You are on page 1of 7

Cryogenic

Storage of

PSD 162
Gases

Continuing Education from Plumbing Systems & Design

NOVEMBER 2009

PSDMAGAZINE.ORG
CONTINUING EDUCATION

Cryogenic Storage of Gases


This chapter describes the bulk storage of cryogenic liquids used for In locating the tanks on a facility site, enough room must be allowed
laboratory purposes. For the purposes of this manual, the definition of for a delivery truck to approach the tanks closely. There must be easy
a “cryogenic gas” is any gas in a liquid state at a temperature of –20°F access to the tank because an operator must vent gas from the hose
(–28.9°C) or lower. There are two reasons to consider the cryogenic connection of the truck to the storage tank by means of a manual vent
storage of gases. The first is where a facility uses a large volume of gas before filling can start. Two connections to the cryogenic tank are pro-
and desires storage on site for practical and economical reasons. The vided. One is to the top of the tank in the vapor space and the other is in
second is where a cold liquid is required for research, cooling, and the lower portion of the tank in the liquid space. This allows the operator
other purposes. to adjust the pressure in the tank during filling. Filling from the bottom
compresses the vapor at the top, increasing pressure. Filling from the
BULK STORAGE vapor space lowers the pressure because some of the vapor condenses
When the volume of gases expected to be used is large enough, it is and turns back to liquid, thereby reducing the volume of vapor. If filling
often eco­nomical and practical to store these gases as cryogenic liq- to a specific pressure, a pressure gauge shall be provided.
uids. The reason for this is volume. The cold liquid occupies consider- One important factor to consider is that there will be leakage of gas-
ably less volume than a comparable quantity of compressed gas. The eous product from the cryogenic tank if no liquid product is withdrawn
most commonly used gases stored as cryogenics are nitrogen, argon, for a period of time.
and oxygen. Also available but less commonly used are carbon dioxide, Each tank is insulated and is not intended to have a high internal
hydrogen, and helium. pressure. The rising of pressure inside the tank resulting from internal
vaporization of product will raise the pressure higher than the working
CODES AND STANDARDS pressure and will have to be vented to atmosphere from the relief vent.
The following codes are used in the fabrication of cryogenic liquid stor- For comparison purposes only, the percent of liquid oxygen (LOX) lost
age tanks: in 1 day is included in Table 1.
1. Underwriters Laboratories, UL-644.
2. ASME Code for Unfired Pressure Vessels. Dewers
3. NFPA 50, 50A, and 50B. “Dewers” are smaller, insulated tanks used to store smaller quantities
4. NFPA 99, Health Care Facilities, is often used as a of cryogenic gases in individual laboratories or outdoors if required for
standard for laboratories. reasons of space. They can be manifolded together for larger storage
capacities if desired. Standard-size dewers are illustrated in Figure 1
SYSTEM COMPONENTS listed under “low-pressure stainless-steel drums.”
The major components of a cryogenic storage system include the bulk-
storage tank that contains a gas in liquid form, a vaporizer if a gas is Sizing the Large Bulk Tank
desired, and the piping network conveying either gas or liquid to the The amount of liquid to be stored is based on the volume of gas expected
point of use. A vaporizer is directly connected to the storage tank and to be used between deliveries. The delivery schedule is a compromise
is used to convert the liquid gas to its gaseous state. Storage tanks are between that preferred by the supplier and that preferred by the client.
categorized as either large bulk tanks or smaller dewers. The most often suggested period of time between deliveries ranges from
once to twice a month. Proceed with the sizing as outlined below:
TANKS 1. Determine the proposed usage of each gas per day, shift, or week as
Large Bulk Tanks closely as possible. This is best done based on past experience. If the
Refer to Table 1 for standard large-tank sizes. Large tanks are highly installation is new, or this information is not available, calculate the
insulated and can be installed either horizontally or vertically. The expected usage based on the total number of outlets and connected
vertical position is most common because the vertical tank occupies equipment, the quantity of gas used by each, and the amount of
less site area than a horizontal one does. Another reason is that the time each day each is expected to be used.
vertical tank presents less wetted area for the liq­uid to vaporize, and
it is desirable to keep the stored liquid in that state as long as it is pos- 2. Contact the intended supplier (or interview several if one supplier
sible. Tank dimensions vary slightly depending on horizontal or verti- is not be­ing used at the present time) to obtain the intended deliv-
cal installation, but the greatest difference is only about 6 in. in length ery schedule and price. Agree on a tank size based on a trade-off.
for the largest tanks. The horizontal tank is slightly smaller and lighter. between keeping the tank as small as possible and having a reason-
All capacities are given in gallons of water. Many manufacturers have able supply between deliveries. A mini­mum of 2 weeks between
similar lines of tanks, with some stan­dard sizes having a capacity as low supplies is a good starting point. Once a month is also a commonly
as 300 gal. All tanks are ASME rated as unfired pressure vessels. used period of time.

