You are on page 1of 12

BOARD OF

CITY OF LOS ANGELES DEPARTMENT OF


BUILDING AND SAFETY CALIFORNIA BUILDING AND SAFETY
COMMISSIONERS 201 NORTH FIGUEROA STREET
LOS ANGELES, CA 90012
___
____
HELENA JUBANY
PRESIDENT
RAYMOND S. CHAN, C.E., S.E.
SUPERINTENDENT OF BUILDING
VAN AMBATIELOS INTERIM GENERAL MANAGER
VICE-PRESIDENT
ERIC GARCETTI
____
E. FELICIA BRANNON MAYOR
VICTOR H. CUEVAS
GEORGE HOVAGUIMIAN

___

HILTI, Inc. RESEARCH REPORT: RR 25901


5400 S. 122 E. Avenue (CSI #03 16 00)
Tulsa, OK 74146
BASED UPON ICC EVALUATION SERVICE
Attn: Tom Haanen REPORT NO. ESR-2302
(918) 872-3731
REEVALUATION DUE
DATE: April 1, 2016
Issued date: March 1, 2014
Code: 2014 LABC

GENERAL APPROVAL – Reevaluation – Hilti Kwik Bolt 3 (KB3) Concrete Anchors.

DETAILS

The above products/assemblies are approved when in compliance with the description,
identification and conditions of use in Report No.ESR-2302, reissued December 1, 2013, of the
ICC Evaluation Service, Incorporated. The report, in its entirety, is attached and made a part of
this general approval.

The parts of Report No.ESR-2302 marked by the asterisks are modified by the Los Angeles
Building Department from this approval.

The approval is subject to the following conditions:

1. The fasteners shall not be used in cracked concrete.

2. The Kwilk Bolt 3 shall not be used to resist seismic loads. The stress increases described
in Section 1605.3.2 of the 2014 LABC are not allowed for wind loads acting alone or
when combined with gravity loads. No increase is allowed for gravity loads acting alone.

RR 25901
Page 1 of 3

LADBS G-5 (Rev.02/20/2014) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER


HILTI, Inc.
RE: Hilti Kwik Bolt 3 (KB3) Concrete Anchors

3. Submit calculation to demonstrate that the applied loads are less than the allowable loads
described in this report. Calculation must be reviewed and approved by the structural plan
check engineer. Calculations must be prepared, sealed and signed by a civil or structural
engineer registered in the State of California.

EXCEPTION: Anchors used for the installation of mechanical, plumbing and


electrical equipment may be designed and detailed on a plan prepared by an
engineer licensed by the state of California.

4. The design loads listed in the attached report and tables are for the anchor bolts only.
Connected members shall be checked for their capacity (which may govern).

5. The concrete shall have attained its minimum design strength prior to installation of the
anchors.

6. Kwik Bolt 3 installed through the underside of steel deck at the ribs and into minimum
3000 psi lightweight concrete shall have minimum edge distance of 7/8" from the edge of
the deck ribs and 6" from the end of the deck. Concrete fill above top ribs shall be a
minimum of 2 1/2 inches.

7. Kwik Bolt 3 shall be installed per the manufacturer's instructions, a copy of which shall be
available at each job site.

8. Use of 5/8” Kwik Bolt 3 is limited to dry interior locations.

9. All Kwik Bolt 3 are identified by an “H” imprinted on the fastener head. Where applicable
the word “Hilti” is stamped on the steel washers. All fasteners are packaged in containers
noting the fastener type, size, manufacturer’s name, and evaluation report number (ESR-
2302).

DISCUSSION

The report is in compliance with the 2014 City of Los Angeles Building Code.

The approval is based on tests in accordance with ICC ES Acceptance Criteria for Mechanical
Anchors in Concrete Elements (AC 193), dated February 2009.

This general approval will remain effective provided the Evaluation Report is maintained valid
and unrevised with the issuing organization. Any revision to the report must be submitted to this
Department for review with appropriate fee to continue the approval of the revised report.

Addressee to whom this Research Report is issued is responsible for providing copies of it,
complete with any attachments indicated, to architects, engineers and builders using items
approved herein in design or construction which must be approved by Department of Building
and Safety Engineers and Inspectors.

RR 25901
Page 2 of 3
ICC-ES Evaluation Report ESR-2302
Reissued December 1, 2013
This report is subject to renewal December 1, 2015.

www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®

DIVISION: 03 00 00—CONCRETE with the manufacturer’s quality documentation, or AISI


