2.6.8.4 The tap changer motor shall operate from a 400V, 3 phase,
50 Hz, supply with 230V single
phase controls and accessories.
2.6.8.5 The remote control panel shall include but not limited
to:
2.6.9 The driving rod through cover or tank wall shall be properly
sealed against air/liquid leakage
under all service conditions.
2.7 CABLE BOXES AND TERMINATION
2.7.1 The cable box and terminals shall be of ample dimension for
accepting the number, type and
size of cable specified on the data sheet.
2.7.5 Where bus duct is specified for the secondary connection, the
terminal box shall be provided
with flange to match up to the busduct which will be provided by
others. The transformer terminals
shall provide a sufficient pre drilled contact area for accepting
flexible connectors, and proper access
shall be provided for making off, or disconnection of, the connections
while the duct remains in place.
Terminal box shall be constructed using bolted steel sheets in such a
way to permit removing any sides
to facilitate flexible connectors connection.