You are on page 1of 49

APPLICATION NOTES

Interfacing DEIF equipment to governors and


AVRs
● Commissioning
● Governor and AVR interfaces
● Troubleshooting

DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com
isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com Document no.: 4189340670C
14 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com SW version:
Interfacing DEIF equipment, application
notes 4189340670 UK

1. Delimitation
1.1. Scope of application notes Interfacing DEIF equipment to governors and AVRs..................................4

2. General information
2.1. Warnings, legal information and safety..................................................................................................5
2.1.1. Warnings and notes ......................................................................................................................5
2.1.2. Legal information and disclaimer ..................................................................................................5
2.1.3. Safety issues ................................................................................................................................5
2.1.4. Electrostatic discharge awareness ...............................................................................................5
2.1.5. Factory settings ............................................................................................................................5
2.2. About the Application Notes...................................................................................................................6
2.2.1. General purpose ...........................................................................................................................6
2.2.2. Intended users ..............................................................................................................................6
2.2.3. Contents and overall structure ......................................................................................................6

3. Abbreviations and names


4. General comments regarding adjustment of governors and AVRs
4.1. DEIF PI step regulators..........................................................................................................................8
4.2. DEIF PI analogue output regulators.......................................................................................................8

5. Commissioning
5.1. The prime mover and generator.............................................................................................................9
5.2. Speed droop on speed governor............................................................................................................9
5.3. Voltage droop on AVR............................................................................................................................9
5.4. Initial setting of speed governor/AVR.....................................................................................................9
5.4.1. With relay output(s) directly connected..........................................................................................9
5.4.2. With analogue output.....................................................................................................................9
5.4.3. With Multi-line 2 PPU/PPM/GPC/AGC PWM output for Caterpillar®..........................................10
5.5. Adjusting DEIF controllers....................................................................................................................10
5.5.1. Delomatic/PPU/PPM/GPC/AGC/AGC 200/BGC.........................................................................10
5.5.2. Analogue output PI......................................................................................................................10
5.5.3. Relay output PI step....................................................................................................................11
5.5.4. Resulting speed/voltage curve upon load change.......................................................................12
5.6. Adjusting Uni-line load sharers and synchronisers..............................................................................13
5.6.1. Resulting speed/voltage curve upon load change.......................................................................14

6. Governor interface basic circuits


6.1. Direct analogue controls.......................................................................................................................15
6.2. Combined analogue controls................................................................................................................15

7. Governor interfaces
7.1. Barber-Colman DYNA 1.......................................................................................................................17
7.2. Barber-Colman DYNA DPG 2200 governor.........................................................................................17
7.3. Barber-Colman DYNA 8000 governor..................................................................................................17
7.4. Barber-Colman DYNA 1 digital controllers...........................................................................................18
7.4.1. Model DYN1 10502/3/4/6............................................................................................................18
7.4.2. Model DYN1 DYNA 2000............................................................................................................18
7.4.3. Model DYN1 10871.....................................................................................................................18
7.4.4. Model DYN1 10794.....................................................................................................................19
7.5. Caterpillar® ADEM engine controller...................................................................................................19
7.6. Caterpillar® PEEC engine controller....................................................................................................20
7.7. Caterpillar® Pulse Width Modulator converter ....................................................................................21
7.8. Cummins EFC governor.......................................................................................................................21
7.9. Cummins ECM controller.....................................................................................................................21
7.10. Cummins Power Command Control (PCC) load sharing system and Multi-line 2.............................22
7.11. Detroit Diesel DDEC-III/DDEC-IV electronic governor.......................................................................23
7.12. Deutz EMR electronic controller.........................................................................................................23

DEIF A/S Page 2 of 49


Interfacing DEIF equipment, application
notes 4189340670 UK

7.13. GAC type ESD 5111, 5221 and 5131................................................................................................24


7.13.1. Combined analogue control.......................................................................................................24
7.14. GAC type ESD 5300 and 5330..........................................................................................................25
7.15. GAC type ESD 5500..........................................................................................................................25
7.15.1. Combined analogue control.......................................................................................................26
7.16. Heinzmann type E1-D and E1-F speed governor..............................................................................26
7.17. Heinzmann type E6, E6V, E10, E16 and E30 speed governor..........................................................27
7.18. Heinzmann Olympus for gas turbines................................................................................................27
7.19. Heinzmann KG 6 - 04 to KG10 - 04...................................................................................................27
7.20. MTU MDEC 4000 controller...............................................................................................................27
7.21. Perkins type ECM controller...............................................................................................................28
7.22. SCANIA type DEC2 controller............................................................................................................28
7.23. TOHO electronic governor speed controller XS-400B-03..................................................................29
7.24. Volvo type EMS2 controller................................................................................................................29
7.25. Woodward type 1724 and 1712 governor..........................................................................................30
7.26. Woodward type 2301A speed control governor.................................................................................30
7.27. Woodward type 2301A load sharing..................................................................................................30
7.28. Woodward type 701A.........................................................................................................................31
7.29. Woodward 721 digital speed control..................................................................................................31
7.30. Woodward generator load sensor......................................................................................................31
7.31. Woodward L-series governor.............................................................................................................32
7.32. Woodward ProAct digital speed control system type I and II.............................................................33
7.33. Woodward PEAKTM 150 digital control for steam turbines...............................................................33
7.34. Woodward UG8 digital control............................................................................................................33

8. CANbus engine controller interface


8.1. CANbus interface.................................................................................................................................34
8.2. DEIF unit terminals...............................................................................................................................34
8.3. CANbus J1939 engine unit terminals...................................................................................................35
8.4. MTU terminals......................................................................................................................................35

9. AVR interface basic circuits


9.1. Direct analogue controls.......................................................................................................................37
9.2. Combined analogue controls, 3-wire....................................................................................................37
9.3. Combined analogue controls, 2-wire....................................................................................................38

10. AVR interfaces


10.1. AVK Cosimat AVR..............................................................................................................................40
10.2. Basler Electric AEC63-7 AVR............................................................................................................41
10.3. Basler Electric digital excitation control system (DECS)....................................................................41
10.4. Basler Electric SR 4A/6A/8A/9A/32A AVR.........................................................................................41
10.5. Basler Electric SSR 32-12, 63-12, 125-12 AVR.................................................................................41
10.6. Caterpillar® VR3................................................................................................................................42
10.7. Caterpillar® VR6................................................................................................................................43
10.8. Caterpillar® DVR................................................................................................................................43
10.9. Caterpillar® CDVR.............................................................................................................................44
10.10. Leroy Somer type R250/R438/R448/R449 LS/C or D AVR.............................................................45
10.11. Leroy Somer type R610 AVR...........................................................................................................46
10.12. Leroy Somer type R610 3F AVR......................................................................................................46
10.13. Marathon Magnamax/DVR 2000C AVR...........................................................................................46
10.14. Marelli Mark 1 AVR..........................................................................................................................47
10.15. Marelli M25FA502A..........................................................................................................................47
10.16. Mecc-Alte S.R.7/2............................................................................................................................47
10.17. Mecc-Alte type U.V.R. AVR..............................................................................................................47
10.18. Stamford Newage type MA325, MA327, MX321, MX341, SR465, SX421 and SX440....................48

11. Troubleshooting

DEIF A/S Page 3 of 49


Interfacing DEIF equipment, application Delimitation
notes 4189340670 UK

1. Delimitation
1.1 Scope of application notes Interfacing DEIF equipment to
governors and AVRs
This document includes application notes for interfacing DEIF's equipment to governors and AVRs and cov-
ers the following DEIF products:

Uni-line series A complete range of single-function components for generator control and -protection
Multi-line series A complete range of multi-function components for generator control and -protection
Delomatic A multi-functional system for power management and generator control and -protection

DEIF A/S Page 4 of 49


Interfacing DEIF equipment, application General information
notes 4189340670 UK

2. General information
2.1 Warnings, legal information and safety
2.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.

Warnings

Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.

Notes

Notes provide general information, which will be helpful for the reader to bear in mind.

2.1.2 Legal information and disclaimer


DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how
to install or operate the engine/generator controlled by the DEIF unit, the company responsible for the instal-
lation or the operation of the set must be contacted.

The DEIF unit is not to be opened by unauthorised personnel. If opened anyway, the warranty
will be lost.

Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.

