You are on page 1of 6

Sr No Item Description UM

A Pump House Equipments


1 Motor driven main fire pump, horizontal centrifugal, 2850LPM @ 88MWC, CI -IS210 Gr FG260 Nos
casing, IS318-LTB2 bronze impeller,shaft sleeve and casing ring,AISI410 shaft, as per IS5120,
painted fire red,coupling/coupling guard, base plate, matching flanges, alignment, grouting,
head shall not below 65% of duty point at 150% flow, the pump characteristic curve shall be
continuously rising towards shut off,etc complete-make KBL/M&P motor sq cage, 3ph, 4
wire, neutral grounded, 415V+/-10%,50Hz +/-5%, 45 deg C ambient, insulation class F,

2 Motor driven jockey pump , horizontal centrifugal,180LPM @ 88MWC, CI -IS210 Gr FG260 Nos
casing, IS318-LTB2 bronze impeller,shaft sleeve and casing ring,AISI410 shaft, as per IS5120,
painted fire red,coupling/coupling guard, base plate, matching flanges, alignment, grouting, etc
complete, the pump characteristic curve shall be continuously rising towards shut off,-
make KBL/M&P. motor sq cage, 3ph, 4 wire, neutral grounded, 415V+/-10%,50Hz +/-5%, 45
deg C ambient, insulation class F, jockey pump motor kw rating shall be more than the highest
KW required for the entire range

3 Diesel engine driven main fire pump, horizontal centrifugal, 2850LPM @ 88MWC, CI -IS210 Nos
Gr FG260 casing, IS318-LTB2 bronze impeller,shaft sleeve and casing ring,AISI410 shaft, as
per IS5120, painted fire red,coupling/coupling guard, base plate, matching flanges, alignment,
grouting, head shall not below 65% of duty point at 150% flow after engine derating for site
altitude -(submit pump power calculations) and temp. of 40deg C,etc complete- the pump
characteristic curve shall be continuously rising towards shut off,make KBL/M&P. 12 V
DC battery system, control panel - auto manual start/stop,auto start with pressure switch signal
including cabling,water temp. lube oil pressure and temp,ammeter -with alarm for high water
temp, overspeed, low lube oil pressure ,all cabling, only 230V AC supply will be given 10 mtr
away from pump, tachometer, MS fuel piping from fuel tank to engine and return, fuel pipe to
be connected to engine by SS braided hose, fuel tank for 4 hour continuous working with
fabricated stand, glass tube level indicator, industrial type silencer, with complete exhaust
piping ( 3 mtr above the highest level of pump house, rope insulation, supporting of exhaust
piping, inclusive of all first fill of consummables including first fill of full diesel tank, engine
make KOEL/Cummins/Greaves

4 The panel shall be used to control all electric pump/s and supply power to jockey pump Nos
controller and diesel engine controller.This shall be a 2mm CRCA sheet steel body and 1.6
mm doors and partitions, modular, floor mounted, single front, draw-out panel. This indoor
panel shall have degree of protection of enclosure of IP 44.The sheet work shall be duly
degreased, derusted, pickled, washed, zinc chromate primer coated, putty finished, final paint
coated in FIRE RED shade 536 of IS 5 in synthetic enamel. The panel is provided with
removable eyebolts at top for handling. The panel is provided at bottom with structural base
frame. All the feeders required for Jockey pump, main pumps to be provided. In addition, a
230V,AC connection for feeding to diesel engine control panel shall be provided. The panel
shall ensure automatic start/stop of the main motor driven pump based on signals from
pressure switches provided. The panel shall also provide signal to the main fire alarm panel
regarding Pump start/stop, pump in auto/manual mode, pump trip, pump trouble. Make of
components - L&T/Siemens.The power and control cabling is also to be supplied and erected.
Also, necessary cabling for pressure switches to be provided. Cable trays as required woth
adequate supports to be provided.Also include for each pump10 mtr of power and control cable
between MCC and pump inclusive of cable tray with cover, cable shall be of Polycab make
Main components of the panel like switchgear and controls shall be Siemens make only. The
cable entry for MCC shall be from top.
5 0.1M3 capacity pressure tank complete with stand, fittings, valves, gauges, pr relief valve etc Nos
connected to main fire pump delivery. Ms fabricated, painted with 2 coats of fire red synthetic
enamel paint as per IS 5, after degreasing and cleaning. All the welding shall be properly
ground for peoper surface finish. the vessel shall be hydro tested for 2 hours at 14bar

