A O DOUBLE LINE DUCT PIPING THESE NOTES APPLY TO ALL M, FP & P DRAWINGS UNLESS NOTED OTHERWISE

AAV AUTOMATIC AIR VENT OA OUTSIDE AIR


AC AIR COMPRESSOR ORD OVERFLOW ROOF DRAIN OR SEE SPECIFICATION DIVISION 15 FOR INSTALLATION AND OTHER REQUIREMENTS FOR
DUCT SECTION SLOPE (DN TOWARD ARROW DIRECTION)
AD AIR DRYER, AUTOMATIC DRAIN MECHANICAL WORK SHOWN ON "M", "FP" AND "P" SERIES DRAWINGS.
(EXHAUST OR RETURN)
AFF ABOVE FINISHED FLOOR P DIRECTION OF FLOW
OR 1. THE DESIGN SHOWN ON THE DRAWINGS IS BASED ON THE EQUIPMENT
ATF AUTOMATIC TRANSMISSION FLUID P PUMP DUCT SECTION (SUPPLY)
MANUFACTURERS LISTED IN THE MECHANICAL EQUIPMENT SCHEDULES.
REDUCER
EQUIPMENT PROPOSED BY THE CONTRACTOR THAT IS NOT LISTED IN THE
B Q SIZE OF SIDE SHOWN
SCHEDULES SHALL BE SUBMITTED TO CITY/BOROUGH OF JUNEAU AS A REQUEST
B BOILER SIZE OF SIDE NOT SHOWN 45° TEE
12x20 FOR SUBSTITUTION IN ACCORDANCE WITH DIVISION 1.
BFF BELOW FINISHED FLOOR
BTUH BRITISH THERMAL UNITS PER HOUR R DUCT SIZE IN INCHES WALL CLEANOUT
2. PROVIDE ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE FIRE WALL, FIRE
BW BOOT WASH RA RETURN AIR
BLOCKING AND FIRE STOP PROVISIONS SHOWN ON THE ARCHITECTURAL
RPBP REDUCED PRESSURE BACKFLOW DUCT WITH LINING/INSULATION STRAINER
DRAWINGS.
PREVENTOR
C CHECK VALVE
RD ROOF DRAIN 3. COORDINATE SUPPLY AIR DIFFUSERS AND RETURN/EXHAUST AIR GRILLE
CA COMPRESSED AIR, LOW PRESSURE, 100PSIG TURNING VANES
RF RETURN FAN LOCATIONS WITH ARCHITECTURAL DRAWINGS. COORDINATE DUCT ROUTING
CW COLD DOMESTIC WATER WCO WALL CLEANOUT
RG RETURN GRILLE WITH LIGHT FIXTURE LOCATIONS.
CFM CUBIC FEET PER MINUTE
CO CLEANOUT FCO/ FLOOR CLEANOUT/ YARD CLEANOUT
S 4. MECHANICAL WORK SHOWN IS DIAGRAMMATIC. PROVIDE OFFSETS,
YCO
TRANSITIONS, AND OTHER DUCTWORK, PIPING AND ASSOCIATED CONSTRUCTION
D S SINK SUPPLY DIFFUSER OR GRILLE. COLD DOMESTIC WATER (CW) WHERE REQUIRED TO AVOID BUILDING STRUCTURAL ELEMENTS OR THE WORK
SA SUPPLY AIR THE NUMBER OF ARROWS AND OF OTHER TRADES.
SCF SOURCE CAPTURE FAN DIRECTION INDICATES 1, 2, 3, HOT DOMESTIC WATER (HW)
E SD SUPPLY DIFFUSER OR 4-WAY DEFLECTION
E EXHAUST 5. DUCTWORK DIMENSIONS SHOWN ARE NET INSIDE DIMENSIONS. ENLARGE DUCT
SF SUPPLY FAN HOT DOMESTIC WATER RECIRC (HDWR) DIMENSIONS AS REQUIRED FOR INTERNALLY LINED DUCTWORK, SEE
EA EXHAUST AIR SHR SHOWER SPECIFICATIONS.
EB ELECTRIC BASEBOARD SL SLOPE RETURN GRILLE OR REGISTER VENT
EC ELECTRIC CEILING PANEL SR SUPPLY REGISTER MOUNTED IN A VERTICAL 6. PAINT EXTERIOR PIPING, DUCTWORK, FANS, CURBS AND SHEET METAL WITH
EF EXHAUST FAN SS STAINLESS STEEL POSITION WASTE BELOW SLAB URETHANE FINISH, COLOR AS SELECTED BY ARCHITECT. PAINT UNFINISHED
EO1 ENGINE OIL, 15W40 STEEL, GALVANIZED, ALUMINUM OR SST EXTERIOR SURFACES, MATERIALS OR
EO2 ENGINE OIL, 5W20 INDICATES LIQUID/GAS TRANSPORTATION BY EQUIPMENT, PROVIDED UNDER DIVISION 15, COLOR AS SELECTED BY ARCHITECT.
EVP EVAPORATOR T SUPPLY GRILLE OR REGISTER PIPE,
EWC ELECTRIC WATER COOLER T TANK MOUNTED IN A VERTICAL CHWR: CHILLED WATER RETURN 7. TEMPERATURE SENSORS SHALL BE LOCATED WHERE SHOWN 48 INCHES ABOVE
EXH EXHAUST TD TRENCH DRAIN POSITION CHWS: CHILLED WATER SUPPLY FINISHED FLOOR.
EXST EXISTING TYP TYPICAL HWR: HEATING WATER RETURN
EW EYEWASH HWS: HEATING WATER SUPPLY 8. PROVIDE BIRDSCREENS FOR ALL LOUVERS AND ALL OUTSIDE AIR INTAKES.
U POWER OR GRAVITY ROOF
VENTILATOR- EXHAUST 45° OR 90° OFF BOTTOM 9. PENETRATE ROOF DECKS AS REQUIRED TO INSTALL MECHANICAL WORK.
F UH UNIT HEATER
FCO FLOOR CLEANOUT UR URINAL PROVIDE BLOCKING AROUND PENETRATIONS AND AS NOTED ON STRUCTURAL
45° OR 90° OFF TOP DRAWINGS. SEAL ALL PENETRATIONS AIR AND WATER TIGHT.
FD FLOOR DRAIN FAN
FTU FAN TERMINAL UNIT V BALL VALVE 10. PROVIDE ACCESS PANELS FOR ALL MECHANICAL EQUIPMENT OR VALVES
FRL FILTER, REGULATOR, LUBRICATOR V VENT ENCLOSED IN PERMANENT CONSTRUCTION OR DUCTWORK.
VFD VARIABLE FREQUENCY DRIVE GATE VALVE FLOW
G VL VEHICLE LIFT SINGLE LINE DUCT 11. INSTALL DUCTWORK TO MAINTAIN SERVICE CLEARANCES, ACCESS DOOR
GPM GALLONS PER MINUTE VTR VENT THRU ROOF CONTROL VALVE CLEARANCES AND COIL PULL CLEARANCES AT ALL HVAC EQUIPMENT.
(DUCTWORK LESS THAN 12"WIDE)
GR GREASE
DUCT END HOSE BIBB 12. COORDINATE FLOOR AND WALL CLEANOUT LOCATIONS WITH OFFICE CASEWORK
W
VENDOR DRAWINGS AND OTHER FURNISHINGS, RELOCATE AS REQUIRED.
H W WASTE PRESSUR GAUGE WITH ISOLATION VALVE
H HEADER WC WATER CLOSET, WATER COLUMN DUCT SECTION
13. PROVIDE FINAL LOCATIONS FOR ROUGH-IN AND FINISH OF WASTE, VENT, AND
HB HOSE BIBB WH WATER HEATER THERMOMETER WATER SUPPLY. CONNECTIONS AND LOCATIONS PER CASEWORK VENDOR
HC HEATING COIL WM WASH MACHINE DUCT BEND DOWN DRAWINGS.
HW HOT DOMESTIC WATER PUMP
HF HYDRAULIC FLUID X DUCT TEE DOWN 14. PROVIDE ALL FLOOR DRAINS, FLOOR SINKS, INDIRECT WASTE CONNECTIONS,
HP HIGH PRESSURE COMPRESSED AIR, 150PSIG IN-LINE PUMP AND OPEN HUB DRAINS WITH VENTS AND TRAP PRIMERS, EXCLUDING THE
HWR HEATING WATER RETURN INCLINED DROP IN MAINTENANCE AREAS AND FUEL BAY.
HWS HEATING WATER SUPPLY
Y RESPECT TO AIR FLOW COMPRESSED AIR STATION, LOW PRESSURE
Y YARD CLEANOUT 15. SURVEY AND FIELD VERIFY ALL INVERT ELEVATIONS SHOWN ON PLUMBING
HV HEATING AND VENTILATION UNIT INCLINED RISE IN COMPRESSED AIR STATION, HIGH PRESSURE DRAWINGS. INVERT ELEVATIONS SHOWN ARE APPROXIMATE, PROVIDE BUILDING
HX HEAT EXCHANGER RESPECT TO AIR FLOW
Z WASTE PLUMBING TO PROPERLY INTERCONNECT WITH SITE WASTE PLUMBING.
TRANSITION DOUBLE LINE TO SEE CIVIL DRAWINGS.
I SINGLE LINE
IA INTAKE AIR 16. T-PULL BRANCH PIPING NOT ALLOWED. ALL CHANGES IN DIRECTION SHALL BE
IW INDUSTRIAL WATER (NON-POTABLE) VOLUME DAMPER MADE WITH FITTINGS.

K 17. ALL PENETRATIONS AND SLEEVES THRU FLOORS/ WALLS SHALL BE SEALED
T THERMOSTAT WEATHERTIGHT.

L S SWITCH 18. ALL CONDENSATE DRAINS SHALL BE ROUTED FULLSIZE TO NEAREST WASTE LINE
L LAVATORY OR APPROVED EXTERIOR LOCATION.
M MOTOR

M P PRESSURE SENSOR 19. ALL UNDER BUILDING PIPING SHALL BE SLOPED AT 2%, FOR YARD PIPING SLOPES
SEE CIVIL DRAWINGS.
MAX MAXIMUM DM MOTORIZED DAMPER
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MS MOTOR STARTER 20. EXTEND VTR PIPING AS REQUIRED TO MAINTAIN 10' MINIMUM CLEARANCE TO
MIN MINIMUM
OUTSIDE AIR INTAKE LOUVERS.
MS MIXING STATION SD SMOKE DETECTOR
MSB MOP SERVICE BASIN
MU MAKE UP AQ AIR QUALITY SENSOR ONE INCH AT FULL
SIZE
DP DIFFERENTIAL PRESSURE SENSOR
N
IF NOT ONE INCH,
SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M0.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, ABBREVIATIONS
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 & SYMBOLS 31 - 72
NOTES:
1. DRAWINGS SHOW GENERAL INTENT OF THE DEMOLITION WORK.
DEMOLITION OF EQUIPMENT AND COMPONENTS SHALL INCLUDE ALL
SUPPORTS, PADS, HANGERS, INSULATION, CONTRLS, STARTERS,
L M N O P ACCESSORIES AND APPURTENANCES NOT REQUIRED FOR THE
INSTALLATION OF THE NEW SYSTEM.

2. SEE DWG M1.02 FOR LOCATION OF RELOCATED EQUIPMENT.

3. ALL OPENINGS CREATED BY THE ABANDONMENT OR REMOVAL OF


EXISTING SYSTEMS SHALL BE PATCHED TO MATCH EXISTING.
1
36x28E
EXHAUST LOUVER
1
- KEY NOTES:
1. RELOCATE EF-3, LOUVER AND ALL RELATED APPURTENANCES AND
T
PATCH 14E DUCTWORK FOR CONTINUITY. PATCH WALL OPENING TO
MATCH EXISTING.

2. COMPLETELY REMOVE INDICATED DUCTWORK AND RELATED


APPURTENANCES AND COORDINATE WITH INSTALLATION OF NEW WORK
T 2 INDICATED IN DWG M1.02.

2
26x42S
T

T RG-1 12x8
275CFM

T
3

T
150CFM
TYP 4
T

T
220CFM

HVAC DEMOLITION PLAN 1

8' 0 8' 16'


N

SCALE: 1/8"=1'-0" ONE INCH AT FULL


SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M1.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, HVAC DEMOLITION
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PLAN 32 - 72
L M N O P Q
NOTES:
AQ
5E 1. RELOCATE EF-3, LOUVER AND RELATED APPURTENANCES.
BALANCE EF-3 TO 1325CFM.

2. SEE P1.02 FOR RADIANT FLOOR ZONING.

3. PROVIDE WALL SPEED CONTROLLER WITH 300CFM IN LOW SPEED


POSITION AND 500CFM IN HIGH SPEED POSITION.

4. PROVIDE RIGID GALVANIZED DRYER DUCT WITH MAXIMUM


NUMBER OF BENDS TO NOT EXCEED TWO 90° ELBOWS. USE TYPE
A VENT HOOD WITH NO MESH SCREEN.
AQ

4E 5. REBALANCE FTU-A2 TO 400CFM

6. PER ADDITIVE ALTERNATE #1, INSTALL PARALLELOGRAM VEHICLE


LIFT IN ROOM 117, BAY 2 OF THE EXISTING MAINTENANCE BAYS
AREA.

AQ

6" DIA. EXH UP 3


AQ
THROUGH ROOF
3E
SD-1 8x8
H-2MACHINE200CFM
FLUID HOSE SHOP 1
REEL, TYP 4 MAINTAIN REQ'D
BAY 3 BAY 1
WORKING SPACE
TYP
SD-2, 6X6
10E UP 100CFM,

10R
AQ AQ AQ
TYP2 MAINTENANCE BAYS
12S UP
4"Ø DRYER SEE M1.02
RG-2, 6X6 12S
AQ
VENT FOR HWS/R
50CFM 8S 4
EF-5 SPEED HC-1 DRYER VENT CAP
2E BAY 4 BAY 2 CONTINUATIONS
UP

CONTROLLER, SD-2, 8X8 T


H-3 RG-1
PARALLELOGRAM LIFT
SEE NOTE 3 300CFM 250CFM
12S

6E SD-1, 8X8 EB-2 FTU-6


RG-2, 12X12 8S 300CFM, OST LIFT SR-1 8x6
300CFM/500CFM MODULE 6" DN TO EXHAUST
6S TYP2 RELOCATED EF-3, 150CFM
K 12X12E UP TO 8S SEE NOTE 1
HOSE REEL, TYP
TYP 2
MACHINE
EF-5 ON MEZZANINE SHOP 2 AQ

SD-1, 6x6 1E PARALLELOGRAM


COMP UH-2, 100CFM 16E LIFT CONTROL MODULE
GAS SEE NOTE 3 CONNECT TO EB-1
RG-1 12x8 RG
EXST DUCT FTU-3
12E 275CFM RG-2 240
T
10"E 300CFM 1 LUBE
14E
CONNECT 14E TYP 2 STORAGE
SD-1 8x8 SD-1 8x8
TO EXST DUCT
6S

VP-1 RG-2 10X6 200CFM 200CFM WALL EXH


175CFM
ELECTRICAL EC-2 TYP 2 VENT CAP
EB-1 EF-2 8E
ROOM TYP 3 5
8S

EC-1 RG-1 EF-6


RG-1 TYP 200CFM
NT 200CFM
NG SD-1 8x8 RG-1
RG-3 EC-1, 200 CFM
LOCKER
200CFMROOM FTU-A2
10S

AQ
TYP 4
150CFM
SD-2 6x6 TYP 2 EB-2 2
SECURE
14X12S

8S
OFFICE STORAGE 150CFM TYP 3
SR-1 8x6 MEN'S TYP 2 6S
T
150CFM RESTROOM 12X10S
9E

8x8 OFFICE
12X10S

10E T

FM 6S CONNECT TO
12R
12S

RG-1 12x8 8S
FTU-5 T
SD-1 8x8 EXST DUCT
Q'D 275CFM
CE VAV-4 200CFM
TYP
6S RG-2 6x6
JAN
OFFICE G H J K
10S 50CFM VAV-7
8S

12S 7S T

3
10R

8S
22X12S 22X12S 16S
CORRIDOR 14X12S
12S 22X12R 18X12R
EC-3

1ST FLOOR HVAC PLAN ADD. ALTERNATE #1 2


1

ONE INCH AT FULL


SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M1.02
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, FIRST FLOOR
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 HVAC PLAN 33 - 72
L M N O P Q

5E
RG-4
1375 CFM
SG-1 TYP 4
687 CFM
TYP 8

4E

OPEN TO BELOW

22S

28E

22S
3E

12S DN 10E DN
36x20IA
BELOW
2E
22S
72x48 INTAKE
LOUVER AHU-3

H J K 72x48x18 26x26S
PLENUM 49x15E RISER
EF-5 BELOW AHU-3 36x26S WH-2 B-2 1E
T-3
EXH DUCT BELOW
203D 203C 203B 203A
12x12E DN P-4
1
60x48
EXHAUST
LOUVER
24x24
EXHAUST
LOUVER

MECH 2
ROOM

202

3
2ND FLOOR HVAC PLAN 1

4
201B
ONE INCH AT FULL
SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M1.03
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, SECOND FLOOR
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 HVAC PLAN 34 - 72
SA EA
OA
EA/RA

EXHAUST AIR BYPASS


DM DAMPER

HEAT RECOVERY
WHEEL EXHAUST/RETURN
PLAN VIEW - UPPER LEVEL AIR TEMP
PLAN VIEW - LOWER LEVEL 1

VFD T DP SD
7 6 3 3 9
EA EA/RA

EF
1 DM RECIRCULATION BYPASS
DAMPER DISCHARGE AIR
2 TEMP
OUTSIDE DM
EA EA/RA AIR TEMP
3 P
H T
4 SF
H
5 OA SA
C

6 DP VFD
DM
7
FILTER
DIFFERENTIAL SUPPLY AIR BYPASS
8
PRESSURE SWITCH, DAMPER
9 TYPICAL
OA SA DM
AHU-3 CONTROL
SCHEMATIC 2
2 AHU-3 NTS -

DETAIL 1
NTS M1.03
9 3 4 6 8 5

ELEVATION VIEW

RETURN AIR
FROM CEILING
PLENUM
H

C H
TO ROOM
C DIFFUSERS
PRIMARY AIR
H
TO ROOM
C HEATING COIL
DIFFUSERS

FTU
HEATING COIL
THERMOSTAT TERMINAL UNIT
CONTROL BOX

ROOM SENSOR
NOTES: SPEED CONTROLLER IN ROOM LOCAL VARIABLE SPEED NOTES: ROOM SENSOR
1. CONTINUOUS OPERATION LOW (300CFM)/HIGH(500CFM) CONTROL 1. INTERLOCK WITH FTU AS
SECOND STAGE OF HEATING

EF-3 EF-5 EF-6 DUCT HEATER ELECTRIC BASEBOARD FAN TERMINAL UNIT
CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL
ONE INCH AT FULL
SCHEMATIC 3 SCHEMATIC 4 SCHEMATIC 5 SCHEMATIC 6 SCHEMATIC 7 SCHEMATIC 8 SIZE

NTS M1.02 NTS M1.03 NTS M1.02 NTS M1.02 NTS M1.02 NTS M1.02
IF NOT ONE INCH,
SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M5.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, HVAC DETAILS AND
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 SCHEMATICS 35 - 72
DRY WALL
DRY WALL
SHEET METAL
BRANCH CONNECTION SHEET METAL
VERTICAL SCREW, 10"OC (TYP) FRAMING, STEEL
FOR ROUND MAIN CONNECTION SCREW, 10"OC (TYP) FRAMING, STEEL
SUPPLY DUCT STUD RUNNER 1" MIN. ON TOP
FSD USE CONICAL TEE STUD RUNNER AND BOTTOM
FOR RECTANGULAR MAIN
22 GA SHEET DUCTWORK ADJUSTABLE
CONNECTION USE SPIN IN ELBOW RINGS
CLOSURE COLLAR MAIN DUCT

SUPPLY
WALL AIRFLOW
AD OPENING
REGISTER OR
CONCRETE WALL SEAL ALL
GRILLE AS AROUND
VD
SHOWN ON ROUND SHEET
L 2"x4"x1/8" DRAWING
NOTE: METAL DUCT, SIZE
CLOSURE COLLAR
1. CLOSURE COLLAR SHALL SHOWN ON PLAN
3/8"x4" SST DRAWINGS
VD BE OF SAME MATERIAL AS PACK OPENING CONCRETE ANCHOR
DUCT. AROUND W/ FIBERGLASS L 2"x4"x1/8"
6"OC MAX
45° CLINCH COLLAR PER 1/2"MAX CLEARANCE CLOSURE COLLAR TYP FTU SUPPLY
VERTICAL
RETURN DUCT NEOPRENE GASKET DUCT TAKE OFF
8° WALL PENETRATION ALL AROUND
DETAIL 4
TRANSITIONS VD (AIR TIGHT)
DETAIL 2 NTS TYP
NTS TYP NOTES:

1. SIMILAR INSTALLATION FOR: BACK TO BACK GRILLE, DUCTWORK


ATTACHED TO WALL OPENING, AND SINGLE WALL OPENING. 24 GAUGE SHEETMETAL
DIFFUSER CAN WITH
OFF SETS 2. PROVIDE FIRE DAMPERS AND VOLUME DAMPERS WHERE SHOWN ON 1" SOUND LINING
FLOOR PLANS. HANGER FLEX DUCT
VD
7' MAX LENGTH
3. CLOSURE COLLAR SHALL BE OF SAME MATERIAL AS DUCT. TAP IN
SUPPLY
RETURN
WALL MOUNTED GRILLE
AND REGISTER
DETAIL 3
NTS TYP

TYPICAL SUPPLY
PERFORATED METAL
OR RETURN DUCT ADJUSTABLE CEILING DIFFUSER
DIFFUSER PLATE
DAMPER
DETAIL 1
NTS TYP SUPPLY OUTLET TYP CEILING MOUNTED
GRIDS AND DAMPERS MUST NOT DAMAGE LINERS SQUARE NECK DIFFUSER
DETAIL 8
NTS TYP

24 GAUGE
SHEETMETAL CAN W/
HANGER FLEX DUCT 1" SOUND LINING
EQUALIZING GRID 7' MAX LENGTH
TAP IN

ADJUSTABLE DAMPER
VOLUME DAMPER
WHERE NOTED

NOTES:

1. REFER TO PLAN DRAWINGS FOR MOUNTING ANGLE ON ROUND


DUCT.

TYPICAL DUCT MOUNTED TYP CEILING MOUNTED


DIFFUSERS SUPPLY GRILLE (SG-1) RETURN/EXHAUST GRILLE
TRANSFER GRILLE DETAIL 6 DETAIL 7 ONE INCH AT FULL

NTS TYP
DETAIL 8 SIZE
NTS TYP
DETAIL 5 NTS TYP
NTS TYP IF NOT ONE INCH,
SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M5.02
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, TYPICAL DETAILS
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 DUCTWORK 36 - 72
TABLE A
SUPPORT MAXIMUM SPAN, IN FEET, FOR PIPES
ROD SIZE NOT IN RACKS SEE NOTE 2.
DESIGN BASED ON
A B CONC ANCHOR PIPE SIZE PLASTIC CAST IRON
WEIGHT SINGLE ROD STEEL COPPER
BOLTS SEE NOTE SEE NOTE
STEEL I BEAM, MAX SEE NOTE1
FLANGE 15" WIDE x 3 4
1.031" THICK 3/8"TO 3/4" 275 LBS 3/8" 5 5 CONTINUOUS
1" 275 LBS 3/8" 7 6 5
1-1/4" 300 LBS 3/8" 7 7 5
CAPACITY: 3/8" PIPE 8
1-1/2" 300 LBS 3/8" 9 5
THROUGH 12" PIPE
2" 325 LBS 3/8" 10 8 6 PRESSURE
2-1/2" 375 LBS 1/2" 10 9 6 PIPE 12 FT
MAXIMUM ALLOWABLE LOAD
3" 575 LBS 1/2" 10 10 7 SOIL PIPE
JAMB NUT 4" 600 LBS 5/8" 10 10 7 10 FT.
3/8"ROD 610 LBS
1/2"ROD 1130 LBS BEAM CLAMP W/ 6" 750 LBS 3/4" 10 10 9 "
SUPPORT ROD EYE NUT
5/8"ROD 1810 LBS 8" 950 LBS 7/8" 10 10 9 "
OR BOLT. CAPACITY: 3/8" PIPE
3/4"ROD 2550 LBS SIZE AS THROUGH 12" PIPE
7/8"ROD 2630 LBS REQUIRED NOTES: (TABLE A)
JAMB NUT
MAXIMUM ALLOWABLE LOAD
MINIMUM SPACING: A=EDGE DISTANCE B=CENTER TO CENTER 1. ROD SIZE IS BASED ON CARRYING SINGLE PIPE. WHEN MORE THAN ONE
3/8"ROD 610 LBS PIPE IS TO BE SUPPORTED. RODS SHALL BE SIZED USING DESIGN WEIGHTS
3/8"ROD 3" 4"
SEE TABLE A AND 1/2"ROD 1130 LBS TO DETERMINE TOTAL LOAD.
1/2"ROD 4" 5"
TYP SUPPORT ROD 5/8"ROD 1810 LBS SUPPORT ROD SIZE
5/8"ROD 4" 6"
FOR PIPES SUBJECT 3/4"ROD 2710 LBS AS REQUIRED 2. WHERE MODULARLY SPACED INSERTS ARE REQUIRED SUPPORT PIPES AT
3/4"ROD 5" 7"
TO HORIZONTAL 7/8"ROD 3770 LBS INSERT MODULE. NO SPECIAL INSERTS WILL BE ALLOWED FOR INDIVIDUAL
7/8"ROD 6" 8"
MOVEMENT DETAIL PIPE SUPPORTS UNLESS SPECIFICALLY DETAILED OR AUTHORIZED BY
THE PROJECT REP.
TYPE B
3. SPACING BASED ON SCHEDULE 80 PIPE AT 100°F. SCHEDULE 40 PIPE OR
TYPE A HIGHER TEMPERATURE REQUIRE SHORTER SPANS. SEE MANUFACTURER'S
DETAIL 2 RECOMMENDATIONS.
DETAIL 1 NTS TYP
NTS TYP 4. INSTALL AT LEAST ONE HANGER PER PIPE LENGTH. LOCATE AS NEAR THE
JOINT OR FITTING AS POSSIBLE.

5. IN ADDITION TO SUPPORTING DUCTS AND PIPES FOR GRAVITY LOADS, DUCTS


AND PIPES SHALL BE SUPPORTED TO RESIST VERTICAL, LATERAL AND
D + 6"SQ
LONGITUDINAL SEISMIC FORCES. FORCES ARE TO BE DETERMINED ACCORDING
TO 2006 INTERNATIONAL BUILDING CODE. SEISMIC BRACE DESIGN SHALL BE
1" TYP
ACCORDING TO THE LATEST "SEISMIC RESTRAINT MANUAL GUIDELINES
FOR MECHANICAL SYSTEMS" BY SMACNA. THE DESIGN FOR SEISMIC
STL PLATE, SEE SUPPORTS SHALL BE STAMPED AND SEALED BY A PROFESSIONAL STRUCTURAL
TABLE B ENGINEER REGISTERED IN THE STATE OF ALASKA.
FOR THICKNESS
6. DESIGN WEIGHTS REFER TO THE PIPE SIZE SHOWN SUPPORTED AT THE
SPACING LISTED AND SHALL BE USED FOR DESIGN OF ALL SPECIAL
HANGER SYSTEMS.
1/4
PIPE STANCHION, 7. AT LEAST ONE PIPE HANGER OR SUPPORT SHALL BE LOCATED IMMEDIATELY
SIZE AS SPECIFIED IN ADJACENT TO THE JOINT OF ANY CONCENTRATED LOAD OR BEND IN THE
TABLE B PIPE SUCH AS VALVES, FITTINGS, ETC., IN ADDITION TO THE MAXIMUM
SPANS LISTED ABOVE.
STRUCTURAL STEEL
SS ANCHOR BOLT 8. TYPICAL DETAILS SHOWN ON THIS DRAWING ARE FOR REFERENCE ONLY.
OR CONCRETE ANCHOR REFER TO SPECIFICATION SECTION 15071 FOR SEISMIC DESIGN REQUIREMENTS.
WITH FULL THREADED
STUDS, TYP., SEE GROUT AFTER
TABLE B LEVELING WITH
NON-SHRINK TABLE B - PIPE STANCHION
WELDED BEAM GROUT
FINISH
ATTACHMENT W/ NOMINAL PIPE
FLOOR PLATE BOLT
BOLT AND NUT. 1" T0 4" PIPE SIZE STANCHION DIA BOLT SIZE
THICKNESS EMBED
CAPACITY: 3/8" PIPE WELD TO STRUC (SCHEDULE 40)
THROUGH 12" PIPE STEEL PER MFRS
EMBED DEPTH, 2" 1 1/2" 1/4" 3/8" 5"
RECOMMENDATIONS
SEE TABLE B
MAXIMUM ALLOWABLE LOAD LEVELING 2 1/2" 1 1/2" 1/4" 3/8" 5"
NUTS 3" 2"
3/8"ROD 610 LBS WELDED EYE ROD 3/8" 1/2" 5"
1/2"ROD 1120 LBS SIZE AS REQUIRED 4" 3" 3/8" 1/2" 5"
5/8"ROD 1810 LBS NOTE:
3/4"ROD 2710 LBS 6" 3" 3/8" 1/2" 5"
7/8"ROD 3770 LBS 1. SPACING SHALL BE AS REQUIRED, BUT SHALL
8" 4" 3/8" 5/8" 8"
NOT EXCEED SPANS SHOWN IN TABLE A.
10" 4" 3/8" 5/8" 8"
TYPE C 12" 6" 3/8" 5/8" 8"
TYPICAL STRUCTURAL
DETAIL 3 ATTACHMENT
14" 6" 1/2" 3/4" 8"
NTS TYP 16" 6" 1/2" 3/4" 8"
DETAIL 4 18" 8" 5/8" 7/8" 8"
NTS TYP
20" 8" 5/8" 7/8" 8"
ONE INCH AT FULL
24" 8" 3/4" 1" 8" SIZE
10"
IF NOT ONE INCH,
SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M5.03
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, HVAC DETAILS AND
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 SCHEMATICS 37 - 72
NOTE: NOTE:
SUPPORT ROD SUPPORT ROD SUPPORT ROD SIZE AND
SUPPORT ROD SIZE AND 1. USE MSS TYPE 4 SINGLE BOLT PIPE 1. WITH COPPER PIPE REPLACE MSS 39
SIZE AND SPACING SIZE AND SPACING SUPPORT ROD
SPACING AS SPECIFIED SPACING AS SPECIFIED CLAMP FOR UNINSULATED PIPE. SADDLES WITH CALCIUM SILICATE OR
AS SPECIFIED IN SIZE AND SPACING
AS SPECIFIED IN IN TABLE A ON M5.03 IN TABLE A ON M5.03
TABLE A ON M5.03 AS SPECIFIED IN WOOD BLOCKS AND MSS TYPE 40
TABLE A ON M5.03
JAM NUT TABLE A ON M5.03 SHIELDS.
JAM NUT JAM NUT JAM NUT JAM NUT
WELDLESS EYE
THERMAL NUT MSS TYPE 17 ADJUSTABLE
SHIELD DOUBLE-BOLT PIPE THERMAL ROLLER HANGER,
CLAMP MSS TYPE 3, SHIELD MSS TYPE 43
ADJUSTABLE SEE NOTE 1
STEEL CLEVIS, "J" HANGER, THERMAL
ADJUSTABLE MSS TYPE 1 MSS TYPE 5 SHIELD
STEEL
CLEVIS, MSS PROTECTIVE MSS TYPE 39
TYPE 1 INSULATION SHIELD, SEE NOTE 1
MSS TYPE 40
VARIES

TYPE 1 TYPE 1A TYPE 2 TYPE 3 TYPE 4


DETAIL 1 DETAIL 2 DETAIL 3 DETAIL 4 DETAIL 5
NTS TYP NTS TYP NTS TYP NTS TYP NTS TYP

DESIGN LOADS:

DESIGN LOADS: SIZE LOAD (LBS)


PIPE CLAMP, SUPPORT ROD
2 1/2" 390
FRAMING PIPE STRAP, FRAMING SIZE AND SPACING SIZE LOAD (LBS)
CHANNEL TYPE AS SPECIFIED IN 3" 530
CHANNEL TYPE 3/4"-1 1/2" 190
TABLE A ON M5.03 4" 810
2"-3" 420 5" 1160
4"-5" 610 6" 1570
6"-12" 870 8"-10" 2500
DOUBLE-BOLT 12"-14" 2700
PIPE CLAMP 16"-30" 2900
MSS TYPE 3

"Z" SHAPED STEEL


FRAMING CHANNEL 1-5/8"SQ. X 12 STRAP FITTING, TYP
GAGE MIN., GALVANIZE AFTER 2 SS EXPANSION
FABRICATION FRAMING CHANNEL RISER
NOTES: ANCHORS EACH CLAMP
1-5/8"SQ. X 12 GAGE MIN., CLAMP, MSS
GALVANIZE AFTER 1/2" THROUGH 30" PIPE
1. DO NOT USE FOR HORIZONTAL PIPES LARGER THAN 2" 3/4" THROUGH 12" PIPE TYPE 8
WHEN FRAMING CHANNEL IS MOUNTED VERTICALLY. FABRICATION 3/4" THROUGH 30" PIPE FOR VERTICAL PIPE ONLY FOR VERTICAL PIPE ONLY

TYPE 5 TYPE 6 TYPE 7 TYPE 8 TYPE 9


DETAIL 6 DETAIL 7 DETAIL 8 DETAIL 9 DETAIL 10
NTS TYP NTS TYP NTS TYP NTS TYP NTS TYP

4 1/2"
SUPPORT ROD SIZE AND
SPACING AS SPECIFIED IN
TABLE A ON M
JAM NUT GENERAL NOTES:
STEEL CLEVIS
WELD TO PIPE BASE ELBOW WELDED LINKED EYE RODS
MSS TYPE 14
BEFORE ANY OR BASE TEE REQUIRED FOR STRUC 1. WITH COPPER PIPE PROVIDE A FULL 360° WRAP OF 1/16

1 1/2"
LINING IS 3" ATTACHMENTS INCH THICK NEOPRENE BONDED TO PIPE WITH A
WELDING LUG STEEL PLATE
APPLIED TO PIPE FORGED STEEL COMPATIBLE WATERPROOF ADHESIVE. FOR
THICKNESS TO MATCH CLEVIS GRIP
ELBOW OR PIPE REQUIREMENTS ON INSULATION USED WITH PIPE HANGERS.

AS REQUIRED
TURNBUCKLE
2. PIPE HANGERS SHALL BE OVERSIZED AS REQUIRED TO
ACCOMMODATE THICKNESS OF INSULATION SPECIFIED.
2"

HANGER SHALL NOT COME INTO CONTACT WITH THE


PIPE STANCHION, DRILL 1/8" DIA INSULATION DIRECTLY, EITHER AT THE VERTICAL YOKE OR
PIPE STANCHION, PLATE TO MATCH
SIZE AS SPECIFIED IN HOLE BEFORE AT THE POINT OF SUPPORT. SEE SPECIFICATIONS.
SIZE AS SPECIFIED IN BASE ELBOW OR TEE
TABLE B ON M5.03 WELDING TABLE ON B/M5.03 1/4
3. REFER TO SPECIFICATION SECTION 15071 FOR SEISMIC
STRUCTURAL DESIGN REQUIREMENTS.
STRUCTURAL REQUIRED FOR PIPE
ATTACHMENT,
ATTACHMENT, 6/M5.03 ATTACHMENTS 1 AND 2
6/M5.03

4 1/2"
2" THROUGH 12" PIPE
NOTE:
1. LUG SHALL BE WELDED TO PIPE BEFORE
2 1/2" THROUGH 30" PIPE INTERNAL LINING IS APPLIED.
4" THROUGH 8" PIPE

TYPE 10 TYPE 11 TYPE 12 TYP SUPPORT ROD ONE INCH AT FULL


SIZE

DETAIL 11 DETAIL 12 DETAIL 13 DETAIL 14


IF NOT ONE INCH,
NTS TYP NTS TYP NTS TYP NTS TYP
SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M5.04
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, TYPICAL DETAILS
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PIPE HANGERS 38 - 72
AIR HANDLING UNIT (AHU) SCHEDULE

SUPPLY FAN - DRAW THRU RETURN FAN ELECTRIC HEATING COIL HEAT EXCHANGER

FILTERS
ELECTRICAL ELECTRICAL AIR TEMP (°F) MOTOR SELECTION BASED ON
WEIGHT
SYMBOL LOCATION SERVICE TOTAL EXTERNAL TOTAL EXTERNAL MANUFACTURER/MODEL
(LBS) MIN.
AIRFLOW STATIC STATIC AIRFLOW STATIC STATIC CAPACITY (OR APPROVED EQUAL)
VOLT-P-HZ TYPE SENSIBLE
(CFM) PRESSURE PRESSURE (CFM) PRESSURE PRESSURE (KW) M
EFF. (%)
(IN W.C.) (IN W.C.) (IN W.C.) (IN W.C.) E SIZE PD DEPTH
BHP HP VOLT-P-HZ BHP HP VOLT-P-HZ ENT. LVG. HP FLA VOLT-P-HZ QTY.
R (IN) (IN) (IN)
V

STREET VARIABLE 4 24x20 YORK SOLUTIONS AIR


AHU-3 4500 6000 2.7 2.1 4.9 7.5 460-3-60 5550 2.1 1.0 3.8 5 460-3-60 28 70 80 460-3-60 WHEEL 63 0.25 0.4 460-3-60 7 0.08 2
WING VOLUME 8 16x20 HANDLING UNIT

NOTES:
NOTES:
1.HEAT
1. HEATRECOVERY
RECOVERYPERFORMANCE
PERFORMANCEISISBASED
BASEDON
ONCOIL
COILEAT
EAT28°F
28°FWITH
WITH29%
29%RH
RHONONBOTH
BOTHSA
SAAND
ANDRA.
RA.
2.2.VFDs
VFD'SSHALL
SHALLBE
BEPROVIDED
PROVIDEDBY
BYDDC
DDCCONTRACTOR
CONTRACTORAND
ANDINSTALLED
INSTALLEDINAT FIELD
THE ON AHU CASING.
FIELD.

FAN POWER TERMINAL UNIT SCHEDULE


ELECTRIC
SIZE CFM NC LEVELS FAN ELECTRICAL
HEATING COIL
SYMBOL MFR/MODEL REMARKS
UNIT INLET OUTLET MAX MIN RAD DISCH CFM ESP HP KW EAT/LAT VOLT PH HZ

FTU-3 IS AN OWNER FURNISHED


FTU-3 C 08 14.1x1.1 600 350 19 13 600 0.20 0.33 5.0 55/95 277 1 60 TITUS/DTFS-F
CONTRACTOR INSTALLED ITEM

NOTES:
1. ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS FROM TABLES IN ARI STANDARD 885-89.
2. SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-94.

FAN SCHEDULE

MOTOR
STATIC SOUND
AIRFLOW FAN WEIGHT
SYMBOL LOCATION TYPE PRESSURE DRIVE POWER CONTROL MFR/MODEL FEATURES
(CFM) RPM (LBS)
(IN W.C.) (dBA)
HP RPM VOLT-P-HZ ENCLOSURE

STREET WINGS 300/


EF-5 INLINE 0.3 DIRECT 1521 54 1/10 1550 115-1-60 TEAO TWO SPEED SWITCH GREENHECK SQ-90-D ADJUSTABLE SPEED FAN 41
MEZZANINE 500
KITCHEN HOOD VARIABLE SPEED REMOTE SWITCH W/ SPEED
EF-6 INLINE 600 0.5 DIRECT - - 1/6 - 120-1-60 - FABER INCA PRO 30 -
FAN CONTROL CONTROL

NOTES:
1. KITCHEN HOOD SHALL INCLUDE TRIM WITH BAFFLE TYPE FILTERS AND LIGHTS.

ELECTRIC HEATER SCHEDULE


SELECTION BASED ON
CAPACITY LENGTH
SYMBOL TYPE LOCATION VOLT-P-HZ AMPS MANUFACTURER/MODEL REMARKS
(KW) (IN)
(OR APPROVED EQUAL)

EB-1 BASEBOARD LUNCH/TRAINING 1.0 48 277-1-60 3.6 MARKEL 3900 HYDRONIC ELECTRIC REMOTE T'STAT

EB-2 BASEBOARD LUNCH/TRAINING 1.5 72 277-1-60 5.4 MARKEL 3900 HYDRONIC ELECTRIC REMOTE T'STAT

HC-1 DUCT HEATER SIGN SHOP 4 - 277-1-60 8.3 NAILOR DH SPACE THERMOSTAT

DIFFUSER/GRILLE/REGISTER SCHEDULE

SELECTION BASED ON
MAX APD (IN
SYMBOL TYPE MANUFACTURER/MODEL (OR MAX NC REMARKS
WC)
APPROVED EQUAL)

SD-1 CEILING MOUNT TITUS MCD 30 0.1 -

SD-2 DUCT MOUNT TITUS MCD 30 0.1 -

SG-1 DUCT MOUNT TITUS 272RL 30 0.1 WITH OPPOSED BLADE DAMPER

RG-1 CEILING MOUNT TITUS 350ZRL 30 0.1 -

RG-2 DUCT MOUNT TITUS 350ZRL 30 0.1 -

RG-4 DUCT MOUNT TITUS 350ZRL 30 0.1 -

NOTES:
1. CEILING MOUNT TYPE SHALL BE MOUNTED ACCORDINGLY FOR 24" x 24" CEILING MODULE OR GYPBOARD
CEILING PER REFLECTED CEILING PLAN. INCLUDE ANY ADDITIONAL APPURTENANCES AS NEEDED. ONE INCH AT FULL
SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL M6.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, HVAC EQUIPMENT
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 SCHEDULES 39 -- 72
L M N O P Q
NOTES:
1. FIELD VERIFY EXACT SIZE AND LOCATION OF STUB OUT.

5E 2. RADIANT FLOOR HEATING SYSTEM UNDER SLAB IS NOT SHOWN. DESIGN


SHALL BE PROVIDED BY CONTRACTOR IN COMPLIANCE WITH SECTION
FCO, TYP
15772.

3"W 3. PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS.

4. PROVIDE ACCESS PANELS FOR ALL IN WALL TRAP PRIMERS.


FCO, TYP
UP TO FD-1, TYP 5

4E
6"RD, SEE CIVIL FOR 6"W
CONNECTION, TYP 4
3"W

3E
FD, UP TO
EYEWASH
TD-1, 3"W
TYP 3 4"W, TYP

OIL WATER
SEPARATOR
SEE 4/P5.01

FCO 3"V 2E
3"V 3"W

FCO

CONNECT 6"W TO 3"W


H J
TRENCH FOR CA PIPING AND
K 3"W
EXST 6"W STUB OUT,
ELECTRICAL CONDUIT SEE SEE NOTE 1
3"RD, SEE CIVIL FOR 12/S5.01 FOR DETAIL AND
3"W STUB OUT FOR
1E
CONNECTION, TYP 6 NOTE 3 COMP TD-2
GAS FUTURE CONNECTION
(IE=36" BFF)

6"W
TD-1 TD-1 TD-1 TD-1
1
2"W FCO
SL

4"W

FD-2
4"W

SL
2"W 2"W
3/4"CA ELECTRICAL
4"W

2"V
4"W

3/8"CA ROOM
FCO WC0

6"W
4"W 4"W 4"W
FCO
4"W
FD-2
DN LOCKER ROOM
FD-1 FD-1 FD-1 FD-1
4"W 2
SECURE
WC0
OFFICE STORAGE
MEN'S
RESTROOM
2"W OFFICE
MACHINE FD-2
SHOP 1 DN
BAY 5 BAY 3 BAY 1 N
FD-2 WITHOUT S-2 2"W
6"W

TRAP AND VENT 2"V JAN 3"W OFFICE

3"W MAINTENANCE BAYS


3
FD-2 WITHOUT 3"W
TRAP AND VENT
CORRIDOR FOUNDATION
PIPING PLAN
6"W

CORRIDOR
BAY 6 BAY64CONDUITS FOR BAY 2
UP WOMEN'S 4
LOCKER
FUTURE LIFT PARTS FILES/
INSTALLATION, OFFICE 8' 0 8' 16'
INVENTORY XEROX
SEE NOTE 2 ONE INCH AT FULL
WC0 SCALE: 1/8"=1'-0" SIZE
4"W
6"W

3"W

"W

FD-1 FD-1 MACHINEFD-1 IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P1.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, FOUNDATION
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PIPING PLAN 40 - 72
L M N O P Q
NOTES:
1. RADIANT FLOOR HEATING SYSTEM UNDER SLAB DESIGN (NOT SHOWN)
SHALL BE PROVIDED BY CONTRACTOR IN COMPLIANCE WITH SECTION
HB-1 5E 15772.

HB-2, TYP 3

FD-1,
TYP 5

RADIANT FLOOR
HEATING SYSTEM ZONE 2 4E
6"RD, RADIANT FLOOR SEE NOTE 1
TYP 4 HEATING SYSTEM ZONE 1 6"RD, TERMINATE
SEE NOTE 1 TO DAYLIGHT,
ZONE 2 SEE CIVIL DWGS
RADIANT HEATING
SYSTEM MANIFOLD

P-6

1/2"CA UP AT
COMPRESSED AIR
STATION, TYP 8
3E

3/4"IW UP, TYP 3 EW-1


FD-2

ZONE 1 1/2" CW
RADIANT HEATING 1/2" HW
SYSTEM MANIFOLD

3"V UP 3/4" HW
P-5
2"IW, 1"CA, 1"HP UP 3/4" CW
WASHER 2E
SERVICE 3"V
6"RD, TERMINATE
BOX
2"IW TO DAYLIGHT,
1"CA SEE CIVIL DWGS
1"HP
3"V
H J K 3/4"CA S-2
3"W FROM FD-2
ABOVE

1/2"IW TO BOOT
1E
COMP 2"V
3"RD, TYP 6 2"V
3/4"IW DN TO GAS WASH
3"VTR
HB-2, TYP BW-1 3"V
3/4" CW
3/4" HW 1
S-1
2"IW POINT OF 3/4"CW, HW UP
3/4"HW CONNECTIONS AT TO MEZZANINE
3/4"CW CAPPED POINT OF
ELECTRICAL CONNECTION
LOCATION
ROOM

6"E UP
THROUGH ROOF LOCKER ROOM
1-1/2"CW
WELDING 1"CW
2
SECURE
EXHAUST OFFICE STORAGE 3/4"HW
SYSTEM 1-1/2"CW MEN'S
RESTROOM OFFICE
welding
MACHINE
table 3"VENT RISER 3/4"IW DN TO HB-1
3/4"CA UP SCF-1
SHOP 1 2"CW
BAY 5 BAY 3 BAY 1
EMERGENCY 3/4"HW OFFICE
EYEWASH-2 JAN
3/4"CW 3/4"CW

MAINTENANCE BAYS
3
2"IW CORRIDOR
2"V RISER
1-1/2"HP N

CORRIDOR
1-1/2"CA
BAY 6 EMERGENCY
BAY 4 BAY 2
UP
UP TO WOMEN'S 4
EYEWASH-1 UPPER LEVEL
PARTS
LOCKER
FILES/
FIRST FLOOR
3/4"CA ALONG OFFICE PIPING PLAN
INVENTORY XEROX 1
TOP OF 7' WALL 1"HW
ONE INCH AT FULL
2"CW SIZE

MACHINE 3"VENT RISER 8' 0 8' 16'


1-1/2"HP IF NOT ONE INCH,
1"CA
SHOP 2 3/4"CA DN TO WH-1 SCALE ACCORDINGLY
1-1/2"CA SEE OFFICE SCALE: 1/8"=1'-0"

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P1.02
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, FIRST FLOOR
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PIPING PLAN 41 - 72
L M N O P Q
NOTES:
1. SLOPE HP AND CA PIPING DOWN TOWARD DRAIN LEG AND PROVIDE
DRAIN VALVE AT 3' AFF.
5E
3/4"IW

PROVIDE DRAIN VALVE


AT BOTTOM OF RISER,
SEE NOTE 1

1/2"CA DN,
TYP 8
3/4"CA 3/4"CA
4E
3"RD,
TYP 4

1/2"HP DN, OPEN TO BELOW


TYP 3 3/4"HP PROVIDE DRAIN VALVE
DN TO ZONE 2
RADIANT HEATING AT BOTTOM OF RISER,
SYSTEM MANIFOLD SEE NOTE 1

3E
3/4"IW DN,
TYP 4

DN TO ZONE 1 1"HWS
3/4"HP 1"HWR
RADIANT HEATING
1"CA SYSTEM MANIFOLD
1"CA
1"IW
3"VTR 3/4"HP

2E
1"HP 1-1/4"HWS
1-1/4"HWR
PROVIDE DRAIN
1-1/2"HWS
VALVES AT BOTTOM
1-1/2"HWR
OF DRAIN LEG, SEE
H J K NOTE 1
3"VTR
FD-2
WH-2 B-2 T-3 P-4 1E
3"RD, TYP 3/4"CA DN TO CA
3/4"IW DN TO HB-2, 1/2" MAKE UP
STATION, TYP
TYP WATER TO B-2

1
3/4"CW, HW DN

3"VTR
VEHICLE EXHAUST FOLLOW ROOF
HOSE REEL MOUNTED SLOPE FOR MAXIMUM
ON SWING ARM, TYP 2 CLEARANCE, TYP

3/4"CA MECH 3"VTR 2


FLUID HOSE REELS ROOM
1"HP
3/4"IW CA, HF, E01, EO2, ATF, BRIDGE CRANE 2"IW
3/4"CA 3/4"CA
3/4"CA GR, TYP. SEE P5.04 TRACKS 3/4"IW 1-1/2"HP
3/4"IW FOR PIPING DETAILS 1-1/2"CA
UP FROM
2"VTR
3/4"CA 1st FLOOR

BALL VALVE, TYP

3 SECOND FLOOR
PIPING PLAN 1
2"IW 1"CA
1-1/2"HP
2'IW
4
1-1/2"CA 1"HP
1"CA 3/4"IW 1-1/2"HP
1"HF 1"CA 1-1/2"CA
1"EO1 1"HF 1-1/2"HF ONE INCH AT FULL
1"EO2 1"EO1 1-1/2"EO1 3"VTR SIZE
1"ATF 1"EO2
1"GR 1"ATF 1-1/2"EO2
IF NOT ONE INCH,
1"GR 1-1/2"ATF SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P1.03
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, SECOND FLOOR
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PIPING PLAN 42 - 72
L M N O P Q

5E

4E

OVERFLOW 3"Ø RD
TYP 4 TYP 4

3E

2E
3"VTR

H J K
1E
3"VTR

1
SLOPE

SLOPE

2
SLOPE SLOPE
SLOPE

3
ROOF PIPING PLAN 1

ONE INCH AT FULL


SIZE
OPE

OPE

OPE

SLOPE SLOPE IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P1.04
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, ROOF
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PIPING PLAN 43 - 72
1"

POC TO
POC TO EXISTING EXISTING 2" IW
1" CW

WATER PIPING
SCHEMATIC 2
NTS -

2"
3"

2" 1-1/2"

1-1/2" 1-1/2"

3"
3" 3"

3"
3" 4" 3" 4" 3" 4"

6"

CONNECTION TO SANITARY PIPING


EXST 6"W
SCHEMATIC 1
NTS -
ONE INCH AT FULL
SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P2.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, PIPING
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 SCHEMATICS 44 - 72
AIR SEPARATOR MEZZANINE MAINTENANCE AREA
1/2" MAKEUP
NOTES:
WATER
1. SEE PLAN DWGS FOR VENT PIPING CONNECTION AND
ROUTING.
RPBP
AAV 2. PROVIDE AIR TIGHT COVERS AND REQUIRED HARDWARE FOR
1-1/4"HWR 1"HWR INDOOR INSTALLATION.
TO FD TO
FD 1-1/4"HWS 1"HWS
3. TOP AND ACCESS PANEL SHALL HAVE H20 VECHICLE LOADING
1-1/2"HWR 1-1/2"HWS CAPABILITY.
NORTH ZONE SOUTH ZONE
TO FD CHEMICAL MANIFOLD MANIFOLD
AAV FEEDER
P-5 P-6
6'-0"
M M
4" OPENING FOR VENT
B-2 TO CONNECTION
HOUSEKEEPING FD P-4
NC
PAD T-3 CLEAR ACCESS
OPENINGS

TO FD TO FD A

4'-0"
RADIANT HEATING SLAB TEMPERATURE SENSOR IN NORTH ZONE
WATER PIPING SLAB TEMPERATURE SENSOR IN SOUTH ZONE

SCHEMATIC 1
NTS -

AIR TIGHT ACCESS


SLOT FOR BAFFLE AND
COVER, TYP
WEIR PLATES, TYP

OIL WATER SEPARATOR


DETAIL 4
3/4"CW NTS -
1/2"

3/4"HW 1/2"CA

1-1/2" DIA LIFT HOLE, 1 EACH SIDE, 3" VENT PIPE,

1'-0"
BOTH SIDES. CONTRACTOR TO SEE NOTE 1
T-4 PLUG AFTER INSTALLATION
FRL

WH-2 CAP

1'-0"

1'-6"
CAP

SEISMIC STRAP 6" INLET PIPING

1'-0"

3'6" Water Depth


450 Gallons @
OIL
1/2" QUICK RETAINER 6"
DISCONNECT BAFFLE OUTLET
PIPING
FLOW DIFFUSER
BAFFLE
DRAIN PAN TO FD 3/8" QUICK
GRIT/SLUDGE

11"
1'-4"
DISCONNECT

9"
RETAINER WEIR
POTABLE WATER

5-1/2"
HEATER PIPING CA STATIONS
1'-4" 1'-0" 1'-9" 1'-11"
DETAIL 3 DETAIL 3
NTS - NTS TYP
OIL WATER SEPARATOR
SECTION A
NTS -
ONE INCH AT FULL
SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P5.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, PIPING
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 DETAILS 45 - 72
HEAVY DUTY FORM 2' DIA DISH PROVIDE SMOOTH
FLOOR DRAIN 2'-0" SQ
FLOOR DRAIN TRANSITION TO
CLASS E ADJACENT

CLEAR
FINISHED FLOOR CONCRETE PAVEMENT

1" MIN

3"
SANITARY TEE OR
COMBINATION WYE 1/8

4"
1'-0"
BEND FOR VENT LINE
WHERE SPECIFIED
2-#3 EW

CAST IRON FRAME


AND COVER PACK ANNULAR
SPACE WITH
90° ELBOW P-TRAP JUTE

FLOOR DRAIN (FD-2) YARD CLEANOUT


HEAVY DUTY
DETAIL 2 DETAIL 3
FLOOR DRAIN (FD-1) NTS TYP
NTS TYP
DETAIL 1
NTS TYP

FINISHED WALL
SURFACE

FLOOR LEVEL
CLEANOUT W/ROUND FLOOR
ACCESS COVER
THREADED
CLEANOUT PLUG
WITH ACCESS
COVER

FLOOR CLEANOUT WALL CLEANOUT

DETAIL 4 DETAIL 5
NTS TYP
NTS TYP

ONE INCH AT FULL


SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P5.02
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, PIPING DETAILS
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 46 - 72
PLUMBING FIXTURE SCHEDULE
CONNECTION SIZES
FIXTURE NO. DESCRIPTION MODEL FLUSH VALVE TRIM TRAP & REMARKS
CW HW VENT
DRAIN

S-1 KITCHEN SINK KOHLER K-3346-3 - KOHLER 15171-FL 3/8" 3/8" 1-1/2" 1-1/2" -

S-2 SERVICE SINK KOHLER K-6714 - K-8905 1/2" 1/2" 3" 3" PROVIDE 3-INCH IRON PIPE TRAP FOR SERVICE SINK

HB-1 HOSE BIBB ZURN Z1300 - - 3/4" - - - NON-FREEZE IN-WALL HYDRANT

HB-2 HOSE BIBB ZURN 195 SERIES - - 3/4" - - - -

FD-1 FLOOR DRAIN JOSAM 37840 - - - - 4" - 16"X16" HEAVY DUTY DRAIN WITH SLOTTED GRATE

FD-2 FLOOR DRAIN ZURN ZS400B - - - - 3" 1-1/2" ROUND WITH SLOTTED OPENINGS

TD-1 TRENCH DRAIN ZURN Z886 - - - - 4" 1-1/2" -

TD-2 TRENCH DRAIN ZURN Z886 - K-973 SHOWER HEAD 1/2" - 3" 1-1/2" BOOT WASH WITH 6' HAND HELD SHOWER HEAD

EW-1 EYE WASH GUARDIAN G1814 - - 1/2" 1/2" - - PROVIDE GUARDIAN G3600 THERMOSTATIC MIXING VALVE

BW-1 BOOT WASH SYMMONS 1-25-FSB - - 1/2" 1/2" - - -

ELECTRIC POTABLE WATER HEATER SCHEDULE


INPUT RECOVERY RATE SELECTION BASED ON
STORAGE TEMPERATURE
SYMBOL LOCATION CAPACIT (GPH)/ TEMP. RISE VOLT-P-HZ FLA MANUFACTURER/MODEL SHIPPING WEIGHT (LBS)
(GAL) RISE (°F)
Y (KW) (°F) (OR APPROVED EQUAL)

STREET WING BRADFORD WHITE


WH-2 1.5 30 21/90 90 120-1-60 - 85
MEZZANINE M-2-30R6DS

ELECTRIC BOILER SCHEDULE

OUTLET
INPUT ELEMENTS SELECTION BASED ON SHIPPING
WATER
SYMBOL LOCATION CAPACITY VOLT-P-HZ MANUFACTURER/MODEL WEIGHT
TEMP
(KW) (OR APPROVED EQUAL) (LBS)
(°F)
QTY KW STEPS@KW

STREET WING
B-2 54 140 3 18 1@18, 1@36 480-3-60 LOCHINVAR BW 1-054C 600
MEZZANINE

PUMP SCHEDULE

MOTOR
FLOW TDH (FT
SYMBOL LOCATION TYPE SERVICE SELECTION BASED ON MFR/MODEL REMARKS
(GPM) H O)
HP RPM VOLT-P-HZ

STREET WING
P-4 INLINE BOILER 24 15 0.33 1750 115-1-60 BELL & GOSSETT 60 1-1/2x5-1/4 -
MEZZANINE
ZONE 1 RADIANT
P-5 INLINE 13 33 0.25 1750 115-1-60 -
MANIFOLD FLOOR
ZONE 2 RADIANT
P-6 INLINE 7 35 0.25 1750 115-1-60 -
MANIFOLD FLOOR

RADIANT FLOOR HEATING SCHEDULE


FLOW HEAD SELECTION BASED ON
MIN OUTPUT NO OF
SYMBOL TYPE ZONE RATE LOSS MANUFACTURER/MODEL REMARKS
(BTUH) LOOPS
(GPM) (FT. H20) (OR APPROVED EQUAL)

- MANIFOLD 1 107000 6 12.9 33.1 HEATLINK -

- MANIFOLD 2 55000 3 6.6 35.4 HEATLINK -

TANK SCHEDULE
TANK SELECTION BASED ON
DIAMETER LENGTH WEIGHT
SYMBOL LOCATION SERVICE TYPE VOLUME MANUFACTURER/MODEL
(IN) (IN) (LBS)
(GAL) (OR APPROVED EQUAL)

STREET WING RADIANT EXPANSION


T-3 16 34 22 270 BELL AND GOSSETT B-85LA
MEZZANINE HEATING TANK
DOMESTIC
STREET WING EXPANSION
T-4 WATER 10 10-3/8 2 21 BELL AND GOSSETT PTA-5
MEZZANINE TANK
HEATING

ONE INCH AT FULL


SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY MECHANICAL P6.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, PLUMBING EQUIPMENT
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 SCHEDULES 47 - 72
L M N O P Q
L M N O P Q
NOTES:
1. SPRINKLER SYSTEM SHALL BE DESIGNED BY LICENSED FIRE
PROTECTION ENGINEER.
5E
2. SPRINKLER DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE
3E WITH NFPA 13 AND APPROVED BY CITY/BOROUGH OF JUNEAU FIRE
DEPARTMENT.

MEZZANINE 4E
AREA
2E
MAINTENANCE BAYS

1E
3E

1 TOOL
REPAIR
MEZZANINE FP PLAN 2
N
SECURE
8' 0 8' 16' STORAGE
SCALE: 1/8"=1'-0"
2E

SIGN SHOP
SPRINKLER PIPE
H J K POINT OF
LUNCH/TRAINING
CONNECTION
1E
CORRIDOR
1

CAP PIPE FOR


FUTURE
CONNECTION

FIRST FLOOR FP PLAN 1


N
FIRE SPRINKLER ZONE
8' 0 8' 16'
ZONE CLASSIFICATION DENSITY
SCALE: 1/8"=1'-0"
MAINTENANCE BAYS/ SIGN SHOP ORDINARY HAZARD GROUP 2 0.25 GPM/SF PER FM GLOBAL STANDARDS
LUNCH/TRAINING/ CORRIDOR LIGHT HAZARD 0.10 GPM/SF OR PER NFPA 13
TOOL REPAIR/ SECURE STORAGE ORDINARY HAZARD GROUP 2 0.20 GPM/SF OR PER NFPA 13
ONE INCH AT FULL
MEZZANINE ORDINARY HAZARD GROUP 2 0.20 GPM/SF OR PER NFPA 13
SIZE

IF NOT ONE INCH,


SCALE ACCORDINGLY

CONSOLIDATED PUBLIC
WORKS FACILITY FP1.01
www.tetratech.com
230 South Franklin, Suite 212 STREETS WING ADDITION, FIRE PROTECTION
Juneau, Alaska 99801
Phone: 907-586-6400 Fax: 907-463-3677
E10-273 PLAN 48 - 72
GENERAL NOTES
GENERAL ABBREVIATIONS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
LABORATORY AND MEDICAL GAS ABBREVIATIONS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
FIRE PROTECTION SYMBOLS A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING, PLUMBING, TEMPERATURE
CONTROLS, AND FIRE PROTECTION WORK.
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION SYMBOL DESCRIPTION ADDITIONAL REMARKS
B. CONTRACTOR SHALL VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING
AD ACCESS DOOR/PANEL MAX MAXIMUM A MEDICAL COMPRESSED AIR MAP MASTER ALARM PANEL COST PROPOSAL. CONTRACTOR IS ADVISED THAT ALL LOCATIONS ARE APPROXIMATE. AN ATTEMPT
AFF ABOVE FINISHED FLOOR MC MECHANICAL CONTRACTOR AAP AREA ALARM PANEL MVP MEDICAL VACUUM PUMP F FLOW SWITCH COORDINATE INTERFACE WITH FIRE ALARM SYSTEM CONTRACTOR HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. THIS CONTRACTOR
SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL
AMB AMBIENT MFR MANUFACTURER CA COMPRESSED AIR (NON-MEDICAL) N MEDICAL NITROGEN
UPRIGHT SPRINKLER COMPONENTS NEED TO BE REMOVED IN THE DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS.
AVERA FACILITY DEVELOPMENT
BOB BOTTOM OF BEAM MIN MINIMUM CO MEDICAL CARBON DIOXIDE NO MEDICAL NITROUS OXIDE REFER TO SPECIFICATIONS FOR TYPES AND FINISHES. IF DEVIATION BETWEEN EXISTING CONDITIONS AND NEW WORK IS FOUND, CONTRACTOR SHALL
PENDANT SPRINKLER
DIA DIAMETER NIC NOT IN CONTRACT EOC EMERGENCY OXYGEN CONNECTION O MEDICAL OXYGEN PENDANT REFERES TO FULL, SEMI-RECESSECT AND RECESSED TYPES. NOTIFY ENGINEER.
CONCEALED SPRINKLER LOCATIONS FOR EACH ARE INDICATED IN THE SPECIFICATIONS OR ON THE PLANS.
DN DOWN NTS NOT TO SCALE HE MEDICAL HELIUM PRV PRESSURE REDUCING VALVE
SIDEWALL SPRINKLER C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED
E EXISTING PC PLUMBING CONTRACTOR HP HORSEPOWER VAC MEDICAL VACUUM
OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE
EC ELECTRICAL CONTRACTOR PSIG POUNDS PER SQUARE INCH GUAGE IA INSTRUMENT AIR VB VALVE BOX EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS
EFF EFFICIENCY RPM REVOLUTIONS PER MINUTE LA LABORATORY AIR WAGD MEDICAL WASTE ANESTHESIA GAS DISPOSAL OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. ALL
FPM
FPS
FEET PER MINUTE
FEET PER SECOND
SHT
TOB
SHEET
TOP OF BEAM
LV
MAC
LABORATORY VACUUM
MEDICAL AIR COMPRESSER
WC WATER COLUMN TEMPERATURE CONTROL SYMBOLS SHUTDOWNS SHALL BE PLANNED TO BE COMPLETED DURING OFF HOURS TO MINIMIZE IMPACT TO
THE OWNER. ALL SHUTDOWNS SHALL BE COORDINATED WITH THE OWNER A MINIMUM OF 14 DAYS
PRIOR TO WORK. THE CONTRACTOR SHALL PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO
GC GENERAL CONTRACTOR TOS TOP OF STEEL SYMBOL DESCRIPTION ADDITIONAL REMARKS ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT
GPM GALLONS PER MINUTE VEL VELOCITY FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING
WALL MOUNTED CONTROL DEVICE REFER TO MOUNTING HEIGHTS DETAIL FOR MOUTING ELEVATION. EQUIPMENT. TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS
#
L
LF
LENGTH
LINEAR FEET
VFD VARIABLE FREQUENCY DRIVE
GENERAL MECHANICAL SYMBOLS # INDICATES TYPE T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON MONOXIDE, ETC.)
REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. WHEN SENSOR
ARE OPERATIONAL AND HAVE PASSED ALL REQUIRED TESTING.