2.1.3 Safety issues


Installing and operating the DEIF unit may imply work with dangerous currents and voltages. Therefore, the
installation should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.

Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.

2.1.4 Electrostatic discharge awareness


Sufficient care must be taken to protect the terminals against static discharges during the installation. Once
the unit is installed and connected, these precautions are no longer necessary.

2.1.5 Factory settings


The DEIF unit is delivered from factory with certain factory settings. These are based on average values and
are not necessarily the correct settings for matching the engine/generator set in question. Precautions must
be taken to check the settings before running the engine/generator set.

DEIF A/S Page 5 of 49


Interfacing DEIF equipment, application General information
notes 4189340670 UK

2.2 About the Application Notes


2.2.1 General purpose
This document includes application notes for interfacing DEIF's equipment of the Uni-line, Multi-line 2 and De-
lomatic series to governors and AVRs. It mainly includes examples of different applications suitable for the
unit.

For functional descriptions, the procedure for parameter setup, parameter lists etc., please see
the relevant documentation for the equipment in question.

The general purpose of the application notes is to offer the designer information about suitable applications
interfacing to governors and AVRs.

Please make sure to read the relevant documentation before starting to work with the DEIF unit
and the gen-set to be controlled. Failure to do this could result in human injury or damage to
the equipment.

2.2.2 Intended users


The Application Notes are mainly intended for the person responsible for designing systems. In most cases,
this would be a panel builder designer. Naturally, other users might also find useful information in this docu-
ment.

2.2.3 Contents and overall structure


This document is divided into chapters, and in order to make the structure simple and easy to use, each
chapter will begin from the top of a new page.

DEIF A/S Page 6 of 49


Interfacing DEIF equipment, application Abbreviations and names
notes 4189340670 UK

3. Abbreviations and names


The following abbreviations and names are used for DEIF units:

● Uni-line: A family of single-function components. The Uni-line synchronisers and load sharers all have re-
lay control outputs.
● EPQ96 and EPN-110DN: Electronic potentiometers giving a DC voltage output.
● Multi-line 2: A family of multi-functional components. These have relay control outputs as standard (for
both speed governor and AVR), and analogue (+/-20 mA) as well as Pulse Width Modulated (PWM) out-
puts as option.
● PPU: Paralleling and Protection Unit.
● GPC: Generator Paralleling Controller.
● AGC/AGC 200: Automatic Generator Controller (Automatic Mains Failure unit with engine control).
● BGC: Basic Generator Controller (Automatic Mains Failure unit with limited control functions).
● PPM: Protection and Power Mangement (power management system for ships).
● Delomatic: A multi-functional system capable of power management functions besides all generator con-
trol and protection functions.
● SCM-1: Generator control plug-in module in Delomatic 3 with relay or analogue outputs for speed
governor and AVR.
● SCM 4.2: Generator control plug-in module in Delomatic 4 with relay or analogue outputs for speed
governor and AVR.

DEIF A/S Page 7 of 49


Interfacing DEIF equipment, application General comments regarding adjustment of
notes 4189340670 UK governors and AVRs

4. General comments regarding adjustment of gov-


ernors and AVRs
4.1 DEIF PI step regulators
PI step regulator is a commonly used regulator for speed control. Also when interfacing to an electronic gov-
ernor/AVR without capability for binary inputs. In this case an electronic potentiometer type EPQ96 or
EPN-110DN is used to convert the relay outputs from PI step regulator into an analogue signal which can be
used by the governor/AVR.

Usually, the most accepted signals are voltage signals.

DEIF controller EPQ96/EPN - 110DN Governor/AVR


0…1/0…5/0…10V DC

4.2 DEIF PI analogue output regulators


Only max. scale outputs are shown in the following. Any scaling within the max. values can be achieved.

The DEIF analogue output regulators are available in:

- Delomatic multi-function generator control and protection system +/-20 mA


- Multi-line 2 units AGC, PPU, PPM and GPC +/-20 mA, PWM
- Multi-line 2 unit BGC +/-20 mA
- Electronic potentiometers EPQ96 and EPN-110DN +/-1/5/10V DC
- Electronic potentiometer EPQ96-2 +/-20 mA
+/-1/5/10V DC
PWM
- IOM 200 external IO module for AGC 200 +/-20 mA
0-20 mA
+/-1/5/10V DC
0-1/5/10 V

DEIF controller Governor/AVR


0…1/0…5/0…10V DC, ±20mA, PWM

DEIF A/S Page 8 of 49


Interfacing DEIF equipment, application Commissioning
notes 4189340670 UK

5. Commissioning
5.1 The prime mover and generator
The prime mover can be diesel engine, gas engine, gas turbine or steam turbine. The type of prime mover is
unimportant. The generator must be a synchronous generator with adjustable Automatic Voltage Regulator
(AVR).

5.2 Speed droop on speed governor


The speed governor is recommended to have a speed droop of 3-4% (speed dropping 3-4% from no load
to full load when the DEIF equipment is not in control). To ensure equal load sharing on parallel running ma-
chines, all governors must have the same droop setting.

Since the DEIF units all contain frequency as well as power control facilities and use these for
control simultaneously, the resulting system will be isochronous (without speed droop), even
though the governors are adjusted with droop.

Even though speed droop is recommended, the DEIF units AGC, AGC 200, BGC, PPU, PPM and
GPC can control isochronous speed governors (without droop) when using analogue/PWM/en-
gine communication output for speed control. Delomatic 3/4 and Uni-line always require droop.

5.3 Voltage droop on AVR


The AVR controls the generator voltage in a manner comparable to the speed governor controlling the prime
mover speed.

This means that the generator AVR must have a voltage droop of 3-4% (voltage dropping 3-4% from no
load to full load when the DEIF equipment has no control). To ensure equal VAr sharing on parallel running
generators, the voltage droop must be the same for all generators.

Since the DEIF units all have options for voltage as well as reactive power/power factor control
facilities and use these for control simultaneously, the resulting system, if the option is selec-
ted, will be with fixed voltage (without voltage droop) even though the AVRs are adjusted with
droop.

5.4 Initial setting of speed governor/AVR


5.4.1 With relay output(s) directly connected
● Disable the outputs from the DEIF controller(s).
● Run the generator with no load.
● Adjust the frequency (on the speed governor) to be base frequency (50 or 60 Hz) plus 50% of the droop
(4% droop means +2% = 1 Hz for 50 Hz).
● Adjust the generator voltage (on the AVR) to nominal voltage plus 50% of the voltage droop (4% voltage
droop means +2%).

5.4.2 With analogue output


The analogue output from Delomatic/PPU/PPM/GPC/AGC/BGC is +/-20 mA, which in most cases must be
converted into a voltage using a resistor across the terminals (250 Ω gives 5V DC at 20 mA).

DEIF A/S Page 9 of 49


Interfacing DEIF equipment, application Commissioning
notes 4189340670 UK

AGC 200 has no analogue outputs, so if needed, the IOM 200 series external IO module must be used.

As especially governors are sensitive to the external circuit impedance, it is essential that the initial settings of
speed governor/AVR are done with the analogue output connected, but disabled (electronic potentiometer:
Turn off the power supply; Delomatic: Set in SWBD mode; Multi-line: Set in MAN mode). If you fail to do this,
you may experience control problems later on. The only exception from this rule is the Woodward load sensor
(please see the chapter Woodward generator load sensor). After this, you adjust the frequency response:

● Run the generator with no load.


● Adjust the frequency (on the speed governor) to be base frequency (50 or 60 Hz) plus 50% of the droop
(4% droop means +2% = 1 Hz for 50 Hz).
● Adjust the generator voltage (on the AVR) to nominal voltage plus 50% of the voltage droop (4% voltage
droop means +2%).
● The output range from the DEIF unit must equal nominal frequency +/-2%.

After this, you can activate the AUTO input again.

5.4.3 With Multi-line 2 PPU/PPM/GPC/AGC PWM output for Caterpillar®


Since the PWM initial setting has an influence on the start-up speed of the engine, the first thing to do is to
set this (setting 2272 for Multi-line, 2662 for AGC/PPM):

● Make sure that the generator cannot start.


● Turn the PPU/PPM/GPC/AGC OFF and ON again (to make sure that the PWM output is reset).
● Start the generator (no load).
● Adjust setting 2272/2662 until the correct speed (and frequency) is achieved.