Section: 03 16 00—Concrete Anchors Type 304 or 316 stainless steel materials.
The carbon steel anchors are available in diameters of
DIVISION: 05 00 00—METALS 1
/4 inch through 3/4 inch (6.4 mm through 19.1 mm) and an
Section: 05 05 19—Post-Installed Concrete Anchors
example is illustrated in Figure 1 of this report. Carbon
steel KB3 anchors and components have a minimum
REPORT HOLDER:
5-micrometer (0.0002 inch) zinc plating. The expansion
elements (wedges) for the carbon steel anchors are made
HILTI, INC. 1
from carbon steel, except all /4-inch (6.4 mm) anchors and
5400 SOUTH 122ND EAST AVENUE 3
the /4-inch-by-12-inch (19.1 mm by 305 mm) anchor have
TULSA, OKLAHOMA 74146
expansion elements made from AISI Type 316 stainless
(800) 879-8000
steel.
www.us.hilti.com
1 5 3
HiltiTechEng@us.hilti.com The /2-, /8-, and /4-inch-diameter (12.7 mm, 15.9 mm,
and 19.1 mm) carbon steel KB3 anchors are also available
EVALUATION SUBJECT: with a hot-dip galvanized coating. The 1/2- and 3/4-inch-
diameter (12.7 mm and 19.1 mm) anchors with hot-dip
HILTI KWIK BOLT 3 (KB3) CONCRETE ANCHORS galvanized coating comply with ASTM A153. All hot-dip
galvanized anchors use stainless steel expansion
1.0 EVALUATION SCOPE elements (wedges).
Compliance with the following codes: The stainless steel KB3 anchors are available in
*  2012, 2009, 2006 and 2003 International Building diameters of 1/4 inch through 1 inch (6.4 mm through 25.4
®
Code (IBC) mm) and have an anchor body in conformance with AISI
 2012, 2009, 2006 and 2003 International Residential Type 304 or 316. The expansion elements (wedges) of the
* Code® (IRC) AISI Type 304 anchors are in conformance with AISI
Property evaluated: Types 304 or 316 stainless steel. The expansion elements
Structural (wedges) of the AISI Type 316 anchors are in conformance
2.0 USES with AISI Type 316 stainless steel.
The Hilti Kwik Bolt 3 Concrete Anchor (KB3) is used to The anchor body is comprised of a rod threaded at one
resist static, wind and earthquake (Seismic Design end and with a tapered mandrel at the other end. The
Categories A and B only) tension and shear loads in tapered mandrel is enclosed by a three-section expansion
uncracked normal-weight concrete and uncracked sand- element which freely moves around the mandrel. The
lightweight concrete having a specified compressive expansion element movement is restrained by the mandrel
strength, f′c , of 2,500 psi to 8,500 psi (17.2 MPa to 58.6 taper and by a collar. The anchor is installed in a predrilled
MPa). hole with a hammer. When torque is applied to the nut of
The anchoring system complies with anchors as the installed anchor, the mandrel is drawn into the
described in Section 1909 of the 2012 IBC, Section 1912 expansion element, which engages the wall of the drilled
of the 2009 and 2006 IBC and Section 1913 of the 2003 hole. Installation information and dimensions are set forth
* IBC, and is an alternative to cast-in-place anchors in Section 4.3 and Table 1 of this report.
described in Section 1908 of the 2012 IBC, Section 1911 3.2 Concrete:
of the 2009 and 2006 IBC, and Section 1912 of the 2003
* IBC. The anchors may also be used where an engineered Normal-weight concrete and sand-lightweight concrete
design is submitted in accordance with Section R301.1.3 of must comply with Section 1903 and 1905 of the IBC.
the IRC. 4.0 DESIGN AND INSTALLATION
3.0 DESCRIPTION
4.1 Strength Design:
3.1 KB3 Anchors:
The KB3 anchors are torque-controlled, mechanical 4.1.1 General: Design strength of anchors complying
expansion anchors. KB3 anchors consist of a stud (anchor * with the 2012 and 2003 IBC, and the 2012 and 2003 IRC
body), expansion element (wedge), nut, and washer. The must be determined in accordance with ACI 318-11
stud is manufactured from medium carbon steel complying Appendix D and this report.

