5.4.9.3 The User shall ensure that the short circuit rating of the
equipment to be connected to the Distributor’s Distribution
System is not less than the design fault level at the point of
connection.
5.5.2 The User shall ensure that the specification of Plant and
Apparatus at the Connection Point shall be such as to permit
operation within the applicable safety procedures agreed between
the Distributor and the User.