PWM output is not possible on an AGC 200.

5.5 Adjusting DEIF controllers


The first attempt is always an "I hope settings are OK". For this purpose, DEIF has with experience gained
over the years come to some initial settings, which may not be perfect but can be used to start the adjustment
of regulators/controllers.

Adjusting PI (Proportional Integral) step regulators (with relay outputs) and PID (Proportional Integral Differ-
ential) (with analogue outputs) controllers is not easy. The following is a shortcut, giving you an acceptable
result (maybe not perfect, but acceptable).

5.5.1 Delomatic/PPU/PPM/GPC/AGC/AGC 200/BGC


The equipment is delivered with a factory setting, which will be acceptable in 90% of the cases. Start the gen-
erator and test it. The worst thing that can happen is a generator trip, in which case a new attempt must be
made.

5.5.2 Analogue output PI


The analogue speed output can be used for engines with electronic governors.

Both Delomatic and PPU/PPM/GPC/AGC/AGC 200/BGC accept push-button inputs for manual speed control
and can be connected directly, even if manual running is required.

The analogue voltage output can be used for generators with electronic AVRs.

DEIF A/S Page 10 of 49


Interfacing DEIF equipment, application Commissioning
notes 4189340670 UK

Both Delomatic and PPU/PPM/GPC/AGC/AGC 200/BGC accept push-button inputs for manual voltage con-
trol and can be connected directly, even if manual running is required.

The output is +/-20 mA. For IOM 200 units, voltage can be chosen as well.

1. The integral time (the time to compensate for deviations from setpoint) should be as short as possible, but
to avoid hunting, the setting is recommended to give a fairly long integral time, so, as a beginning, the
integral time (Ki factor in Multi-line) can remain as factory setting.
2. The gain is now adjusted. Increase the value until the speed governor/AVR becomes unstable, and de-
crease until it stabilises again.
3. Repeat 2., but this time by lowering the integral time (increase Ki in Multi-line, decrease Tn in Delomatic)
until instability, and increase the integral time again until stability is reached.
4. The easiest way to test is to use (if possible) a load bank, applying "jumps" in generator load and thereby
testing the speed/AVR control.

5.5.3 Relay output PI step


Delomatic and Uni-line:

There are 2 settings: Time pulse, which is the shortest relay "ON" signal time.
Gain Kp, which is the amplification factor for the proportional part.

The shortest acceptable time pulse time is dependent on the reaction of the governor/AVR and connection
type. Slow reaction => long time pulse.

Multi-line:
Apart from the Kp (proportional gain) and Ki (integrator gain) there are settings for:

● Pulse width time (the output is a Pulse Width Modulated output).


● Shortest acceptable pulse ON length.

Electronic potentiometer:
If an electronic potentiometer is being used to convert the relay signals into analogue value, both the time
pulse and the gain factory setting can be used. In this case, the adjustments are easiest done on the elec-
tronic potentiometer, gain = a combination of ∆Uo (full scale output) and TIME (sec.). Higher ∆Uo/shorter
TIME = higher gain.

Direct connection to mechanical speed governor:


If the connection is directly onto a mechanical governor with pilot motor, it may be necessary to increase the
time pulse value. This depends on the mechanical characteristics of the governor system.

After finding the proper time pulse length, the gain Kp is adjusted. Increase the value until the speed be-
comes unstable, and decrease until it stabilises again.

Direct connection to AVR with binary voltage up/down inputs:


If the connection is directly onto binary inputs, it may be necessary to increase the time pulse value. This de-
pends on the characteristics of the AVR.

After finding the proper time pulse length, the gain Kp is adjusted. Increase the value until the voltage be-
comes unstable, and decrease until it stabilises again.

DEIF A/S Page 11 of 49


Interfacing DEIF equipment, application Commissioning
notes 4189340670 UK

5.5.4 Resulting speed/voltage curve upon load change


The easiest way to test is to use (if possible) a load bank, applying "jumps" in generator load and thereby
testing the speed/voltage control.

The optimal result should look like this curve:

Freq./voltage

Freq./voltage

Nominal freq./voltage

Time
Load change

As it can be seen, 2-3 "overshoots" before stabilising after a sudden change are OK.

Gain too high:

Freq./voltage Freq./voltage

Nominal freq./voltage

Time
Load change

If the gain is too high, the speed/voltage will not reach stability and the hunting may increase over time and
eventually cause a trip.

DEIF A/S Page 12 of 49


Interfacing DEIF equipment, application Commissioning
notes 4189340670 UK

Gain too low:

Freq./voltage

Nominal freq./voltage

Freq./voltage

Time
Load change

If the gain is too low, the return to nominal takes too long time or may even never happen.

5.6 Adjusting Uni-line load sharers and synchronisers

There are 2 settings: Tn, which is the shortest relay signal "ON" time.
Xp, which is the amplification factor for the proportional part.

The shortest Tn is dependent on the reaction of the governor/AVR and connection type. Slow reaction => lon-
ger Tn.

As a beginning, place both potentiometers in centre position.

Electronic potentiometer:
If an electronic potentiometer is being used to convert the relay signals into analogue value, both the time
pulse and the gain potentiometer centre position can be used. In this case, the adjustments are done on the
electronic potentiometer, gain = a combination of ∆Uo (full scale output) and TIME (sec.). Increase ∆Uo/de-
crease TIME = increase gain.

Direct connection to mechanical speed governor:


If the connection is directly onto a mechanical governor with pilot motor, it may be necessary to increase the
time pulse value. This depends on the mechanical characteristics of the governor system, but the shortest
possible time pulse value is preferable.

After finding the proper time pulse length, the gain Xp is adjusted. Increase the value until the speed be-
comes unstable, and decrease until it stabilises again.

Direct connection to AVR with binary voltage up/down inputs:


If the connection is directly onto binary inputs, it may be necessary to increase the time pulse value. This de-
pends on the characteristics of the AVR. Slower reaction => longer time pulse.

After finding the proper time pulse length, the gain Kp is adjusted. Increase the value until the voltage be-
comes unstable, and decrease until it stabilises again.

DEIF A/S Page 13 of 49


Interfacing DEIF equipment, application Commissioning
notes 4189340670 UK

On the Uni-line synchroniser FAS-115DG, the voltage control relay output settings are fixed
and cannot be adjusted. This is done under the assumption that the outputs are used for an
electronic AVR or an electronic potentiometer, where adjustments can be made.

5.6.1 Resulting speed/voltage curve upon load change


The easiest way to test is to use (if possible) a load bank, applying "jumps" in generator load and thereby
testing the speed/voltage control.

For resulting speed/voltage curves, please refer to the chapter "Resulting speed/voltage curve upon load
change".

As it can be seen, 2-3 "overshoots" before stabilising after a sudden change are OK. If more "overshoots" are
present, decrease the gain (increase TIME on the electronic potentiometer) and try again.

DEIF A/S Page 14 of 49


Interfacing DEIF equipment, application Governor interface basic circuits
notes 4189340670 UK

6. Governor interface basic circuits

The following contains indications of resistor values. These values are for guidance only, and
you may have to change the resistors to obtain proper control. Generally, choosing too big re-
sistors across the +/-20mA outputs from DEIF units will result in unstable control; choosing
too small resistors will result in the system being unable to control the generator in the full op-
erating range (0-100% load).

6.1 Direct analogue controls


The direct analogue control utilises the fact that most governors are prepared for external control devices
such as synchronisers and load sharers.

GOVERNOR
DEIF equipment terminals

R1 EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


IN 1 10 (+) 10 (+) 23 (+) 7 (+)
IN 2 9 (┴) 11 (┴) 24 (┴) 8 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage input.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
GOVERNOR SCM 4.2 SCM 1 GPC/ AGC
R1
IN 1 30 (+) 29 (+) 66 (+) 66 (+)
32 (┴) 30 (┴) 67 (┴) 65 (┴)
R2

IN 2

6.2 Combined analogue controls


The combined analogue control uses the combination of the DEIF unit’s analogue output and a speed setting
potentiometer.

The advantage of this solution is the possibility to do basic speed settings with the potentiometer and there-
after let the DEIF unit take over.

If the potentiometer is only used for initial adjustments, it can be replaced by fixed resistors,
once the adjustment is done.