OCCUPANCY SENSOR IS NOT SHOWN ON ELECTRICAL DRAWINGS IT SHALL BE PROVIDED AND INSTALLED D. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. DURING
SYMBOL DESCRIPTION ADDITIONAL REMARKS BY THE TEMPERATURE CONTROLS CONTRACTOR. EACH PHASE THE CONTRACTOR SHALL COMPLETE ALL WORK LOCATED WITHIN THE BOUNDARY OF

HVAC ABBREVIATIONS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
# SHEET NOTE
DENOTES SPECIFIC REQUIREMENT FOR THE SHEET ON WHICH THE NOTE APPEARS
AND IS USED TO DESCRIBE WORK THAT IS TOO LENGHTY TO PLACE ON PLAN.
# DUCT, PIPE, OR CEILING MOUNTED CONTROL SENSOR
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS
FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON DIOXIDE, ETC.)
THAT PHASE. ANY WORK AND THAT MUST BE COMPLETED IN THE AREA AFTER THAT AREA HAS BEEN
TURNED OVER TO THE OWNER SHALL BE IDENTIFIED AT THE BEGINNING OF THE PHASE FOR
EVALUATION AND ACCEPTANCE OF THE OWNER.
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION PIPING NUMBER INDICATES NOMINAL DIAMETER IN INCHES,
- SOLID LINE INDICATES SYSTEM SUPPLY LETTER(S) INDICATES SYSTEM. AUTOMATIC CONTROL VALVE (3-WAY) REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS E. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING,
AB AIR BLENDER HC HEATING COIL -- DASHED LINE INDICATES SYSTEM RETURN REFER TO ABBREVIATIONS FOR SYSTEM TYPE. AUTOMATIC CONTROL VALVE (2-WAY) FOR ADDITIONAL INFORMATION AND REQUIREMENTS. ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND
AC AIR CONDITIONING UNIT (SPLIT SYSTEM INDOOR UNIT) HP HORSEPOWER MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND REFINISHING SHALL MATCH THE
AHU AIR HANDLING UNIT HPC HIGH PRESSURE STEAM CONDENSATE DIAMETER DAMPER SHALL BE SAME SIZE AS DUCT UNLESS NOTED OTHERWISE. REFER TO EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE.
MOTORIZED CONTROL DAMPER
BFU BOILER FEED UNIT HPS HIGH PRESSURE STEAM SUPPLY (86 PSIG AND ABOVE) SEQUENCES, SCHEMATICS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
M AND REQUIREMENTS. F. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, "TO BE RETAINED, RELOCATED"
DENOTES CONNECTION OF NEW
BLR BOILER HRC HEAT RECOVERY CHILLER PROTECT EXISTING SYSTEM FROM ENTRANCE OF FOREIGN DEBRIS DURING WORK. OR HEREINAFTER NOTED, ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE
WORK TO EXISTING SYSTEM
CAV CONSTANT AIR VOLUME BOX HUM HUMIDIFIER REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW
PRESSURE/TEMPERATURE TEST PORT CONSTRUCTION AND/OR WITH PROPOSED USAGE OF SPACE BY OWNER AS FOLLOWS:
CC COOLING COIL HWR HYDRONIC HOT WATER RETURN ARROW INDICATES DIRECTION OF FLOW IN PIPING
CD CONDENSATE DRAIN HWS HYDRONIC HOT WATER SUPPLY REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS 1. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP AT THE
F/S FLOW MEASURING STATION
CFM CUBIC FEET PER MINUTE LPC LOW PRESSURE STEAM CONDENSATE #/# ARROW INDICATES DOWNWARD PIPE SLOPE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. NEAREST ACTIVE MAIN WITH MATERIAL TO MATCH EXISTING
WHERE PIPING IS NOT MARKED, REFER TO SPECIFICATIONS FOR REQUIREMENTS 2. REMOVE ALL FIXTURES, CARRIERS, SUPPLY AND WASTE AND VENT PIPING, STEAM, HEATING HOT
#/# INDICATES SLOPE IN INCHES PER FOOT
CH CHILLER LPS LOW PRESSURE STEAM SUPPLY (0-12 PSIG) WATER, HVAC SUPPLY, RETURN AND EXHAUST AS NOTED. CAP AT NEAREST ACTIVE MAIN. SUPPLY
CP CONDENSATE PUMP LV LOUVER ISOLATION VALVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM AND RETURN MAINS ON PIPING SYSTEMS CONVEYING WATER OR GASES SHALL BE VALVED AND
CR CONDENSER WATER RETURN LWT LEAVING WATER TEMPERATURE FIRE PROTECTION GENERAL NOTES CAPPED.
3. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED
CS CONDENSER WATER SUPPLY MBH BTU (1000'S) CHECK VALVE A. FIRE PROTECTION WORK SHALL INCLUDE, BUT NOT LIMITED TO, THE FOLLOWING: REMOVAL OF EXISTING STANDARD RESPONSE HEADS AND AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CT COOLING TOWER MD MANUAL DAMPER ARROW INDICATES DIRECTION OF NORMAL FLOW BRANCH PIPING AND INSTALLATION OF NEW QUICK RESPONSE HEADS AND ASSOCIATED BRANCH PIPING WITHIN ALL RENOVATED SPACES. AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE
CU CONDENSING UNIT MOD MOTOR OPERATED DAMPER REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE
PIPE IN SLEEVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM B. ALL AREAS OF THE BUILDING INDICATED SHALL BE SPRINKLERED ACCORDING TO THE CURRENTLY ADOPTED EDITION OF NFPA STANDARD 13 AND ACCOMPLISHED IN THE REMODELED AREA.
CUH CABINET UNIT HEATER MPC MEDIUM PRESSURE STEAM CONDENSATE
OTHER NFPA STANDARDS AS REQUIRED. ENTIRE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE STATE FIRE 4. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH
CWR CHILLED WATER RETURN MPS MEDIUM PRESSURE STEAM SUPPLY (13-85 PSIG) BALANCING DEVICE CIRCUIT SETTER, AUTOFLOW, ETC. MARSHAL OFFICE, OWNER'S INSURANCE COMPANY AND AUTHORITIES HAVING JURISDICTION. EXISTING.
CWS CHILLED WATER SUPPLY NC NORMALLY CLOSED # # INDICATES FLOW TO BE BALANCED IN GPM REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM 5. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED
D DIFFUSER NO NORMALLY OPEN C. FIRE SPRINKLER DESIGN SHALL BE BASED ON HYDRAULIC CALCULATIONS ACCORDING NFPA 13, WITH SHOP DRAWINGS PREPARED ACCORDING TO PIPING OR DUCTWORK SHALL BE PATCHED TO MATCH EXISTING CONSTRUCTION.
ELBOW UP THE REQUIREMENTS OF THE STATE FIRE MARSHAL AND AUTHORITIES HAVING JURISDICTION. 6. RE-SUPPORT ANY PIPING AND DUCTWORK WHICH WAS SUPPORTED FROM ELEMENTS OF THE
DD DUAL DUCT OA OUTDOOR AIR ELBOW DOWN BUILDING WHICH WERE REMOVED AS A PART OF THE WORK REQUIRED UNDER THESE DOCUMENTS.
DX DIRECT EXPANSION P PUMP D. SPRINKLER CONTRACTOR SHALL OBTAIN STATIC AND RESIDUAL WATER PRESSURE AND FLOW PRIOR TO SYSTEM DESIGN AND SHALL SUBMIT 7. RECONNECT ANY CONTROL WIRING OR PNEUMATIC TUBING THAT WAS CONNECTED TO REMOVED
TEE UP RECENT HYDRANT FLOW TEST DATA WITH SHOP DRAWING SUBMITTALS. EQUIPMENT AND WHICH IS REQUIRED FOR THE CONTINUED PROPER OPERATION OF THE BUILDING
EA EXHAUST AIR PC PUMPED CONDENSATE
TEE DOWN AUTOMATION SYSTEM.
EAT ENTERING AIR TEMPERATURE PRV PRESSURE REDUCING VALVE E. DRAWINGS ARE SCHEMATIC IN NATURE, INTENDED TO CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF THE SYSTEM. SPRINKLER
TEE HORIZONTAL G. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO OWNER FOR FIRST RIGHT OF
EF EXHAUST FAN PSC PUMPED STEAM CONDENSATE SYSTEM INSTALLING CONTRACTOR SHALL COORDINATE SYSTEM ARRANGEMENT WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND SALVAGE. IF OWNER REFUSES SALVAGE ITEMS, REMOVING CONTRACTOR SHALL BE RESPONSIBLE
EFF EFFICIENCY R REGISTER ELECTRICAL COMPONENTS. SPRINKLER PIPING SHALL NOT BE INSTALLED BELOW MECHANICAL EQUIPMENT OR WITHIN CLEARANCE SPACES FOR FOR DISPOSAL.
INDICATES POINT WHERE PIPING CHAGES FROM ONE SIZE TO ANOTHER. SMALL MECHANICAL EQUIPMENT. PROVIDE SPRINKLER PROTECTION BELOW ALL DUCTS GREATER THAN 48 INCHES IN WIDTH. INSTALLING CONTRACTOR
ERC ENERGY RECOVERY COIL RA RETURN AIR PIPE REDUCER
POINT OF ARROW INDICATES SMALLER SIZE SIDE OF TRANSITION. SHALL BE RESPONSIBLE FOR ANY MODIFICATIONS TO THE SYSTEM REQUIRED TO AVOID CONFLICTS.
ERW ENERGY RECOVERY WHEEL REFL REFRIGERANT DX LIQUID H. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH
EXTENT OF WORK INCLUDING BUT NOT LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED,
ET EXPANSION TANK REFS REFRIGERANT DX SUCTION GAS UNION F. AREAS IDENTIFIED INDICATE THE RECOMMENDED MINIMUM OCCUPANCY CLASSIFICATION, SPRINKLER TEMPERATURE CHARACTERISTIC OR WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING REMOVED AND/OR
EWT ENTERING WATER TEMPERATURE RF RETURN FAN SPRINKLER TYPES TO BE INSTALLED. SPRINKLER SYSTEM SHALL BE DESIGNED TO MEET OR EXCEED THESE RECOMMENDATIONS AND SHALL BE REPLACED, ETC.
SUBJECT TO APPROVAL BY THE AUTHORITY HAVING JURISDICTION.
FB FILTER BANK (CONSISTING OF ONE OR MORE FILTERS) RH RELATIVE HUMIDITY STRAINER WITH BLOW-OFF VALVE REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
I. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS,
FCU FAN COIL UNIT RTU ROOF TOP UNIT G. A PRE-DESIGN MEETING SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO SUBMITTAL OF PIPING LAYOUT DRAWINGS. ARCHITECT SHALL VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS,
FMS FLOW MEASURING STATION SA SUPPLY AIR PRESSURE GUAGE REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES ISSUE COMMENTS CONCERNING SUBMITTAL PACKAGE PRIOR TO COMMENCEMENT OF WORK. DRAINS, AND DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING SYSTEM.
FOR FUEL OIL RETURN SD SMOKE DAMPER H. REFER TO ARCHITECTURAL PLANS FOR SPECIFIC CEILING TYPES AND HEIGHTS, AND AREAS OF EXPOSED STRUCTURE. J. PERFORM AIR AND FLUID BALANCE PRE-TEST ON ALL DISTRIBUTION EQUIPMENT AND ALL AIR
FOS FUEL OIL SUPPLY SF SUPPLY FAN THERMOMETER REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES OUTLETS IN THE AREA PRIOR TO COMMENCING WORK. SUBMIT PRE-TEST INFORMATION TO
FOV FUEL OIL VENT SP STATIC PRESSURE I. COORDINATE PIPING AND SPRINKLERS IN EXPOSED AREAS TO MINIMIZE APPEARANCE. INSTALL SPRINKLERS A MINIMUM OF SIX INCHES FROM OWNER/ENGINEER.
DIFFUSERS, GRILLES AND LIGHT FIXTURES. INSTALL SPRINKLERS IN LAY-IN CEILINGS WITHIN THREE INCHES OF THE CENTER OF CEILING TILE.
FRD FIRE DAMPER STM STEAM REQUIRED SERVICE CLEARANCE FOR EQUIPMENT
K. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO
FSD FIRE SMOKE DAMPER TEMP TEMPERATURE J. COORDINATE INSTALLATION OF SPRINKLERS AND PIPING SYSTEMS TO AVOID FREEZING CONDITIONS. NOTIFY ARCHITECT OF AREAS FOR WHERE ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES
FTR FINNED TUBE RADIATOR TR TRANSFER FIRST SYMBOL APPLIES TO ROUND DUCT AND PIPING. SYSTEM MAY BE EXPOSED TO FREEZING. INSTALL DRY SIDEWALL SPRINKLERS IN ROOMS INDICATED WHERE ROOMS MAY BE UNCONDITIONED OR BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS
CONTINUATION SYMBOLS
SECOND SYMBOL APPLIES TO RECTUANGULAR AND OVAL DUCT. EXPOSED TO FREEZING CONDITIONS. PROVIDE AUXILIARY DRAINS WHERE REQUIRED. DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS
G GRILLE UH UNIT HEATER
GCWR GLYCOL CHILLED WATER RETURN VAV VARIABLE AIR VOLUME BOX REQUIRED AND ACTIVITY. INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE
K. EXPOSED SPRINKLER PIPING, EXCEPT IN MECHANICAL AND STORAGE ROOMS, SHALL BE CLEANED, PRIMED AND PREPARED FOR PAINTING. FESSION
REMOVAL OF ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC. INSTALL IN A PRO AL
GCWS GLYCOL CHILLED WATER SUPPLY VTR VENT THROUGH ROOF LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT ED . NO.

HVAC SYMBOLS REG

ER
L. WHERE SPRINKLER PIPING SYSTEM PENETRATES FIRE RESISTIVE RATED ASSEMBLIES, SEAL OPENINGS WITH APPROVED CONSTRUCTION METHODS

EN
GE GRAVITY EXHAUST WB WET BULB TEMPERATURE REQUIRED. WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A

REGIST

GINEE
AND MATERIALS. FIRE AND/OR SMOKE RATING, ACCESS DOOR SHALL MAINTAIN THE REQUIRED RATING. 10229
GHWR GLYCOL HOT WATER RETURN WC WATER COLUMN
ERIC G.

R
GHWS GLYCOL HOT WATER SUPPLY WPD WATER PRESSURE DROP SYMBOL DESCRIPTION ADDITIONAL REMARKS M. AVOID ROUTING SPRINKLER PIPING ABOVE ELECTRICAL, DATA, IT AND COMMUNICATION PANELS. L. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) INTO ROOMS THAT SHERMAN

A
GI GRAVITY INTAKE WSHPR WATER SOURCE HEAT PUMP RETURN

S
RECTANGULAR DUCTWORK REQUIRE PRESSURE CONTROL OR SOUND ISOLATION.

T
O
U O
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL T H
D A
K
WSHPS WATER SOURCE HEAT PUMP SUPPLY W/H W = DIMENSION IN VIEW (INCHES)
INFORMATION AND REQUIREMENTS. M. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER,
D"Ø ROUND DUCTWORK REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING 11/25/14
PLUMBING ABBREVIATIONS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
D = DUCT DIAMETER INFORMATION AND REQUIREMENTS.
MEDICAL
AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR DRAIN PIPING AS
REQUIRED BY THE SPECIFICATIONS.
TURNING VANES REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. GAS No. Description Date
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION THERMOSTAT/
OUTLETS N. REMOVAL AND REINSTALLATION OF CEILINGS IN AREAS NOT PART OF THE REMODEL AREA OR NOT
AV ACID VENT HW HOT WATER HUMIDISTAT
DUCT CROSS SECTION - SUPPLY CROSS SECTION INDICATES DUCT EXTENDING PERPENDICULAR TO THE PAGE. IN INDICATED BY THE ARCHITECTURAL PLANS TO BE REMOVED IS THE RESPONSIBILITY OF THIS
(ADA)
AW ACID WASTE HWC HOT WATER CIRCULATION PLAN VIEW THIS INDICATES A DUCT RISE OR DROP TO ANOTHER LEVEL. SOLID CONTRACTOR. CONTRACTOR SHALL REPAIR OR REPLACE ALL DAMAGED CEILING COMPONENTS TO
DUCT CROSS SECTION - RETURN MATCH EXISTING. WHERE AN IDENTICAL MATCH IS NO LONGER AVAILABLE, CONTRACTOR SHALL
BF BOTTLE/GLASS FILLER L LAVATORY INTERIOR LINE INDICATES EXTENSION UP. DASHED INTERIOR LINE INDICATES
DUCT CROSS SECTION - EXHAUST EXTENSION DOWN. PROVIDE A SIMILAR REPLACEMENT UPON APPROVAL FROM THE OWNER.
BFP BACK FLOW PREVENTOR LPG PROPANE 60"
BT BATH TUB LWT LEAVING WATER TEMPERATURE REFER TO SPECIFICATIONS FOR TYPE. LOCATE MANUAL BALANCE DAMPERS IN AN 48" O. REGARDLESS OF THE LENGTH SHOWN ON THE DRAWINGS, THE MAXIMUM LENGTH OF 60" SHALL NOT
MANUAL BALANCE DAMPER BE EXCEEDED FOR FLEXIBLE DUCTWORK. FLEX DUCT INSTALLATION SHALL BE AT TERMINAL ENDS
CA COMPRESSED AIR (NON-MEDICAL) MBH BTU (1000'S) ACCESSIBLE LOCATION AND AS CLOSE TO THE MAIN DUCT AS POSSIBLE.
ONLY. CONNECTIONS AT VAV BOX INLETS SHALL BE SOLID HARD DUCT. THE DUCTWORK AT ANY FIRE
CD CONDENSATE DRAIN MS MOP SINK FR.D. REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE AND/OR FIRE SMOKE DAMPER SHALL BE HARD DUCT.
CO CLEANOUT NC NORMALLY CLOSED FR.D. FIRE DAMPER
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
A. COORDINATE ELEVATION OF DEVICES WITH ALL ADJACENT DEVICES INCLUDING THOSE WITH OTHER TRADES. P. LOCATE PIPING AND DUCTWORK IN EXTERIOR BUILDING WALLS ON THE WARM SIDE IF THE BUILDING
CP CONDENSATE PUMP NO NORMALLY OPEN ALL DEVICES WHICH HAVE ADA AND NON-ADA HEIGHTS LISTED SHALL BE MOUNTED TO COMPLY WITH ADA
FS.D. REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE AND VAPOR BARRIER. COORDINATE INSTALLATION OF BUILDING INSULATION TO RUN CONTINUOUS
CS CLINICAL SINK NON-POT NON-POTABLE WATER FIRE/SMOKE DAMPER EXCEPT WHERE NOTED ON THE PLANS AS NON-ADA.
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL. BETWEEN PIPING AND BUILDING WALL.
CW COLD WATER PIV POST INDICATOR VALVE B. GROUP DEVICES IN AN ORGANIZED AND UNIFORM MANNER.
DF DRINKING FOUNTAIN PRV PRESSURE REDUCING VALVE DIFFUSER BLANK OFF SHADED AREA INDICATES QUADRANT OF DIFFUSER TO BE PROVIDED WITH BLANK C. REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL REQUIREMENTS. WHERE THESE REQUIREMENTS Q. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. HOLD
OFF PANEL. DIFFER FROM THE ARCHITECTURAL PLANS, THE ARCHITECTURAL PLANS SHALL TAKE PRECEDENCE. PIPING TIGHT TO BOTTOM OF STRUCTURAL MEMBERS OR RUN THROUGH JOIST WEBS IF POSSIBLE. DO
DGCO DOUBLE GRADE CLEANOUT RD ROOF DRAIN
NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER
DI DEIONIZED WATER RO REVERSE OSMOSIS WATER D. REFER TO ARCHITECTURAL ELEVATIONS FOR ALL PLUMBING FIXTURES.
ARROW INDICATES DIRECTION OF AIRFLOW FROM DIFFUSERS WITH PIPING, DUCTWORK AND/OR ELECTRICAL CONDUITS. DO NOT SUPPORT FROM WOOD TONGUE AND
FLOW ARROW E. ALL DEVICES SHALL BE COORDINATED SO AS NOT TO INTERRUPT A BACK SPLASH OR MATERIAL TRANSITIONS.
DIC DEIONIZED WATER CIRCULATING RPZ REDUCED PRESSURE ZONE (BACK FLOW PREVENTOR) ADJUSTABLE THROWS. GROOVE ROOF DECK. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS.
REFER TO ARCHITECTURAL ELEVATION TO CONFIRM DEVICE IS NOT LOCATED WITHIN TRANSITION AREA.
DIH DEIONIZED HOT WATER S SINK REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE
D-# DIFFUSER TAG F. PROVIDE BACKING IN WALLS WHERE WALL MOUNTED DEVICES OR EQUIPMENT ARE INSTALLED. REFER TO R. PROVIDE CONSTRUCTION FILTERS ON AHUS SERVING THE CONSTRUCTION AREA AS WELL AS ALL
DIHC DEIONIZED HOT WATER CIRCULATING SAN SANITARY SEWER D = TYPE # = TYPE NUMBER ### = AIRFLOW IN CFM TO AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, ARCHITECTURAL SPECIFICATIONS. RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE
###
DIS DISTILLED WATER SCW DOMESTIC SOFT COLD WATER PROVIDE D-1 FOR SUPPLY OR G-1 FOR RETURN/EXHAUST. COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION FILTERS AND PROVIDE NEW
DISC DISTILLED WATER CIRCULATING SHW DOMESTIC SOFT HOT WATER REFER TO SPECIFICATIONS FOR TYPE. REFER TO DETAILS FOR INSTALLATION
MECHANICAL EQUIPMENT MOUNTING HEIGHTS DETAIL FILTERS FOR ALL AHUS.
DR DIALYSIS WATER RETURN SHWC DOMESTIC SOFT HOT WATER CIRCULATING
FLEXIBLE DUCT REQUIREMENTS. MAXIMUM LENGTH SHALL BE 48 INCHES UNLESS NOTED
OTHERWISE ON THE PLANS OR IN THE SPECFICATIONS.
1 NONE S. PROTECT ALL DUCTWORK AND PIPING DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR
DS DIALYSIS WATER SUPPLY SE SEWAGE EJECTOR ADDITIONAL INFORMATION. AT A MINIMUM, DUCTWORK AND PIPING ENDS SHALL BE COVERED AND
DT DRAIN TILE SH SHOWER FLEXIBLE PIPING REFER TO SPECIFICATIONS FOR TYPE. SEALED TO PREVENT THE COLLECTION OF DUST AND DEBRIS. CLEAN ALL INTERIOR SURFACES PRIOR
TO INSTALLATION AND PROTECT ONCE INSTALLED. MEDICAL GAS PIPING SHALL BE PROTECTED IN
EEW EMERGENCY EYE WASH SO STORM OVERFLOW
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION ACCORDANCE WITH NFPA 99 REQUIREMENTS.
ES EMERGENCY SHOWER SP SUMP PUMP VARIABLE AIR VOLUME BOX - NO COIL AND INSTALLATION REQUIREMENTS.
ESEW EMERGENCY SHOWER AND EYE WASH COMBO SS SERVICE SINK T. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS LOCATED PROVIDED AS A PART OF THE WORK
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED.
ET EXPANSION TANK ST STORM SEWER VARIABLE AIR VOLUME BOX - HOT WATER COIL AND INSTALLATION REQUIREMENTS. ON EXISTING EQUIPMENT, COORDINATE WORK WITH OWNER.
EWC
EWT
ELECTRIC WATER COOLER
ENTERING WATER TEMPERATURE
TEMP
UR
TEMPERATURE
URINAL VB-# VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE
TO AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, U. PROVIDE INTERMEDIATE TESTING AND BALANCING AT THE COMPLETION OF EACH PHASE AND AS
SACRED HEART
### CFM REQUIRED TO MAINTAIN PROPER OPERATION OF SYSTEMS SERVING OCCUPIED AREAS OF THE
F FILTER V VENT ### = AIRFLOW IN CFM PROVIDE D-1 FOR SUPPLY OR G-1 FOR RETURN/EXHAUST.
FACILITY.
FCO
FD
FLOOR CLEANOUT
FLOOR DRAIN
VTR
WB
VENT THROUGH ROOF
WALL BOX
VB-#
#.# GPM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE
TO AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED,
V. REFER TO SHEETS M500 THROUGH M502 FOR GENERAL CONSTRUCTION DETAILS.
4TH & 5TH
#.# = WATER FLOW RATE IN GPM PROVIDE D-1 FOR SUPPLY OR G-1 FOR RETURN/EXHAUST.
FS FLOOR SINK WC WATER CLOSET
G
GCO
NATURAL GAS
GRADE CLEANOUT
WCO
WH
WALL CLEANOUT
WATER HEATER
2014 C COPYRIGHT MECHANICAL COVER
HB HOSE BIB WS WATER SOFTENER PLUMBING SYMBOLS PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SHEET
HD HUB DRAIN WPD WATER PRESSURE DROP PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
HP HORSEPOWER YCO YARD CLEANOUT SYMBOL DESCRIPTION ADDITIONAL REMARKS OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
PIPING ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
- SINGLE DASH INDICATES DOMESTIC COLD WATER DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
- DOUBLE DASH INDICATES DOMESTIC HOT WATER BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
FIRE PROTECTION ABBREVIATIONS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
- TRIPLE DASH INDICATES HOT WATER CIRCULATING
- SOLID INDICATES SANITARY ABOVE FLOOR
NUMBER INDICATES NOMINAL DIAMETER IN INCHES,
LETTER(S) INDICATES SYSTEM. COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:13 PM
- CONTINUOUS DASHED INDICATES VENT REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION 10360 Ellison Circle SES PROJECT # 14041
BFP
F
BACK FLOW PREVENTOR
FIRE PROTECTION
FS
PIV
FLOW SWITCH
POST INDICATOR VALVE C.O.
- LONG DASHED LINES INDICATE SANITARY BELOW
FLOOR

CLEANOUT CIRCLE INDICATES UP TO FLOOR OR WALL CLEANOUT.


Omaha, NE 68134
Phone: 402.991.5520 M000
FDC FIRE DEPARTMENT CONNECTION SPR SPRINKLER C.O. LINE INDICATES END OF PIPE CLEANOUT LOCATED ABOVE A CEILING. www.specializedeng.com Scale NONE
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

SHEET NOTES
1 REMOVE EXISTING FAN COIL LOOP PUMP AND APPURTANCES.
REMOVE HWS/R AND CWS/R TO MAIN AND CAP. PUMPS SERVING
2ND FLOOR SHALL REMAIN IN SERVICE. COORDINATE REMOVAL
WITH PHASE OF CONSTRUCTION FOR FAN COILS SERVED.

2 REMOVAL OF AHU-10 INCLUDING ASSOCIATED DUCTWORK,


A1 CONTROLS, PIPING CONNECTIONS, COILS, HUMIDIFIERS AND
REHEAT COILS TO BE COMPLETED BY OWNER.

B
B.0
P-13 P-15 3 REMOVE EXISTING SUPPLY DUCT SERVING NEGATIVE AIR ROOMS
DURING PHASE 2. CAP DUCT AT MAIN.
1
4 REMOVE EXISTING SUPPLY DUCT SERVING ISOLATION ROOMS
DURING PHASE 3. CAP DUCT AT MAIN.
2
5 REMOVE EXISTING SUPPLY DUCT BETWEEN NEW AHU 10 AND
1.7 2.1 3
EXISTING SUPPLY MAIN DURING PHASE 1. PROVIDE TEMPORARY
CONNECTION TO SERVE EXISTING ROOMS UNTIL PHASE 3.

6 REMOVE PORTION OF EXISTING DUCT TO ALLOW FOR

B1.1 1 INSTALLATION OF NEW WORK. REFER TO SHEET M131 FOR NEW


WORK SCOPE.
2

C 2
2

2 P-16

C1 P-14
1

2
1

2 3
6

D
1
P-12

FESSION
PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
10229
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
T H K
D A

11/25/14

E No. Description Date

E1 1

4 5
1
P-18 P-11

F
F1

SACRED HEART
1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
THIRD LEVEL DEMOLITION - HVAC AND PIPING 4TH & 5TH
1 1/8" = 1'-0"
2014 C COPYRIGHT THIRD LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION - HVAC
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
AND PIPING
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:17 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M031
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

SHEET NOTES
1 REMOVE FAN COIL UNIT AND ALL ASSOCIATED PIPING,
CONDENSATE DRAIN, ACCESSORIES, CONTROLS AND
APPURTANENCES. COORDINATE REMOVAL WITH WORK ON 3RD
AND 5TH FLOORS. COORDINATE WORK WITH PHASING TO
PHASE 4 ENSURE CONTINUOUS SYSTEM OPERATION FOR EQUIPMENT

A1
OUTSIDE OF CURRENT PHASE.

1 1 1 1 1 1 1 1 1 2 PATCH PIPING PENETRATIONS THROUGH FLOOR. PATCH


B METHOD SHALL MAINTAIN EXISTING FIRE RESISTANCE RATING
OF FLOOR.
1 1/2"ø 1 1/2"ø RAD CONTROLLER 3
2"ø 2"ø 3

T
1 1/2"ø 3 (ABOVE CEILING) 3 REMOVE DIFFUSER/GRILLE AND ALL ASSOCIATED DUCTWORK,

FS.D.
3 2"ø 3 4
3 ACCESSORIES, AND APPURTANENCES. COORDINATE WORK
3 3 3 3 3 3 3 WITH PHASING TO ENSURE CONTINUOUS SYSTEM OPERATION
4

FS.D.
3 FOR ROOMS OUTSIDE OF CURRENT PHASE.
1
6"x6" 1.7 2.1 3 4 REMOVE EXISTING FINNED TUBE RADIATION. REMOVE ALL
ASSOCIATED PIPING AND CONTROLS.
T 2

26"x8" SA
T T T T T T T T T
B1.1
3 3
6"x4" 10"x4" 12"x8" 12"x10"
1 1
16"x10" 18"x10"

18"x10"
3 3 3 3 3 3 3 3 3
3 3
T

T
C
T

T
3 3
CAP PIPING AT

20"x10"
ACTIVE MAINS 3/4" HWS/R
C1 1
8"x6" 1

26"x8" SA
3 3

3 16"x8" 32"x12" 3

1 1 1/2"ø 1
1 1/2"ø 2 16"x8"
2"ø
2"ø 10"x12"
3

24"x10"
3 1 1/4"ø
10"x12" 1 1/4"ø

T
1 1/4"ø
T

1 1/4"ø
D
PHASE 3 PHASE 2

12"x14"

T
T

3 32"x12" 3 1 1/2"ø
12"x14" SA
2"ø 1 1/2"ø
16"x8" 2"ø
1 10"x8" 2 1

3 FESSION
16"x8" 16"x8" 3 PRO AL
ED
26"x8" SA

. NO.
REG

ER

EN
REGIST

GINEE
10229

22"x10"
3 ERIC G.
3

R
SHERMAN

A
S

T
1
D1

O
U O
1 T H
D A
K

3 3 11/25/14
T

T
E 3/4" HWS/R CAP PIPING AT
ACTIVE MAINS
No. Description Date

T
T

3 3
12"x8" 12"x8" 3 3 3 3 3 3 3 3 3

1 14"x8" 16"x8" 16"x10" 18"x10" 20"x10" 22"x10"


1
3 3
26"x8" SA

E1
T T T T T 2 T T T
T
RAD CONTROLLER
3
(ABOVE CEILING)
3
3 2"ø 1
4 3 3 3 3 3 3 3 3
3 2"ø
3
T

2"ø 1 1/2"ø
T

4 3 3 1 1/2"ø 1 1/2"ø

F
1 1 1 1 1 1 1 1 1
F1
PHASE 1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
FOURTH LEVEL DEMOLITION - HVAC AND PIPING 4TH & 5TH
1 1/8" = 1'-0"
2014 C COPYRIGHT FOURTH LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION - HVAC
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
AND PIPING
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:21 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M041
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

SHEET NOTES
1 REMOVE EXISTING PLUMBING TO FIXTURES ABOVE INCLUDING
ALL APPURTENANCES. REMOVE ASSOCIATED COLD WATER,
HOT WATER, SANITARY, AND VENT PIPING TO ABOVE CEILING
AND EXTEND TO NEW FIXTURES. COMPLETE WORK WITHIN
PHASE 4
A1
ASSOCIATED PHASE. MAINTAIN PROPER SYSTEM OPERATION
TO ALL EXISTING AREAS AND COMPLETED PHASES. REFER TO
NEW WORK SHEETS FOR ADDITIONAL INFORMATION.

B
B.0
3 3 3 3 3
1/2"ø
1 1
2 REMOVE EXISTING PLUMBING FIXTURE INCLUDING ALL
APPURTENANCES. REMOVE ASSOCIATED COLD WATER, HOT
2 WATER, SANITARY, AND VENT PIPING TO NEAREST ACTIVE
1 1/2"ø MAIN AND CAP. COMPLETE WORK WITHIN ASSOCIATED
2 3/4"ø PHASE. MAINTAIN PROPER SYSTEM OPERATION TO ALL
1 EXISTING AREAS AND COMPLETED PHASES.

1.7 2.1 3 EXISTING PIPING IS LOCATED IN VICINITY OF NEW DUCT


MAINS. ADJUST PIPE HANGERS AND LOCATION AS REQUIRED
3/4"ø
3 3/4"ø 3 TO ACCOMMODATE NEW WORK INSTALLATION.
1 1/2"ø
B1.1
1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1
3
1 1
1 1 1 1 1 1 1 1 1

1 1 1 1
C 1 1 1 1

1
C1 1

1 1

1 1 1 1
D
PHASE 3 PHASE 2
1 1 1 1

1 1

FESSION
PRO AL
3 ED . NO.
REG

ER

EN
REGIST

GINEE
3 10229
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
T H K
D A
1 1

11/25/14
1 1 1 1
E 1 1 1 1
No. Description Date

1 1 1 1 1 1 1 1 1
1 1
3
1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1

E1
3/4"ø 3 3/4"ø
3/4"ø
1 1/2"ø
1/2"ø
1 1 1/2"ø
1 1/2"ø
3/4"ø
T

1 1
F 1/2"ø 3 3 3 3 3

F1
PHASE 1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FOURTH LEVEL DEMOLITION - PLUMBING AND MED GAS
1 1/8" = 1'-0"
2014 C COPYRIGHT FOURTH LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION -
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
PLUMBING AND MED
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
GAS
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:24 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M042
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

SHEET NOTES
1 REMOVE FAN COIL UNIT AND ALL ASSOCIATED PIPING,
CONDENSATE DRAIN, ACCESSORIES, CONTROLS AND
APPURTANENCES. COORDINATE REMOVAL WITH WORK ON 3RD
AND 4TH FLOORS. COORDINATE WORK WITH PHASING TO
PHASE 4 ENSURE CONTINUOUS SYSTEM OPERATION FOR EQUIPMENT
A1 OUTSIDE OF CURRENT PHASE.

1 4 1 1 4 1 4 1 1 4 1 1 4 1 2 REMOVE DIFFUSER/GRILLE AND ALL ASSOCIATED DUCTWORK,


B
B.0
ACCESSORIES, AND APPURTANENCES. COORDINATE WORK
WITH PHASING TO ENSURE CONTINUOUS SYSTEM OPERATION
RAD CONTROLLER 2 2 2 FOR ROOMS OUTSIDE OF CURRENT PHASE.
(ABOVE CEILING)

T
FS.D.
2 2
2 3 REMOVE EXISTING FINNED TUBE RADIATION. REMOVE ALL
2 2 2 2 2 2 2 3 ASSOCIATED PIPING AND CONTROLS.
3

FS.D.
2
2
1.7 2.1
4 PATCH PIPING PENETRATIONS THROUGH FLOOR. PATCH
5
2 METHOD SHALL MAINTAIN EXISTING FIRE RESISTANCE RATING OF
1 FLOOR.
T 4
4 T T T T T T T T T 5 REMOVE EXISTING EXHAUST DUCT AND FAN. PREPARE EXISTING

26"x8"
B1.1 1 6 1
CURB FOR NEW FAN.
2 2 6 REMOVE EXISTING GRILLES AND DIFFUSERS IN CORRIDOR,
6 6"x4" 10"x4" 12"x8" 12"x10"
CLEAN AND REINSTALL IN NEW CEILING GRID. REFER TO
16"x10" 18"x10" EXISTING DRAWINGS ISSUED FOR REFERENCE.

18"x10"
2 2 2 2 2 2 2 2 2
2 2
6"x6"

T
T

C 6

T
T

2 6 6 CAP PIPING AT 3/4" HWS/R 2

20"x10"
ACTIVE MAINS
C1
2 8"x6" 2
1 1

26"x8"
4 4

1 32"x12" 1
2 16"x8" 2

16"x8"

2 2

24"x10"
T

10"x12"

T
10"x6"

D
PHASE 3 PHASE 2
6 6 6

12"x14"
T

T
2 2
32"x12"

16"x8"

2 FESSION
1 10"x8"
16"x8" 16"x8" 2
1 PRO AL
ED . NO.
REG

ER

EN
4 4

REGIST
26"x8"

GINEE
10229

22"x10"
6
1 1 ERIC G.
2

R
2 SHERMAN

A
S

T
D1

O
U O
T H K
D A

2 2
6 11/25/14
T

T
6 6
E 3/4" HWS/R CAP PIPING AT
ACTIVE MAINS
No. Description Date

T
T

12"x8"
2 6
6 2
2 2 2 2 2 2 2 2 2
12"x8" 14"x8" 16"x8" 16"x10" 18"x10" 20"x10" 22"x10"

2 2
26"x8"

1 1
E1 4 4
T T T T T T T T T
T
1
2 2
5
2 3
2 2 2 2 2 2 2 2
FS.D.

FS.D.

2
2
RAD CONTROLLER
T

3 2 2 (ABOVE CEILING)

F 1 4 1 1 4 1 4 1 1 4 1 1 4 1

F1 PHASE 1

1b 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL DEMOLITION - HVAC AND PIPING
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION - HVAC
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
AND PIPING
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:28 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M051
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

SHEET NOTES
1 REMOVE EXISTING PLUMBING FIXTURE INCLUDING ALL
APPURTENANCES. REMOVE ASSOCIATED COLD WATER, HOT
WATER, SANITARY, AND VENT PIPING TO NEAREST ACTIVE MAIN
AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE.
MAINTAIN PROPER SYSTEM OPERATION TO ALL EXISTING AREAS
PHASE 4 AND COMPLETED PHASES.
A1 2 DISCONNECT MEDICAL GASES FROM EXISTING HEADWALL UNIT.

B 1/2"ø SALVAGE EXISTING OUTLETS FROM HEADWALL FOR

B.0 6 2
REINSTALLATION. PROVIDE NEW MOUNTING BRACKETS AND
HARDWARE AS REQUIRED. REMOVE PIPING TO NEAREST ACTIVE
1 MAIN AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE.
2 6
3/4"ø 2 MAINTAIN PROPER SYSTEM OPERATION TO ALL EXISTING AREAS
1 AND COMPLETED PHASES. COORDINATE WORK TO MINIMIZE
2 2 2 2 2 2 2 2 1 1/2"ø
6 OUTAGES. COORDINATE WORK TO CONSOLIDATE NUMBER OF
CERTIFICATION VISITS.
1.7 2.1 3/4"ø 3 CAP MEDICAL GAS PIPING AT MAIN. COORDINATE CAPPING
3/4"ø ACTIVITIES WITH PHASE 0 NEW WORK MEDICAL GAS PIPING.
1 1/2"ø 4 1 1/2"ø 1/2"ø WORK SHALL BE COORDINATED SUCH THAT ONE MEDICAL GAS
3/4"ø
B1.1
CERTIFICATION IS REQUIRED.
1 1 1 1 1 1 1 1 4 CAP MEDICAL GAS PIPING AT MAIN. COORDINATE CAPPING
1 ACTIVITIES WITH PHASE 1 NEW WORK MEDICAL GAS PIPING.
WORK SHALL BE COORDINATED SUCH THAT ONE MEDICAL GAS
1 1 1 1 1 1 1 1 1 CERTIFICATION IS REQUIRED.
1 1 1 1 1 1 1 1 1 1 1
5 CAP MEDICAL GAS PIPING AT MAIN. COORDINATE CAPPING
2 1 1 2 ACTIVITIES WITH PHASE 3 NEW WORK MEDICAL GAS PIPING.
1 1 WORK SHALL BE COORDINATED SUCH THAT ONE MEDICAL GAS

C
CERTIFICATION IS REQUIRED.
5 1
1 6 REMOVE EXISTING PLUMBING FIXTURE AND PREPARE EXISTING
1 1
2 PIPING FOR ACCEPTANCE AND INSTALLATION OF NEW FIXTURE.
2

C1
1 1

1 1

2 1 1 2
1 1

D
PHASE 3 PHASE 2

1 1
1 1
2 2

1 1

FESSION
PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
10229
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
T H K
D A
1 1

2 1 1 2 11/25/14
1 1
3
E 1
No. Description Date
1
1 1
2
2
1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1
E1
3 3/4"ø
3/4"ø 3/4"ø
1 1/2"ø

1/2"ø
6 2 2 2 2 2 2 2 2
1 1/2"ø
1 1/2"ø
6 2 3/4"ø
6
2

F 1/2"ø

F1
PHASE 1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL DEMOLITION - PLUMBING AND MED GAS
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION -
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
PLUMBING AND MED
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
GAS
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:32 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M052
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

SHEET NOTES
1 REMOVE EXISTING SPRINKLER AND BRANCH PIPING TO MAIN
AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE.
MAINTAIN PROPER SYSTEM OPPERATION TO ALL EXISTING
AREAS AND COMPLETED PHASES.
PHASE 4
A1 2 CLEAN EXISTING SPRINKLER HEAD AND CENTER IN NEW
CEILING GRID. REFER TO EXISTING DRAWINGS ISSUED FOR

B
B.0
REFERENCE.

T
1 1/4"ø 1
1.7 2.1
1
1 1 1 1 1 1 1 1 1
B1.1 1 1

1 1 1/4"ø 1 1/4"ø 1
1 1 1 1 1 1 1 1 1 2

1 1/4"ø
1 1/4"ø

1 1/4"ø

1 1/4"ø

1 1/4"ø
1 1/4"ø

1 1/4"ø
1 1/4"ø
1 1/4"ø
C
2 2 2 2 2 2 2 2 2

C1 1 1 1/4"ø
2
1 1/4"ø 1

1 1

1 ZONE 13W 6" STANDPIPE 1

1 1 1/4"ø INSPECTOR'S TEST 1 1/4"ø 1


CONNECTIONS 2

2 2

D
PHASE 3 PHASE 2

2
1 1 1/4"ø 2 1 1/4"ø 1

2 FESSION
1 6" STANDPIPE ZONE 14W PRO AL
1 ED . NO.
REG

ER
2

EN
REGIST

GINEE
1 10229
1
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
1 1/4"ø 1 T H
D A
K
1 1 1/4"ø 2

11/25/14
2 2 2 2 2 2 2 2 2

E No. Description Date


1 1/4"ø

1 1/4"ø
1 1/4"ø
1 1/4"ø

1 1/4"ø

1 1/4"ø
1 1/4"ø

1 1/4"ø

1 1/4"ø

1 1 1 1 1 1 1 1 1
1 1 1/4"ø 2 1 1/4"ø 1
2

E1 1 1

1 1 1 1 1 1 1 1 1
1
1

1 1 1/4"ø 1
1"ø 1

1
T

F
F1
PHASE 1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL DEMOLITION - FIRE PROTECTION
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION - FIRE
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
PROTECTION
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:36 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M053
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR
GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS,
AND MOUNTING ELEVATION REQUIREMENTS.

SHEET NOTES
1 PROVIDE TEMPORARY CONNECTION TO EXISTING
SUPPLY DUCT. PROVIDE BALANCING DAMPER FOR
CONTROLLED OPERATION UNTIL PHASE 3 WHEN
DUCTWORK IS REMOVED.

2 REMOVE EXISTING PLENUM WALL AND DOOR FOR


A1 INSTALLATION OF AHU. REINSTALL PLENUM WALL
AND DOOR TO MATCH ORIGINAL INSTALLATION.

B
B.0
7 P-15 3 REMOVE EXISTING LOUVER AND DOOR FOR
EF-17 INSTALLATION OF AHU. REINSTALL LOUVER AND
EF-21 24"x14" DOOR TO MATCH ORIGINAL INSTALLATION.
EF-16
9 EF-15 8
4 106"x26" RELIEF AIR DUCT BELOW. TOP OF DUCT TO
38"x38" EA 22"x22" 9
BE ALIGNED WITH TOP OF RELIEF AIR PLENUM
20"x20" (APPROX. 9' A.F.F.). 106"x24" OUTDOOR AIR DUCT
1.7 2.1 28"x28" EA 16"x16" HX-CW1 EF-07 VB-3-1
ABOVE. BOTTOM OF DUCT TO BE ALLIGNED WITH
BOTTOM OF OUTDOOR AIR PLENUM (APPROX 9'-6"
24"x16" SA 22"x16" SA 22"x14" SA

10"x14" EA
28"x16" SA

32"x20" EA
38"x16" SA 1500 CFM A.F.F.).

30"x14" EA
UP EF-18 COOLING
38"x16" SA ONLY
B1.1 EF-20 EF-14 5 RELOCATE EXISTING PLENUM ACCESS DOOR TO THIS

10"x16" EA
LOCATION.

26"x14" EA
6 EXTEND CONCRETE HOUSEKEEPING PAD TO
20"x10" EA 20"x10" EA 9 ACCOMMODATE NEW AHU.

10"x22" EA
44"x24" RA
7 DUCT UP TO 4TH FLOOR. SAW CUT FLOOR TO ALLOW
FOR INSTALLATION OF NEW DUCT. COORDINATE
LOCATION WITH STRUCTURAL CONCRETE TEES.
30"x12" RA 28"x10" RA
44"x24" SA AHU-03
C 24"x12" RA 24"x12" RA
8 CONNECT TO EXISTING 24x14 SUPPLY DUCT.

20"x18"
16"x20" EA 9 AREA IS CONGESTED WITH EXISTING DUCTWORK AND
DN
30"x26"

P-16 PIPING WHICH MAY NOT ALLOW FOR DIRECT


10"x20" EA 20"x10" RA 20"x10" RA INSTALLATION. PROVIDE ADDITIONAL OFFSETS AND
DN RELOCATE EXISTING DUCTWORK AND PIPING AS
C1
24"x24" EA

44"x24" SA
AHU-11 REQUIRED TO FACILITATE INSTALLATION OF NEW

44"x24" RA
54"x12"

DN WORK.

44"x24" SA
60"x22" RA
DN DN 10"x14" EA 10 RELOCATE EXISTING SANITARY WASTE PIPING,
60"x26" SA BELOW CONTROL TUBING, WIRING, CONDUITES, AND

12"x16"

12"x26"
BELOW DN DN 30"x14" EA HANGERS TO ACCOMMODATE INSTALLATION OF DUCT
9
60"x12" RA THROUGHT WALL.

60"x24"
44"x24" RA DN
20"x10" 44"x20" SA
44"x24" SA DN 32"x20" EA
9 24"x12" DN 30"x24" SA UP
9 20"x18"
30"x26"

44"x20" RA
48"x24" 9 DN 10"x14" EA
24"x30" RA UP 30"x14" EA
26"x14" EA
DN DN 12"x26" RA
10"x20" RA UP
20"x10" 22"x10" EA
30"x24" SA
D 88"x24" SA 9
24"x12" 12"x24" RA UP
30"x32" SA UP
DN
16"x10" EA
26"x22" RA
9
AHU-09
10 DN
44"x24" SA
48"x24"

44"x24" RA BELOW
DN 32"x20" EA
9 30"x26" 9

30"x32" SA
16"x12" RA

20"x18"
44"x24" SA BELOW

44"x20" SA ABOVE
26"x22" RA UP
60"x22" RA

44"x20" RA ABOVE
32"x20" EA UP FESSION
6 VFD-SF-10A 16"x12" RA UP PRO AL
ED . NO.
VFD-SF-10B REG

ER

EN
REGIST

GINEE
10229
AHU-10
26"x22" RA ERIC G.

R
44"x24" SA UP SHERMAN

A
30"x32" SA 36"x22" SA DN

T
D1

O
U O
9 T H
D A
K
24"x30" RA
48"x18"

44"x20" SA
11/25/14
AHU-06

E 30"x32" SA 30"x32" SA
No. Description Date
AHU-05
24"x30" RA 24"x30" RA 9
54"x14" RA

110"x20"
AHU-02
AHU-07
60"x22" RA

44"x20" RA
9 AHU-08
112"x30"

AHU-04
E1 VFD-RF-10A
48"x24"

110"x20"
48"x18"

20"x18"
VFD-RF-10B
4
18"x18"

70"x16"

72"x22" RA 9
5 P-18 72"x12" RA DN
P-17 30"x18"
1 2
9 48"x18" 9 9

F 3
9 7

F1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
THIRD LEVEL- HVAC 4TH & 5TH
1 1/8" = 1'-0"
2014 C COPYRIGHT THIRD LEVEL - HVAC
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:39 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M131
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR

6"ø GCWR
GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS,
AND MOUNTING ELEVATION REQUIREMENTS.

6"ø GCWS
SHEET NOTES
1 ROUTE PIPING UP TO NEW VAV TERMINAL UNITS ON
6"ø GCWR 5 FLOORS 4 AND 5 DURING PHASE 1.
6"ø GCWS
2 ROUTE PIPING UP TO NEW VAV TERMINAL UNITS ON
FLOORS 4 AND 5 DURING PHASE 3.
A1
4
3 CORE DRILL PENETRATIONS IN STRUCTURAL SLAB.
COORDINATE LOCATIONS WITH EXISTING
B
B.0
6 6
6"ø GCWR
6 STRUCTURAL TEES.
6"ø GCWS
4 PROVIDE 3-WAY DIVERTER VALVE AT PIPE JUNCTION.
2 3 2 REFER TO CHILLED WATER CONTROL DETAIL FOR
6 6
M502 4 ADDITIONAL REQUIREMENTS.

PROVIDE DRAIN PAN WITH MOISTURE 6"ø CWS 5 PROVIDE OFFSETS REQUIRED TO MAKE

8"ø CWS
CONNECTIONS. HALLWAY OUTSIDE MECHANICAL
1.7 2.1
SENSOR TIED TO BAS FOR NEW PIPING.

6"ø CWS
HX-CW1 ROOM IS CONGESTED AND WILL REQUIRE ADDITIONAL

6"ø CWS
6"ø CWR
OFFSETS TO ACCOMMODATE INSTALLATION.

6"ø CWS
2"ø CWS
2"ø CWR

6"ø CWR
6 RELOCATE EXISTING HANGERS, SUPPORTS AND
B1.1 2 1/2"ø CWR
2 1/2"ø CWS
CONDUIT TO ALLOW FOR INSTALLATION OF NEW
CHILLED WATER PIPING.
3/4"ø HWR 1"ø HWR 1"ø HWR 2"ø HWR
1"ø HWS 3/4"ø 3/4"ø HWS 4"ø HWS

1"ø HWR
AHU-03 2 1/2"ø CWS
C 8"ø CR
8"ø CWS 8"ø CWS 1 1/4"ø HWR
2 1/2"ø CWR
8"ø CS
2 1/2"ø CWR 1 1/4"ø HWS
1"ø HWR 4"ø HWR 1"ø HWS 4"ø HWR 4"ø HWR
1"ø HWS

C1 AHU-11 4"ø HWR 6"ø HWR

4"ø HWS
3"ø MPC DN 3"ø MPC DN
2"ø CWS DN

4"ø HWS
2"ø CWR DN 8"ø CR
8"ø CS 2"ø HWR
1 1/2"ø CWR 1"ø HWS DN
1 1/2"ø CWS 4"ø HWR DN
6"ø HPS DN 6"ø MPS
6"ø MPS 2 1/2"ø HWR
4"ø HWS
1 1/2"ø HWS
1"ø HWS
2 1/2"ø HWS 2 1/2"ø HWR

1 1/2"ø MPC 6"ø MPS


3"ø CWR

4"ø HWS
2 1/2"ø HWS
1 1/4"ø HPC DN
8"ø CWS

4"ø HWR
4"ø HWR

DN
6"ø HPS
8"ø CR DN
8"ø CS DN 1 1/2"ø CWS
2"ø MPS
1 1/2"ø MPC DN 1 1/2"ø CWR

D 2 1/2"ø HWS
2 1/2"ø HWR
AHU-09
3"ø MPS 1 1/2"ø CWS
1 1/2"ø CWR
1 1/2"ø CWS
1 1/2"ø CWR
4"ø HWR
4"ø HWR
8"ø CWS

4
M501 STEAM RELIEF VENT UP 6"ø HPS
2"ø HWS

6"ø
1 1/2"ø HWS

FESSION
6"ø STEAM RELIEF VENT UP 3"ø CWS PRO AL
ED
3"ø CWR

2"ø HWS

3"ø CWR . NO.


REG

ER

EN
2"ø HWR
1

REGIST

GINEE
1"ø HPC 10229
M502 ERIC G.

R
2"ø HWS 2
EXISTING PRV SHERMAN

A
2"ø HWR

S
M501
D1

T
O
U O
AHU-10 5 T H
D A
K
4"ø CWR 2"ø LPS 1 1/2"ø HWS
4"ø CWS M501 1 1/2"ø HWR
2"ø LPS 2
1"ø HPC 1 1/4"ø HWR
6"ø HPS 1 1/4"ø HWS 11/25/14
AHU-06 2 1/2"ø HWR 1
E
2 1/2"ø HWS
3"ø CWR
3"ø CWS

2"ø HWS 2 1/2"ø HWS 3"ø HWS No. Description Date


4"ø HWR 4"ø HWR 4"ø HWR 3"ø HWR
2"ø HWS 2 1/2"ø HWS 3"ø HWS
3"ø HWS 3"ø HWS
4"ø HWR 3"ø HWR 3"ø HWR 3"ø HWR 2 1/2"ø HWR
6"ø CWR 1 1/4"ø LPS AHU-05 6"ø CWR 6"ø CWR
6"ø CWS 6"ø CWS 1 1/4"ø HWS 1 1/4"ø HWR 4"ø CWS
1 1/4"ø HWS

1 1/4"ø HWS 2"ø CWR


1 1/4"ø HWR

1 1/4"ø HWR
AHU-02 2"ø CWS
2"ø HWR

AHU-07
3"ø CWS

2 1/2"ø HWS
6 3"ø CWR
AHU-08
M501 AHU-04
2"ø HWS

E1
2

2 1/2"ø HWR
M501

1"ø CWR
1"ø CWS 2 1/2"ø
3"ø CWS 2 1/2"øCWR
CWS
1
3
2"ø HDTS
2"ø HDTR

F
F1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 SACRED HEART
THIRD LEVEL- PIPING 4TH & 5TH
1 1/8" = 1'-0"
2014 C COPYRIGHT THIRD LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PIPING
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:43 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M132
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

B. PIPING TO INDIVIDUAL VAV BOXES SHALL BE 3/4" UNLESS NOTED


OTHERWISE.
ELEVATOR LINK
4900 SHEET NOTES
1 SEAL EXISTING AND NEW PENETRATIONS WITHIN ROOM AIR
TIGHT.
PHASE 4
7
D-3 D-3 D-3 D-3 D-3 D-3 D-3 D-3 D-3 2 2" HWS/HWR UP TO FIFTH FLOOR. 2-1/2" HWS/HWR DOWN TO
100 CFM 100 CFM M501 THRID FLOOR.
100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM
A1
4 4
6 3 26" x 18" SA DUCT UP TO FIFTH FLOOR. 26" x 30" SA DUCT DOWN
M500 M500
M500 TO THIRD FLOOR.
B
B.0 3
18"x16" 26"x12" SA 16"x12" SA
10"x10" SA
G-2 G-2
RAD-1 G-2 200 CFM 200 CFM
16"x12" D-1 D-1 D-1 D-1
D-1 D-1 D-1 D-1 D-1 100 CFM

FS.D.
FS.D.
FS.D.
200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 1
2 RESTROOM 1
12"x8" SA 16"x8" EA
12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA 418
G-2
12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA
OFFICE VB-4-27 G-1 100
200 CFM 1 1/2"ø 1 1/2"ø 1 1/2"ø 1"ø 1"ø 3/4"ø 16"x8" EA D-3
D-3 1 1/2"ø 1 1/2"ø 1 1/2"ø 1"ø 1"ø 3/4"ø
1.7 2.1
4621 1/2"ø 200 CFM VB-4-21
100 CFM 1 1/2"ø VB-4-26 VB-4-25 VB-4-24 VB-4-23 VB-4-22 VB-4-20 VB-4-19 10"x10" NEGATIVE AIR 100 CFM
300PATIENT
CFM RM
16"x12"

D-1 300PATIENT
CFM RM PATIENT
300 RM
CFM PATIENT
300 CFM RM PATIENT RM
300 CFM PATIENT RM
300 CFM PATIENT RM
300 CFM PATIENT
300 CFM RM PATIENT RM 420
100 CFM 400 402 404 406 408 410 412 414 416 D-1
250 CFM
VB-4-18
B1.1
16"x8"

26"x8"
22"x8" 26"x8" RA 300 CFM
12"x8" RA G-1
12"x8"

D-3 G-1 12"x8" 125 CFM


100 CFM G-1 G-1 G-1 G-1 G-1 12"x8" D-3
125 CFM 6"x4" 10"x4" 12"x8" 12"x10" G-1 G-1 PATIENT RM
200 CFM 200 CFM 200 CFM 200 CFM 200 CFM D-1 100 CFM
G-1 200 CFM 200 CFM 422
16"x10" 18"x10" 100 CFM
1 1/2"ø

200 CFM

OFFICE 200 CFM


VB-4-28

G-1

3/4"ø
200 CFM
VB-4-16
18"x10"
26"x8" RA
460 G-2 200 CFM G-2
100 CFM G-2 G-2 100 CFM
1 1/2"ø

3/4"ø
G-2 G-2 G-2 G-2
D-1 100 CFM 100 CFM 100 CFM 100 CFM G-2 G-2 G-2
MECH 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM
100 CFM
C
459
RESTROOM
D-1 421
100 CFM
200 CFM
VB-4-29

G-2 G-2
100 CFM 100 CFM 12"x8" D-1
3/4" HWS/R
C1
100 CFM
16"x8"

20"x10"
D-3

1"ø
12"x8"

8"x6" G-1

200 CFM
VB-4-15
100 CFM

1"ø
125 CFM G-1 D-3

26"x8" RA
ELEC 125 CFM
534
100 CFM
G-1
1"ø

12"x8" 125 CFM


1"ø

HSKG CLEAN UTILITY DIRTY UTILITY 10"x10"


536 OFFICE 550 549
D-3 32"x12" PATIENT RM
16"x8" 537

200 CFM
TOILET

VB-4-14
100 CFM 424 D-3
TOILET 548 G-1 100 CFM
16"x12"

12"x8" 16"x8" RA 535 125 CFM


26"x8" RA
10"x12"
200 CFM

G-2

1"ø
UP
VB-4-30

G-2 12"x8"
100 CFM 12"x26" RA 30"x16" SA UP 100 CFM
D-1 18"x30" RA UP

1"ø
24"x18" RA DN D-1
100 CFM RESTROOM 10"x12" RA 24"x30" RA DN 100 CFM
30"x24" SA DN
10"x12" RA UP 30"x16" SA
D
PHASE 3 455 STORAGE PHASE 2
DIET
10"x20" RA DN

24"x10"
16"x8"
10"x6" EA 539
12"x14" RA544UP 26"x14" RA
CONFERENCE LOCKER ROOM
12"x14" RA 12"x24" RA DN 546 547
14"x26" RA
200 CFM

12"x8"
VB-4-31

G-2 30"x20" SA UP 32"x12" EA G-2 D-1


12"x14" RA 30"x32" SA DN UP 100 CFM
D-1 100 CFM 26"x22" RA 100 CFM
WAITING ROOM 16"x8" RA

200 CFM
VB-4-13
D-3 100 CFM DN
538
100 CFM 32"x12" EA G-1 D-3
12"x8"

1"ø
G-1 UP 8"x16" RA 125 CFM 100 CFM

1"ø
125 CFM 32"x20" EA UP FESSION
16"x12" RA 16"x8" PRO AL
EQUIPMENT CLEAN UTILITY
DN ED . NO.
REG
26"x8" RA

ER
DN

EN
540 541

REGIST
SOILED

GINEE
NUTRITION OMNI CELL
6"ø 10229
542 543 6"ø 545
D-3 G-1 G-1 D-3 ERIC G.

22"x10"
1"ø

12"x8"

R
100 CFM 125 CFM STEAM RELIEF 125 CFM D-1 100 CFM SHERMAN

200 CFM
VB-4-12
1"ø

A
VENTS TO ROOF

S
100 CFM

T
D1

O
10"x8" EA U O
D-1 T H
D A
K
G-2
3/4"ø

100 CFM
200 CFM
VB-4-32

100 CFM 5 G-2


10"x10"

TYP 100 CFM


M500
3/4"ø

12"x8" 11/25/14

E G-2
3/4" HWS/R
G-2 G-2 G-2 G-2 G-2 G-2 12"x8"
No. Description Date
100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM
26"x8"

2
200 CFM
VB-4-33

16"x12"
12"x8" EA G-2 TYP G-2 12"x8"
G-1 G-1 G-2
G-2 100 CFM M500 100 CFM
D-1 200 CFM 200 CFM G-1 100 CFM
100 CFM
100 CFM 14"x8" 200 CFM 16"x8" 16"x10" 18"x10" 20"x10" 22"x10"
D-3

200 CFM
VB-4-11
100 CFM 12"x8" G-1 G-1 D-1 D-3
12"x8"

G-1 G-1 G-1 G-1


G-1 200 CFM 200 CFM 100 CFM 100 CFM
200 CFM 200 CFM 12"x8" 200 CFM 200 CFM
26"x8"

125 CFMANTERIOR RM 12"x8"


E1 VB-4-34
550 CFM
450
16"x8" RA 26"x8" RA 22"x8"
G-1
125 CFM
1
D-1

200 CFM
VB-4-10
10"x10" VB-4-2 VB-4-3 VB-4-4 VB-4-5 VB-4-6 VB-4-7 VB-4-8 VB-4-9 D-3
300 CFM VB-4-1 RM
PATIENT PATIENT RM PATIENT RM PATIENT300
RM CFM PATIENT300
RMCFM G-1 D-1 100 CFM
300 CFM 300 CFM 300PATIENT
CFM RM PATIENT RM
300 CFM 300PATIENT
CFM RM PATIENT
300 RM
CFM
300 CFM
448 446 3/4"ø 444 1"ø 442 440 1 1/2"ø 438 436 434 432 125 CFM 100 CFM
D-3 16"x8" 1 3/4"ø 1"ø 1 1/2"ø 2
100 CFM 1
RESTROOM D-1 D-1 12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA 12"x8" SA D-1 1 1/2"ø
16"x8" 1 1/2"ø
451 150 CFM 200 CFM 200 CFM 12"x8"
FS.D.

D-1 D-1 D-1 D-1 D-1 D-1 D-1 RESTROOM


G-2 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM STORAGE 429
G-2 G-2 200 CFM
200 CFM 200 CFM 100 CFM 431
16"x12"
16"x12" SA 26"x12"
F

FS.D.

FS.D.
3
G-2 10"x10" SA RAD-2 6
10"x8"
200 CFM M500 4
F1 M500
4
D-3
3
M500
TYP M500
D-3 D-3 D-3 D-3 D-3 D-3 D-3 D-3 7
100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM
PHASE 1 M501 REBALANCE TO 75 CFM

1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
FOURTH LEVEL - HVAC AND PIPING 4TH & 5TH
1 1/8" = 1'-0"
2014 C COPYRIGHT FOURTH LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE HVAC AND PIPING
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:37:54 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M141
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

B. PIPING TO INDIVIDUAL VAV BOXES SHALL BE 3/4" UNLESS NOTED


OTHERWISE.

SHEET NOTES
1 SEAL EXISTING AND NEW PENETRATIONS WITHIN ROOM AIR
PHASE 4 TIGHT.

D-3 D-3 2 REBALANCE EXISTING EXHAUST GRILLE TO 75 CFM.


4 100 CFM 100 CFM D-3 D-3 D-3 D-3 D-3 D-3 D-3
100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM
A1 M500 4 3 2" HWS/HWR DOWN TO 4TH FLOOR.
M500
4 26" x 18" SA DUCT DOWN TO 4TH FLOOR.
B
B.0
FS.D.
4 G-2 G-2
18"x16" 26"x12" 1
D-1 D-1 D-1 D-1 D-1 D-1 D-1 D-1 G-2 200 CFM 200 CFM
16"x12" 100 CFM
200 CFM D-1 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM

FS.D.
FS.D.
3 200 CFM G-2 1
100 CFM 16"x8"
VB-5-27
200 CFM G-1 1 1/2"ø 1 1/2"ø 1 1/2"ø 1"ø 1"ø 3/4"ø D-3
D-3 1 1/2"ø 1 1/2"ø 1 1/2"ø 1"ø 1"ø 3/4"ø
100 CFM
1 1/2"ø
1 1/2"ø
200 CFM
1.7 2.1 VB-5-26 VB-5-25 VB-5-24 VB-5-23 VB-5-22 VB-5-21 VB-5-20 VB-5-19 VB-5-18 10"x10" 100 CFM
16"x12"

D-1 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM VB-5-17
100 CFM 350 CFM D-1 14"x10"
12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8"
250 CFM

B1.1
16"x8"

26"x8"
22"x8" 26"x8"
12"x8" G-1
12"x8"

D-3 G-1 G-1 G-1 12"x8" G-1 G-1 G-1 G-1 125 CFM
100 CFM G-1 G-1 12"x8" D-3
125 CFM 200 CFM 200 CFM 10"x4" 200 CFM 200 CFM 200 CFM 12"x10" 200 CFM 200 CFM 200 CFM
G-1 100 CFM
12"x8" 200 CFM 16"x10" 18"x10"
1 1/2"ø

G-2
200 CFM
VB-5-28

3/4"ø
G-2 6"x4" G-2 G-2 G-2 G-2 G-2
G-2 100 CFM G-2 G-2 G-2

200 CFM
VB-5-16
100 CFM 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM D-1
100 CFM 100 CFM 100 CFM 100 CFM

3/4"ø
1 1/2"ø

100 CFM
D-1
100 CFM
C D-1
100 CFM
200 CFM
VB-5-29

G-2 3/4" HWS/R CAPPED G-2


100 CFM 12"x8"

20"x10"
100 CFM
C1 D-3 16"x8"

1"ø
12"x8"

100 CFM G-1 D-1

200 CFM
VB-5-15

1"ø
125 CFM G-1 100 CFM D-3
125 CFM 100 CFM

26"x8" RA
8"x6" G-1
1"ø

12"x8" 125 CFM


1"ø

D-3 32"x12"
16"x8"
100 CFM D-1 D-3
G-1 100 CFM
16"x12"

100 CFM
125 CFM

10"x10"
12"x8" 16"x8"

200 CFM
VB-5-14
10"x12"
200 CFM

G-2

1"ø
G-2
VB-5-30

100 CFM 100 CFM


D-1

1"ø
24"x10"
100 CFM 10"x12" 12"x8"

D
PHASE 3 PHASE 2
10"x6"

16"x8"
12"x14"
200 CFM
VB-5-31

G-2 32"x12" G-2 12"x8" D-1


100 CFM 100 CFM 100 CFM
D-1
100 CFM 16"x8"

200 CFM
VB-5-13
D-3
100 CFM G-1 D-3
12"x8"

1"ø
G-1 125 CFM 100 CFM

1"ø
125 CFM FESSION
6"ø 16"x8" PRO AL
ED
26"x8" RA

6"ø REG
. NO.

