0 0 0 0 0
ENVIRONMENTAL, CLIMATIC, FIRE BEHAVIOUR CLASS : E2 - C2 - F1
Signatures for acceptance: Customer: Date

Emmanuel Sahi 05/04/2018