Subtotal Pump House Equipments


Total Pump House Equipments
B Hydrant System
1 Underground Piping - MS, Black,ERW,made from hot rolled steel (IS2062),suitable for butt
welding, IS1239, Part 1, C Class (up to 150NB pipe) and IS3589 (from 200NB to 400NB pipe)
6.35mm thick,with underground protection as per IS 10221, all weld joints to be DP
tested,Fittings- for 65NB and below -use socket welded fittings and for 80NB and above use
butt welded fittings, flanges shall be ASA150.FF,3mm thick champion gasket (asbestos not
acceptable), fasteners as per IS1367 class 4.6/4,including necessary supports, make
Jindal/Tata, including excavation to provide pipe top at 1m below ground level, sand bed of
100mm below pipe, backfilling including compacting to the satisfaction of site engineer,carting
away excess excavation etc complete, hydraulic testing at 14 bar for 2 hours

150NB Mtr
100NB Mtr
80NB Mtr
40NB Mtr
2 Aboveground Piping - MS, Black,ERW,made from hot rolled steel (IS2062),suitable for butt
welding, IS1239, Part 1, C Class (up to 150NB pipe) and IS3589 (from 200NB to 400NB pipe)
6.35mm thick,Fittings- for 65NB and below -use socket welded fittings and for 80NB and above
use butt welded fittings, flanges shall be ASA150.FF,3mm thick champion gasket (asbestos not
acceptable), fasteners as per IS1367 class 4.6/4, Jindal/Tata, hydraulic testing at 14 bar for 2
hours, including painting PO red enamel 2 coats after 2 coats of primer after wire brushing and
cleaning, with FM approved/Tyco Grooved fittings - optional - so that the welding inside
shed can be kept to minimum

200NB Mtr
150NB Mtr
100NB Mtr
80NB Mtr
50NB Mtr
40NB Mtr
25NB Mtr
3 Gate Valves - Double flanged, OS &Y rising spindle, Cast Iron construction CI, IS 210, Gr. FG
260, Class PN16, as per IS 780/IS2906, ASA150 FF flange,Painting Fire Red, make
Kirloskar/Eq
200NB Nos
50NB Nos
4 Butterfly Valves - flanged, PN16 rating, waferv type, bidirectional, flanged ASA150, Body –
Cast Iron, IS 210 Gr FG260, Disc - SGI, Seat Ring – Nitrile, Shaft – AISI410, operation manual
lever, 90 deg movement, bubble tight shut off , intermediate position locking.Valves 150NB and
above shall be gear operated
150NB Nos
100NB Nos
50NB Nos
5 Ball Valve, 800 lb rating,NPT screwed connection, body ASTM A105/WPB, ball AISI410, seat
PTFE, 3 piece, 2 way, Hand Lever, 90 Degrees, Bubble Tight, painted fire red
40NB Nos
25NB Nos
6 Non Return Valves - Double flanged, wafer type, Cast Iron construction, Class PN16, as per IS
5312,body and bonnet SGI, trim SS304,seat - nitrile,Painting Fire Red, make Kirloskar/Eq

150NB Nos
50NB Nos
7 Air release valve - 25NB Nos
8 Pressure Relief Valves,800 lb rating,NPT screwed connection, body ASTM A105/WPB, Nos
pressure setting at 10% higher than maximum system pressure -- size 25NB
9 Complete Fire Brigade Connection with 4x63mm quick connections, built-in reflux valves Nos
150NB tap piping complete, MOC bronze/SS304
10 Pressure Gauges- Bourden type, 100mm dial gauge, range 0-15Bar,SS316 bourden, glycerin Nos
filled,Isolation globe/ball valve with pigtail connection required, connectin size 15mm NPT

11 Pressure switches- range 0-15bar, on-line/wall mounting type, SS316 wetted parts, 5A/230V Nos
ratingmake Switzer/Infoss
12 Level gauge for Under ground Tank - range 6 mtr, Pune Techtrol make Nos
13 Level switch with controller, cabling to send signal to Fire alarm panel in case the level goes Nos
below 90% of total height, cable length suitable for 6 mtr tank height
14 Hydrant Valves Single, 63mm,SS304 construction, complete as per IS5290, IS approved and Nos
stamped,
15 Hoses 15Mtr, for hydrant, IS14933, complete with SS304 coupling as per IS903, duly wound Nos
with GI wire to hose, ISI marked, Type A
16 Branch Pipe, SS304,short branch pipe with nozzle 19mm dia, coupling complete as per IS903, Nos
instanteneous inlet, male threaded outlet
17 Hose Cabinets suitable to accommodate 15/7.5 mtr long , 2 nos. hoses with branch pipe, MS Nos
CRCA 18 SWG sheet steel,painted fire red,Double leaf, glass window front, lockable with
break glass key pocket (one key spare) and locking arrangement. Mounting with MS fabricated
steel structure / wall mounting / floor mounting as per site requirement.- structure to be painted
black, all supports inclusive, wall mounting for internal hydrants and support stand for external
hydrants, including grouting and necessary excavation for proper mounting, erc complete. Also
provide hammer for breaking glass