ER

EN
REGIST
STEAM RELIEF

GINEE
10"x8" 10229
D-3 G-1 VENTS TO ROOF

200 CFM
ERIC G.

VB-5-12
G-1 D-3
1"ø

12"x8"

R
100 CFM 125 CFM 125 CFM D-1 100 CFM SHERMAN
1"ø

A
S
5 100 CFM

T
D1

O
U O
T H K

22"x10"
D-1 TYP D A
3/4"ø

100 CFM M500


200 CFM

G-2
VB-5-32

G-2
10"x10"

100 CFM 100 CFM


3/4"ø

12"x8" 11/25/14
2
TYP
E 3/4" HWS/R CAPPED M500
12"x8"
No. Description Date
200 CFM
VB-5-33

16"x12"
12"x8" G-2 G-2 G-2 G-2 G-2 G-2 12"x8"
G-2 G-2 G-2 G-2
G-2 100 CFM 100 CFM 100 CFM 100 CFM 100 CFM
D-1 100 CFM 75 CFM 100 CFM 100 CFM 100 CFM
100 CFM
100 CFM

200 CFM
D-3 12"x8" 14"x8" 16"x8" 16"x10" 18"x10" 20"x10" 22"x10"

VB-5-11
100 CFM D-1 D-3
12"x8"

G-1 G-1 G-1 G-1 G-1 G-1 G-1 100 CFM


G-1 G-1 G-1 100 CFM
200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 12"x8" 200 CFM 200 CFM
26"x8"

125 CFM 200 CFM 200 CFM 12"x8"


E1 VB-5-34
550 CFM 16"x8" 26"x8" 22"x8"
G-1
125 CFM
D-1
300 CFM 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8" 12"x8"
D-3

200 CFM
10"x10" VB-5-3

VB-5-10
VB-5-1 VB-5-2 VB-5-4 VB-5-5 VB-5-6 VB-5-7 VB-5-8 VB-5-9 G-1 D-1 100 CFM
14"x10" 1 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM
3/4"ø 1"ø 1 1/2"ø 3 125 CFM 100 CFM
D-3 3/4"ø 1"ø 1 1/2"ø
100 CFM D-1
D-1 D-1 D-1 D-1
18"x10" 200 CFM
150 CFM D-1 200 CFM 200 CFM 200 CFM 12"x8"
FS.D.

1 200 CFM D-1 D-1 D-1 2


G-2 200 CFM 200 CFM D-1
200 CFM
G-2 G-2 200 CFM 200 CFM
1 16"x12"
200 CFM 200 CFM G-2 10"x10" 16"x12" 26"x12"
F

FS.D.

FS.D.
4
100 CFM RAD-3 6
4
NOTE BACKGROUND IS
F1 M500
M500
SHOW CORRECTLY ON
D-3 D-3 D-3 D-3 D-3 D-3 D-3 3
D-3 D-3 7
4 ARCHITECTURALS. FEILD
TYP
100 CFM 100 CFM 100 CFM 100 CFM 100 CFM PHASE 1 100 CFM 100 CFM M500 100 CFM 100 CFM M501
M500 VERIFY.

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL - HVAC AND PIPING
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL - HVAC
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE AND PIPING
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:02 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M151
www.specializedeng.com Scale 1/8" = 1'-0"
AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A. REFER TO MECHANICAL COVER SHEET M000 AND ELECTRICAL
COVER SHEET E000 FOR GENERAL REQUIREMENTS, SYMBOLS,
2.4 3.4 3.6 ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.

A1
B
B.0

EF-1

1.7 2.1
8
M501

B1.1

C1

FESSION
PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
10229
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
T H K
D A

11/25/14

E No. Description Date

E1
EF-2
8
M501

F
F1

1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
MECHANICAL ROOF PLAN
1 1/8" = 1'-0"
4TH & 5TH
2014 C COPYRIGHT MECHANICAL ROOF
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PLAN
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:04 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M161
www.specializedeng.com Scale 1/8" = 1'-0"
AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
2.4 3.4 3.6 REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

ELEVATOR LINK
4900
SHEET NOTES
1 CONNECT TO EXISTING PIPING SERVING REMOVED FIXTURE.

2 OFFSET EXISTING WASTE AND VENT STACK AND DOMESTIC


WATER RISERS SERVING 5TH FLOOR TO EXISTING CHASE AS
PHASE 4 REQUIRED (TYPICAL PATIENT RESTROOM GROUPS). COORDINATE

A1
ROUTING OF PIPING WITH NEW AND EXISTING DUCTWORK.

4"ø V
4"ø SAN
B
B.0
RESTROOM
418
OFFICE 2"ø SAN
462
1.7 PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM
1"ø CW NEGATIVE AIR
420
2400 402 2 2 404 406
2 408 2 2 410 412 2 2 414 2 416
3/4"ø 1/2"ø

B1.1
1 1/2"ø
T T

PATIENT RM
7&8 7&8 7&8 7&8 7&8 7&8 7&8 7&8 7&8
422
OFFICE M500 M500 M500 M500 M500 M500 M500 M500 M500 2"ø V
460 2 2

MECH

C
459 2 2 2 2 2 2
2 2
RESTROOM
421

2 2
C1
ELEC
T 534 T
HSKG CLEAN UTILITY DIRTY UTILITY
T 536 OFFICE 550 549 T
3/4"ø O PATIENT RM
6"ø ST 537 TOILET
3/4"ø A 424
UP/DN TOILET 548
3/4"ø O 1 1/2"ø VAC
535 3/4"ø A
1 1/2"ø VAC
2 2
5"ø ST DN
UP/DN 5"ø ST UP/DN
RESTROOM 1 1/2"ø VAC

D
PHASE 3 455
2 STORAGE 3/4"ø A 2 PHASE 2
DIET
539 3/4"ø O
544
DN CONFERENCE LOCKER ROOM
546 547

2 5"ø ST 2
WAITING ROOM
538
1 1/2"ø VAC
3/4"ø A
3/4"ø O FESSION
T PRO AL
T ED . NO.
EQUIPMENT CLEAN UTILITY REG

ER

EN
REGIST
540 541 SOILED

GINEE
NUTRITION OMNI CELL
T 10229
542 543 545 T
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
T H K
D A

2 2
11/25/14

E 2
2 2 2 2 2 2
2 No. Description Date

3/4"ø
2 3/4"ø 2
7&8 1 1/2"ø 7&8 7&8 7&8 7&8 7&8 7&8 7&8 7&8
M500 M500 M500 M500 M500 M500 M500 M500 M500

ANTERIOR RM
E1 T
450
T

T 2 2 2 2 2 2 2 2 2 T

PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM


1"ø HW 2 448 446 444 442 440 438 436 434 432

1"ø CW RESTROOM
2"ø HW
1 1/2"ø CW 451 2"ø V RESTROOM
3/4"ø HW 2"ø CW
STORAGE 429
2
4"ø4"ø
SAN 2"ø V
431
2"ø
2"øV 4"ø SAN
F
F1
PHASE 1

1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FOURTH LEVEL - PLUMBING AND MED GAS
1 1/8" = 1'-0"
2014 C COPYRIGHT FOURTH LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PLUMBING AND MED
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
GAS
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:12 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M241
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.
ELEVATOR
LINK
5900

SHEET NOTES
1 REINSTALL EXISTING MEDICAL GAS OUTLETS IN ARCHITECTURAL
HEADWALL. REFER TO ARCHITECTURAL HEADWALL ELEVATIONS
FOR ARRANGEMENT AND DIMENSIONAL INFORMATION. PROVIDE
ONE VACUUM SLIDE FOR EACH VACUUM OUTLET LOCATION.
PROVIDE ADDITIONAL OUTLETS AS REQUIRED TO MEET
PHASE 4
A1 QUANTITY SHOWN.

2 VALVES AND PIPING TO EXISTING MAINS SHALL BE DONE PRIOR


1
B

VS

VS

VS

VS
VS

VS

VS

VS

VS
1 1 1 1 1 1 TO BEGINNING DEMOLITION OF EXISTING MEDICAL GAS.
1 1
B.0

V
V

V
WC-2 VS V A O O V VS
COORDINATE CONNECTION TO EXISTING MAINS WITH PHASE 2
5

O
DEMOLITION WORK. WORK SHALL BE COORDINATING SUCH

O
5 THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
SH-1 1
1/2"ø O

O
O

O
L-1 3 VALVES AND PIPING TO EXISTING MAINS SHALL BE DONE PRIOR
5 1"ø VAC TO BEGINNING DEMOLITION OF EXISTING MEDICAL GAS.

A
OFFICE

A
1/2"ø A COORDINATE CONNECTION TO EXISTING MAINS WITH PHASE 1
5902
1.7 2.1

V
V

V
DEMOLITION WORK. WORK SHALL BE COORDINATING SUCH

VS

VS

VS

VS
VS

VS

VS

VS

VS
THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
SH-1 L-1 L-1 SH-1 SH-1 L-1 L-1 SH-1 L-1 SH-1 SH-1 L-1 L-1 SH-1 SH-1 L-1 L-1 SH-1
4 ROUTE NEW VENT STACK TO EXISTING VENT THROUGH ROOF.
B1.1 3/4"ø O
COORDINATE ROUTE WITH OTHER UTILITIES.

FD-2 FD-1 FD-1 FD-1 FD-1 FD-1 FD-1 FD-1 FD-2 1 1/4"ø VAC 5 CONNECT TO EXISTING PIPING SERVING REMOVED FIXTURE.
L-2 L-2 1/2"ø A
7&8 7&8 7&8 7&8 7&8 7&8 7&8 7&8 7&8
L-1 L-1 2"ø V
CORRIDOR M500 M500 WC-1 M500 M500 WC-1 M500 WC-1 M500 M500 WC-1 M500 M500
5901 L-1 L-1 WC-1 L-1 L-1 L-1 WC-1 L-1 L-1 WC-1 L-1 L-1 WC-1 2"ø V 1 1/2"ø SAN
SH-1 WC-1 SH-1
1 4"ø SAN 1
FD-2 FD-2 2"ø SAN
VS V O O A V VS WC-1 4 WC-1 VS V A O O V VS

C
4 4 4 4 4
4
VS V O O A V VS VS V A O O V VS
FD-2 WC-1 WC-1 FD-2
SH-1 2 2 2"ø SAN
1 2"ø V SH-1 1
4"ø SAN 1 1/2"ø SAN
4
C1 L-1 L-1 2"ø V
L-2 L-2

3/4"ø O
6"ø ST 3/4"ø A
UP/DN 1 1/2"ø VAC
L-2 L-2
5"ø ST 3/4"ø O
L-1 UP/DN 3/4"ø A L-1 2"ø V
1 1/2"ø VAC
DN 2"ø V 1 1/2"ø SAN
SH-1 SH-1
1 5"ø ST UP/DN 1
FD-2 1 1/2"ø VAC 4"ø SAN FD-2 2"ø SAN
VS V O O A V VS WC-1 3/4"ø A WC-1 VS V A O O V VS

D
PHASE 3 PHASE 2
4 3/4"ø O 4
VS V O O A V VS
WC-1 3/4"ø O DN WC-1 VS V A O O V VS
FD-2 3/4"ø A 4"ø SAN FD-2
SH-1 2"ø SAN
1 1 1/2"ø VAC 1
SH-1
5"ø ST
1 1/2"ø SAN
L-1 L-1 L-1
2"ø V
L-2 L-2
FESSION
PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
1/2"ø A 10229
1 1/2"ø VAC ERIC G.

R
1/2"ø O
L-2 L-2 SHERMAN

A
S

T
D1

O
U O
L-1 T H K
L-1 D A

SH-1
1 4 1 11/25/14
SH-1
FD-2 FD-2
VS V O O A V VS WC-1 WC-1 VS V A O O V VS

E VS V O O A V VS
WC-1 4
3 3 4 4 4 4 4 4
WC-1 VS V A
O

O O V VS
No. Description Date
FD-2 FD-2
SH-1 SH-1
1 WC-1 WC-1 1

T
L-1 L-1 L-1 L-1 L-1 L-1 L-1 L-1 L-1
WC-1
7&8 7&8 WC-1 WC-1 7&8 7&8 7&8 WC-1 WC-1 7&8 7&8 WC-1 WC-1 7&8 7&8
2"ø V L-1 L-1
M500 M500 M500 M500 M500 M500 M500 M500 M500
3/4"ø O L-2 FD-2 FD-1 FD-1 FD-1 FD-1 FD-1 FD-1 FD-1 FD-2 L-2
1 1/2"ø VAC
E1 1/2"ø A L-1 L-1
SH-1
L-1 L-1 L-1 L-1 L-1 L-1
SH-1 SH-1 SH-1 SH-1 SH-1 SH-1 SH-1 SH-1 L-1 SH-1
1"ø VAC
VS

VS

VS

VS

VS
VS

VS

VS

VS
1/2"ø O
5
L-1
V

V
V

V
1/2"ø O
1"ø VAC
A

A
A

A
1/2"ø A 1/2"ø A
O

O
O

O
1 SH-1 1 1/2"ø CW
5 3/4"ø HW
4"ø SAN
O

O
O

O
VS V O O A V VS 5 WC-2
2"ø V
F 1
V

V
V

V
1 1 1 1 1 1
1 1
VS

VS

VS

VS

VS
VS

VS

VS

VS
F1
PHASE 1

1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL - PLUMBING AND MED GAS
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PLUMBING AND MED
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
GAS
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:21 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M251
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.
B. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING
LAYOUT.

PHASE 4
A1
B AREA DESIGN REQUIREMENTS
B.0
1
1 1 1 1 1 1 1 1 1 SPR-3 MARK CLASSIFICATION COVERAGE DENSITY

1
SPR-3 1 LIGHT HAZARD 0.10 GPM OVER 1500 SQ. FT.
1
1.7 2.1 2 ORDINARY HAZARD GROUP 1 0.15 GPM OVER 1500 SQ. FT.

3 ORDINARY HAZARD GROUP 2 0.20 GPM OVER 1500 SQ. FT.

B1.1
1 1 1 1 1 1 1 1 1 1

1
1
1
FIRE SPRINKLER HATCHING LEGEND

C EXISTING SPRINKLER COVERAGE TO REMAIN

1 1
EXISTING SPRINKLER SYSTEM TO BE REVISED
1 TO ACCOMMODATE NEW WORK
1
C1 F
FLOW SWITCH

FIRE SPRINKLER FINISH LEGEND


ALL SPRINKLERS SHALL BE RECESSED, CHROME
PLATED UNLESS NOTED OTHERWISE.
SPR-1 CONCEALED, WHITE
1 SPR-2 CONCEALED, BRUSHED COPPER
6"ø F
SPR-3 CONCEALED, GASKETED, WHITE
1
SPR-4 CONCEALED, MRI RATED, WHITE
1 1 SPR-5 UPRIGHT, ROUGH BRONZE, PROTECTIVE WIRE CAGE

D
PHASE 3 PHASE 2

1 1

1 1

FESSION
6"ø F PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
10229
ERIC G.

R
SHERMAN
1

A
S

T
D1

O
U O
T H K
D A

1 11/25/14
1

E No. Description Date

1 1

1
1
1 1 1 1 1 1 1 1 1

E1

1
1
SPR-3
SPR-3
1 1 1 1 1 1 1 1 1 1 1
1
SPR-3
F W
F
F1
PHASE 1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL FIRE PROTECTION
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL - FIRE
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROTECTION
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:28 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M351
www.specializedeng.com Scale 1/8" = 1'-0"
WALL OPENING SHALL BE 1/8"
WALL
LARGER THAN DAMPER PER
LINEAR FOOT IN HEIGHT AND
WIDTH. (NOT LESS THAN 1/4"
MAIN RETURN ACOUSTIC LINING BREAKAWAY CONNECTION LARGER.)
MAIN SUPPLY AVERA FACILITY DEVELOPMENT
AIR DUCT AIR DUCT WHERE INDICATED

DUCTWORK INSULATION WHEN DUCT IS LINED


OR WRAPPED. (ALL AROUND
DUCT ON BOTH SIDES OF WALL.)
AIR FLOW

AIR FLOW
SUPPLY DUCT
COLLAR FUSIBLE LINK
FLEX DUCT MAX. 5'-0" AIR
45° * HIGH- FLOW
FLEX DUCT SIZE SHALL 45° * SLEEVE THRU WALL. EXTEND DUCTWORK
HIGH- EFFICIENCY SLEEVE 3" MIN. TO 6" MAX. ON
MATCH NECK SIZE TAKE-OFF
EFFICIENCY THIS SIDE OF WALL OPERATING SPRING
TAKE-OFF
SLEEVE THRU WALL. EXTEND
L.P. BRANCH DUCT HAND SLEEVE 3" MIN. TO 16" MAX. ON
HAND VOLUME ACCESS DOOR SIDE OF WALL.
VOLUME DAMPER
DAMPER RETURN AIR
BRANCH DUCT 1 1/2" x 1 1/2" MINIMUM 14 GAUGE
ANGLE ON ALL SIDES OF OPENING AND ANCHOR DAMPER AND ANGLES TO
HAND DAMPER BOTH SIDES OF WALL. ANGLES SHALL SLEEVE IN ACCORDANCE WITH
OVERLAP OPENING BY 1" MINIMUM AND MANUFACTURERS
OPPOSED *-EQUALS WIDTH OF BRANCH DUCT UP TO 12" COVER CORNERS OF OPENING RECOMMENDATIONS. DO NOT
BLADE DAMPER SEE SPECIFICATIONS FOR CONNECTION *-EQUALS WIDTH OF BRANCH DUCT UP TO 12" FASTEN ANGLES TO WALL.
12" FOR ALL BRANCH DUCTS LARGER THAN 12" 12" FOR ALL BRANCH DUCTS LARGER THAN 12"
CEILING

NOTE:

CEILING DIFFUSER
SUPPLY AIR EXHAUST/RETURN AIR TYPE "B"
PROVIDE ACCESS DOORS FOR ALL FIRE DAMPERS AND LABEL WITH
1/2" HIGH LETTERING "FIRE DAMPER".

TYPICAL DIFFUSER CONNECTION DETAIL TYPICAL BRANCH DUCT TAKE-OFF DETAIL FIRE DAMPER THROUGH WALL DERTAIL
3 NONE
2 NONE
1 NONE

INSULATE RADIANT CEILING PANEL WITH 3"


FIBERGLASS INSULATION WITH FOIL SKRIM
FACING UP. OVERLAP ALL SIDES AT LEAST
THREE INCHES.
SUPPORT
3" MINIMUM INDEPENDENTLY FROM 3" MINIMUM WALL OPENING SHALL BE 1/8" LARGER
CEILING (TYP.) THAN DAMPER PER LINEAR FOOT IN
HEIGHT AND WIDTH. (NOT LESS THAN 1/4"
WALL OR FLOOR. LARGER.)

INSULATION WHEN DUCT IS LINED OR


1 1 WRAPPED. (ALL AROUND DUCT ON BOTH
1/2" DEEP 10 GAUGE MINIMUM SIDES OF WALL.)
GALVANIZED CHANNEL IF DUCT IS TIGHT
TO STRUCTURE.
METAL NOSING. (IF DUCT IS LINED.)

CROSS CHANNEL BRACE NORMALLY CLOSED ELECTRIC OPERATOR


AND LINKAGE OUTSIDE OF AIRSTREAM.
BREAKAWAY CONNECTION

TILE TILE

NOTE: PROVIDE ACCESS DOORS FOR ALL


FIRE AND SMOKE DAMPERS. LABEL WITH
PANEL 1/2" HIGH LETTERING:
WALL ANGLE
PIPING SLEEVE THRU WALL. EXTEND SLEEVE 3"
MOLDING
MIN. TO 16" MAX. ON ACTUATOR SIDE OF
CEILING GRID "T" "FIRE/SMOKE DAMPER" WALL.
24" GRID CEILING OPENING VARIES
SLEEVE THRU WALL. EXTEND SLEEVE 3" TO FIRE SMOKE DAMPERS AS REQUIRED.
FESSION
NOTE: MIN. TO 6" MAX. ON THIS SIDE OF WALL. M PRO AL
ED . NO.
REG

ER

EN
1 INSULATE RADIANT PANEL WITH 3" FIBERBLASS INSULATION WITH FOIL SKRIM FACING UP. WIRING BY A.T.C. A.T.C. SHALL

REGIST

GINEE
OVERLAP ALL SIDES AT LEAST THREE INCHES. ANCHOR DAMPER AND ANGLES TO SLEEVE PROVIDE TRANSFORMER IF REQUIRED. 10229
IN ACCORDANCE WITH MANUFACTURERS ERIC G.

R
SHERMAN
RADIANT CEILING PANEL DETAIL
RECOMMENDATIONS. DO NOT FASTEN

A
S
6
ANGLES TO WALL.

T
O
U O
T H K
D A
NONE ARD
1-1/2" x 1-1/2" MINIMUM 14 GAUGE
ANGLE ON ALL SIDES OF OPENING AND
ROUTE NEW VENT STACK TO EXISTING BOTH SIDES OF WALL. ANGLES SHALL 11/25/14
VENT THROUGH ROOF. COORDINATE OVERLAP OPENING BY 1" MINIMUM AND
ROUTE WITH OTHER UTILITIES. WIRING BY E.C. TEMPERATURE CONTROLS RELAY
COVER CORNERS OF OPENING.
No. Description Date

4"ø V

1 1/2"ø V JUNCTION BOX BY E.C.


NOTES:
1 1/2"ø V 1. CONNECTION OF DAMPER TO SLEEVE SHALL BE AS SHOWN IN FIGURE 1 OF SMACNA "FIRE DAMPER AND
2 1/2"ø V HEAT STOP GUIDE FOR AIR HANDLING SYSTEMS", SECOND EDITION.

2. DAMPER CLOSES BY SPRING ACTION IN EVENT OF HIGH TEMPERATURE.


SH-1 1 1/2"ø V
1/2"ø CW SH-1 3. FLOOR MOUNTED DAMPER SIMILAR WITH ACTUATOR ON SIDE WITH ACCESS DOOR.
1/2"ø HW
2 1/2"ø V 4. WHERE DUCT SMOKE DETECTORS CANNOT BE ACCESSED BY THE DAMPER ACCESS DOOR THE ELECTRICAL
CONTRACTOR SHALL FURNISH A DUCT ACCESS DOOR FOR THE DETECTOR. THE MECHANICAL CONTRACTOR
L-(1)(2) L-1 L-(1)(2) L-1 SHALL INSTALL THE DOOR IN THE DUCT.

1 1/2"ø CW 5. SEE SMOKE DAMPER CONTROLLER SCHEMATIC DETAIL ON ELECTRICAL DRAWINGS FOR WIRING DETAILS. A.T.C.
WC-1 SHALL PROVIDE RELAYS TO CLOSE FIRE SMOKE DAMPERS IN NON-FIRE EVENTS. REFER TO ELECTRICAL DRAWINGS
WC-1
1"ø CW FOR LOCATIONS.
1"ø HW FD-(1)(2)
FD-(1)(2)
COMBINATION FIRE AND SMOKE DAMPER THROUGH WALL DERTAIL
4 NONE

MAINTAIN MIN. 3 DUCT DIAMETERS


OF STRAIGHT RIGID DUCT
NOTE: MATCHING INLET SIZE HI-EFFICIENCY DUCT TAKEOFF
REFER PLUMBING FIXTURE SCHEDULE
FOR PIPE SIZES TO INDIVIDUAL FIXTURES 4"ø SAN
AIR TERMINAL UNIT BUILT WITH
1 1/2"ø V
INSULATED FIBER FREE LINER
FLOW SENSOR GRID
SACRED HEART
VAV CONTROLLER BY CONTROLS
CONTRACTOR 4TH & 5TH
AUTOMATIC FLOW CONTROL VALVE
NOTE:
REFER PLUMBING FIXTURE SCHEDULE
REHEAT COIL 2014 C COPYRIGHT MECHANCIAL
1 1/2"ø CW
FOR PIPE SIZES TO INDIVIDUAL FIXTURES BALL VALVE (TYP) PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DETAILS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
2"ø SAN OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
UNOBSTRUCTED ACCESS LOCATED STRAINER WITH BLOW-DOWN VALVE ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
AT ACCESS PANEL OR ABOVE
CEILING TILE 2-WAY CONTROL VALVE DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
UNION WITH P/T PLUG COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:31 PM

TERMINAL UNIT DETAIL 10360 Ellison Circle SES PROJECT # 14041

DOMESTIC WATER ISOMETRIC WASTE AND VENT ISOMETRIC


5 NONE
Omaha, NE 68134
Phone: 402.991.5520 M500
7 NONE
8 NONE www.specializedeng.com Scale NONE
FULL SIZE CONDENSATE DRAIN,
CONNECT TO DRAIN PAN AS RISER CLAMP
RECOMMENDED BY MANUFACTURER. CLEANOUT PLUG (TYP.) INSTALL CLAMP ON ALL
PIPES LESS THAN 4"Ø THREADED ROD
INSULATION AND
CLEVIS HANGER NEOPRENE MOUNTS.
PIPE INSULATION. (TYP.) INSULATION LUG, COUPLING, OR HUB

THREADED ROD. (TYP.) INSULATION


HIGH DENSITY INSULATION AVERA FACILITY DEVELOPMENT
STEEL PIPE FLOOR
INSERT. SADDLE, TACK
HIGH DENSITY INSULATION INSERT. OVERSIZE HANGER TO WELDED TO PIPE,
ALLOW LONGITUDINAL FILL SADDLE
H PIPE EXPANSION AND WITH INSULATION. INSULATION
INSULATION SHIELD. UNI-STRUT OR INSULATION SHIELD
PIPE INSULATION TO
(TYP.) EQUIVALENT PASS THROUGH
UNBROKEN. (TYP.)
TRAPEZE HANGER STRUT CLAMP HANGERS CLEVIS HANGER ROLLER SUPPORT VERTICAL PIPE SUPPORT

PIPE SUPPORT DETAIL


H/2
ROUTE DIRECTLY ABOVE
FLOOR DRAIN
1 NONE

NOTE:
1. FOR DRAW-THROUGH SYSTEMS, DIMENSION FOR EVERY UNIT. H= FAN INLET PRESSURE
(IN W.C.) + 1 INCH. (2" MIN.) WALL WITH INSULATION
SUPPORT

CONDENSATE TRAP DETAIL (NEGATIVE PRESSURE SECTION)


2 NONE FLANGES ON EACH SIDE
PACK AROUND PIPE WITH OF WALL. CAULK AT WALL
FIBERGLASS INSULATION AND SLEEVE.
4" TO 8"
CLEANOUT PLUG (TYP.)
FULL SIZE CONDENSATE DRAIN, TYP. ON
ESCUTCHEON PLATES
CONNECT TO DRAIN PAN AS BOTH SIDES
ON BOTH SIDES
RECOMMENDED BY MANUFACTURER. PIPE
1" +/- 1/4" 1/4" FOR
ITEMS LESS THAN 4"

SHEET METAL SLEEVE,


PENETRATING ITEM
2" LARGER THAN PIPE
OVERALL DIAMETER.
H
ESCUTCHEON (TYP. ON
12" BOTH SIDES.)
ROUTE DIRECTLY ABOVE ACOUSTICAL SEALANT
FLOOR DRAIN
FOAM BACKER ROD NOT REQUIRED FOR
SLEEVE ITEMS LESS THAN
SAFING BATT INSULATION 4" DIAMETER

WALL

NOTE: CONCRETE/MASONARY
GYPSUM WALL WALL CONSTRUCTION
1. FOR BLOW-THROUGH SYSTEMS, DIMENSION FOR EVERY UNIT. H= FAN
OUTLET PRESSURE (IN W.C.) + 1 INCH. (2" MIN.) CONSTRUCTION

CONDENSATE TRAP DETAIL (POSITIVE PRESSURE SECTION)


4 NONE NOTES:
1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTIONS ARE TO CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH ALL
PENETRATIONS, PERMIT THERMAL EXPANSION WITHOUT DAMAGING THE INSULATION, AND SEAL AIRTIGHT AROUND INSULATED
AND UNINSULATED PIPES FOR NOISE TRANSMISSION CONTROL.

2. METHODS THAT ARE LISTED FOR THE REQUIRED HOURLY RATINGS MUST BE USED FOR FIRE RATED WALLS. ALL OF THE
INTENTIONS IN NOTE 1 MUST BE MET BY THE SYSTEM SELECTED.
FESSION
PRO AL
ED
NOISE CONTROL WALL PENETRATION DETAIL
. NO.
REG

ER

EN
3

REGIST

GINEE
10229
NONE ERIC G.

R
SHERMAN

A
S

T
O
U O
T H K
D A

FULL SIZE BYPASS WITH FULL SIZE BYPASS WITH


MANUAL THROTTLING VALVE MANUAL THROTTLING VALVE 11/25/14

2-WAY MODULATING 2-WAY MODULATING


VALVE (TYP) ISOLATION VALVE (TYP) VALVE (TYP) No. Description Date
ISOLATION VALVE (TYP)

AIRFLOW
STRAINER WITH
STRAINER WITH BLOW-DOWN VALVE
MANUAL AIR VENT MANUAL AIR VENT PIPE WELLS (TYP)
PIPE WELLS BLOW-DOWN VALVE (TYP) FOR CONTROLS
(TYP) (TYP)
ROOF FAN FOR CONTROLS (TYP)
(TYP) COOLING COIL
SECURE FAN BASE TO CURB MIN. 2 HEATING COIL
LOCATIONS EACH SIDE AND ON 6" AUTOMATIC BALANCING VALVE AUTOFLOW
CENTERS FOR CURBS OVER 18"x18" BALANCING VALVE
INTERMEDIATE
DRAIN PAN

MANUAL AIR VENT MANUAL AIR VENT


(TYP) (TYP) P/T PLUG (TYP)
P/T PLUG (TYP)
HEATING COIL CONDENSATE DRAIN COOLING COIL
EXISTING FAN CURB PIPE. REFER TO PIPING
3/4 DRAIN VALVE 3/4 DRAIN VALVE
MATERAL SCHEDULE (TYP)
(TYP) AND SPECIFICATIONS
FOR MATERIAL
12" MIN. REQUIREMENTS PRIMARY DRAIN UNION WITH P/T PLUG
UNION WITH P/T PLUG
(TYP) PAN (TYP)

AHU HEATING COIL PIPING DETAIL AHU COOLING COIL PIPING DETAIL
SEE SPECIFICATIONS/
6 NONE
5 NONE
SCHEDULE FOR DAMPER TYPE
SACRED HEART
Exhaust Fan Detail
8 NONE
STRAINER
4TH & 5TH
3/4" HWS TO
RADIANT

AUTOFLOW
PANEL
2014 C COPYRIGHT MECHANICAL
VALVE PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DETAILS
3/4" HWR PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
FROM OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
RADIANT ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
PANEL DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
2-WAY BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
CONTROL COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:32 PM
VALVE
10360 Ellison Circle SES PROJECT # 14041

7
RADIANT PANEL CONNECTION DETAIL
NONE
Omaha, NE 68134
Phone: 402.991.5520 M501
www.specializedeng.com Scale NONE
CONTROL VALVE FOR
BMS SHUTOFF

DUCTWORK OR IN UNIT AS
SHOWN ON PLAN AVERA FACILITY DEVELOPMENT

RETURN
DISPERSION TUBE DISCHARGE
AGAINST AIRFLOW.
MANUAL AIR VENT UNION (TYP.)
(TYP)
DRIP TRAP

PLATE AND FRAME


HEAT EXCHANGER
SUPPLY

CONTROL VALVE

ISOLATION VALVE
HUMIDIFIER AIR
SEPARATOR FLO
W
2-WAY MODULATING
HOUSEKEEPTING PAD VALVE (TYP).

THERMOMETER (TYP)

UNION (TYP)
PTT PORT
SUPPLY (TYP)

PROVIDE MULTIPLE TUBES AND


DRAIN (TYP) MANIFOLD IF REQUIRED TO
SUPPLY CAPACITY SPECIFIED.
PIPE WELLS FOR
CONTROLS (TYP)
TRAP FURNISHED WITH
FULL SIZE DIRT LEG HUMIDIFIER
PRESSURE GAUGE (TYP)
10" LONG. (TYP.)
TEMPERATURE
RETURN SWITCH FURNISHED
WITH HUMIDIFIER.

PLATE AND FRAME HEAT EXCHANGER CONNECTION DETAIL HUMIDIFIER DETAIL (DIRECT INJECTION)
2 NONE
1 NONE

FESSION
PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
10229
ERIC G.

R
SHERMAN

A
S

T
O
U O
T H K
D A

11/25/14

No. Description Date

SACRED HEART
4TH & 5TH
2014 C COPYRIGHT MECHANICAL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DETAILS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:33 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M502
www.specializedeng.com Scale NONE
SECTION 23 73 13

MODULAR INDOOR AIR-HANDLING UNITS 2.4 FAN SECTION 2.11 ULTRAVIOLET LIGHTS
PART 1 - GENERAL A. Fan-Section Construction: Belt-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1.1 RELATED DOCUMENTS assembly, and support structure and equipped with formed-steel channel base for integral mounting of fan, motor, and casing panels. Mount fan 1. Steril-aire.
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply with spring vibration isolation. 2. UV Resources.
to this Section. B. Centrifugal Fan Housings: Formed- and reinforced-steel panels to make curved scroll housings with shaped cutoff, spun-metal inlet bell, and 3. Ultraviolet Devices, Inc.
1.2 SUMMARY access doors or panels to allow entry to internal parts and components. B. Provide UV-C emitters/lamps downstream of all cooling coils and above all drain pans to control airborne and surface microbial growth
A. This Section includes variable-volume, modular air-handling units with coils for indoor installations. 1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and supporting fan scroll, wheel, motor, and accessories. and transfer. AVERA FACILITY DEVELOPMENT
1.3 SUBMITTALS 2. Performance Class: AMCA 99-2408, all Classes. C. Lamps shall be manufactured, selected, and installed specific for the unit. Provide all safety interlocks including on/off switch(es),
A. Product Data: For each type of modular indoor air-handling unit indicated. Include the following: 3. Horizontal Flanged Split Housing: Bolted construction. external fusing, ETL listing to UL 1598, and lamp monitor.
1. Certified fan-performance curves with system operating conditions indicated. 4. Plug Fans: With steel cabinet. Fabricate without fan scroll and volute housing. D. Voltage shall be 120V. Electrical wiring shall be separately wired to a junction box mounted on the outside of the unit. Furnish and install
2. Certified fan-sound power ratings. C. Fan Assemblies: Statically and dynamically balanced and designed for continuous operation at maximum rated fan speed and motor horsepower. separate disconnect and associated wiring outside of each applicable section.
3. Certified coil-performance ratings with system operating conditions indicated. D. Airfoil-Fan Wheels: Steel construction with smooth-curved inlet flange, heavy backplate, and hollow die-formed airfoil-shaped blades continuously E. Provide UV protected glass in applicable sections for access doors with integral window
4. Motor ratings, electrical characteristics, and motor and fan accessories. welded at tip flange and backplate; cast-iron or cast-steel hub riveted to backplate and fastened to shaft with set screws. PART 3 - EXECUTION
5. Material gages and finishes. E. Shafts: Statically and dynamically balanced and designed for continuous operation at maximum rated fan speed and motor horsepower, with final 3.1 EXAMINATION
6. Filters with performance characteristics. alignment and belt adjustment made after installation. A. Examine areas and conditions for compliance with requirements for installation tolerances and other conditions affecting performance.
7. Dampers, including housings, linkages, and operators. 1. Turned, ground, and polished hot-rolled steel with keyway. Ship with a protective coating of lubricating oil. B. Examine roughing-in of steam, hydronic, and condensate drainage piping systems and electrical services to verify actual locations of
8. Ultraviolet lights. 2. Designed to operate at no more than 70 percent of first critical speed at top of fan's speed range. connections before installation.
B. Shop Drawings: Signed and sealed by a qualified professional engineer. F. Grease-Lubricated Shaft Bearings: Self-aligning, pillow-block-type, ball or roller bearings with adapter mount and two-piece, cast-iron housing. C. Proceed with installation only after unsatisfactory conditions have been corrected.
1. Design Calculations: Calculate requirements for selecting vibration isolators and seismic restraints and for designing vibration isolation bases. 1. Ball-Bearing Rating Life: ABMA 9, L10 of 100,000 hours. 3.2 FIELD TESTING
2. Vibration Isolation Base Details: Detail fabrication including anchorages and attachments to structure and to supported equipment. Include 2. Roller-Bearing Rating Life: ABMA 11, L10 of 100,000 hours. A. Field-Leak Testing. The Mechanical Contractor shall provide a field leak test on units at 1.5 times design total static pressure (minimum 8
auxiliary motor slides and rails, and base weights. G. Vibration Control: Install fans on open-spring vibration isolators having a minimum of 1-inch static deflection and side snubbers. inches w.g.) across the cabinet exterior walls and L/240 deflection at 8 inch w.g. Cabinet leakage is not to exceed 1 percent of specified
3. Wiring Diagrams: Power, signal, and control wiring. H. Fan-Section Source Quality Control: airflow on the operating side of the unit. A written test report shall be prepared by the Mechanical Contractor submitted for review by the
C. Field Quality-Control Test Reports: From manufacturer. 1. Sound Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan Sound Ratings from Laboratory Test Data." Test fans Engineer prior to placement into service, and be included with the operation and maintenance manual.
1.4 QUALITY ASSURANCE according to AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Fans shall bear AMCA-certified sound ratings seal. 3.3 FIELD QUALITY CONTROL
A. Source Limitations: Obtain modular indoor air-handling units through one source from a single manufacturer. 2. Factory test fan performance for flow rate, pressure, power, air density, rotation speed, and efficiency. Establish ratings according to AMCA A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment
B. Product Options: Drawings indicate size, profiles, and dimensional requirements of modular indoor air-handling units and are based on the specific 210, "Laboratory Methods of Testing Fans for Rating." installation, including piping and electrical connections. Report results in writing.
system indicated. Refer to Division 01 Section "Product Requirements." 2.5 MOTORS 1. Leak Test: After installation, fill water and steam coils with water and test coils and connections for leaks. Repair leaks and retest until
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to A. Motors shall be NEMA Design B; T -FRAME mounted on an adjustable steel base. All motors shall be tested to IEEE standard 112 test method B no leaks exist.
authorities having jurisdiction, and marked for intended use. and rated per NEMA MG1, Part 31 "Inverter Fed Motors, premium efficiency. All motors shall be specifically designed to meet or exceed all 2. Fan Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.
D. NFPA Compliance: Modular indoor air-handling units and components shall be designed, fabricated, and installed in compliance with NFPA 90A, (EPAct) requirements for energy efficiency and include Class F insulation. Motors shall be as manufactured by Baldor, Toshiba, Reliance, or Remove malfunctioning units, replace with new units, and retest.
"Installation of Air Conditioning and Ventilating Systems." equal. All motors shall include shaft grounding: Aegis or equal. Provide NEMA premium efficiency motors. 3. Final Filter Operational Test: Pressurize housing to a minimum of 3-inch wg or to designed operating pressure, whichever is higher;
E. ARI Certification: Modular indoor air-handling units and their components shall be factory tested according to ARI 430, "Central-Station Air- 2.6 COILS test housing joints, door seals, and sealing edges of filter for air leaks according to ASME N510, pressure-decay method.
Handling Units," and shall be listed and labeled by ARI. A. Coil Sections: Common or individual, insulated, stainless steel casings for cooling and galvanized steel casings for heating. Design and construct 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
F. Comply with NFPA 70. to facilitate removal and replacement of coil for maintenance and to ensure full airflow through coils. 3.4 STARTUP SERVICE
1.5 EXTRA MATERIALS B. Water Coils: Self-draining coil fabricated according to ARI 410. A. Engage a factory-authorized service representative to perform startup service.
A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified 1. Piping Connections: Threaded, on same end, Red Brass. B. Final Checks before Startup: Perform the following:
with labels describing contents. 2. Tubes: Copper. 1. Verify that shipping, blocking, and bracing are removed.
1. Filters: One set for each modular indoor air-handling unit, to be installed at time of project completion. 3. Fins: Aluminum. 2. Verify that unit is secure on mountings and supporting devices and that connections to piping, ducts, and electrical systems are
1.6 WARRANTY 4. Headers: Carbon-steel with drain and air vent tappings. complete. Verify that proper thermal-overload protection is installed in motors, starters, and disconnect switches.
A. Air Handling Unit Warranty: Manufacturer's standard form in which manufacturer agrees to replace any component of AHUs that fail in materials or 5. Frames: Galvanized-steel channel frame for heating coils, 0.052 inch. 3. Perform cleaning and adjusting specified in this Section.
workmanship within specified warranty period. 6. Frames: Stainless steel, 0.0625 inch for cooling coils. 4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify free fan wheel rotation and smooth bearing operations.
1. Warranty Period: Manufacturer's standard, but not less than two years from date of shipment from factory. 7. Ratings: Design tested and rated according to ASHRAE 33 and ARI 410. Reconnect fan drive system, align belts, and install belt guards.
PART 2 - PRODUCTS a. Working-Pressure Ratings: 200 psig, 325 deg F. 5. Lubricate bearings, pulleys, belts, and other moving parts with factory-recommended lubricants.
2.1 MANUFACTURERS 8. Source Quality Control: Test to 300 psig and to 200 psig underwater. 6. Set face-and-bypass dampers to full face flow.
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 2.7 DAMPERS 7. Comb coil fins for parallel orientation.
1. Carrier. A. General: Leakage rate, according to AMCA 500, "Laboratory Methods for Testing Dampers for Rating," shall not exceed 2 percent of air quantity 8. Install clean filters.
2. Daikin/McQuay. at 2000-fpm face velocity through damper and 4-inch wg pressure differential. C. Starting procedures for modular indoor air-handling units include the following:
3. Huntair. B. Supply and Return Isolation Dampers: Heavy-duty steel assembly with channel frame and sealed ball bearings, and parallel blades constructed of 1. Energize motor; verify proper operation of motor, drive system, and fan wheel. Adjust fan to indicated rpm. Replace fan and motor
4. Trane. two plates formed around and welded to shaft, with blades linked out of airstream to single control lever. Install on supply and return duct openings pulleys as required to achieve design conditions.
2.2 MANUFACTURED UNITS of unit. 2. Measure and record motor electrical values for voltage and amperage.
A. Modular indoor air-handling units shall be factory assembled and consist of fans, motor and drive assembly, coils, dampers, plenums, filters, C. Low-Leakage, Outdoor-Air and Relief-Air Dampers: Double-skin, airfoil-blade galvanized-steel dampers with compressible jamb seals and 3. Manually operate dampers from fully closed to fully open position and record fan performance.
condensate pans, mixing dampers, dehumidification wheels, and ultraviolet lights. extruded-vinyl blade edge seals, in opposed-blade arrangement with steel operating rods rotating in stainless-steel sleeve bearings mounted in a 3.5 DEMONSTRATION
2.3 CABINET single galvanized-steel frame, and with operating rods connected with a common linkage. Leakage rate shall not exceed 5 cfm/sq. ft. at 1-inch wg A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain modular
A. Materials: Formed and reinforced double-wall insulated panels, fabricated to allow removal for access to internal parts and components, with and 9 cfm/sq. ft. at 4-inch wg. indoor air-handling units.
joints between sections sealed. D. Mixing Boxes: Parallel-blade galvanized-steel dampers mechanically fastened to steel operating rod in reinforced, galvanized-steel cabinet. END OF SECTION 23 73 13
1. Outside Casing: Galvanized steel, 0.0299 inch or 22 gauge thick. Connect operating rods with common linkage and interconnect linkages so dampers operate simultaneously.
2. Inside Casing (fan sections and discharge plenums): Galvanized steel, 0.0299 inch or 22 gauge thick, perforated. E. Provide damper actuators for all dampers listed above, including supply, return, outdoor, relief, and mixing dampers.
3. Inside Casing (all other sections): Galvanized steel, 0.0299 inch or 22 gauge thick, solid. F. Provide backdraft dampers on fan inlet on units with multiple fans in parallel.
4. Floor Plate: Aluminum, 0.1382 inch thick with tread plate flooring. 2.8 FILTER SECTION
5. Factory Base Rail: 6 inch on low/medium pressure units. A. Filters: Comply with NFPA 90A.
B. Cabinet Insulation: Comply with NFPA 90A or NFPA 90B. B. Filter Section: Provide filter holding frames arranged for flat or angular orientation, with access doors on both sides of unit. Filters shall be
1. Cabinets will have 2” foam insulation (minimum R-13 insulation value). removable from one side.
2. Materials: ASTM C 1071 with coated surface exposed to airstream to prevent erosion of glass fibers. C. Extended-Surface, Disposable Panel Filters: Factory-fabricated, dry, extended-surface filters with holding frames.
3. Thickness: 2 inches. 1. Media: Fibrous material formed into deep-V-shaped pleats and held by self-supporting wire grid.
4. Thermal Conductivity (k-Value): 0.26 at 75 deg F mean temperature. 2. Media and Media-Grid Frame: Nonflammable cardboard.
5. Fire-Hazard Classification: Maximum flame-spread index of 25 and smoke-developed index of 50, when tested according to ASTM C 411. 3. Duct-Mounting Frames: Welded, galvanized steel with gaskets and fasteners, suitable for bolting together into built-up filter banks.
6. Liner Adhesive: Comply with NFPA 90A or NFPA 90B and ASTM C 916. D. Final Filters: Factory-fabricated filters with holding casing.
7. Mechanical Fasteners: Galvanized steel, suitable for adhesive attachment, mechanical attachment, or welding attachment to duct without 1. Media: UL 586, fibrous glass, constructed of continuous sheets with closely spaced pleats with aluminum separators.
damaging liner when applied as recommended by manufacturer and without causing leakage in cabinet. 2. Frame Material: Aluminum.
8. Location and Application: Factory applied with adhesive and mechanical fasteners to the internal surface of section panels downstream from 3. Media to Frame Side Bond: Neoprene adhesive.
and including the cooling coil section. 4. Face Gasket: Neoprene expanded rubber.
9. Location and Application: Encased between outside and inside casing. 5. Duct-Mounting Frames: Construct downstream corners of holding device with cushion pads to protect media. Provide bolted filter-
C. Access Panels and Doors: Same materials and finishes as cabinet, complete with hinges, latches, handles, and gaskets. Access panels and sealing mechanism to mount and continuously seal each individual filter.
doors shall be sized and located to allow periodic maintenance and inspections. All sections with access doors shall have viewing windows. 2.9 BLANK SECTIONS
Provide access panels and doors in the following locations: A. Provide an 18 inch blank section for future humidifier grid. Provide knock out holes in cabinet to accept future humidifier grid.
1. Fan Sections: Access door on main access side of unit, access panels on other two (2) sides.
2. Access Sections: Access door on both sides of unit.
3. Coil Sections: Access panel on both sides of unit.
2.10 ELECTRICAL
A. Fan Motors
1. Each fan motor shall be separately wired to a junction box mounted on the outside of the unit. Wiring shall include separate ground for
FOR REFERENCE ONLY
4. Damper Sections: Access door on main access side, access panel on other side of unit. each motor.
5. Surgery Dehumidification Sections: Access door on main access side, access panel on other side of unit. 2. VFDs will be furnished and installed by the Temperature Controls Contractor.
6. UV Lights Sections: Access door on main access side, access panel on other side of unit. B. Lighting Circuits
FESSION
7. Filter Sections: Access door on main access side, access panel on other side of unit. 1. Each section shall be provided with a vapor proof LED light fixture with a guard and mounted not to interfere with service including filter PRO AL
D. Condensate Drain Pans: Formed sections of stainless-steel sheet complying with requirements in ASHRAE 62. Fabricate pans with slopes in two replacement. Wiring shall include separate ground for each motor. ED . NO.
REG

ER

EN
planes to collect condensate from cooling coils (including coil piping connections and return bends) and humidifiers when units are operating at 2. All lighting rigid, not flexible, conduit to be installed by manufacturer and terminated to a switch location at the front of the unit. Provide

REGIST

GINEE
maximum catalogued face velocity across cooling coil. empty junction box next to switch for receptacle furnished and installed by Electrical Contractor. 10229
1. Double-Wall Construction: Fill space between walls with foam insulation and seal moisture tight. 3. Wiring sizing shall be determined, and installed, in accordance with applicable NEC standard. ERIC G.

R
2. Pan-Top Surface Coating: Elastomeric compound. 4. Furnish small flexible metal conduit splices for Electrical Contractor to install at shipping splits for lighting circuit. SHERMAN

A
S
3. Units with stacked coils shall have an intermediate drain pan or drain trough to collect condensate from top coil. C. UV Lights

T
O
U O
T H K
D A
5. Duct-Mounting Frames: Construct downstream corners of holding device with cushion pads to protect media. Provide bolted filter- 1. All UV lights shall be separately wired to a junction box mounted on the outside of the unit. Wiring shall include separate ground for
sealing mechanism to mount and continuously seal each individual filter. each motor.
2. VFDs will be furnished and installed by the Temperature Controls Contractor.
D. Duct Detectors 11/25/14
1. Duct smoke detectors for supply and return sections will be furnished and installed by AHU manufacturer. Electrical Contractor will wire
up to detectors for fire alarm interface.
No. Description Date
FILTER SCHEDULE
STEAM HUMIDIFIER SCHEDULE MARK LOCATION TYPE THICKNESS
MAX. FACE
VELOCITY
EFFICIENCY/
QUANTITY SIZE
INITIAL
PRESSURE LOSS MANUFACTURER MODEL REMARKS
MERV
STEAM DISPERSION MAXIMUM CASING MAXIMUM [FPM] [IN.W.C.]
STEAM FLOW
MARK PRESSURE IN TUBE SPACING NOT-WETTING DIMENSIONS PRESSURE MANUFACTURER MODEL REMARKS 12 24x24
[#/HR] FB-10A PRE FILTER PLEATED 2" 437 MERV 8 0.20 CAMFIL FARR 30/30 (1)(2)
[PSIG] [IN] DISTANCE [IN] (WxH) [IN] DROP [IN.W.C.] 3 20x24
12 24x24
HUM-10 5 108 12 24 86x94 0.01 DRI-STEEM ULTRA-SORB (1)(2) FB-10B FINAL FILTER RIGID 12" 437 MERV 14 0.47 CAMFIL FARR RIGA-FLO (1)(2)
3 20x24

REMARKS REMARKS
(1) CONTRACTOR TO PIPE UNIT AS INDICATED FROM FACTORY. (1) PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING.
(2) DISPERSION SYSTEM SHALL BE REMOVABLE FROM AHU THROUGH ACCESS DOORS OR REMOVABLE PANEL WITHOUT REMOVAL OF OTHER EQUIPMENT. (2) PROVIDE FILTER BANK HOLDING FRAME, BASIS OF DESIGN: CAMFIL FARR TYPE 8.

AIR HANDLING UNIT SCHEDULE


SUPPLY FAN RETURN FAN CHILLED WATER HEATING WATER
MIN. OA COIL COIL FILTER DATA FILTER DATA
MARK LOCATION TYPE MANUFACTURER REMARKS
[CFM] TYPE # FANS CFM S.P. [IN.] HP VOLTS/Ø TYPE # FANS CFM S.P. [IN.] HP VOLTS/Ø BANK #1 BANK #2
MARK MARK
PLENUM PLENUM
AHU-10 3RD FLOOR VAV 7,850 2 24,000 6.57 40 460/3 2 16,150 2.87 20 460/3 CC-1 HC-1 MERV 7 MERV 14 MCQUAY (1)(2)(3)(4)(5)(6)(7)(8)
ARRAY ARRAY
FILTER BANK #1 (FB-10A)

FILTER BANK #2 (FB-10B)

REMARKS
COOLING COIL (CC-10)
HEATING COIL (HC-10)
RETURN AIR PLENUM

HUMIDIFIER (HUM-10)

SUPPLY AIR PLENUM


MIXING CHAMBER

(1) PROVIDE WITH UV LIGHTS ON DOWN STREAM FACE OF COOLING COIL WITH EXTERIOR CONRTOL SWITCH AND DOOR INTERLOCK SWITCH.
RETURN FANS

SUPPLY FANS
AIR BLENDER

UV LIGHTS

(2) PROVIDE WITH INTEGRAL VFD WITH CONTROL CENTER.


(3) MOUNT ON 4" HOUSEKEEPING PAD.
(4) PROVIDE WITH STRUCTURAL BASE RAIL.
(5) PROVIDE WITH PRESSURE RELIEF DOORS.
(6) PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING AT FILTERS.
(7) PROVIDE WITH AIR BLENDER.
SACRED HEART
EXH OA
(8) AHU SELECTION SHALL ALLOW FOR 70% AIRFLOW WITH ONE FAN NOT OPERATING. AHU MUST BE CAPABLE OF STABLE OPERATION AT 15% OF TOTAL AIRFLOW.
SA
4TH & 5TH
RA
HYDRONIC COIL SCHEDULE 2014 C COPYRIGHT MECHANICAL
MARK SERVES FLUID TYPE
AIR FLOW
[CFM]
MIN.
ROWS
MAX.
FINS PER
MAX.
VELOCITY
MAX. AIR
P.D.
ENTERING
DB/WB [°F]
LEAVING
DB/WB [°F]
TOTAL CAPACITY
[MBH]
SENS. CAPACITY
[MBH] FLOW [GPM]
FLUID DATA
EWT/LWT [°F] MAX. P.D. [FT.]
MANUFACTURER REMARKS
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PRE-PURCHASED
INCH [FPM] [IN. WC.] PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
CC-10 AHU-10 WATER 24,000 8 10 489 0.51 82/68 52/52 1,185 785 186.0 44/56 18.8 MCQUAY (1)(2)(3)(4)
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
EQUIPMENT
HC-10 AHU-10 WATER 24,000 2 8 503 0.16 45 95 1,359 - 87.5 180/150 7.3 MCQUAY (1)(3)(4) DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:35 PM
REMARKS
(1) MAINTAIN COIL PULL SPACE ON INSTALLATION. 10360 Ellison Circle SES PROJECT # 14041

1
AHU-10 DETAIL
(2) PROVIDE DOUBLE SLOPED DRAIN PAN.
(3) CONTRACTOR TO PIPE UNIT AS INDICATED FROM FACTORY, COUNTERFLOW.
(4) VALUES GIVEN ARE FOR ENTIRE BANK. COIL BANK SHALL CONSIST OF 2 COILS.
Omaha, NE 68134
Phone: 402.991.5520 M503
NONE
www.specializedeng.com Scale NONE
PLATE AND FRAME HEAT EXCHANGER SCHEDULE HVAC PIPE CONSTRUCTION SCHEDULE
COLD SIDE HOT SIDE HEAT OPERATING SYSTEM
CONNECTION CONNECTION EXCHANGER NUMBER OF SYSTEM MATERIAL CONNECTIONS LOCATION INSULATION FINISH
MARK TYPE MFGR MODEL TEMPERATURE SIZE RANGE PRESSURE FITTINGS REMARKS
FLUID GPM EWT LWT PD [PSI] SIZE [INCHES] FLUID GPM EWT LWT PD [PSI] SIZE [INCHES] PASSES DESCRIPTION (1) (4) (2) (1) (1)(3)
[MBH] RANGE (DEG F) CLASS (PSI)
PLATE 30% PROP. BELL AND AVERA FACILITY DEVELOPMENT
HX-CW1 456 55 45 9.94 6 WATER 430 57 47 6.96 6 2,162 2 GPX P62 BY5432 95/5 SOLDER WROUGHT COPPER ABOVE CEILING 2" PREFORMED FIBERGLASS ASJ JACKET 5
FRAME GLYCOL GOSSETT TYPE L COPPER
0" TO 2" 125 OR OR EXPOSED - FINISHED SPACE 2" PREFORMED FIBERGLASS PAINT TO MATCH 5
TYPE K COPPER PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE 2" PREFORMED FIBERGLASS ASJ JACKET 5
REMARKS HEATING WATER
110-180
(1) PROVIDE INSULATED JACKET FOR HEAT EXCHANGER ASSEMBLY. SUPPLY AND RETURN ASTM A53 SCHEDULE THREADED/FLANGED CAST IRON ABOVE CEILING 2" PREFORMED FIBERGLASS ASJ JACKET 5
2-1/2" AND ABOVE 40 , TYPE E, GRADE B 125 OR OR EXPOSED - FINISHED SPACE 2" PREFORMED FIBERGLASS PAINT TO MATCH 5
STEEL PIPE GROOVED MECHANICAL-JOINT GROOVED MECHANICAL-JOINT EXPOSED - UNFINISHED SPACE 2" PREFORMED FIBERGLASS ASJ JACKET 5
DUCT CONSTRUCTION SCHEDULE 0" TO 2"
TYPE L COPPER
125
95/5 SOLDER
OR
WROUGHT COPPER
OR
ABOVE CEILING
EXPOSED - FINISHED SPACE
1-1/2" PREFORMED FIBERGLASS
1-1/2" PREFORMED FIBERGLASS
NONE
PAINT TO MATCH
5
5
DUCT SMACNA DUCT TYPE K COPPER PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE 1-1/2" PREFORMED FIBERGLASS NONE 5
SYSTEM DUCT MATERIAL INSULATION FINISH CHILLED WATER
DESCRIPTION LOCATION PRESSURE DUCT SEAL CLEANLINESS REMARKS 45-60
DESCRIPTION FUNCTION (1) (2) (3) SUPPLY AND RETURN ASTM A53 SCHEDULE THREADED/FLANGED CAST IRON ABOVE CEILING 1-1/2" PREFORMED FIBERGLASS NONE 5
CLASS (4) CLASS (5) LEVEL (6)
2-1/2" AND ABOVE 40 , TYPE E, GRADE B 125 OR OR EXPOSED - FINISHED SPACE 1-1/2" PREFORMED FIBERGLASS PAINT TO MATCH 5
SUPPLY FAN DISCHARGE TO VAV BOX ABOVE CEILING GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET 6" A ADVANCED - STEEL PIPE GROOVED MECHANICAL-JOINT GROOVED MECHANICAL-JOINT EXPOSED - UNFINISHED SPACE 1-1/2" PREFORMED FIBERGLASS NONE 5
SUPPLY FAN DISCHARGE TO VAV BOX EXPOSED GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET 6" A ADVANCED - ASTM A53 ABOVE CEILING 4.5" PREFORMED FIBERGLASS ASJ JACKET 5
SUPPLY VAV BOX TO DIFFUSER ABOVE CEILING GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET 2" A ADVANCED - 0" TO 2" SCHEDULE 40, 125 THREADED CAST IRON EXPOSED - FINISHED SPACE 4.5" PREFORMED FIBERGLASS PAINT TO MATCH 5
AHU-10
RETURN GRILLE TO FAN INLET ABOVE CEILING GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET -3" A ADVANCED - TYPE S, GRADE B
STEAM EXPOSED - UNFINISHED SPACE 4.5" PREFORMED FIBERGLASS ASJ JACKET 5
AND STEEL PIPE
RETURN GRILLE TO FAN INLET EXPOSED GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET -3" A ADVANCED - 0-80 PSIG ASTM A53
WELDED ABOVE CEILING 4.5" PREFORMED FIBERGLASS ASJ JACKET 5
RELIEF VENT SCHEDULE 40,
RELIEF LOUVER TO AHU/FAN HOUSING EXPOSED GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET +/-6" A ADVANCED - 2-1/2" AND ABOVE 150 OR WROUGH STEEL EXPOSED - FINISHED SPACE 4.5" PREFORMED FIBERGLASS PAINT TO MATCH 5
TYPE E, GRADE B
EF-1,2 EXHAUST GRILLE TO FAN INLET ABOVE CEILING GALVANIZED STEEL 2" EXTERNAL WRAP FSK JACKET -1" B INTERMEDIATE - FLANGED EXPOSED - UNFINISHED SPACE 4.5" PREFORMED FIBERGLASS ASJ JACKET 5
STEEL PIPE
ASTM A53 ABOVE CEILING 2.5" PREFORMED FIBERGLASS ASJ JACKET 5
REMARKS SCHEDULE 80,
0" TO 2" 125 THREADED CAST IRON EXPOSED - FINISHED SPACE 2.5" PREFORMED FIBERGLASS PAINT TO MATCH 5
(1) REFER TO PROJECT SPECIFICATIONS FOR MATERIAL REQUIREMENTS. TYPE S, GRADE B
(2) REFER TO PROJECT SPECIFICATIONS FOR INSULATION MATERIAL DESCRIPTIONS AND REQUIREMENTS. PROVIDE INSULATION WITHIN 10 FEET OF EXTERIOR STEEL PIPE EXPOSED - UNFINISHED SPACE 2.5" PREFORMED FIBERGLASS ASJ JACKET 5
CONDENSATE 0-80 PSIG ASTM A53
PENETRATIONS FOR ALL DUCT SYSTEMS. WELDED ABOVE CEILING 3" PREFORMED FIBERGLASS ASJ JACKET 5
SCHEDULE 80,
(3) REFER TO PROJECT SPECIFICATIONS FOR FINISH DESCRIPTIONS AND REQUIREMENTS. 2-1/2" AND ABOVE 150 OR WROUGH STEEL EXPOSED - FINISHED SPACE 3" PREFORMED FIBERGLASS PAINT TO MATCH 5
TYPE E, GRADE B
(4) REFER TO SMACNA DUCT CONSTRUCTION STANDARDS, CURRENT EDITION FOR CONSTRUCTION REQUIREMENTS. FLANGED EXPOSED - UNFINISHED SPACE 3" PREFORMED FIBERGLASS ASJ JACKET 5
STEEL PIPE
(5) REFER TO SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL FOR REQUIREMENTS.
95/5 SOLDER WROUGHT COPPER ABOVE CEILING 1" PREFORMED FIBERGLASS NONE 5
(6) REFER TO SMACNA DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES FOR REQUIREMENTS.
CONDENSATE DRAIN 45-60 ALL TYPE L COPPER 125 OR OR EXPOSED - FINISHED SPACE 1" PREFORMED FIBERGLASS PAINT TO MATCH 5
PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE 1" PREFORMED FIBERGLASS NONE 5
DOMESTIC HOT WATER 95/5 SOLDER WROUGHT COPPER ABOVE CEILING 1.5" PREFORMED FIBERGLASS ASJ JACKET 5
DIFFUSER, REGISTER, AND GRILLE SCHEDULE AND HOT WATER RE-
CIRCULATING
110-120 0" TO 4" ASTM B88 TYPE L COPPER 125 OR
PRESSURE SEAL
OR
PRESSURE SEAL
EXPOSED - FINISHED SPACE
EXPOSED - UNFINISHED SPACE
1.5" PREFORMED FIBERGLASS
1.5" PREFORMED FIBERGLASS
PAINT TO MATCH
ASJ JACKET
5
5
MAX. S.P. CONST. 95/5 SOLDER WROUGHT COPPER ABOVE CEILING 1" PREFORMED FIBERGLASS NONE 5
MARK (1) DESCRIPTION FINISH FACE SIZE NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKS DOMESTIC COLD WATER
[IN. W.C.] MATERIAL 40-60 0" TO 4" ASTM B88 TYPE L COPPER 125 OR OR EXPOSED - FINISHED SPACE 1" PREFORMED FIBERGLASS PAINT TO MATCH 5
SOFT COLD WATER
PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE 1" PREFORMED FIBERGLASS NONE 5
6" 0-185
8" 186-290 GRAVITY ABOVE CEILING NONE NONE -
LOUVERED FACE TITUS TDX ALL
D-1 STYLE SUPPLY 0.1 STEEL WHITE 24"x24" 10" 291-410 KRUEGER SH (1)(2)(3) SOIL AND WASTE AMBIENT PVC DWV N/A SOLVENT CEMENT PVC DRAINAGE FITTINGS EXPOSED - FINISHED SPACE NONE NONE -
SIZES
DIFFUSER 12" 411-540 PRICE SMD AND VENT EXPOSED - UNFINISHED SPACE NONE NONE -
14" 541-685 ABOVE CEILING NONE NONE -
STANDARD WEIGHT
6" 0-155 0" TO 2" 125 THREADED GRAY -IRON THREADED EXPOSED - FINISHED SPACE NONE PAINT TO MATCH -
BLACK STEEL PIPE
LOUVERED FACE 8" 156-230 TITUS TDX EXPOSED - UNFINISHED SPACE NONE NONE -
D-2 STYLE SUPPLY 0.1 STEEL WHITE 12"x12" - - KRUEGER SH (1)(2)(3) STANDARD WEIGHT
PRICE SMD FIRE PROTECTION AMBIENT ABOVE CEILING NONE NONE -
DIFFUSER - - BLACK STEEL PIPE
THREADED GRAY -IRON THREADED
- - 2-1/2" AND OR
125 OR OR EXPOSED - FINISHED SPACE NONE PAINT TO MATCH -
ABOVE SCHEDULE 10 BLACK
GROOVED MECHANICAL-JOINT GROOVED-MECHANICAL JOINT
STEEL PIPE WITH ROLL-
LINEAR SLOT TITUS ML GROOVED ENDS EXPOSED - UNFINISHED SPACE NONE NONE -
24"x4" 2 KRUEGER 1900
D-3 STYLE SUPPLY 0.1 STEEL WHITE 8" 0-100 (1)(2)(3)
SLOTS @ 1" ABOVE CEILING NONE NONE 5
DIFFUSER PRICE SDS MEDICAL ASTM B819 TYPE K WROUGHT-COPPER, CLEANED,
COMPRESSED AIR, AMBIENT ALL COPPER CLEANED FOR 150 BRAZED PURGED AND BAGGED FOR EXPOSED - FINISHED SPACE NONE NONE 5
OXYGEN OXYGEN SERVICE OXYGEN SERVICE EXPOSED - UNFINISHED SPACE NONE NONE 5
6"x6" 0-195
8"x8" 196-290 TITUS PAR ABOVE CEILING NONE NONE 5
DUCTED
G-1 PERFORATED 0.1 STEEL WHITE 24"x24" 10"x10" 291-400 KRUEGER 6490 (1)(2)(3) MEDICAL VACUUM AMBIENT ALL ASTM B819 TYPE L 150 BRAZED WROUGHT-COPPER EXPOSED - FINISHED SPACE NONE NONE 5
RETURN GRILLE 12"x12" 401-500 PRICE PFR EXPOSED - UNFINISHED SPACE NONE NONE 5
14"x14" 500-730
REMARKS
6"x6" 0-195
8"x8" 196-290 (1) REFER TO PROJECT SPECIFICATIONS FOR REQUIREMENTS.
DUCTED TITUS PAR
G-2 PERFORATED 0.1 STEEL WHITE 24"x12" 10"x10" 291-400 KRUEGER 6490 (1)(2)(3) (2) FINISHED SPACES INCLUDE BUT ARE NOT LIMITED TO NORMALLY OCCUPIED SPACES, STORAGE ROOMS WITHOUT CEILINGS, LOADING AREAS, ETC.
RETURN GRILLE PRICE PFR UNFINSHED SPACES INCLUDE BUT ARE NOT LIMITED TO SHELL SPACES, UTILITY ROOMS, EQUIPMENT ROOMS, ETC.
12"x12" 401-500
(3) PROVIDE PVC JACKET FOR FITTINGS AND ELBOWS. PROVIDE REMOVABLE JACKETS ON VALVES AND CONTROL DEVICES.
- -
(4) WHERE MORE THAN ONE TYPE IS LISTED, THE CONTRACTOR HAS THE OPTION OF UTILIZING ONE OR A COMBINATION OF THE TYPES LISTED. USE OF MULTIPLE TYPES WITHIN THE SAME SYSTEM SHALL BE APPROVED BY THE ENGINEER.
6"x6" 0-195 FESSION
PRESSURE SEAL SYSTEM BASED ON VIEGA PROPRESS. OTHER SYSTEMS WILL BE CONSIDERED THROUGH THE APPROVAL PROCESS. PRO
8"x8" 196-290 AL
DUCTED TITUS PAR GROOVED MECHANICAL-JOINT SYSTEM BASED ON VICTAULIC AGS. OTHER SYSTEMS WILL BE CONSIDERED THROUGH THE APPROVAL PROCESS. ED . NO.
REG

ER

EN
G-3 PERFORATED 0.1 STEEL WHITE 12"x12" - - KRUEGER 6490 (1)(2)(3) (5) FOR PIPE CONNECTIONS REQUIRING HOT WORK, CONTRACTOR SHALL FOLLOW OWNER'S HOT WORK PROCEDURES AND PROVIDE ALL NECESSARY EQUIPMENT AND PERSONNEL REQUIRED.