DEIF A/S Page 15 of 49


Interfacing DEIF equipment, application Governor interface basic circuits
notes 4189340670 UK

GOVERNOR
DEIF equipment terminals
IN 1 (+)
Pot
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
10 (+) 10 (+) 23 (+) 7 (+)
IN 2 (0)
9 (┴) 11 (┴) 24 (┴) 8 (┴)
R1
IN 3 (signal)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into V DC range:

GOVERNOR DEIF equipment terminals


IN 1 (+)
DELOMATIC DELOMATIC PPU/ PPM/
Pot BGC
SCM 4.2 SCM 1 GPC/ AGC
30 (+) 29 (+) 66 (+) 66 (+)
IN 2 (0) R2
32 (┴) 30 (┴) 67 (┴) 65 (┴)
R1
IN 3 (signal)

DEIF A/S Page 16 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

7. Governor interfaces

This chapter refers to the chapter 6 diagrams for terminals and resistor values unless other-
wise stated.

7.1 Barber-Colman DYNA 1


DYNA I is intended for a potentiometer connected to terminal D (+8V DC), H (wiper) and F (+4V DC). When
moving the wiper towards terminal D, the speed increases. Both direct and combined control circuits can be
used:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
H F 499 kΩ 100 Ω

The combined analogue control uses terminal I instead of terminal F as reference.

Combined analogue controls


Input terminals Resistor values
IN 1 (+) IN 2 (0) IN 3 (signal) Pot R1 R2
D I H 5 kΩ 499 kΩ 100 Ω

7.2 Barber-Colman DYNA DPG 2200 governor

The EPQ/EPN electronic potentiometers must be set to lowest range, +/-300 mV ~ +/-3 Hz.
Only direct analogue control is possible.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
LS signal 9 LS ref (2.5 V) 10 0Ω 15 Ω

7.3 Barber-Colman DYNA 8000 governor


DYNA 8000 is similar to DYNA I, i.e. it is intended for a remote potentiometer speed control - terminal 6 (+8V
DC), 7 (+4V DC), 9 (wiper) and 10 (0 V). When moving the wiper towards 6, the speed increases.

DEIF A/S Page 17 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
9 7 0Ω 220 Ω

The combined analogue control uses terminal I instead of terminal F as reference.

Combined analogue controls


Input terminals Resistor values
IN 1 (+) IN 2 (0) IN 3 (signal) Pot R1 R2
6 10 9 5 kΩ 0Ω 220 Ω

7.4 Barber-Colman DYNA 1 digital controllers


7.4.1 Model DYN1 10502/3/4/6
Replace the remote speed potentiometer as follows:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
8 7 499 kΩ 100 Ω

7.4.2 Model DYN1 DYNA 2000


Replace the remote speed potentiometer as follows:

The input accepts 0…2V DC signals.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
9 7 0Ω 100 Ω

7.4.3 Model DYN1 10871


There are 2 possibilities:

1. Use the speed increase (term. 15)/decrease (term. 16) binary inputs and relay outputs from the DEIF
equipment. Inputs activate when connected to terminal 1 (+9…30V DC).
2. Replace the remote speed potentiometer.

The input is quite sensitive. Therefore the circuit is a bit special:

DEIF A/S Page 18 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

BARBER- DEIF equipment terminals


350 kΩ
COLMAN
11
DYN1
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
10 10 (+) 10 (+) 23 (+) 7 (+)
10 kΩ 10 kΩ 9 (┴) 11 (┴) 24 (┴) 8 (┴)
12

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 2V DC range:

BARBER- DEIF equipment terminals


350 kΩ
COLMAN
11
DYN1 DELOMATIC DELOMATIC PPU/ PPM/
BGC
SCM 4.2 SCM 1 GPC/ AGC
10 30 (+) 29 (+) 66 (+) 66 (+)
100 Ω
10 kΩ 10 kΩ 32 (┴) 30 (┴) 67 (┴) 65 (┴)
12

7.4.4 Model DYN1 10794


Replace the remote speed potentiometer as follows:

The input accepts 0…3.75V DC signals.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
8 9 350 kΩ 200 Ω

7.5 Caterpillar® ADEM engine controller


The ADEM requires PWM signals for speed and droop settings. These can only be obtained with Multi-line 2
and EPQ96-2 units, all other DEIF units do not have this capability.

DEIF A/S Page 19 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

PPU/
ADEM GPC/ EPQ96-2
AGC
RATED
67 + 15 +
SPEED (10)
68 14
DROOP
92 + 13 +
SPEED (12)
93 -

BATTERY -

If DROOP is not needed, the connection can be removed.

Terminal numbers are plug numbers.

7.6 Caterpillar® PEEC engine controller


The PEEC requires PWM signals for speed and droop settings. These can only be obtained with Multi-line 2
and EPQ96-2 units, all other DEIF units do not have this capability.

PPU/
PEEC GPC/ EPQ96-2
AGC
PRIMARY
67 + 15 +
THROTTLE (9)
68 14
DROOP (3) 92 + 13 +
93 -
BATTERY - (19)

DEIF A/S Page 20 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

If DROOP is not needed, the connection can be removed.

Terminal numbers are plug numbers.

7.7 Caterpillar® Pulse Width Modulator converter


The CAT 9x9591 Pulse Width Modulator converter converts analogue signals into PWM signals for the ADEM
and/or PEEC controllers, i.e. it must be used for controllers which do not have the PWM option.

Combined analogue controls


Input terminals Resistor values
IN 1 (+) IN 2 (0) IN 3 (signal) Pot R1 R2
2 1 3 1kΩ 0Ω 250Ω

The polarity of the DEIF units' outputs must be reversed compared to the diagram in paragraph
6.

7.8 Cummins EFC governor


Cummins EFC governor accepts voltage signals directly, but the range is below the DEIF standard range.
Therefore a voltage drop resistor (500 kΩ) is needed. In the following, two sets of terminals are shown. This is
due to the fact that the EFC comes with two different terminal strip layouts.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
10 (wiper) 11 (+4 V ) 499 kΩ 120 Ω
8 (wiper) 9 (+4 V)

7.9 Cummins ECM controller

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
23 (+) 14 (gnd) 0Ω 200 Ω

The ECM gain must be set OFF.

DEIF A/S Page 21 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

The ECM must be set to Barber-Colman interface.

If screened cable is used, the screen must be connected to ECM terminal 19 only.

7.10 Cummins Power Command Control (PCC) load sharing


system and Multi-line 2
Since the Multi-line 2 (ML-2) uses a 0…5V DC load sharing line, which is not compatible with the PCC load
sharing line, a conversion must be made.

As the same problem occurs with other manufacturers’ systems (Barber-Colman (BC)/Woodward/GAC),
Cummins has made an interface unit called "Isochronous Load Sharing (ILSI) kit", Cummins part no.
300-5456, which is the one to be used for ML-2 connection to PCC.

The load sharing is for power load sharing only, kVAr load sharing must be made using different units.

Following the Cummins instruction sheet C-604 11-01, the procedure is as follows:

1. The 100% kW ML-2 load share line voltage is 5V DC.


2. Power up the ILSI module by applying 12-24V DC on TB2 terminals 5 (gnd) and 6 (+). Do not connect the
load sharing lines yet.
3. Set the "Calibration Switch" to Cal.
4. Set the "ILS Type Switch" to BC.
5. Adjust the "Load Share Gain" potentiometer to 5V DC (measured on terminals TB1 1 (+) and 2 (-)).
6. Measure the "Calibration Voltage" on terminal TB2 5 (-) and "Calibration Voltage Test Point" (+). Typical
value is 2.10V DC.
7. Adjust the "PCC Matching Potentiometer" until "PCC Voltage" is equal to "Calibration Voltage" in 6)
(measured on terminals TB2 3 (+) and 4 (-)).
8. Move the "Calibration Switch" back to normal position.

It is important that the "Calibration Switch" is moved back to normal position before starting the generators.
Failure to do this will provoke reverse power trips.