18 Hose Reels, IS884 type A, red color PVC hose 20mm dia and 25 mtr long minimum, hydraulic Nos
test pressure 21 bar minimum, painted fire red
19 RCC Hume Pipes for Road Crossing 400NB, NP3 Mtr
20 RCC Hume Pipes for Road Crossing 250NB, NP3 Mtr
21 Concrete M20, RCC bed blocks for pipe support, including curing, shuttering etc complete- Nos
size 0.5 x 0.5 x 0.7 mtr
22 Vortex Plate - 6 thk, OD= 2 x pipe dia, Id= Pipe OD, material MS with epoxy painting
200NB Nos
50NB Nos
23 Pipe Supports as required - use structural steel, painted black ISI marked Kg
24 Sign indicators
Flow direction stickers with arrow marking - computer printed - red color arrow with white Nos
background - -
Portable Extinguisher background stickers Nos
Numbering of hydrants/hose reels/portable extinguishers/alarm devices/mcp- red oil paint with Nos
white background - computer printed
A0 size layout with all the Sprinklers/hydrant/ hose reel marking with serial numbers, printed on Nos
Vinyl, pasted on sunboard
A0 size layout with all the fire alarm devices marking with serial numbers, printed on Vinyl, Nos
pasted on sunboard
25 Chain and padlock arrangement for valves Nos
26 Pump and motor nameplate,tank capacity nameplate giving all details, on wooden laminated Nos
board - size 500mm x 300mm installed on the wall in front of pump, as per requirement

27 Water Monitors, 1750lpm capacity @ 6.8 bar, hot dip galvanized carbon steel waterway,brass Nos
barrel, range Horizontal – 55-60 Mtr, Vertical 25-30 Mtr,Horizontal rotation - 360 deg, vertical
rotation - +90 to -45 degrees, fire red painting
Subtoal Hydrant System
Total Hydrant System
C Portable Extinguishers - as per IS standard with BIS marking
1 Fire Buckets filled with fine sand, with stand for 4 buckets - IS2546- set of 4 buckets Set
2 6Kg ABC Type - IS15683 - Mono ammonium phosphate (MAP) 90%, stored pressure Nos
3 4.5 Kg CO2 - IS15683 - without metal horn Nos
4 9 Ltr Foam Type - IS15683 Nos
Subtoal Portable Extinguishers
Total Portable Extinguishers
D Sprinkler System
1 Aboveground Piping - MS, Black,ERW,made from hot rolled steel (IS2062),suitable for butt
welding, IS1239, Part 1, C Class (up to 150NB pipe) and IS3589 (from 200NB to 400NB pipe)
6.35mm thick,Fittings- for 65NB and below -use socket welded fittings and for 80NB and above
use butt welded fittings, flanges shall be ASA150.FF,3mm thick champion gasket (asbestos not
acceptable), fasteners as per IS1367 class 4.6/4, Jindal/Tata, hydraulic testing at 14 bar for 2
hours, including painting PO red enamel 2 coats after 2 coats of primer after wire brushing and
cleaning, with FM approved/Tyco Grooved fittings - optional - so that the welding inside
shed can be kept to minimum

150NB Mtr
100NB Mtr
50NB Mtr
40NB Mtr
25NB Mtr
2 Butterfly Valves - flanged, PN16 rating, waferv type, bidirectional, flanged ASA150, Body –
Cast Iron, IS 210 Gr FG260, Disc - SGI, Seat Ring – Nitrile, Shaft – AISI410, operation manual
lever, 90 deg movement, bubble tight shut off , intermediate position locking.Valves 150NB and
above shall be gear operated
150NB Nos
100NB Nos
3 Ball Valve, 800 lb rating,NPT screwed connection, body ASTM A105/WPB, ball AISI410, seat
PTFE, 3 piece, 2 way, Hand Lever, 90 Degrees, Bubble Tight, painted fire red
25NB Nos
50NB Nos
4 Installation Alarm Valve, double flanged, for wet sprinkler system, rating PN16, Body CI to IS
210 FG 260/DI,alarm gong and standard trims required, FM approved and stamped, ASA 150
flange, painted fire red
150NB Nos
5 Deluge valve, double flanged, for foam system, rating PN16, Body CI to IS 210 FG
260/DI,alarm gong and standard hydraulic trimrequired, FM approved and stamped, ASA 150
flange, painted fire red, maximum working pressure 12 bar, with all standard hydraulic trim,
electrical trim,and manual trim, the entire assembly to be FM approved and stamped