Reprinted from Pharmaceutical Facilities Handbook, Chapter 6: “Cryogenic Storage of Gases,” by Michael Frankel.
© American Society of Plumbing Engineers, 2004.

2  Plumbing Systems & Design  NOVEMBER 2009 WWW.PSDMAGAZINE.ORG


will raise the pressure higher than the working pressure and will have to be vented
to atmosphere from the relief vent. For comparison purposes only, the percent of
liquid oxygen (LOX) lost in 1 day is included in Table 6-1.
Table 1 Cryogenic storage tank dimensions
Normal
Nominal Working Nominal Evaporation
Capacity, Pressure, Tare Rate, % /
gal Diameter Height psig Weight, lb day LOX
315 4’-0” 8’-1” 250 2,600 0.90
525 4’-0” 11’-1” 250 3,600 0.55
900 5’-0” 11’-7” 250 5,500 0.40
1,500 5’-6” 15’-0” 250 9,100 0.35
1,500 5’-6” 15’-8” 150 10,800 1.5
1,500 5’-6” 6’-6” 150 11,000 1.5
3,000 8’-0” 16’-7” 50 14,900 0.17
3,000 8’-0” 16’-7” 250 20,360 0.50
3,000 8’-0” 16’-4” 250 17,340 0.17
6,000 8’-0” 9’-0” 250 34,500 0.30
6,000 8’-0” 27’-0” 50 19,900 0.15
9,000 9’-6” 30’-9” 250 53,500 0.26
9,000 9’-6” 30’-9” 250 51,300 0.10
11,000 9’-6” 35’-7” 75 34,900 0.10
11,000 9’-6” 35’-7” 250 65,900 0.25
11,000 9’-6” 35’-7” 250 60,000 0.10
13,000 10’-0” 36’-7” 72 41,000 0.10
13,000 10’-0” 36’-7” 250 68,300 0.10
13,000 10’-0” 36’-7” 250 74,100 0.25
Source: Minnesota Valley Engineering, Inc.
Note: LOX = Liquid oxygen

Table 2 Conversion of 1 gallon of liquid to gas


Gas Ft3/Gal
nitrogen 93
oxygen 115
argon 112
carbon dioxide 92
helium 100
hydrogen 113
Note: At atmospheric pressure.

3. Calculate the actual usable capacity of the storage tank(s) based


on the proposed usage per day multiplied by the time, in days,
between deliveries. Use Table 2 to convert gallons of liquid to
Figure
Figure 1 Cryogenic 6-1 Cryogenic
container dimensions.Container Dimensions
Chapter 6 — Cryogenic Storage of Gases
cubic feet of gas.
155
4. Add 25% to the actual usable capacity found in step 3. This figure
allows 15% for additional empty volume used as vaporization space
above the allowable high liquid level when the tank is full andPharmaceutical
10% Facilities Handbook 2004.indd 155 7/22/2005 3:30:39

for the additional volume occupied by the liquid gas present as a


reserve capacity. This 10% should allow for a 2-day reserve supply of
liquid to be in the tank when the low-level alarm point is reached,
giving enough time for the supplier to send more product. An abso-
lute low-level point should be 5% of capacity, which will trigger an
emergency call to the supplier.