* Deleted by the City of Los Angeles


ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000

Copyright © 2013 Page 1 of 9


ESR-2302 | Most Widely Accepted and Trusted Page 2 of 9

Design strength of anchors complying with the 2009 IBC Strength reduction factors ϕ corresponding to ductile steel
and 2009 IRC must be in accordance with ACI 318-08 elements are appropriate for stainless steel and carbon
Appendix D and this report. steel elements.
Design strength of anchors complying with the 2006 IBC 4.1.6 Requirements for Static Concrete Breakout
* and 2006 IRC must be in accordance with ACI 318-05 Strength in Shear, Vcb or Vcbg: The nominal static
Appendix D and this report. concrete breakout strength of a single anchor or group of
anchors, Vcb or Vcbg, respectively must be calculated in
Design parameters and nomenclature provided in Tables
accordance with ACI 318 D.6.2, based on the values
3, 4 and 5 of this report are based on the 2012 IBC (ACI
provided in Tables 3 through 5 of this report. The basic
318-11), unless noted otherwise in Sections 4.1.1 through
concrete breakout strength of a single anchor in uncracked
4.1.11 of this report.
concrete, Vb, must be calculated in accordance with ACI
The strength design of anchors must comply with the 318 D.6.2.2 using the values given in Tables 3, 4 and 5.
requirements in ACI 318 D.4.1.1 and D.4.1.2. Strength The value of le used in ACI 318 D.6.2.2, must be no
reduction factors ϕ as given in ACI 318-11 D.4.3 must be greater than the lesser of hef or 8da.
used for load combinations calculated in accordance with
4.1.7 Requirements for Static Concrete Pryout
Section 1605.2 of the IBC and Section 9.2 of ACI 318.
Strength in Shear, Vcp or Vcpg: The nominal static
Strength reduction factors ϕ as given in ACI 318-11 D.4.4
concrete pryout strength of a single anchor or group of
must be used for load combinations calculated in
anchors, Vcp or Vcpg, respectively must be calculated in
accordance with Appendix C of ACI 318. An example
accordance with ACI 318 D.6.3 based on the values given
calculation in accordance with the 2012 IBC is provided in
in Tables 3, 4 and 5 of this report; the value of Ncb or Ncbg
Figure 5. The value of f′c used in calculations must be
is as calculated in Section 4.1.3 of this report.
limited to a maximum of 8,000 psi (55.2 MPa), in
accordance with ACI 318-11 D.3.7. 4.1.8 Requirements for Interaction of Tensile and
Shear Forces: For anchors or groups of anchors that are
4.1.2 Requirements for Static Steel Strength in
subject to the effects of combined tensile and shear forces,
Tension, Nsa: The nominal static steel strength of a single
the design must be determined in accordance with ACI 318
anchor in tension, Nsa, must be calculated in accordance
D.7.
with ACI 318 D.5.1.2. The resulting values of Nsa are
described in Tables 3, 4 and 5 of this report. Strength 4.1.9 Requirements for Critical Edge Distance: In
reduction factors ϕ corresponding to ductile steel elements applications where c < cac and supplemental reinforcement
are appropriate for stainless steel and carbon steel to control splitting of the concrete is not present, the
elements. concrete breakout strength in tension for uncracked
concrete, calculated according to ACI 318 D.5.2, must be
4.1.3 Requirements for Static Concrete Breakout
further multiplied by the factor ψcp,N given by the following
Strength in Tension, Ncb or Ncbg: The nominal static
concrete breakout strength of a single anchor or group of equation:
anchors in tension, Ncb or Ncbg, respectively must be c
calculated in accordance with ACI 318 D.5.2, with
ψcp,N = (Eq-2)
cac
modifications as described in this section. The values of f′c
where the factor ψcp,N need not be taken as less
must be limited to 8,000 psi (55.2 MPa) in accordance with
1.5hef
ACI 318-11 D.3.7. The nominal concrete breakout strength than . For all other cases, ψcp,N = 1.0. In lieu of ACI
cac
in tension in regions of concrete where analysis indicates 318 D.8.6, values of cac provided in Table 1 of this report
no cracking at service loads, must be calculated in must be used.
accordance with ACI 318 D.5.2.6 with Ψc,N = 1.0. The basic
concrete breakout strength of a single anchor in tension, 4.1.10 Requirements for Minimum Member Thickness,
Nb, must be calculated in accordance with ACI 318 D.5.2.2 Minimum Anchor Spacing and Minimum Edge
using the values of hef and kuncr as given in Tables 3, 4, Distance: In lieu of ACI 318 D.8.1 and D.8.3, values of smin
and 5 in lieu of hef and kc, respectively. and cmin as given in Tables 3, 4 and 5 of this report must
be used. In lieu of ACI 318 D.8.5, minimum member
4.1.4 Requirements for Static Pullout Strength in thicknesses hmin as given in Tables 3, 4 and 5 of this report
Tension, Np: The nominal static pullout strength, Np,uncr of must be used. Additional combinations for minimum
a single anchor installed in uncracked concrete (regions edge distance cmin and spacing smin may be derived by
where analysis indicates no cracking in accordance with linear interpolation between the given boundary values.
ACI 318 D.5.3.6), where applicable, is given in Tables 3, 4 (See Figure 3.)
and 5 of this report. The nominal pullout strength in tension
may be adjusted for concrete compressive strengths other 4.1.11 Sand-lightweight Concrete: For ACI 318-11 and
than 2,500 psi according to the following equation: ACI 318-08, when anchors are used in sand-lightweight
concrete, the modification factor λa or λ, respectively, for
Np,f′c = Np,uncr f c′ (lb, psi) (Eq-1) concrete breakout strength must be taken as 0.6. In
2,500 addition, the pullout strength Np,uncr must be multiplied by
0.6, in lieu of ACI 318 Section D.3.6 (2012 IBC) or ACI 318
Np,f′c = Np,uncr f c′ (N, MPa) Section D.3.4 (2009 IBC).
17.2 For ACI 318-05, when anchors are used in sand-
Where values for Np,uncr are not provided in Table 3, 4, or lightweight concrete, Nb, Np,uncr, Vb and Vcp must be
5 of this report, the pullout strength in tension need not be multiplied by 0.60, in lieu of ACI 318 D.3.4.
evaluated. 4.2 Allowable Stress Design:
4.1.5 Requirements for Static Steel Strength in Shear, 4.2.1 Design values for use with allowable stress design
Vsa: In lieu of the value of Vsa as given in ACI 318 D.6.1.2, load combinations calculated in accordance with Section
the nominal static steel strength in shear of a single anchor 1605.3 of the IBC, must be established using the equations
given in Tables 3, 4 and 5 of this report must be used. below:
* Deleted by the City of Los Angeles
ESR-2302 | Most Widely Accepted and Trusted Page 3 of 9
ϕNn anchor installation to verify anchor type, anchor
Tallowable,ASD = (Eq-3)
α dimensions, concrete type, concrete compressive strength,
ϕVn drill bit type, hole dimensions, hole cleaning procedure,
Vallowable,ASD = (Eq-4) concrete member thickness, anchor embedment, anchor
α
spacing, edge distances, anchor embedment, tightening
where: torque and adherence to the manufacturer’s printed
Tallowable,ASD = Allowable tension load (lbf or kN). installation instructions. The special inspector must be
present as often as required in accordance with the
Vallowable,ASD = Allowable shear load (lbf or kN). “statement of special inspection.” Under the IBC, additional
φNn = Lowest design strength of an anchor or requirements as set forth in Sections 1705, 1706 and 1707
anchor group in tension as determined in must be observed, where applicable.
accordance with ACI 318 D.4.1, and 2009 5.0 CONDITIONS OF USE
IBC Section 1908.1.9 or 2006 IBC Section
1908.1.16, as applicable (lbf or N). The Hilti Kwik Bolt 3 (KB3) anchors described in this report
comply with, or are suitable alternatives to what is
φVn = Lowest design strength of an anchor or specified in, those codes listed in Section 1.0 of this report,
anchor group in shear as determined in subject to the following conditions:
accordance with ACI 318 D.4.1, and 2009
IBC Section 1908.1.9 or 2006 IBC Section 5.1 KB3 anchor sizes, dimensions, minimum embedment
1908.1.16, as applicable (lbf or N). depths, and other installation parameters are as set
forth in this report.
α = Conversion factor calculated as a weighted
5.2 The KB3 anchors must be installed in accordance
average of the load factors for the
with the manufacturer’s (Hilti) published instructions
controlling load combination. In addition, α
and this report in uncracked normal-weight concrete
must include all applicable factors to and uncracked sand-lightweight concrete having a
account for nonductile failure modes and specified compressive strength f′c = 2,500 psi to 8,500
required over-strength. psi (17.2 MPa to 58.6 MPa). In case of conflict
The requirements for member thickness, edge distance between the manufacturer’s instructions and this
and spacing, described in this report, must apply. An report, this report governs.
example of allowable stress design values for illustrative 5.3 The values of f′c used for calculation purposes must
purposes is shown in Table 6. not exceed 8,000 psi (55.2 MPa).
4.2.2 Interaction of Tensile and Shear Forces: The 5.4 Strength design values are established in accordance
interaction of tension and shear loads must be consistent with Section 4.1 of this report.
with ACI 318 D.7 as follows:
5.5 Allowable stress design values are established in
For shear loads Vapplied ≤ 0.2Vallowable,ASD, the full accordance with Section 4.2 of this report.
allowable load in tension Tallowable,ASD may be used.
5.6 Anchor spacing, edge distance and minimum member
For tension loads Tapplied ≤ 0.2Tallowable,ASD, the full thickness must comply with Tables 3 , 4 and 5 of this
allowable load in shear Vallowable,ASD may be used. report.
For all other cases: 5.7 Prior to installation, calculations and details
demonstrating compliance with this report must be
+ ≤1.2 submitted to the code official for approval. The
Tallowable,ASD Vallowable,ASD
calculations and details must be prepared by a
(Eq-5)
registered design professional where required by the
4.3 Installation: statutes of the jurisdiction in which the project is to be
constructed.
Installation parameters are provided in Table 1 and Figure
2. Anchor locations must comply with this report and the 5.8 Since an ICC-ES acceptance criteria for evaluating
plans and specifications approved by the code official. data to determine the performance of expansion
Anchors must be installed in accordance with the anchors subjected to fatigue or shock loading is
manufacturer's published installation instructions and this unavailable at this time, the use of these anchors
report. In case of conflict, this report governs. Embedment, under such conditions is beyond the scope of this
spacing, edge distance, and concrete thickness are report.
provided in Tables 3, 4 and 5 of this report. Holes must be 5
5.9 Use of carbon steel anchors and hot-dipped /8-inch
drilled using carbide-tipped masonry drill bits complying
(15.9 mm) galvanized KB3 anchors is limited to dry,
with ANSI B212.15-1994. The nominal drill bit diameter
interior locations.
must be equal to that of the anchor. Prior to installation,
dust and debris must be removed from the drilled hole to 5.10 Use of KB3 anchors in structures assigned to Seismic
enable installation to the stated embedment depth. The Design Category C, D, E or F (IBC) is beyond the
anchor must be hammered into the predrilled hole until at scope of this report. Anchors may be used to resist
least four threads are below the fixture surface. The nut short-term loading due to wind forces, subject to the
must be tightened against the washer until the torque conditions of this report.
value, Tinst, specified in Table 1 is achieved.
5.11 Special inspection must be provided in accordance
4.4 Special Inspection: with Section 4.4 of this report.
Periodic special inspection is required in accordance with 5.12 Where not otherwise prohibited in the code, KB3
Section 1705.1.1 of the 2012 IBC, Section 1704.15 of the anchors are permitted for use with fire-resistance-
* 2009 IBC or Section 1704.13 of the 2006 or 2003 IBC. The rated construction provided that at least one of the
special inspector must make periodic inspections during following conditions is fulfilled:
* Deleted by the City of Los Angeles
ESR-2302 | Most Widely Accepted and Trusted Page 4 of 9