REGIST

GINEE
RETURN GRILLE - - PRICE PFR 10229
- - ERIC G.

R
SHERMAN

A
S

T
O
U O
REMARKS T H
D A
K

(1) COORDINATE EXACT MODEL AND FRAME WITH CEILING/WALL TYPE.


(2) PROVIDE REMOTE DAMPER ACTUATION IN HARD CEILINGS.
(3) PROVIDE BLACKOUT PANELS ON TRANSFER GRILLES. 11/25/14

No. Description Date


VARIABLE FREQUENCY
DRIVE SCHEDULE
FAN SCHEDULE ELECTRICAL DATA
ELECTRICAL DATA MARK SERVES CONNECTED REMARKS
MAX. WEIGHT AIR FLOW TOTAL S.P. MAX. FAN MAX. FAN VOLTS/PHASE
MARK TYPE MANUFACTURER MODEL REMARKS MOTOR HP
[LBS.] [CFM] [IN.W.C.] RPM BHP
HP VOLTS/PHASE
VFD-SF-10A SF-10A 480/3 20 (1)
EF-1 UPBLAST 110 1000 0.75 1504 0.25 1/2 115/1 TWIN CITY DCRU-110BE (1)(2)(3)(4)(5)
VFD-SF-10B SF-10B 480/3 20 (1)
EF-2 UPBLAST 114 1400 1.00 1539 0.43 3/4 115/1 TWIN CITY DCRU-120BE (1)(2)(3)(4)(5)
VFD-RF-10A RF-10A 480/3 10 (1)
REMARKS
VFD-RF-10B RF-10B 480/3 10 (1)
(1) PROVIDE DISCONNECT.
(2) PROVIDE ECM MOTOR WITH SPEED CONTROLLER.
(3) PROVIDE AUTOMATIC BACKDRAFT DAMPER INTERLOCKED WITH MOTOR. REMARKS
(4) PROVIDE BIRDSCREEN. (1) REMOVE FACTORY PROVIDED VFD AND CONNECT NEW VFDS. REFER TO
(5) PROVIDE VIBRATION ISOLATION. ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. PATCH ALL CASING
PENETRATIONS. PROVIDE NEW UNISTRUT STAND FOR NEW VFDS. STAND
SHALL BE SUPPORTED FROM THE FLOOR.

RADIANT PANEL SCHEDULE


MAX.
SIZE BTU PER FLOW RATE NUMBER OF MEAN WATER
MARK PRESSURE MANUFACTURER MODEL REMARKS
[IN] LINEAL FT. [GPM] TUBES TEMP. [DEG F]
DROP [FT]
RAD-1 24 x 48 375 2 4 3 170 AIRTEX HPH (1)(2)(3)(4)
RAD-2 24 x 48 375 2 4 3 170 AIRTEX HPH (1)(2)(3)(4)
SACRED HEART
RAD-3 24 x 48 375 2 4 3 170 AIRTEX HPH (1)(2)(3)(4)

REMARKS
4TH & 5TH
(1) COORDINATE PANEL WITH CEILING SYSTEM.
(2) INSULATE BACK OF RADIANT PANEL. 2014 C COPYRIGHT MECHANICAL
(3) PROVIDE TRIM RING IN HARD CEILINGS.
(4) COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER STANDARD FINSIHES.
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEDULES
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:37 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M600
www.specializedeng.com Scale NONE
PLUMBING FIXTURE SCHEDULE HYDRONIC VARIABLE VOLUME BOX SCHEDULE
LEAVING AIR TEMP. NUMBER
PIPING CONNECTIONS
MARK TYPE DESCRIPTION ENTERING OF
COLD WATER HOT WATER WASTE VENT SUPPLY BOX WATER COIL HEATING
WATER HAMMER ARRESTERS - PROVIDE BELLOWS OR PISTON TYPE WATER HAMMER MARK AIR FLOW INLET COOLING HEATING TEMP FLOW ROWS MANUFACTURER MODEL REMARKS
ARRESTERS AT EACH FIXTURE GROUP. SIZE AND INSTALL IN ACCORDANCE WITH VB-3-1 1500 CFM 12" 55 °F 55 °F 0 °F 0.0 GPM 0 Krueger LMHS-12 (1)(2)(3)(4)
AVERA FACILITY DEVELOPMENT
MANUFACTURER'S RECOMMENDATIONS AND PDI STANDARD WH 201. INSTALL IN AN PDI# / SFU PDI# / SFU VB-4-1 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
ACCESSIBLE LOCATION AND PROVIDE ACCESS DOOR IN CEILING AND/OR WALL WHERE
REQUIRED FOR PROPER ACCESS. AA / 1-3 AA / 1-3 VB-4-2 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
A / 1-11 A / 1-11 VB-4-3 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
NONE PRE-CHARGED, BELLOWS TYPE, ALL STAINLESS STEEL CONSTRUCTION, ASSE 1010 B / 12-32 B / 12-32 - - VB-4-4 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
APPROVED, PDI CERTIFIED. C / 33-60 C / 33-60 VB-4-5 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
WATER D / 61-113 D / 61-113
HAMMER PRE-CHARGED WITH 60 PSIG AIR, COPPER BODY, BRASS OR HIGH HEAT POLY- E / 114-154 E / 114-154 VB-4-6 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
ARRESTER PROPYLENE PISTON WITH DUAL EDPM O-RING SEALS LUBRICATED WITH FDA APPROVED F / 155-330 F / 155-330 VB-4-7 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
SILICONE LUBRICANT. PDI CERTIFIED, A.S.S.E. 1010 APPROVED FOR SEALED WALL VB-4-8 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
INSTALLATION. VB-4-9 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-4-10 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
FLOOR DRAIN - 3.75" WIDE BY 60" LONG STAINLESS STEEL CHANNEL DRAIN WITH VB-4-11 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
FD-1 MEMBRANE CLAMP, 2" BOTTOM OUTLET, FRAMELESS TILEABLE GRATE ASSEMBLY. - - 2" 1-1/2" VB-4-12 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
SCHLUTER KERDI-LINE KLV 60 E 150 WITH KLDRE 150 OR APPROVED EQUAL. VB-4-13 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
SHOWER DRAIN
VB-4-14 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-4-15 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
FLOOR DRAIN - 3.75" WIDE BY 36" LONG STAINLESS STEEL CHANNEL DRAIN WITH VB-4-16 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
FD-2 MEMBRANE CLAMP, 2" BOTTOM OUTLET, FRAMELESS TILEABLE GRATE ASSEMBLY. - - 2" 1-1/2"
VB-4-18 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
SCHLUTER KERDI-LINE KLV 60 E 90 WITH KLDRE 90 OR APPROVED EQUAL.
SHOWER DRAIN VB-4-19 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-4-20 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-4-21 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BOWL - SINGLE COMPARTMENT SINK INTEGRAL TO COUNTERTOP BY ARCHITECT. VB-4-22 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-4-23 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
TRIM - TWO HANDLE MIXING FAUCET, CHROME PLATED, SWING
GOOSENECK SPOUT WITH 5" REACH AND PRESSURE COMPENSATING LAMINAR FLOW VB-4-24 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BOWL OUTLET IN FAUCET BASE, WITHOUT INLET SCREEN, 4" WRIST BLADE HANDLES AT 4" VB-4-25 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
L-1 CENTERS, PERFORATED DRAIN GRATE WITH 1-1/2" 17 GAUGE TAILPIECE, CHROME 1/2" 1/2" 1-1/2" 1-1/4" VB-4-26 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
PLATED CAST BRASS "P" TRAP WITH CLEANOUT, 3/8" CHROME PLATED HEAVY BRASS VB-4-27 200 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
ANGLE SUPPLIES AND LOOSE KEY STOPS WITH CHROME PLATED SOFT COPPER RISERS.
MAXIMUM FLOW TO BE 1.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND VB-4-28 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
ASME/ANSI STANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOEN VB-4-29 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
MODEL 8279SM WITH 52652 INSERT OR APPROVED EQUAL. VB-4-30 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-4-31 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
TRIM VB-4-32 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BOWL - WALL MOUNTED, WHITE VITREOUS CHINA, 4" HIGH CONTOURED BACKSPLASH, 20" X VB-4-33 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
18", 4" CENTERS, DRILLED FOR CONCEALED ARM CARRIER. FURNISH SUPPORT CARRIER VB-4-34 550 CFM 6" 55 °F 110 °F 180 °F 3.3 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BOLTED SECURELY TO FLOOR. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO VB-5-1 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BOTTOM OF APRON IN COMPLIANCE WITH ANSI A117.1-1986 AND ADA SECTION 4.19. TOP OF VB-5-2 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BASIN RIM TO BE MAXIMUM OF 34" ABOVE FLOOR IN COMPLIANCE WITH ADA SECTION 4.19.
PROVIDE OFFSET DRAIN AND TAILPIECE. PRE-MANUFACTURED P-TRAP, STOP VALVE AND VB-5-3 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BOWL SUPPLY LINE INSULATION KIT. AMERICAN STANDARD MODEL 0355.012 OR APPROVED EQUAL. VB-5-4 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-5-5 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
L-2 TRIM - TWO HANDLE MIXING FAUCET, CHROME PLATED, SWING 1/2" 1/2" 1-1/2" 1-1/4" VB-5-6 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
GOOSENECK SPOUT WITH 5" REACH AND PRESSURE COMPENSATING LAMINAR FLOW
VB-5-7 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
OUTLET IN FAUCET BASE, WITHOUT INLET SCREEN, 4" WRIST BLADE HANDLES AT 4"
CENTERS, PERFORATED DRAIN GRATE WITH 1-1/2" 17 GAUGE TAILPIECE, CHROME PLATED VB-5-8 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
CAST BRASS "P" TRAP WITH CLEANOUT, 3/8" CHROME PLATED HEAVY BRASS ANGLE VB-5-9 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
SUPPLIES AND LOOSE KEY STOPS WITH CHROME PLATED SOFT COPPER RISERS. MAXIMUM VB-5-10 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
FLOW TO BE 1.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI VB-5-11 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
TRIM STANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOEN MODEL 8279SM
WITH 52652 INSERT OR APPROVED EQUAL. VB-5-12 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
ENCLOSURE - BY ARCHITECT. VB-5-13 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-5-14 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
TRIM - SINGLE HANDLE COMBINATION PRESSURE BALANCED AND THERMOSTATIC VB-5-15 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
MIXING FAUCET, BRASS OR BRONZE CONSTRUCTION, WASHERLESS DESIGN, OFF- VB-5-16 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
COLDHOT TEMPERATURE RANGE INDICATOR DIAL, POLISHED CHROME CAST METAL
VB-5-17 350 CFM 6" 55 °F 110 °F 180 °F 2.1 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
LEVER HANDLE, INTEGRAL CHECK STOPS, ADJUSTABLE TEMPERATURE LIMIT STOP SET
TO 110 DEGREE F DISCHARGE. ASSE 1016 LISTED. INSTALL ALL CONTROLS BETWEEN VB-5-18 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
38" AND 48" ABOVE FINISHED FLOOR IN COMPLIANCE WITH ADA. VB-5-19 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
SH-1 3/4" 3/4" - - VB-5-20 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
ACCESSORIES - ADJUSTABLE SPRAY HAND HELD SHOWER, CHROME PLATED 36" VB-5-21 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
MOUNTING RAIL, SWIVEL CONNECTOR, 60" CHROME PLATED METAL HOSE, CHROME
PLATED BRASS SUPPLY ELBOW WITH FLANGE, CHROME PLATED ELEVATED VACUUM VB-5-22 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
BREAKER WITH CHROME PLATED PIPING AND FLANGES. MAXIMUM FLOW TO BE 1.5 GPM VB-5-23 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI STANDARD VB-5-24 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
TRIM A112.18.1M. VB-5-25 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
VB-5-26 300 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
LAWLER MODEL M7800 SC1-RB HS3 EVB OR APPROVED EQUAL.
VB-5-27 200 CFM 6" 55 °F 110 °F 180 °F 1.8 GPM 2 Krueger LMHS-06 (1)(2)(3)(4) FESSION
PRO AL
ACCESSIBLE WATER CLOSET - FLOOR MOUNTED, REAR DISCHARGE FLUSH VALVE TYPE,
VB-5-28 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4) ED . NO.
REG

ER

EN
WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP VB-5-29 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)

REGIST

GINEE
SPUD, BEDPAN LUGS BOLT CAPS. TOP OF SEAT AT 17" TO 19" ABOVE FINISHED FLOOR. VB-5-30 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4) 10229
INTERFACE WITH FLOOR AND WALL SHALL FORM A STRAIGHT EDGE FOR EASY CLEANING. VB-5-31 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4) ERIC G.

R
AMERICAN STANDARD MODEL 3313.001 OR APPROVED EQUAL. SHERMAN
VB-5-32 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)

A
S

T
O
U O
T H K
SEAT - WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID PLASTIC SEAT WITH VB-5-33 200 CFM 6" 55 °F 110 °F 180 °F 1.2 GPM 2 Krueger LMHS-06 (1)(2)(3)(4) D A

CHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS AND VB-5-34 550 CFM 6" 55 °F 110 °F 180 °F 3.3 GPM 2 Krueger LMHS-06 (1)(2)(3)(4)
WATER CLOSET ANTIMICROBIAL COATING. BEMIS MODEL 2155C OR APPROVED EQUAL.
WC-1 1" - 3" 1-1/2" 11/25/14
FLUSH VALVE - EXPOSED, CHROME PLATED 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE, REMARKS
CHEMICAL RESISTANT MATERIAL, VACUUM BREAKER, WALL AND SPUD FLANGES, BED PAN
WASHER DIVERTER, 1.6 GALLONS PER FLUSH. 3 YEAR WARRANTY. FLUSH HANDLE SHALL (1) MAXIMUM FULL FLOW AIR PRESSURE DROP ACROSS THE BOX ASSEMBLY INCLUDING HEATING COIL SHALL BE 0.75 IN. W.C. No. Description Date
BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND SHALL BE 12" MAXIMUM (2) MAXIMUM FULL FLOW WATER PRESSURE DROP THROUGH THE COIL SHALL BE 5 FT.
ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB FORCE, IN COMPLIANCE (3) MAXIMUM RADIATED SOUND LEVEL BASED ON ARI 880-98 AT 1.0 IN.W.C. DIFFERENTIAL PRESSURE SHALL NOT EXCEED NC 30.
WITH ADA SECTION 4.16.5 AND 4.27.4. CONTRACTOR TO VERIFY EQUIPMENT
REQUIREMENTS AND ROUGH-IN LOCATIONS. SLOAN MODEL BPW-1150 OR APPROVED (4) MAXIMUM DISCHARGE SOUND LEVEL BASED ON ARI 880-98 AT 1.0 IN.W.C. DIFFERENTIAL PRESSURE SHALL NOT EXCEED NC 25.
FLUSH VALVE EQUAL.

ACCESSIBLE WATER CLOSET - FLOOR MOUNTED, BOTTOM DISCHARGE FLUSH VALVE


TYPE, WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-
1/2" TOP SPUD, BEDPAN LUGS BOLT CAPS. TOP OF SEAT AT 17" TO 19" ABOVE
FINISHED FLOOR. INTERFACE WITH FLOOR AND WALL SHALL FORM A STRAIGHT EDGE
FOR EASY CLEANING. AMERICAN STANDARD MODEL 3043.001 OR APPROVED EQUAL.

SEAT - WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID PLASTIC SEAT
WITH CHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS AND
WATER CLOSET
ANTIMICROBIAL COATING. BEMIS MODEL 2155C OR APPROVED EQUAL.
WC-2 1" - 3" 1-1/2"
FLUSH VALVE - EXPOSED, CHROME PLATED 1" I.P.S. SCREWDRIVER STOP-CHECK
VALVE, CHEMICAL RESISTANT MATERIAL, VACUUM BREAKER, WALL AND SPUD
FLANGES, BED PAN WASHER DIVERTER, 1.6 GALLONS PER FLUSH. 3 YEAR WARRANTY.
FLUSH HANDLE SHALL BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND
SHALL BE 12" MAXIMUM ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB
FORCE, IN COMPLIANCE WITH ADA SECTION 4.16.5 AND 4.27.4. CONTRACTOR TO
VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS. SLOAN MODEL BPW-
FLUSH VALVE 1150 OR APPROVED EQUAL.

SACRED HEART
4TH & 5TH
2014 C COPYRIGHT MECHANICAL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEDULES
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:40 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M601
www.specializedeng.com Scale NONE
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

A1
B
B.0

1.7 2.1
2
M991

HX-CW1

B1.1

C
MODIFY EXISTING FAN COIL CHANGE
OVER PANEL TO REFLECT REMOVAL
OF 4TH AND 5TH FLOOR SYSTEMS.

C1

FESSION
PRO AL
ED . NO.
REG

ER

EN
REGIST

GINEE
10229
ERIC G.

R
SHERMAN

A
S

T
D1

O
U O
T H K
D A

11/25/14
AHU-10
E No. Description Date
1
M990

E1

F
F1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
THIRD LEVEL- CONTROLS
1 1/8" = 1'-0"
2014 C COPYRIGHT THIRD LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE CONTROLS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:42 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M931
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

ELEVATOR LINK
4900

PHASE 4
SHEET NOTES
A1 1 REPLACE EXISTING THERMOSTAT.

B
B.0
1

T
VB-4-27 RAD-1
1 RESTROOM
M991 418
OFFICE T
462 1 1 1 1 1 1 1 1 1
1.7 2.1 PATIENT RM M991 M991 PATIENT RM PATIENT RM M991 M991 PATIENT RM M991 PATIENT RM PATIENT RM M991 M991 PATIENT RM PATIENT RM M991 M991 PATIENT RM
3 2
NEGATIVE AIR
420
T 400 VB-4-26 VB-4-25 402 404 VB-4-24 VB-4-23 406 VB-4-22 408 410 VB-4-21 VB-4-20 412 414 VB-4-19 VB-4-18 416 M992
1 M991

B1.1 T T
1

T
1 VB-4-16
1 PATIENT RM
VB-4-28 422
M991
OFFICE
460 1
1
M991
MECH

C
459
RESTROOM
1 421

M991
VB-4-29 VB-4-15
C1 1
1 ELEC M991 1
T 534 T
HSKG CLEAN UTILITY DIRTY UTILITY
T 1 536 OFFICE 550 549 1 T
1 PATIENT RM 1
537 TOILET
M991 M991 424
TOILET 548
535 VB-4-14

VB-4-30

RESTROOM

D
PHASE 3 455 STORAGE PHASE 2
DIET
539 544
CONFERENCE LOCKER ROOM
1
546 547
1 M991

M991 WAITING ROOM VB-4-13


538
VB-4-31
1 FESSION
1 PRO
T T AL
EQUIPMENT CLEAN UTILITY ED . NO.
REG

ER

EN
540 541

REGIST
SOILED

GINEE
NUTRITION OMNI CELL
T 10229
542 543 545 T
1 1 ERIC G.

R
SHERMAN

A
VB-4-32

T
D1

O
U O
T H K
D A
1 VB-4-12
M991
1 11/25/14
M991
E No. Description Date

1
1
M991
M991
VB-4-33
VB-4-11
T

T
T

T
1 1
T
T

ANTERIOR RM
E1 T
450
T

T VB-4-1 VB-4-2 VB-4-3 VB-4-4 VB-4-5 VB-4-6 VB-4-7 VB-4-8 VB-4-9 T


VB-4-34 1
1
1 1 PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM
448
1 1 446 444
1 1 442
1 440 438
1 1 436 434
1 1 432 M991
M992
RESTROOM M991 M991 M991 M991 M991 M991 M991 M991 M991 VB-4-10
T 3
451
M991 RESTROOM
STORAGE 429
431 RAD-2

F
F1
PHASE 1

99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FOURTH LEVEL - CONTROLS
1 1/8" = 1'-0"
2014 C COPYRIGHT FOURTH LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE CONTROLS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:45 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M941
www.specializedeng.com Scale 1/8" = 1'-0"
1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

GENERAL NOTES
A A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL
REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING
ELEVATION REQUIREMENTS.

ELEVATOR LINK
5900

PHASE 4 SHEET NOTES


A1 1 REPLACE EXISTING THERMOSTAT.

B
B.0 1
M991 1

T
VB-5-27
1 1 1 1 1 1 1 3
OFFICE 1 1 NEGATIVE
EF-1 AIR
M992
1.7 2.1
5902 M991 M991 M991 M991 M991 M991 M991 520
M991 M991
PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM
2 ON ROOF
VB-5-26 VB-5-22 508 VB-5-21 VB-5-20 512
1 T 500 VB-5-25 502 504 VB-5-24 VB-5-23 506 510 514 VB-5-19 VB-5-18 516 M992
VB-5-17

B1.1 1
SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER

T
T
T
T

T
T
M991 VB-5-16 1
RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM
501 503 505 507 509 511 513 515 517 M991

VB-5-28
SHOWERSHOWER

SHOWERSHOWER

T
1
T

MECH.

C
565

1
1
T

T
M991

C1 VB-5-29 1
VB-5-15 M991
ELEC
551

HSKG
552 EQUIPMENT
553 VB-5-14
VB-5-30 1
1
M991
M991
SHOWERSHOWER

SHOWERSHOWER
1
T

T
D
PHASE 3 PHASE 2

1 1

T
T

SOILED UTILITY
CLEAN UTILITY 559
1 558 1
M991 VB-5-31 M991
VB-5-13
FESSION
PRO AL
ED . NO.
REG

ER
NUTRITION SOILED UTILITY STORAGE

EN
STOREROOM

REGIST

GINEE
557 556 555 554 10229
1
ERIC G.

R
M991
1 VB-5-32 SHERMAN

A
S

T
D1

O
U O
M991 VB-5-12 T H
D A
K

1
SHOWERSHOWER
T

SHOWERSHOWER

T
11/25/14
CORRIDOR
5901
E No. Description Date

T
1
T

RESTROOM RESTROOM RESTROOM


1 547 545 543 VB-5-11
M991 RESTROOM RESTROOM RESTROOM RESTROOM
VB-5-33 1
541 539 537 535
T

T
T

T
E1 M991
SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER SHOWER

VB-5-34 1 VB-5-1 T
VB-5-2 VB-5-3 VB-5-4 VB-5-5 VB-5-6 VB-5-7 VB-5-8 VB-5-9
3 M992 PATIENT RM 1
PATIENT RM PATIENT RM PATIENT RM PATIENT RM 542 PATIENT RM PATIENT RM PATIENT RM PATIENT RM
1 1
M992 550 548 546 1 1 544 1 540 1 1 538 536 1 1 534
EF-2 1
ON ROOF ISOLATION M991 M991 M991 M991 M991 M991 M991 M991 M991

T
M991
554
VB-5-10
T

1
RAD-3

F
3
F1 M991
PHASE 1

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
SACRED HEART
4TH & 5TH
FIFTH LEVEL - CONTROLS
1 1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE CONTROLS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:48 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M951
www.specializedeng.com Scale 1/8" = 1'-0"
42 12 13 RELIEF AIR 44

CO2 ACTUATOR CO2


BLENDER
H C
AVERA FACILITY DEVELOPMENT
RETURN SUPPLY
RETURN FAN FAN
AIR

DP SMOKE SMOKE DP
DETECTOR ACTUATOR MOTOR ACTUATOR MOTOR ACTUATOR DETECTOR
C C
01 41
DP VFD CO2 43 DP VFD DP DP

HWR

CWR
HWS

CWS

LPS
02 03 04 06 07 08 09 10 11 16 17 18 19 20 21 24 25 29 30 31 32 33 34 35 36 37 39 40
05 14 38
ACTUATOR 22 26 28
15
23 27
OUTDOOR AIR

SEQUENCE OF OPERATION

DIRECT DIGITAL CONTROL POINTS LIST DESCRIPTION: THE AIR HANDLING UNIT IS A VARIABLE AIR VOLUME UNIT AND CONSISTS OF A SUPPLY FAN WITH VFD, RETURN FAN WITH VFD, OUTDOOR AIR DAMPER, RETURN AIR DAMPER, RELIEF AIR DAMPER, BLENDER, PRE-FILTER BANK, HOT
WATER HEATING COIL, CHILLED WATER COOLING COIL, STEAM HUMIDIFIER, FINAL FILTER BANK AND UNIT ISOLATION DAMPERS.
POINT SOURCE TYPE I/O SETPOINT ALARMS APPLICATIONS SUPPLY FAN CONTROL: START/STOP: THE DDC SYSTEM SHALL START THE SUPPLY FAN VIA THE VFD WITH A TIME DELAY TO ALLOW ALL FIRE/SMOKE AND SMOKE DAMPERS IN THE AIR HANDLING SYSTEM TO OPEN PRIOR TO SUPPLY FAN OPERATION.
POINT DESCRIPTION UNITS
ID (1) (2) (3) ADJUSTMENT (4) (5)
VFD RESET: IN CASE OF VFD FAULT DETECTION, THE DDC SYSTEM SHALL WAIT 30 SECONDS (ADJUSTABLE) AND THEN CALL THE VFD TO START. IF THE VFD DOES NOT START, THE DDC SYSTEM SHALL CALL A SECOND TIME. IF THE
INCHES VFD STILL HAS NOT STARTED, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE.
01 RETURN DUCT DIFFERENTIAL STATIC PRESSURE E A I YES - T, A, G
W.C.
CURRENT STATUS SWITCH: IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION IN VFD OR BYPASS MODE, THE UNIT SHALL SHUT DOWN AND SEND AN ALARM TO THE OPERATOR INTERFACE.
02 AHU RETURN AIR ISOLATION DAMPER POSITION E B I NO - E, A, G OPEN/CLOSED
SPEED CONTROL: THE PURPOSE OF THE SUPPLY FAN CONTROL IS TO MAINTAIN A MINIMUM STATIC PRESSURE IN THE SUPPLY DUCTWORK TO INSURE PROPER TERMINAL AIR BOX OPERATION. THE DDC SYSTEM SHALL CONTROL THE
03 RETURN AIR TEMPERATURE E A I NO - T, A, G DEGREES F SUPPLY FAN VFD FROM THE SUPPLY DUCT DIFFERENTIAL PRESSURE TRANSMITTER SIGNAL. INITIAL SETPOINT SHALL BE +1.0" W.C. (ADJUSTABLE). FINAL SETPOINT SHALL BE OPTIMIZED BY THE BALANCING CONTRACTOR. ON A
% RELATIVE DECREASE IN SYSTEM LOAD, THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET AND REDUCE THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE UNTIL ONE TERMINAL AIR BOX DAMPER IS
04 RETURN AIR HUMIDITY E A I NO - T, A, G 95% OPEN. ON AN INCREASE IN SYSTEM LOAD, THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO INCREASE THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE (NOT-TO-EXCEED THE FINAL
HUMIDITY
SETPOINT) UNTIL ONE TERMINAL AIR BOX DAMPER IS 95% OPEN.
% RELATIVE
05 RETURN AIR HUMIDITY SETPOINT E A O YES - T, A, G
HUMIDITY
HIGH PRESSURE LIMIT: DIFFERENTIAL PRESSURE SWITCH SHALL BE A MANUAL RESET TYPE AND WIRED IN SERIES WITH THE START/STOP CONTROL OF THE SUPPLY FAN. THE DDC SYSTEM SHALL MONITOR THE STATUS OF THE
06 RETURN FAN SUCTION STATIC PRESSURE SWITCH E B I YES C, H E, A, G INCHES W.C. DIFFERENTIAL PRESSURE SWITCH. INITIAL SETPOINT SHALL BE +3.0" W.C. (ADJUSTABLE).

07 RETURN FAN VFD STATUS E B I NO G, F E, A - RETURN FAN CONTROL: START/STOP: THE DDC SYSTEM SHALL START THE RETURN FAN VIA THE VFD WITH A TIME DELAY TO ALLOW ALL FIRE/SMOKE AND SMOKE DAMPERS IN THE AIR HANDLING SYSTEM TO OPEN PRIOR TO RETURN FAN OPERATION.

VFD RESET: IN CASE OF VFD FAULT DETECTION, THE DDC SYSTEM SHALL WAIT 30 SECONDS (ADJUSTABLE.) AND THEN CALL THE VFD TO START. IF THE VFD DOES NOT START, THE DDC SYSTEM SHALL CALL A SECOND TIME. IF THE
08 RETURN FAN VFD START/STOP E B 0 NO - - -
VFD STILL HAS NOT STARTED, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE.
09 RETURN FAN VFD SPEED CONTROL E A O YES - T, A, G % SPEED CURRENT STATUS SWITCH: IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION IN VFD OR BYPASS MODE, THE UNIT SHALL SHUT DOWN AND SEND AN ALARM TO THE OPERATOR INTERFACE.

10 RETURN FAN CURRENT STATUS SWITCH E B I NO G, F E, A, G ON/OFF SPEED CONTROL: THE PURPOSE OF THE RETURN FAN CONTROL IS TO MAINTAIN A SLIGHTLY POSITIVE BUILDING PRESSURE, +0.05 W.C. (ADJUSTABLE). THE RETURN FAN VFD SHALL MODULATE TO MAINTAIN A CONSTANT CFM OFFSET
FROM THE SUPPLY FAN BASED ON AIRFLOW MEASUREMENT TO ACCOUNT FOR TOTAL EXHAUST FROM THE BUILDING WHILE MAINTAINING A SLIGHTLY POSITIVE PRESSURE. IN THE EVENT OF A SENSOR FAILURE, PROVIDE AN
11 RETURN FAN AIRFLOW VOLUME E A I NO - T, A, G CFM ADJUSTABLE FREQUENCY OFFSET ALGORITHM FOR THE RETURN FAN RELATIVE TO THE SUPPLY FAN. WORK WITH THE BALANCER TO ESTABLISH THE CORRECT RETURN FAN VFD SPEED RELATIVE TO THE SUPPLY FAN SPEED TO
ACHIEVE CORRECT AIRFLOW BALANCE AT 100% OF THE MAXIMUM SUPPLY CFM AND AT 50% OF THE MAXIMUM SUPPLY CFM. A LINEAR EQUATION SHALL THEN BE DEVELOPED FOR THE RETURN FAN SPEED.
12 RELIEF AIR DAMPER ACTUATOR E A O NO - - -
LOW PRESSURE LIMIT: DIFFERENTIAL PRESSURE SWITCH SHALL BE A MANUAL RESET TYPE AND WIRED IN SERIES WITH THE START/STOP CONTROL OF THE RETURN FAN. INITIAL SETPOINT SHALL BE -2.0" W.C. (ADJUSTABLE).
13 RELIEF AIR DAMPER POSITION E A I NO - T, A, G % OPEN
DISCHARGE AIR CONTROL: DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE 55ºF (ADJUSTABLE).
14 OUTDOOR AIR DAMPER ACTUATOR E A O NO - - -
WHENEVER THE DISCHARGE AIR TEMPERATURE IS ABOVE THE SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE:
1. THE HEATING COIL CONTROL VALVE(S) SHALL MODULATE CLOSED.
15 OUTDOOR AIR DAMPER POSITION E A I NO - T, A, G % OPEN 2. IF THE OUTSIDE AIR ENTHALPY IS BELOW THE RETURN AIR ENTHALPY, THE OUTSIDE AIR DAMPER SHALL MODULATE
OPEN. THIS SHALL CONTINUE UNTIL THE SETPOINT IS ACHIEVED OR THE DAMPER IS IN THE 100% OUTSIDE AIR POSITION.
16 RETURN AIR DAMPER ACTUATOR E A O NO - - - 3. IF THE OUTSIDE AIR ENTHALPY IS ABOVE THE RETURN AIR ENTHALPY, THE OUTSIDE AIR DAMPER(S) SHALL CLOSE
TO THEIR MINIMUM OUTSIDE AIR POSITION(S).
17 RETURN AIR DAMPER POSITION E A I NO - T, A, G % OPEN 4. IF THE SETPOINT CANNOT BE ACHIEVED BY MODULATION OF THE OUTSIDE AIR DAMPER, THE DDC SYSTEM SHALL
MODULATE THE CHILLED WATER CONTROL VALVE(S) OPEN.
18 OUTDOOR AIRFLOW E A I NO - T, A, G CFM 5. IF THE SETPOINT CANNOT BE ACHIEVED BY MODULATION OF THE OUTSIDE AIR DAMPER, THE DDC SYSTEM SHALL ENABLE THE ASSOCIATED CONDENSING UNIT CONTROLS TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT.
6. IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 10ºF (ADJUSTABLE) ABOVE THE SETPOINT, SEND AN ALARM TO THE OPERATOR INTERFACE.
19 MIXED AIR TEMPERATURE E A I NO - T, A, G DEGREES F
WHENEVER THE DISCHARGE AIR TEMPERATURE IS BELOW THE SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE:
% RELATIVE 1. THE CHILLED WATER CONTROL VALVE(S) SHALL MODULATE CLOSED.
20 MIXED AIR HUMIDITY E A I NO - T, A, G
HUMIDITY 2. IF THE OUTSIDE AIR ENTHALPY IS BELOW THE RETURN AIR ENTHALPY, THE OUTSIDE AIR DAMPER SHALL MODULATE
INCHES CLOSED. THIS SHALL CONTINUE UNTIL THE SETPOINT IS ACHIEVED OR THE DAMPER IS IN THE MINIMUM OUTSIDE AIR POSITION.
21 PRE-FILTER DIFFERENTIAL PRESSURE E A I YES G, H T, E, A, G 3. IF THE SETPOINT CANNOT BE ACHIEVED BY DAMPER MODULATION, THE HEATING COIL CONTROL VALVE SHALL
W.C.
MODULATE OPEN TO MAINTAIN SETPOINT.
FESSION
22 HEATING WATER COIL CONTROL VALVE E A O NO - - - 4. IF THE SETPOINT CANNOT BE ACHIEVED BY DAMPER MODULATION, THE HEATING COIL CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN SETPOINT. THE HEATING COIL PUMP SHALL START ON A CALL FOR HEAT IF THE OUTDOOR PRO AL
AIR REFERENCE TEMPERATURE IS BELOW 40° F (ADJUSTABLE). IF THE CURRENT STATUS SWITCH ON THE PUMP DOES NOT PROVE OPERATION, SEND AN ALARM TO THE OPERATOR INTERFACE. ED . NO.
REG

ER

EN
23 HEATING WATER TEMPERATURE - RETURN E A I NO - T, A, G DEGREES F 5. IF THE SETPOINT CANNOT BE ACHIEVED BY DAMPER MODULATION, THE HEATING COIL CONTROL VALVE SHALL BE FULLY OPEN AND THE FACE AND BYPASS DAMPERS SHALL MODULATE TO MAINTAIN SETPOINT.

REGIST

GINEE
6. IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 10ºF (ADJUSTABLE) BELOW THE SETPOINT, SEND AN ALARM TO THE OPERATOR INTERFACE. 10229
24 HEATING COIL DISCHARGE AIR TEMPERATURE E A I NO G, H, L T, A, G DEGREES F ERIC G.

R
HUMIDIFIER CONTROL: THE RETURN AIR RELATIVE HUMIDITY SETPOINT SHALL BE 30% (ADJUSTABLE). THE HUMIDIFIER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE RETURN AIR RELATIVE HUMIDITY SETPOINT. THE DDC SYSTEM SHERMAN

A
S

T
SHALL OVERRIDE THE SIGNAL TO THE HUMIDIFIER CONTROL VALVE TO LIMIT THE SUPPLY AIR RELATIVE HUMIDITY TO A MAXIMUM OF 70% (ADJUSTABLE). IF THE SUPPLY AIR RELATIVE HUMIDITY EXCEEDS 75% (ADJUSTABLE) AN ALARM

O
U O
25 FREEZESTAT ALARM E B I NO F E, A, G NORMAL/ALARM T H
D A
K
SHALL BE SENT TO THE OPERATOR INTERFACE. WHENEVER THE OUTDOOR AIR DRY BULB REFERENCE TEMPERATURE IS ABOVE 40ºF (ADJUSTABLE), THE DDC SYSTEM SHALL CLOSE THE HUMIDIFIER CONTROL VALVE AND DISABLE THE
ALARM.
26 CHILLED WATER COIL CONTROL VALVE E A O NO - - -
VENTILATION AIR CONTROL: MINIMUM OUTSIDE AIR: WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE OPEN TO AT LEAST ITS MINIMUM POSITION. 11/25/14
27 CHILLED WATER TEMPERATURE - RETURN E A I NO - T, A, G DEGREES F
MIXED AIR TEMPERATURE: MONITOR THE MIXED AIR TEMPERATURE.
28 HUMIDIFIER CONTROL VALVE E A O NO - - - No. Description Date
AIRFLOW STATION: THE RETURN AIR DAMPER AND THE RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAIN THE MINIMUM SCHEDULED OUTSIDE AIR CFM.
29 HUMIDITY HIGH LIMIT ALARM E B I NO F E, A, G -
CARBON DIOXIDE: THE OUTSIDE AIR DAMPER SHALL HAVE A MINIMUM POSITION THAT CORRESPONDS TO 5% (ADJUSTABLE) OF FULL AIRFLOW. THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN A RETURN AIR CARBON DIOXIDE
30 SUPPLY FAN VFD STATUS E B I NO G, F E, A - LEVEL OF 700 PPM (ADJUSTABLE) ABOVE THE OUTSIDE AIR REFERENCE CARBON DIOXIDE LEVEL. THE MIXED AIR TEMPERATURE SHALL NOT BE ALLOWED TO FALL BELOW 40° F (ADJUSTABLE). AN ALARM SHALL BE SENT TO THE
OPERATOR INTERFACE IF THE RETURN AIR CARBON DIOXIDE LEVEL EXCEEDS 1800 PPM. THE RETURN AIR DAMPER SHALL MODULATE IN OPPOSITION TO THE OUTSIDE AIR DAMPER AND THE RELIEF AIR DAMPER SHALL MODULATE IN
31 SUPPLY FAN VFD START/STOP E B 0 NO - - - UNISON WITH THE OUTSIDE AIR DAMPER. THE OUTSIDE AIRFLOW QUANTITY SHALL BE THE MAXIMUM OF THE DISCHARGE AIR CONTROL OR CARBON DIOXIDE CONTROL.

UNIT SHUTDOWN: THE SUPPLY, AND RETURN, AND RELIEF FANS SHALL STOP.
32 SUPPLY FAN VFD SPEED CONTROL E A O YES - T, A, G % SPEED
THE OUTSIDE AIR DAMPERS AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN DAMPERS SHALL OPEN.
THE CHILLED WATER CONTROL VALVE(S) SHALL CLOSE. THE ASSOCIATED CONDENSING UNIT SHALL BE DISABLED.
33 SUPPLY FAN CURRENT STATUS SWITCH E B I NO G, F E, A ON/OFF THE HUMIDIFIER CONTROL VALVE AND THE HUMIDIFIER SHUT-OFF VALVE SHALL CLOSE.
THE HEATING COIL CONTROL VALVE(S) SHALL CLOSE. FREEZESTAT SHALL OVERRIDE HEATING CONTROL VALVE(S) AS REQUIRED.
34 SUPPLY FAN AIRFLOW VOLUME E A I NO - T, A, G CFM ALL FIRE/SMOKE AND SMOKE DAMPERS ASSOCIATED WITH THE AIR HANDLING SYSTEM SHALL CLOSE.

35 SUPPLY FAN DISCHARGE STATIC PRESSURE SWITCH E B I YES C, H E, A, G INCHES W.C. UNOCCUPIED CONTROL: OCCUPIED/UNOCCUPIED SCHEDULE SHALL BE SET AT THE OPERATOR INTERFACE.
THE SUPPLY AND RETURN FANS SHALL SHUTDOWN. WHEN USING CONSTANT VOLUME OFFSET FOR RETURN AIR FAN CONTROL, THE OFFSET SHALL GO TO ZERO AND SUPPLY FAN SHALL BE LIMITED TO THE MAXIMUM RETURN FAN
36 FINAL FILTER DIFFERENTIAL PRESSURE E A I YES G, H T, E, A, G INCHES W.C. AIRFLOW.
THE MINIMUM OUTSIDE AIR, OUTSIDE AIR, AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION.
37 SUPPLY AIR TEMPERATURE E A I NO - T, A, G DEGREES F IF ANY OF THE SPACE TEMPERATURES FALL BELOW 60ºF (ADJUSTABLE), THE DDC SYSTEM SHALL RESTART THE SUPPLY AND RETURN FANS AND COOLING CAPABILITIES SHALL BE DISABLED. THE FANS SHALL CONTINUE RUNNING
UNTIL THE SPACE TEMPERATURE RISES 5ºF (ADJUSTABLE).
IF ANY OF THE SPACE TEMPERATURES RISE ABOVE 80ºF (ADJUSTABLE), THE DDC SYSTEM SHALL RESTART THE SUPPLY AND RETURN FANS AND MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. THE FANS SHALL CONTINUE
38 SUPPLY AIR TEMPERATURE SETPOINT E A O YES - T, A, G DEGREES F
RUNNING UNTIL THE SPACE TEMPERATURE FALLS 5ºF (ADJUSTABLE).
% RELATIVE
39 SUPPLY AIR HUMIDITY E A I NO - T, A, G HEATING OPTIMUM START-UP: THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC SYSTEM SHALL
HUMIDITY
MEASURE EACH OF THE SPACE TEMPERATURES AND THE OUTSIDE AIR DRY BULB REFERENCE TEMPERATURE TO DETERMINE THE MINIMUM RUN TIME TO WARM THE SPACES TO THEIR SETPOINT. WHEN THE COMPUTED START TIME IS
40 AHU SUPPLY AIR ISOLATION DAMPER POSITION E B I NO - E, A, G OPEN/CLOSED REACHED, THE DDC SYSTEM SHALL START THE AIR HANDLING SYSTEM AND OPERATE WITH THE OUTSIDE AIR AND RELIEF AIR DAMPERS CLOSED AND THE RETURN AIR DAMPER OPEN. THE AIR HANDLING UNIT DISCHARGE AIR
TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJUSTABLE). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 65ºF (ADJUSTABLE). AT THAT TIME, THE DDC
INCHES
41 SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE E A I YES - T, A, G SYSTEM SHALL SWITCH TO OCCUPIED CONTROL. THE VENTILATION AIR CONTROL SHALL BE INACTIVE.
W.C.
PARTS PER COOLING OPTIMUM START-UP: THE DDC SYSTEM SHALL MEASURE EACH OF THE SPACE TEMPERATURES AND THE OUTSIDE AIR DRY BULB REFERENCE TEMPERATURE TO DETERMINE THE MINIMUM RUN TIME TO COOL THE SPACES TO THEIR
42 CARBON DIOXIDE LEVEL - RETURN AIR E A I NO C, H T, A, G
MILLION SETPOINT. WHEN THE COMPUTED START TIME IS REACHED, THE DDC SYSTEM SHALL START THE AIR HANDLING SYSTEM AND OPERATE WITH OUTSIDE AIR AND RELIEF AIR DAMPERS CLOSED AND THE RETURN AIR DAMPER OPEN. THE AIR
PARTS PER HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJUSTABLE). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL SPACE TEMPERATURES ARE LESS THAN A SETPOINT
43 CARBON DIOXIDE LEVEL - OUTDOOR AIR E A I NO C, H T, A, G
MILLION OF 78ºF (ADJABLE). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL. THE ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER THIS MODE OF CONTROL. THE VENTILATION AIR CONTROL SHALL BE INACTIVE.
PARTS PER
44 CARBON DIOXIDE LEVEL - SUPPLY AIR E A I NO C, H T, A, G
MILLION FILTER MONITORING: FOR EACH FILTER BANK WITH RATING OF MERV 8 AND BELOW, PROVIDE AN ALARM TO THE OPERATOR INTERFACE WHEN THE DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.75" W.C. (ADJUSTABLE).
- OUTDOOR AIR REFERENCE TEMPERATURE S A I NO - T, A, G DEGREES F
FOR EACH FILTER BANK WITH RATING OF MERV 14 AND ABOVE, PROVIDE AN ALARM TO THE OPERATOR INTERFACE WHEN THE DIFFERENTIAL STATIC PRESSURE EXCEEDS 1.25" W.C. (ADJUSTABLE). SACRED HEART
% RELATIVE ALARM MONITORING: FREEZESTAT: INSTALL AN ELECTRIC FREEZESTAT, LOCATED DOWNSTREAM OF THE HEATING COIL PER MANUFACTURER'S RECOMMENDATION, TO SHUT DOWN THE UNIT IF THE TEMPERATURE DOWNSTREAM OF THE HEATING COIL DROPS
- OUTDOOR AIR REFERENCE HUMIDITY S A I NO - T, A, G

- HEATING WATER TEMPERATURE - SUPPLY S A I NO - T, A, G


HUMIDITY
DEGREES F
BELOW 35ºF (ADJUSTABLE). THE ELECTRIC FREEZESTAT SHALL ACT INDEPENDENTLY OF THE DDC SYSTEM VIA RELAYS AND SHALL OVERRIDE THE DDC SYSTEM TO SHUT DOWN THE AIR HANDLING UNIT. A SECOND SET OF CONTACTS
SHALL NOTIFY THE DDC SYSTEM THAT SHALL SEND AN ALARM TO THE OPERATOR INTERFACE (MANUAL RESET TYPE). 4TH & 5TH
FIRE ALARM INTERFACE: UPON ACTUATION OF THE FIRE ALARM SYSTEM, THE UNIT SHALL BE SHUT DOWN AND ALL FIRE/SMOKE AND SMOKE DAMPERS WITHIN THIS SYSTEM SHALL CLOSE. THE FIRE ALARM SYSTEM SHALL NOTIFY THE
- CHILLED WATER TEMPERATURE - SUPPLY S A I NO - T, A, G DEGREES F OPERATOR INTERFACE WHENEVER AN ALARM CONDITION IS EXPERIENCED.
2014 C COPYRIGHT CONTROL
- FIRE ALARM STATUS S B I NO C, F E, A NORMAL/ALARM
GENERAL NOTES
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEMATICS
REMARKS PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
(1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS 2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING. ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
(2) A = ANALOG B = BINARY 3. WIRE ALL SENSORS AND CONTROL DEVICES BACK TO CONTROLLER.
(3) I = INPUT O = OUTPUT DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
4. COORDINATE ALL CASING AND DUCT PENETRATIONS WITH FURNISHING CONTRACTOR. ENSURE ALL PENETRATIONS ARE PROPERLY SEALED. BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
(4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE 5. DUCT STATIC PRESSURE SENSORS SHALL BE LOCATED APPROXIMATELY 2/3 OF THE DUCT RUN AWAY FROM THE AIR HANDLING EQUIPMENT. REFER TO FLOOR PLANS FOR LOCATIONS. COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:49 PM
(5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT

10360 Ellison Circle SES PROJECT # 14041

1
AHU-10 CONTROL
NONE
Omaha, NE 68134
Phone: 402.991.5520 M990
www.specializedeng.com Scale NONE
LOOP #1 5 LOOP #2 10
TO/FROM TO/FROM
SECONDARY TO/FROM LOAD PRIMARY TO/FROM LOAD SPACE BOUNDARY
PUMPS PUMPS
AVERA FACILITY DEVELOPMENT
H
4 9

2 8 6 06 T S
C
02 03 08
ACTUATOR 01

HWR

HWS
CONTROLLER
CHILLED WATER 04 05
SYSTEM 07
INTERCONNECTION
1 3 HEAT EXCHANGER 7

TEMPERATURE
CONTROL WIRING (TYP.)

DIRECT DIGITAL CONTROL POINTS LIST DIRECT DIGITAL CONTROL POINTS LIST
POINT SOURCE TYPE I/O SETPOINT ALARMS APPLICATIONS POINT SOURCE TYPE I/O SETPOINT ALARMS APPLICATIONS
POINT DESCRIPTION UNITS POINT DESCRIPTION UNITS
ID (1) (2) (3) ADJUSTMENT (4) (5) ID (1) (2) (3) ADJUSTMENT (4) (5)

01 LOOP #1 HEAT EXCHANGER ENTERING TEMPERATURE E A I NO - T, A, G DEGREES F 01 TERMINAL AIR BOX DISCHARGE AIR TEMPERATURE E A I NO - T, A, G DEGREES F

02 LOOP #1 HEAT EXCHANGER LEAVING TEMPERATURE E A I NO - T, A, G DEGREES F 02 SPACE TEMPERATURE SETPOINT E A I YES - T, A, G DEGREES F

03 LOOP #1 HEAT EXCHANGER CONTROL VALVE E A O NO - G 100% OPEN 03 SPACE TEMPERATURE E A I NO G, H, L T, A, G DEGREES F

04 LOOP #1 DIVERTER VALVE E A O NO - G SUPPLY/RETURN 04 TERMINAL AIR BOX DAMPER ACTUATOR E A O NO - - -


SPACE BOUNDARY
GENERAL NOTES 05 LOOP #1 SELECTOR VALVE E A O NO - G HX/LOOP 05 TERMINAL AIR BOX DAMPER POSITION E A I NO - T, A, G % OPEN

1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED 06 AIRFLOW VOLUME E A I NO - T, A, G CFM
06 LOOP #2 HEAT EXCHANGER ENTERING TEMPERATURE E A I NO - T, A, G DEGREES F
WITHIN 6 FEET OF CONTROLLER.
2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 07 LOOP #2 HEAT EXCHANGER LEAVING TEMPERATURE E A I NO - T, A, G DEGREES F 07 REHEAT COIL CONTROL VALVE E A O NO - - -
3 FEET OF CEILING.
3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY 08 LOOP #2 HEAT EXCHANGER CONTROL VALVE E A O NO - G 100% OPEN 08 OCCUPANCY SENSOR E B I NO - T, A, G OCC/UNOCC
SENSORS TO TERMINAL AIR BOX CONTROLLER.
SEQUENCE OF OPERATION 09 LOOP #2 DIVERTER VALVE E A O NO - G SUPPLY/RETURN REMARKS
H (1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS
EACH ZONE HAS A DIRECT DIGITAL CONTROLLER AND PERIMETER RADIATION WITH PERIMETER RADIATION T 10 LOOP #2 SELECTOR VALVE E A O NO - G HX/LOOP (2) A = ANALOG B = BINARY
CONTROL VALVE. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE PERIMETER
01 02 (3) I = INPUT O = OUTPUT
OF 68°F (ADJUSTABLE) WITH A DEAD BAND RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND RADIATION
COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE REMARKS (4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE
SENSOR REQUIREMENTS. C (1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS (5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT
(2) A = ANALOG B = BINARY
SEQUENCE OF OPERATION
WHEN THE OUTDOOR REFERENCE TEMPERATURE IS ABOVE 65°F (ADJUSTABLE) THE PERIMETER (3) I = INPUT O = OUTPUT
HWR

HWS

RADIATION CONTROL VALVE SHALL BE CLOSED. WHEN THE OUTDOOR REFERENCE TEMPERATURE IS (4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE
CONTROLLER EACH ZONE HAS A TERMINAL AIR BOX WITH A HOT WATER REHEAT COIL, REHEAT COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A SINGLE POINT TEMPERATURE
BELOW 65°F (ADJUSTABLE) THE PERIMETER RADIATION CONTROL VALVE SHALL BE ALLOWED TO (5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT
03 SENSOR 2'-0" DOWNSTREAM OF THE REHEAT COIL. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJUSTABLE) WITH A DEAD BAND
OPERATE BASED ON THE FOLLOWING: TEMPERATURE
RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.
CONTROL
ON A FALL IN SPACE TEMPERATURE THE PERIMETER RADIATION CONTROL VALVE SHALL MODULATE OPEN WIRING (TYP.) SEQUENCE OF OPERATION
WHEN THE SENSOR INDICATES THAT THE ROOM IS OCCUPIED, THE TERMINAL AIR BOX SERVING THE ROOM WILL OPERATE IN ITS NORMAL MODE. WHEN THE SENSOR INDICATES THAT
IN UNTIL SETPOINT IS MAINTAINED.
DESCRIPTION THE SYSTEM CONSISTS OF A PLATE AND FRAME HEAT EXCHANGER INTERCONNECTING TWO EXISTING CHILLED WATER LOOPS. LOOP #1 IS A THE ROOM IS UNOCCUPIED, THE TERMINAL AIR BOX SERVING THE ROOM WILL GO TO UNOCCUPIED MODE. IN UNOCCUPIED MODE, THE TERMINAL AIR BOX WILL INITIALLY CLOSE,
CONSTANT PRIMARY, VARIABLE SECONDARY ARRANGEMENT CONSISTING OF TWO WATER COOLED CHILLERS. LOOP #2 IS A VARIABLE PRIMARY OVERRIDING THE MINIMUM AIRFLOW SETTING. THE TERMINAL AIR BOX WILL THEN OPERATE TO MAINTAIN THE SPACE TEMPERATURE ABOVE 55 DEGREES (ADJUSTABLE) AND BELOW
IF HEATING WATER SYSTEM TEMPERATURE IS 5°F (ADJUSTABLE) BELOW SETPOINT ON A CALL FOR
ARRANGMENT CONSISTING OF ONE AIR COOLED CHILLER. 85 DEGREES (ADJUSTABLE). WHERE MULTIPLE ROOMS ARE SERVED BY A SINGLE TERMINAL AIR BOX, THE TERMINAL AIR BOX WILL OPERATE IN THE OCCUPIED MODE WHENEVER ANY
HEATING AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE.
ONE OF THE ROOMS BEING SERVED IS DETERMINED TO BE OCCUPIED. ALL ROOMS MUST BE DETERMINED TO BE UNOCCUPIED TO INITIATE THE UNOCCUPIED MODE.
THE PRIMARY FUNCTION OF THE INTERCONNECTION IS TO PROVIDE SWING SEASON CHILLED WATER TO THE EQUIPMENT SERVED BY LOOP #1. THE
SECONDARY FUNCTION IS TO PROVIDE EMERGENCY BACKUP TO THE EQUIPMENT SERVED BY LOOP #2. AT FULL COOLING, THE TERMINAL AIR BOX SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED.
DIRECT DIGITAL CONTROL POINTS LIST HEAT EXCHANGER CONTROL: WHEN ALL CHILLERS ARE ENABLED AND AVAILABLE, THE CONTROL VALVES FOR THE HEAT EXCHANGER SHALL BE CLOSED AND NO HEAT TRANSFER ON A FALL IN SPACE TEMPERATURE, THE TERMINAL AIR BOX SHALL MODULATE CLOSED UNTIL SPACE SETPOINT IS MAINTAINED OR UNTIL IT REACHES ITS MINIMUM CFM POSITION. THE
FESSION
SHALL OCCUR. REHEAT COIL CONTROL VALVE SHALL BE CLOSED. PRO AL
POINT SOURCE TYPE I/O SETPOINT ALARMS APPLICATIONS ED . NO.
REG

ER

EN
POINT DESCRIPTION UNITS ON A FURTHER FALL IN SPACE TEMPERATURE THE TERMINAL AIR BOX AND REHEAT COIL CONTROL VALVE SHALL MODULATE OPEN IN UNISON UNTIL SETPOINT IS MAINTAINED OR UNTIL
ID (1) (2) (3) ADJUSTMENT (4) (5) WHEN THE AIR COOLED CHILLER IS ENABLED AND AVAILABLE AND THE WATER COOLED CHILLERS ARE DISABLED, THE FOLLOWING SHALL OCCUR:

REGIST

GINEE
SPECIFIED MAXIMUM HEATING CFM POSITION IS REACHED. 10229
1. THE LOOP #1 CONTROL VALVE SHALL BE 100% OPEN. ERIC G.

R
01 SPACE TEMPERATURE SETPOINT E A I YES - T, A, G DEGREES F IF HEATING WATER SYSTEM TEMPERATURE IS 5°F (ADJUSTABLE) BELOW SETPOINT ON A CALL FOR HEATING THE TERMINAL AIR BOX SHALL REMAIN AT ITS MINIMUM CFM POSITION. SHERMAN
2. THE LOOP #2 CONTROL VALVE SHALL MODULATE TO MAINTAIN LOOP #1 SUPPLY WATER TEMPERATURE SETPOINT.

A
S

T
3. THE LOOP #1 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE SUPPLY MAIN.

O
U O
T H K
02 SPACE TEMPERATURE E A I NO G, H, L T, A, G DEGREES F OCCUPANCY OPTIMUM RECOVERY: THIS CYCLE SHALL OVERRIDE THE OCCUPIED CONTROL CYCLE. IF THE SPACE TEMPERATURE IS MORE THAN 3 DEGREES (ADJUSTABLE) BELOW D A
4. THE LOOP #2 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE RETURN MAIN.
5. THE LOOP #1 SELECTOR VAVLE SHALL BE 50% OPEN (ADJUSTABLE). BALANCER SHALL DETERMIN %OPEN REQUIRED FOR PROPER OPERATION THE OCCUPIED SETPOINT AND ANY OCCUPANCY SENSOR INDICATES OCCUPANCY, THE VAV BOX AND REHEAT COIL CONTROL VALVE SHALL MODULATE TO FULLY OPEN AND SHALL
03 PERIMETER RADIATION CONTROL VALVE E A O NO - - - AND VALUE SHALL BE RECORDED WITHIN THE BAS. REMAIN FULLY OPEN UNTIL SETPOINT IS REACHED. ONCE SETPOINT IS REACHED, CONTROL SHALL RETURN TO NORMAL OPERATION. IF THE SPACE TEMPERATURE IS MORE THAN 3
6. THE LOOP #2 SELECTOR VALVE SHALL BE 100% OPEN. DEGREES (ADJUSTABLE) ABOVE THE OCCUPIED SETPOINT AND ANY OCCUPANCY SENSOR INDICATES OCCUPANCY, THE VAV BOX SHALL MODULATE TO FULLY OPEN AND THE REHEAT 11/25/14
04 OUTDOOR REFERENCE DRY BULB TEMPERATURE S A I NO - - - COIL CONTROL VALVE SHALL MODULATE TO FULLY CLOSED AND THEY SHALL REMAIN AT THESE OPERATING POINTS UNTIL SETPOINT IS REACHED. ONCE SETPOINT IS REACHED,
WHEN THE AIR COOLED CHILLER IS DISABLED AND THE WATER COOLED CHILLERS ARE ENABLED AND AVAILABLE, THE FOLLOWING SHALL OCCUR: CONTROL SHALL RETURN TO NORMAL OPERATION.
No. Description Date
REMARKS THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
1. THE LOOP #1 CONTROL VALVE SHALL MODULATE TO MAINTAIN LOOP #1 SUPPLY WATER TEMPERATURE SETPOINT.
(1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS 2. THE LOOP #2 CONTROL VALVE SHALL BE 100% OPEN.
(2) A = ANALOG B = BINARY 3. THE LOOP #1 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE RETURN MAIN. GENERAL NOTES
(3) I = INPUT O = OUTPUT 4. THE LOOP #2 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE SUPPLY MAIN. 5. THE 5. 1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.
(4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE 5. THE LOOP #1 SELECTOR VAVLE SHALL BE 100% OPEN. 2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING.
(5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT 6. THE LOOP #2 SELECTOR VALVE SHALL BE 100% CLOSED.
3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER.

RADIANT PANEL CONTROL CHILLED WATER SYSTEM INTERCONNECTION CONTROL VAV BOX CONTROL - TYPICAL
3 NONE
2 NONE
1 NONE

SACRED HEART
4TH & 5TH
2014 C COPYRIGHT CONTROL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEMATICS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:51 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 M991
www.specializedeng.com Scale NONE
ROOM ROOM ANTIROOM
EXHAUST EXHAUST EXHAUST
BALANCED BALANCED BALANCED
TO 12 ACH. TO 12 ACH. TO 12 ACH.

NEGATIVE AIR ROOM NEGATIVE AIR ROOM ANTEROOM


AVERA FACILITY DEVELOPMENT
ROOM
ROOM SUPPLY AIR EXHAUST ROOM SUPPLY AIR
BALANCED TO MAINTAIN BALANCED BALANCED TO MAINTAIN
-0.01IN W.C. DIFFERENTIAL TO 10 ACH. -0.01IN W.C. DIFFERENTIAL
PRESSURE BETWEEN ROOM H PRESSURE BETWEEN ROOM H
AND CORRIDOR. MECHANICAL AND CORRIDOR. MECHANICAL MECHANICAL
AIRFOW TOILET ROOM AIRFOW AIRFOW
T INDICATOR T INDICATOR INDICATOR

06 T 06 T
C C
02 03 02 03
ACTUATOR 01 ACTUATOR 01

HWR

HWR
HWS

HWS
CONTROLLER CONTROLLER
04 05 04 05
07 07 TOILET ROOM

ROOM
TEMPERATURE TEMPERATURE EXHAUST
CONTROL WIRING (TYP.) CONTROL WIRING (TYP.) BALANCED
TO 10 ACH.

DIRECT DIGITAL CONTROL POINTS LIST DIRECT DIGITAL CONTROL POINTS LIST
POINT SOURCE TYPE I/O SETPOINT ALARMS APPLICATIONS POINT SOURCE TYPE I/O SETPOINT ALARMS APPLICATIONS
POINT DESCRIPTION UNITS POINT DESCRIPTION UNITS
ID (1) (2) (3) ADJUSTMENT (4) (5) ID (1) (2) (3) ADJUSTMENT (4) (5)

01 TERMINAL AIR BOX DISCHARGE AIR TEMPERATURE E A I NO - T, A, G DEGREES F 01 TERMINAL AIR BOX DISCHARGE AIR TEMPERATURE E A I NO - T, A, G DEGREES F

02 SPACE TEMPERATURE SETPOINT E A I YES - T, A, G DEGREES F 02 SPACE TEMPERATURE SETPOINT E A I YES - T, A, G DEGREES F

03 SPACE TEMPERATURE E A I NO G, H, L T, A, G DEGREES F 03 SPACE TEMPERATURE E A I NO G, H, L T, A, G DEGREES F

04 TERMINAL AIR BOX DAMPER ACTUATOR E A O NO - - - 04 TERMINAL AIR BOX DAMPER ACTUATOR E A O NO - - -

05 TERMINAL AIR BOX DAMPER POSITION E A I NO - T, A, G % OPEN 05 TERMINAL AIR BOX DAMPER POSITION E A I NO - T, A, G % OPEN

06 AIRFLOW VOLUME E A I NO - T, A, G CFM 06 AIRFLOW VOLUME E A I NO - T, A, G CFM

07 REHEAT COIL CONTROL VALVE E A O NO - - - 07 REHEAT COIL CONTROL VALVE E A O NO - - -

REMARKS REMARKS
(1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS (1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS
(2) A = ANALOG B = BINARY (2) A = ANALOG B = BINARY
(3) I = INPUT O = OUTPUT (3) I = INPUT O = OUTPUT
(4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE (4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE
(5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT (5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT

SEQUENCE OF OPERATION SEQUENCE OF OPERATION

EACH ZONE HAS A TERMINAL AIR BOX WITH A HOT WATER REHEAT COIL, REHEAT COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A SINGLE POINT TEMPERATURE EACH ZONE HAS A TERMINAL AIR BOX WITH A HOT WATER REHEAT COIL, REHEAT COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A SINGLE POINT TEMPERATURE
SENSOR 2'-0" DOWNSTREAM OF THE REHEAT COIL. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJUSTABLE) WITH A DEAD BAND SENSOR 2'-0" DOWNSTREAM OF THE REHEAT COIL. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJUSTABLE) WITH A DEAD BAND
RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS. RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.

AT FULL COOLING, THE TERMINAL AIR BOX SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED. AT FULL COOLING, THE TERMINAL AIR BOX SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED.

ON A FALL IN SPACE TEMPERATURE THE REHEAT COIL CONTROL VALVE SHALL MODULATE OPEN IN UNISON UNTIL SETPOINT IS MAINTAINED. ON A FALL IN SPACE TEMPERATURE THE REHEAT COIL CONTROL VALVE SHALL MODULATE OPEN IN UNISON UNTIL SETPOINT IS MAINTAINED.

IF THE SPACE TEMPERATURE VARIES MORE THAN 5°F (ADJUSTABLE) FROM SETPOINT, SEND ALARM TO THE OPERATOR INTERFACE. IF THE SPACE TEMPERATURE VARIES MORE THAN 5°F (ADJUSTABLE) FROM SETPOINT, SEND ALARM TO THE OPERATOR INTERFACE.

THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE. THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.

GENERAL NOTES GENERAL NOTES FESSION


PRO AL
1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. 1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. ED . NO.
REG

ER

EN
2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING. 2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING.

REGIST

GINEE
3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER. 3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER. 10229
4. SEAL ALL SPACE BOUNDARY PENETRATIONS AIR TIGHT. PENETRATION SEALS MUST INCLUDE EXTERIOR AND INTERIOR OF CONDUITS. 4. SEAL ALL SPACE BOUNDARY PENETRATIONS AIR TIGHT. PENETRATION SEALS MUST INCLUDE EXTERIOR AND INTERIOR OF CONDUITS. ERIC G.

R
SHERMAN

A
S

T
O
U O
T H K
D A

NEGATIVE AIR ROOM CONTROL ISOLATION ROOM CONTROL


2 NONE
1 NONE
11/25/14

No. Description Date

GENERAL NOTES
1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN
6 FEET OF CONTROLLER.
2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES. THE TERMINAL BOX CONTROLLER MOTOR FAN
MUST BE WITHIN 3 FEET OF CEILING.
CONTROLLER
SEQUENCE OF OPERATION 01 02

EACH FAN HAS AN ISOLATION DAMPER WITH END SWITCH TO PROVE DAMPER OPEN AND CURRENT STATUS SWITCH
TO PROVE FAN OPERATION. IF THE END SWITCH DOES NOT PROVE OPEN, SEND AN ALARM TO THE OPERATOR
INTERFACE. IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, SEND AND ALARM TO THE USER ACTUATOR
INTERFACE.
03 04
FAN SHALL RUN CONTINUOUSLY. MOTORIZED DAMPER SHALL CLOSE ON LOSS OF POWER TO FAN.