5. Another point to consider when filling a tank is that the pressure of


nitrogen varies with temperature. Refer to Figure 2 for the relation-
ship of density and pressure. The higher the pressure, the more Figure 6-2 Vapor Pressure Curve for Nitrogen
liquid nitrogen can be loaded into the tank. Figure 2 Vapor pressure curve for nitrogen.
poured over a 6-in. layer of crushed stone or gravel. The thickness of the
pad depends on the capacity of the tank, and the pad should be reinforced.
6. Vertical tanks must be installed on a concrete pad. The strength of layer
The of crushed stone
reinforcement shouldorbegravel. The thickness
wire mesh of the
for small pads andpad depends
rebar each way
the concrete should be a minimum of 3000 psi. The size of the pad (top
on theandcapacity
bottom) offorthe
larger pads.
tank, andSince it may
the pad be required
should that the tanks
be reinforced. The be
tested with water at some time during their lives, water weight must be used
should be a minimum of 6 in. larger than the diameter of the tank, reinforcement should be wire mesh for small pads and rebar each
to determine the weight of the filled tank, which in turn is used to determine
and if there is ad­ditional equipment (e.g., a vaporizer), the pad waytank
the (topfoundation
and bottom) for larger To
requirements. pads. Sincethe
estimate it may
totalbe required
weight thatto be
required
should be enlarged accordingly. Manufacturers’ recommendations supported,
the tanks be find the tare
tested (empty)
with waterweight
at some of the
timetank and use
during thelives,
their capacity as if
water
indicate that the minimum bearing strength of the soil should be itweight
is filledmust
with be
water. For a quick estimate, multiply the capacity,
used to determine the weight of the filled tank, in gallons,
by 15.
2000 psi. In addition, the concrete should be poured over a 6-in. which in turn is used to determine the tank foundation require-
Tank-pad thickness should conform to these minimums:
Less than 900-gal capacity 12 in. thick
1500 to 3000-gal capacity 15 in. thick
6000 to 9000-gal capacity NOVEMBER 2009  Plumbing Systems & Design  3
18 in. thick
11,000-gal capacity 21 in. thick
Chapter 6 — Cryogenic Storage of Gases
have good drainage or be provided with a drainage inlet.
CONTINUING EDUCATION:
A typical schematic detail of a bulkCryogenic Storage
storage tank and vaporizer of Gases
installation is shown
in Figure 6-4.

Figure 6-4 Detail of Large-Scale Storage Tank


Figure 4 Detail of large-scale storage tank.