100NB Nos
6 Flow Switch, 24V Dc, to comminicate with fire alarm control panel, addressable, vane type
paddle, FM approved and stamped
150NB Nos
100NB Nos
7 Sprinklers, threaded NPT, brass/with chrome plated, FM approved and stamped
Sprinklers - K Factor-80(lpm-bar), Upright, 68 deg C Nos
Sprinklers - K Factor-80(lpm-bar), Pendent, 68 deg C, with escutcheon plate duly fitted, Nos
escutcheon plate to be of same make as sprinkler manufacturer.
Sprinklers - K Factor-115(lpm-bar), Upright, 79 deg C Nos
Sprinklers - K Factor-80(lpm-bar), Upright, 141 deg C Nos
8 Water curtain nozzle, 15NB threaded NPT, brass construction
K factor 53 LPM_Bar, HD fire model no. WC15 Nos
9 Flexi Drops - flexible hose for sprinklers, pr rating 16bar, size 25NB with end connection to suit Nos
sprinkler, maximum length 1500mm, FM approved and stamped
10 Pressure Relief Valves,800 lb rating,NPT screwed connection, body ASTM A105/WPB,
pressure setting at 10% higher than maximum system pressure -- size 25NB
11 Pipe Supports as required - use structural steel, painted black ISI marked Kg
12 Hanger Supports - GI , rod dia 10mm for pipe size up to 100NB, 12 mm for larger pipes up to
200NB
50NB Nos
40NB Nos
25NB Nos
Subtoal Sprinkler System
Total Sprinkler System
E Fire Detection and Alarm System
1 Fire Alarm Control Panel - solid state, microprocessor based, addressable, 15 to 24 V DC, Nos
supply voltage by Customer = 230V AC. Panel shall be supplied with ite own UPS module
sufficient to take care of the devices connected, and also a battery unit inside the panel. wall
mounting type, ambient temp 45 deg C, 95% RH. No. of loops will depend upon the total
devices and each loop shall not cater to more than 1500mtr cable length. Connected devices
will be all detectors, manual call points, flow switches and all pumps. The panel shall also
monitor flow switches, all detectors, fire pump status like pump running, pump trouble, engine
trouble etc for each pump, engine trouble signal like trouble on the diesel engine such as low
oil pressure (level), high engine jacket water temperature, shutdown from over speed, battery
failure and failure to start, shall also be monitored, The panel shall be UL listed or FM
approved
2 Smoke Detectors - addressable, photoelectric, As per IS:2189/NFPA72/FMDS0548, loop Nos
powered, FM approved
3 Smoke Detectors - addressable, photoelectric, As per IS:2189/NFPA72/FMDS0548, loop
powered, FM approved, above false ceiling with cable box for installation on rack structure

4 Response Indicators - -for smoke deetctors installed above false ceiling Nos
5 Heat Detector - Addressable FT & ROR heat , loop powered, thermistor sensor, As per Nos
IS:2189/NFPA72/FMDS0548, FM approved
6 Beam Smoke Detector Nos
7 Manual Call Points with Hooter and Strobe - adressable, loop powered, MCP to be provided Nos
with break glass type to prevent misuse, As per IS:2189/NFPA72/FMDS0548, Also provide
hammer for breaking glass
8 Cabling for detection system, 2 core, 1.5mm2, FRLS,Generally to IS 1554 (Part 1), IS 8130, IS Mtr
5831,armoured, red color, voltage grade 1100 volts, screened cable
9 Cable Tray 50x50, GI Mtr
10 GI Conduit for cable Mtr
11 Isolator Module Nos
12 Control module Nos
13 Monitor Module Nos
Subtoal Fire Detection and Alarm System
Total Fire Detection and Alarm System
F Liason
Liason with authorities for obtaining final NOC for fire Nos
Subtoal F
Total F
TOTAL
TOTAL SUPPLY + ERECTION

Notes
1 All material supplied shall be new and first quality. The test cettificate dates shall be not earlier
than 6 months
2 Excavation, backfilling and carting away excess excavation is in the Contractors scope.
3 All underground piping shall be protected against corrosion by proper wrapping/coating as per
IS 10221.
4 All piping after hydrotest shall be painted Fire RED.
5 Contractor to ensure quality of all components as per relevant IS/International standards.
6 The piping length and unit rate shall be inclusive of all necessary fittings.
7 Contractor to obtain all necessary approvals of the fire protection system installed by him from
the respective authorities.
8 The Bill of Material indicated above is approximate and tentative and Contractor to ascertain
and provide all the necessary materials for satisfactory performance/operation and approval of
the system from the authorities.
9 The Unit rates shall include supply, erection, testing, commissioning, hand over with approval
of authorities
10 The BOM given above is tentative. Contractor to supply material as per actual site requirement
and any excess material will be taken back by the Contractor
11 Initially, Contractor to supply only 70% of the material required as per approved shop drawings
and balance as per requirement