Load sharing lines diagram:

DEIF A/S Page 22 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

The generator breaker feedback(s)


is (are) necessary to make the
Cummins PCC+ system run
PCC system PCC-
12/24V DC GND (-)
Supply +
GB1 GB2 GB3......... GBn

TB2: 6 5 4 3 2 1
ILSI unit
TB1: 1 2

DEIF ML-2 units


BGC PPU/GPC/AGC
80 (LS+) 37 (LS+)
79 (LS-) 38 (LS-)

7.11 Detroit Diesel DDEC-III/DDEC-IV electronic governor


The DDEC accepts 0…5V DC signals directly:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
D1 (speed) C3 (ref) 0Ω 250 Ω

Combined analogue controls


Input terminals Resistor values
IN 1 (+) IN 2 (0) IN 3 (signal) Pot R1 R2
A3 C3 (ref) D1 (speed) 5 kΩ 0Ω 250 Ω

Terminals are referring to the 30 pole connector on the DDEC-lll.

7.12 Deutz EMR electronic controller


The EMR accepts a 0.5...4.5V DC signal, but only half the range is needed, so 2V DC is sufficient:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
24 (+) 23 (gnd) 0Ω 100 Ω

DEIF A/S Page 23 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

A higher voltage range can be used (200 Ω to give 4V DC). In this case the EMR frequency set-
ting must be checked to be 49-51 Hz.

7.13 GAC type ESD 5111, 5221 and 5131


This GAC range has a terminal for external equipment. This terminal accepts +/-5V DC signals, so most of
the DEIF controllers can be connected directly.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
G (gnd) N (input) 0Ω 250 Ω

7.13.1 Combined analogue control


For EPQ and EPN the output range must be set to 1.3V DC:

GAC 5xxx
G DEIF equipment terminals
J EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
K
10 (+) 10 (+) 23 (+) 7 (+)
L
P 10 kΩ 75 Ω 9 (┴) 11 (┴) 24 (┴) 8 (┴)
E(0V)
N

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

GAC 5xxx DEIF equipment terminals


G
DELOMATIC DELOMATIC PPU/ PPM/
J BGC
SCM 4.2 SCM 1 GPC/ AGC
K
30 (+) 29 (+) 66 (+) 66 (+)
L
P 10 kΩ 75 Ω 32 (┴) 30 (┴) 67 (┴) 65 (┴)
E(0V)
N

DEIF A/S Page 24 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

7.14 GAC type ESD 5300 and 5330


The ESD 5330 has an input for 0…10V DC control as follows:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
G (gnd) M (aux.) 0Ω 500 Ω

7.15 GAC type ESD 5500


The output signal from EPQ/EPN must be set to give +2.5 V after power up.

For EPQ/EPN the "up" input will result in a decreasing speed, and the "down" input will result in an increasing
speed.

For Delomatic/Multi-line the output signal must be set to give -10.0 mA on power up. Since the connections
are reversed, the ESD 5500 will see a +2.5V DC across the 250 Ω resistor, and increase/decrease will work
properly.

On the ESD 5500, terminal J can be used instead of N. The J input has a lower impedance (5
kΩ) than N (1 MΩ). The G terminal on the ESD 5500 is connected to battery -.

DEIF equipment terminals


ESD 5500
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
N (Input) 10 (+) 10 (+) 23 (+) 7 (+)
G (Gnd) 9 (┴) 11 (┴) 24 (┴) 8 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 10V DC range:

DEIF equipment terminals


ESD 5500
DELOMATIC DELOMATIC PPU/ PPM/
BGC
SCM 4.2 SCM 1 GPC/ AGC
G (Gnd) 30 (+) 29 (+) 66 (+) 66 (+)
32 (┴) 30 (┴) 67 (┴) 65 (┴)
60Ω

N (Input)

DEIF A/S Page 25 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

7.15.1 Combined analogue control


For EPQ, EPN and IOM 2xx, the output range must be set to 1.3V DC:

GAC 5xxx
G DEIF equipment terminals
J EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
K
10 (+) 10 (+) 23 (+) 7 (+)
L
P 10 kΩ 75 Ω 9 (┴) 11 (┴) 24 (┴) 8 (┴)
E(0V)
N

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

GAC 5xxx DEIF equipment terminals


G
DELOMATIC DELOMATIC PPU/ PPM/
J BGC
SCM 4.2 SCM 1 GPC/ AGC
K
30 (+) 29 (+) 66 (+) 66 (+)
L
P 10 kΩ 75 Ω 32 (┴) 30 (┴) 67 (┴) 65 (┴)
E(0V)
N

7.16 Heinzmann type E1-D and E1-F speed governor


Type E1-D/F accepts control voltage signals (0-5V DC) directly on terminal 3 (-) and 4 (+), so most of the
DEIF controllers can be connected directly.

The signal must be protected by a diode as shown in order to prevent malfunction of the sys-
tem.

E1-D/F
DEIF equipment terminals

EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


3 10 (+) 10 (+) 23 (+) 7 (+)
4 9 (┴) 11 (┴) 24 (┴) 8 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DEIF A/S Page 26 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 5V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
E1-D/F SCM 4.2 SCM 1 GPC/ AGC
3 30 (+) 29 (+) 66 (+) 66 (+)
32 (┴) 30 (┴) 67 (┴) 65 (┴)
250Ω

7.17 Heinzmann type E6, E6V, E10, E16 and E30 speed gov-
ernor
The E6...E30 series is intended for a 5K speed trim potentiometer. The DEIF equipment giving a voltage out-
put can be connected in series with the wiper of the potentiometer:

Combined analogue controls


Input terminals Resistor values
IN 1 (+) IN 2 (0) IN 3 (signal) Pot R1 R2
A C B (In) 5 kΩ 0Ω 250 Ω

7.18 Heinzmann Olympus for gas turbines


Heinzmann Olympus accepts binary (relay) control signals as follows:

● Raise speed: Connect terminal H (connector 2) to +24V DC supply.


● Lower speed: Connect terminal S (connector 2) to +24V DC supply.

7.19 Heinzmann KG 6 - 04 to KG10 - 04


The Heinzmann KG series accepts voltage signals (1…5V DC) directly connected:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
C3 A3 0Ω 250 Ω

7.20 MTU MDEC 4000 controller


The MDEC 4000 controller accepts both binary and analogue inputs.

Binary inputs are optocoupler inputs requiring 24V DC as follows:

Speed raise: X1-EE (cable wire 4) to gnd, X1-FF (cable wire 3) to +24V DC.

DEIF A/S Page 27 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

Speed lower: X1-u (cable wire 14) to gnd, X1-v (cable wire 13) to +24V DC.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
8 36 0Ω 500 Ω

Set the Multi-line analogue governor offset to 50% to compensate the MTU speed internal off-
set.

7.21 Perkins type ECM controller


The Perkins ECM accepts binary signals for speed control:

ECM

J1/59 (Lower)

J1/7 (Raise)

J1/18 (-)

The ECM terminal numbers refer to the ECM module connectors. The equivalent Customer in-
terface connector P3 connectors are:
ECM P3
J1/59 29
J1/7 28
J1/18 12

7.22 SCANIA type DEC2 controller


The DEC2 accepts 0…3V DC input for 0…100% speed, max. 5V DC to avoid damage, so the DEIF equip-
ment can be connected directly.

The electronic potentiometers must have the range 5V DC.

DEIF A/S Page 28 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
B8 A7 0Ω 200 Ω

7.23 TOHO electronic governor speed controller XS-400B-03


The TOHO speed controller accepts voltage signals and therefore DEIF equipment can be connected direct-
ly. NOTE: As the TOHO unit operates at 4V DC as base setting, the initial adjustment must be carried out
with the DEIF equipment connected and powered up, but set at 0 V (0 mA for Delomatic/PPU/GPC) output.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
1 -S 0Ω 200 Ω

7.24 Volvo type EMS2 controller


Volvo type EMS2 controller accepts 1.0 to 4.7V DC signals only, with an active range of 2.85V DC. In order to
meet these requirements, the following network must be made:

The diodes are to prevent negative signals to the EMS2 which it cannot accept.

Set EPQ/EPN output range to 3V DC.