Model No. PRESSURE-RELIEF VALVES


Nominal Pressure-relief
Flow
250 SCFH 500 SCFH 1000 SCFH 1500 SCFH 2000 SCFH 5000 SCFH 7. Cryogenicvalves
storagefortanks
over-pressure
are actuallyprotection mustone
two tanks, be provided
inside the in all cases
where gases or cryogenic liquids could become trapped between valves. For oxygen
Capacity other. The annulus is filled with insulation and a vacuum in order
service, a condition known as “adiabatic compression” could occur. This is a situa-
Part No. 97-1450-9 97-1451-9 97-1454-9 97-1452-9 97-1453-9 97-1455-9 to provide
Drwg. No. D-9427 C-9414 C-12996 D-9246 D-12993 D-12757 tion where a gas aathigh
highdegree
pressureofescapes
insulation.
into aStorage
region ortanks
pipeused only pressure
at a lower for
No. and then gas supply an
encounters areobstruction;
normally constructed
the temperaturefor aofworking pressurerises
the gas suddenly ranging
to a very
Length of Four 3' Four 6' Six 6' Nine 6' Twelve 6' Thirty 6' high between
temperature.
150This
andcould causewith
250 psig, auto-ignition of the pipe.
a pressure-relief Forset
valve noncombustible
to 10%
Elements or nonflammable gases,pressure.
the pressure of the
Shipping Wt. 80# 150# 175# 250# 310# 510# over the working If the lowliquid turned towere
temperature gas bynot
absorbing
main- heat
could exceed the burst pressure of the pipe.
Maximum tained, the liquid gas introduced into the tank during filling would
Working 350 psig 350 psig 350 psig 350 psig 350 psig 350 psig Pressure-relief valves shall be installed on a thermal standoff. They must be sized
vaporize instantly and the pressure inside the tank would quickly
Pressure to vent the amount of gas needed to lower the pressure inside the tank or piping
6063 6063 6063 6063 6063 6063 riseAabove
system. the working
pressure-relief valvepressure. If a filled
shall be installed tank isany
between nottwo
used for aWhen the
valves.
Material Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum period
PRV goes off,of time,not
it does usually about
reset at 2 days,
the set approximately
pressure but, rather, at½a of 1% of the
pressure about 20
A 7½" 8 1⁄8" 10 3⁄8" 14 3⁄8" 20 5⁄8" 35 3⁄8" psig lower. Thisof may
contents thecause
tank excessive lossbe
per day will of gas
lostifthrough
it is allowed to happen
the relief valveregularly.
in
B 14" 10 3⁄8" 14 3⁄8" 16 5⁄8" 16 5⁄8" 29 1⁄8" Another type
C — — — — — 17 5⁄8"
order to of relief valve
maintain thefound on storage tanks is a rupture disk. This device is
set pressure.
set to break at a predetermined pressure and cannot be reset; it is considered an
D 6 ¼" 6 ¼" 6 ¼" 12½" 6 ¼" 18 ¾" emergency vent and is used when all other pressure-relief devices have failed to re-
E ⁄8" ⁄16" 2 1⁄16" ⁄16" 7 3⁄16" 8 1⁄16" lieve Another
pressure.option for havingof a storage-tank
tank are lostsystem installed
ruptureis to allow
5 15 15
All the contents the when the disk is used.
F 3 7⁄8" 2 1⁄16" 15
⁄16" 2 1⁄16" 2 1⁄16" 1 13⁄16" the supplier to size, design, and install the tank based on a perfor-
G 11 7⁄16" 12 ¼" 18 3⁄8" 18 3⁄8" 18 3⁄8" 30 7⁄8" PIPE MATERIALS AND INSULATION
mance
When specification.
a cryogenic liquid It
is is then the
desired, responsibility
it must be piped fromof thethesupplier
point ofto size to
origin
H 11 7⁄16" 12 ¼" 12 1⁄8" 18 3⁄8" 24 5⁄8" 37 1⁄8"
I 42" 84 3⁄16" 84 3⁄8" 84 3⁄8" 90 3⁄8" 90 3⁄16" thethe storage
point of usesystem based
with the leaston the provided
amount usage
of heat loss criteria;
possible. if any mistake
In cryogenic work, it
J 48" 89 9⁄16" 89 ¾" 89 ¾" 95 ¾" 95 9⁄16" is made, it to
is impossible is separate
the supplier’s, assuming
the piping materialthe usage
from in­formation
the insulation is correct.
because, in most
K 7
⁄16" dia. 17
⁄32" dia. 17
⁄32" dia. 17
⁄32" dia. 17
⁄32" dia. 17
⁄32" dia. cases, the method of retarding heat loss from the network is an integral
In many cases it is also possible to have the installation of the storage part of the
3
⁄8" MPT pipe. The material of the piping system and the insulation used to keep the heat
tank and equipment paid for by the supplier and the cost paid out over
Female 1" NPT 1" NPT 1" NPT 1" NPT 1" NPT loss to a minimum must be a major consideration.
L coupling, Male half Male half Male half Male half Male half 7 to 10 years along with the cost of the gases.
located on nipple nipple nipple nipple nipple
top of unit The information required is as follows:
Figure 6-3 Ambient Air Vaporizers
1. Location of the facility to determine outside air conditions. If site
Figure 3 Ambient air vaporizers. 160 ranges are available, provide this also.
temperature