DIRECT DIGITAL CONTROL POINTS LIST


POINT
ID
POINT DESCRIPTION
SOURCE
(1)
TYPE
(2)
I/O
(3)
SETPOINT
ADJUSTMENT
ALARMS
(4)
APPLICATIONS
(5)
UNITS SACRED HEART
01 EXHAUST FAN STATUS E B I NO G, F E, A, G ON/OFF

02 EXHAUST FAN START/STOP E B 0 NO - - -


4TH & 5TH
03 EXHAUST FAN ISOLATION DAMPER ACTUATOR E A O NO - T, A, G -
2014 C COPYRIGHT CONTROL
04 EXHAUST FAN ISOLATION DAMPER POSITION E B I NO F T, A, G OPEN/CLOSED PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEMATICS
REMARKS PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
(1) E = ELECTRIC P = PNEUMATIC S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK O = BY OTHERS ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
(2) A = ANALOG B = BINARY
(3) I = INPUT O = OUTPUT DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
(4) G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
(5) T = TRENDING E = EVENT HISTORY A = ARCHIVE TT=TOTALIZATION G = GRAPHICAL POINT COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 4:38:52 PM

10360 Ellison Circle SES PROJECT # 14041

3
EXHAUST FAN CONTROL
NONE
Omaha, NE 68134
Phone: 402.991.5520 M992
www.specializedeng.com Scale NONE
ELECTRICAL SYMBOLS TELECOM SUPPLEMENTAL SYMBOLS ELECTRICAL SUPPLEMENTAL SYMBOL LEGEND - NURSE CALL SYSTEM ROUGH-IN
LIGHTING AND POWER "X" INDICATES FIXTURE NUMBER IN SCHEDULE SYMBOL DESCRIPTION
PLAN SYMBOL DEVICE (3) DEVICE MODEL NO. ROUGH-IN GANG QTY BOX TYPE BOX DEPTH CONDUIT SIZE CONDUIT STUB LOCATION REMARKS
COMMUNICATIONS OUTLET:
X CEILING TROFFER FIXTURE X STRIP FIXTURE NC BSID BEDSIDE STATION 353000 3 RACO 697 3-1/2" 1" DOME LIGHT NOTE 1
OUTLET TYPE INDICATED PER PLAN. OUTLETS WITH NO CABLING DESIGNATION SHALL BE EMPTY
WITH BLANK COVERPLATE. CABLING DESIGNATIONS TYPICAL FOR FLOOR AND CEILING DEVICES. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION. AVERA FACILITY DEVELOPMENT
X LINEAR WALL FIXTURE X WALL FIXTURE REFER TO INFORMATION DELIVERY DETAILS, OUTLET DETAIL, AND SPECIFICATIONS FOR FURTHER
REQUIREMENTS. PROVIDE CABLING AS FOLLOWS:
A = 1 ANALOG VOICE CABLE NC DOME DOME LIGHT 352000 1 RACO 695 3-1/2" 1" CABLE TRAY NOTE 1
X DOWN LIGHT FIXTURE EMERGENCY BATTERY FIXTURE V = 1 DIGITAL VOICE CABLE
X COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
D = 1 DATA CABLE
SHADED FIXTURES REPRESENT BATTERY W = 1 DIGITAL VOICE CABLE WITH PHONE MOUNTING BRACKET FACEPLATE AT 48" AFF.
WALL MOUNTED EXIT SIGN WITH DIRECTIONAL ARROW
PACKS OR EMERGENCY CIRCUIT X NC ZONE ZONE LIGHT 352000 1 RACO 695 3-1/2" 1" CABLE TRAY NOTE 1
FLOOR COMMUNICATIONS OUTLET:
REFER TO SUPPLEMENTAL SYMBOL LEGENDS FOR FURTHER REQUIREMENTS. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
CEILING MOUNTED EXIT SIGN WITH DIRECTIONAL ARROW X PENDENT FIXTURE
X
COMBINATION FLOOR OUTLET - POWER & COMMUNICATIONS: NC PULL PULL CORD 354001 1 RACO 695 3-1/2" 1" DOME LIGHT NOTE 1
UNDERCABINET FIXTURE COVE FIXTURE REFER TO SUPPLEMENTAL SYMBOL LEGENDS FOR FURTHER REQUIREMENTS.
X
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
SWITCH - SINGLE POLE 4 SWITCH - 4-WAY
CEILING COMMUNICATIONS OUTLET:
3 SWITCH - 3-WAY MC SWITCH - MOMENTARY CONTACT REFER TO SUPPLEMENTAL SYMBOL LEGENDS FOR FURTHER REQUIREMENTS.
D WALL BOX DIMMER CEILING OCCUPANCY SENSOR (LOCAL RELAY) NC APULL PULL CORD - AUDIO 354000 1 RACO 695 3-1/2" 1" DOME LIGHT NOTE 1
LIGHTING CONTACTOR Z CEILING OCCUPANCY SENSOR (CONTROL PANEL RELAY - ZONE) TELEVISION OUTLET: COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
TV
REFER TO SUPPLEMENTAL SYMBOL LEGENDS AND DETAILS FOR FURTHER REQUIREMENTS.
PUSH BUTTON WALL SWITCH OCCUPANCY SENSOR (LOCAL RELAY)
RECEPTACLE - DUPLEX RECEPTACLE - SINGLE
WALL SLEEVE WALL COMMUNICATIONS FIRE RATED PATHWAY: NC PB PUSH BUTTON CALL CANCEL 354010 1 RACO 695 3-1/2" 1" DOME LIGHT NOTE 1
G RECEPTACLE - DUPLEX - GFCI RECEPTACLE - DOUBLE DUPLEX DESIGNATION PROVIDE "EZ-PATH" FIRE RATED PATHWAY THROUGH WALL ABOVE CEILING. INSTALL PER
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
* RECEPTACLE - DUPLEX - EXTRA HEAVY DUTY RECEPTACLE - DOUBLE DUPLEX - ISOLATED GROUND MANUFACTURERS RECOMMENDATIONS. SLEEVE DESIGNATIONS PER PLANS. PROVIDE SLEEVES AS
A1 FOLLOWS:
T RECEPTACLE - DUPLEX - SAFETY TYPE (TAMPER RESISTANT) RECEPTACLE - DOUBLE DUPLEX - EMERGENCY (RED)
RECEPTACLE - DUPLEX - EMERGENCY (RED) RECEPTACLE - SPECIAL PURPOSE - (NEMA CONFIG. AS NOTED) (A1) - CATALOG NO. EZDP133CWK. (1-3"x3" PATHWAY) NC BED FEATURE BED RECEPTACLE NCBED5 1 VERIFY 3-1/2" VERIFY VERIFY --
RECEPTACLE - DUPLEX - CEILING MOUNTED MULTI-OUTLET ASSEMBLY - LENGTH AS INDICATED (A2) - CATALOG NO. EZDP233GK. (2-3"x3" PATHWAY) COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
(A3) - CATALOG NO. EZDP333GK. (3-3"x3" PATHWAY)
LIGHTING PANEL J JUNCTION BOX - WALL (A4) - CATALOG NO. EZDP433GK. (4-3"x3" PATHWAY)
DISTRIBUTION PANEL, SWITCHBOARD OR MOTOR CONTROL CENTER J JUNCTION BOX - CEILING (A5) - (1) CATALOG NO. EZDP233GK. AND (1) CATALOG NO. EZDP333GK. (5-3"x3" PATHWAY) (STACKED) NC MASTER MASTER STATION 351200 1 RACO 695 3-1/2" NOTE 4 CABLE TRAY NOTE 1
BRANCH CIRCUIT - EXPOSED J JUNCTION BOX - FLOOR (A6) - (2) CATALOG NO. EZDP333GK. (6-3"x3" PATHWAY) (STACKED)
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
(A7) - CATALOG NO. EZDP733GK. (7-3"x3" PATHWAY)
BRANCH CIRCUIT CONCEALED IN CEILING OR WALL J PHOTOCELL PHOTOCELL (A8) - (2) CATALOG NO. EZDP433GK. (8-3"x3" PATHWAY) (STACKED)
BRANCH CIRCUIT CONCEALED IN FLOOR OR BELOW GRADE CIRCUIT DOWN (B1) - CATALOG NO. EZD22. (1-2"x2" PATHWAY) NC CP CONTROL PANEL NC2828 VERIFY VERIFY VERIFY VERIFY VERIFY --
(C1) - CATALOG NO. EZDP44. (1-4"x4" PATHWAY)
HOMERUN TO PANEL (NUMBER OF ARROWS INDICATES CIRCUIT UP COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
(C2) - (2) CATALOG NO. EZDP44 & (1)-EZP544W. (2-4"x4" PATHWAY)
NUMBER OF CIRCUITS) CONDUIT STUB-OUT (C3) - (3) CATALOG NO. EZDP44. & (1)-EZP544W. (3-4"x4" PATHWAY)
SPECIAL PURPOSE HOMERUN AS INDICATED CIRCUIT BREAK (C4) - (4) CATALOG NO. EZDP44. & (1)-EZP544W. (4-4"x4" PATHWAY)
(C5) - (5) CATALOG NO. EZDP44. & (1)-EZP544W. (5-4"x4" PATHWAY) GENERAL NOTES:
SAFETY SWITCH - FUSED UNLESS OTHERWISE NOTED COMBINATION MAGNETIC STARTER/DISCONNECT (C5) - (6) CATALOG NO. EZDP44. & (1)-EZP544W. (6-4"x4" PATHWAY) 1. PROVIDE NURSE CALL DEVICE ROUGH-IN PER THE SCHEDULE. COORDINATE MOUNTING DEPTH (OR PLASTER RING WHERE APPLICABLE) TO ACCOMMODATE WALL FINISH. PROVIDE CONDUIT STUBBED FROM BOX TO ASSOCIATED NURSE CALL
SINGLE POLE MANUAL MOTOR STARTER WITH THERMAL SWITCH & FUSE CORRIDOR DOME LIGHT. WHERE AN ASSOCIATED NURSE CALL CORRIDOR DOME LIGHT IS NOT AVAILABLE, STUB CONDUIT TO NEAREST CORRIDOR J-HOOK. PROVIDE DEVICE BOX WITH BACK-SIDE SUPPORT. ROUGH-INS SHALL NOT BE MOUNTED
TE O.L. AND PILOT LIGHT BACK-TO-BACK AND SHALL NOT SHARE CONDUITS, UNLESS SPECIFICALLY NOTED OR APPROVED BY THE MANUFACTURER. ROUTE CONDUITS CONCEALED IN WALLS AND CEILINGS. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS FOR EXACT
FLOOR SLEEVE FLOOR COMMUNICATIONS FIRE RATED PATHWAY: DEVICE MOUNTING LOCATIONS. WHERE DEVICES ARE NOT SHOWN IN ELEVATION, SEEK CLARIFICATION FROM ARCHITECT. PROVIDE MOCK-UPS WHERE REQUESTED. SPAN WALL STUDS WITH BRACKETS WHERE REQUIRED TO ACCOMMODATE
FIRE ALARM SYSTEM "W" INDICATES WALL MOUNTED UNLESS NOTED OTHERWISE DESIGNATION PROVIDE "EZ-PATH" FIRE RATED PATHWAY THROUGH FLOOR. INSTALL PER MANUFACTURERS
RECOMMENDATIONS. SLEEVE DESIGNATIONS PER PLANS. PROVIDE SLEEVES AS FOLLOWS:
DEVICE PLACEMENT.
2. WHERE LOCATED IN AN ARCHITECTURAL WALL, CONDUIT SHALL STUB TO THE CORRIDOR DOME LIGHT.
AUTOMATIC SMOKE DETECTOR - CEILING F STROBE - CEILING 3. RAULAND RESPONDER V IS USED AS BASIS OF DESIGN FOR SPECIFIED NURSE CALL SYSTEM ROUGH-IN REQUIREMENTS. VERIFY FINAL MANUFACTURER AND PRODUCTS AND COORDINATE REQUIREMENTS WITH OWNER PRIOR TO INSTALLATION.
F1 (F1) - CATALOG NO. EZDP144FK. (1-4"x4" PATHWAY) 4. PROVIDE 1" METALLIC SURFACE RACEWAY, MOUNT TO VERTICAL MULLION, AT LOCATION OF CURRENT SURFACE RACEWAY FOR NURSE CALL CABLING.
AUTOMATIC HEAT DETECTOR - CEILING F HORN - CEILING (F2) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZDG444 AND (1) PATHWAY MODULE CATALOG 5. NURSE CALL SYSTEM AND CABLES SHALL BE OWNER FURNISHED AND OWNER INSTALLED.
SAMPLING TUBE TYPE SMOKE DETECTOR F HORN & STROBE COMBINATION - CEILING NO. EZD444MB. (4-4"x4" PATHWAYS) 6. PROVIDE INDIVIDUAL 1" CONDUIT STUB OUTS FOR EACH NURSE CALL ROUGH-IN INDICATED.
F SPEAKER - CEILING (F3) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG844 AND (1) PATHWAY MODULE CATALOG
FSD OR SD COMBINATION FIRE/SMOKE DAMPER NO. EZD444MB. (4-4"x4" PATHWAYS AND 4-4"x4" SPACES)
F SPEAKER & STROBE COMBINATION - CEILING (F4) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG844 AND (2) PATHWAY MODULES CATALOG
MAGNETIC DOOR HOLDER F CHIME - CEILING NO. EZD444MB. (8-4"x4" PATHWAYS)
F FIRE SPRINKLER VALVE TAMPER SWITCH F CHIME & STROBE COMBINATION - CEILING (F5) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG1644 AND (2) PATHWAY MODULES
CATALOG NO. EZD444MB. (8-4"x4" PATHWAYS AND 8-4"x4" SPACES)
F FIRE SPRINKLER FLOW SWITCH F CM CONTROL MODULE (F6) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG1644 AND (3) PATHWAY MODULES
F MANUAL STATION F MM MONITORING MODULE CATALOG NO. EZD444MB. (12-4"x4" PATHWAYS AND 4-4"x4" SPACES)
(F7) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG1644 AND (4) PATHWAY MODULES
SOUND CATALOG NO. EZD444MB. (16-4"x4" PATHWAYS)

S CEILING SPEAKER IC INTERCOM STATION EXAMPLE C5 CABLE SPILLWAY:


INTERCOM CONTROL PANEL PROVIDE CABLE SPILLWAY "EZ-PATH" CATALOG NO. RCM33 AT FIRE RATED PATHWAYS INDICATED
IC
C5S WITH A SUBSCRPT 'S'. PROVIDE (1) SPILLWAY PER SLEEVE. VERIFY QUANTITIES PER PLAN.
SECURITY SYSTEMS LIGHTING GENERAL NOTES POWER GENERAL NOTES
EXAMPLE C5 EXTENSION MODULE: (LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)
DOOR CONTACT SC SECURITY CONTROL PANEL PROVIDE EXTENSION MODULE "EZ-PATH" CATALOG NO. EZD33E AT FIRE RATED PATHWAYS INDICATED (POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)
CR CARD READER DP DOOR PLATE C5E WITH A SUBSCRPT 'E'. PROVIDE (1) EXTENSION MODULE PER SLEEVE. VERIFY QUANTITIES PER PLAN. A. LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.
WHERE FIRE RATED PATHWAY IS INDICATED WITH (2) 'E', PROVIDE (1) EXTENSION MODULES ON EACH BEING CONTROLLED. WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS
DO DOOR OPENER
END. FIXTURE(S) LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH WITH ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT
A SUBSCRIPT LETTER IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT
MISCELLANEOUS 12x4 VERTICAL CABLE MANAGEMENT: DEVICE SERVING AREA WITH MATCHING SUBSCRIPT SHALL CONTROL CORRESPONDING SPECIFICATIONS.
DIMENSIONS ARE INDICATED IN INCHES. FIRST NUMBER INDICATES WIDTH, SECOND NUMBER LIGHT FIXTURES.
FESSION
C CHIME BELL
INDICATES DEPTH. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS. B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND PRO AL
B. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75'-0" SHALL UTILIZE #10 AWG ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES ED G . NO.
RE

ER
CONDUCTORS.

EN
SUBSCRIPT "WP" APPLIED TO ANY SYMBOL INDICATES SUBSCRIPT "RT" APPLIED TO ANY SYMBOL INDICATES RAINTIGHT CABLE TRAY: SPECIFIED ON THE ARCHITECTURAL DRAWINGS. ROUTE ALL ELECTRICAL BRANCH CIRCUITS

REGIST

GINEER
WP WEATHERPROOF NEMA TYPE 4 OR EQUIVALENT RT 12x4 AND CONDUITS SPECIFIED, TO COORDINATE WITH OTHER TRADES AND TO ALLOW FOR 10206
NEMA 3R OR EQUIVALENT TYPE INDICATED PER SPECIFICATION. DIMENSIONS ARE INDICATED IN INCHES. FIRST NUMBER C. SWITCHES SERVING UNDERCABINET TASK LIGHTING SHALL MATCH RECEPTACLE HEIGHT
INDICATES WIDTH, SECOND NUMBER INDICATES DEPTH. REFER TO SPECIFICATIONS FOR FURTHER ABOVE COUNTER. SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE TRACY J.
E SUBSCRIPT "E" ADDED TO ANY SYMBOL INDICATES EXISTING P SUBSCRIPT "P" ADDED TO ANY SYMBOL INDICATES PILOT LIGHT ACCESS PANELS CANNOT BE AVOIDED, ARRANGE WORK TO INSTALL PANELS IN LOCATIONS
REQUIREMENTS. D. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL HAUSER

A
ACCEPTABLE TO ARCHITECT.

S
V SUBSCRIPT "V" ADDED TO ANY SYMBOL INDICATES VOICE W SUBSCRIPT "W" ADDED TO ANY SYMBOL INDICATES WALL PHONE

T
O
U O
FLOOR PLANS. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND T H
D A
K
D SUBSCRIPT "D" ADDED TO ANY SYMBOL INDICATES DATA # SHEET NOTE MOUNTING HEIGHTS WITH ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE C. BRANCH CIRCUIT WITH A TOTAL LENGTH LONGER THAN 75'-0" SHALL UTILIZE #10 AWG
CONDUIT SLEEVE WITH BUSHINGS: CONDUCTORS.
R SUBSCRIPT "R" ADDED TO ANY SYMBOL INDICATES REUSED PART SUBSCRIPT "PART" ADDED TO ANY SYMBOL INDICATES PARTIAL MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT
REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS.
INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS. D. REFER TO DETAILS, SCHEDULES, AND SUPPLEMENTAL LEGENDS FOR ADDITIONAL
C SUBSCRIPT "C" ADDED TO ANY SYMBOL INDICATES CEILING 11/25/14
E. CONTRACTOR SHALL COORDINATE ALL LIGHTING CONTROL DEVICE ROUGH-IN LOCATIONS REQUIREMENTS.
CONDUIT SLEEVE(S) WITH BUSHINGS:
AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH E. BRANCH CIRCUITS SERVING PATIENT CARE AREAS SHALL UTILIZE A CONTINUOUS METALLIC
(4)-4"C. LOCATE ABOVE CEILING. SIZE AND QUANTITY AS INDICATED. REFER TO SPECIFICATIONS FOR No. Description Date
FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL CONDUIT PATH FOR GROUNDING IN ADDITION TO AN INSULATED EQUIPMENT GROUNDING
FURTHER REQUIREMENTS.
ELECTRICAL BRANCH CIRCUITS AND CONDUIT WITH OTHER TRADES TO ALLOW FOR CONDUCTOR. REFER TO SPECIFICATIONS FOR CONDUIT AND CABLE WIRING METHODS
SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ALLOWED AND DISALLOWED FOR APPLICATION ON THIS PROJECT.
PLYWOOD BACKING: ACCESS PANELS CANNOT BE AVOIDED, WORK TO INSTALL PANELS IN LOCATIONS
4' WIDE x 8' TALL PLYWOOD BACKING. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS. F. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC
ACCEPTABLE TO ARCHITECT.
FOR REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE
F. REFER TO PROJECT MANUAL AND ARCHITECTURAL DRAWINGS FOR LIMITS OF METHODS/APPLICATIONS.
TELECOMMUNICATIONS RACK: CONSTRUCTION FOR EACH PHASE.
PROVIDE 7' TELECOMMUNICATIONS RACK. G. REFER TO PROJECT MANUAL AND ARCHITECTURAL DRAWINGS FOR LIMITS OF
G. REFER TO DETAILS, SCHEDULES, AND SUPPLEMENTAL LEGENDS FOR ADDITIONAL CONSTRUCTION FOR EACH PHASE.
REQUIREMENTS.

ELECTRICAL DEMOLITION GENERAL NOTES FIRE ALARM GENERAL NOTES


(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND ALL
ELECTRICAL DEMOLITION WORK) (FIRE ALARM GENERAL NOTES SHALL APPLY TO ALL SHEETS)
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. A. FIRE ALARM CABLING SHALL BE INSTALLED IN CONDUIT WHERE PLENUM RATED CABLING
DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING IS NOT UTILIZED.
WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR
DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS B. PROVIDE DUCT SMOKE DETECTION WITHIN SUPPLY AND RETURN DUCTS OF AHU-10.
REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK LOCATIONS WITHIN SUPPLY DUCTS SHALL BE DOWNSTREAM OF SERVING UNIT AND BEFORE
OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST CLARIFICATION FROM THE ARCHITECT.
REMAIN. BRANCH DUCTS. LOCATIONS WITHIN RETURN DUCTS SHALL BE UPSTREAM OF SERVING UNIT
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT AND BRANCH DUCTS. PROVIDE CONNECTIONS SO THAT SMOKE SENSING WILL SHUT DOWN
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ALL TIMES. MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN SERVING UNIT. REFER TO MECHANICAL SCHEDULES FOR UNIT CFM OUTPUT.
ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN HATCHED SHALL BE REMOVED (D- CONTINUITY OF SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR
DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY C. PROVIDE MONITORING/CONTROL MODULE FOR EACH FIRE/SMOKE (F/S) DAMPER SYSTEM.
REINSTALLED PER NEW WORK (R-RELOCATION). FOR DISCONNECTION AND IMMEDIATE RECONNECTION. INTERRUPTION TO SERVICE REFER TO ELECTRICAL FLOOR PLANS FOR DAMPER LOCATIONS, PROVIDE POWER CONNECTION
DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED FOR FIRE/SMOKE DAMPERS AS IDENTIFIED ON FLOOR PLANS. REFER TO DETAIL 5 ON SHEET
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE E501 FOR CONNECTION REQUIREMENTS. PROVIDE ALL CONNECTIONS FOR A COMPLETE
WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY
CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO SYSTEM.
EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE
FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF
METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF D. PROVIDE DUCT SMOKE DETECTOR WITHIN 5' OF EACH FIRE/SMOKE DAMPER WITH
DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT
ACCIDENTAL INTERRUPTION. CONNECTION TO LOCAL FIRE ALARM SYSTEM. ALARM OF DUCT DETECTOR SHALL INSTALL GREEN INSULATED
DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE
CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY ACTIVATE DAMPER. GROUND WIRE WITH
DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE POWER AND LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO LIGHTING, RECEPTACLE AND
E. PROVIDE REMOTE STATUS INDICATOR FOR EACH DUCT SMOKE DETECTOR, LOCATE
DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE
AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND IS ENCOURAGED TO REVIEW
FACILITY DRAWINGS PRIOR TO THE BID DATE. I.
PROCEED.
PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED
ADJACENT TO AHU-10. COORDINATE EXACT LOCATIONS WITH OWNER PRIOR TO INSTALLATION. EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY. NEUTRAL CONDUCTORS FOR
REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
4TH & 5TH
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION,
SINGLE POLE CIRCUIT BREAKER
SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE
REMOVED WITH WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED.
ABANDON CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED
FIRE RATING, AND FINISH. SEE ARCHITECTURAL SPECIFICATIONS FOR MEANS AND
METHODS. 2014 C COPYRIGHT ELECTRICAL COVER
K. CONSTRUCTION SHALL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS
CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS
TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED
FOR DETAILS AND LIMITS OF DEMOLITION FOR EACH PHASE. SYSTEM SERVICES TO
AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT ALL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SHEET
ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
TIMES.
CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE L. CHANGES REQUIRED FOR EXISTING VOICE AND DATA CABLING AND OUTLETS IN ROOMS ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE NOT BEING RENOVATED BY THIS PROJECT WILL BE PROVIDED BY THE OWNER. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND M. PROVIDE RECIRCUITING, AS REQUIRED, OF EXISTING TO REMAIN ELECTRICAL ITEMS
AFFECTED BY DEMOLITION OF PERIMETER FAN COIL UNITS ON FOURTH FLOOR. PROVIDE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:32 PM
PATCH WHERE BOXES ARE NOT REUSED.
$30,000 BID ALLOWANCE FOR ASSOCIATED RECIRCUITING OF FOURTH FLOOR PATIENT
ROOM BRANCH CIRCUITS. 10360 Ellison Circle SES PROJECT # 14041
Omaha, NE 68134
Phone: 402.991.5520 E000
www.specializedeng.com Scale NONE
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

A SHEET NOTES
1 DEMOLISH EXISTING ELECTRICAL CONNECTIONS SERVING AHU-
10. REMOVE BRANCH CIRCUIT CONDUCTORS FROM EXISTING
CONDUIT AND DISCONNECT FROM SOURCE FUSIBLE SWITCH.
LABEL FUSIBLE SWITCH COMPARTMENT AS SPARE. EXISTING
BRANCH CIRCUIT CONDUIT IS SHARED WITH OTHER
MECHANICAL EQUIPMENT NEARBY. EXISTING MECHANICAL
EQUIPMENT NOT SERVING AHU-10, SHARING COMMON CONDUIT,
SHALL REMAIN OPERATIONAL.

2 DEMOLISH ELECTRICAL CONNECTIONS SERVING PUMP.


REMOVE BRANCH CIRCUIT CONDUCTORS FROM EXISTING
CONDUIT AND DISCONNECT FROM SOURCE FUSIBLE SWITCH.
A1 LABEL FUSIBLE SWITCH COMPARTMENT AS SPARE. EXISTING
BRANCH CIRCUIT CONDUIT IS SHARED WITH OTHER
MECHANICAL EQUIPMENT NEARBY. EXISTING ELECTRICAL
B
B.0
D E EQUIPMENT NOT SERVING PUMP INDICATED, SHARING
COMMON CONDUIT, SHALL REMAIN OPERATIONAL. EXISTING TO
2 P-13 P-15 REMAIN PUMP INDICATED ON FLOOR PLAN, NEAR PUMP BEING
DEMOLISHED, HAS BRANCH CIRCUIT SHARING CONDUIT WITH
E E BRANCH CIRCUIT SHARING DEMOLISHED PUMP.
4
E 3 EXISTING THIRD LEVEL MAIN TELECOM ROOM.

1.7 2.1 MCC-2 MCC-3


4 EXISTING VOICE WALL FIELD.
DSWB

B1.1 AHU-10
1
MCC-1 EMCC-1
3
AHU-03

C
P-16
E

C1 AHU-11 E 2 P-14
D

D
P-12 2

D
AHU-09

FESSION
PRO AL
E ED G . NO.
RE

ER

EN
REGIST

GINEER
10206
RF-9A RF-9C TRACY J.
D1 HAUSER

A
S

T
O
U O
T H K
D A
E E

AHU-06
11/25/14
E
No. Description Date
AHU-05
AHU-02
AHU-07

AHU-08
AHU-04
E1
E

E
E E
P-18
E D E E E
P-11 2 P-17

F
F1

INSTALL GREEN INSULATED


GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)

THIRD LEVEL DEMOLITION - ELECTRICAL NEUTRAL CONDUCTORS FOR


4TH & 5TH
1 1/8" = 1'-0"
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT THIRD LEVEL


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITON -
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
ELECTRICAL
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:32 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E031
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

SHEET NOTES
A
1 DEMOLISH ELECTRICAL CONNECTIONS SERVING PERIMETER
FAN COIL UNIT, DEMOLISH FAN COIL BRANCH CIRCUIT BACK
TO SOURCE ELECTRICAL PANEL. DISONNECT BRANCH
CIRCUIT FROM SOURCE CIRCUIT BREAKER AND LABEL
BREAKER AS SPARE. (TYPICAL FOR PATIENT ROOM FAN COIL
UNITS)
2 EXISTING TO REMAIN TELEPHONE CABINET. (TYPICAL FOR
'TTC' CABINETS)
3 EXISTING TO REMAIN CATV AND MUSIC SYSTEMS CABINET.
1 (TYPICAL FOR 'TVC' CABINETS)
PHASE 4 1
4 EXISTING TO REMAIN PUBLIC ADDRESS INTERCOM CABINET.

A1 5
(TYPICAL FOR 'ICC' CABINETS)
EXISTING TO REMAIN FIRE ALARM TERMINAL CABINET.
D D D D D D D D D (TYPICAL FOR 'FATC' CABINETS)
B
B.0 6 EXISTING TO REMAIN DICTATION SYSTEM CABINET. (TYPICAL
FOR 'DCTC' CABINETS)
7 CONSTRUCTION PHASE (TYPICAL)

D 1.7 2.1
D

B1.1
1
D D

E E
C 1
TTC4B NP4B
2

E
C1 E
TTC4A
D 3 TVC4 E D
4 ICC4 E E
5 FATC4
DCTC4
6
D D
E NP4C

E
CP4B PHASE 2 7

D
PHASE 3 E
NP4A
E
D CP4A
D
FESSION
PRO AL
ED G . NO.
RE

ER

EN
REGIST

GINEER
10206
D TRACY J.
D HAUSER

A
D1

T
E

O
U O
T H K
D A
TTC4C

11/25/14
NP4D LS4A
E
TTC4D
E E 1 E No. Description Date

D D

E1
D

F D D D D D D D D D

F1
PHASE 1

INSTALL GREEN INSULATED


GROUND WIRE WITH
LIGHTING, RECEPTACLE AND

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR

1
FOURTH LEVEL DEMOLITION - ELECTRICAL EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
4TH & 5TH
1/8" = 1'-0" SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT FOURTH LEVEL


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION -
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
ELECTRICAL
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:33 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E041
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

SHEET NOTES
A 1 DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS
BOUNDARY ARE DIAGRAMATIC, REFER TO TYPICAL NORTH &
SOUTH ROOM LAYOUT - 4TH/5TH LEVEL - DEMOLITION PLAN
(DETAIL 1, SHEET E400) FOR SPECIFIC DEMOLITION
REQUIREMENTS WITHIN THIS BOUNDARY.
2 EXISTING TO REMAIN TELEPHONE CABINET. (TYPICAL FOR
'TTC' CABINETS)
3 EXISTING TO REMAIN CATV AND MUSIC SYSTEMS CABINET.
(TYPICAL FOR 'TVC' CABINETS)
1 4 EXISTING TO REMAIN PUBLIC ADDRESS INTERCOM CABINET.
7 (TYPICAL FOR 'ICC' CABINETS)
12 PHASE 4
5
A1
EXISTING TO REMAIN FIRE ALARM TERMINAL CABINET.
(TYPICAL FOR 'FATC' CABINETS)
D D D D D D D D D 6 EXISTING TO REMAIN DICTATION SYSTEM CABINET. (TYPICAL
B
B.0
FOR 'DCTC' CABINETS)
7 DEMOLISH ELECTRICAL CONNECTIONS SERVING PERIMETER
V FAN COIL UNIT, DEMOLISH BRANCH CIRCUIT BACK TO SOURCE

TV

TV

TV

TV
TV

TV

TV

TV
V/2D V/2D V/2D V/2D V/2D V/2D V/3D V/3D ELECTRICAL PANEL. DISONNECT BRANCH CIRCUIT FROM
SOURCE CIRCUIT BREAKER AND LABEL BREAKER AS SPARE.
13 (TYPICAL FOR PATIENT ROOM FAN COIL UNITS)

D 1.7 2.1 TV
8 OWNER TO PROVIDE DEMOLITION OF EXISTING NURSE CALL
MASTER STATION AND CONTROL PANEL, PROVIDE DEMOLITION
9 D OF EXISTING SURFACE RACEWAY AT NURSE STATION.
1
9 DISCONNECT EXISTING ELECTRICAL CONNECTIONS TO
B1.1 EXHAUST FAN SERVING THIS ROOM. EXHAUST FAN LOCATED
ON ROOF ABOVE, DEMOLISH DISCONNECT SWITCH RETAIN
TV TV EXISTING CONDUIT FOR REUSE.
D D
10 LOCATION OF EXISTING DATA AND VOICE RACK CABINET.
PROVIDE PER DETAIL 2 ON SHEET E501.
LIMITS OF ELECTRICAL
DEMOLITION 11 PROVIDE SUPPORT DURING CEILING REPLACEMENT FOR
EXISTING TO REMAIN CEILING MOUNT DEVICES LOCATED WITHIN
COORIDOR. REMOVE AND REINSTALL IF REQUIRED. CLEAN AND
E E
C TTC5B
1
NP5B
REINSTALL EXISTING CEILING DEVICES UPON COMPLETION OF
NEW CEILING WORK. REFER TO EXISTING PLAN E12 AND E13,
2 INCLUDED FOR REFERENCE ONLY AS A PART OF ADDENDUM #3,
E400 FOR EXISTING CEILING DEVICES AND QUANTITIES.
11
12 CONSTRUCTION PHASE (TYPICAL).
C1
E
E TTC5A 13 LIGHTING, POWER AND SYSTEMS SHALL BE EXISTING TO
D 3 TVC5 REMAIN EXCEPT SPECIFIED DEMOLITION OF FAN COIL UNIT.
TV E MASTER TV D
(THIS ONE ROOM ONLY).

NC
4 ICC5 E E D
8
5 FATC5
DCTC5
TV 5 TV
D D
2
E NP5C
E501
E
12 PHASE 3 CP5B 11 PHASE 2 12
10
D
T5 8
CP E

NC
NP5A
D

11 CP5A E
D D
TV TV
FESSION
11 PRO AL
ED G . NO.
RE

ER

EN
REGIST

GINEER
10206
TRACY J.
D TV HAUSER
D

A
S

T
D1

O
U O
T H K
4 D A
E
E400
TTC5C
11/25/14
1 11
NP5D LS5A
E
TTC5D
No. Description Date
E E E

LIMITS OF ELECTRICAL
DEMOLITION

D D
TV 1 TV

E1
V/2D
D 4D
9
TV
D

V/2D V/2D V/2D V/2D V/2D V/2D V/2D V/2D


TV

TV

TV

TV

TV
TV

TV

TV

TV
F D D D D D D D D D

F1
12 PHASE 1

INSTALL GREEN INSULATED


GROUND WIRE WITH
LIGHTING, RECEPTACLE AND

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE 4TH & 5TH
FIFTH LEVEL DEMOLITION - ELECTRICAL CONDUCTOR SERVED FROM A
1 SINGLE POLE CIRCUIT BREAKER
1/8" = 1'-0"
2014 C COPYRIGHT FIFTH LEVEL
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DEMOLITION -
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
ELECTRICAL
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:34 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E051
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

A SHEET NOTES
1 DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS
BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL NORTH &
ELEVATOR LINK SOUTH ROOM LAYOUT - 5TH LEVEL - LIGHTING PLAN (DETAIL 2,
5900
SHEET E400) FOR SPECIFIC LIGHTING REQUIREMENTS WITHIN
THIS BOUNDARY.
2 PROVIDE INDIVIDUAL 120V, 20A TOGGLE SWITCH FOR
CONTROL OF EXAM PORTION OF LIGHT FIXTURE. PROVIDE
ENGRAVED FACEPLATE, PER SPECIFICATIONS, WITH LABEL
INDICATING 'EXAM LIGHT'.
8 PHASE 4 3 AMBIENT (ZONE 'd') AND READING (ZONE 'e') PORTION OF LIGHT
FIXTURE SHALL BE CONTROLLED BY NURSE CALL PILLOW
A1 D D D D D D D D SPEAKER. PROVIDE RELAY(S) TO INTERCONNECT NURSE CALL
D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 SYSTEM WITH AMBIENT AND READING PORTION OF LIGHT

B
B.0
D1 D1 D1 D1 D1
4
FIXTURE.
LIGHTING IN THIS ROOM SHALL BE EXISTING TO REMAIN.
A1 D1
H1 PATIENT RM H1 PATIENT RM PATIENT RM H1 PATIENT RM H1 H1 PATIENT RM PATIENT RM H1 H1 PATIENT RM PATIENT RM H1 D2 5 CONNECT TO EXISTING NORMAL SOURCE 120V, 20A LIGHTING
500 504 506 508 510 512 514 516 D1 H1 BRANCH CIRCUIT PREVIOUSLY SERVING DEMOLISHED DEVICES,
PATIENT RM W1 MADE AVAILABLE DURING DEMOLITION OF THIS PROJECT.

D
4 D1 D1 U2
502
OFFICE 6 WHERE MULTIPLE BRANCH CIRCUIT HOME RUNS ARE
1.7 2.1
D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D
558 NEGATIVE AIR INDICATED WITH IDENTICAL BRANCH CIRCUIT NUMBERS,
U2 520 COMBINE INDIVIDUAL ROOM BRANCH CIRCUITS INTO SINGLE
U2 U2 U2 U2 U2 U2 D1 D1 D1
W2 HOME RUN BACK TO SOURCE PANELBOARD. (TYPICAL)
W2 W2 W2 W2 D1
W2 W2
U2 U2 U2 U2 7 CONNECT TO NEAREST AVAILABLE 120V 20A LIFE SAFETY
B1.1 D2 U2 D1 W2 D2 U2 D1 D1 D2 W2
D1
D2 D2 U2 D1 D1
D2 D2 U2 D1
D2
W2
LIGHTING BRANCH CIRCUIT.
D1 D1 D1 CP5A2-10 D1 D1 Room D1 9 8 CONSTRUCTION PHASE (TYPICAL).
Room D D
566 522
9
D

A1 D1 A1 A1 A1 A1 D1 D1 A1 A1 D1 D1 A1 U2 DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS


D1 D1 D1
MECH. W1 BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL WEST &

D
W1 EAST ROOM LAYOUT - 5TH LEVEL - LIGHTING PLAN (DETAIL 5,
565 CORRIDOR W1 W1 W1 W1 W1 W1 W1 W1

D
D

D
H1 SHEET E400) FOR SPECIFIC LIGHTING REQUIREMENTS WITHIN
5901 CP5A2-14 H1
A1 A1 THIS BOUNDARY.
D1 D1 D2 E E D1 D1
CP5A2 D2
C CP5A2-9
TTC5B 1
NP5B
9 CP5B2-15 2 CP5A2-9 CP5A2-9 CP5A2-10 CP5A2-10 CP5A2-10
A1 CP5A2-10 CP5A2-14 A1
D1 H1 D1 D2 CP5A2-10 6 D2 D1 H1 D1
E400
W1 CP5B2-15 W1
C1
E
D

D
Room
Room
564 U2 U2
D TTC5A D 524
D1 D1 D1
ELEC D1 D1 D1
W2 W2
551
W2 D1 HSKG EQUIPMENT D1
552 553 W2
D1 Room
D1 D1 D1
D D Room
562
E NP5C U2 526
CP5A2-14 W1

D
D

E
D1 H1 D1 D2 CP5B D2 D1 H1 D1
8 PHASE 3 A1 CP5B2-27 A1 PHASE 2 8

D
CP5B2-15

A1 A1
D1 H1 D1 D2 D2 D1 H1 D1
CP5B2-18 NP5A E
SOILED UTILITY
W1 W1
D

D
559 E
Room CLEAN UTILITY Room
U2 U2
560 D 558 CP5A D 528

D1 D1 D1
D1 W2 D1 D1
W2
STOREROOM NUTRITION SOILED UTILITY STORAGE FESSION
W2 PRO AL
557 556 555 554 ED G . NO.
RE

ER

EN
D1 D1 D1

REGIST

GINEER
D
10206
TRACY J.
D1 E Room
5
HAUSER

A
W1 E400

S
530
D

T
O
U O
T H K
TTC5C D A
H1 CP5B2-27
D1 D1 D2 CP5B2-2 CP5B2-2 CP5B2-12
A1 CP5B2-18 CP5B2-12
1 CP5B2-12 CP5B2-12
NP5D LS5A CP5B2-12
E CP5B2
E E E
TTC5D 11/25/14

A1 CP5B2-18 5
A1 No. Description Date
D1 H1 D1 D2 D2 D1 H1 D1
W1 W1

D
D

D
W1 W1 W1 W1 W1 W1 W1

D
D

W1 7 W1
D

D
Room
556
U2 CP5B2-2 A1 D1 CP5B2-2 D1 A1 A1 D1 CP5B2-2 D1 A1 D1 A1 A1 D1 A1 A1 D1 D1 A1 U2
D D

D1 D1 D1
5 D2 W2
E1 W2 D2
U2 U2
D2 D2
U2
D1
D1
U2 D2 U2 D2 D2
U2
U2 D2 D2
U2 D1
U2
D1
D1 D1 D1

c bW2 D1 D1 D1 D1 D1
g W2 W2 W2 W2 W2 W2 W2 W2 LS
2 U2 U2 U2 U2 U2 U2 U2 W2 U2
D1 D1 a D1
g L1 A1 LS A1 A1 A1
f ISOLATION b D a
554 F W FAMILY WAITING
5
U2 i D1 D1 D1 D1 D1 D1 D1 D1 D1 558
f c W1 D1 D1 D1 D1 D1 D1 D1 D1 D1 W1
D

E501
i
D1 H1 D1 PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM D1
L1 H1 H1 H1 H1 H1 H1 H1 A1 A1 A1
f b D2 h A1 550 548 546 544 542 540 538 536 534 STORAGE
i h
d,e 3 560 F W F W
F D1
D1 D1 D1 D1 D1
RESTROOM
559
D1 D D D D
D1 D
D1 D1 D
D1 D1 D D1 D1 D D1 D1 D

F1
8 PHASE 1

INSTALL GREEN INSULATED


GROUND WIRE WITH

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
FIFTH LEVEL - LIGHTING INSTALL INDIVIDUAL (DEDICATED)

1 1/8" = 1'-0"
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE 4TH & 5TH
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT FIFTH LEVEL -


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE LIGHTING PLAN
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:39 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E151
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

1937
HSKG
UTILITY
1933
1932
AVERA FACILITY DEVELOPMENT
ELEC /
DISCONNECT TELECOM
ELEVATOR 2
1904 1903
2331 SHEET NOTES
'MSB11'
PHYS/ COUR CONFERENCE 1 EQUIPMENT DISTRIBUTION PANEL (EDP) 600A 3PH 3W.
ROOM
E
ENTRANCE MAIL ROOM
1942 1941 1907 E 2 CRITICAL DISTRUBITION PANEL (CDP).
ELEVATOR 1
FIRE
E 2330
SPRINKLER 3 NON-ENERGIZED EQUIPMENT.
ROOM
1905 4
E E UP LIFE SAFETY TRANSFER SWITCH.
5 EQUIPMENT TRANSFER SWITCH.
CORRIDOR
OFFICE 1902 6
1943
CRITICAL TRANSFER SWITCH.
EXISTING 800KW 7 RECOMMENDED LOCATION FOR ROUTING OF NEW
DIESEL GENERATOR EP3A 2" CONDUIT AND TWO ATS-CDP2 2" CONDUITS UP
GENERATOR VOLUNTEER TO 3RD LEVEL. CORE DRILL CONCRETE FLOOR IN PAN
OFFICE PORTION OF STRUCTURE, AS CLOSE TO COLUMN AS
ROOM 1909 ENTRY
1970 RECEPTION 1000
POSSIBLE. REFER TO ARCHITECTURAL DRAWINGS
OFFICE
1944 CONFERENCE 1901 FOR CONDUIT CHASE CONSTRUCTION
1908 REQUIREMENTS. COORDINATE EXACT CONDUIT
'HGEN' ROUTING WITH OWNER PRIOR TO INSTALLATION.
VOLUNTEER
E WORKROOM PERFORM WORK WITH MINIMAL IMPACT TO OWNER.
1910 SEAL ALL FLOOR PENETRATIONS AND PENETRATIONS
ELEVATOR 3
THROUGH RATED WALLS.
CATH LAB
ESSENTIAL 2332
8
E ROUTE TWO (2) 2" CONDUITS FOR ATS-CDP2
E BRANCHES
OLD GENERATOR THROUGH EXISTING TUNNEL TO MECHANICAL ROOM
ROOM REGISTRATION
ROOM 'EDP-A' 6 ATS-2 CONFERENCE WAITING 1031. FROM MECHANICAL ROOM ROUTE CONDUITS
E 1945 1911 OVER TO COLUMN INDICATED BY SHEET NOTE 7 FOR
1971
E ROUTING UP TO THIRD LEVEL.
5 ATS-3 4 1 'EDP' CORRIDOR
ATS-1 E 1940
3 'GDP'
E GIFT SHOP
E E E E
E 1005
'EP1A'
A LOBBY
1900
'CDP' 2 COPY
CENTER
1947
REGISTRATION REGISTRATION
1912 1913

CORRIDOR
1946 STORAGE
EXISTING MECHANICAL
OUTLINE OF PATIENT
8 1949
TUNNEL 1031 TOWER ABOVE.
ROOM
WORKROOM

A1
1006
HSKG 1914
1950

B
B.0 CONFERENCE ROOM
1704 1007
MCC-4 CORRIDOR
1017
UNASSIGNED
1008

'US-1'
B1.1
MEN'S WOMEN'S
HOSP. MAIN TOILET TOILET
SURGEON ELEC ROOM 1029 1028
TOILET LOUNGE 1030A MEDITATION
TOILET 1802 MEN'S 1807 PHYSICIAN ROOM
1804 LOCKER LOUNGE 1009

C
ROOM 1703 EXIT
1801 PASSAGE
WOMEN'S 1034
LOCKER
ROOM
'MSWB'
OFFICE
EQUIPMENT 1803

C1
1702 RECEPTION
1555 1600 IMAGING
7 WAITING
1961

TOILET STAIR
1538A 1
FESSION
EXIT PRO AL
PASSAGE ED G . NO.
RE

ER

EN
1033

REGIST

GINEER
TOILET 10206
TOILET 1541A CONSULT
PRE/POST 1549A PRE/POST PRE/POST (FUTURE TRACY J.
1538 1549 1545 PRE/POST OFFICE PRE-OP PRE-OP) HAUSER

A
1541 1556 MED. 1611 1608

T
O
U O

D
TOILET AFFAIRS PRE-OP OFFICE
T H
D A
K
1545A OFFICE 1612 1011 IMAGING
1614 IMAGING WAITING
RECEPTION 1963
1962
11/25/14
PRE/POST
1536
HALLWAY CLEAN No. Description Date
1603 HALLWAY SUPPLY
HSKPG 1602 1628
1537

TOILET NURSE
PRE/POST PRE/POST PRE/POST
1536A TOILET STATION TOILET TOILET
1551 1547 1543

D1
1535A 1520 1617 1620A
TOILET
PRE-OP /
1551A SOILED
INPT HOLD PRE-OP PRE-OP
HOLD
1616 1618 1620
1020
HSKPG

E PRE/POST
1535 PACU PACU
NURSE
STATION
TOILET
1619
1621

PACU 1525 1523 1519


1527

HALLWAY
1622
SOILED

E1 HOLD
1532
BREAK
STAFF ROOM
TOILET 1021
STAFF CONTROL DIRECTOR'S ANES.
1019
TOILET DESK OFFICE OFFICE
1531 1625 1626 1627
DECONTAM HALLWAY
PACU
PACU 1508 1022
PACU PACU ISOLATION SERVICE
PACU ISOLATION
1529 1528 PACU 1522 ACCESS
1526 1521
1524 1604

F HSKP
SUB
F1
1512A
STERILE
1507
Stair O.R. 2
3 1501
INSTALL GREEN INSULATED
GROUND WIRE WITH
98 1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
4TH & 5TH
FIRST LEVEL - POWER
1
SINGLE POLE CIRCUIT BREAKER
3/32" = 1'-0"
2014 C COPYRIGHT FIRST LEVEL -
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE POWER PLAN
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:40 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E211
www.specializedeng.com Scale 3/32" = 1'-0"
98.5 1.3 2.4 3.4 3.6

GENERATOR
ROOM

AVERA FACILITY DEVELOPMENT


LOCATED ON FIRST FLOOR
APPROXIMATELY 20FT NORTH &
EXISTING EMERGENCY 56FT WEST OF THIS LOCATION
A SWITCHBOARD 'HGEN' SHEET NOTES
1 RECOMMENDED LOCATION FOR ROUTING OF NEW EP3A 2"
CONDUIT AND TWO ATS-CDP2 2" CONDUITS FROM 1ST
LEVEL BELOW. CORE DRILL CONCRETE FLOOR IN PAN
PORTION OF STRUCTURE, AS CLOSE TO COLUMN AS
POSSIBLE. ROUTE CONDUITS ON THIS FLOOR OVERHEAD
TO ELECTRICAL EQUIPMENT BEING SERVED. COORDINATE
EXACT CONDUIT ROUTING WITH OWNER PRIOR TO
EQUIPMENT BRANCH INSTALLATION. PERFORM WORK WITH MINIMAL IMPACT TO
OLD OWNER. SEAL ALL FLOOR PENETRATIONS AND
DIST. PANEL 'EDP-A'
GENERATOR PENETRATIONS THROUGH RATED WALLS.
ROOM

A1
B
B.0 E
P-15

E E

E
1.7 2.1 MCC-2 MCC-3

DSWB

B1.1
HOSP. MAIN
ELEC ROOM

MCC-1 EMCC-1
LOCATED ON FIRST FLOOR AHU-03
APPROXIMATELY 23FT WEST
OF THIS LOCATION

C
EXISTING NORMAL
SWITCHBOARD 'MSWB' 1 P-16
E

C1 AHU-11 E

D
AHU-09

EP3A

CDP-2
XFMR-CDP2
ATS-CDP2 FESSION
PRO AL
ED G . NO.
RE

ER
E

EN
REGIST

GINEER
10206
TRACY J.
RF-9A RF-9C
HAUSER
D1

A
S

T
O
U O
T H K
D A

E E

AHU-06 11/25/14

E AHU-10
No. Description Date
AHU-05
AHU-02
AHU-07

AHU-08
AHU-04
E1
E

E
E E
P-18
E E E E
P-17

F
F1

INSTALL GREEN INSULATED


GROUND WIRE WITH
LIGHTING, RECEPTACLE AND

98 1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
THIRD LEVEL - POWER EACH 120V OR 277V PHASE 4TH & 5TH
1 1/8" = 1'-0" CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT THIRD LEVEL -


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE POWER PLAN
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:41 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E231
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

A SHEET NOTES
1 CONNECT FIRE/SMOKE DAMPERS TO A COMMON 120V 20A LIFE
SAFETY BRANCH CIRCUIT FROM PANEL 'LS4A'. PROVIDE 20/1 CIRCUIT
BREAKER WITHIN PANEL, MATCH EXISTING MANUFACTURER AND
RATINGS OF EXISTING. PROVIDE #10 CONDUCTORS. PROVIDE ONE
DUCT TYPE SMOKE DETECTOR WITHIN 5' OF EACH SIDE OF
FIRE/SMOKE DAMPER (TOTAL OF TWO (2) DETECTORS PER
FIRE/SMOKE DAMPER). (TYPICAL)

A1
B
B.0 1 1

FS.D.
FS.D.
FS.D.
1

1.7 2.1

B1.1

E E
C TTC4B
NP4B

E
C1 E TTC4A
TVC4 E
ICC4
E E
FATC4

DCTC4

E NP4C

E
CP4B

D
NP4A E

E
CP4A

FESSION
PRO AL
ED G . NO.
RE

ER

EN
REGIST

GINEER
10206
TRACY J.
HAUSER
D1

A
S
E

T
O
U O
T H K
D A
TTC4C

TTC4D 11/25/14
NP4D LS4A
E E E E No. Description Date

E1

1
FS.D.

1 1

FS.D.

FS.D.
F1

INSTALL GREEN INSULATED


GROUND WIRE WITH
LIGHTING, RECEPTACLE AND

1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR

FOURTH LEVEL - POWER EACH 120V OR 277V PHASE 4TH & 5TH
1 1/8" = 1'-0"
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT FOURTH LEVEL -


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE POWER AND
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
SYSTEMS PLAN
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:42 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E241
www.specializedeng.com Scale 1/8" = 1'-0"
98.5 1.3 2.4 3.4 3.6

AVERA FACILITY DEVELOPMENT

A SHEET NOTES
1 DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS
BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL NORTH &
ELEVATOR LINK SOUTH ROOM LAYOUT - 5TH LEVEL - POWER PLAN (DETAIL 3,
5900 SHEET E400) FOR SPECIFIC POWER & SYSTEMS REQUIREMENTS
WITHIN THIS BOUNDARY.
2 REFER TO ENLARGED FLOOR PLAN FOR BRANCH CIRCUITING
REQUIREMENTS.

3 CONNECT FIRE/SMOKE DAMPERS TO A COMMON 120V 20A LIFE


9 PHASE 4 SAFETY BRANCH CIRCUIT FROM PANEL 'LS5A'. PROVIDE 20/1
CIRCUIT BREAKER WITH PANEL, MATCH EXISTING
A1 10
MANUFACTURER AND RATINGS OF EXISTING. PROVIDE #10
CONDUCTORS. (TYPICAL)

B
B.0
4 CONNECT TO EXISTING NORMAL SOURCE 120V, 20A RECEPTACLE

FS.D.
NC NC BRANCH CIRCUIT PREVIOUSLY SERVING DEMOLISHED DEVICES,
3 3 PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM MADE AVAILABLE DURING DEMOLITION OF THIS PROJECT.

FS.D.
500 504 506 508 510 512 514 516 NC NC

FS.D.
502

TV

TV

TV

TV
TV

TV

TV

TV
5 REFER TO TYPICAL NORTH & SOUTH ROOM LAYOUT - 5TH LEVEL -

NC

NC

NC

NC
NC

NC

NC

NC
8 POWER PLAN (DETAIL 3, SHEET E400) FOR SPECIFIC HEADWALL

NC

NC

NC

NC
NC

NC

NC

NC
NEGATIVE AIR
3 DEVICE LOCATIONS AND BRANCH CIRCUITING REQUIREMENTS.
OFFICE 520

1.7 2.1

NC
NC

NC

NC
NC

NC

NC
E, 65"

NC
5902 EF-1 6 6 NEW EXHAUST FAN EF-1 (1/2HP, 120V) LOCATED ON ROOF ABOVE
2 CP5A2-12 TV E, 65" E AT APPROXIMATELY THIS LOCATION. SEE SHEET M161.

NC
CP5A2-1 CP5A2-2 CP5A2-5 CP5A2-7
2 2 CP5A2-4 NC 7 NEW EXHAUST FAN EF-2 (3/4HP, 120V) LOCATED ON ROOF ABOVE
2 2
CP5A2-3 CP5A2-6 CP5A2-8 AT APPROXIMATELY THIS LOCATION. SEE SHEET M161
B1.1
2
NC 2 2 2 NC

NC

NC

NC

NC

NC

NC

NC

NC
NC 8 POWER AND SYSTEMS IN THIS ROOM SHALL BE EXISTING TO

NC
CP5B2-26 CP5A2-19
TV TV REMAIN EXCEPT SPECIFIED DEMOLITION OF FAN COIL UNIT.
2 2
9 CONSTRUCTION PHASE (TYPICAL).
Room 10 DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS

NC

NC

NC

NC
Room

NC

NC

NC

NC
10 BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL WEST &
566 CORRIDOR 522
NC 5901 NC EAST ROOM LAYOUT - 5TH LEVEL - POWER PLAN (DETAIL 6,
MECH. SHEET E400) FOR SPECIFIC POWER & SYSTEMS REQUIREMENTS
NC NC565 NC CP5A2 NC NC NC WITHIN THIS BOUNDARY.
E E
C
NC NC NC NC NC NC NC NC
TTC5B 1 NP5B
NC NC NC 3 NC NC NC
NC E400 NC

E
C1 Room
564 2 E TTC5A 2
Room
524
TVC5
TV CP5B2-25
NC E ELEC MASTER NC TV

NC
ICC5 CP5A2-20
E 551
NC E
FATC5 NC

8"x 2"
NC DCTC5 NC
HSKG EQUIPMENT CP5A2-21
1
552 553
TV CP5B2-24 NC NC 2 TV
2
2
Room E NP5C
562 (3) 4"C. E501 Room
E 526
NC CP5B NC
9 PHASE 3 PHASE 2 9
NC NC NC NC NC NC
D NC NC NC 8"x 2"
T51
T52 NC NC NC
T53
NC T54 NC
CP NP5A E

NC
SOILED UTILITY
CLEAN UTILITY 559 E Room
Room 558
CP5A 528
560 2
2

8"x 2"
TV CP5B2-23 NC TV
NC CP5A2-22
NC NC
STOREROOM NUTRITION SOILED UTILITY STORAGE FESSION
NC 557 556 555 554 PRO AL
NC ED G . NO.
RE

ER

EN
TV CP5B2-22

REGIST

GINEER
2 10206

D1 6 TRACY J.
E Room
HAUSER

A
530 E400

T
O
U O
TTC5C T H
D A
K

NC
NC NC NC CP5B2 NP5D LS5A 1
E NC NC NC NC NC E E NC NC NC NC NC E
TTC5D
NC NC NC NC NC
11/25/14

NC NC No. Description Date


NC

NC

NC

NC
NC

NC

NC

NC

NC
Room
556
2 2
TV TV
CP5B2-21 NC CP5A2-23
NC

NC

NC
NC

NC

NC

NC

NC

NC

NC
E1 NC
2
2
2
2 NC NC
CP5B2-8 2 2 2 CP5B2-3 4
4 NC 2 CP5B2-10 2 CP5B2-5
CP5B2-6
E, 65" CP5B2-11 CP5B2-9 CP5B2-7 CP5B2-4
E, 65" TV
7 EF-2 CP5B2-13 2

NC

NC
NC

NC
NC
NC

NC
NC

NC

5 T FAMILY WAITING
4 ISOLATION 558
NC

NC

NC

NC
NC

NC

NC

NC

NC
2D G
554 G 44" 3 RESTROOM
NC

NC

NC

NC
NC

NC

NC

NC

NC
V/D BSID2D G 44" 559
FS.D.

STORAGE
TV

TV

TV

TV

TV
TV

TV

TV

TV
NC NC PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM PATIENT RM T
550 548 546 544 538 536 534 560 T
PULL 542 540 3 3
NC BED NC
F

FS.D.

FS.D.
APULL

F1
9 PHASE 1

INSTALL GREEN INSULATED


GROUND WIRE WITH
1b 99 1 1c 2b 3c 3A 4 4a 5 5.1 6 B1.2
7 8 LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
FIFTH LEVEL - POWER
1
NEUTRAL CONDUCTORS FOR
1/8" = 1'-0" EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
4TH & 5TH
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT FIFTH LEVEL -


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE POWER AND
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
SYSTEMS PLAN
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:49 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E251
www.specializedeng.com Scale 1/8" = 1'-0"
SHEET NOTES GENERAL NOTES
1 UNLESS OTHERWISE NOTED, PROVIDE DEMOLITION OF LIGHTING, POWER, & A. PROVIDE DEVICE'S MOUNTING HEIGHTS PER ARCHITECTURAL INTERIOR
SYSTEMS DEVICES AS REQUIRED FOR DEMOLITION, LOCATED WITHIN ELEVATIONS.
BOUNDARY. RETAIN LIGHTING AND POWER BRANCH CIRCUITS. DEMOLISH BACK
TO SOURCE CABINET INTERCOM AND DICTATION SYSTEM DEVICES.
B. PROVIDE FOR PATIENT ROOMS RENOVATED BY THIS PROJECT PER TYPICAL AVERA FACILITY DEVELOPMENT
PATIENT ROOMS INDICATED ON THIS SHEET.
2 EXISTING BACK BOX AND CONDUIT IN FOOTWALL SHALL REMAIN, DEMOLISH
1 EXISTING DEVICE AND CRITICAL BRANCH CIRCUIT BACK TO SOURCE
A1 PANELBOARD. PROVIDE NEW DEVICE AND BRANCH CIRCUIT AS INDICATED ON
A1 NEW WORK FLOOR PLAN.
A1 D
3 DEMOLISH EXISTING COMMUNICATIONS OUTLET AND ASSOCIATED CONDUIT IN
WALL. EXISTING TWISTED PAIR VOICE CABLING, DISCONNECT AT BOTH ENDS
f AND DEMOLISH BACK TO SOURCE CORRIDOR TELEPHONE CABINET. RETAIN
B EXISTING DATA CABLING, FIELD VERIFY QUANTITIES INDICATED ON FLOOR PLAN.