EMS2
DEIF equipment terminals
C (+5V) Gn/Sb 1kΩ
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
10 (+) 10 (+) 23 (+) 7 (+)
B (Input) Gn/Or
9 (┴) 11 (┴) 24 (┴) 8 (┴)
250Ω
A (0V) Gn/Y

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor circuit is needed to convert into 2.85V
DC range:

DEIF A/S Page 29 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

EMS2 DEIF equipment terminals

C (+5V) Gn/Sb 1kΩ DELOMATIC DELOMATIC PPU/ PPM/


BGC
SCM 4.2 SCM 1 GPC/ AGC
30 (+) 29 (+) 66 (+) 66 (+)
B (Input) Gn/Or 250Ω 330Ω
32 (┴) 30 (┴) 67 (┴) 65 (┴)

A (0V) Gn/Y

Abbreviations for wire colours on EMS2: Gn/Sb: Green/black, Gn/Or: Green/orange, Gn/Y: Green/yellow.

7.25 Woodward type 1724 and 1712 governor


Woodward 17xx accepts voltage signals (+/-5V DC) directly on terminal 7 (+) and 8 (-), so the DEIF control-
lers can be connected directly:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
7 (+) 8 (-) 0Ω 250 Ω

7.26 Woodward type 2301A speed control governor


Woodward 2301A speed control voltage signals (+/-5V DC) directly on terminal 17 (-) and 15 (+), so the DEIF
controllers can be connected directly:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
15 (+) 17 (-) 0Ω 250 Ω

7.27 Woodward type 2301A load sharing


Woodward 2301A load sharing is intended for a 100 Ω potentiometer for external speed control.

For DEIF equipment with voltage output:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
24 (+) 23 (-) 0Ω 140 Ω

DEIF A/S Page 30 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

7.28 Woodward type 701A


The type 701A can accept both analogue and binary signals for speed control.

For DEIF equipment with voltage output:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
21 (+) 22 (-) 0Ω 140 Ω

Binary signals:

701A

11 (Lower)
+24V DC
12 (Raise)

8 (-) 0V DC

7.29 Woodward 721 digital speed control


Even though the unit accepts analogue signals, we recommend using the binary input terminal 27 (lower
speed) and 28 (raise speed). The inputs are activated when connected to terminal 1 (+).

7.30 Woodward generator load sensor


The Woodward generator load sensor (using a Pulse Width Modulated signal for the governor) is intended for
a 3-pole potentiometer.

Due to the internal circuits, the standard DEIF way of doing the connections cannot be used. Instead of con-
necting the outputs from the DEIF units to one side of the potentiometer and the wiper input, connections
must be made for ground and wiper. Because of this the usual way of initial setting by switching off the DEIF
unit during initial governor adjustment cannot be used. The DEIF unit must be switched ON and the output
adjusted to 0V DC when adjusting the governor. After this, the normal procedure can be carried out. Please
also note that the output is "inverted"; connect the + output from the DEIF unit to the gnd on the load sensor.
This is possible due to the fact that the DEIF unit’s output is galvanically separated from the rest of the unit.

DEIF A/S Page 31 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

DEIF equipment terminals


Load sensor
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
21 (gnd) 10 10 (+) 23 7 (+)
27 (wiper) 9 11 (┴) 24 8 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

An alternative solution is to use the SPM-A synchroniser input:

The load sensor terminals 13-14 connection must remain open. Do not close with the generator
breaker, as that will make the load sensor ignore the SPM-A input.

DEIF equipment terminals


Load sensor
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
24 (+) 10 (+) 10 (+) 23 (+) 7 (+)
25 (-) 9 (┴) 11 (┴) 24 (┴) 8 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

The load sensor inputs accept +/-3V DC. The DEIF units must have the output adjusted accord-
ingly.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 10V DC range:

DEIF equipment terminals

Load sensor DELOMATIC DELOMATIC PPU/ PPM/


BGC
SCM 4.2 SCM 1 GPC/ AGC
24 (+) 30 (+) 29 (+) 66 (+) 66 (+)
32 (┴) 30 (┴) 67 (┴) 65 (┴)
150Ω

25 (-)

7.31 Woodward L-series governor


The L-series analogue input AUX #1 is especially designed for speed setting input, 0-5V DC, which is recom-
mended.

DEIF A/S Page 32 of 49


Interfacing DEIF equipment, application Governor interfaces
notes 4189340670 UK

The input can be configured to +/-3V DC as well. Refer to Woodward for details.

This configuration is for 0-5V DC input:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
8 (+) 3 (-) 0Ω 250 Ω

7.32 Woodward ProAct digital speed control system type I


and II
The ProAct analogue input AUX is especially designed for speed setting input, +/-3V DC.

Direct analogue control


Input terminals (TB2) Resistor values
IN 1 IN 2 R1 R2
12 (+) 13 (-) 0Ω 150 Ω

7.33 Woodward PEAKTM 150 digital control for steam tur-


bines
The unit accepts relay (discrete) inputs. Binary input 12 (lower speed) and 13 (raise speed). Internally pow-
ered (jumper 15 set, see manual), the inputs are activated when connecting terminal 33 (+24V DC internal
source) to the input in question (12 or 13). Externally powered (jumper 16 set, see manual), the external neg-
ative (-) is to be connected to terminal 20, and the inputs (12 or 13) are then activated when the external
+24V DC is connected to them.

7.34 Woodward UG8 digital control


The UG8 digital control accepts 4…20 mA input for speed control. This means that a standard electronic po-
tentiometer cannot be used directly, as it is giving a voltage output.

The electronic potentiometers can be changed into giving 0-20 mA outputs, but this is a special version that
has to be asked for. The Delomatic/PPU/GPC/AGC/BGC can connect directly:

UG 8 DEIF equipment terminals


Digital
SPECIAL SPECIAL DELOMATIC DELOMATIC PPU/ PPM/
EPQ96-2 IOM 2xx BGC
EPQ96 EPN - 110DN SCM 4.2 SCM 1 GPC/ AGC
9 (+) 10 (+) 10 (+) 7 (+) 23 (+) 30 (+) 29 (+) 66 (+) 66 (+)
10 (-) 9 (┴) 11 (┴) 8 (┴) 24 (┴) 32 (┴) 30 (┴) 67 (┴) 65 (┴)

EPQ96/EPN must be modified for current output. EPQ96-2 standard can be used.

DEIF A/S Page 33 of 49


Interfacing DEIF equipment, application CANbus engine controller interface
notes 4189340670 UK

8. CANbus engine controller interface

The following contains information of CANbus connections for various electronic Engine Con-
troller Units (ECUs). For information about the signals that can be received/transmitted, please
see the Option H5/H7/H13 manual.

8.1 CANbus interface

Engine system Deif unit

CAN-H CAN-H
CAN-L CAN-L

120 Ω 120 Ω

2 x 120 Ohm end terminal resistors are always needed. Note that some engine systems have
the resistor incorporated. Please refer to the engine controller installation manual for details.

Use twisted pair cable, 1 mm2 (16 AWG). If screened cable is used, connect one end to earth
(ground) and isolate the other end. Do not connect screen to the DEIF or the engine unit.

8.2 DEIF unit terminals

AGC AGC/GPU/GPC/ AGC/GPU/GPC/ AGC 200 BGC GC-1F GC-1/EC-1


Option H13 PPU/PPM PPU/PPM Option H5 Option H5 Option H5
Option H5/H13 Option H7
130 130 A1 13 47 or 55 53 1
(CAN-H) (CAN-H) (CAN-H) (CAN-H) (CAN-H) (CAN-H) (CAN-H)
128 128 A3 15 49 or 57 55 3
(CAN-L) (CAN-L) (CAN-L) (CAN-L) (CAN-L) (CAN-L) (CAN-L)

DEIF A/S Page 34 of 49


Interfacing DEIF equipment, application CANbus engine controller interface
notes 4189340670 UK

8.3 CANbus J1939 engine unit terminals

Engine controller Connector Terminals Remark


Caterpillar ADEM A4 Customer harness J1/P1 17 (CAN-H)
18 (CAN-L)
Cummins QSK 50/60 en- J1939 backbone A (CAN-H) Built-in 120 Ω end resistor
gine B (CAN-L)
Cummins QSB 5/7 and 50 pin OEM connector 46 (CAN-H)
QSL 9 engine 47 (CAN-L)
Deutz EMR 2 Plug F 12 (CAN-H)
13 (CAN-L)
Deutz EMR 3 Diagnostic plug X22 M (CAN-H)
F (CAN-L)
Iveco Vector engines Engine harness 255 (CAN-H)
256 (CAN-L)
Perkins ECM Connector P3 31 (CAN-H) Terminals 2 (digital control ena-
32 (CAN-L) ble) and 12 (digital ground) on
connector P3 must be connec-
ted if speed setting signals are
to be transmitted via J1939
Scania EMS-S6 Connector B1 9 (CAN-H) Built-in 120 Ω end resistor
10 (CAN-L)
Volvo Penta EMS 2 8-pole Deutsch connector 1 (CAN-H)
receptacle 2 (CAN-L)

8.4 MTU terminals

Engine controller Connector Terminals Remark


ADEC CANopen protocol SAM module X23 6 (CAN-H) Option H5 or H13 is required
5 (CAN-L) Built-in 120 Ω end resistor

ADEC J1939 Smart connect X3 1 (CAN-H) Option H5 or H13 is required


(smart connect) 2 (CAN-L) Built-in 120 Ω end resistor

ADEC M501 MTU protocol ECU7 19 (CAN1-H) Option H13 is required


X1 35 (CAN1-L) Built-in 120 Ω end resistor

MDEC ECU G (CAN-H) Option H5 or H13 is required


X1 F (CAN-L) MTU protocol

Option H7 cannot be used for MTU MDEC/ADEC module 501interface.