159
ments. To estimate the total weight required to be supported, find 2. Peak quantity of gas to be used in cfm and cfh (L/min or L/h). Indi-
the tare (empty) weight of the tank and use the capacity as if itPharmaceutical
is cate
Facilities peak
Handbook usage
2004.indd 160 per day and week if possible. If this quantity is not7/22/2005 3:30:41

filled with water. For a quick estimate, multiply the capacity, in gal- obtainable, then indicate the use to which the gas will be put and
Pharmaceutical Facilities Handbook 2004.indd 159 7/22/2005 3:30:40 PM
lons, by 15. the total number of outlets or stations in the facility.
Tank-pad thickness should conform to these minimums:
• Less than 900-gal capacity 12 in. thick 3. Will the use of gas be constant or intermittent? If only a portion of
• 1500 to 3000-gal capacity 15 in. thick the use is constant, the use is considered constant. This information
• 6000 to 9000-gal capacity 18 in. thick is used to deter­mine if a vaporizer is necessary and to size it based
• 11,000-gal capacity 21 in. thick on usage.
• 13,000-gal capacity 24 in. thick
Large horizontal tanks usually have piers located 8 ft 0 in. from 4. Required pressure range of the gas.
each end of the tank. Smaller tanks have supports located ¼ of that
distance from each end. It is necessary to design foundations based 5. The proposed location of the tank on the site. In determining this
on the weight of the tank and contents spread between the two location, consideration must be given to easy road access to the
piers. Vertical tanks are attached to their foundations by bolts con- location by the supply truck.
necting the legs on the tanks to the concrete pad. The bolts are sup-
plied by the manufacturer and installed by the contractor supplying 6. If the gas is .flammable or reactive, separation of the tank from the
the pad. The specifications should require that the contractor install building and any other material storage must be allowed for.
the tanks based strictly on manufacturers’ requirements and under
their supervision. THE VAPORIZER
Bulk gases are stored as liquids and must be converted to gases prior to
use. If the volume used by the facility is large, not enough liquid can be