 Anchors are used to resist wind forces only. 6.0 EVIDENCE SUBMITTED
 Anchors that support fire-resistance-rated Data in accordance with the ICC-ES Acceptance Criteria
construction or gravity load bearing structural for Mechanical Anchors in Concrete Elements (AC193),
elements are within a fire-resistance-rated dated March 2012; and quality control documentation.
envelope or a fire-resistance-rated membrane,
7.0 IDENTIFICATION
are protected by approved fire-resistance-rated
materials, or have been evaluated for resistance to The concrete anchors are identified in the field by their
fire exposure in accordance with recognized dimensional characteristics, size, and the length code
standards. stamped on the anchor, as indicated in Table 2. Packages
are identified with the manufacturer’s name (Hilti, Inc.) and
 Anchors are used to support nonstructural address, anchor name, anchor size, evaluation report
elements. number (ESR-2302), and the name of the inspection
5.13 The anchors are manufactured by Hilti AG with quality agency (UL LLC).
control inspections by UL LLC (AA-668).

TABLE 1—INSTALLATION INFORMATION

Nominal anchor diameter


Setting Information Symbol 1 3 1 5 3
/4 /8 /2 /8 /4 1
in. 0.250 0.375 0.500 0.625 0.750 1.000
Anchor O.D. do
(mm) (6.4) (9.5) (12.7) (15.9) (19.1) (25.4)
1 3 1 5 3
in. /4 /8 /2 /8 /4 1
ANSI drill bit dia dbit
(mm) (6.4) (9.5) (12.7) (15.9) (19.1) (25.4)
1 1 1 3 3
Effective min. in. 1 /2 2 2 3 /4 3 /8 4 3 /4 5 4 5 /4
hef
embedment (mm) (38) (51) (51) (83) (79) (102) (95) (127) (102) (146)
5 5 7 3 1 3 3
in. 2 2 /8 2 /8 4 3 /8 4 /4 4 /2 5 /4 5 6 /4
Min. hole depth hhole
(mm) (51) (67) (67) (102) (98) (121) (114) (146) (127) (171)
ft-lb 4 20 40 60 110 150
Installation torque Tinst
(Nm) (5) (27) (54) (81) (149) (203)
5 7 9 11 13 1
Expansion element in. /16 /16 /16 /16 /16 1 /8
dh
clearance hole (mm) (7.9) (11.1) (14.3) (17.5) (20.6) (28.6)