MTU ADEC requires SAM module.
The MTU MDEC uses an MTU protocol.

DEIF A/S Page 35 of 49


Interfacing DEIF equipment, application CANbus engine controller interface
notes 4189340670 UK

MTU ADEC, SAM module: Parameters PR500, PR501 and PR533 must be set correctly to obtain
speed control.
Normal selection: PR500=0, PR501=0, PR533=1.

MTU ADEC, SAM module: Parameter PR2.1060.150 must be set to "ANALOG CAN" to obtain
speed control.

The above settings for SAM module and ADEC are for guidance only. Values may vary between
different models.

DEIF A/S Page 36 of 49


Interfacing DEIF equipment, application AVR interface basic circuits
notes 4189340670 UK

9. AVR interface basic circuits

The following contains indications of resistor values. These values are for guidance only, and
you may have to change the resistors to obtain proper control. Generally, choosing too big re-
sistors across the +/-20 mA outputs from DEIF units will result in unstable control; choosing
too small resistors will result in the system being unable to control the generator in the full op-
erating range (maintaining voltage in the 0-100% load range).

9.1 Direct analogue controls

AVR
DEIF equipment terminals

R1 EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


IN 1 10 (+) 10 (+) 23 (+) 9 (+)
IN 2 9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
AVR SCM 4.2 SCM 1 GPC/ AGC
R1
IN 1 33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)
R2

IN 2

9.2 Combined analogue controls, 3-wire


The combined analogue control uses the combination of the DEIF unit’s analogue output and a speed setting
potentiometer.

The advantage of this solution is the possibility to do basic speed settings with the potentiometer and there-
after let the DEIF unit take over.

If the potentiometer is only used for initial adjustments, it can be replaced by fixed resistors
once the adjustment is done.

DEIF A/S Page 37 of 49


Interfacing DEIF equipment, application AVR interface basic circuits
notes 4189340670 UK

AVR
DEIF equipment terminals
IN 1 (+)
Pot
EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
10 (+) 10 (+) 23 (+) 9 (+)
IN 2 (0)
9 (┴) 11 (┴) 24 (┴) 10 (┴)
R1
IN 3 (signal)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into V DC range:

AVR DEIF equipment terminals


IN 1 (+)
DELOMATIC DELOMATIC PPU/ PPM/
Pot BGC
SCM 4.2 SCM 1 GPC/ AGC
33 (+) 31 (+) 70 (+) 64 (+)
IN 2 (0) R2
35 (┴) 32 (┴) 71 (┴) 63 (┴)
R1
IN 3 (signal)

9.3 Combined analogue controls, 2-wire


The combined analogue control uses the combination of the DEIF unit’s analogue output and a speed setting
potentiometer.

The advantage of this solution is the possibility to do basic speed settings with the potentiometer and there-
after let the DEIF unit take over.

If the potentiometer is only used for initial adjustments, it can be replaced by fixed resistors
once the adjustment is done.

The connection to DEIF equipment is as follows:

AVR
DEIF equipment terminals

EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


IN 1 10 (+) 10 (+) 23 (+) 9 (+)
Pot
IN 2 9 (┴) 11 (┴) 24 (┴) 10 (┴)

DEIF A/S Page 38 of 49


Interfacing DEIF equipment, application AVR interface basic circuits
notes 4189340670 UK

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 3V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
AVR SCM 4.2 SCM 1 GPC/ AGC
IN 1 33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)
R2
Pot
IN 2

DEIF A/S Page 39 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

10. AVR interfaces

This chapter refers to the chapter 8 diagrams for terminals and resistor values unless other-
wise stated.

10.1 AVK Cosimat AVR


This applies for all types of the AVK COSIMAT:

The COSIMAT has an auxiliary input for external equipment, which accepts 0…10V DC signals. As the input
only accepts positive signals, a diode is needed to prevent negative signals:

COSIMAT
DEIF equipment terminals

EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


n (+) 10 (+) 10 (+) 23 (+) 9 (+)
M/m (-) 9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 10V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
COSIMAT SCM 4.2 SCM 1 GPC/ AGC
N (+) 33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)
500Ω

M/m (-)

Adjustment:

● The R4 potmeter in the COSIMAT (18-turn) must be adjusted to "min.".


● Use manual control to raise the DEIF equipment to +10V DC.
● Start the generator and use R4 to set the max. allowable voltage.
● Adjust the integration time of the DEIF equipment if needed.

DEIF A/S Page 40 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

10.2 Basler Electric AEC63-7 AVR

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
7 (+) 6 0Ω 80 Ω

Voltage droop set to 4%.

10.3 Basler Electric digital excitation control system (DECS)


The DECS accepts binary inputs directly on terminals 6D (lower voltage), 7 (common) and 6U (increase volt-
age).
To increase voltage: Connect 6U to 7.
To decrease voltage: Connect 6D to 7.

Also analogue signals can be used (+/-10V DC or 4-20 mA range):

Direct analogue control


Input terminals Resistor values for the +/-10V DC range
IN 1 IN 2 R1 R2
A (+) B 0Ω 150 Ω

10.4 Basler Electric SR 4A/6A/8A/9A/32A AVR


The Basler SR series is intended for a 2-wire 175 Ω potentiometer input.

The connection to DEIF equipment is as follows:

Combined analogue control, 2-wire


Input terminals Resistor values
IN 1 IN 2 Pot R2
7 (+) 6 175 Ω 150 Ω

10.5 Basler Electric SSR 32-12, 63-12, 125-12 AVR


The SSR series works in an "inversed" way, meaning that the standard DEIF way cannot be used.

The input used is the "ext. adj.".

The diode mounted in the connection prevents positive voltages from being sent to the SSR unit. As both
EPQ/EPN and Delomatic/PPU/GPC/AGC/BGC are using bipolar galvanically separated outputs, this is not a
problem.

When adjusting the generator voltage initially, adjust the (internal) idle voltage to 25% above nominal. The
DEIF units will then bring the voltage down to nominal level when activated:

DEIF A/S Page 41 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

SSR
DEIF equipment terminals

EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


24 10 (+) 10 (+) 23 (+) 9 (+)
23 1kΩ 9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 5V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
SSR SCM 4.2 SCM 1 GPC/ AGC
24 33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)
250Ω

23 1kΩ

10.6 Caterpillar® VR3


Set the EPQ/EPN output to +/-5V DC.

The 100 Ω resistor is there to dampen the signal.

DEIF equipment terminals


VR3 EPQ96 EPQ96-2 EPN - 110DN IOM 2xx

9 10 (+) 10 (+) 23 (+) 9 (+)


4 100 Ω
7 9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 1V DC range:

DEIF A/S Page 42 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


VR3 BGC
SCM 4.2 SCM 1 GPC/ AGC

9 33 (+) 31 (+) 70 (+) 64 (+)


4 50 Ω
35 (┴) 32 (┴) 71 (┴) 63 (┴)
7

10.7 Caterpillar® VR6


Set the EPQ/EPN output to +/-5V DC.

The 100 Ω resistor is there to dampen the signal.