4  Plumbing Systems & Design  NOVEMBER 2009 WWW.PSDMAGAZINE.ORG


converted to gas inside the insulated storage tank to satisfy demand. To There are two general classes of preinsulated piping: double-wall
convert the necessary volume of liquid to gas, a device called a “vapor- piping with the annulus vacuum insulated and the single-wall piping
izer” is required. with the pipe exterior thermally insulated. Vacuum-insulated piping
The most often-used vaporizer has no moving parts and uses ambi- is double walled. The vacuum could be either a static vacuum, where
ent air to warm the cryogenic liquid as it passes through a long length the annulus vacuum is factory accomplished during manufacturing,
of finned tubing. The vapor­izer is installed close to the storage tank, or a dynamic vacuum applied to the annulus by continuous vacuum
usually on the same pad as the storage tank. Each manufacturer has pumping.
standard size units that are selected by the scfh, type of cryogenic liquid • Double-wall piping with annulus under static vacuum This
to be vaporized, and the lowest expected outdoor temperature. For typ- double-wall system is usually manufactured from schedule 40, 304
ical sizes of atmospheric vaporizers, refer to Figure 3. If the expected SS with nonmetallic spacers used to keep the piping apart. The pipe
vol­ume is large, a vaporizer using an additional source of heat obtained is manufactured in sections with the vacuum applied to the annulus
from steam, electricity, or fuel gas may be required. during the manufacturing process and simultaneously sealed. Pipe
The most common material for the vaporizer is aluminum. If high joints are assembled using a mechanical “bayonet” joint with an
purity is required, stainless steel is used. For preliminary sizing, based O ring to connect the sections, which consist of a long male sec-
on a temperature of 70°F and 70% relative humidity, each 8 ft 0 in. tion inserted into a female section and physically connected with a
length of 8-in. aluminum tubing with 8 fins/ft will vaporize 500 cfh. bolted flange. This provides a long heat-leakage path.
Manufacturer’s have multiple methods of sizing vaporizers. Two items
are necessary for sizing; the lowest mean ambient outside temperature • Double-wall piping with annulus under dynamic vacuum This
for 72 hr and the flow rate of the gas. Aluminum vaporizers are rated at double-wall system is often manufactured from corrugated copper
400 psig, with stainless steel being rated higher. tube with nonme­tallic spacers used to keep the piping apart. Pipe
The area under the vaporizer is constantly wet. This is due to the ice joints are assembled using a bayonet joint as previously discussed
formed on the fins melting and dripping to the ground. Because of this, or a brazed joint using a silver braz­ing alloy. A connection to the
the immediate area must have good drainage or be provided with a outer double-wall pipe provides the inlet to a vacuum pump, which
drainage inlet. is used to produce the vacuum-insulating pressure.
A typical schematic detail of a bulk storage tank and vaporizer instal-
lation is shown in Figure 4. • Single-wall pipe with exterior thermal insulation Typical pipe is
most of­ten made up of copper water tube (ASTM B88), type K or
PRESSURE-RELIEF VALVES L, or stainless steel (type ASTM 304 or 316) preinsulated with high
Pressure-relief valves for over-pressure protection must be provided density Polyethylene (PE) of 2 lb/ft2 from 1½ to 6 in. in thickness.
in all cases where gases or cryogenic liquids could become trapped Fittings are wrought copper. The pipe is jacketed with PVC 0.06 in.
between valves. For oxygen service, a condition known as “adiabatic thick. The piping is preinsulated with space left between pipes so
compression” could occur. This is a situa­tion where a gas at high pres- joints can be observed. Additional insulation is added after the pipe
sure escapes into a region or pipe at a lower pressure then encounters has completed testing. Copper pipe is joined by brazing, SS pipe by
an obstruction; the temperature of the gas suddenly rises to a very high welding.
temperature. This could cause auto-ignition of the pipe. For noncom-
bustible or nonflammable gases, the pressure of the liquid turned to Pipe Sizing Methods
gas by absorbing heat could exceed the burst pressure of the pipe. Cryogenic piping is sized based on the flow rate and head loss for
Pressure-relief valves shall be installed on a thermal standoff. They the liquid. Because the specific gravity of the liquid is almost, but not
must be sized to vent the amount of gas needed to lower the pres- always, less than that of water, water charts can be used for velocity and
sure inside the tank or piping system. A pressure-relief valve shall be friction loss with the assurance that there is a slight safety factor. As an
installed between any two valves. When the PRV goes off, it does not example, the specific gravity of liquid nitrogen is 0.81.
reset at the set pressure but, rather, at a pressure about 20 psig lower. The available vapor pressure in the storage tank can be adjusted by
This may cause excessive loss of gas if it is allowed to happen regularly. setting the relief valve to a higher pressure, which is often required to
Another type of relief valve found on storage tanks is a rupture disk. overcome any static lift and friction loss through the piping. The vapor-
This device is set to break at a predetermined pressure and cannot be pressure curve for nitrogen is given in Figure 2.
reset; it is considered an emergency vent and is used when all other A combination of vapor and liquid in the same pipe is called a “two-
pressure-relief devices have failed to relieve pressure. All the contents phase flow.” The flow rate of a two-phase flow is reduced compared to
of the tank are lost when the rupture disk is used. that of liquid flow alone. For laboratories that use small amounts of
cryogenic liquid for freezer cooling or to fill dewers, two-phase flow is
PIPE MATERIALS AND INSULATION not important because only a small amount of liquid is desired after the
When a cryogenic liquid is desired, it must be piped from the point of gas is eliminated. There is a special fitting available for installation on
origin to the point of use with the least amount of heat loss possible. In the discharge pipe to separate the vapor from the liquid. It is important
cryogenic work, it is impossible to separate the piping material from for facilities where there is an open-end discharge to provide adequate
the insulation because, in most cases, the method of retarding heat ventilation in the room to avoid an accumulation of gas.
loss from the network is an integral part of the pipe. The material of A typical detail of a large-scale cryogenic storage tank is illustrated
the piping system and the insulation used to keep the heat loss to a in Figure 4.
minimum must be a major consideration.