TABLE 2—LENGTH IDENTIFICATION SYSTEM

Length marking on the


bolt head A B C D E F G H I J K L M N O P Q R S

Length of From 11 / 2 2 21 / 2 3 31 / 2 4 41 / 2 5 51 / 2 6 61 / 2 7 71 / 2 8 81 / 2 9 91 / 2 10 11
anchor
Up to but not
(in.) 2 21 / 2 3 31 / 2 4 41 / 2 5 51 / 2 6 61 / 2 7 71 / 2 8 81 / 2 9 91 / 2 10 11 12
including

FIGURE 1—HILTI CARBON STEEL KWIK BOLT 3 (KB3) FIGURE 2—KB3 INSTALLED
ESR-2302 | Most Widely Accepted and Trusted Page 5 of 9

TABLE 3—DESIGN INFORMATION CARBON STEEL KB3

Nominal anchor diameter


DESIGN INFORMATION Symbol Units 1 3 1 5 3
/4 /8 /2 /8 /4
7
in. 0.250 0.375 0.500 0.625 0.750
Anchor O.D. da (d0)
(mm) (6.4) (9.5) (12.7) (15.9) (19.1)
1 1 1 3
1 in. 1 /2 2 2 3 /4 3 /8 4 3 /4 5
Effective min. embedment hef
(mm) (38) (51) (51) (83) (79) (102) (95) (127)
in. 4 4 5 4 6 6 8 5 6 8 6 8 8
Min. member thickness hmin
(mm) (102) (102) (127) (102) (152) (152) (203) (127) (152) (203) (152) (203) (203)
3 1 7 7 5 3 5 1 1 1 3 1 1
in. 2 /4 4 /2 3 /8 4 /8 3 /8 6 /4 5 /8 7 /2 9 /2 7 /2 9 /4 7 /2 9 /2
Critical edge distance cac
(mm) (70) (114) (98) (124) (92) (171) (143) (191) (241) (191) (248) (191) (241)
3 1 1 5 5 1 3 3 3 5 1
in. 1 /8 2 1 /2 2 /8 2 1 /8 1 /8 2 /4 1 /4 1 /4 2 /4 2 /8 2 /2
cmin
(mm) (35) (51) (38) (54) (51) (41) (41) (57) (44) (44) (70) (67) (64)
Min. edge distance 3 7 1 7 3 1 1 3 7 1 3
in. 1 /4 2 /8 3 /2 4 /8 4 /4 4 /4 4 5 /4 4 /4 4 6 /8 6 /2 6 /8
for s ≥
(mm) (44) (73) (89) (124) (121) (108) (102) (133) (121) (102) (175) (165) (162)
1 3 3 1 1 7 3 1 1 3 3 1
in. 1 /4 1 /4 1 /4 2 /2 2 /4 2 1 /8 2 /8 2 /8 2 /8 3 /4 3 /8 3 /4
smin
(mm) (32) (44) (44) (64) (57) (51) (48) (60) (54) (54) (95) (86) (83)
Min. anchor spacing 5 3 3 5 3 1 1 3 1 3 3 3
in. 1 /8 2 /8 2 /8 2 /8 2 /8 2 /4 2 3 /8 2 /8 2 /4 3 /4 3 /8 3 /8
for c ≥
(mm) (41) (60) (60) (67) (60) (57) (51) (79) (60) (57) (95) (86) (86)
5 5 7 3 1 3
in. 2 2 /8 2 /8 4 3 /8 4 /4 4 /2 5 /4
Min. hole depth in concrete hhole
(mm) (51) (67) (67) (102) (98) (121) (114) (146)
psi 84,800 84,800 84,800 84,800 84,800
Min. specified yield strength fya 2
(N/mm ) (585) (585) (585) (585) (585)
psi 106,000 106,000 106,000 106,000 106,000
Min. specified ult. strength futa 2
(N/mm ) (731) (731) (731) (731) (731)
2
in 0.02 0.06 0.11 0.17 0.24
Effective tensile stress area Ase 2
(mm ) (12.9) (38.7) (71.0) (109.7) (154.8)
lb 2,120 6,360 11,660 18,020 25,440
Steel strength in tension Nsa
(kN) (9.4) (28.3) (51.9) (80.2) (113.2)
lb 1,640 4,470 6,635 6,750 12,230 15,660 16,594
Steel strength in shear Vsa
(kN) (7.3) (19.9) (29.5) (30.0) (54.4) (69.7) (73.8)
Pullout strength uncracked lb 1,575 6,800 10,585
2 Np,uncr NA NA NA NA
concrete (kN) (7.0) (30.2) (47.1)
3 1
Anchor category 1,2 or 3 -
Effectiveness factor kuncr
4 kuncr - 24
uncracked concrete
Modification factor for
Ψc,N - 1.0
uncracked concrete
Coefficient for pryout kcp - 1.0 2.0
ft*lb 4 20 40 60 110
Installation torque Tinst
(Nm) (5) (27) (54) (81) (149)
Axial stiffness in service
β uncr (lb/in) 116,150 162,850 203,500 191,100 222,150 170,700 207,400 164,000
load range
COV βuncr % 60 42 29 29 25 21 19 24
Strength reduction factor ϕ for tension, steel
5 0.75
failure modes
Strength reduction factor ϕ for shear, steel
5 0.65
failure modes
Strength reduction factor ϕ for tension, concrete
6 0.65
failure modes, Condition B
Strength reduction factor ϕ for shear, concrete
6 0.70
failure modes, Condition B
For SI: 1 inch = 25.4 mm, 1lbf = 4.45 N, 1 psi = 0.006895 MPa. For pound-in units: 1 mm = 0.03937 inches.
1
See Fig. 2
2
See Section 4.1.4 of this report, NA (not applicable) denotes that this value does not govern for design.
3
See ACI 318-11 D.4.3.
4
See ACI 318-11 D.5.2.2.
5
The carbon Steel KB3 is a ductile steel element as defined by ACI 318 D.1.
6
For use with the load combinations of ACI 318 Section 9.2 or IBC Section 1605.2. Condition B applies where supplementary reinforcement
in conformance with ACI 318-11 D.4.3 is not provided, or where pull-out or pry out strength governs. For cases where the presence of
supplementary reinforcement can be verified, the strength reduction factors associated with Condition A may be used.
7
The notation in parenthesis is for the 2006 IBC.
ESR-2302 | Most Widely Accepted and Trusted Page 6 of 9