B.0
12 D1 D1
B COIL CABLING UP IN CEILING ABOVE AND PROTECT DURING CONSTRUCTION FOR
V/D B f f
B.0
REUSE. REUSE EXISTING CABLING TO SERVE DEVICE(S) INDICATED ON NEW
WORK FLOOR PLAN. (TYPICAL FOR COMMUNICATIONS OUTLETS INDICATED AS
B.0 DEMO)
4 EXISTING BRANCH CIRCUITS SERVING DEMOLISHED ELECTRICAL DEVICES SHALL
BE REUSED AS INDICATED PER ENLARGED FLOOR PLANS. WHERE EXISTING
E, 65" BRANCH CIRCUITS SHARE COMMON NEUTRAL CONDUCTOR, PROVIDE ADDITIONAL
BSID (EXAM) H1 D
TV

10 E, 65" NEUTRAL CONDUCTOR(S) WITHIN EXISTING CONDUIT AS REQUIRED FOR ALL 120V

NC
d,e V/2D

TV
c BRANCH CIRCUITS TO HAVE DEDICATED NEUTRAL CONDUCTORS.
D

NC
E, 65" 2D 3
BED 4 5 DEMOLISH WALL MOUNT NURSE CALL DOME LIGHT AT THIS LOCATION.
E, 65" 7
6 UTILIZE EXISTING DATA CABLING PREVIOUSLY SERVING DEMOLISHED DATA
2 OUTLET.
9 D1 D1
2D c 7 EXISTING TELEVISION POWER RECEPTACLE BRANCH CIRCUITS AND
54" b b b
54" DEMOLISHED FAN COIL UNIT BRANCH CIRCUIT SHARE COMMON NEUTRAL.
PB 6
NC

REFER TO FLOOR PLANS FOR BRANCH CIRCUITS SERVING EXISTING TO REMAIN


RECEPTACLES. PROVIDE ONE (1) ADDITIONAL NEUTRAL CONDUCTOR FOR
CP5B2-1 42" DEDICATED NEUTRALS FOR EXISTING TO REMAIN BRANCH CIRCUITS.
13 8 DISCONNECT EXISTING CATV CABLING FROM DEMOLISHED OUTLET AND COIL
U2
ABOVE CEILING FOR REUSE. PROTECT CABLING DURING CONSTRUCTION,
EXTEND CABLING TO NEW LOCATION AS INDICATED ON NEW WORK FLOOR PLAN.
B1.1 W2
a U2 DEMOLISH UNUSED CATV CABLING BACK TO SOURCE.
B1.1
NC

D1
B1.1
PULL g SHOWER
D2 9 PROVIDE INDIVIDUAL120V, 20A TOGGLE SWITCH FOR CONTROL OF EXAM
PORTION OF LIGHT FIXTURE. PROVIDE ENGRAVED FACEPLATE, PER
SPECIFICATIONS, WITH LABEL INDICATING 'EXAM LIGHT'.
10 AMBIENT (ZONE 'd') AND READING (ZONE 'e') PORTION OF LIGHT FIXTURE SHALL BE
CONTROLLED BY NURSE CALL PILLOW SPEAKER. PROVIDE RELAY(S) TO
CP5A2-9 INTERCONNECT NURSE CALL SYSTEM WITH AMBIENT AND READING PORTION OF
LIGHT FIXTURE.
14
12 APULL A1 11 UTILIZE EXISTING CATV CABLING TO SERVE NEW OUTLET ON NEW WALL.
(TYPICAL)
NC

a
D1
12 CONNECT TO EXISTING NORMAL SOURCE 120V, 20A RECEPTACLE BRANCH CIRCUIT
G 44"
g PREVIOUSLY SERVING DEMOLISHED DEVICES, MADE AVAILABLE DURING DEMOLITION
OF THIS PROJECT.
a W1

D
5 13 REFER TO 1/8" SCALE FLOOR PLANS FOR CRITICAL BRANCH CIRCUIT SERVING
DOME 15 EACH PATIENT ROOM.
NC
14 REFER TO FLOOR PLANS FOR CRITICAL LIGHTING BRANCH CIRCUIT SERVING EACH
PATIENT ROOM. WHERE BRANCH CIRCUIT IS INDICATED IN MULTIPLE PATIENT
ROOMS, ASSOCIATED LIGHTING SHALL SHARE COMMON BRANCH CIRCUIT INDICATED.
TYPICAL NORTH & SOUTH PATIENT ROOM LAYOUT - TYPICAL NORTH & SOUTH PATIENT ROOM LAYOUT - TYPICAL NORTH & SOUTH PATIENT ROOM LAYOUT - 15 CONNECT TO EXISTING NORMAL SOURCE 120V, 20A LIGHTING BRANCH CIRCUIT
PREVIOUSLY SERVING DEMOLISHED DEVICES, MADE AVAILABLE DURING DEMOLITION
5TH LEVEL - POWER AND SYSTEMS 5TH LEVEL - LIGHTING 5TH LEVEL - DEMO (SIMILAR FOR EAST & WEST PATIENT ROOMS) OF THIS PROJECT.
3 1/4" = 1'-0"
2 1/4" = 1'-0"
1 1/4" = 1'-0"

FESSION
NC b c D PRO AL
W2 g ED G . NO.
PB RE

ER

EN
TV 15 TV

REGIST

GINEER
NC E, 65" E, 65" 7 E, 65" E, 65" 10206
D1 D1
a b D1 f TRACY J.
DOME
HAUSER

A
S
12

T
O
g U O
a D T H
D A
K

U2
D1 G, 44" D1 W1
CP5B2-27 D1 4
11/25/14
f

D
CP5A2-24 14 c
13 12 No. Description Date

6 H1
SHOWER

SHOWER

2D BED V/D A1 D1
NC D2 b
APULL PULL D1 f
3 V
NC NC BSID NC 10 de D
E E E

TYPICAL EAST & WEST PATIENT ROOM LAYOUT - TYPICAL EAST & WEST PATIENT ROOM LAYOUT - 8
8 8
5TH LEVEL - POWER AND SYSTEMS 5TH LEVEL - LIGHTING FIFTH LEVEL DEMOLITION - ELECTRICAL - Callout 1
6 1/4" = 1'-0"
5 1/4" = 1'-0"
4 1/4" = 1'-0"

INSTALL GREEN INSULATED


GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
4TH & 5TH
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT ENLARGED FLOOR


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PLANS & TYPICAL
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
ROOM LAYOUTS
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:50 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E400
www.specializedeng.com Scale NONE
EQUIPMENT CONNECTION SCHEDULE LIGHTING FIXTURE SCHEDULE
HP/KW/ STARTER/ CONTROL KEY FIXTURE INPUT
MARK DESCRIPTION FLA VOLTS PHASE MCA MOCP LOAD. CONTROLLER TYPE DISCONNECT FEEDER PANEL. GEN NOTES NO. SUBS MANUFACTURER CATALOG NO. (NOTE A) LAMP VOLTAGE WATTS MOUNTING DESCRIPTION NOTES AVERA FACILITY DEVELOPMENT
AHU-10-RF-1 AIR HANDLING UNIT 10 HP 480 V 3 17.5 35 11639 VA VFD DDC/FA STOP DIV 15 (1M) (1/2 - 10 HP 480V) 3-#12, #12 GND - 3/4"C. EP3A Yes A1 P LITHONIA 2VT8-2-17-ADP-MVOLT-GEB10IS (2) 17W T8 120 V 36 W CEILING RECESSED 2x2 VOLUMETRIC - 2 LAMP
AHU-10-RF-2 AIR HANDLING UNIT 10 HP 480 V 3 17.5 35 11639 VA VFD DDC/FA STOP DIV 15 (1M) (1/2 - 10 HP 480V) 3-#12, #12 GND - 3/4"C. MCC-1 No NOTE 1 D1 P WILA 621-549-DA60-80-120-DFS-BDIM LED 120 V 15 W CEILING RECESSED 4" LOW PROFILE DOWNLIGHT
AHU-10-SF-1 AIR HANDLING UNIT 20 HP 480 V 3 33.8 70 22447 VA VFD DDC/FA STOP DIV 15 (3M) (20 HP 480V) 3-#8, #8 GND - 1"C. EP3A Yes D2 P GOTHAM EVO-35-10-6-DFR-MVOLT LED 120 V 22 W CEILING RECESSED 6" SHOWER LIGHT
AHU-10-SF-2 AIR HANDLING UNIT 20 HP 480 V 3 33.8 70 22447 VA VFD DDC/FA STOP DIV 15 (3M) (20 HP 480V) 3-#8, #8 GND - 1"C. MCC-1 No NOTE 1 H1 P KENALL MPC24-G-1/1/3-50B-120-L-LVC (5) F50TT (BIAX) 120 V 278 W CEILING RECESSED 2x4 MULTIFUNCTION EXAM LIGHT
EF-1 EXHAUST FAN 1/2 HP 120 V 1 17.3 20 1176 VA DIV 15 CONT. DIV 15 (1M1) (1/6 - 1 HP 120V) 2-#12, #12 GND - 3/4"C. CP5A2 Yes L1 P LITHONIA SP8-G-2-32-A12125-MVOLT-GEB10RS 2 -32W T8 120 V 66 W CEILING RECESSED 2x4 LENSED TROFFER
EF-2 EXHAUST FAN 3/4 HP 120 V 1 17.3 35 1656 VA DIV 15 CONT. DIV 15 (1M1) (1/6 - 1 HP 120V) 2-#12, #12 GND - 3/4"C. CP5B2 No U2 P HEALTHCARE HUC523-120-LED35-AM LED 120 V 14 W SURFACE 2' UNDERCABINET TASK LIGHT
W1 P TECH LIGHTING 700BCLYNN-W-S-LED LED 120 V 20 W WALL SURFACE VANITY NOTE 1
KEY NOTES: (EQUIPMENT CONNECTION SCHEDULE) W2 P HEALTHCARE HNL610-MVOLT-LEDAMB-AM LED 120 V 3W WALL RECESSED NIGHT LIGHT NOTE 1

1. PROVIDE NEW FUSED SWITCH WITHIN EXISTING MOTOR CONTROL CENTER, SWITCH SHALL MATCH MANUFACTURER AND RATINGS OF EXISTING.
KEY NOTES:
GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE) 1. WALL MOUNTING - COORDINATE EXACT MOUNTING LOCATION WITH ARCHITECT AND ARCHITECTURAL DETAILS.
A. EQUIPMENT LISTED MAY NOT BE UNIQUE, VERIFY QUANTITY ON PLANS. REFER TO DEFINITIONS BELOW FOR CLARIFICATION OF CONNECTION REQUIREMENTS. 2. PENDANT/SUSPENSION MOUNTING - COORDINATE EXACT LOCATION, MOUNTING ELEVATION, AND REQUIRED PENDANT/SUSPENSION LENGTH
B. ITEMS NOTED AS "NA" ARE NOT APPLICABLE TO THE CONNECTION. WITH ARCHITECT AND ARCHITECTURAL DETAILS.
C. "STARTER/CONTROLLER" - PROVIDE STARTER AND ASSOCIATED CONNECTIONS TO EQUIPMENT AND BRANCH CIRCUIT: GENERAL NOTES:
·"MAG" = COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT (COORDINATE COIL VOLTAGE WITH CONTROL SOURCE).
·"MAN" = COMBINATION MANUAL MOTOR STARTER WITH DISCONNECT. A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS AND CATALOG NUMBER
·"DIV 15" = STARTER OR CONTROLLER IS FURNISHED BY MECHANICAL CONTRACTOR, TEMPERATURE CONTROLS CONTRACTOR, OR PROVIDED WITH PRIOR TO ORDERING.
·EQUIPMENT. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR THESE LOOSE STARTERS AND CONTROLLERS. B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH 'P' (PRIOR APPROVAL),
·"VFD-___" = VARIABLE FREQUENCY DRIVE CONTROLLER FURNISHED BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM. WHERE INDICATED WITH 'Y' (YES), THE
AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE VFD CONTROLLERS FURNISHED BY THE MECHANICAL CONTRACTOR. REFER TO MECHANICAL DOCUMENTS FOR VFD LOCATIONS AND FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF
QUANTITIES. THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND CHARACTERISTICS AS THAT SCHEDULED:
·"INT" = STARTER/CONTROLLER IS MANUFACTURED INTEGRAL TO THE EQUIPMENT. 1. ACUITY BRANDS
·LOCATE STARTER/CONTROLLER ADJACENT TO INDOOR EQUIPMENT - PROVIDE WITH STRUT MOUNTING AS REQUIRED. 2. COOPER
·WHERE STARTER SERVES OUTDOOR EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM. 3. HUBBELL
D. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS: 4. WILLIAMS
·"INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED). SEE PROJECT SPECIFICATIONS FOR SPECIFIC MANUFACTURER/MODEL EQUIVALENCY OF COMMONLY USED LIGHTING FIXTURE TYPES.
·"CONT" = EQUIPMENT OPERATES CONTINUOUSLY (NO CONTROLS). ABSENCE OF A SELECTION INDICATES THAT PRIOR APPROVALS ARE REQUIRED.
·"NONE" = EQUIPMENT OPERATES CONTINUOUSLY OR CONTROLS ARE SELF-CONTAINED. C. DOWNLIGHT CEILING TRIM FINISH/COLOR SELECTION:
·"DDC" = CONTROL SIGNAL FROM TEMPERATURE CONTROL SYSTEM PROVIDED BY MECHANICAL CONTRACTOR OR TEMPERATURE CONTROLS CONTRACTOR. PROVIDE DOWNLIGHT REFLECTOR FINISH/COLOR AS SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE. SELECT CEILING TRIM FINISH/COLOR
·"TIME SW" = CONTROL SIGNAL FROM TIME SWITCH PROVIDED BY ELECTRICAL CONTRACTOR. TIME SWITCH SHALL BE 7-DAY DIGITAL TYPE WITH AUTOMATIC TO COORDINATE WITH CEILING TYPE. "WHITE" TRIM FOR DOWNLIGHTS MOUNTED IN WHITE ACOUSTICAL TILE CEILINGS. "CLEAR" (TO MATCH
DAYLIGHT SAVINGS ADJUSTMENTS AND BATTERY BACKUP. LOCATE TIMESWITCH IN NEAREST MECHANICAL OR ELECTRICAL UTILITY ROOM. LABEL TIME REFLECTOR FINISH/COLOR) FOR DOWNLIGHTS MOUNTED IN PAINTED GYPSUM BOARD CEILINGS.
SWITCH. COORDINATE TIME SCHEDULE WITH OWNER AND MECHANICAL ENGINEER.
·"WALL SW" = CONTROL SIGNAL FROM WALL SWITCH PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE LOCATION OF WALL SWITCH WITH OWNER. LABEL D. PRIOR APPROVALS - THE FOLLOWING MANUFACTURERS ARE APPROVED EQUALS FOR THE FIXTURE TYPE INDICATED:
WALL SWITCH. A1 - COLUMBIA LIGHTING
·"FA STOP" = FANS WITH CFM OF 2000 OR GREATER AND FANS SERVING DUCTS CONTAINING SMOKE DAMPERS. FIRE ALARM SYSTEM SHALL SHUTDOWN D1 & D2 - PRESCOLITE
FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL ADDRESSABLE CONTROL MODULE AT H1 - NEW STAR LIGHTING
MOTOR CONTROLLER/STARTER AND CONNECT TO SHUTDOWN FAN. L1 - COLUMBIA
·"FA START" = FANS USED FOR SMOKE EVACUATION OR PRESSURIZATION. FIRE ALARM SYSTEM SHALL START FAN UPON DETECTION OF SMOKE IN DUCT P1 - AFX INC.
OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL ADDRESSABLE CONTROL MODULE AT MOTOR CONTROLLER/STARTER AND CONNECT TO W1 - ACCESS LIGHTING
START FAN. W2 - NEW STAR LIGHTING
·"DATA" = PROVIDE WITH DATA CONNECTION FROM NEAREST DATA NETWORK COMMUNICATIONS ROOM.
·"CONDUIT" = PROVIDE EMPTY 3/4" CONTROLS CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT TO ACCOMMODATE CONTROL CABLING BY MECHANICAL OR
TEMPERATURE CONTROLS CONTRACTOR.
E. "DISCONNECT" - PROVIDE DISCONNECT/RECEPTACLE AT EQUIPMENT LOCATION AND ASSOCIATED CONNECTION TO EQUIPMENT AND BRANCH CIRCUIT:
·"NEMA-___" = DUPLEX (TYP) RECEPTACLE TO ACCOMMODATE CORD AND PLUG CONNECTION (CORD AND PLUG FURNISHED WITH EQUIPMENT UNLESS NOTED OTHERWISE)
·"REC/SW" = PROVIDE 20A 120V RECEPTACLE OR 20A TOGGLE SWITCH DISCONNECT. COORDINATE REQUIRED SELECTION WITH EQUIPMENT. MMP20
·"NF" = NON-FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. 20/1 AND SMALLER SHALL BE TOGGLE SWITCH DISCONNECT.
·"F" = FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. FUSE PER MANUFACTURER'S RECOMMENDATIONS. 1 2 H201 U1 MTR2
·"FUSTAT" = SWITCH AND FUSTAT. FUSE SIZE PER EQUIPMENT MANUFACTURER. LOCATE SWITCH IN CONCEALED ACCESSIBLE LOCATION. 3M 3M SF-1
·"ENCL CB" = ENCLOSED CIRCUIT BREAKER DISCONNECT. SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.
M DETAIL NOTE
·"ENCL MCSW" = ENCLOSED MOLDED CASE SWITCH DISCONNECT. SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. TO 3 4 H202 V1
·"SHUNT ENCL CB" = SHUNT TRIP ENCLOSED CIRCUIT BREAKER DISCONNECT. SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. PROVIDE WITH INTEGRAL 120V CONTROL EP3A A DISCONNECT AHU SUPPLY FANS
3M 3M
TRANSFORMER SERVED FROM LINE SOURCE WITH PRIMARY AND SECONDARY FUSING. COORDINATE ENCLOSURE AND COVER SIZE TO ACCOMMODATE TRANSFORMER. PROVIDE WITH 3 FROM FURNISHED VFD. PROVIDE
EQUIPMENT GROUND BAR AND SEPARATE INSULATED ISOLATED GROUND BAR. WHERE NEUTRAL CONDUCTOR IS UTILIZED, PROVIDE SOLID NEUTRAL BAR. CONNECT SHUNT TRIP VOLTAGE 5 6 H203 W1 PE INDIVIDUALLY MOUNTED 20 HP
SOURCE AND ACTUATOR TO ASSOCIATED EMERGENCY POWER OFF (EPO) SWITCHES. PROVIDE EPO AND COORDINATE LOCATION. 3M 3M 27-32A 20HP VFDS AND CONNECT SUPPLY FANS
·"DIV 15" = DISCONNECT IS FURNISHED BY MECHANICAL CONTRACTOR OR PROVIDED WITH MECHANICAL EQUIPMENT. ELECTRICAL CONTRACTOR SHALL AS INDICATED.
PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS FURNISHED BY THE MECHANICAL CONTRACTOR. GROUND
NB
·INT" = DISCONNECT IS MANUFACTURED INTEGRAL TO THE EQUIPMENT. PROVIDE INDIVIDUALLY
·"HW" = HARDWIRE. DISCONNECT NOT REQUIRED. MOUNTED COMBINATION H.D.
(136)
·LOCATE DISCONNECT ADJACENT TO EQUIPMENT PER NEC - PROVIDE WITH STRUT MOUNTING AS REQUIRED. NON-FUSED SAFETY SWITCH
·LOCATE RECEPTACLE OR JUNCTION BOX TO DIRECTLY SERVE EQUIPMENT. COORDINATE EXACT LOCATION WITH ARCHITECT, ARCHITECTURAL DETAILS, AND EQUIPMENT MANUFACTURER'S AND VFD-20HP(70A FUSES)
REQUIREMENTS. MMP60
·WHERE DISCONNECT SERVES OUTDOOR EQUIPMENT, PROVIDE AS NEMA-3R.
·PROVIDE DISCONNECT WITH EQUIPMENT GROUND KIT. 1 2 H601 U1 MTR6
·WHERE FEEDER INDICATED UTILIZES A NEUTRAL, PROVIDE DISCONNECT WITH SOLID NEUTRAL KIT. 3M 3M SF-2
·WHERE FEEDER INDICATED UTILIZES AN ISOLATED GROUND, PROVIDE DISCONNECT WITH ADDITIONAL INSULATED GROUND KIT.
·DISCONNECTS NOT SHOWN AS "F" OR "NF" SHALL BE NON-FUSED. TO 3 4 H602 V1 M
·DISCONNECTS OF MOTORS SERVED FROM A VFD SHALL CONTAIN AUXILIARY CONTACTS CONNECTED TO THE VFD TO DISABLE VFD UPON DISCONNECTION. MCC1 3M 3M
3
·WHERE STARTERS VFD'S CONTAIN INTEGRAL DISCONNECTS AND ARE LOCATED PER NEC TO SATISFY AS THE EQUIPMENT DISCONNECT, AN ADDITIONAL EQUIPMENT DISCONNECT IS NOT 5 6 H603 W1 PE
FESSION
REQUIRED. 20HP PRO AL
F. "GEN" 3M 3M 27-32A ED G . NO.
RE

ER

EN
·EQUIPMENT IS SERVED FROM A SOURCE PANEL PROVIDED WITH GENERATOR BACK-UP. GROUND

REGIST

GINEER
NB 10206
TRACY J.
HAUSER

A
AHU-10 SUPPLY FANS CONNECTION DETAIL

T
O
U O

1
T H K
D A

NOT TO SCALE
FEEDER SCHEDULE
OVERCURRENT DEVICE SETTINGS SCHEDULE 11/25/14
MARK NOMINAL SIZE WIRE AND CONDUIT
DEVICE MANUFACTURER TYPE FRAME SENSOR PLUG Ir (tr) Isd (tsd) Ii MMP10 No. Description Date
1M -- 3-#12, #12 GND - 3/4"C.

MSWB - CDP2 JKS FUSE CLASS J 200 -- -- -- --


1M1 -- 2-#12, #12 GND - 3/4"C. 1 2 H101 U1 MTR1
BUSSMANN 3M -- 3-#8, #8 GND - 1"C.
1M 1M RF-1
JG WITH 10N 110 A 4-#1, #6 GND - 2"C.
M DETAIL NOTE
HGEN - CDP2 CUTLER HAMMER DIGITRIP 310
JGE 250 100 A 100 (7) 12 (J,K,L) FIXED
TO 3 4 H102 V1
11 125 A 3-#1, #6 GND - 1-1/2"C.
EP3A A DISCONNECT AHU SUPPLY FANS
POWERPACT WITH 11N 125 A 4-#1/0, #6 GND - 2"C. 1M 1M
CDP2 MAIN SQUARE D LD 250 250 250 (4) -- 12 3 FROM FURNISHED VFD. PROVIDE
MICROLOGIC 3.3 TU 5 6 H103 W1
14 200 A 3-#3/0, #6 GND - 2"C. PE INDIVIDUALLY MOUNTED 20 HP
POWERPACT WITH 10HP VFDS AND CONNECT SUPPLY FANS
CDP2 BRANCH SQUARE D HD 150 150 100 (FIXED) 3 (FIXED) 15 16T 250 A 4-300 KCMIL, #2 GND - 3"C. 1M 1M 11-16A
MICROLOGIC 3.3 TU AS INDICATED.
TYP. 120V BRANCH GROUND
SQUARE D QO -- 20 -- FIXED -- -- NB
CIRCUIT PROVIDE INDIVIDUALLY
MOUNTED COMBINATION H.D.
(136)
NON-FUSED SAFETY SWITCH
GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE) AND VFD-10HP(35A FUSES)
MMP50
A. DEVICES AND SETTINGS HAVE BEEN SELECTED TO ENSURE SELECTIVE COORDINATION TO 0.01 SECONDS. ANY SUBSTITUTIONS SHALL BE
APPROVED BY THE ENGINEER OF RECORD, PROVIDE SELECTIVE COORDINATION STUDY FOR ANY SUBSTITUTIONS. 1 2 H501 U1 MTR6
1M 1M RF-2
TO 3 4 H502 V1 M
MCC1 1M 1M
3
5 6 H503 W1 PE
1M 1M 11-16A 10HP

GROUND
NB

AHU-10 RETURN FANS CONNECTION DETAIL


2 NOT TO SCALE INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
4TH & 5TH
SINGLE POLE CIRCUIT BREAKER

2014 C COPYRIGHT ELECTRICAL


PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEDULES
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:50 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E500
www.specializedeng.com Scale NONE
GENERAL NOTES
SHEET NOTES TELECOM RACK (TYP.)

D
A. COORDINATE RACKS LAYOUTS WITH OWNERS IT REPRESENTATIVE PRIOR TO EXISTING DATA
IN PATIENT FLOORS CORRIDORS. STARTING WORK. D 1 EXISTING 25PR COPPER FROM 48 PORT ORTRONICS RACK MOUNT, VOICE PATCH
PANEL ON 5TH LEVEL TO 3RD FLOOR VOICE WALL FIELD. RELOCATION BY OWNER IT. NURSES CABINET
SUPPORT CABLE WITH J-HOOK TYPE B. PROVIDE #6 AWG CU GREEN GROUND FROM TELECOM RACKS TO GROUND BAR STATION TYPICAL
CABLE TRAY (5TH FLOOR ONLY) CORRIDOR PHONE
CABLE SUPPORT OR APPROVED OF NEW CRITICAL PANEL ON ROOF. T53 T51 T5
PER PLANS 2 EXISTING (TO BE RELOCATED AND RECONNECTED BY OWNER IT) 12 STRAND FIBER CABINET 'TTC__'
EQUAL, MAX OF 5' ON CENTER D
CABLE.
3 EXISTING WALL MOUNTED SWING OPEN TYPE 19" VOICE AND DATA RACK.(T5). D
REMOVE T5 AFTER T51 AND T52 ARE INSTALLED AND SERVING EXISTING OUTLETS. T54 T52 EXISTING COPPER AVERA FACILITY DEVELOPMENT
PROVIDE WITH BUSHING PROVIDE T5 TO OWNER. PAIRS BUNDLE
FIFTH LEVEL
ROOF ROOF 4 CABLE TRAY, REFER TO FLOOR PLANS FOR SIZES.
ROUTE COMMUNICATIONS CABLES 174' - 4" NURSES
ABOVE ACCESSIBLE CEILING TO FLOOR
2092" 5 EXISTING DOOR TO REMAIN. STATION
SERVING EQUIPMENT
6 EXISTING WALL TO REMAIN.
4' - 7 15/16"
4
7 SEE ARCHITECTURAL DRAWINGS FOR RACKS ENCLOSURE ASSEMBLY.
8 PROVIDE RACKS T51 AND T52 FIRST. OWNER WILL MIGRATE ELECTRONICS,
PATCH PANELS, AND SWITCHES SERVING EXISTING OUTLETS TO THESE COPPER CABLING
1' - 8 5/8" 7 FURNISHED AND
PROVIDE 1" CONDUIT STUBBED RACKS. REMOVE CABINETS T5. THEN PROVIDE RACKS T53 AND T54.
UP ABOVE NEAREST INSTALLED BY OWNER
TV OR 9 PROVIDE 30/1 125V SIMPLEX RECEPTACLE (CRITICAL BRANCH SOURCE) VIA #10
ACCESSIBLE CORRIDOR CEILING 12 8 AWG. SEE ELECTRICAL DRAWINGS. PROVIDE 30/1 CIRCUIT BREAKER TO MATCH FOURTH LEVEL
PROVIDE AT 6 RATING OF EXISTING.
2' - 11"
PLAN SYMBOL CP5A2-11 10 EXISTING CABLES ROUTE THROUGH OPENING IN WALL. ALL REROUTED AND NEW
T53 T51 CABLES SHALL BE ROUTED FROM ABOVE, NOT IN EXSTING WALL CAVITY. OWNER FURNISHED, OWNER
MAXIMUM 12" BETWEEN BOX
PROVIDE 4" SQUARE CENTERS UNLESS SPECIFICALLY 9 11 OWNER FURNISHED, OWNER INSTALLED 25PR COPPER FROM RACK TO 3RD INSTALLED WALL MOUNT 110
CR 5
BY 2-1/8" DEEP BOX NOTED OTHERWISE. COORDINATE T5 3 FLOOR TELECOM ROOM PHONE WALL FIELD. OWNER TO PROVIDE TERMINATION BLOCKS TO ACCOMMODATE
GENERAL NOTES: WITH SINGLE GANG 10 11 COPPER BACKBONE AND
1. PROVIDE CABLING PER SPECIFICATIONS AND PLANS. WITH ARCHITECTURAL DETAILS. 2 ON 110 WALL MOUNTED BLOCKS ON 3RD FLOOR AND ON RACK PATCH PANELS E E
PLASTER RING ON 5TH FLOOR. CROSS CONNECT TO SERVER.
2. LABEL CABLES PER ANSI/TIA/EIA-606 STANDARDS. 1
RECEPTACLE
T54 T52 12 EXISTING CRITICAL BRANCH RECEPTACLE SHALL BE RELOCATED OUT OF
PER PLAN FOOTPRINT OF NEW WALL MOUNT TELECOM RACKS. RECONNECT TO EXISTING SERVICE PROVIDER VOICE ROUTER,
FIFTH LEVEL FIFTH LEVEL CRITICAL BRANCH CIRCUIT PREVIOUSLY SERVING DEVICE. PRIMARY PROTECTION, AND WALL
TERMINATE CABLES AND PROVIDE 161' - 8" FIELD. THIRD LEVEL
FACEPLATE PER SPECIFICATIONS, 1940"
PROVIDE BLANK COVERPLATES
FOR LOCATIONS WITHOUT CABLING
DESCRIPTION OF WORK
Telecommunications Cabling Routing Schematic
1.
2.
PROVIDE WALL RACKS T51 AND T52.
PROVIDE 120V 30/1 RECEPTACLES.
1 NOT TO SCALE
3. PROVIDE FIBER TERMINATION EQUIPMENT.
Communications or CATV Outlet
3
4. OWNER TO PROVIDE PHONE RISER CABLE.
NOT TO SCALE 5. OWNER WILL MIGRATE EXISTING SWITCHES, RACK PATCH PANELS, UPS'S,
ELECTRONICS AND EXISTING CABLES TO RACKS T51 AND T52.
6. AFTER MIGRATION OF EXISTING ELECTRONICS AND CABLES TO RACKS T51 AND T52 IS
COMPLETE, PROVIDE WALL RACKS T53 AND T54.
7. PROVIDE NEW DATA AND VOICE OUTLETS AND CABLES AS REQUIRED BY
CONSTRUCTION SPECIFICATIONS.

Data Closet Elevation


2 1/4" = 1'-0" TO ADDITIONAL RELAYS
FIRE ALARM CONTROL RELAY.
PROVIDE (1) RELAY PER AIR
HANDLING UNIT ZONE (TYP)
TO ADDITIONAL
DAMPERS SERVING
SAME AIR HANDLING
UNIT ZONE. (TYP)

M
120V. MOTORIZED
CIRCUIT PER PLANS SMOKE DAMPER BY
OWNER PROVIDED BACKBONE OWNER PROVIDED 48 PORT MECHANICAL (TYP)
CABLE PER SPECIFICATIONS PROVIDE HORIZONTAL
PATCH PANEL(S) (TYPICAL)
CABLING PER SPECIFICATIONS
UNSWITCHED BRANCH POWER PACK(S) IN
TO 3RD FLOOR CIRCUIT SOURCE PER PLAN JUNCTION BOX ADDITIONAL LIGHTING ZONES (WHERE
TELECOM ROOM COMMUNICATIONS OUTLET APPLICABLE)
(TYPE INDICATED PER M
SPECIFICATIONS)
LABELING TO MATCH LEGEND
LOCATION SERVED BY LOW VOLTAGE WIRING
OWNER PER MANUFACTURER'S 120V. POWER FESSION
XXX RECOMMENDATIONS F.A. CONTROL PRO AL
OWNER WILL PROVIDE ED G . NO.
RE

ER
CIRCUIT

EN
PATCH CORD(S) PROVIDED LABELING

REGIST

GINEER
SCHEME AS DIRECTED 10206
BY OWNER NOTES: TRACY J.
NOTES: 1. VERIFY ARRANGEMENT OF AIR HANDLING UNIT ZONES HAUSER

A
S
1. CONTRACTOR SHALL PROVIDE AND INSTALL PATCH PANELS (TYPICAL). SEE ELECTRICAL DRAWINGS FOR PRIMARY LIGHTING

T
WITH MECHANICAL

O
U O
T H K
COMMUNICATION DEVICES. CONTRACTOR IS RESPONSIBLE FOR DEVICE COUNT AND QUANTITY OF PATCH LOW VOLTAGE CEILING ZONE D A
PANELS REQUIRED PLUS 1 SPARE PATCH PANEL. OCCUPANCY SENSOR 2. LABEL EACH RELAY WITH THE NAME OF THE AIR
2. COORDINATE INSTALLATIONS WITH OWNER'S IS/IT REPRESENTATIVE. HANDLING SERVING THE SMOKE ZONE AND WITH THE
FIRE ALARM WORDS "SMOKE DAMPER CONTROL". 11/25/14

Typical Voice Information Delivery


UNDERCABINET LIGHT CONTROL PANEL
6
FIXTURE(S) (WHERE 3. RELAY SHALL INTERRUPT DAMPER POWER CIRCUIT
APPLICABLE)
No. Description Date
NOT TO SCALE UPON ALARM FROM VERIFIED SPOT TYPE DETECTOR
LINE VOLTAGE WITHIN THE ASSOCIATED AIR HANDLING UNIT ZONE
TOGGLE SWITCH LINE VOLTAGE TOGGLE OR DIMMER UNLESS OTHERWISE INDICATED.
SWITCH (ROOMS WITH MULTIPLE
ZONES) 4. PROVIDE BREAKER LOCKS ON 120V. CIRCUITS.

LINE VOLTAGE
TOGGLE SWITCH Smoke Damper Connection
INDIVIDUAL
4 NOT TO SCALE
ROOM/CORRIDOR ADDITIONAL LINE VOLTAGE TOGGLE SWITCH
FOR BI-LEVEL SWITCHING

NOTES: PLAN SYMBOL CONTROL CONFIGURATION


COMBINATION
1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE INSTALLATION. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
OCCUPANCY SENSOR WITH DIMMER
2. WHERE CEILING LIGHT FIXTURES ARE 277V, PROVIDE ADDITIONAL RELAYS AND POWER PACKS D AND SWITCH
PROVIDE FIBER ENCLOSURE(S) WITH AS NECESSARY TO CONTROL 120V UNDERCABINET LIGHTING.
CAPACITIES TO ACCOMMODATE DATA SWITCH(ES) OCCUPANCY SENSOR WITH DIMMER
EXISTING FIBER CABLES OWNER PROVIDED 48 PORT -OR-
PROVIDED BY OWNER PATCH PANEL(S) (TYPICAL) PROVIDE HORIZONTAL 3. WHERE BI-LEVEL SWITCHING IS BEING IMPLEMENTED: D OR SWITCH
CABLING PER 3 LAMP FIXTURES - SWITCH CLOSEST TO DOOR SHALL CONTROL OUTER TWO LAMPS IN
SPECIFICATION EACH FIXTURE. SECOND SWITCH SHALL CONTROL CENTER LAMP IN EACH FIXTURE. OCCUPANCY SENSOR WITH BI-
FIBER ENCLOSURE 2 LAMP FIXTURES - EACH SWITCH SHALL CONTROL 50% OF THE LIGHT LEVEL IN EACH LEVEL SWITCHING
COMMUNICATIONS FIXTURE.
OUTLET (TYPE
OCCUPANCY SENSOR WITH BI-
INDICATED PER PLAN)
OWNER PROVIDED LABELING LEVEL SWITCHING - MULTIPLE
TO MATCH LOCATION SERVED 3 3 LOCATIONS
EXISTING FIBER BACKBONE XXX OCCUPANCY SENSOR ONLY
RACK
CABLE (EXCLUDE WALL SWITCH INDICATED
OWNER WILL PROVIDE 2 MOUNT OWNER WILL PROVIDE
STRAND FIBER WITH PATCH CORD(S) PROVIDED LABELING IN DETAIL)
SCHEME AS SPECIFIED
CONNECTORS EACH END
CEILING OCC SENSOR WITH SWITCH OR DIMMER SACRED HEART
NOTES: 5 1/8" = 1'-0"
1. CONTRACTOR SHALL PROVIDE AND INSTALL PATCH PANELS (TYPICAL). SEE ELECTRICAL DRAWINGS FOR
COMMUNICATION DEVICES. CONTRACTOR IS RESPONSIBLE FOR DEVICE COUNT AND QUANTITY OF PATCH
PANELS REQUIRED PLUS 1 SPARE PATCH PANEL.
4TH & 5TH
2. COORDINATE INSTALLATIONS WITH OWNER'S IS/IT REPRESENTATIVE.

2014 COPYRIGHT ELECTRICAL


Typical Data Information Delivery
C

7 NOT TO SCALE
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE DETAILS
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:50 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E501
www.specializedeng.com Scale NONE
Lighting Panel: CDP-2
Location: 3RD LEVEL Volts: 120/208 Wye Rating: 250 A
Supply From: ATS-CDP2 Phases: 3 Mains Type: MCB
Branch: CRITICAL Wires: 4 Panel Poles: 30 AVERA FACILITY DEVELOPMENT
Mounting: Surface Available SCC (kA): 9.8 Sections: 1

Ckt Circuit Description Opt Rati... Poles A B C Poles Rati... Opt Circuit Description Ckt
1 2
3 4
5 6
7 9441 VA 9623 VA 8
9 CP5A2 100 A 3 7390 VA 9183 VA 3 100 A CP5B2 10
11 7640 VA 7820 VA 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30

Lighting Panel Remarks:


1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: 2-100/3

General Lighting Panel Notes:


1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current).
2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.

Lighting Panel: CP5A2


Location: Space 1974 Volts: 120/208 Wye Rating: 100 A
Supply From: CDP-2 Phases: 3 Mains Type: MLO
Branch: Critical Wires: 4 Panel Poles: 42
Mounting: Recessed Available SCC (kA): 4.1 Sections: 1

Ckt Circuit Description Opt Rati... Poles A B C Poles Rati... Opt Circuit Description Ckt
1 PWR - CNV SPACE 527 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 525 2
3 PWR - CNV SPACE 524 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 523 4
5 PWR - CNV SPACE 522 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 521 6
7 PWR - CNV SPACE 520 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 519 8
9 LTG ROOM 500,501,502,503,504 20 A 1 940 VA 1410 VA 1 20 A LTG ROOM 505,506,507,508 10
11 PWR SPACE 1949 20 A 1 2000 VA 1320 VA 1 20 A PWR - CNV SPACE 517 12
13 HVAC 20 A 1 1176 VA 705 VA 1 20 A LTG SPACE 1845 14
15 PWR - CNV SPACE 512 20 A 1 720 VA 16
17 18
19 PWR - CNV 20 A 1 540 VA 540 VA 1 20 A PWR - CNV SPACE 515 20
21 PWR - CNV SPACE 514 20 A 1 540 VA 540 VA 1 20 A PWR - CNV SPACE 513 22
23 PWR - CNV 20 A 1 540 VA 540 VA 1 20 A PWR - CNV SPACE 512 24
25 26
27 28 FESSION
PRO AL
29 30 ED G . NO.
RE

ER

EN
31 32

REGIST

GINEER
10206
33 34
TRACY J.
35 36 HAUSER

A
S
37 38

T
O
U O
T H K
D A
39 40
41 42
11/25/14
Lighting Panel Remarks:
1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: 10-20/1 No. Description Date

General Lighting Panel Notes:


1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current).
2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.

Lighting Panel: CP5B2 Lighting Panel: EP3A


Location: Space 1975 Volts: 120/208 Wye Rating: 100 A Location: 3RD LEVEL Volts: 480/277 Wye Rating: 100 A
Supply From: CDP-2 Phases: 3 Mains Type: MLO Supply From: EDP Phases: 3 Mains Type: MLO
Branch: Critical Wires: 4 Panel Poles: 42 Branch: Equipment Wires: 4 Panel Poles: 42
Mounting: Recessed Available SCC (kA): 3.9 Sections: 1 Mounting: Surface Available SCC (kA): 4.1 Sections: 1

Ckt Circuit Description Opt Rati... Poles A B C Poles Rati... Opt Circuit Description Ckt Ckt Circuit Description Opt Rati... Poles A B C Poles Rati... Opt Circuit Description Ckt
1 PWR - CNV SPACE 526 20 A 1 720 VA 1307 VA 1 20 A LTG ROOM 509,510,511,512,513 2 1 7482 VA 3880 VA 2
3 PWR - CNV SPACE 509 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 508 4 3 AHU-10-SF-1 70 A 3 7482 VA 3880 VA 3 35 A AHU-10-RF-1 4
5 PWR - CNV SPACE 507 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 506 6 5 7482 VA 3880 VA 6
7 PWR - CNV SPACE 505 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 504 8 7 8
9 PWR - CNV SPACE 503 20 A 1 1620 VA 1620 VA 1 20 A PWR - CNV SPACE 502 10 9 10
11 PWR - CNV SPACE 501 20 A 1 1620 VA 1175 VA 1 20 A LTG ROOM 514,515,516,517 12 11 12
13 PWR - CNV SPACE 535 35 A 1 1620 VA 1656 VA 1 20 A HVAC 14 13 14
15 ROOM 529, 1884 20 A 1 705 VA 16 15 16
17 705 VA 1 20 A ROOM 532, 1873 18 17 18
19 20 19 20
21 PWR - CNV SPACE 534 20 A 1 540 VA 540 VA 1 20 A PWR - CNV SPACE 533 22 21 22
23 PWR - CNV SPACE 532 20 A 1 540 VA 540 VA 1 20 A PWR - CNV SPACE 531 24 23 24 SACRED HEART
25 PWR - CNV SPACE 530 20 A 1 540 VA 540 VA 1 20 A PWR - CNV SPACE 529 26 25 26
27 LTG SPACE 1860 20 A 1 705 VA 213 VA 1 20 A LTG SPACE 512 28 27 28
29 30 29 30 4TH & 5TH
31 32 31 32
33
35
34
36
33
35
34
36 2014 C COPYRIGHT ELECTRICAL PANEL
37
39
38
40
37
39
38
40
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE SCHEDULES
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE
41 42 41 42 OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
Lighting Panel Remarks: Lighting Panel Remarks: DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: 10-20/1 1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:51 PM
General Lighting Panel Notes: General Lighting Panel Notes:
10360 Ellison Circle SES PROJECT # 14041
1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current).
2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.
1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current).
2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker. Omaha, NE 68134
Phone: 402.991.5520 E502
www.specializedeng.com Scale NONE
AVERA FACILITY DEVELOPMENT

RISER DIAGRAM NOTES


PROVIDE PROVIDE 1 PROVIDE 100/3 NEW CIRCUIT BREAKER 'HGEN-CDP2' IN EXISTING
208/120V 208/120V SWITCHBOARD. CIRCUIT BREAKER SHALL MATCH MANUFACTURER
100A MLO PANEL CP5A2 CP5B2 100A MLO PANEL AND RATINGS OF EXISTING. INSTALL CIRCUIT BREAKER IN CRITICAL
3 SECTION OF SWITCHBOARD.
4 3
4 2 PROVIDE 200/3 NEW FUSED SWITCH 'MSWB-CDP2' IN EXISTING
SWITCHBOARD. FUSES AND SWITCH SHALL MATCH MANUFACTURER
FIFTH LEVEL AND RATINGS OF EXISTING. INSTALL FUSED SWITCH IN CRITICAL
SECTION OF SWITCHBOARD.
10N 10N 3 PROVIDE #6 AWG CU GROUND CONDUCTOR FROM NEW CRICTICAL
PANELBOARDS TO EXISTING NORMAL BRANCH PANELBOARDS AND
EXISTING CRITICAL BRANCH PANELBOARD LOCATED ON SAME FLOOR.
BOND CRITICAL PANELBOARDS AND NORMAL PANELBOARDS
TOGETHER PER NEC.
4 STUB UP FIVE (5) SPARE 1"C. CONDUITS FROM TOP OF PANELBOARDS TO
ACCESSIBLE CORRIDOR CEILING SPACE ABOVE.
5 REFER TO SHEET E211 - FIRST LEVEL - POWER PLAN FOR
FOURTH LEVEL SWITCHBOARD LOCATION.
6 PROVIDE 100/3 CIRCUIT BREAKER IN EXISTING DISTRIBUTION PANEL.
CIRCUIT BREAKER SHALL MATCH MANUFACTURER AND RATINGS OF
3 PROVIDE EXISTING.
PROVIDE CDP-2 PANEL E503 480/277V 7 PROVIDE 200/3 DISCONNECT ON PRIMARY FEEDERS OF TRANSFORMER
208/120V 250A MCB 100A MLO PANEL PER NEC.
8 COORDINATE ROUTING OF FEEDERS WITHIN EXISTING HOSPITAL WITH
EP3A
OWNER. ROUTE FEEDERS FROM GENERATOR ROOMS THROUGH
14 EXISTING TUNNEL.
16T
7 THIRD LEVEL
ATS-CDP2
480/277V
PROVIDE XFMR-CDP2 2 200A 3-POLE
480/277V TO 208Y/120V TRANSFER SW. 11N
E503
75KVA TRANSFORMER SCCR: 8.5KA

HOSP. MAIN ELEC EXISTING TUNNEL GENERATOR OLD GENERATOR


ROOM 1030A ROOM 1970 ROOM 1971
14
11
E 8 E E E
2 1 6
5 EXISTING HOSPITAL ATS-3
SWITCHBOARD 'MSWB' (EQUIP BRANCH)
480/277V 3-PHASE 480/277V
CRITICAL CRITICAL 600A
2500A
SECTION SECTION
FIRST LEVEL

HOSPITAL EMERGENCY EQUIPMENT BRANCH


SWITCHBOARD 'HGEN' DISTRIBUTION PANEL 'EDP-A' 5
480/277V 3-PHASE 1600A 5 480/277V 3-PHASE 600A

1980 ORIGINAL 2012 NORTHERN LIGHTS


HOSPITAL HOSPITAL ADDITION

Partial Hospital Riser Diagram


1 NOT TO SCALE FESSION
PRO AL
ED G . NO.
RE

ER

EN
REGIST

GINEER
10206
TRACY J.
HAUSER

A
S

T
O
U O
T H K
D A

11/25/14

No. Description Date

PHASE PHASE

EXISTING OUTPUT
ATS-CDP2 CIRCUIT BREAKER
EXISTING SERVICE 3-POLE
ENTRANCE SOLID NEUTRAL GENERATOR
AUTOMATIC TRANSFER SWITCH
PHASE PHASE
PHASE (TYPICAL)

XO TERMINAL

NEUTRAL BUS (TYPICAL)


NEUTRAL N N N

PHASE PHASE
GROUND BUS (TYPICAL)
G G G
GROUND
EQUIPMENT GROUND TO
GROUND CABINET
Transformer Ground Schedule
Transformer kVA Grounding Mark Size
SACRED HEART
CONNECT TO LOCAL GROUND TO FRAME
3, 6 G1 #12 IN 3/4" CONDUIT
GROUND BAR (SEE GROUND TO TO LOAD
9
15,30,45
G2
G3
#10 IN 3/4" CONDUIT
#6 IN 3/4" CONDUIT
SCHEDULE FOR SIZE) EXISTING SERVICE
GROUNDING
CABINET 4TH & 5TH
ELECTRODE
75 G4 #2 IN 3/4" CONDUIT
112.5 G5 #1/0 IN 3/4" CONDUIT 2014 C COPYRIGHT ELECTRICAL RISER
150 G6 #2/0 IN 1" CONDUIT
Generator Grounding with 3-Pole A.T.S. PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY
DIAGRAM
150+ G7 #3/0 IN 1" CONDUIT
2 NOT TO SCALE
GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE
PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE

Dry-Type Transformer Grounding Detail


OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED

3
ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
NOT TO SCALE DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL
BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE
COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. Date 11/25/2014 2:15:51 PM

10360 Ellison Circle SES PROJECT # 14041


Omaha, NE 68134
Phone: 402.991.5520 E503
www.specializedeng.com Scale NONE
NOTES:

FIRST FLOOR PIPING DEMOLITION PLAN


NOTES:

SECOND FLOOR PIPING DEMOLITION PLAN


NOTES:

THIRD FLOOR PIPING DEMOLITION PLAN


NOTES:

FIRST FLOOR UNDER SLAB HVAC DEMOLITION PLAN


NOTES:

FIRST FLOOR (CEILING SPACE) HVAC DEMOLITION PLAN


NOTES:

SECOND FLOOR HVAC DEMOLITION PLAN


NOTES:

THIRD FLOOR HVAC DEMOLITION PLAN


NOTES:

ROOF PLAN
NOTES:

FIRST FLOOR WASTE & VENT PIPING PLAN


NOTES:

FIRST FLOOR DOMESTIC PIPING PLAN


NOTES:

SECOND FLOOR PIPING PLAN


NOTES:

THIRD FLOOR PIPING PLAN


NOTES:

FIRST FLOOR HVAC PLAN


NOTES:

SECOND FLOOR HVAC PLAN


NOTES:

THIRD FLOOR HVAC PLAN


NOTES:

ROOF PLAN
PLUMBING / MECHANICAL ABBREVIATED SPECIFICATIONS GENERAL MECHANICAL NOTES

DESIGN CONDITIONS

GAS LOAD:

PLUMBING / MECHANICAL ABBREVIATIONS

PLUMBING / MECHANICAL LEGEND


PACKAGED MAKE UP AIR UNITS PLUMBING FIXTURES

FAN SCHEDULE

GRILLE & REGISTER SCHEDULE

SPLIT SYSTEM GAS FURNACES

WATER HEATER SCHEDULE

CIRCULATING PUMPS
14 9 5 1

15 10 6 2

16 11 7 3

13 12 8 4
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
GENERAL NOTES

GENERAL Y. All air-conditioning condensate drain lines from each air handling unit and rooftop unit shall be piped full size of dishwasher, kitchen, and laundry exhausts shall be of unvaned, smooth radius construction with a radius equal to
A. Provide all materials and equipment and perform all labor required to install complete and operable mechanical the unit drain outlet, with "P" trap, and piped to the nearest allowable drain in accordance with the authority having 1-1/2 times the width of the duct. Provide access doors upstream of all elbows with turning vanes.
systems as indicated on the drawings, as specified, and as required by authorities having jurisdiction. jurisdiction. See the details shown in the drawings or contract specifications for the depth of the air conditioning
condensate trap. H. Coordinate diffuser, register, and grille locations with architectural reflected ceiling plans, lighting, and other ceiling
B. Contract document drawings for mechanical work (HVAC and plumbing) are diagrammatic and are intended to items and make minor duct modifications to suit.
convey scope and general arrangement only. Z. Refer to typical details for ductwork, piping, and equipment installation.
I. Field-erected and factory-assembled air handling unit coils shall be arranged for removal from the upstream side
without dismantling supports. Provide galvanized structural steel support for all coils (except the lowest coil) in
C. Install all mechanical equipment and appurtenances in accordance with manufacturers' recommendations, PIPING
contract documents, and applicable codes and regulations. banks over two coils high to permit the independent removal of any coil.
A. Provide all materials and equipment and perform all labor required to install complete and operable piping
systems as indicated on the drawings, and as specified and required by authorities having jurisdiction.
D. Provide vibration isolation for all mechanical equipment to prevent transmission of vibration to building structure. J. All air handling units shall operate without moisture carryover.
B. Elevations shown on the drawings are to the bottom of all pressure piping an to the invert of all gravity piping
E. Provide vibration isolators for all piping supports connected to, and within 50 feet of, isolated equipment (except at K. Locate all mechanical equipment (single duct, dual duct, variable volume, constant volume, and fan-powered
unless otherwise noted.
base elbow supports and anchor points) throughout mechanical equipment rooms. boxes; fan-coil units; cabinet heaters; unit heaters; unit ventilators; coils; steam humidifiers; etc.) for unobstructed
access to unit access panels, controls, and valving.
C. Unless otherwise noted, all piping is overhead, tight to the underside of the structure or slab, with space for
F. The location of existing underground utilities is shown in an approximate way only. The contractor shall determine insulation if required.
the exact location of all existing utilities before commencing work. The contractor shall pay for and repair all L. Finned tube radiation enclosures shall be wall-to-wall unless otherwise indicated.
damages caused by failure to exactly locate and preserve any and all underground utilities unless otherwise D. Install piping so all valves, strainers, unions, traps, flanges, and other appurtenances requiring access are
noted. M. Provide flexible connections in all ductwork systems (supply, return, and exhaust) connected to air handling units,
accessible.
fans, and other equipment that require vibration isolation. Flexible connections shall be provided at the point of
G. Coordinate construction of all mechanical work with architectural, structural, civil, electrical work, etc., shown on connection to the equipment unless otherwise indicated.
E. All valves shall be installed so that the valve remains in service when equipment or piping on the equipment side
other contract document drawings. of the valve is removed.
N. Unless otherwise noted, all ductwork is overhead, tight to the underside of the structure, with space for insulation
H. Maintain a minimum 6'-8" clearance to the underside of pipes, ducts, conduits, suspended equipment, etc., if required.
F. All balancing valves and butterfly valves shall be provided with position indicators and the maximum adjustable
throughout access routes in mechanical rooms. stops (memory stops).
O. Runs of flexible duct shall not exceed 5 feet in length.
I. All tests shall be completed before any mechanical equipment or piping insulation is applied. G. Unless otherwise noted, all valves (except control valves) and strainers shall be the full size of the pipe before
P. All ductwork shall be coordinated with all trades involved. Offsets in ducts, including divided ducts and transitions
reducing in size to make connections to equipment and controls.
J. Locate all temperature, pressure, and flow measuring devices in accessible locations with the straight section of around obstructions, shall be provided at no additional cost to the owner.
pipe or duct up- and downstream as recommended by the manufacturer to ensure accuracy of measurements. H. Unions and/or flanges shall be installed at each piece of equipment, in bypasses, and in long piping runs (100 feet
Q. Provide access doors in ductwork to provide access for all smoke detectors, fire dampers, smoke dampers,
or more) to permit disassembly for alteration and repairs.
K. Testing, adjusting, and balancing agency shall be a member of the Associated Air Balance Council (AABC) or the volume dampers, humidifiers, coils, and other items located in the ductwork that require service and/or inspection.
National Environmental Balancing Bureau (NEBB). Testing, adjusting, and balancing shall be performed in I. Install all piping without forcing or springing.
accordance with the AABC standards. R. Provide access doors in ductwork for the operation, adjustment, and maintenance of all fans, valves, and
mechanical equipment.
J. All piping shall clear doors and windows.
L. Where two or more items of the same type of equipment are required, the product of one manufacturer shall be
used. S. Smoke detectors shall be furnished and wired by the electrical contractor. The mechanical contractor shall be
K. All valves shall be adjusted for smooth and easy operation.
responsible for mounting the smoke detector in ductwork as shown on the drawings and in accordance with the
M. Coordinate all equipment connections with manufacturers' certified drawings. Coordinate and provide all duct and manufacturer's printed instructions.
L. All piping work shall be coordinate with all trades involved. Offsets in piping around obstructions shall be provided
piping transitions required for final equipment connections to furnished equipment. Field verify and coordinate all at no additional cost to the owner.
duct and piping dimensions before fabrication. T. Terminate gas vents for unit heaters, water heaters, high-pressure parts washers, high-pressure cleaners, and
other gas appliances a minimum of 30 inches above the roof with rain cap.
M. Provide flexible connections in all piping systems connected to pumps, chillers, cooling towers, and other
N. All control wire and conduit shall comply with the National Electric Code and Division 26 of the specification. equipment which require vibration isolation except water coils. Flexible connections shall be provided as close to
U. See specifications for ductwork gauges, bracing, hangers, and other requirements.
the equipment as possible or as indicated on the drawings.
O. Where beams are indicated to be penetrated with ductwork or piping, coordinate ductwork and piping layout with
beam opening size and opening locations. Coordination shall be done prior to the fabrication of ductwork, cutting N. Slope refrigerant piping one percent in the direction of oil return. Liquid lines may be installed level.
of piping, or fabrication of beams.
O. Provide line size liquid indicators in the main liquid line leaving the condenser or receiver. Install moisture-liquid
P. When mechanical work (HVAC, plumbing, sheet metal, etc.) is subcontracted, it shall be the mechaincal indicators in liquid lines between filter dryers and thermostatic expansion valves, and in liquid line to receiver.
contractor's responsibility to coordinate subcontractors and the associated contracts. When discrepancies arise
pertaining to which contractor provides a particular item of the mechanical contract or which contractor provides P. Provide a line size strainer upstream of each automatic valve. Provide a shutoff valve on each side of a strainer.
final connections for a particular item of the mechanical contract, it shall be brought to the attention of the
mechanical contractor, whose decision shall be final. Q. Provide permanent filter dryers in low-temperature systems and systems using hermetic compressors.

Q. The locations of all items shown on the drawings or called for in the specifications that are not definitely fixed by R. Provide replaceable cartridge filter dryers with a three-valve bypass assembly for solenoid valves, adjacent to
dimensions are approximate only. The exact locations necessary to secure the best conditions and results must receivers.
be determined by the project site conditions and shall have the approval of the engineer before being installed. Do
not scale drawings. S. Provide refrigerant charging valve connections in the liquid line between the receiver shutoff valve and the
expansion valve.
R. All miscellaneous steel required to ensure proper installation and as shown in details for piping, ductwork, and
equipment (unless otherwise noted) shall be furnished and installed by the mechanical contractor.
HVAC/SHEET METAL
S. Provide access panels for installation in walls and ceilings, where required, to service dampers, valves, smoke A. Provide all materials and equipment and perform all labor required to install complete and operable HVAC
detectors, and other concealed mechanical equipment. Access panels shall be turned over to the general systems as indicated on the drawings, and as specified and required by authorities having jurisdiction.
contractor for installation.
B. Certain items such as rises and drops in ductwork, access doors, volume dampers, etc., are indicated on the
T. All equipment, piping, ductwork, etc., shall be supported as detailed, specified, and required to provide a contract document drawings for clarity for a specific location requirement and shall not be interpreted as the extent
vibration-free isolation. of the requirements for these items.

U. All ductwork, piping, and equipment supported from structural steel shall be coordinate with the general C. In corridors where ceiling speakers and air diffusers are indicated between the same light fixtures, install both
contractor. All attachments to steel bar joists, trusses, or joist girders shall be at panel points. Provide beam devices at the quarter points between the same fixture.
clamps meeting MSS standards. Welding to structural members shall not be permitted. The use of C-clamps shall
not be permitted. D. Unless otherwise shown, locate all room thermostats and humidistats 4'-0" (centerline) above the finished floor.
Notify the engineer of any rooms where the preceding location cannot be maintained or where there is a question
V. Mechanical equipment, ductwork, and piping shall not be supported from a metal deck. on location.

W. Locations and sizes of all floor, wall, and roof openings shall be coordinated with all other trades involved. E. All ductwork shall clear doors and windows.

X. All openings in fire walls due to ductwork, piping, conduit, etc., shall be fire stopped with a product similar to 3M or F. All ductwork dimensions, as shown on the drawings, are internal clear dimensions and duct size shall be
an approved equal. increased to compensate for duct lining thickness.

G. Provide all 90-degree square elbows with double radius turning vanes unless otherwise indicated. Elbows in

ABBREVIATIONS PIPING SYMBOLS HVAC SYMBOLS DESIGN INFORMATION


AFF ABOVE FINISHED FLOOR LWT LEAVING WATER TEMPERATURE
LINETYPES TWO LINE SINGLE LINE APPLICABLE CODES:
2012 INTERNATIONAL PLUMBING CODE (IPC)
AFG ABOVE FINISHED GRADE MAX MAXIMUM
2012 INTERNATIONAL MECHANICAL CODE (IMC)
NG NATURAL GAS ACCESS PANEL AP
AP
2012 INTERNATIONAL FUEL GAS CODE (IFGC)
APPROX APPROXIMATE, APPROXIMATELY MBH BTU PER HOUR (THOUSAND)
2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
COND HVAC CONDENSATE
BAS BUILDING AUTOMATION SYSTEM MCA MINIMUM CIRCUIT AMPACITY
ELBOW, RADIUS PROJECT DESIGN CONDITIONS:
BFF BELOW FINISHED FLOOR MEZZ MEZZANINE REFRIGERANT 2013 ASHRAE FUNDAMENTALS
LOCATION
BFG BELOW FINISHED GRADE MFS MAXIMUM FUSE SIZE COOLING OADB 99.0°F
ELBOW W/VANES COOLING OAWB 73.5°F ENGINEERING FIRM NO. F-9414
BHP BRAKE HORSE POWER MIN MINIMUM HEATING OADB 29.2°F

BTU BRITISH THERMAL UNIT MISC MISCELLANEOUS


ROOM DESIGN CONDITIONS:
BTUH BTU PER HOUR MOP, MAXIMUM OVER CURRENT FLEXIBLE DUCT OFFICE
MOCP PROTECTION COOLING 75°F
CA COMPRESSED AIR SYMBOLS COOLING 50% RH
MTR MOTOR MANUAL BALANCING DAMPER HEATING 70°F JONATHAN R. OLSON
CFH CUBIC FEET PER HOUR TRUCK MAINTENANCE BAYS
N/A NOT APPLICABLE COOLING 80°F 119296
CFM CUBIC FEET PER MINUTE BALANCING VALVE PUMP REDUCER
HEATING 55°F
N/C NORMALLY CLOSED
CI CAST IRON CHECK VALVE - SWING
N/O NORMALLY OPEN
PRESSURE GAUGE RETURN/EXHAUST, UP/DN NATURAL GAS UTILITY CONTACT INFORMATION:
CPVC CHORINATED POLYVINYL CHLORIDE
ELBOW UP/DOWN
CPS ENERGY
PO BOX 1771
12/19/16
NG NATURAL GAS PRESSURE GAUGE W/ COIL SYPHON
ROUND RETURN/EXHAUST, UP/DN SAN ANTONIO, TX 78296
CU FT CUBIC FEET
NTS NOT TO SCALE ELBOW UP/DOWN W/ VALVE IN DROP PRESSURE REGULATING VALVE (210) 353-4050
CU IN CUBIC INCH
ROUND SUPPLY/INTAKE, UP/DN
OC ON CENTER END CAP
DEG, ° DEGREES SAFETY RELIEF VALVE
OD OUTSIDE DIAMETER SUPPLY/INTAKE, UP/DN
DIA, Ø DIAMETER FLANGE OR UNION CONNECTION SHUT-OFF VALVE
PSI POUNDS PER SQUARE INCH
DN DOWN FLEXIBLE CONNECTOR SOLENOID VALVE
PSIG PSI GAUGE
TAKE-OFF
EA EACH
GLOBE VALVE STRAINER - Y-PATTERN
POC POINT OF CONNECTION
EL ELEVATION
POD POINT OF DISCONNECTION IMMERSION THERMOSTAT STRAINER - Y-PATTERN W/ DRAIN
ESP EXTERNAL STATIC PRESSURE SYMBOLS
PVC POLYVINYL CHLORIDE M METER TEE UP/DOWN
DRAWING INDEX
EWT ENTERING WATER TEMPERATURE
REQD REQUIRED B DAMPER - BYPASS H HUMIDISTAT
MIXING VALVE (TAG)
FLA FULL LOAD AMPERES TEE UP/DOWN W/ VALVE IN DROP H001T ABBREVIATIONS, GENERAL NOTES, AND SYMBOLS
RPM REVOLUTIONS PER MINUTE F DAMPER - FIRE C2 SENSOR - CARBON DIOXIDE
FT,' FEET POINT OF CONNECTION (TAG) H201T AREA 'H' HVAC PLAN
THERMOMETER
SENS SENSIBLE
FS DAMPER - FIRE/SMOKE C SENSOR - CARBON MONOXIDE
FPM FEET PER MINUTE POINT OF DISCONNECTION (TAG) H202T AREA 'H' MEZZANINE HVAC PLAN
SPEC SPECIFICATION TRAP (RUNNING)
FPS FEET PER SECOND M DAMPER - MOTORIZED DP SENSOR - DEWPOINT H203T AREA 'J' & 'K' HVAC PLANS
SQ FT SQUARE FEET (TAG)
GA GAUGE S DAMPER - SMOKE H240T AREA 'H' HVAC ROOF PLAN
H2 SENSOR - HYDROGEN
SQ IN SQUARE INCHES (TAG)
GAL GALLON H501T DETAILS
SS STAINLESS STEEL FLOW ARROW PD SENSOR - PRESSURE DIFFERENTIAL
(TAG)
GALV GALVANIZED H801T EQUIPMENT SCHEDULES
STD STANDARD DG DOOR GRILLE RH SENSOR - RELATIVE HUMIDITY
GPD GALLONS PER DAY (TAG)
TEMP TEMPERATURE
UC DOOR UNDERCUT RT SENSOR - ROOM TEMPERATURE
GPH GALLONS PER HOUR
(TAG)
T-STAT THERMOSTAT
GPM GALLONS PER MINUTE POINT OF CONNECTION S SENSOR (W/ EQUIPMENT TAG)
TYP TYPICAL (TAG)
HG MERCURY POINT OF DISCONNECTION
V VOLTS SD SMOKE DETECTOR
HP HORSE POWER
VFD VARIABLE FREQUENCY DRIVE T THERMOSTAT (W/ EQUPMENT TAG)
HR HOUR (TAG)
W WATTS
HZ HERTZ
WG WATER GAUGE
ID INSIDE DIAMETER
W/ WITH
IN, " INCHES
W/O WITHOUT
KW KILOWATT

LBS POUNDS
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
# SHEET KEY NOTES SHEET GENERAL NOTES
1. 30"X30" EXHAUST AIR DUCT UP TO EXHAUST FAN. SEE DETAIL 2/H501T.
1. SEE APPLICABLE NOTES ON SHEET H001T.
2. 18"Ø EXHAUST AIR DUCT UP THROUGH ROOF.

3. 22"X60" SUPPLY AIR DUCT FROM MAKE-UP AIR.

4. 22x28 OUTSIDE AIR AND 18x46 EXHAUST UP TO DEDICATED OUTSIDE AIR UNIT.

5. 22x18 SUPPLY DOWN FROM MAKE-UP AIR UNIT. INSTALL MANUFACTURER'S THREE-WAY
DIFFUSER AT 16'-0" AFF.

6. PROVIDE 20x20 ROOF OPENING AND EXHAUST DUCT.

7. PROVIDE 18x18 ROOF OPENING AND EXHAUST DUCT.

8. PROVIDE 20x20 ROOF OPENING AND EXHAUST DUCT. PROVIDE DRIP PAN 12" BELOW
PRECAST PLANK.

9. CARMON MODEL 55-S8 PLUG-IN FLOOR CONNECTION FOR CLOSE CAPTURE EXHAUST
SYSTEM.

10. MOUNT TOP OF LOUVER 1'-0" BELOW ROOF.

11. 42"Ø EXHAUST DUCT FROM PAINT BOOTH FAN CONNECTION, UP THROUGH ROOF, TERMINATE
ON ROOF WITH MANUFACTURERS EXHAUST PACKAGE.

12. SPUNSTRAND OR EQUAL FRP DUCT WITH WATER TIGHT JOINTS.

13. 12"X12" EXHAUST AIR DUCT UP TO EXHAUST FAN. SEE DETAIL 2/H501T.

14. CARMON MODEL 55-S5 PLUG-IN FLOOR CONNECTION FOR CLOSE CAPTURE EXHAUST
SYSTEM.

15. PROVIDE (2) 5Ø BY 20 FOOT CARMON TYPE HTC FLEX HOSE ASSEMBLIES WITH CTA-5
ADAPTER & PLUG-IN ASSEMBLY. PROVIDE (3) 8Ø BY 20 FOOT CARMON TYPE HTC HOSE
ASSEMBLIES WITH CTA-8 ADAPTER & PLUG-IN ASSEMBLY. PROVIDE (2) CARMON MODEL
DCA-R AND (3) CARMON MODEL DCA-8 DIESEL CANE ASSEMBLIES. PROVIDE (3) CARMON
PORTABLE STORAGE CARTS FOR HOSE ASSEMBLIES AND (5) CARMON WALL HANGERS FOR
DIESEL CANE ASSEMBLIES.

H1 H2 H3 H4 H5 H6 H7 H8

30"X30" EA DUCT FROM 12" AFF,


HA END OF DUCT OPEN TO ROOM
WITH BIRDSCREEN.
EWH-1T
34"X34" SA DUCT DOWN TO
PAINT BOOTH SUPPLY AIR
PLENUM.

30"X30"
ROUTE HORIZONTAL
DUCT IN JOIST SPACE

1
6

8"Ø EA DUCT OPEN TO PIT,


36"X36" 12"AFF OF PIT. PROVIDE SS
SR-1 BIRDSCREEN. (215CFM)
20X40

5100CFM
MOUNT BOTTOM OF
30"X18" SUPPLY DUCT AT 20'-0" AFF. 1-1/4" NG FROM ROOF
X" NG FROM ROOF 9
TO WATER HEATER SR-1 TO WATER HEATER.
1800CFM


10Ø
CG-4 7

PITCH
75CFM 15
3
13
12
UC

16X40

CD-3 36"X36" ENGINEERING FIRM NO. F-9414

12Ø
400 SR-1
5100CFM
CD-3 9 ROUTE DUCT IN JOIST

12"X12"
400 SPACE 11
2 8"Ø EA DUCT FROM BFF
10Ø

10Ø

14Ø 5
CD-3 MOUNT BOTTOM OF
HB 400 SUPPLY DUCT AT 20'-0" AFF.
10Ø 10Ø CD-3 H JONATHAN R. OLSON
18Ø
400
RTU-1T T 119296
12Ø

15
26x14 12x14
MOUNT BOTTOM OF
1-1/2" NG FROM ROOF
SUPPLY DUCT AT 20'-0" AFF.

26x14 15 12 TO PRESSURE WASHER


36"X36"
20X40

SR-1

PITCH

PITCH
T MAU-1T & 2T
10Ø

12/19/16

20x14

H 5100CFM

UC CD-1 CG-4 30"X18"


50 75CFM SR-1
CG-3
1800CFM



12"X12" EA DUCT UP THRU CD-1


MEZZANINE CG-4
150

100
12x12
9

3

CG-4
8"Ø EA DUCT OPEN TO PIT,
100
16X40

36"X36" 12"AFF OF PIT. PROVIDE SS


CG-4 CD-1 SR-1 BIRDSCREEN. (135CFM)
190 8"Ø EA DUCT OPEN TO PIT,
100 5100CFM

12"AFF OF PIT. PROVIDE SS


BIRDSCREEN. (215CFM)
CG-3

1
MOUNT BOTTOM OF SUPPLY 8
CG-3
CD-1 DUCT AT 20'-0" AFF.
250

CD-1 ROUTE HORIZONTAL

30"X30"
190 DUCT IN JOIST SPACE

20"X20" EA DUCT UP TO EF,


CG-5 PROVIDE DRIP PAN MOUNTED
100 12" BELOW BOTTOM OF
CONCRETE PLANK. SEE
DETAIL 1/H501T

MAU-4T
T
HC

30"X30" EA DUCT FROM 12" AFF, 10 AREA 'K'


END OF DUCT OPEN TO ROOM
LVR-1T
WITH BIRDSCREEN.
AREA 'H' AREA 'J'

AREA 'L'
AREA 'B'
AREA 'E' AREA 'C'

AREA 'A'
AREA 'F'
AREA 'D'

MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART


OF A SEPARATE DRAWING SET
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
SHEET GENERAL NOTES
1. SEE APPLICABLE NOTES ON SHEET H001T.

H1 H2

HA

ENGINEERING FIRM NO. F-9414

32"X18" SUPPLY AND


RETURN UP TO ROOF
HB
TO UNIT.

JONATHAN R. OLSON
26X14 119296
26X14

26"X14" SUPPLY AND


RETURN DOWN
12/19/16

12"X12" EA DUCT 12"X12" EA DUCT UP TO


FROM BELOW EF-7T, SEE DETAIL 2/H501T

12X12

HC

AREA 'K'

AREA 'H' AREA 'J'

AREA 'L'
AREA 'B'
AREA 'E' AREA 'C'

AREA 'A'
AREA 'F'
AREA 'D'

MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART


OF A SEPARATE DRAWING SET
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
SHEET GENERAL NOTES
1. SEE APPLICABLE NOTES ON SHEET H001T.

2. ROUTE CONDENSATE FROM ROOF TOP UNIT TO DOWN SPOUT SCUPPER.

# SHEET KEY NOTES


1. 10"x10" EXHAUST DUCT UP TO EF-1G.

2. 16"x16" SUPPLY AND 14"X24" RETURN AIR DUCT UP TO RTU-1G.

J1 J2

JA

CD-2
100

CG-5
100


JB

CG-4
50
CD-2
100


CG-5
100


EF-1G 6Ø
(ON ROOF)
8x10
CD-1
100 WALL OUTLET EXHAUST WEATHERHOOD
TERMINAL

UC
JC
1

CG-3 19"x8"

CD-1 EF-1FP EF-2FP
100 UC

2 RTU-1G
T
H
MOUNT BOTTOM OF
EXHAUST FAN AT
16x14 8'-0" AFF.
10x10

MOUNT BOTTOM OF
EXHAUST FAN AT 6'-0" AFF.
12x14

RTU-1G
(ON ROOF)

12Ø 12Ø

CD-1 CD-1
400 400
ENGINEERING FIRM NO. F-9414

JD

JONATHAN R. OLSON
EUH-1FP 119296
REVERSE ACTING
MOUNT BOTTOM OF UNIT
HEATER AT 7'-0" AFF.
EF-2FP REV. T
EUH-1FP T 12/19/16

MOUNT BOTTOM OF LVR-1FP


LOUVER AT 16" AFF.

AREA 'K'

AREA 'H' AREA 'J'

AREA 'L'
AREA 'B'
AREA 'E' AREA 'C'

AREA 'A'
AREA 'F'
AREA 'D'

MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART


OF A SEPARATE DRAWING SET
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
SHEET GENERAL NOTES
1. SEE APPLICABLE NOTES ON SHEET H001T.