NOVEMBER 2009  Plumbing Systems & Design  5


CONTINUING EDUCATION: Cryogenic Storage of Gases

Continuing Education from Plumbing Systems & Design


Do you find it difficult to obtain continuing education units
(CEUs)? Through this special section in every issue of PS&D, ASPE
can help you accumulate the CEUs required for maintaining your
About This Issue’s Article
Certified in Plumbing Design (CPD) status. The November 2009 continuing education article is
“Cryogenic Storage of Gases,” Chapter 6 of Pharmaceutical
Facilities Handbook by Michael Frankel, CPD.
Now Online! This chapter describes the bulk storage of cryogenic
The technical article you must read to complete the exam is located liquids used for laboratory purposes. There are two
at www.psdmagazine.org. Just click on “Plumbing Systems & Design
reasons to consider the cryogenic storage of gases. The
Continuing Education Article and Exam” at the top of the page. The
following exam and application form also may be downloaded from first is where a facility uses a large volume of gas and
the website. Reading the article and completing the form will allow desires storage on site for practical and economical
you to apply to ASPE for CEU credit. If you earn a grade of 90 percent reasons. The second is where a cold liquid is required for
or higher on the test, you will be notified that you have logged research, cooling, and other purposes.
0.1 CEU, which can be applied toward CPD renewal or numerous You may locate this article at www.psdmagazine.org.
regulatory-agency CE programs. (Please note that it is your responsi- Read the article, complete the following exam, and submit
bility to determine the acceptance policy of a particular agency.) CEU your answer sheet to the ASPE office to potentially receive
information will be kept on file at the ASPE office for three years.
0.1 CEU.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using informa-

PSD 162
tion from other materials may result in a wrong answer.

CE Questions — “Cryogenic Storage of Gases” (PSD 162)


1. Cryogenic gases are gases in a liquid state of ________ or lower. 7. The strength of the concrete pad under a vertical tank should be
a. 20°F at least ________.
b. -20°F a. 3,000 psi
c. 28.9°F b. 2,500 psi
d. -28.9°F c. 2,000 psi
d. none of the above
2. Which of the following codes pertains to the fabrication of
cryogenic liquid storage tanks? 8. Which of the following helps provide a high degree of
a. NFPA 99 insulation in the annulus of the tank?
b. NFPA 50A a. insulation
c. UL-644 b. vacuum
d. all of the above c. gravel
d. both a and b
3. What is the working pressure of a 6,000-gallon, 8-foot-diameter,
9-foot-tall cryogenic storage tank? 9. What is the most common material for a vaporizer?
a. 250 psig a. stainless steel
b. 150 psig b. aluminum
c. 75 psig c. copper
d. 50 psig d. concrete
4. The abbreviation of liquid oxygen is ________. 10. What do you need to know to size a vaporizer?
a. LO2 a. gas flow rate
b. LOX b. 72-hour lowest mean ambient outside temperature
c. LiqO2 c. both a and b
d. LiOx d. none of the above
5. 1 gallon of liquid helium equals ________ ft3/gal of gas. 11. Which of the following is used as an emergency vent when all
a. 113 other relief devices have failed?
b. 112 a. rupture disk
c. 100 b. pressure-relief valve
d. 93 c. manual vent
d. vaporizer
6. When the liquid level in the tank reaches ________ of capacity,
an emergency call to the supplier will be triggered. 12. Cryogenic pipe sizing is based on ________.
a. 25 percent a. liquid flow rate
b. 15 percent b. liquid head loss
c. 10 percent c. liquid volume
d. 5 percent d. both a and b