TABLE 4—DESIGN INFORMATION STAINLESS STEEL KB3

DESIGN Nominal anchor diameter


Symbol Units
INFORMATION 1
/4
3
/8
1
/2
5
/8
3
/4 1

7
in. 0.25 0.375 0.500 0.625 0.750 1.000
Anchor O.D. da (d0)
(mm) (6.4) (9.5) (12.7) (15.9) (19.1) (25.4)
1 1 1 3 3
Effective min. in. 1 /2 2 2 3 /4 3 /8 4 3 /4 5 4 5 /4
1 hef
embedment (mm) (38) (51) (51) (83) (79) (102) (95) (127) (102) (146)
Minimum member in. 4 4 5 4 6 6 8 5 6 8 6 8 8 8 10
hmin
thickness (mm) (102) (102) (127) (102) (152) (152) (203) (127) (152) (203) (152) (203) (203) (203) (254)
3 7 7 3 3 3 1 1 1 1 3
in. 3 4 /8 3 /8 4 /8 4 6 /4 5 /4 7 /8 9 /2 7 /2 10 /2 9 /4 9 /4 10 11
Critical edge distance cac
(mm) (76) (111) (98) (124) (102) (171) (146) (187) (241) (191) (267) (235) (248) (254) (279)
3 5 1 7 5 5 1 1 1 1 7 1
in. 1 /8 2 1 /8 2 /2 1 /8 1 /8 1 /8 3 /4 2 /2 2 /2 3 /4 3 2 /8 3 /2 3
cmin
(mm) (35) (51) (41) (64) (48) (41) (41) (83) (64) (64) (83) (76) (73) (89) (76)
Min. edge distance 3 5 5 1 1 5 1 7 5 3 3
in. 1 /4 4 3 /8 5 4 /8 4 /2 4 /4 5 /8 5 /4 5 7 6 /8 6 /8 6 /4 6 /4
for s ≥
(mm) (44) (102) (92) (127) (117) (114) (108) (143) (133) (127) (178) (175) (168) (172) (172)
1 3 1 1 1 7 1 1 1 1 1 3
in. 1 /4 2 1 /4 2 /2 2 /4 2 /8 1 /8 3 /8 2 /8 2 /8 4 3 /2 3 /2 5 4 /4
smin
(mm) (32) (51) (44) (64) (57) (54) (48) (79) (54) (54) (102) (89) (89) (127) (121)
Min. anchor spacing 5 1 1 7 3 3 1 7 3 1 3 3 1 3
in. 1 /8 3 /4 2 /2 2 /8 2 /8 2 /8 2 /8 3 /8 3 2 /4 4 /8 3 /4 3 /4 4 /4 3 /4
for c ≥
(mm) (41) (83) (64) (73) (60) (60) (54) (98) (76) (70) (105) (95) (95) (108) (95)
5 5 7 3 1 3 3
Min. hole depth in in. 2 2 /8 2 /8 4 3 /8 4 /4 4 /2 5 /4 5 6 /4
hhole
concrete (mm) (51) (67) (67) (102) (98) (121) (114) (146) (127) (171)
Min. specified yield psi 92,000 92,000 92,000 92,000 76,000 76,000
fya 2
strength (N/mm ) (634) (634) (634) (634) (524) (524)
Min. specified ult. psi 115,000 115,000 115,000 115,000 90,000 90,000
futa 2
strength (N/mm ) (793) (793) (793) (793) (621) (621)
2
Effective tensile stress in 0.02 0.06 0.11 0.17 0.24 0.47
Ase 2
area (mm ) (12.9) (38.7) (71.0) (109.7) (154.8) (303.2)
lb 2,300 6,900 12,650 19,550 21,600 42,311
Steel strength in tension Nsa
(kN) (10.2) (30.7) (56.3) (87.0) (96.1) (188.2)
lb 1,680 4,980 4,195 6,940 8,955 14,300 11,900 23,545 12,510 27,345
Steel strength in shear Vsa
(kN) (7.5) (22.2) (18.7) (30.9) (39.8) (63.6) (52.9) (104.7) (55.6) (121.6)

Pullout strength lb 1,325 2,965 3,310 6,030 6,230 7,830 8,555 10,830 15,550
2 Np,uncr NA
uncracked concrete (kN) (5.9) (13.2) (14.7) (26.8) (27.7) (34.8) (38.1) (48.2) (69.2)
3
Anchor category 1,2 or 3 - 2 1
Effectiveness factor for
4 kuncr - 24
uncracked concrete
Modification factor for
Ψc,N - 1.0
uncracked concrete