H1 H2 H3 H4 H5 H6 H7 H8

2" NATURAL GAS SERVICE


PRESSURE = 10 PSIG
CONNECTED LOAD = 4,670 CFH
LONGEST LENGTH = 1,275 FT

2" (2509 CFH) 2" (3641 CFH)

HA
NG NG

2" (2509 CFH) 1-1/4" (1132 CFH)

NG
EF-3T
NG

MAU-3T

NG
EF-4T

1" (199 CFH)

NG

1-1/4" NG DOWN TO
MAU-1T WATER HEATER
1-1/4" (898 CFH)
NG

1-1/2" (2310 CFH)


EF-8T
NG

NG 1-1/4" (1029 CFH)


3/4" (131 CFH)
EF-6T 1-1/4" (398 CFH)
1-1/4" (1080 CFH)

NG
X" (199CFH) NG DOWN TO
WATER HEATER
NG

1-1/4" (1230 CFH) ENGINEERING FIRM NO. F-9414


EF-1T
HB

1-1/2" NG DOWN TO
MAU-4T 1-1/2" (500 CFH) PRESSURE WASHER.
42"Ø EXHAUST DUCT FROM PAINT
BOOTH FAN. TERMINATE WITH
MANUFACTURERS EXHAUST JONATHAN R. OLSON
DUCTWORK PACKAGE.
RTU-1T 119296

12/19/16
NG

MAU-2T

NG

1-1/4" (1080 CFH)

EF-2T EF-5T

HC

AREA 'K'

AREA 'H' AREA 'J'

AREA 'L'
AREA 'B'
AREA 'E' AREA 'C'

AREA 'A'
AREA 'F'
AREA 'D'

MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART


OF A SEPARATE DRAWING SET
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
POWER WIRING TO DISCONNECT ROOF MOUNTED EXHAUST FAN GALVANIZED WIRES
BY ELECTRICAL CONTRACTOR. WITH INSULATED CURB. SEE
DO NOT ROUTE WIRING MECHANICAL AND ARCHITECTURAL
THROUGH DAMPER. DETAILS FOR CURB INSTALLATION
AND FLASHING.

FACTORY MOUNTED AND REMOVABLE CAP TO ALLOW CONNECTION OF


HINGED BASE WITH CURB SEAL. WIRED DISCONNECT A PRESSURE MEASURING INSTRUMENT.
FINISH TO MATCH FAN.

MINIMUM (10) PIPE DIAMETERS


EXHAUST DUCT GALVANIZED 1" MIN
BAND SADDLE INSULATED
FLEXIBLE DUCT

REGULATOR RELIEF VENT.


PROVIDE VENT PROTECTOR.
GALVANIZED
BAND SUPPORT
UNION
OPENING IN ROOF DECK PER
MANUFACTURERS RECOMMENDATIONS.
EQPT
DAMPER

DRIP PAN WITH WATERTIGHT UNION


FILL EXPOSED OPENINGS IN
SOLDERED OR WELDED SEAMS.
ROOF DECK AROUND CURB WITH GAS PRESSURE REGULATOR
MINIMUM DEPTH = 2 INCHES. GALVANIZED 1" MIN
FOAM-IN-PLACE INSULATION. INSULATED
PROVIDE SUPPORTS AS BAND CLAMP
NECESSARY AND INSTALL FLEXIBLE DUCT
GAS COCK DIRT LEG WITH REMOVABLE CAP TO ALLOW
ABOVE BOTTOM OF JOISTS. CONNECTION OF A PRESSURE MEASURING NOTES
INSTRUMENT AND SERVE AS A SEDIMENT TRAP. 1. SUPPORT SYSTEM MUST NOT DAMAGE DUCT OR DEFORM DUCT SHAPE.
2. MAXIMUM PERMISSIBLE SAG IS 1/2" PER FOOT OF SPACING BETWEEN SUPPORTS. A CONNECTION TO
ANOTHER DUCT OR EQUIPMENT CONSTITUTES A SUPPORT POINT.
3. THE SUPPORT SADDLE MUST COVER ONE-HALF THE CIRCUMFERENCE OF THE OUTSIDE DIAMETER OF
THE FLEXIBLE DUCT AND FIT NEATLY AROUND THE LOWER HALF OF THE DUCT'S OUTER
CIRCUMFERENCE.

ROOF MOUNTED EXHAUST FAN


POWER WIRING TO DISCONNECT WITH INSULATED CURB. SEE
BY ELECTRICAL CONTRACTOR. MECHANICAL AND ARCHITECTURAL
DO NOT ROUTE WIRING DETAILS FOR CURB INSTALLATION
THROUGH DAMPER. AND FLASHING.

FACTORY MOUNTED AND


WIRED DISCONNECT
HINGED BASE WITH CURB SEAL.
FINISH TO MATCH FAN.
ANCHOR PIPE TO SUPPORT STAND DUCT, SEE PLANS FOR SIZE

COLUMN
DUCT THRU CURB

D
BEN
F FINISHED FLOOR
"O
10
' -0 2 '-0
DAMPER OPENING IN ROOF DECK PER "M
MANUFACTURERS RECOMMENDATIONS. AX UNDERGROUND DUCT
IM
UM
SP
AC TOP DRILLED PIER
ING

EXHAUST DUCT
DRIP PAN
MINIMUM DEPTH = 2 INCHES. DRILLED PIER
SYNTHETIC PIPE SUPPORT.
MIFAB C-PORT MODEL C610 OR
APPROVED EQUAL.

PROVIDE INSULATED ROOF CURB OR SEALANT AND BACKER ROD (TYP)


FLASHING BY ROOFING CONTRACTOR.
SEE ARCHITECTURAL DRAWINGS FOR KNOCKDOWN CURB WITH ROOF INSULATED PLENUM SIDE OF DIFFUSER TO
PROPER FLASHING OF ROOF CURB. INSULATION. PROVIDE SHIMS/BLOCKING PREVENT CONDENSATION.
AS NECESSARY FOR LEVEL INSTALLATION.
OPERATOR LINKAGE AT CENTER OF BLADES GALVANIZED SHEET
SEE TABLE BELOW FOR GREENHECK METAL STRAP HANGER
FASTENING REQUIREMENTS. REFER TO
MANUFACTURER'S FASTENING INSECT SCREEN INSULATED FLEXIBLE DUCTWORK
RECOMMENDATIONS FOR OTHER (5'-0" MAX LENGTH)
EQUIPMENT. CONTINUOUS INTEGRAL BLADE HINGE
SUPPLY AIR BRANCH DUCT
VOLUME DAMPER WITH LOCKABLE
ROOF CURB SUPPORT HAND QUADRANT

ALUMINUM BLADE BRACKET


ENGINEERING FIRM NO. F-9414
ALUMINUM ADJUSTABLE BLADE
STEEL DECK ANCHORING OF ROOF CURB TO ROOF DECK
GREENHECK MINIMUM MINIMUM OPERATOR LINKAGE CONNECTING ARM
GREENHECK GREENHECK
CURB CAP SIZE FASTENERS FASTENERS
FAN MODEL FAN SIZE SUPPLY DUCT MAIN
INCHES PER SIDE TOTAL
GB/CUBE 060 - 141 17x17 - 22x22 (3) 1/4" (12) 1/4" SHEET METAL SHIELD
161 - 300 26x26 - 40x40 (3) 1/4" (12) 1/4" JONATHAN R. OLSON
GB/CUBE 2 RADIUS ELBOW
R/RB 18 - 24 14x14 - 30x30 (3) 5/16" (12) 5/16" 119296
R/RB 30 - 36 31x31 - 51x51 (3) 5/16" (12) 5/16"
R/RB 42 52x52 - 72x72 (4) 5/16" (16) 5/16"

NOTES
CEILING
12/19/16
1. CURB SUPPORT FRAMING PROVIDED BY STRUCTURAL CONTRACTOR. COORDINATE LOCATION OF UNIT SUPPLY DIFFUSER
PRIOR TO INSTALLATION.
LIGHT FIXTURE (FOR ILLUSTRATION ONLY)
2. INSTALL ONE FASTENER AT EACH CORNER & IN CENTER OF EACH SIDE. ADD ADDITIONAL FASTENERS AS
NECESSARY TO MAINTAIN A MAXIMUM OF 8" ON CENTER. 16 GAUGE WALL SLEEVE

3. FOLLOW MANUFACTURER'S INSTALLATION REQUIREMENTS FOR EQUIPMENT NOT SHOWN IN CHART.

TURNING VANES PER ACCESS PANEL


WEATHERHOOD WITH (ALTERNATE LOCATION)
W

MAKE-UP AIR UNIT SMACNA


BIRDSCREEN FOR OA INTAKE R= 1.5 x W RECOMMENDATIONS HVAC CONTRACTOR FABRICATED
PLENUM BOX WITH 12" THICK, BLACK

INSULATE DECK FOR


℄ ACCOUSTICAL LINING. PROVIDE
CONNECTION SIZED PER PLAN.
SOUND ATTENUATION.
MATCH SURROUND ROOF INSULATED FLEXIBLE DUCTWORK
INSULATION. ACCESS PANEL (5'-0" MAX LENGTH)
W
INSULATE DECK VOLUME DAMPER WITH LOCKABLE
OPENINGS FOR SOUND HAND QUADRANT.
ATTENUATION. EXHAUST/RETURN DUCT
CURB
RADIUS ELBOW MITERED ELBOW
30° MAX
60° MAX
FLEXIBLE CONNECTION

CONCENTRIC TRANSITION ECCENTRIC TRANSITION


(INCLUDING SQUARE-TO-ROUND) (INCLUDING SQUARE-TO-ROUND)
ROUND BRANCH

SPIN-IN FITTING LAY-IN CEILING

COORDINATE WITH CEILING CONTRACTOR. IF GRILLE IS


SMALLER THAN CEILING GRID SPACING, IT SHALL BE CENTERED
ON THE CEILING TILE AND GRILLE SHALL BE PROVIDED WITH
45 SURFACE MOUNT BORDER. CEILING GRID ASSEMBLY AND TILE
° L=W/4
WORK SHALL BE PERFORMED BY CEILING CONTRACTOR.
W
NOTES
1. CURB SUPPORT FRAMING PROVIDED BY STRUCTURAL CONTRACTOR. COORDINATE LOCATION OF
UNIT PRIOR TO INSTALLATION. RECTANGULAR BRANCH
RECTANGULAR MAIN
W/ BRANCH CONNECTIONS
DESIGN SERVICES

950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F


SMART BUILDING SOLUTIONS
PACKAGED ROOFTOP UNIT SCHEDULE
AIR-HANDLING DATA COOLING PERFORMANCE DATA HEATING PERFORMANCE DATA ELECTRICAL DATA
MAXIMUM MINIMUM TOTAL SENSIBLE WEIGHT REFERENCE
TAG BASIS OF DESIGN TYPE LOCATION OUTSIDE-AIR ESP MOTOR NOMINAL EADB EAWB LADB LAWB INPUT OUTPUT EAT LAT
SUPPLY-AIR SUPPLY-AIR CAPACITY CAPACITY (S)EER IEER STAGES TYPE STAGES VOLTS PHASE HERTZ MCA MOP LBS NOTES
CFM INCHES WC HP TONS DEG-F DEG-F DEG-F DEG-F MBH MBH DEG-F DEG-F
CFM CFM MBH MBH
TRANE UNITARY COOLING GUARD HOUSE 1, 2, 3, 4, 5, 6, 7,
RTU-1G 1,200 1,200 250 0.75 0.75 3 36.0 27.0 80 67 60 58 15.0 - 1 ELECTRIC 12.0 - 60 91 - 208 3 60 40.0 45.0 700
THC037 ROOFTOP ROOF 9, 10, 11, 13
TRANE UNITARY COOLING TRUCK MAINT.
RTU-1T 2,430 2,430 650 1.00 3 7.5 88 64 80 67 57 56 12.5 - 2 NATURAL GAS 150 120 60 105 2 460 3 60 19.5 25.0 1,500 1, 3, 4, 5, 6, 7, 9, 10, 13
YHC092 ROOFTOP GARAGE ROOF

SCHEDULE DEFINITIONS
AFUE = ANNUAL FUEL UTILIZATION EFFICIENCY DEG-F = DEGREES FAHRENHEIT EER = ENERGY EFFICIENCY RATIO LAWB = LEAVING AIR WET-BULB TEMPERATURE MCA = MINIMUM CIRCUIT AMPACITY VVT = VARIABLE VOLUME AND TEMPERATURE
BTUH = BRITISH THERMAL UNITS PER HOUR EADB = ENTERING AIR DRY-BULB TEMPERATURE ESP = EXTERNAL STATIC PRESSURE LAT = LEAVING AIR TEMPERATURE MOP = MAXIMUM OVERCURRENT PROTECTION
CFM = CUBIC FEET PER MINUTE EAWB = ENTERING AIR WET-BULB TEMPERATURE IEER - INTEGRATED ENERGY EFFICIENCY RATIO LBS = POUNDS SEER = SEASONAL ENERGY EFFICIENCY RATIO
dBA = A-WEIGHTED SOUND PRESSURE DECIBELS EAT = ENTERING AIR TEMPERATURE LADB = LEAVING AIR DRY-BULB TEMPERATURE MBH = BTUH x 1000 VAV = VARIABLE AIR VOLUME

SCHEDULE GENERAL NOTES


1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTIONS 237416 AND 237417.
2. UNIT WEIGHT IS APPROXIMATE AND INCLUDES ACCESSORIES.

SCHEDULE REFERENCE NOTES


1. PROVIDE UNIT WITH FACTORY-MOUNTED DISCONNECT AND THROUGH-THE-BASE ELECTRICAL CONNECTIONS. 6. PROVIDE UNIT WITH PLEATED, DISPOSABLE MERV-8 FILTERS. 11. PROVIDE UNIT WITH HUMIDIMIZER HOT-GAS REHEAT (HGRH) DEHUMIDIFICATION CONTROL.
2. PROVIDE UNIT WITH POWERED CONVENIENCE OUTLET. POWER SHALL BE UNAFFECTED BY DISCONNECT POSITION. 7. PROVIDE UNIT WITH 0-100% COMPARATIVE DRY-BULB ECONOMIZER WITH MODULATING OUTDOOR-AIR DAMPER. 12. SMOKE DETECTORS TO BE FURNISHED AND WIRED BY ELECTRICAL CONTRACTOR. INSTALL DETECTOR IN DUCTWORK AND PROVIDE CONTROL WIRING AS NECESSARY TO DISABLE UNIT.
3. PROVIDE UNIT WITH HINGED ACCESS PANELS. 8. PROVIDE UNIT WITH POWERED EXHAUST RELIEF. 13. PROVIDE UNIT WITH COMMUNICATION INTERFACE FOR BUILDING AUTOMATION SYSTEM.
4. PROVIDE UNIT WITH 14-INCH ROOF CURB. 9. PROVIDE UNIT WITH FAN STATUS AND DIRTY FILTER SWITCHES.
5. PROVIDE UNIT WITH HAIL GUARD FOR CONDENSER COIL. 10. PROVIDE UNIT WITH STAINLESS-STEEL DRAIN PAN.

MAKE-UP AIR UNIT SCHEDULE


AIR-HANDLING DATA COOLING PERFORMANCE DATA REHEAT PERFORMANCE DATA HEATING PERFORMANCE DATA ELECTRICAL DATA CURB DATA
MAXIMUM MINIMUM TOTAL SENSIBLE WEIGHT REFERENCE
TAG BASIS OF DESIGN DESCRIPTION ESP MOTOR EADB EAWB LADB LAWB CAPACITY INPUT OUTPUT AFUE EAT TEMP. RISE HEIGHT
SUPPLY-AIR SUPPLY-AIR TYPE CAPACITY CAPACITY EER TYPE TYPE STAGES VOLTS PHASE HERTZ MCA MOP BASIS OF DESIGN LBS NOTES
INCHES WC HP DEG-F DEG-F DEG-F DEG-F MBH MBH MBH % DEG-F DEG-F INCHES
CFM CFM MBH MBH
AAON DX COOLED
MAU-1T 12,000 12,000 0.75 (2) 5 DX 735 478 99 78 60 60 - HOT-GAS 128 NG 1080 864 - 30 95 10:1 480 3 60 140 150 - 14 7,500 1, 2, 3, 4, 5, 6
RN-070 INDIRECT GAS-FIRED
AAON DX COOLED
MAU-2T 12,000 12,000 0.75 (2) 5 DX 735 478 99 78 60 60 - HOT-GAS 128 NG 1080 864 - 30 95 10:1 480 3 60 140 150 - 14 7,500 1, 2, 3, 4, 5, 6
RN-070 INDIRECT GAS-FIRED
GREENHECK
MAU-3T DIRECT-FIRED GAS 21,435 21,435 0.5 20 - - - - - - - - - - DIRECT 1,132 1,041 30 45 30:1 480 3 60 35.0 60.0 GREENHECK 12 3,000 1, 2, 3, 5, 8
DGX-125-H35
GREENHECK
MAU-4T DIRECT-FIRED GAS 2,800 2,800 0.5 2 - - - - - - - - - - DIRECT 131 121 - 30 40 30:1 480 3 60 4.6 15.0 GREENHECK 12 1,100 1, 2, 3, 5, 7, 8
DGX-110-H12

SCHEDULE DEFINITIONS
AFUE = ANNUAL FUEL UTILIZATION EFFICIENCY DEG-F = DEGREES FAHRENHEIT EER = ENERGY EFFICIENCY RATIO IEER = INTEGRATED ENERGY EFFICIENCY RATIO LBS = POUNDS
BTUH = BRITISH THERMAL UNITS PER HOUR EADB = ENTERING AIR DRY-BULB TEMPERATURE ESP = EXTERNAL STATIC PRESSURE LADB = LEAVING AIR DRY-BULB TEMPERATURE MBH = BTUH x 1000
CFM = CUBIC FEET PER MINUTE EAWB = ENTERING AIR WET-BULB TEMPERATURE HGRH = HOT-GAS REHEAT LAWB = LEAVING AIR WET-BULB TEMPERATURE MCA = MINIMUM CIRCUIT AMPACITY
dBA = A-WEIGHTED SOUND PRESSURE DECIBELS EAT = ENTERING AIR TEMPERATURE HP = HORSEPOWER LAT = LEAVING AIR TEMPERATURE MOP = MAXIMUM OVERCURRENT PROTECTION

SCHEDULE GENERAL NOTES


1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 237423 AND 237433.
2. UNIT FURNISHED WITH FACTORY-MOUNTED AND WIRED DISCONNECT. INTERNALLY MOUNTED CONTROL CENTER INCLUDES MOTOR STARTERS, 24 VAC CONTROL TRANSFORMERS AND CONTROL CIRCUIT FUSING.
3. UNIT WEIGHT IS APPROXIMATE AND INCLUDES ACCESSORIES.

SCHEDULE REFERENCE NOTES


1. PROVIDE UNIT WITH LOW-LEAKAGE, MOTORIZED OUTDOOR-AIR DAMPER. 7. PROVIDE MANUFACTURER'S THREE DIFFUSER.
2. PROVIDE UNIT WITH 2" PLEATED, DISPOSABLE MERV-8 FILTERS AND DIRTY FILTER SENSORS. 8. PROVIDE WEATHERHOOD WITH ALUMINUM MESH FILTERS.
3. PROVIDE UNIT WITH BUILDING AUTOMATION SYSTEM INTERFACING.
4. PROVIDE UNIT WITH HAIL GUARDS.
5. PROVIDE UNIT WITH BAKED ENAMEL FINISH. COLOR TO BE DETERMINED DURING SUBMITTAL PROCESS.
6. INTAKE WEATHERHOOD WITH BIRDSCREEN.

POWER VENTILATOR SCHEDULE ELECTRIC UNIT HEATER SCHEDULE


MOTOR DATA ELECTRICAL DATA CURB INFORMATION DAMPER INFORMATION MOUNTING HEATING DATA ELECTRICAL DATA
AIRFLOW ESP WEIGHT REFERENCE AIRFLOW THROW WEIGHT REFERENCE
TAG BASIS OF DESIGN TYPE SIZE HEIGHT SIZE TAG BASIS OF DESIGN TYPE AREA SERVED HEIGHT CAPACITY
CFM INCHES WC DRIVE BHP HP RPM VOLTS PHASE HERTZ BASIS OF DESIGN BASIS OF DESIGN ACTUATOR dBA SONES LBS NOTES CFM FT STAGES VOLTS PHASE HERTZ FLA LBS NOTES
INCHES INCHES INCHES FT KW
CARMON MARKEL HORIZONTAL
EF-1T UTILITY SET 3,600 4.00 BELT - 7 1/2 - 480 3 60 N/A - - INTEGRAL - - - - 300 2 EUH-1FP K101 800 45 7 15.0 1 480 3 60 18.0 54 1, 2
CMB-25 UH SERIES UNIT HEATER
GREENHECK DOWNBLAST GREENHECK GREENHECK
EF-2T 8,820 0.50 BELT - 2 630 480 3 60 - 18 120V 30x30 66 15.6 300 1, 5
GB-300 CENTRIFUGAL GPI VCD-23
SCHEDULE GENERAL NOTES
GREENHECK DOWNBLAST GREENHECK GREENHECK 1. SEE SPECIFICATION SECTION 238238.
EF-3T 8,820 0.50 BELT - 2 630 480 3 60 - 18 120V 30x30 66 15.6 300 1, 5
GB-300 CENTRIFUGAL GPI VCD-23 2. MOUNTING HEIGHTS ARE MANUFACTURER'S RECOMMENDED MAXIMUM MOUNTING HEIGHT. COORDINATE/ADJUST MOUNTING HEIGHTS AS NECESSARY IN FIELD.
GREENHECK UPBLAST GREENHECK GREENHECK 3. SUPPORT UNITS FROM BUILDING STRUCTURE. DO NOT SUPPORT UNITS FROM INSULATED METAL PANELS. PROVIDE ALL MOUNTING HARDWARE AS NECESSARY.
EF-4T 5,400 0.50 DIRECT - 2 1140 460 3 60 - 18 GRAVITY - 73 22 200 1, 5
CUE-200 CENTRIFUGAL GPI WD-100
GREENHECK DOWNBLAST GREENHECK GREENHECK SCHEDULE REFERENCE NOTES
EF-5T 2,575 0.25 BELT - 1/2 780 208 3 60 - 18 GRAVITY 18x18 57 7.9 150 1, 3, 5
GB-180 CENTRIFUGAL GPI WD-100
1. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED DISCONNECT.
GREENHECK DOWNBLAST GREENHECK GREENHECK 2. PROVIDE UNIT WITH REMOTE THERMOSTAT, TRANSFORMER, AND HEAT PURGE FAN DELAY SWITCH.
EF-6T 565 0.80 DIRECT - 1/4 1660 120 1 60 - 18 GRAVITY 12x12 59 11 100 1, 3, 5
G-098-VG CENTRIFUGAL GPI WD-100
GREENHECK DOWNBLAST GREENHECK GREENHECK
EF-7T 550 0.75 DIRECT - 1/4 1405 120 1 60 - 18 GRAVITY 12x12 57 9 100 1, 3, 5
G-099-VG CENTRIFUGAL GPI WD-100

EF-8T
GREENHECK UPBLAST
2,500 0.50 BELT - 3/4 1598 480 3 60
GREENHECK
22X22 18
GREENHECK
GRAVITY 16X16 65 13.1 150 1, 5 CEILING VENTILATOR SCHEDULE
CUBE-161 CENTRIFUGAL GPI WD-100 ELECTRICAL DATA
AIRFLOW ESP WEIGHT REFERENCE
GREENHECK DOWNBLAST GREENHECK GREENHECK TAG BASIS-OF-DESIGN TYPE LOCATION SONES
EF-1G 250 0.50 DIRECT - 1/10 1500 120 1 60 17x17 18 GRAVITY 10x10 54 7.1 75 1, 3, 5 CFM INCHES WC WATTS VOLTS PHASE HERTZ LBS NOTES
G-085-VG CENTRIFUGAL GPI WD-100
GREENHECK CEILING
GREENHECK THRU WALL GREENHECK EF-1FP K101 700 0.25 350 120 1 60 5 50 1, 2, 3, 4, 5
EF-2FP 14,000 0.25 BELT - 1 1/2 440 480 3 60 - - - 120V 44x44 70 18 650 2, 6, 7, 8, 9 SP-A700 EXHAUST FAN
SBE-2L-42 PROPELLER VCD-23

SCHEDULE GENERAL NOTES


SCHEDULE DEFINITIONS
1. PROVIDE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 233423.
BHP = BRAKE HORSE POWER ENCL = ENCLOSURE ODP = OPEN DRIP PROOF TENV = TOTALLY ENCLOSED, NOT VENTILATED
2. ALL FANS SHALL HAVE AMCA-CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR THE AMCA-CERTIFIED RATINGS SEAL. ENGINEERING FIRM NO. F-9414
CFM = CUBIC FEET PER MINUTE ESP = EXTERNAL STATIC PRESSURE RPM = REVOLUTIONS PER MINUTE VDC = VOLTAGE DIRECT CURRENT
3. VENTILATORS SHALL COMPLY WITH UL 507.
dBA = A-WEIGHTED SOUND PRESSURE DECIBELS EXP = EXPLOSTION PROOF TEFC = TOTALLY ENCLOSED, FAN-COOLED WC = WATER COLUMN
4. FAN WEIGHTS ARE APPROXIMATE AND INCLUDE ACCESSORIES.

SCHEDULE GENERAL NOTES


1. PROVIDE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 233423. 4. FAN WEIGHTS ARE APPROXIMATE AND INCLUDE ACCESSORIES. SCHEDULE REFERENCE NOTES
2. ALL FANS SHALL HAVE AMCA-CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR THE AMCA-CERTIFIED RATINGS SEAL. 5. ALL SINGLE-PHASE FAN MOTORS SHALL INCLUDE THERMAL OVERLOAD PROTECTION. 1. UNIT FURNISHED WITH INTERNAL DISCONNECT HARNESS PLUG. EXTERNAL DISCONNECT SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.
3. POWER VENTILATORS SHALL COMPY WITH UL 705. 6. ALL THREE-PHASE FAN MOTORS SHALL BE PREMIUM EFFICIENCY AND INVERTER-DUTY RATED. 2. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED SPEED CONTROL.
JONATHAN R. OLSON
3. PROVIDE UNIT WITH ISOLATION KIT.
4. PROVIDE UNIT WITH ALUMINUM GRILLE WITH WHITE ENAMEL FINISH. 119296
SCHEDULE REFERENCE NOTES
1. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED, NEMA-1 TOGGLE DISCONNECT. 5. PROVIDE UNIT WITH WALL OUTLET EXHAUST TERMINAL.
6. PROVIDE FLUSH EXTERIOR WALL HOUSING WITH OSHA GUARD.
2. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED, NEMA-3R TOGGLE DISCONNECT. 7. PROVIDE UNIT WITH CLOSURE ANGLES.
3. PROVIDE MOTOR WITH SPEED CONTROL DIAL ON MOTOR. 8. PROVIDE 45 DEGREE WEATHERHOOD WITH BIRDSCREEN.
4. PROVIDE UNIT WITH 0-10 VDC SIGNAL SPEED CONTROL. 9. PROVIDE PERMATECTOR COATING FOR FAN, WALL HOUSING, GUARD, DAMPER, AND WEATHERHOOD. DIFFUSER, GRILLE, AND REGISTER SCHEDULE 12/19/16
5. PROVIDE UNIT WITH HINGED BASE AND CURB SEAL.
PANEL SIZE NECK SIZE REFERENCE
TAG BASIS OF DESIGN TYPE MOUNTING FINISH
INCHES INCHES NOTES
TITUS SQUARE PLAQUE
CD-1 LAY-IN 24 x 24 - WHITE 1
LOUVER SCHEDULE OMNI DIFFUSER
NOMINAL DIMENSIONS FREE-AREA PRESSURE NET ACTUATOR TITUS SQUARE PLAQUE
AIRFLOW REFERENCE CD-2 SURFACE 24 x 24 - WHITE 1
TAG BASIS-OF-DESIGN TYPE LOCATION VELOCITY DROP FREE AREA FINISH OMNI DIFFUSER
LENGTH HEIGHT DEPTH LOUVER CFM FAIL NOTES
FPM INCHES WC SQ FT TYPE QUANTITY VOLTS PHASE HERTZ
INCHES INCHES INCHES SECTIONS POSITION LOW VELICTY
TITUS
GREENHECK COMBINATION KYNAR 70% CD-3 PERFORATED DIFFUSER LAY-IN 24 x 24 - WHITE 1
LVR-1T H114 54 31 6 1 2,575 500 0.04 5.20 NEMA 3R 1 CLOSED 120 1 60 1, 2, 3 TRITEC
ECD-601 INTAKE LOUVER/DAMPER THREE-COAT (TWO-WAY THROW)
GREENHECK COMBINATION KYNAR 70% LOW VELICTY
LVR-1FP K101 96 88 6 2 14,700 485 0.03 30.30 NEMA 3R 2 OPEN 120 1 60 1, 2, 3 TITUS
ECD-601 INTAKE LOUVER/DAMPER THREE-COAT CD-4 PERFORATED DIFFUSER LAY-IN 24 x 48 - WHITE 1
TRITEC
(TWO-WAY THROW)
SCHEDULE GENERAL NOTES TITUS FILTERED, EGG CRATE
CG-1 LAY-IN 24 x 24 22 x 22 WHITE
1. ALL LOUVERS SHALL HAVE AMCA-CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR THE AMCA-CERTIFIED RATINGS SEAL. 50FF RETURN GRILLE
TITUS FILTERED, EGG CRATE
CG-2 LAY-IN 24 x 12 22 x 10 WHITE
50FF RETURN GRILLE
SCHEDULE REFERENCE NOTES
1. PROVIDE UNIT WITH INTERNAL INSECT & BIRDSCREEN. TITUS EGG CRATE
CG-3 LAY-IN 24 x 24 22 x 22 WHITE
2. PROVIDE UNIT WITH 2-INCH FLANGED FRAME. 50F RETURN GRILLE
3. FINISH COLOR TO BE CUSTOM COLOR SELECTED BY ARCHITECT DURING SUBMITTAL PHASE. TITUS EGG CRATE
CG-4 LAY-IN 24 x 12 22 x 10 WHITE
50F RETURN GRILLE
TITUS EGG CRATE
CG-5 SURFACE 24 x 12 22 x 10 WHITE
50F RETURN GRILLE
ELECTRIC WALL AND CEILING HEATER SCHEDULE TITUS EGG CRATE
CG-6 LAY-IN 48 x 24 46 x 22 WHITE
ENCLOSURE ELECTRICAL DATA 50F RETURN GRILLE
AIRFLOW COIL REFERENCE
TAG BASIS OF DESIGN TYPE LOCATION LENGTH HEIGHT TITUS LINEAR 2-SLOT
CFM kW MOUNTING VOLTS PHASE HERTZ FLA NOTES LD-1 LAY-IN - - BLACK 4, 5
INCHES INCHES TBDI-80-24-2HP-8-1.5 DIFFUSER PLENUM
MARKEL TITUS LINEAR 4-SLOT
EWH-1T WALL HEATER H101 175 2.3 16 21 SURFACE 277 1 60 10.8 1, 2 LD-2 LAY-IN - - BLACK 4, 5
3320 SERIES TBDI-80-48-4HP-8-.75 DIFFUSER PLENUM
TITUS SINGLE DEFLECTION
RG-1 SURFACE - - WHITE
SCHEDULE GENERAL NOTES 350RL RETURN GRILLE
1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 238239. TITUS DOUBLE-DEFLECTION
SG/R-1 SURFACE - - WHITE 1
2. COLOR TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS BY ARCHITECT DURING SUBMITTAL PROCESS. 122RL SUPPLY GRILLE
TITUS DOUBLE-DEFLECTION
SG/R-2 SURFACE - - PRIMER 3
SCHEDULE REFERENCE NOTES S300FL SUPPLY GRILLE
1. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED DISCONNECT. SCHEDULE GENERAL NOTES
2. PROVIDE UNIT WITH INTEGRAL, VANDAL-PROOF, DOUBLE-POLE THERMOSTAT. 1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS
LISTED IN SPECIFICATIONSECTION 233713.
2. SCHEDULE IS TYPICAL FOR BOTH DISTRIBUTION FACILITY AND TRUCK MAINTENANCE FACILITY.
ALL DEVICES MAY NOT BE USED IN BOTH DRAWING SETS.

SCHEDULE REFERENCE NOTES


1. NECK SIZE TO MATCH BRANCH DUCT SIZE AS INDICATED ON PLANS.
2. PROVIDE UNIT WITH OPPOSED BLADE DAMPER FOR AIR-BALANCING.
3. PROVIDE UNIT WITH AIR SCOOP DAMPER.
4. PROVIDE CROSS NOTCH AS NECESSARY.
5. COORDINATE CEILING TRIM TEES WITH GENERAL CONTRACTOR.
HVAC Characteristics

Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including
types of ventilation, equipment configurations, and operation and maintenance issues was acquired by examining the building plans,
conducting a building walk-through, and speaking with the building owner, manager, and/or operator. This information was collected
using standard forms available in the appendices of the protocol during the building preliminary visit, and verified by the field team during
the study week.

Exhibit Contents 

1. Type of Ventilation
2. Cooling System Equipment - Primary and Secondary
3. Heating System Equipment - Primary and Secondary
4. Heating and Cooling Profiles - Number of Space Conditioning Days Per Week and Weekend
5. Heating and Cooling Profiles - Number of Space Conditioning and Ventilation Hours Per Day
6. Primary HVAC Control Implementation
7. Primary HVAC Control Response Strategy
8. Particle Filtration Systems - Frequency of Maintenance Actions for Different Configurations
9. Frequency of Inspection for HVAC Components
10. Frequency of Cleaning for HVAC Components
11. Frequency of Maintenance Actions for Fan Coil Units and Terminal Units
12. Control System - Frequency of Inspection and Sensor Calibration
13. Frequency of Testing and Balancing

 
BASE Buildings HVAC Characteristics: Type of Ventilation

Number of Buildings
Type of Ventilation Reporting1
Mechanical 98
Natural 3
Total Number of Buildings Reporting 100
1
Column total adds up to greater than the total number of buildings
reporting as one building used a combination of mechanical
ventilation and natural ventilation (the building's study space
employed natural ventilation, while mechanical ventilation was
used in another portion of the building).

Variable Descriptions:

Type of Ventilation defines the primary means of providing outdoor air to the building.

The following categories apply:

Mechanical ventilation employs a powered system to bring outdoor air into the building.

Natural ventilation operates without external power, employing pressure differences caused by wind and
temperature to induce airflow through the building, and includes any un-powered ventilation approach such as
operable windows, ventilation shafts, intentional ventilation openings in walls, and envelope leakage. A building
with a natural ventilation system may still have powered exhaust systems serving certain areas in the building.

BHC-1
BASE Buildings HVAC Characteristics: Cooling System Equipment - Primary and Secondary

Number of Buildings Reporting


Primary Secondary
Cooling System Equipment Cooling System 1 Cooling System 1
Chillers 72 0
Packaged AC Units 9 23
Heat Pump 2 10
Ducted Air Distribution 94 2
Fan Coil Units 6 20
Individual Room AC 4 68
Central System With Cooling Coils 80 1
Split AC System 9 21
Makeup Air Units 16 13
Total Number of Buildings Reporting 99 99
Notes:
1
Based on those buildings in the dataset that had cooling systems (n=99). Values
within each column add up to greater than 99 as some buildings had more than one
primary or secondary cooling system equipment entered into the database.

Variable Descriptions:

Primary Cooling System is the equipment that provides cooling to the majority of the building.

Secondary Cooling System is the equipment that provides cooling to the remaining areas of the building or serves as back up to the primary
system.

The following cooling system categories apply:

Chillers are evaporators that chill water or other liquids and provide a chilled liquid to a central air handling system.
Packaged AC Units are factory assembled air conditioning units equipped with the ability to heat or cool. Cooling is provided using a direct
expansion refrigeration cycle.
Heat Pumps are factory assembled units with the capacity to heat and cool. A single system can be used to condition an entire building or
individual zones. Heat pump types include air-to-air, water-to-air, air-to-water, and water-to-water. Ventilation air may be supplied by a central
system to the individual units through a system of ductwork or the individual units may provide ventilation.
Ducted Air Distribution a network of ducts to carry the air to the rooms to be heated or cooled.
Fan-Coil Units consist of a finned-tube coil supplied with hot or chilled water from a central source and a fan that circulates room air over the
coil. These units are sometimes provided with an outdoor air connection through the exterior wall.
Individual Room AC is a unit that is located in and provides cooling for an individual room.
Central System with Cooling Coils are air conditioning systems that are centrally located in the building, or on the building roof. These units
may provide cooling using a chilled water cooling coil.
Split AC System is a system used for cooling where the condenser and compressor are in one package located outdoors, and the fan and
evaporator coil are located inside the building.
Makeup Air Units are fan units that solely provide outdoor air to the building.

BHC-3
BASE Buildings HVAC Characteristics: Heating System Equipment - Primary and Secondary

Number of Buildings Reporting


Primary Secondary
1
Heating System Equipment Heating System Heating System 1
Steam or Hot Water Boiler 60 1
Central System With Heating Coils 49 9
Reheat Coils in Air Distribution System 41 19
Packaged Units 4 11
Forced Air Furnace 2 2
Heat Pump 2 10
Ducted Air Distribution 81 6
Fan Coil Units 8 25
Individual Space Heating 1 7
Fin-Tube Radiators 26 17
Electric Baseboard 1 20
Makeup Air Units 9 8
Total Number of Buildings Reporting 100 100
Notes:
1
Based on those buildings in the dataset that had heating systems (n=100). Values within
each column add up to greater than 100 as some buildings had more than one primary or
secondary heating system equipment entered into the database.

Variable Descriptions:

Primary Heating System is the equipment that provides heating to the majority of the building.

Secondary Heating System is the equipment that provides heating to the remaining areas of the building or serves as back up to the primary system.

The following heating system categories apply:

Steam or Hot Water Boilers produce hot water or steam which is delivered through pipes to space heating equipment. Key components to a boiler are the combustion chamber,
burner, and the heat exchanger.
Central System with Heating Coils are air conditioning systems that are centrally located in the building, or on the building roof. These units may provide heating using a hot
water or steam heating coils.
Reheat Coils in Air Distribution System are heating coils that are located in the ductwork near the distribution point to control the temperature in an individual zone.
Packaged Units are factory assembled air conditioning units equipped with the ability to heat or cool. Heating is generally provided using gas fired heat exchanger or electric
resistance heating coils.
Forced Air Furnace heats by delivering warmed air to the spaces in a building. Components of the furnace are a heat exchanger, fuel burner, and air blower.
Heat Pumps are factory assembled units with the capacity to heat and cool. A single system can be used to condition an entire building or individual zones. Heat pump types
include air-to-air, water-to-air, air-to-water, and water-to-water. Ventilation air may be supplied by a central system to the individual units through a system of ductwork or the
individual units may provide ventilation.
Ducted Air Distribution a network of ducts to carry the air to the rooms to be heated or cooled.
Fan Coil Units consist of a finned-tube coil supplied with hot or chilled water from a central source and a fan that circulates room air over the coil. These units are sometimes
provided with an outdoor air connection through the exterior wall. Temperature controllers in the unit meter the chilled or hot water to the coil.
Individual Space Heating is a unit that is located in and provides heat for the room where it is located.
Fin-Tube Radiators are hydronic terminal units equipped with metal fins that dissipate the heat from the hot water in the piping through natural convection.
Electric Baseboard are electric terminal units that heat by electrical resistance and natural convection.
Makeup Air Units are fan units that solely provide outdoor air to the building.

BHC-4
BASE Buildings HVAC Characteristics: Heating and Cooling Profiles - Number of Space Conditioning and Ventilation Days Per Week and Weekend

Number of Buildings Reporting


Number of Space Number of Space Number of Space Number of Space
Conditioning Weekdays Conditioning Weekend Ventilation Weekdays Ventilation Weekend
Days Per Week Per Week Days Per Week 1 Per Week 2 Days Per Week 3
None 0 17 2 20
One 0 23 0 24
Two 0 59 0 54
Three 0 0 0 0
Four 0 0 0 0
Five 100 0 97 0
Total Number of Buildings Reporting 100 99 99 98
Notes:
1
Number of space conditioning days per weekend was not reported for one building.
2
Number of ventilation days weekdays per week was not reported for one building.
3
Number of ventilation days per weekend was not reported for two buildings.

Variable Descriptions:

Number of Space Conditioning Weekdays Per Week refers to the number of weekdays per week that the building's space
conditioning systems are reported to be operating.

Number of Space Conditioning Weekend Days Per Week refers to the number of days per weekend that the building's space
conditioning systems are reported to be operating.

Number of Space Ventilation Weekdays Per Week refers to the number of weekdays per week that the building's ventilation systems
are reported to be operating.

Number of Space Ventilation Weekend Days Per Week refers to the number of days per weekend that the building's ventilation
systems are reported to be operating.

BHC-5
BASE Buildings HVAC Characteristics: Heating and Cooling Profiles - Number of Space Conditioning and Ventilation Hours Per Day

Number of Space Number of Space Number of Ventilation


Conditioning Hours Conditioning Hours Number of Ventilation Hours Per Weekend
Per Weekday Per Weekend Day 1 Hours Per Weekday 2 Day3
Number of Buildings Reporting 100 98 99 97
Mean (Arithmetic) 17 13 17 12
Standard Deviation 5 9 6 9
Minimum 7 0 0 0
10th Percentile 11 0 11 0
25th Percentile 12 5 12 5
50th Percentile 16 12 16 9
75th Percentile 24 24 24 24
90th Percentile 24 24 24 24
Maximum 24 24 24 24
Notes:
1
Two buildings did not report the number of space conditioning hours per weekend day.
2
One building did not report the number of ventilation hours per weekday.
3
Two buildings did not report the number of ventilation hours per weekend day.

Variable Descriptions:

Number of Space Conditioning Hours Per Weekday refers to the number of hours per weekday that the building's space
conditioning systems are reported to be operating.

Number of Space Conditioning Hours Per Weekend Day refers to the number of hours per weekend day that the building's
space conditioning systems are reported to be operating.

Number of Ventilation Hours Per Weekday refers to the number of hours per weekday that the building's ventilation
systems are reported to be operating.

Number of Ventilation Hours Per Weekend Day refers to the number of hours per weekend day that the building's
ventilation systems are reported to be operating.

BHC-6
BASE Buildings HVAC Characteristics: Primary HVAC Control Implementation

Primary HVAC Control Implementation Number of Buildings Reporting 1


Pneumatic 42
Low Voltage Analog Electric 8
Direct Digital 20
Pneumatic / Low Voltage Analog Electric Combination 2
Pneumatic / Direct Digital Combination 18
Low Voltage Analog Electric / Direct Digital Combination 3
Pneumatic / Low Voltage Analog Electric / Direct Digital Combination 4
Total Number of Buildings Reporting 97
Notes:
1
Based on those buildings reporting a primary HVAC control implementation method (n=97).

Variable Descriptions:

Primary HVAC Control Implementation refers to the control system in place to control the operation of the heating, ventilating, and air conditioning system.

The following categories apply:

Pneumatic systems use compressed air as the source of energy to actuate the control devices of the heating, ventilating, and air conditioning system.
Low Voltage Analog Electric systems use electrical energy to actuate the control devices of the heating, ventilating, and air conditioning system.
Direct Digital systems use digital signals to control the devices of the heating, ventilating, and air conditioning system.

BHC-7
BASE Buildings HVAC Characteristics: Primary HVAC Control Response Strategy

Number of Buildings
Primary HVAC Control Response Strategy Reporting1
Two-Position 9
Proportional 79
Floating Point 3
Proportional-Integral 5
Proportional-Integral-Derivative 22
Total Number of Buildings Reporting 98
Notes:
1
Number of buildings based on those buildings reporting a primary HVAC
control response strategy (n=98). Column total adds up to greater than the
total number of buildings reporting as some buildings used a combination
of these methods.

Variable Descriptions:

Primary HVAC Control Response Strategy refers to the primary control response strategy for the building HVAC systems.

The following categories apply:

Two-Position refers to a control system in which the device being controlled is either full on or full off, with no intermediate operating positions available.

Proportional refers to a control algorithm or method in which the final control device (e.g. damper or valve) moves to a position proportional to the deviation
from the setpoint value of the controlled variable such as a temperature setpoint.

Floating Point refers to a system where the controlled device is still operated by a two position controller, but the device moves gradually between full open
and full closed. There is a neutral zone where no signal is transmitted and the controlled device "floats" in an intermediate position until a new signal is
received.

Proportional-Integral also known as "proportional plus reset" refers to a proportional control system where the control point is changed automatically back
toward the setpoint when an offset occurs.

Proportional-Integral-Derivative offers the same features as proportional-integral, but also controls the rate at which the control point is moved back to the
setpoint.

BHC-8
BASE Buildings HVAC Characteristics: Particle Filtration Systems - Frequency of Maintenance Actions for Different Configurations

Number of Buildings Reporting


Frequency of Panel Filters Frequency of Manual Roll Frequency of Automatic Roll
Frequency of Actions Replacement1 Filters Advancement2 Filters Inspection3
None 1 0 0
As Needed 4 4 0
Daily 0 0 0
Weekly 0 0 2
Bi-Weekly 0 0 0
Monthly 10 6 0
Semi-Quarterly 2 3 0
Quarterly 47 2 0
Semi-Annually 17 2 1
Annually 12 1 1
Total Number of Buildings Reporting 93 18 4
Notes:
1
Data represent panel filter replacement frequencies for 93 BASE buildings equipped with this filter type.
2
Data represent frequency of manual roll filter advancement for 18 BASE buildings equipped with this filter type.
3
Data represent frequency of automatic roll filter inspection for 4 BASE buildings equipped with this filter type.

Variable Descriptions:

Frequency of Panel Filters Replacement refers to the frequency that panel filters are changed out by building facilities personnel. Panel filters are manufactured
in rectangular panels that are placed alongside each other in the filter bed. They are removed and either replaced or cleaned when dirty.

Frequency of Manual Roll Filters Advancement refers to the frequency that manual roll filters are advanced by building facilities personnel. Manual roll filters
consist of a fabric roll mounted on a spool that moves across the airstream. The media is manually wound on a take up spool to expose new filter material when
necessary.

Frequency of Automatic Roll Filters Inspection refers to the frequency that automatic roll filters are inspected by building facilities personnel. Automatic roll filters
consist of a fabric roll mounted on a spool that moves across the airstream. The media is automatically wound on a take up spool to expose new filter. The
movement of the media is often controlled by a pressure switch which senses the pressure drop across the media, or by an automatic timer.

The frequency categories are as follows:


None means that filters are not changed, advanced or inspected.
As needed means that filters are changed, advanced or inspected only when deemed necessary.
Daily means that filters are changed, advanced or inspected each day.
Weekly means that filters are changed, advanced or inspected once per week.
Bi-weekly means that filters are changed, advanced or inspected twice a month.
Monthly means that filters are changed, advanced or inspected once per month.
Semi-Quarterly means that filters are changed, advanced or inspected twice every three months.
Quarterly means that filters are changed, advanced or inspected every three months.
Semi-annually means that filters are changed, advanced or inspected once every six months.
Annually means that filters are changed, advanced or inspected once a year.

BHC-9
BASE Buildings HVAC Characteristics: Frequency of Inspection for HVAC Components

Number of Buildings Reporting


Air Handler Heating and Air Distribution Evaporative
Frequency of Inspection Housing1 Cooling Coils2 Drain Pans 3
Ductwork4 Humidifiers 5
Coolers6 Air Washers7 Cooling Towers8
None 25 6 8 59 4 1 1 0
As Needed 10 7 7 32 4 0 0 1
Daily 7 0 3 0 1 0 0 19
Weekly 2 1 4 0 0 0 0 11
Bi-Weekly 1 0 1 0 1 1 0 3
Monthly 14 14 15 1 9 1 0 17
Semi-Quarterly 1 2 3 0 0 0 0 1
Quarterly 23 29 27 2 9 0 0 10
Semi-Annually 5 13 6 1 4 0 0 3
Annually 10 26 22 4 6 4 0 2
Total Number of Buildings Reporting 98 98 96 99 38 7 1 67
Notes:
1
Data represent 98 BASE buildings, which indicated an inspection frequency for air handling unit housing inspections.
2
Data represent 98 BASE buildings, which indicated an inspection frequency for coil inspections.
3
Data represent 96 BASE buildings, which indicated an inspection frequency for drain pans.
4
Data represent 99 BASE buildings, which indicated an inspection frequency for ductwork.
5
Data represent 38 BASE buildings, which indicated an inspection frequency for humidifiers.
6
Data represent 7 BASE buildings, which indicated an inspection frequency for evaporative coolers.
7
Data represent 1 BASE building, which indicated an inspection frequency for air washers.
8
Data represent 67 BASE buildings, which indicated an inspection frequency for cooling towers.

Page 1 of 2 BHC-10
Variable Descriptions:

Air Handler Housing refers to the inspection frequency of the air handling housing. The housing is a casing that is usually made up of galvanized sheet metal that contains the
air handling unit components.
Cooling Coils refers to the inspection frequency of the air handling unit cooling coils.
Heating Coils refers to the inspection frequency of the air handling unit heating coils.
Drain Pans refers to the inspection frequency of the cooling coil condensate drain pans. The drain pan is generally located under the cooling coil to collect and drain away water
vapor that condenses on the cooling coil.
Air Distribution Ductwork refers to the inspection frequency of the air handling unit air distribution ductwork.
Humidifiers refers to the inspection frequency of humidifiers.
Evaporative Coolers refers to the inspection frequency of evaporative coolers. Evaporative coolers are non-refrigerant systems that cool air by exchanging sensible heat for
latent heat, reducing temperatures, but raising humidity.
Air Washers refers to the inspection frequency of air washers. In some applications, air washers serve as evaporative coolers or humidifiers as their operating principle is
similar to that of evaporative coolers. These may also be used to filter wettable dust from the airstream by drawing air through a mist (caused by spray nozzles) and then through
eliminators to remove dust and the water particles not evaporated in the air.
Cooling Towers refers to the inspection frequency of cooling towers. Cooling towers are used primarily to reject building heat to the atmosphere.

The frequency categories are as follows:


None refers to no inspections taking place in the building.
As Needed refers to an inspection schedule where inspection occurs only when deemed necessary.
Daily refers to an inspection schedule where inspection occurs each day.
Weekly refers to an inspection schedule where inspection occurs on a once per week.
Bi-weekly refers to an inspection schedule where inspection occurs twice a month.
Monthly refers to an inspection schedule where inspection occurs once per month.
Semi-Quarterly refers to an inspection schedule where inspection occurs twice every three months.
Quarterly refers to an inspection schedule where inspection occurs every three months.
Semi-annually refers to an inspection schedule where inspection occurs every six months.
Annually refers to an inspection schedule where inspection occurs once a year.

Page 2 of 2 BHC-10
BASE Buildings HVAC Characteristics: Frequency of Cleaning for HVAC Components

Air Handler Heating and Air Distribution Evaporative Cooling Towers8


Frequency of Cleaning Housing1 Cooling Coils2 Drain Pans3 Ductwork4 Humidifiers5 Coolers6 Air Washers7 (surface cleaning)
None 36 13 14 77 7 0 0 1
As Needed 17 25 24 16 14 1 1 9
Daily 0 0 0 0 0 0 0 0
Weekly 0 0 0 0 0 0 0 0
Bi-Weekly 0 0 0 0 0 1 0 0
Monthly 2 0 1 0 0 0 0 2
Semi-Quarterly 0 0 0 0 1 0 0 1
Quarterly 14 5 7 1 3 0 0 7
Semi-Annually 4 8 10 0 3 0 0 10
Annually 24 47 40 2 8 5 0 36
Total Number of Buildings Reporting 97 98 96 96 36 7 1 66
Notes:
1
Data represent 97 BASE buildings, which indicated a cleaning frequency for air handling unit-housing cleaning. For one building, the response was left blank.
2
Data represent 98 BASE buildings, which indicated a cleaning frequency for heating and cooling coils.
3
Data represent 96 BASE buildings, which indicated a cleaning frequency for drain pans.
4
Data represent 96 BASE buildings, which indicated a cleaning frequency air distribution duct work.
5
Data represent 36 BASE building, which indicated a cleaning frequency for humidifiers.
6
Data represent 7 BASE buildings, which indicated a cleaning frequency for evaporative coolers.
7
Data represent 1 BASE buildings, which indicated a cleaning frequency for air washers.
8
Data represent 66 BASE buildings, which indicated a cleaning frequency for cooling towers.

Page 1 of 2 BHC-11
Variable Descriptions:

Air Handler Housing refers to the cleaning frequency of the air handling housing. The housing is a casing that is usually made up of galvanized sheet metal that contains the air
handling unit components.
Cooling Coils refers to the cleaning frequency of the air handling unit cooling coils.
Heating Coils refers to the cleaning frequency of the air handling unit heating coils.
Drain Pans refers to the cleaning frequency of the cooling coil condensate drain pans. The drain pan is generally located under the cooling coil to collect and drain away water
vapor that condenses on the cooling coil.
Air Distribution Ductwork refers to the cleaning frequency of the air handling unit air distribution ductwork.
Humidifiers refers to the cleaning frequency of humidifiers.
Evaporative Coolers refers to the cleaning frequency of evaporative coolers. Evaporative coolers are non-refrigerant systems that cool air by exchanging sensible heat for latent
heat, reducing temperatures, but raising humidity.
Air Washers refers to the cleaning frequency of air washers. In some applications, air washers serve as evaporative coolers or humidifiers as their operating principle is similar to
that of evaporative coolers. These may also be used to filter wettable dust from the airstream by drawing air through a mist (caused by spray nozzles) and then through
eliminators to remove dust and the water particles not evaporated in the air.
Cooling Towers refers to the cleaning frequency of cooling towers. Cooling towers are used primarily to reject building heat to the atmosphere.

The frequency categories are as follows:


None refers to no cleaning implemented on these systems.
As Needed refers to a cleaning schedule where cleaning occurs only when deemed necessary.
Daily refers to a cleaning schedule where cleaning occurs each day.
Weekly refers to a cleaning schedule where cleaning occurs on a once per week.
Bi-weekly refers to a cleaning schedule where cleaning occurs twice a month.
Monthly refers to a cleaning schedule where cleaning occurs once per month.
Semi-Quarterly refers to a cleaning schedule where cleaning occurs twice every three months.
Quarterly refers to a cleaning schedule where cleaning occurs every three months.
Semi-annually refers to a cleaning schedule where cleaning occurs every six months.
Annually refers to a cleaning schedule where cleaning occurs once a year.

Page 2 of 2 BHC-11
BASE Buildings HVAC Characteristics: Frequency of Maintenance Actions for Fan Coil Units and Terminal Units

Number of Buildings Reporting


Fan Coil Units - Fan Coil Units - Terminal Units -
Frequency of Frequency of Filter Frequency of
1 2
Frequency of Actions Inspection Changing Inspection3
None 7 2 21
As Needed 2 5 41
Daily 1 0 0
Weekly 1 0 0
Bi-Weekly 0 1 0
Monthly 9 4 1
Semi-Quarterly 0 1 1
Quarterly 11 14 6
Semi-Annually 6 3 4
Annually 8 9 9
Total Number of Buildings Reporting 45 39 83
Notes:
1
Data represent 45 BASE buildings, which indicated an inspection frequency for fan coil units.
2
Data represent 39 BASE buildings, which indicated a filter changing frequency for fan coil units.
3
Data represent 83 BASE buildings, which indicated an inspection frequency for terminal units.

Variable Descriptions:

Fan Coil Units - Frequency of Inspection refers to the frequency of inspection for fan coil units.

Fan Coil Units - Frequency of Filter Changing refers to the frequency that fan coil unit filters are changed out by building facilities personnel.

Terminal Units - Frequency of Inspection refers to the frequency of inspection for terminal units.

The frequency categories are as follows:


None means that no inspection or filter change out takes place.
As Needed refers to a maintenance schedule where maintenance occurs only when deemed necessary.
Daily refers to a schedule where inspection or filter change out occurs each day.
Weekly refers to a schedule where inspection or filter change out occurs once per week.
Bi-weekly refers to a schedule where inspection or filter change out occurs twice a month.
Monthly refers to a schedule where inspection or filter change out occurs once per month.
Semi-Quarterly refers to a schedule where inspection or filter change out occurs twice every three months.
Quarterly refers to a schedule where inspection or filter change out occurs every three months.
Semi-annually refers to a schedule where inspection or filter change out occurs every six months.
Annually refers to a schedule where inspection or filter change out occurs once a year.

BHC-12
BASE Buildings HVAC Characteristics: Control System - Frequency of Inspection and Sensor Calibration

Number of Buildings Reporting


Frequency of Control Frequency of Sensor
Frequency of Actions System Inspection1 Calibration2
None 12 15
As Needed 28 58
Daily 14 0
Weekly 2 0
Bi-Weekly 1 0
Monthly 4 4
Semi-Quarterly 0 0
Quarterly 12 3
Semi-Annually 11 7
Annually 14 10
Total Number of Buildings Reporting 98 97
Notes:
1
Data represent 98 BASE buildings, which indicated an inspection frequency.
2
Data represent 97 BASE buildings, which indicated a calibration frequency.

Variable Descriptions:

Frequency of Control System Inspection refers to the frequency of inspection for the heating, ventilating, and air conditioning system control system.

Frequency of Sensor Calibration refers to the frequency of sensor calibration for the heating, ventilating, and air conditioning system control system.

The frequency categories are as follows:


None means that no inspections or calibrations take place.
As Needed refers to an inspection or calibration schedule that occurs only when deemed necessary.
Daily refers to an inspection or calibration schedule where inspection occurs each day.
Weekly refers to an inspection or calibration schedule where inspection occurs on a weekly cycle.
Bi-weekly refers to an inspection or calibration schedule where inspection occurs twice a month.
Monthly refers to an inspection or calibration schedule where inspection occurs on a monthly schedule.
Semi-Quarterly refers to an inspection or calibration schedule where inspection occurs twice every three months.
Quarterly refers to an inspection or calibration schedule where inspection occurs every three months.
Semi-annually refers to an inspection or calibration schedule where inspection occurs every six months.
Annually refers to an inspection or calibration schedule where inspection occurs once a year.

BHC-13
BASE Buildings HVAC Characteristics: Frequency of Testing and Balancing

Number of Buildings
Frequency of Testing and Balancing Reporting1
None 43
As Needed 52
Daily 0
Weekly 0
Bi-Weekly 0
Monthly 0
Semi-Quarterly 0
Quarterly 0
Semi-Annually 0
Annually 3
Total Number of Buildings Reporting 98
Notes:
1
Data represent 98 BASE buildings, which indicated a frequency for
testing and balancing.

Variable Descriptions:

Frequency of Testing and Balancing refers to the frequency that testing and balancing is implemented on the building's air distribution system.

The frequency categories are as follows:


None means that no testing and balancing takes place.
As Needed refers to a schedule where testing and balancing occurs only when deemed necessary.
Daily refers to a schedule where testing and balancing occurs each day.
Weekly refers to a schedule where testing and balancing occurs on a weekly cycle.
Bi-weekly refers to a schedule where testing and balancing occurs twice a month.
Monthly refers to a schedule where testing and balancing occurs on a monthly schedule.
Semi-Quarterly refers to a schedule where testing and balancing occurs twice every three months.
Quarterly refers to a schedule where testing and balancing occurs every three months.
Semi-annually refers to a schedule where testing and balancing occurs every six months.
Annually refers to a schedule where testing and balancing occurs once a year.