6  Plumbing Systems & Design  NOVEMBER 2009 WWW.PSDMAGAZINE.ORG


Plumbing Systems & Design Continuing Education Application Form
This form is valid up to one year from date of publication. The PS&D Continuing Education program is approved by ASPE for up to one
contact hour (0.1 CEU) of credit per article. Participants who earn a passing score (90 percent) on the CE questions will receive a letter
or certification within 30 days of ASPE’s receipt of the application form. (No special certificates will be issued.) Participants who fail and
wish to retake the test should resubmit the form along with an additional fee (if required).
1.  Photocopy this form or download it from www.psdmagazine.org.
2.  Print or type your name and address. Be sure to place your ASPE membership number in the appropriate space.
3.  Answer the multiple-choice continuing education (CE) questions based on the corresponding article found on
www.psdmagazine.org and the appraisal questions on this form.
4.  Submit this form with payment ($35 for nonmembers of ASPE) if required by check or money order made payable to ASPE or credit
card via mail (ASPE Education Credit, 2980 S. River Road, Des Plaines, IL 60018) or fax (847-296-2963).

Please print or type; this information will be used to process your credits.
Name_________________________________________________________________________________________________________
Title __________________________________________________ ASPE Membership No._____________________________________
Organization___________________________________________________________________________________________________
Billing Address_ ________________________________________________________________________________________________
City_ _________________________________________ State/Province_________________________ Zip_______________________
Country_______________________________________________ E-mail_ _________________________________________________
Daytime telephone_ ____________________________________ Fax_____________________________________________________
PE State _ _____________________________________________ PE No._ _________________________________________________

I am applying for the following continuing education credits: ❏ ASPE Member ❏ Nonmember
Each examination: $25 Each examination: $35
I certify that I have read the article indicated above. Limited Time: No Cost to ASPE Member
Payment: ❏ Personal Check (payable to ASPE) $
❏ Business or government check $
❏ DiscoverCard ❏ VISA ❏ MasterCard ❏ AMEX $

Signature If rebilling of a credit card charge is necessary, a $25 processing fee will be charged.
ASPE is hereby authorized to charge my CE examination fee to my
credit card
Expiration date: Continuing education credit will be given
for this examination through November 30, 2010.
Applications received after that date will not be processed. Account Number Expiration date

Signature Cardholder’s name (Please print)


PS&D Continuing Education Answer Sheet
Cryogenic Storage of Gases (PSD 162)
Questions appear on page 6. Circle the answer to each question. Appraisal Questions
Q 1. A B C D Cryogenic Storage of Gases (PSD 162)
Q 2. A B C D 1. Was the material new information for you?  ❏ Yes ❏ No
Q 3. A B C D
Q 4. A B C D 2. Was the material presented clearly?  ❏ Yes ❏ No
Q 5. A B C D 3. Was the material adequately covered?  ❏ Yes ❏ No
Q 6. A B C D
Q 7. A B C D 4. Did the content help you achieve the stated objectives?  ❏ Yes ❏ No
Q 8. A B C D 5. Did the CE questions help you identify specific ways to use ideas presented in
Q 9. A B C D the article?  ❏ Yes ❏ No
Q 10. A B C D
Q 11. A B C D 6. How much time did you need to complete the CE offering (i.e., to read the
Q 12. A B C D article and answer the post-test questions)?

NOVEMBER 2009  Plumbing Systems & Design  7

You might also like