Coefficient for pryout kcp - 1.0 2.0

ft*lb 4 20 40 60 110 150


Installation torque Tinst
(Nm) (5) (27) (54) (81) (149) (203)
Axial stiffness in service
β uncr (lb/in) 57,400 158,300 154,150 77,625 227,600 189,200 275,600 187,000 126,400 174,800
load range

COV βuncr % 40 34 36 17 31 22 35 21 38 22
Strength reduction factor ϕ for tension,
5 0.75
steel failure modes
Strength reduction factor ϕ for shear,
5 0.65
steel failure modes
Strength reduction factor ϕ for tension,
6 0.55 0.65
concrete failure modes, Condition B
Strength reduction factor ϕ for shear,
6 0.70
concrete failure modes, Condition B
For SI: 1 inch = 25.4 mm, 1lbf = 4.45 N, 1 psi = 0.006895 MPa. For pound-in units: 1 mm = 0.03937 inches.
1
See Fig. 2
2
See Section 4.1.3 of this report, NA (not applicable) denotes that this value does not govern for design.
3
See ACI 318-11 Section D.4.3.
4
See ACI 318-11 Section D.5.2.2.
5
The Stainless Steel KB3 is a ductile steel element as defined by ACI 318 D.1.
6
For use with the load combinations of ACI 318 Section 9.2 or IBC Section 1605.2.1. Condition B applies where supplementary reinforcement
in conformance with ACI 318-11 Section D.4.3 is not provided, or where pull-out or pry out strength governs. For cases where the presence of supplementary
reinforcement can be verified, the strength reduction factors associated with Condition A may be used.
7
The notation in parenthesis is for the 2006 IBC.
ESR-2302 | Most Widely Accepted and Trusted Page 7 of 9

TABLE 5—DESIGN INFORMATION HOT-DIP GALVANIZED KB3

DESIGN Nominal anchor diameter


Symbol Units
INFORMATION 1
/2
5
/8
3
/4
7
in. 0.500 0.625 0.750
Anchor O.D. da (d0)
(mm) (12.7) (15.9) (19.1)
1 1 3
Effective min. in. 2 3 /4 3 /8 4 3 /4 5
1 hef
embedment (mm) (51) (83) (79) (102) (95) (127)
Min. member in. 4 6 6 8 5 6 8 6 8 8
hmin
thickness (mm) (102) (152) (152) (203) (127) (152) (203) (152) (203) (203)
7 5 1 3 5 1 3 3 1 1
in. 4 /8 3 /8 7 /2 5 /4 7 /8 9 /2 7 /4 9 /4 7 /2 9 /2
Critical edge distance ccr
(mm) (124) (92) (191) (146) (194) (241) (197) (248) (191) (241)
1 5 1 7 1 5
in. 3 /4 2 /8 2 2 /4 2 1 /8 3 /2 3 /8
cmin
(mm) (83) (67) (51) (57) (51) (48) (89) (92)
Min. edge distance 1 1 7 1 3 1 3
in. 6 /4 5 /2 4 /8 5 /4 5 4 /4 7 /2 7 /8
for s ≥
(mm) (159) (140) (124) (133) (127) (121) (191) (187)
1 3 3 1 1 1 1 7
in. 3 /8 2 /4 2 /8 2 /8 2 /2 2 /8 2 /8 4 3 /8
smin
(mm) (79) (70) (60) (54) (64) (54) (54) (102) (98)
Min. anchor spacing 3 3 5 1 1 1 1 1 3
in. 3 /4 2 /4 2 /8 2 /4 3 /2 2 /2 2 /4 6 /2 4 /4
for c ≥
(mm) (95) (70) (67) (57) (89) (64) (57) (165) (121)
5 7 3 1 3
Min. hole depth in in. 2 /8 4 3 /8 4 /4 4 /2 5 /4
hhole
concrete (mm) (67) (102) (98) (121) (114) (146)
Min. specified yield psi 84,800 84,800 84,800
fya 2
strength (N/mm ) (585) (585) (585)
Min. specified ult. psi 106,000 106,000 106,000
futa 2
strength (N/mm ) (731) (731) (731)
2
Effective tensile stress in 0.11 0.17 0.24
Ase 2
area (mm ) (71.0) (109.7) (154.8)
Steel strength in lb 11,660 18,020 25,440
Nsa
tension (kN) (51.9) (80.2) (113.2)
lb 4,500 5,870 11,635 17,000
Steel strength in shear Vsa
(kN) (20.0) (26.1) (51.8) (75.6)
Pullout strength lb 6,540 6,465 9,017 10,175
2 Np,uncr NA NA
uncracked concrete (kN) (29.1) (28.8) (40.1) (45.3)
5
Anchor category 1,2 or 3 - 1
Effectiveness factor
kuncr uncracked kuncr - 24
4
concrete
Modification factor for
Ψc,N - 1.0
uncracked concrete
Coefficient for pryout kcp - 1.0 2.0

ft*lb 40 60 110
Installation torque Tinst
(Nm) (54) (81) (149)
Axial stiffness in
β uncr (Nm) 177,000 332,850 347,750 190,130 364,725 314,650
service load range
COV βuncr % 42 18 37 36 27 21
Strength reduction factor ϕ for tension,
5 0.75
steel failure modes

