air. The inlet and discharge valve then assume the filling position for The difference in cost between a simplex and a duplex is usually not
a repetition of the cycle. The compressed air can be supplied from an great enough to warrant the specifying of a simplex system. The added
individual or duplex compressor selected for the exclusive operation safety provided by a duplex system is generally worth the nominal
of the pneumatic ejector, or the supply can be taken from the building additional expenditure.
central compressed air system (if available). To determine the head of the pump, add the static head and the fric-
tion head loss in the discharge piping. The static head is measured from
Ejector Pump Sizing (Centrifugal) the low water line in the receiver up to the highest point pumped. The
Use the water supply fixture unit method to determine the flow into friction head loss can be calculated by using Equation 8-7:
the receiver. The following example illustrates the sizing procedure.
Assume 10 flush valve-operated water closets (WC), 4 urinals (UR), (10-1)
10 lavatories (Lav), 2 service sinks (SS), and 6 kitchen sinks (SK) are fLV
h = 2gD
2
The high water level should be maintained at least 3 in. below the
invert of the entering pipe so as not to flood the subdrain piping and
to provide air circulation throughout the system. The low level should
always be maintained at least 6 in. above the bottom of the basin so
that the suction intake of the pump is always covered by water. Verify
this dimension with the manufacturer’s recommendations. Following
the above parameters, the depth of the basin below the invert of the
entering pipe can be determined:
Installation
The criteria for design of the subdrain system up to the point of dis- Where the runoff from paved and impervious areas is collected in a
charge into the receiver are exactly the same as those for the regular sump, a value of 1 gpm/24 ft2 can be assigned for locations where the
gravity drainage system, including all venting requirements. The ejec- annual rate of rainfall is 4 in./hr. When the total gpm discharge into
tor vent of the basin can be connected to the venting system for the the sump basin has been determined, calculation for the size of the
rest of the building or it can be run independently to the atmosphere. basin is exactly the same as that for the ejector basin.
Criteria for design and installation are the same as those for the grav-
ity venting system used for the rest of the building. When the ejector Sump Pump Sizing
vent is connected to the building venting system, it is necessary to The head on a sump pump is calculated exactly the same as it is for the
convert the gpm discharge rate to FU to determine the additional load ejector pump. It is good practice to select a capacity of 1¼ times the
imposed on the building system. Assign 2 FU for each gpm of pump maximum inflow rate to provide an adequate factor of safety for possi-
discharge. A rule of thumb that has proved satisfactory for sizing the ble periods when calculated maximum flows are exceeded by unusual
ejector vent is to assign a size that is one‑half the size of the subdrain storm conditions. Due to the ever-present danger of flooding caused
discharge pipe into the basin. by unusual rainfall conditions or the failure of one pump, it is recom-
A check valve and shut-off valve should always be installed in each mended that a duplex sump pump system always be provided. Each
pump discharge line. A swing check should always be used and it is pump should be sized for a capacity 1¼ times the maximum inflow.
recommended the weight-loaded type be specified. A weight-loaded The occurrence of a power failure is more likely during a storm than
check valve will eliminate water hammer when the pump shuts off at other times—just when the sump pump is most needed. It is there-
and reverse flow occurs due to the water in the discharge piping. The fore advisable to provide a source of emergency power for sump pumps.
shut-off valve should always be located on the discharge side of the
check valve so that it can be closed and the check valve serviced. Controls
Controls, alarms, alternation, etc., are exactly the same as those for the
Sump Basin Sizing ejector system.
The sump basin receives storm water and other clear water wastes.
Subsoil drains, because of their low elevations, are generally piped to A General Rule for a Subdrainage System
a sump basin. A settling basin should always be provided so that sand, It should be a cardinal rule that any drainage that can possibly flow
grit, and other deleterious material that could cause damage to the by gravity to a sewer should never be connected to the subdrainage
sump pump is settled out before entering the sump basin. The rate of system. The subdrainage system is dependent upon mechanical
discharge from a subsoil drainage system can be calculated by assign- equipment (pumps and controls) for its operation and is therefore
ing a value of 2 gpm for each 100 ft2 of area where the soil is sandy and subject to failure, whereas the gravity drainage system will always
1 gpm per 100 ft2 for clay soils. (See Chapter 7 for further discussion of remain in service during most types of emergencies.
subsoil drainage systems.)
PSD 157
tion from other materials may result in a wrong answer.
Please print or type; this information will be used to process your credits.
Name_________________________________________________________________________________________________________
Title __________________________________________________ ASPE Membership No._____________________________________
Organization___________________________________________________________________________________________________
Billing Address_ ________________________________________________________________________________________________
City_ _________________________________________ State/Province_________________________ Zip_______________________
Country_______________________________________________ E-mail_ _________________________________________________
Daytime telephone_ ____________________________________ Fax_____________________________________________________
PE State _ _____________________________________________ PE No._ _________________________________________________
I am applying for the following continuing education credits: ❏ ASPE Member ❏ Nonmember
Each examination: $25 Each examination: $35
I certify that I have read the article indicated above. Limited Time: No Cost to ASPE Member
Payment: ❏ Personal Check (payable to ASPE) $
❏ Business or government check $
❏ DiscoverCard ❏ VISA ❏ MasterCard ❏ AMEX $
Signature If rebilling of a credit card charge is necessary, a $25 processing fee will be charged.
ASPE is hereby authorized to charge my CE examination fee to my
credit card
Expiration date: Continuing education credit will be given
for this examination through May 31, 2010.
Applications received after that date will not be processed. Account Number Expiration date