DEIF equipment terminals


VR6 EPQ96 EPQ96-2 EPN - 110DN IOM 2xx

9 10 (+) 10 (+) 23 (+) 9 (+)


6a 100 Ω
7 9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 1V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


VR6 BGC
SCM 4.2 SCM 1 GPC/ AGC

9 33 (+) 31 (+) 70 (+) 64 (+)


6a 50 Ω
35 (┴) 32 (┴) 71 (┴) 63 (┴)
7

10.8 Caterpillar® DVR


The DVR 2-wire input gives an increasing generator voltage with increasing resistance.

Set the EPQ/EPN output to +/-5V DC.

DEIF A/S Page 43 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

DVR
DEIF equipment terminals

EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


45 (com) 10kΩ 10 (+) 10 (+) 23 (+) 9 (+)
7 (+) 9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 5V DC range:

DEIF equipment terminals

DELOMATIC DELOMATIC PPU/ PPM/


BGC
DVR SCM 4.2 SCM 1 GPC/ AGC
45 (Com) 10kΩ 33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)
250Ω

7 (+)

10.9 Caterpillar® CDVR


The CDVR accepts binary inputs for voltage up/down control or analogue signals.

Binary inputs:

CDVR

P9-4 (Lower)

P9-5 (Raise)

P9-6 (common)

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
P12-6 P12-3 0Ω 500 Ω

DEIF A/S Page 44 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

10.10 Leroy Somer type R250/R438/R448/R449 LS/C or D


AVR
The type R250/R438/R448/R449 does not have a terminal strip, but uses automotive spade connectors.

As the external control is 2-wire potentiometer, the following circuit must be used:

Circuit as described by Leroy Somer:

Terminal strip ST 4

Spade connectors

Bottom of AVR, as mounted in generator

470Ω

Using DEIF equipment:

Terminal strip ST 4

Spade connectors

Bottom of AVR, as mounted in generator

DEIF equipment terminals

EPQ96 EPQ96-2 EPN - 110DN IOM 2xx


10 (+) 10 (+) 23 (+) 9 (+)
9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

The output from the electronic potentiometer is set to 1V DC.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 1V DC range:

DEIF A/S Page 45 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

Terminal strip ST 4

Spade connectors

Bottom of AVR, as mounted in generator

50Ω
DEIF equipment terminals
DELOMATIC DELOMATIC PPU/ PPM/
BGC
SCM 4.2 SCM 1 GPC/ AGC
33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)

10.11 Leroy Somer type R610 AVR


As a standard, R610 is not equipped with external control possibilities. There is, however, an option for both
potentiometer and binary control of voltage/reactive power/cos φ control.

We recommend using "Digital pot U/P.F. Optional Card". When this card is fitted, terminals 35, 36 and 37 are
used as follows:

U/VAr/cos φ R610 terminal block

Up 35

Down 36

Com. 37

10.12 Leroy Somer type R610 3F AVR


The R610 3F external voltage control is intended for a 3-wire 10 kΩ potentiometer. Terminals used are 21, 22
and 23. The DEIF equipment is connected like this:

Combined analogue controls, 3-wire


Input terminals Resistor values
IN 1 (+) IN 2 (0) IN 3 (signal) Pot R1 R2
21 (+) 23 (-) 22 (ln) 10 kΩ 0Ω 250 Ω

10.13 Marathon Magnamax/DVR 2000C AVR


The Magnamax/2000C accepts binary inputs directly on terminals 6D (lower voltage), 7 (common) and 6U
(increase voltage).
To increase voltage: Connect 6U to 7.
To decrease voltage: Connect 6D to 7.

DEIF A/S Page 46 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

10.14 Marelli Mark 1 AVR

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
6 (+) 8 (-) 0Ω 150 Ω

10.15 Marelli M25FA502A


The M25FA502A requires a +/-2.5V DC signal.

The signal must not exceed 3V DC in either direction. Set EPQ/EPN range to 2.5 V.

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
Q (+) P (-) 0Ω 125 Ω

10.16 Mecc-Alte S.R.7/2

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
7 (+) 5B (-) 0Ω 470 Ω

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

Output voltage range must be set to 9 V. Since the offset required is -80%, a special version of
EPQ/EPN is needed.

10.17 Mecc-Alte type U.V.R. AVR


The Mecc-Alte U.V.R. has no terminal numbers, but the connection for external voltage control is placed next
to the 50/60 Hz selection connection:

DEIF A/S Page 47 of 49


Interfacing DEIF equipment, application AVR interfaces
notes 4189340670 UK

DEIF equipment terminals


U.V.R.
60Hz EPQ96 EPQ96-2 EPN - 110DN IOM 2xx
10 (+) 10 (+) 23 (+) 9 (+)
9 (┴) 11 (┴) 24 (┴) 10 (┴)

EPQ96-2 terminals 11-12 must be linked (connected together) to activate the internal 500 Ω
shunt in order to create a voltage output.

Output voltage range must be set to 9 V. Since the offset required is -80%, a special version of
EPQ/EPN is needed.

DELOMATIC/PPU/GPC/AGC/BGC output is +/-20 mA, so a resistor is needed to convert into 5V DC range:

DEIF equipment terminals


U.V.R.
DELOMATIC DELOMATIC PPU/ PPM/
60Hz BGC
SCM 4.2 SCM 1 GPC/ AGC
33 (+) 31 (+) 70 (+) 64 (+)
35 (┴) 32 (┴) 71 (┴) 63 (┴)
470Ω

Set DEIF equipment output offset to -80%.

10.18 Stamford Newage type MA325, MA327, MX321, MX341,


SR465, SX421 and SX440
These AVRs have an auxiliary input (terminal A1 and A2), which accepts voltage signals (+/-5 V). Therefore
the DEIF equipment can usually be connected directly:

Direct analogue control


Input terminals Resistor values
IN 1 IN 2 R1 R2
A1 (+) A2 (-) 0Ω 250 Ω

Stamford Newage type SX460 has no A1 and A2 terminals and cannot be controlled.

DEIF A/S Page 48 of 49


Interfacing DEIF equipment, application Troubleshooting
notes 4189340670 UK

11. Troubleshooting

Problem indication Problem cause Remedy


Load sharing or parallel with mains power control No speed droop on gen- Apply 3-4% speed droop
unstable. erators. on prime mover gover-
Synchronisation OK. nor.
Single generator running frequency control OK.
Load sharing or parallel with mains voltage (VAr) No voltage droop on Apply 3-4% voltage
control unstable. generators. droop on generator
Synchronisation OK. AVR.
Single generator running voltage control OK.
Uni-line active power load sharing units only: Faulty connection of Correct connections.
Load sharing or parallel with mains power control measuring voltage and/ Voltage on L1 and L2,
unstable. or current transformer in- current transformer in
Synchronisation OK. put. L1.
Single generator running frequency control OK.
Speed droop OK.
Uni-line active power load sharing units only: Load sharers have been Remount the load shar-
Load sharing stable but not equal. mounted to control the ers to match the genera-
Synchronisation OK. wrong size generators tors. The load sharers
Single generator running frequency control OK. (can happen in systems are preconfigured for a
Speed droop OK. with different size of specific generator.
generators).
Uni-line reactive power load sharing units only: Faulty connection of Correct connections.
Load sharing or parallel with mains VAr control un- measuring voltage and/ Voltage on L1 and L2,
stable. or current transformer in- current transformer in
Synchronisation OK. put and/or voltage trans- L1, voltage transducer to
Single generator running voltage control OK. ducer. US-line (term. 38 (+) and
Voltage droop OK. 39 (-)).
Uni-line reactive power load sharing units only: VAr load sharers have Remount the VAr load
VAr load sharing stable but not equal. been mounted to control sharers to match the
Synchronisation OK. the wrong size genera- generators. The VAr
Single generator running voltage control OK. tors (can happen in sys- load sharers are precon-
Voltage droop OK. tems with different size figured for a specific
of generators). generator.
Generator not able to take load to 100%. Initial setting of speed See "Initial setting of
governor not correct. speed governor/AVR".
Generator not able to take load to 100%. Analogue output from Increase the full scale
DEIF equipment has too value. This is mostly a
low output range. case when using elec-
tronic potentiometers.
Speed decreases when increase was expected (re- Relay outputs "up" and Swap connections.
lay outputs). "down" reversed.
Speed decreases when increase was expected (an- Outputs "+" and "-" re- Swap connections.
alogue output). versed.

DEIF A/S Page 49 of 49

You might also like