Strength reduction factor ϕ for shear,


5 0.65
steel failure modes
Strength reduction factor ϕ for tension,
8 0.65
concrete failure modes, Condition B
Strength reduction factor ϕ for shear,
8 0.70
concrete failure modes, Condition B
For SI: 1 inch = 25.4 mm, 1lbf = 4.45 N, 1 psi = 0.006895 MPa. For pound-in units: 1 mm = 0.03937 inches.
1
See Fig. 2
2
See Section 4.1.4 of this report, NA (not applicable) denotes that this value does not govern for design.
3
See ACI 318-11 Section D.4.3.
4
See ACI 318-11 Section D.5.2.2.
5
The carbon Steel KB3 is a ductile steel element as defined by ACI 318 D.1.
6
For use with the load combinations of ACI 318 Section 9.2 or IBC Section 1605.2.1. Condition B applies where supplementary reinforcement
in conformance with ACI 318-11 Section D.4.3 is not provided, or where pull-out or pry out strength governs. For cases where the presence of
supplementary reinforcement can be verified, the strength reduction factors associated with Condition A may be used.
7
The notation in parenthesis is for the 2006 IBC.
ESR-2302 | Most Widely Accepted and Trusted Page 8 of 9

TABLE 6—EXAMPLE ALLOWABLE STRESS DESIGN VALUES FOR ILLUSTRATIVE PURPOSES

Allowable tension (lbf)


Nominal Anchor diameter Embedment f'c=2500 psi
(in.) depth (in.)
HDG
Carbon Steel Stainless Steel
1 1
/4 1 /2 692 492
3
/8 2 1,491 1,370
1
2 1,491 1,537 1,490
/2 1
3 /4 3,026 2,784 2,870
1
5
3 /8 2,911 2,893 2,840
/8
4 4,216 3,439 4,120
3
3
3 /4 3,827 3,757 3,830
/4
5 5,892 4,756 4,470
4 4,216
1 3
5 /4 6,829
For SI: 1 lbf = 4.45 N, 1 psi = 0.00689 MPa 1 psi = 0.00689 MPa. 1 inch = 25.4 mm.
1
Single anchors with static tension load only.
2
Concrete determined to remain uncracked for the life of the anchorage.
3
Load combinations from ACI 318 Section 9.2 (no seismic loading).
4
30% dead load and 70% live load, controlling load combination 1.2D + 1.6 L.
5
Calculation of the weighted average for α = 0.3*1.2 + 0.7*1.6 = 1.48
6
f'c = 2,500 psi (normal weight concrete)
7
ca1 = ca2 ≥ cac
8
h ≥ hmin
9
Values are for Condition B (Supplementary reinforcement in accordance with ACI 318-11 D.4.3 is not provided).

FIGURE 3—INTERPOLATION OF MINIMUM EDGE DISTANCE AND ANCHOR SPACING (SEE TABLES 3, 4 AND 5)
ESR-2302 | Most Widely Accepted and Trusted Page 9 of 9

Given:
2 – 1/2-in. KB3 carbon steel anchors under static
tension load as shown.
hef = 3.25 in.
Normal wt. concrete, f’c = 3,000 psi
No supplementary reinforcing.
Assume uncracked concrete.
Condition B per ACI 318-11 D.4.3(c)

Calculate the allowable tension load for this


configuration.

Code Report
Calculation per ACI 318-11 Appendix D and this report.
Ref. Ref.
Step 1. Calculate steel strength of anchor in tension
D.5.1.2 Table 3
N sa = nA se f uta = 2 x 0.11 x 106,000 = 23,320 lb

§ 4.1.2
Step 2. Calculate steel capacity ΦNsa = 0.75 x 23,320 = 17,490 lb D.4.3 (a)
Table 3

Step 3. Calculate concrete breakout strength of anchor in tension


A Nc
N cbg = ψ ec, Nψ ed , Nψ c , Nψ cp, N Nb D.5.2.1 § 4.1.3
A Nco
Step 3a. Verify minimum member thickness, spacing and edge distance:
§ 4.1.10
hmin = 6 in. ≤ 6 in. ∴ ΟΚ D.8
Table 3
From Table 3; ca,min = 1.625-in. when s ≥ 4.25-in. ∴ ΟΚ

Step 3b. Check 1.5*hef = 1.5*(3.25) = 4.88 in. > c 3.0*hef = 3.0*(3.25) = 9.75 in. > s D.5.2.1 Table 3

Step 3c. Calculate ANco and ANc for the anchorage: = 9ℎ = 9 × (3.25) = 95.1
D.5.2.1 Table 3
A Nc = (1.5h ef + c)(3h ef + s) = [1.5x(3.25) + 4 ]× [3x(3.25) + 6 ] = 139.8 in < 2 xANc 0 ∴ OK
2

Step 3d. Calculate Ψec,N: en’ = 0: Ψec,N = 1.0 D.5.2.4 -

N b = k uncr λa f'c h ef
1.5
Step 3e. Calculate Nb:
D.5.2.2 Table 3
Nb = 24 × 1.0 × 3000 × 3.251.5 = 7,702 lb
Ψ

4
Step 3f. Calculate modification factor for edge distance: ed,N = 0 .7 + 0 .3 = 0.95 D.5.2.5 Table 3
1.5( 3.25 )

Step 3g. Calculate modification factor for splitting:


max c a,min : 1.5 xh ef max 4 : 1.5 x3.25 § 4.1.9
D.5.2.7
ψ cp,N = = = 0.72 Table 3
c ac 6.75

Step 3h. Calculate Ncbg:


§ 4.1.3
139 .8 D.5.2.1
N cbg = x1.0 x 0.95 x1.0 x 0.72 x 7,702 = 7,744 lb Table 3
95 .1

3000
Step 4. Check pullout strength: Per Table 3, N p,uncr = 2x6890 x = 15,095 lb § 4.1.4
2500 D.5.3.2
Table 3
does not control

Step 5. Controlling strength: ΦNcbg = 0.65 x 7,744 lb = 5,034 lb, controls D.4.3 (c) Table 3

5,034
Step 6. Convert value to ASD: Tallow = = 3,401 lb
1.48 - § 4.2

FIGURE 5—DESIGN EXAMPLE

You might also like