BHC-14
GENERAL NOTES: HVAC SPECIFICATIONS: MECHANICAL LEGEND ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
1. IT IS THE INTENT OF THESE SPECIFICATIONS TO COVER FIRST CLASS WORKMANSHIP THROUGHOUT. PERSONNEL SHALL BE THOROUGHLY TRAINED 19. MECHANICAL CONTRACTOR SHALL HAVE THE FINAL START-UP OF ALL HVAC EQUIPMENT SUPERVISED AND MONITORED BY A FACTORY AUTHORIZED DUCTWORK BHP BRAKE HORSEPOWER
AND EXPERIENCED IN THE PRODUCTS INVOLVED AND RECOMMENDED METHODS FOR THEIR FABRICATION AND INSTALLATION. NO ALLOWANCE TECHNICIAN. CONTRACTOR SHALL SUBMIT A WRITTEN HVAC SYSTEM START-UP SUPERVISION VERIFICATION FORM. SUPPLY: ELBOW BOD BOTTOM OF DUCT
SHALL BE MADE FOR LACK OF SKILL ON THE PART OF THE WORKMAN IN THE ACCEPTANCE AND/OR REJECTION OF COMPLETED WORK. UNLESS OTHERWISE NOTED, SUPPLY AIR DUCT SHALL BE GALVANIZED SHEET METAL OF GAUGE & CONSTRUCTION AS REQUIRED BY BOP BOTTOM OF PIPE
20. PROVIDE ACCESS TO ALL DAMPERS AS REQUIRED FOR MAINTENANCE. SMACNA 2 in-wg PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. NO INCREASE IN SIZE REQUIRED CFM CUBIC FEET PER MINUTE
2. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED AS INDICATED ON THE DRAWINGS AND/OR SPECIFICATIONS. THEY SHALL BE INSTALLED FOR DUCT LINER). SEAL ALL DUCTWORK PER SMACNA CLASS B. D DRAIN
PLUMB, LEVEL, AND TRUE-TO-LINE WITH ADJACENT WORK. WHERE INSTALLATION METHODS ARE NOT SPECIFICALLY COVERED BY THE DRAWINGS 21. FIRE DAMPERS WITH ACCESS DOORS SHALL BE INSTALLED IN ALL DUCTWORK PASSING THROUGH FIRE SEPARATING WALLS, PARTITIONS, AND FIRE DWG DRAWING
AND/OR SPECIFICATIONS, FIRST CLASS TRADE PRACTICES AND MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS SHALL GOVERN. RATED CEILINGS. ALL SUPPLY DUCT FROM RTU-17 TO AIR TERMINAL UNITS SHALL BE GALVANIZED SHEET METAL OF GAUGE AND CONSTRUCTION AS RECTANGULAR TEE EA EXHAUST AIR
REQUIRED BY SMACNA 6" W.G. PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS.) SEAL ALL EAT ENTERING AIR TEMPERATURE
DUCTWORK PER SMACNA CLASS A. EF EXHAUST FAN
3. CAREFULLY EXAMINE ALL ARCHITECTURAL, STRUCTURAL, PLUMBING, HVAC, FIRE PROTECTION, AND ELECTRICAL DRAWINGS PERTAINING TO THE 22. MAINTAIN A MINIMUM DISTANCE OF 10'-0" FROM ROOF MOUNTED HVAC EQUIPMENT TO THE EDGE OF THE ROOF.
EWH ELECTRIC WALL HEATER
CONSTRUCTION. COOPERATE WITH OTHER TRADES IN LOCATING DUCTWORK, PIPING, EQUIPMENT, ETC., IN ORDER TO AVOID CONFLICT WITH INSULATED DOUBLE WALL DUCT SHALL BE FABRICATED WITH AN OUTER SHELL AND A PERFORATED INNER LINER WITH 1" FFE FINISHED FLOOR ELEVATION
OTHER TRADES' WORK. NO CLAIM FOR COSTS WILL BE ALLOWED FOR RELOCATING EQUIPMENT, PIPING, DUCTWORK, ETC., WHICH INTERFERES 23. HVAC UNIT LEVELING SHALL BE BY MECHANICAL CONTRACTOR. FIBERGLASS INSULATION BETWEEN THE SHELL AND LINER. (DUCT DIMENSIONS SHOWN ARE EXTERIOR SHEET METAL DIMENSIONS.) FIN FL FINISHED FLOOR
WITH OTHER TRADES' WORK. FV FIELD VERIFY
24. MECHANICAL CONTRACTOR SHALL PROVIDE CONDENSATE TRAP AT EACH AIR HANDLING UNIT. ELBOWS & TEES SHALL INCLUDE TURNING VANES. G.C. GENERAL CONTRACTOR
4. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF DUCTWORK, PIPING AND EQUIPMENT. DO NOT SCALE DRAWINGS. RECTANGULAR/ROUND TRANSITION HP HORSEPOWER
THE EXACT LOCATION AND/OR ROUTING OF EQUIPMENT, DUCTWORK, PIPING, ETC., UNLESS SPECIFICALLY DIMENSIONED ON THE DRAWINGS, 25. FRESH AIR INTAKE SHALL BE MINIMUM OF 10'-0" FROM ANY EXHAUST FAN, FLUE OR PLUMBING VENT. COORDINATE WITH GENERAL CONTRACTOR. PROVIDE FLEXIBLE CONNECTIONS AT EQUIPMENT. LAT LEAVING AIR TEMPERATURE
SHALL BE DETERMINED IN THE FIELD. MAKE REASONABLE MODIFICATIONS IN THE INSTALLATION SO ALL DUCTWORK FITS PROPERLY AND M MANUAL VOLUME DAMPER
EQUIPMENT CAN BE SERVICED. RETURN: M.C. MECHANICAL CONTRACTOR
26. MECHANICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CATALOG SHEETS TO ARCHITECT/ENGINEER AND SHALL INCLUDE: UNLESS OTHERWISE NOTED, RETURN AIR DUCT SHALL BE GALVANIZED SHEET METAL OF GAUGE & CONSTRUCTION AS REQUIRED MD MOTORIZED DAMPER
BY SMACNA 2 in-wg PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. NO INCREASE IN SIZE HIGH-EFFICIENCY TAKE-OFF NC NORMALLY CLOSED
5. HVAC EQUIPMENT AND INSTALLATION SHALL CONFORM TO THE LATEST EDITION OF THE STATE PLUMBING CODE, STATE MECHANICAL CODE, STATE FIRE A. FANS
REQUIRED FOR DUCT LINER). SEAL ALL DUCTWORK PER SMACNA CLASS B. N.C. NOISE CRITERIA
CODE, STATE BUILDING CODE, APPLICABLE OSHA AND NFPA STANDARDS, COUNTY AND CITY BUILDING REGULATIONS AND CODES.
B. ELECTRIC WALL HEATERS NG NATURAL GAS
ELBOWS & TEES SHALL INCLUDE TURNING VANES. RECTANGULAR BEVELED TAP NO NORMALLY OPEN
6. FABRICATION AND INSTALLATION OF DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS, STATE NTS NOT TO SCALE
MECHANICAL CODE AND APPLICABLE NFPA STANDARDS. C. GRILLES, REGISTERS, AND DIFFUSERS
PROVIDE FLEXIBLE CONNECTIONS AT EQUIPMENT. P.C. PLUMBING CONTRACTOR
D. HVAC CONTROLS PD PRESSURE DROP
7. MECHANICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, TOOLS, AND EQUIPMENT TO INSTALL ALL HVAC SYSTEMS AS INDICATED ON THESE EXHAUST/TRANSFER: RECTANGULAR/ROUND EXTERNALLY INSULATED DUCT PRV PRESSURE REDUCING VALVE
DRAWINGS. E. VIBRATION ISOLATORS UNLESS OTHERWISE NOTED, EXHAUST AIR DUCT SHALL BE GALVANIZED SHEET METAL OF GAUGE & CONSTRUCTION AS REQUIRED RA RETURN AIR
BY SMACNA 2 in-wg PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. NO INCREASE IN SIZE RH RELATIVE HUMIDITY
8. MECHANICAL CONTRACTOR SHALL ARRANGE AND PAY FOR MECHANICAL PERMITS AND INSPECTIONS AS REQUIRED BY LOCAL ORDINANCES. REQUIRED FOR DUCT LINER). SEAL ALL DUCTWORK PER SMACNA CLASS B. RTU ROOF TOP UNIT
F. INSULATION
RECTANGULAR/ROUND INTERNALLY INSULATED DUCT SA SUPPLY AIR
ELBOWS & TEES SHALL INCLUDE TURNING VANES. SF SUPPLY FAN
9. DELIVER MATERIALS TO PROJECT IN GOOD CONDITION. STORE MATERIALS OFF GROUND AND PROTECTED FROM THE ELEMENTS. G. AIR TERMINAL UNITS SHT SHEET
PROVIDE FLEXIBLE CONNECTIONS AT EQUIPMENT. SP STATIC PRESSURE
10. VERIFY DIMENSIONS IN FIELD. VERIFY STRUCTURAL DETAILS BEFORE INSTALLING DUCTWORK. NO EXTRA COMPENSATION WILL BE ALLOWED H. ROOFTOP UNITS TBE THREADED BOTH ENDS
BECAUSE OF DIFFERENCES BETWEEN ACTUAL MEASUREMENTS AND DIMENSIONS AND THOSE INDICATED ON THE DRAWINGS. NOTIFY
TOD TOP OF DUCT
ARCHITECT/ENGINEER IN WRITING OF ANY DIFFERENCE WHICH MAY BE FOUND BEFORE PROCEEDING WITH WORK I. GAS REGULATORS INSULATION TOP TOP OF PIPE
DUCTWORK: RECTANGULAR 1.5xCL RADIUS ELBOW TYP TYPICAL
11. MECHANICAL CONTRACTOR SHALL KEEP ACCURATE RECORDS OF ALL DUCTWORK AND EQUIPMENT WHICH DEVIATED FROM THE DRAWINGS. AT 27. PROVIDE PIPE MARKERS FOR NATURAL GAS PIPING SYSTEMS. PIPE MARKERS SHALL BE PRESSURE SENSITIVE VINYL, CONFORM TO ANSI A13.1 AS INTERNAL FIBERGLASS DUCT LINER: UNO UNLESS NOTED OTHERWISE
COMPLETION OF WORK, CONTRACTOR SHALL SUBMIT A MARKED SET OF DESIGN PRINTS INDICATING CHANGES. MANUFACTURED BY SETON NAMEPLATE CORPORATION, OR APPROVED EQUAL. PIPE MARKERS SHALL BE APPLIED NEAR EACH BRANCH JOHNS MANVILLE LINACOUSTIC RC FIBERGLASS DUCT LINER WITH REINFORCED COATING (OR APPROVED EQUAL) INSTALLED IN VAV VARIABLE AIR VOLUME
CONNECTION, EVERY TWENTY FEET IN STRAIGHT RUNS, AND INCLUDE FLOW ARROWS. ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION SPECIFICATIONS. VFD VARIABLE FREQUENCY DRIVE
12. ALL PENETRATIONS THROUGH WALLS SHALL BE PROVIDED WITH PROPER SIZED SLEEVES. SEAL ALL PIPE SLEEVES WITH APPROPRIATE VIF VERIFY IN FIELD
CAULKING. ALL SIX (6) INCH AND SMALLER PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE INSTALLED IN 28. CONTRACTOR SHALL FIELD DETERMINE ALL DUCT TRANSITIONS PER DUCT SIZES INDICATED, AIR HANDLING EQUIPMENT INLETS/OUTLETS AND/OR EXTERNAL FIBERGLASS DUCT WRAP:
ACCORDANCE WITH APPROPRIATE 3M FIRESTOP SYSTEM (OR APPROVED EQUAL). ALL PIPING SLEEVES SHALL BE SCHEDULE 40, CARBON STEEL, SUPPLY/RETURN AIR GRILLES/DIFFUSERS. PROVIDE FLEXIBLE CONNECTIONS AT ALL EQUIPMENT AND AT ALL CEILING MOUNTED JOHNS MANVILLE MICROLITE FORMALDEHYDE-FREE FIBERGLASS DUCT WRAP (OR APPROVED EQUAL) INSTALLED IN ACCORDANCE
ASTM A53, GRADE B. SUPPLY/RETURN/EXHAUST GRILLES/DIFFUSERS.. WITH THE MANUFACTURER'S INSTALLATION SPECIFICATIONS.
ROUND 1.5xCL RADIUS GORED ELBOW
13. ANY CUTTING OR PATCHING OF NEW OR EXISTING SURFACES THAT IS REQUIRED SHALL BE BY THIS CONTRACTOR AND SHALL BE REPLACED WITH
INSIDE BUILDING:
MATERIAL OF THE SAME QUALITY AND THICKNESS AS THE EXISTING SURFACE. ANY DAMAGES TO EXISTING MATERIALS SHALL BE REPAIRED OR 29. PROVIDE DUCT TRANSITIONS AT ALL EQUIPMENT CONNECTIONS. TRANSITION DETAIL SHALL BE DETERMINED IN THE FIELD.
REPLACED TO MATCH EXISTING.
SUPPLY DUCTWORK FROM RTU-17 TO AIR TERMINAL UNITS TO HAVE 2” THICK FIBERGLASS DUCT WRAP WITH FOIL FACING.
30. MECHANICAL CONTRACTOR SHALL PROVIDE MISCELLANEOUS STEEL AS REQUIRED TO INSTALL NEW HVAC EQUIPMENT, DUCTWORK AND PIPING.
14. ALL DUCTWORK SHALL BE IDENTIFIED AFTER INSULATION WITH PLASTIC DUCT MARKERS. THESE MARKERS SHALL BE THE MANUFACTURER'S SUPPLY DUCTWORK DOWNSTREAM OF AIR TERMINAL UNITS TO HAVE 1” FIBERGLASS DUCT LINER.
STANDARD LAMINATED PLASTIC IN THE FOLLOWING COLOR CODES: 31. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING PIPING MODIFICATIONS DUE TO FINAL SELECTION OF EQUIPMENT, INSTRUMENTS AND PIPING
COMPONENTS. RETURN DUCTWORK TO HAVE 1” FIBERGLASS DUCT LINER.
A. BLUE: SUPPLY AIR. ROUND 1.5xCL RADIUS STAMPED ELBOW
32. MAKE WELDS TO EXISTING/NEW STEEL WITH LOW HYDROGEN ELECTRODES. STORE ELECTRODES IN ACCORDANCE WITH AWS SPECIFICATIONS. ALL OTHER CONCEALED SUPPLY AND RETURN AIR DUCTWORK SHALL BE INTERNALLY INSULATED.
B. RED: RETURN AND MIXED AIR. WELDING PROCESSES SHALL BE PRE-QUALIFIED PER AWS D1.1 FOR DUCT SUPPORTS AND MISCELLANEOUS SUPPORT STEEL.
UNLESS OTHERWISE NOTED, EXHAUST DUCTWORK SHALL BE UNINSULATED.
C. YELLOW: OUTSIDE AIR. 33. MECHANICAL CONTRACTOR SHALL PROVIDE ZINC-RICH COATING TO ALL WELDS.
FLEXIBLE DUCTWORK TO BE INSULATED FLEX MASTER TYPE 3 OR APPROVED EQUAL. RECTANGULAR/ROUND INSULATED FLEXIBLE DUCT
D. GREEN: EXHAUST AIR.
NATURAL GAS (2 PSI AND UNDER)
E. TERMINOLOGY: INCLUDE DIRECTION OF AIRFLOW; DUCT PIPING: SUPPLY AIR RISER
SERVICE SUCH AS SUPPLY, RETURN, AND EXHAUST; DUCT 2" & SMALLER:
ORIGIN, DUCT DESTINATION, AND DESIGN FLOW. SCHEDULE 40, CARBON STEEL, T&C ENDS, SEAMLESS OR ERW, ASTM A53 GRADE B.
EXHAUST AIR RISER
15. ENGAGE AN INDEPENDENT TESTING, ADJUSTING AND BALANCING AGENT CERTIFIED BY EITHER AABC OR NEBB FOR ALL TESTING, ADJUSTING AND 2-1/2" AND LARGER:
BALANCING. THE INDEPENDENT AGENT SHALL BE RESPONSIBLE FOR THE FOLLOWING: SCHEDULE 40, CARBON STEEL, PLAIN ENDS, SEAMLESS OR ERW, ASTM A53 GRADE B.
RETURN AIR RISER
A. TESTING, ADJUSTING, AND BALANCING CONFERENCE WITH THE OWNER'S AND FITTINGS:
ARCHITECT'S REPRESENTATIVES SHALL BE SCHEDULED WITH 7 DAYS ADVANCE 2" & SMALLER:
150 LB., MALLEABLE IRON, THREADED, ASTM A197. SUPPLY AIR DIFFUSER
NOTICE SUPPLIED TO ALL INVOLVED.
2-1/2" AND LARGER:
B. SET HVAC SYSTEM AIR FLOW RATES WITHIN THE FOLLOWING TOLERANCES: RETURN AIR GRILLE
STANDARD WEIGHT, CARBON STEEL, BUTTWELD ENDS, SEAMLESS, ASTM A234 GRADE WPB.
i. SUPPLY, RETURN, AND EXHAUST FANS AND EQUIPMENT WITH FANS: +5% TO +10%
UNIONS: EXHAUST AIR GRILLE
2" & SMALLER:
ii. AIR OUTLETS AND INLETS: ±5% 150 LB., MALLEABLE IRON, THREADED, GROUND POINT.
AIRFLOW INDICATOR
C. SUBMIT (6) COPIES OF TESTING, ADJUSTING & BALANCING REPORTS TO ENGINEER. FLANGES:
USE TESTING, ADJUSTING & BALANCING STANDARD FORMS. FORMS TO BE STAMPED & 2-1/2" AND LARGER: CO2 SENSOR
C
CERTIFIED BY THIS TESTING & BALANCING AGENCY. 150 LB., RAISED FACE OR FLAT FACE, WELDNECK OR SLIP-ON, STANDARD WEIGHT BORE, F&D TO ANSI B16.5, ASTM A105.

D. A FINAL REPORT SHALL BE PROVIDED TO OWNER. TYPE WRITTEN OR COMPUTER PRINTOUT BOLTS: S REMOTE SENSOR
IN LETTER-QUALITY FONT ON STANDARD BOND PAPER IN A 3-RING BINDER TABULATED INTO HEAVY HEX HEAD MACHINE BOLTS, WITH HEAVY HEX HEAD NUT CARBON STEEL, ASTM A307.
SECTIONS BY THE TESTING OF CFM SETTINGS, ZONE SETTINGS, O/A SETTINGS AND FAN T THERMOSTAT
SPEEDS SHALL BE INCLUDED IN THIS REPORT. GASKETS:
NON-METALLIC GASKETS FOR PIPE FLANGES (DURABLA, GARLOCK, CRANITE, ETC.), ANSI B16.21.
X-X DIFFUSER TAG
16. ALL THERMOSTATS SHALL BE MOUNTED AT 60" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. IF ELECTRICAL SWITCHES OR OTHER DEVICE IS MOUNTED IN
VALVES: CFM CFM
THE SAME LOCATION, ALL DEVICES SHALL BE ALIGNED VERTICALLY. VERIFY ALL THERMOSTAT LOCATIONS WITH ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
PLUG VALVES:
2" & SMALLER:
17. PROVIDE ONE DAY OF TRAINING FOR START-UP AND OPERATION OF ALL HVAC EQUIPMENT. 200 LB. WOG, THREADED, SHORT PATTERN, SEMI-STEEL LUBRICATED PLUG COCK WITH STANDARD PATTERN CAST IRON HANDLE,
HOMESTEAD FIG. 611 OR APPROVED EQUAL.
18. SEISMIC RESTRAINT HANGERS & SUPPORTS FOR ALL DUCTWORK, PIPING, AND EQUIPMENT:
2-1/2" AND LARGER:
A. ALL MECHANICAL EQUIPMENT, PIPING AND DUCTWORK SHALL BE RESTRAINED TO RESIST SEISMIC FORCES. 200 LB. WOG, ANSI 125 LB. FLANGED, SHORT PATTERN, SEMI-STEEL LUBRICATED PLUG COCK WITH STANDARD PATTERN OPERATING
RESTRAINTS SHALL MAINTAIN EQUIPMENT, PIPING AND DUCTWORK IN A CAPTIVE POSITION. RESTRAINT WRENCH, HOMESTEAD FIG. 612 OR APPROVED EQUAL.
DEVICES SHALL BE DESIGNED AND SELECTED TO MEET THE SEISMIC REQUIREMENTS AS DEFINED IN THE
LATEST ISSUE OF THE STATE BUILDING CODE OR LOCAL JURISDICTION BUILDING CODE. CONTRACTOR TO NATURAL GAS VALVES ON ROOF SHALL BE TWO PIECE, FULL PORT, BRONZE BALL VALVE WITH BRONZE TRIM.
PROVIDE SEISMIC CALCULATIONS TO FM GLOBAL, FOR APPROVAL, FOR ANY EQUIPMENT OR SUPPORTS
REQUIRING SEISMIC CALCULATIONS. REGULATOR:
B. PROVIDE CALCULATIONS TO DETERMINE RESTRAINT LOADS RESULTING FROM SEISMIC FORCES PRESENTED IN SENSUS OR APPROVED EQUAL. CONSULT MANUFACTURER FOR ORIFICE SIZE PER APPLICATION. SEE REGULATOR SCHEDULE
LATEST EDITION OF THE LOCAL BUILDING CODE OR STATE BUILDING CODE. SEISMIC CALCULATIONS SHALL BE SHEET M-601.
CERTIFIED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF INDIANA AND IN THE DIRECT EMPLOY
OF THE SEISMIC EQUIPMENT MANUFACTURER. THESE CALCULATIONS SHALL BE PROVIDED TO THE OWNER FOR
SUBMISSION TO FM GLOBAL FOR REVIEW. PROVIDE CALCULATIONS FOR ALL EQUIPMENT 20 POUNDS OR
GREATER.
C. CALCULATIONS MUST SHOW THE ENTIRE LOAD PATH FROM THE EQUIPMENT TO THE BUILDING STRUCTURE AND
INDICATE THE METHOD OF ATTACHMENT OF THE EQUIPMENT TO THE SEISMIC RESTRAINT AND THE SEISMIC
RESTRAINT TO THE BUILDING STRUCTURE.

D. ALL DUCTWORK, PIPING AND EQUIPMENT NOT REQUIRING CALCULATIONS SHALL BE SEISMICALLY SUPPORTED AND
BRACED PER THE SEISMIC SUPPLIER'S INSTRUCTIONS.

E. INSTALLATION INSTRUCTIONS MUST BE SUBMITTED TO THE ENGINEER PRIOR TO THE INSTALLATION OF THE
EQUIPMENT.

F. THE IMPORTANCE FACTOR Ip = 1.25

G. THE SEISMIC SUPPLIER SHALL BE AMBER / BOOTH COMPANY, MASON INDUSTRIES, THE HILL CO. OR APPROVED EQUAL.

H. THE CONTRACTOR SHALL PROVIDE ANY MISCELLANEOUS STEEL REQUIRED FOR MOUNTING THE EQUIPMENT
AND SEISMIC RESTRAINTS TO THE STRUCTURE. THE CONTRACTOR SHALL SUBMIT DETAIL OF HOW SEISMIC
ROOF CURB WILL BE ATTACHED TO THE BUILDING ROOF STEEL.

I. A REPRESENTATIVE OF THE SEISMIC SUPPLIER SHALL VISIT THE JOB SITE PRIOR TO THE INSTALLATION OF ANY
PIPING, DUCTWORK, EQUIPMENT, ETC. AND SHALL INSTRUCT THE CONTRACTOR ON THE PROPER INSTALLATION
OF THE SEISMIC RESTRAINTS. THE REPRESENTATIVE SHALL CERTIFY IN WRITING AND SUBMIT TO THE
ENGINEER, THAT THE INSTRUCTION HAS OCCURRED.

J. AT THE COMPLETION OF THE PROJECT A REPRESENTATIVE OF THE SEISMIC SUPPLIER SHALL VISIT THE JOB
SITE TO VERIFY THAT ALL SEISMIC RESTRAINTS ARE INSTALLED PER CODE PROVIDE A WRITTEN REPORT TO
THE ENGINEER OF ANY DEFICIENCIES. THE REPRESENTATIVE SHALL THEN REVISIT THE JOB SITE FOR A FINAL
INSPECTION TO VERIFY THAT ALL DEFICIENCIES HAVE BEEN CORRECTED. THE REPRESENTATIVE SHALL
PROVIDE TO THE ENGINEER A WRITTEN CERTIFICATION THAT ALL SEISMIC RESTRAINTS ARE INSTALLED AS D 04/07/16 ISSUED FOR BIDDING PCIS
REQUIRED BY CODE AND SEISMIC SUPPLIER INSTALLATION INSTRUCTIONS.
C 03/18/16 ISSUED FOR OWNER REVIEW PCIS
B 02/29/16 ISSUED FOR 50% BID PCIS
K. SEE EQUIPMENT SCHEDULES ON DWG. M-601 FOR EQUIPMENT REQUIRING SEISMIC CURBS, SPRING ISOLATORS AND A 02/05/16 ISSUED FOR 30% BID PCIS
EQUIPMENT RAILS. APP
ISSUE DATE DESCRIPTION
BY
L. ALL ROOF CURBS SHALL BE 14" ABOVE FINISHED ROOF SURFACE.

401 N.W. First St. 812 425 4264


Evansville, IN 47708

PROPOSED HIGH SCHOOL


EVANSVILLE CHRISTIAN SCH.
WARRICK COUNTY
NEWBURGH, IN
The drawings, specifications and other documents, including those in electronic form prepared by
PCI Skanska Inc. for this project are Instruments of Service, and may be used solely with respect
to this project. The documents may not be reproduced without first obtaining the express written
consent of PCI Skanska Inc. Authorized use of electronic media or file does not guarantee that
these files contain complete and accurate information. In order to insure the accuracy of the
information contained and that no changes or modifications have been made, either intentional or
unintentional, these files must be compared to the project's contract documents with stamped and
sealed certification and applicable approved modifications. There shall be no unauthorized use
or material modification of such drawings, specifications and other documents, including those in
electronic form prepared by PCI Skanska Inc. for this project. By and through any use, including
any unauthorized use, or any material modification, or in connection with, related to, or arising out
of such use or modification, the user agrees that: PCI Skanska Inc. will not be liable or
responsible for such use or modification; the user will not assert a claim or file any suit, including
for contribution or indemnification, against PCI Skanska Inc. for such use or modification; and the
user will indemnify and hold PCI Skanska Inc. harmless from any loss, damage, liability or cost
including reasonable attorney's fees.
CREATED BY: DATE:
TNF II 01/04/16
CHECKED BY: PRINTED DATE: 4/8/2016 7:59:47
SRP
AM
PROJECT NUMBER:
20150351.00.00

HVAC NOTES

ISSUE

M-001 SHEET NUMBER


D
04/07/16

ISSUED FOR BIDDING/NOT FOR CONSTRUCTION


AIR DISTRIBUTION SCHEDULE
HVAC LEGEND & SYMBOLS
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS BEFORE FABRICATION OF H.V.A.C. COMPONENTS OR
SYM. SERVICE DESCRIPTION MATERIAL MFG & MOD
ACCESSORIES & FEATURES
A. RECTANGULAR DUCT:
PURCHASE OF EQUIPMENT.
* MANUAL OPPOSED BLADE DAMPER WITH LOCKING QUADRANT. LEVER
LOUVERED * FOUR-WAY STEEL PRICE * OPPOSED BLADE DAMPER OR
2. CONTRACTOR SHALL COORDINATE ALL OTHER TRADES WITH THE INSTALLATION OF H.V.A.C. SYSTEM.
SUPPLY CONSTRUCTION SCDA OPE RATOR, OF STEEL CONSTRUCTION.
DEFLECTION * NC < 35 * LOUVERS & DAMPERS MODEL CD-400; KRUEGER MODEL 0BD-DM
3. H.V.A.C. LEGEND MAY CONTAIN SYMBOLS AND ABBREVIATIONS NOT USED ON THIS SPECIFIC PROJECT, LEGEND
REGISTER WITH WHITE TYPE 2 OPERATION FOR LESS THAN 10" WIDE.

CD-1 * FACE AIR VOLUME * FACE VELOCITY TO BE SHALL BE USED FOR REFERENCE PURPOSES. Mc C A R T Y
BAKED ENAMEL B. ROUND DUCT:
CONTROL BETWEEN 500-700 FPM 4. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE H.V.A.C. SYSTEM AS IT RELATES TO DRAWINGS AND H O LSAPLE
FINISH * ROUND BLADE CONTROL DAMPER OF STEEL CONSTRUCTION WITH SPECIFICATIONS. Mc C A R T Y
MA NUAL OPERATOR 5. CONTRACTOR IS REQUIRED TO REVIEW ARCHITECTURAL PLANS FOR RATED ASSEMBLIES. CONTRACTOR IS
EGGCRATE * FREE PATTERN ALUMINUM PRICE * LOUVERS AND DAMPERS MODEL CD-600.
RETURN CONSTRUCTION 80 RESPONSIBLE FOR INSTALLATION OF FIRE AND/OR SMOKE DAMPERS IN ACCORDANCE WITH THE SPECIFICATIONS
WITH WHITE * NC < 35
CR-1 GRILLE AND APPLICABLE BUILDING CODES.
BAKED ENAMEL * MAX FACE VELOCITY <500 FPM
FINISH 6. "STANDARD" ACCESSORIES OR CONTROLS ON H.V.A.C. EQUIPMENT SHALL BE THOSE WHICH MANUFACTURER ARCHITECTS
PROVIDES ON THE MAJORITY OF STOCK MERCHANDISE. & INTERIOR
DESIGNERS
OR
7. BRAND NAMES AND MODEL NUMBERS ARE PROVIDED TO ESTABLISH A LEVEL OF QUALITY AND PERFORMANCE.
EGGCRATE * FREE PATTERN ALUMINUM PRICE * RECTANGULAR ELBOW WITH SINGLE THICKNESS TURNING
"EQUAL TO" ITEMS MAY BE SUBMITTED FOR CONSIDERATION BY THE ENGINEER AND OWNER.
EXHAUST CONSTRUCTION 80
* NC < 35
VANE S OF STEEL CONSTRUCTION.
8. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND INDICATE THE APPROXIMATE ROUTING OF PIPING AND 15012
GRILLE WITH WHITE
BAKED ENAMEL * MAX FACE VELOCITY <500 FPM DUCTWORK. CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES. MINOR OFFSETS AND 550 W. MAIN STREET, SUITE 300
FINISH ADJUSTMENTS SHALL BE PROVIDED WHERE REQUIRED AT NO ADDITIONAL COST TO THE OWNER. KNOXVILLE, TENNESSEE 37902

9. COORDINATE CEILING DIFFUSERS AND REGISTER LOCATIONS WITH ARCHITECT'S REFLECTED CEILING PLAN. CONTACT: DOUG McCARTY
EMAIL: DMcCarty@mhminc.com
* SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR MOUNTING TYPE REQUIRED. * CONSTRUCT ALL BRANCH CONNECTIONS WITH 45° FITTING PER
TELEPHONE: (865) 544-2000
* ALTERNATE MANUFACTURERS: METALAIRE AMD TITUS 45°
SMACNA STANDARDS.
HVAC NOTES: FACSIMILE: (865) 544-0402
BINDING EDGE

1. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE SUPPLY, RETURN AND EXHAUST DUCT AS FOLLOWS: INTERNET: mhminc.com
* DIMENSION: L = 1/4W, 4"MINIMUM
L DUCTWORK TO BE DESIGNED, BRACED, AND SUPPORTED IN ACCORDANCE WITH SMACNA FOR LOW PRESSURE PROJECT INFORMATION

* W APPLICATIONS, SEAL CLASS C PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE CONTRACT: SBC - 166/005-02-2013

DUCTWORK (FLEXIBLE DUCT MAX. 10') SMACNA-06). SING LE WIRE HANGERS SHALL NOT BE ALLOWED FOR
* SHEET METAL CONNECTORS, INC. HIGH EFFICIENCY TAKEOFF WITH FLEXIBLE DUCTWORK SUPPORT. FLEXIBLE DUCTWORK SHALL BE SUPPORTED IN A MANNER THAT PREVENTS NEW FOOTBALL STADIUM
DAMPER AND LO CKING QUADRANT FOR ROUND DUCT TAKEOFFS FROM CONSTRICTION OR DIPS. INSULATION SHALL BE AS NOTED BELOW. -EA ST TENNESSEE STATE
RECTANGULAR DUCTWORK. INCREASE MAIN DUCT SIZE AT FITTING TO 2. ALL DUCT ELBOWS SHALL BE 1.5 R/D, UNLESS NOTED OTHERWISE. UNIVERSITY
ACCOMMODATE ITS INSTALLATION IF REQUIRED TO MEET SMACNA AND 3. MANUAL, OPPOSED BLADE DAMPERS SHALL BE PLACED IN EACH BRANCH OF SUPPLY DUCTWORK FOR FINAL 1415 MURFREESBORO ROAD, SUITE 664
MANUFACTU RER'S INSTRUCTIONS. BALANCING PURPOSES. BALANCING DEVICES SHALL BE IN ACCORDANCE WITH IMC (2006) 603.17. NASHVILLE , TENNESSEE 37614

* D 4. CONTRACTOR SHALL FIELD VERIFY ALL DUCT ROUTING DIMENSIONS AND TERMINAL DEVICES TO AVOID
* DIMENSION: D = RUNOUT DIAMETER (6"-14") ACTIVE DESIGN PHASE
INTERFERENCES. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL SUPPORTS FOR PIPING AND DUCTWORK. SCHEMATIC DESIGN

5. CONDENSATE DRAIN PIPING SHALL BE FULL SIZE PER EQUIPMENT CONNECTION ROUTED TO INDIRECT  DESIGN DEVELOPMENT
* SUPPLY DUCT CONNECTION WITHOUT CREATING AN OBSTRUCTION. ALL SUPPORTS FOR THE CONDENSATE DRAIN PIPING  REDI-CHECK
 CONSTRUCTION BIDDING PHASE
IS BY THE MECHANICAL/HVAC CONTRACTOR.

 CONSTRUCTION DOCUMENTS
CONSTRUCTION DOCUMENTS
6 PROVIDE MINIMUM 10 FEET SEPARATION BETWEEN OUTSIDE AIR INTAKES AND EXHAUST VENTS, PLUMBING
* RETURN DUCT  AS-BUILT RECORDS
VENTS, ETC. SEAL:
7. PROVIDE SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR DUCTS OF ALL UNITS 2000 CFM AND OVER.
* EXHAUST DUCT
LOCATE DETECTOR IN THE RETURN AIR DUCT UPSTREAM OF FRESH AIR MIXING, AND UPSTREAM OF EXHAUST
IN ACCORDANCE WITH IMC 606.2.1. LOCATE DETEC TOR IN THE SUPPLY AIR DUCT DOWNSTREAM OF THE
* SUPPLY DUCT RISER FILTERS AND UPSTREAM OF THE FIRST BRANCH CONNECTION IN ACCORDANCE WITH NFPA 90A. DETECTORS
SHALL BE WIRED INTO BUILDING FIRE ALARM SYSTEM AND SHALL BE WIRED TO SHUT UNIT/S DOWN UPON
* SUPPLY DUCT DROP DETECTION OF SMOKE.
8. THERMOSTATS SHALL BE MOUNTED 48" ABOVE FINISHED FLOOR UNLESS INDICATED OTHERWISE.
* ROUND SUPPLY DUCT RISER 9. PROVIDE ACCESS DOOR (12"x12" MIN) AS REQUIRED FOR DAMPER AND CONTROL ACCESS IN WALLS AND
CEILINGS.
* ROUND SUPPLY DUCT DROP 1
10. PROVIDE MANUAL VALVES FOR AIR RELEASE AT ALL HIGH POINTS IN HYDRONIC SYSTEMS.
© McCarty Holsaple McCarty, Inc.

* FLEXIBLE DUCT EQUAL TO FLEXMASTER TYPE 3 INSULATED FLEXIBLE DUCT


11. FIRE DAMPERS ARE NOT REQUIRED IN ONE OR MORE HOUR FIRE WALLS AS LONG AS ALL EXCEPTIONS STATED IN Do NOT scale drawings, use given dimensions only.

WITH ALUMINUM FOIL JACKET AND ALUMINUM FOIL FIBERGLASS POLYESTER


IMC 607.5.3 ARE MET. If not shown, verify correct dimension with ARCHITECT.

Contractor shall check and verify all dimensions and

LAMINATE LINER. INSTALL IN ACCORDANCE WITH SECTION III OF SMACNA'S


conditions at job site.

VAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE".


"H DUCT SEALING: CONSULTANT INFORMATION

SUPPLY DUCT A. PRESSURE SENSITIVE TAPE USED AS THE PRIMARY SEALANT IS CERTIFIED AND SHALL COMPLY WITH
UL-181A OR UL-181B.
BINDING EDGE

RETURN DUCT
B. PROVIDE LONGITUDINAL SEAMS ON RIGID DUCT AND TRANSVERSE SEAMS ON ALL DUCTS.
MAKE-UP AIR SUPPLY DUCT C. PROVIDE MECHANICAL FASTENERS AND SEALANTS SHALL BE USED TO CONNECT DUCTS AND AIR
DISTRIBUTION DEVICES.
EXHAUST DUCT

XX
XX * INDIC ATES NEW HVAC EQUIPMENT PENETRATIONS:
1. SLEEVES SHALL BE INSTALLED WHERE DUCTS, LOUVERS, OR PIPING PENETRATE NON-RATED
EXTERIOR WALLS, PARTITIONS, FLOORS, OR ROOF. PACK AR OUND SLEEVES AND SEAL WEATHER
* DU CT TRANSITION
TIGHT. IN STALL FLASHING AS REQUIRED. SLEEVES SHALL BE MINIMUM 16 GAUGE GALVANIZED
DG * DOOR GRILLE STEEL AND SHALL BE FIRMLY SET IN BUILDING STRUCTURE.
FD
* FIRE DAMPER
SD

SD * SMOKE DAMPER

U/C
* INDI CATES 3/4" UNDERCUT DOOR
CODES OFFICIAL REVIEW

HWS
* HOT WATER SUPPLY PIPING

HWR
* HOT WATER RETURN PIPING

* 3-WAY VALVE

* 2-WAY VALVE

* BALL VALVE

* BUTT ERFLY VALVE

T KEY PLAN:
* WALL MOUNTED THERMOSTAT

S * WALL MOUNTED SENSOR


CO2 * WALL MOUNTED CO2 SENSOR

SP * DUCT MOUNTED STATIC PRESSURE SENSOR


BINDING EDGE

* SUPPLY DIFFUSER W/FLEX DUCT

* RETUR N GRILLE

* EXHAUST G RILLE OR EXHAUST FAN (REFER TO DRAWINGS FOR CLARIFICATION)

REVISION INFORMATION
* S IDEWALL SUPPLY GRILLE
No. Date Description
1 2/12/2016 SFMO Revisions

* SIDE WALL RETURN GRILLE

DRAWING INFORMATION

SCALE: 1/8" = 1'-0"


SCALE GUIDE:
DWG ISSUED: 12.30.15
PRJ MGR: S. WEBB
PA / PC: S. BUTCHER / C. MOELLENDICK
DRAWN BY: SGP
CHECKED BY: JMK/LTH
2/18/2016 1:35:31 PM

DRAWING TITLE:

MECHANICAL NOTES

& LEGENDS

TIME / DATE:

DRAWING NO:

M001

MECHANICAL ABBREVIATIONS:

SINGLE LINE

PIPING CONT'D.
DUCTWORK SYMBOLS
MECHANICAL SYMBOLS:

DOUBLE LINE

CONTROL SYMBOLS
PIPING SYMBOLS
DIFFUSER SYMBOLS

WELDING
GENERAL NOTES:

DELIVERY, STORAGE, AND HANDLING

0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

NOTES &
3062 ROUTE 9W, SUITE 500
SYMBOLS NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

M-001 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
MEASURE 1" THEN DRAWING IS
IF THIS BAR DOES NOT

NOT TO FULL SCALE


1
1/2
0
CIRCULAR BRANCH CONNECTON
TO SINGLE OUTLET

PIPE HANGER DETAIL


DIFFUSER, GRILLE AND REGISTER SCHEDULE (ANEMOSTAT AS STD.)
DESIGNATION CFM SERVICE NECK SIZE (IN.)/ NOMINAL FACE TYP. BRANCH REMARKS

3062 ROUTE 9W, SUITE 500


NO. OF SLOTS SIZE - W x L (IN.) DUCT SIZE

NEW WINDSOR, NY 12553


CD-A 0-175 SUPPLY 6 24X24 12x4 EPL
CD-B 176-350 SUPPLY 8 24X24 14x6 EPL

FAX: 845-562-7007
TEL: 845-562-7005
CD-C 351-450 SUPPLY 10 24X24 16x6 EPL
CD-D 451-650 SUPPLY 12 24X24 16x8 EPL

CG-A 0-1100 RET / EXH - 24X24 - XAC35LD W/ LIGHT SHIELD PAINTED BLACK
CG-B 0-1100 RET / EXH - 24X24 - X3HD-81-L FILTER GRILLE
CG-C 151-270 RET / EXH 10X10 10X10 12x4 X35H-D W/ LIGHT SHIELD PAINTED BLACK
TR - SUPPLY SEE DWGS SEE DWGS SEE DWGS S20V WITH OPPOSED BLADE DAMPERS

NOTES:
1. SEE HVAC FLOOR PLAN FOR CFM'S.
2. COORDINATE BORDER AND FRAME TYPES WITH ARCHITECTUAL CEILING DETAILS.
TOILET EXHAUST ROOF CURB/HOOD DETAIL
3. PROVIDE VOLUME DAMPERS AT ALL BRANCH OUTLETS.
4. PROVIDE ALL DIFFUSERS WITH FLOW EQUALIZING DEFLECTORS.
5. PROVIDE ALL DIFFUSERS AND REQISTERS WITH OPPOSED BLADE DAMPERS.

COUNTY OF ROCKLAND
TOWN OF ORANGETOWN
6. ALL DIFFUSERS, GRILLES AND REGISTERS TO HAVE MANUFACTURERS STANDARD WHITE BAKED-ON FINISH.

HOMES FOR HEROES


ROUND DUCT HANGERS

335 WESTERN HIGHWAY


TAPPAN, NY 10983
FAN COIL UNIT SCHEDULE

Tel 845-708-9200
New City, NY 10956
AIR-COOLED CONDENSING UNIT SCHEDULE

www.shilale.com
140 Park Avenue
SCHEDULES
DETAILS &

M-002
PIPE PENETRATION THROUGH ROOF DETAIL
T
T

T
T

0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

FLOOR PLAN 3062 ROUTE 9W, SUITE 500


NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

M-100 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
ELECTRICAL
SYMBOL
LIST

J
3,1

ELECTRICAL ONE-LINE DIAGRAM


FEEDER SCHEDULE.

0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

NOTES &
3062 ROUTE 9W, SUITE 500
SYMBOLS NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

E-001 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

FLOOR PLAN 3062 ROUTE 9W, SUITE 500


NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

E-100 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

NOTES &
3062 ROUTE 9W, SUITE 500
SYMBOLS NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

P-001 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

DETAILS
3062 ROUTE 9W, SUITE 500
1 OF 2 NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

P-002 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

DETAILS
3062 ROUTE 9W, SUITE 500
2 OF 2 NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

P-003 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
WATER SERVICE MECHANICAL ROOM PART PLAN

PLUMBING FLOOR PLAN

0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

3062 ROUTE 9W, SUITE 500


NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

P-100 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

NOTES &
3062 ROUTE 9W, SUITE 500
SYMBOLS NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

FP-001 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
0 1/2 1

IF THIS BAR DOES NOT


MEASURE 1" THEN DRAWING IS
NOT TO FULL SCALE

FLOOR PLAN 3062 ROUTE 9W, SUITE 500


NEW WINDSOR, NY 12553
TEL: 845-562-7005
FAX: 845-562-7007
HOMES FOR HEROES

FP-100 140 Park Avenue New City, NY 10956 Tel 845-708-9200


www.shilale.com 335 WESTERN HIGHWAY TOWN OF ORANGETOWN
TAPPAN, NY 10983 COUNTY OF ROCKLAND
1 2 *** Safety Pays *** 4 5

HVAC SYMBOLS PIPING SYMBOLS ABBREVIATIONS ABBREVIATIONS ABBREVIATIONS GENERAL NOTES

US Army Corps
1. THE INSTALLATION OF MECHANICAL SYSTEMS SHALL COMPLY WITH: of Engineers
SYMBOL DESCRIPTION SYMBOL DESCRIPTION ABBREV DESCRIPTION ABBREV DESCRIPTION ABBREV DESCRIPTION
A. UNIFIED FACILITIES CRITERIA.
LOUISVILLE DISTRICT
B. 2006 INTERNATIONAL BUILDING CODE
C. 2006 INTERNATIONAL MECHANICAL CODE
S SOIL
EXHAUST AIR DUCT SECTION FLOW CONTROL AC AIR CONDITIONING UNIT, AIR COMPRESSOR G NATURAL GAS D. 2006 INTERNATIONAL PLUMBING CODE
E. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

Appr.
F. CURRENT EDITIONS OF THE FOUR AMERICAN SOCIETY OF HEATING
SA SUPPLY AIR
AD ACCESS DOOR GA GAUGE REFRIGERATION AND AIR CONDITIONING (ASHRAE) HANDBOOKS:
SUPPLY AND OUTSIDE AIR SECTION THERMOMETER WELL
APPLICATIONS, SYSTEMS AND EQUIPMENT, REFRIGERATION AND

Date
FUNDAMENTALS.
SAD SUPPLY AIR DUCT
AFF ABOVE FINISHED FLOOR GD GLYCOL DRAIN G. HVAC DUCT CONSTRUCTION STANDARD (SMACNA)
PRESSURE TAP, PETE’S PLUG H. SEISMIC RESTRAINT MANUAL (SMACNA)
RETURN AIR DUCT SECTION I. LOCAL COUNTY CODES AND REQUIREMENTS.
SD SMOKE DETECTOR
AP ACCESS PANEL GFH GAS FIRED HEATER J. ENERGY POLICY ACT OF 2005.
K. ASHRAE STANDARDS.
UNION
R DUCT RISE SF SUPPLY FAN L. ARMY RESERVE IT MANUAL.
ARCH ARCHITECTURE HC HEATING COIL

D S 2. THE INSTALLATION OF SYSTEMS SHALL BE IN STRICT ACCORDANCE WITH


SLOPE LINE DOWN IN DIRECTION OF ARROW SP STATIC PRESSURE THE LATEST STANDARDS BY THE AMERICAN SOCIETY OF HEATING,
D DUCT DROP AS AIR SEPARATOR HD HEAT DETECTOR REFRIGERATING, AND AIR CONDITIONING ENGINEERS (ASHRAE), SHEET
METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION
CONCENTRIC REDUCER SR SUPPLY REGISTER (SMACNA).
BC BRANCH CONTROL HWR HEATING HOT WATER RETURN
TURNING VANES
3. EQUIPMENT, PIPING, AND DUCTWORK SHALL BE SEISMICALLY SECURED TO
SS STAINLESS STEEL THE STRUCTURE IN COMPLIANCE WITH UNIFIED FACILITIES CRITERIA AND
ECCENTRIC REDUCER BDD BACK DRAFT DAMPER HWS HEATING HOT WATER SUPPLY
MANUFACTURER RECOMMENDATIONS.
AIR EXTRACTOR
TG TRANSFER GRILLE 4. ROOM THERMOSTATS SHALL BE INSTALLED 48" ABOVE THE FINISHED
BLDG BUILDING HS HAND SWITCH
OBD PRESSURE RELIEF VALVE FLOOR, UNLESS OTHERWISE NOTED ON PLANS.
OPPOSED BLADE DAMPER
U/C UNDERCUT (DOOR) 5. DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSION. WHERE

on
BOD BOTTOM OF DUCT HOA HAND OFF AUTO

pti
DUCT LINER IS INSTALLED IN DUCT, INCREASE DUCT SIZE TO PROVIDE
VD GLOBE VALVE

Descri
INSIDE CLEAR DIMENSIONS SHOWN ON DRAWINGS. EXPOSED DUCT LINER IS
VOLUME DAMPER UTR UP THRU ROOF NOT PERMITTED UPSTREAM OF VAV BOXES.
S BODF BOTTOM OF DIFFUSER HP HORSEPOWER, HEAT PUMP
M
SOLENOID VALVE 6. DUCT BRANCHES SHALL HAVE A MANUAL VOLUME DAMPER IN AN
MOTORIZED LOW LEAKAGE DAMPER V VOLT ACCESSIBLE LOCATION. PROVIDE ACCESS PANELS WHERE NOT
BOU BOTTOM OF UNIT HT HEIGHT
ACCESSIBLE. COORDINATE LOCATIONS WITH ARCHITECT.
SD
DIAPHRAGM VALVE VAV VARIABLE AIR VOLUME
HU HUMIDIFIER UNIT 7. MAINTAIN COORDINATION OF EQUIPMENT, DUCTWORK AND PIPING WITH
DUCT SMOKE DETECTOR BOP BOTTOM OF PIPE
OTHER TRADES TO AVOID INTERFERENCES.
VD VOLUME DAMPER
BOT BOTTOM HVU HEATING VENTILATION UNIT 8. PROVIDE SUPPORTS (THRUST RESTRAINTS, ETC.) FOR PIPING AT POINTS
EMERGENCY SHUTOFF VALVE
WHERE EQUIPMENT IS DISCONNECTED FROM THE SYSTEM.
AIRFLOW MEASURING/MONITORING STATION
HWP HOT WATER PUMP VF VENTILATION FAN
BR BASEBOARD RADIATOR 9. CONNECTION, DEMOLITION OR INTERRUPTION TO EXISTING SERVICES
BDD GATE VALVE SHALL BE MINIMIZED AND COORDINATED WITH THE CONTRACTING
BACK DRAFT DAMPER OFFICER REPRESENTATIVE.
IA INSTRUMENT AIR VFD VARIABLE FREQUENCY DRIVE
CA COMPRESSED AIR
10. PREPARE AND SUBMIT PROFESSIONAL SHOP DRAWINGS TO THE
PLUG VALVE CONTRACTING OFFICER FOR REVIEW AND APPROVAL PRIOR TO
20 x 10 DUCT WIDTH x DEPTH(INCHES) C INFOR. INFORMATION VI VIBRATION ISOLATOR
L CENTERLINE COMMENCEMENT OF ANY WORK.

BALL VALVE 11. PROVIDE AND INSTALL VOLUME DAMPERS ON SUPPLY, RETURN AND
IV INTAKE VENTILATOR WB WET BULB

Mark
LINED DUCTWORK CC COOLING COIL EXHAUST AIR BRANCH DUCTS AS REQUIRED FOR PROPER BALANCING OF
THE SYSTEM.
JC JANITOR’S CLOSET WG WATER GAGE

Appr.
GAS COCK CD CEILING DIFFUSER 12. INSTALL PIPING AND DUCTWORK OUT OF NATURAL WALKWAYS.
TRANSITION DUCT
WIH INTAKE GRAVITY LOUVERED PENTHOUSE 13. DUCT CONNECTIONS TO CEILING DIFFUSERS IN EXPOSED LOCATIONS
KW KILOWATT

Date
CHM CHEMICAL POT FEEDER SHALL BE MADE WITH RIGID DUCT. NO FLEX DUCT WILL BE ALLOWED
FLOW CONTROL VALVE (B & G CIRCUIT SETTER) AT THESE CONNECTIONS.
SPLITTER DAMPER
WMS WIRE MESH SCREEN
LAT LEAVING AIR TEMPERATURE
CER CEILING EXHAUST REGISTER 14. FIRE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS SHALL BE PROVIDED
AT FIRE RATED DUCT PENETRATIONS AND SHALL CONFORM TO THE
DUCT FLEXIBLE CONNECTION CHECK VALVE
C REQUIREMENTS OF THE STATE OF NEW MEXICO. PROVIDE DUCT
M MALE
CFM CUBIC FEET PER MINUTE MOUNTED SMOKE DETECTOR FOR COMBINATION FIRE/SMOKE DAMPERS.

FSD BALANCE VALVE MAU MAKE-UP AIR UNIT 15. DUCT AND PIPE PENETRATIONS AT FIRE-RATED WALLS AND AT FLOORS
COND CONDENSER SHALL BE SLEEVED AND SEALED WITH FIRE STOP TO PREVENT THE
FIRE & SMOKE DAMPER
PASSAGE OF SMOKE.
MAX MAXIMUM
FD PRESSURE REDUCING VALVE 16. DUCTWORK AND PIPING SHALL PASS THROUGH WALLS WITHOUT RIGID
CONT CONTINUATION
FIRE DAMPER CONNECTIONS. PENETRATION POINTS SHALL BE SLEEVED TO ALLOW
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR PASSAGE OF PIPING OR DUCTWORK AND TO MAINTAIN 3/4" MIN. &
SD COMPR COMPRESSOR 1-1/4" MAX. CLEARANCE AROUND THE OUTSIDE SURFACE. THIS
STRAINER W/BLOW DOWN CLEARANCE SHALL BE TIGHTLY PACKED WITH ONE POUND DENSITY
SMOKE DAMPER GLASS FIBER AND CAULKED AIRTIGHT WITH NON-HARDENING SEALANT
MFR MANUFACTURER

on
CRG CEILING RETURN GRILLE AFTER INSTALLATION OF PIPING OR DUCTWORK. INTEGRITY OF FIRE

pti
EXPANSION COMPENSATOR RATED WALLS AND FLOORS SHALL BE MAINTAINED WITH SUITABLE FIRE

Descri
RECTANGULAR SMOOTH RADIUS ELBOW MIN MINIMUM STOPPING.
CRR CEILING RETURN REGISTER
17. INDICATE DUCT SIZES ON SHOP DRAWINGS WITH DIMENSIONS FOR
PIPE GUIDE
MVC MANUAL VOLUME CONTROL LOCATION.
RECTANGULAR SMOOTH RADIUS WYE CS CONDENSER WATER SUPPLY
18. THE LOCATION OF ACCESS PANELS FOR CONCEALED VALVES, FUSIBLE
PIPE ANCHOR
MVD MANUAL VOLUME DAMPER LINKS, DAMPER OPERATORS AND EQUIPMENT SHALL BE COORDINATED
CSD CEILING SUPPLY DIFFUSER WITH THE ARCHITECT. ACCESS PANELS SHALL BE PROVIDED FOR
INFRARED RADIANT HEATER CONCEALED EQUIPMENT INCLUDING FAN COILS AND HOT WATER COILS.
AUTOMATIC CONTROL VALVE NAT’L NATIONAL
CU COOLER UNIT 19. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING
AREAS, PIPING, DUCTWORK, ETC., EXISTING OR NEW, DAMAGED AS A
D MANUAL AIR VENT, 3/8" BALL W/DISCHARGE TO DRAIN NC NORMALLY CLOSED
DOOR LOUVER RESULT OF THE WORK. REPAIR TO MATCH EXISTING CONDITIONS.
L CV CONSTANT VOLUME BOX
20. UNIONS SHALL BE PROVIDED AND INSTALLED PRIOR TO EQUIPMENT
UNDER CUT DOOR BUTTERFLY VALVE NIC NOT IN CONTRACT CONNECTIONS. PROVIDE DIELECTRIC UNIONS, GASKETS AND FASTENERS
U
DB DRY BULB AT DISSIMILAR METAL CONNECTIONS OR CONTACT POINTS.

OUTSIDE SCREW & YOKE GATE VALVE NO NUMBER, NORMALLY OPEN


DIRECTION OF AIR FLOW 21. UNIT OR DUCT MOUNTED SMOKE DETECTORS SHALL BE INTERLOCKED
D DRAIN WITH ASSOCIATED MECHANICAL EQUIPMENT TO SHUT DOWN THE UNIT
UPON SMOKE DETECTION. COORDINATE WIRING WITH ELECTRICAL
FM FLOW METER NP NON-POTABLE WATER
ER-# CONTRACTOR.
DIA., DIAMETER
CEILING EXHAUST REGISTER
CFM 22. ACCURATE "AS-BUILT" DRAWINGS SHALL BE MAINTAINED DURING
NTS NOT TO SCALE
FLEX CONNECTION CONSTRUCTION AND SUBMITTED FOR APPROVAL UPON COMPLETION OF
DN O
/ DOWN

Mark
RR-# INSTALLATION.
CEILING RETURN DIFFUSER OA OUTSIDE AIR
CFM 23. MECHANICAL SYSTEMS SHALL BE TESTED, BALANCED AND OPERATED T0
ORIFICE DP DIFFERENTIAL PRESSURE

dgn
DEMONSTRATE TO THE CONTRACTING OFFICER REPRESENTATIVE OR

0010.
R DESIGNATED REPRESENTATIVE THAT THE INSTALLATION AND
OAU OUTSIDE AIR UNIT

Rev.

7/22/2011
SD-# PERFORMANCE OF THE SYSTEMS CONFORM TO THE DESIGN INTENT.

W 912QR-11-R-0071

e nam e:LCARC_M -
CEILING SUPPLY DIFFUSER EA EXHAUST AIR
CFM AIR FILTER REGULATOR TESTING AND BALANCING SHALL BE PERFORMED BY A QUALIFIED

on No.
INDEPENDENT AGENCY CERTIFIED BY THE ASSOCIATION AIR BALANCE

e:NONE
F-171-40-160
Project Code:
OAL OUTSIDE AIR LOUVER
B COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU
EAD EXHAUST AIR DUCT
(NEBB). TEST RESULTS SHALL BE DOCUMENTED AND SUBMITTED FOR

tati

ot date:
SD-#

ot scal
ROUND CEILING SUPPLY DIFFUSER

11
POINT OF CONNECTION OBD OPPOSED BLADE DAMPER APPROVAL.

ci
28-
Date:
CFM

i
Sol
07-
EAT ENTERING AIR TEMPERATURE

Pl

Pl
Fi
24. EXHAUST DUCTWORK SHALL BE RIGID, NO FLEX.
OED OPEN END DUCT W/ INSECT SCREEN

C.KORPASH
24x24
SIDE WALL REGISTER MS MOTOR STARTER EC EVAPORATIVE COOLER 25. HVAC DRAWINGS ARE SCHEMATIC AND DIAGRAMMATIC. THE CONTRACTOR

Ckd by:
200 CFM WILL COORDINATE WITH OTHER TRADES PRIOR TO INSTALLATION TO
ON-1 OVERFLOW NOZZLE (EQUIP. NUMBER) AVOID CONFLICTS. CONFLICTS THAT ARISE DUE TO LACK OF
12x8

tted by:
COORDINATION WILL BE REMEDIED BY THE CONTRACTOR AT NO

ewed by:
EF EXHAUST FAN

gned by:
EXHAUST REGISTER CENTRIFUGAL PUMP ADDITIONAL COST.
300 CFM

.FRANCO
OV OUTLET VELOCITY

Dwn by:

M .BETZ
A.REED

A.REED

Subm i
ER EXHAUST REGISTER 26. CONTRACTOR TO MAINTAIN A SAFE WORKING ENVIRONMENT AT THE

Revi
12x8

Desi
CONSTRUCTION SITE AND SURROUNDING AREAS. REFER TO
RETURN REGISTER

I
PD PRESSURE DROP SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
300 CFM PIPE TURNING UP
ERV ENERGY RECOVERY VENTILATOR

NEERS
27. TO THE EXTENT POSSIBLE, PROVIDE MIN 1" CLEARANCE BETWEEN
18x12 PH PHASE MECHANICAL EQUIPMENT IN CEILING AND OTHER EQUIPMENT, STRUCTURAL,
SCREENED DUCT OPENING PIPE TURNING DOWN
ESP EXTERNAL STATIC PRESSURE BUILDING COMPONENTS, ETC.

CORPS OF ENGI
200 CFM SC.

LLE,KENTUCKY
CT
PRD PRESSURE RELIEF DAMPER

FAX (714) 327-1601


CAPPED PIPE

STRI

TE 800
M
EUH ELECTRIC UNIT HEATER

A 92707
CABINET UNIT HEATER

VE,SUI
LLE DI
2-WAY CONTROL VALVE PVC POLYVINYL CHLORIDE

FORNI
HUTTON CENTRE DRI
EXH EXHAUST

SANTA ANA, CALI


M

SVI
UNIT HEATER 3-WAY CONTROL VALVE RA RETURN AIR

TEL (714) 327-1600


SVI
LOUI
U.S.ARMY

LOUI
F FILTERS, FEMALE

4
RAD RETURN AIR DUCT

POINT OF CONNECTION FC FLEXIBLE CONNECTION


SYMBOL DESCRIPTION
RCP REMOTE CONTROL PANEL

FCO FLOOR CLEANOUT


ng\gbna\m oraja\dm s97636\LCARC_M-0010.dgn

PRESSURE RELIEF VALVE SECTION NO. RG RETURN GRILLE


X
SECTION REFERENCE FD FIRE DAMPER
X
PRESSURE REGULATOR VALVE SHEET NO. RH RELATIVE HUMIDITY
FF FINISHED FLOOR

RESERVE CENTER
DETAIL NO.

CO
X RL REFRIGERANT LIQUID LINE
FLA FULL LOAD AMP

MEXI
X DETAIL REFERENCE
SHEET NO.
RM ROOM
FOB FLAT ON BOTTOM

COVER SHEET
LAS CRUCES,NEW
X RN-1 ROOF NOZZLE (EQUIP. NUMBER)
FOT FLAT ON TOP
A X EQUIPMENT IDENTIFICATION TAG
RLA RELIEF AIR
FPM FEET PER MINUTE

U.S.ARMY
RPM REVOLUTIONS PER MINUTE
FRP FIBERGLASS REINFORCED PLASTIC
X SHEET NOTE REFERENCE TAG
c:\pwworki
7/22/2011

FSD FIRE SMOKE DAMPER RR RETURN REGISTER

FT FOOT/FEET RS REFRIGERANT SUCTION LINE

RV RELIEF VENTILATOR

NOTE: NOT ALL ABBREVIATIONS AND SHEET


REFERENCE
SYMBOLS SHOWN HEREIN ARE UTILIZED.
NUMBER:

M-0010
Sheet 121 of 222
AM
9:59:03
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

1 2 3
16
UH
HVU C4
GENERAL NOTES
5 US Army Corps
1-1 M-5020
of Engineers

SEE SHEET M-112A


1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES LOUISVILLE DISTRICT
AND ABBREVIATIONS.

NE
A

LI
UH 19 2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,

Appr.
4 M-6010 AND 6020.
STAGING ARMORER

MATCH
SUPPLY
16 AREA WORK AREA T
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
OFFICE

Date
A110 A109 AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
A111
CEILING PLAN.

B
23 FC 4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND
4 EXHAUST BRANCH OUTLET.

14
5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND
FC
D HP REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
3 17 20
21 4
6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER
(TYP 3)
23 SPECIFICATIONS.
T HP
20
ARMS 3
7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL
VAULT 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DH DRAWINGS.
A108
1
8x8
8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE
(TYP 3)
FINISHED GRADE PER ATFP REQUIREMENTS.
230 CFM G

on
UH

pti
UH (TYP 3) 9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

Descri
6
3
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL
18 EQUIPMENT.

11. FOR EMERGENCY AIR DISTRIBUTION STOP SWITCH SEE


C
M-112A

EF C2
1-5 M-5020
KEY NOTES
UH UH
1 44x18 SA DUCT THRU WALL WITH FSD ONTO ROOF
7 8
TO EC 1-1.

2 8x8 SS EA DUCT UTR TO EF 1-8 ON ROOF.

3 BLANK OFF UNUSED PORTIONS OF CONTINUOUS 1 1/2"


SLOT DIFFUSER. CUSTOM BEND TO RADIUS OF CEILING
SOFFIT.

Mark
4 14x12 WELDED GREASE DUCT IN 1-HOUR RATED SHAFT

Appr.
UTR SEE DETAIL
A1
M-5020

Date
5 10x8 WELDED GREASE DUCT DN TO HOOD.
F
6 12x8 WELDED GREASE DUCT DN TO HOOD.
C
7 12x10 MAKE-UP AIR DUCT DN TO HOOD.

UH
8 16x16 MAKE-UP AIR DUCT UTR.
2

9 36x24 RA DUCT UTR TO EC 1-1.


UNIT
10 24x14 SA DUCT UTR TO EC 1-6.
STORAGE UH
A107 1
11 24x14 RA DUCT UTR TO EC 1-6.
T
12 26x14 RA DUCT UTR TO EC 1-7.

on
100

pti
EF C2 C2 EF A

Descri
CFM 13 26x14 SA DUCT UTR TO EC 1-7.
1-6 M-5020 M-5020 1-7
15
14 15 14 BELLMOUTH OPENING WITH WMS.
STORAGE
15 18x18 EA DUCT UTR TO RV ON ROOF.
A106
100
C 16 18x18 OSA DUCT UTR TO IV ON ROOF.
CFM
J
275 CFM S 17 ROUTE 3/8" RL AND 5/8" RS TO HP-3.
A TRANSFER
(TYP 8)
DUCT 18 12x12 EA DUCT UTR TO RV-3.
1100 CFM C (TYP)
100
22 C 19 ROUTE 3/8" RL AND 5/8" RS TO HP-4.
CFM

300 D3
J 20 MOUNT HP UNITS ON PLATFORM. FOR DETAIL SEE
CFM M-5020
WEAPONS
20x18
CONTROL 21 8x8 TRANSFER AIR OPENING IN WALL.
SIMULATOR RM.
ROOM
A105A
PROVIDE CO2, RH, AND TEMPERATURE SENSOR
A105B 22
MOUNTED ON WALL.
8 300
C D1
1100 CFM C CFM 23
4 M-5010

Mark
20x18 GOOSENECK, SEE
12"
K
24 ROUTE 3/8" RL AND 5/8" RS TO HP-5
5

dgn
13

111A.
DAC
6 25 6x6 EA DUCT UTR TO EF-14

Rev.

7/22/2011
1 12

W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS NOTED
420 CFM

on No.
A

F-171-40-160
Project Code:
B (TYP 5)
7 TABLE AND
KITCHEN

tati

ot date:

ot scal
11
23 CHAIR STORAGE

ci
A103A

28-
Date:
150

i
Sol
A

07-
A104

Pl

Pl
Fi
CFM A1
75
D

C.KORPASH
M-301A
CFM 9 LOBBY

Ckd by:
25 11
OFFICE A101
S 1

tted by:
10 A103B

ewed by:
gned by:
2 36x24

.FRANCO
Dwn by:
M

M .BETZ
A.REED

A.REED

Subm i
FC 525 CFM

Revi
Desi
24 22 C 150
5 (TYP 4) (TYP 4)
C

I
CFM
26x18
JANITOR

NEERS
1875 CFM
H A103C 44x18
(TYP 4)

CORPS OF ENGI

LLE,KENTUCKY
CT
S

FAX (714) 327-1601


22

STRI

TE 800
400 CFM A

A 92707
VE,SUI
A 400 CFM

LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


640 CFM
E

SVI

TEL (714) 327-1600


SVI
(TYP 5)

LOUI
U.S.ARMY

LOUI

4
26x18

450 CFM A ASSEMBLY


A102
P
26x18
ng\gbna\m oraja\dm s97636\LCARC_M-111A.dgn

700 CFM
A
(TYP 3)
3

RST FLOOR PLAN-SECTOR ONE


RESERVE CENTER

CO
MEXI
A 475 CFM

CAL
LAS CRUCES,NEW

MECHANI
A 475 CFM A

U.S.ARMY
SEE SHEET M-112A

26x18
NE

ARC-FI
B
LI
c:\pwworki
7/22/2011

MATCH

OMS
C1

M-300A

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-111A
ARC-FIRST FLOOR PLAN-SECTOR ONE Sheet 122 of 222
A1 SCALE :1/8"=1’-0" KEY PLAN
AM
8:55:54
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

4 5 6 7 8 9 9.8 10 11

GENERAL NOTES US Army Corps


of Engineers

SEE SHEET M-111A


LOUISVILLE DISTRICT
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES

NE
AND ABBREVIATIONS.

LI
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,

Appr.
MATCH
M-6010 AND 6020.

Date
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLAN.

4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND


EXHAUST BRANCH OUTLET.

5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


D
REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


FINISHED GRADE PER ATFP REQUIREMENTS.

on
11 VESTIBULE VESTIBULE

pti
Descri
9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
A120B A123B
C2 EF
EF C2
M-5020 1-1 10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL
1-2 M-5020
125 125 550 EQUIPMENT.
A A A
CFM CFM CFM
11. FOR ENLARGE MECHANICAL ROOM PLAN SEE A1/M-400B

D
T
UH UH
ELECTRICAL 9 10 12x12
KEY NOTES
A114
MECHANICAL 1 46x18 SA AND RA DUCTS UTR TO EC 1-3 ON ROOF.
A117 23 WOMENS 100 I MENS TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN
B CURB.
CFM
LOCKER 300 LOCKER
SD WOMENS MENS
24 A118 16x16 CFM A125 550
12 M 15 600 SHOWER SHOWER A 2 24x20 SA AND RA DUCTS UTR TO EC 1-4 ON ROOF.
CFM
MECH
TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN
D CFM A119S A124S
450
A CURB.
(TYP2) 14 A122
EF CFM
16 SD 300
14x14 A 3 40x18 SA AND RA DUCTS UTR TO EC 1-2 ON ROOF.

Mark
A113 CFM 10x14
18x18
18x18 SD SD TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN
13 M
14x14 CURB.
20

Appr.
SD
SD
E 4 36x20 TRANSFER GRILLE WITH SMOKE DAMPER
S 12x10
17 A
22

Date
250 14x12 5 12x12 EA DUCT UTR TO EF 1-12 AND DN TO E CFM
900 16x14 I
SIPRNET M WOMENS CFM MENS
18 SD CFM JANITORIAL 19
TER CAFE TOILET SD SD 6 10x10 EA DUCT UTR TO EF 1-10
14x12 TOILET
STORAGE 300
A112 A115 A119T 22x20 I
A124T CFM
C A121 7 12x12 EA DUCT UTR TO EF 1-4
16x16 (TYP 3)
21 T T
8 3/8"RL AND 5/8"RS UP TO HP-1 UNIT ON ROOF
SD
G
9 3/8"RL AND 5/8" RS UP TO HP-2 UNIT ON ROOF
FC FC 20x16
8 B B D 26 I 595 540 595
1-2 21 1-1 FACILITY WOMENS MENS C C C
400 I CFM CFM CFM 10 EMERGENCY AIR DISTRIBUTION STOP SWITCH. KELE
MAINTENANCE CFM 325 VESTIBULE 150 200 250 VESTIBULE (TYP 4) ST120 BREAK GLASS TYPE. REFER TO CONTROL
9 CFM CFM CFM 25
(TYP 3) DIAGRAMS
A116 CFM A120A A123A
(TYP 4)
H 11 48x24 EX LOUVER IN WALL. CONNECT EA PLENUM
TO EF 1-1, 1-2

on
S

pti
Descri
12 16x16 OSA DUCT UTR TO IV-5 WITH MD

13 10x10 OSA DUCT UTR TO IV-3 WITH MD


24x20
(TYP)
14 18x18 OSA DUCT UTR TO IV-4 WITH MD

15 16x16 EA DUCT DN TO D 1300 CFM, 12" AFF


INTERIOR
PHYSICAL
YARD 16 10x10 EA DUCT DN TO D 300 CFM
READINESS
12"
A126 (TYP 8) 17 8x8 EA DUCT DN TO D 200 CFM

24x20 18 8x8 OSA DUCT DN TO B 200 CFM

28x16 SA AND RA DUCTS UTR TO EC 1-5 ON ROOF.


19
TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN
CURB.
INTERIOR

CORRIDOR A
PROVIDE TEMPERATURE AND RH WALL MOUNTED
20
RESTROOM A150 420 SENSOR.
CFM
A146
(TYP 8)
1 21 GOOSENECK, SEE

Mark
D1
K
M-5010

dgn
500 310 100
240 CFM C C C

112A.
J CFM 2 2 35
CFM CFM C

Rev.
8" EA DUCT (TYP 6) 22 DDC CONTROL PANEL WITH 120V POWER, SECURED

7/22/2011
CFM 400

W 912QR-11-R-0071
J

e nam e:LCARC_M -
12" TO WALL

e:AS NOTED
330 130 UTR 10" (TYP) 240 CFM 375 35 CFM
J A EF 3 C C 100 A

on No.
CFM CFM 250 CFM CFM C 46x18

F-171-40-160
CFM

Project Code:
10" 1-11 (TYP 6) J CFM
B (TYP 2) BOILER CONTROL PANEL WITH 120V POWER, SECURED
23
L TO WALL

tati

ot date:

ot scal
18x16 BREAK

11
12" 10"
26x18

ci
12"

28-
26x18

Date:
8"

i
Sol
AREA 350

07-
FSD PUMP CONTROL PANEL WITH VFD’s AND CONTROLS,

l
FSD STOR

Pl

Pl
Fi
FAMILY
J 24
FULL TIME FULL TIME FULL TIME FULL TIME FULL TIME FULL TIME UNIT EXCLUSIVE LIBRARY LIBRARY LEARNING CFM SECURED TO WALL
26x14 A128 A127
14x14 EA

C.KORPASH
SUPPORT OFF. SPACE OFF. SPACE OFF. SPACE OFF. SPACE OFF. SPACE OFF. SPACE SPACE READING STORAGE CENTER FSD
8" 12" DUCT UTR

Ckd by:
A147 ELEC A142 A141 A140 A139 A138 A137 A136 A133 A132 A130 8" 6"
TO EF
25 PROVIDE TEMPERATURE, CO2, AND RH WALL MOUNTED
7 12" 10 14" SENSOR
A145 TRAINING AID A1

tted by:
12" J 375 CFM 8" FSD

ewed by:
$

gned by:
A J 8" M-301A
6 20x18 FSD 10" STORAGE 26 10x10 EA DUCT UTR TO EF-13
12" S S

.FRANCO
Dwn by:
M

M .BETZ
310 CFM

A.REED

A.REED
100 CFM

Subm i
330 SD A129
240

Revi
27 MOTORIZED EMERGENCY SHUTOFF DAMPER (LOW

Desi
C C 5 10" 20 S 24x18 24x18 100
CFM CFM 4 20x18 C J LEAKAGE TYPE)

I
10" 46x20 (TYP) CFM
RETENTION 700
1535 14" D
10" 24x14 FSD FSD FSD CFM

NEERS
A148 CFM 12"
350 25 18x14 (TYP 4)
E
12" CFM

CORPS OF ENGI
J 10" 16" 1500

LLE,KENTUCKY
210 10" C

CT

FAX (714) 327-1601


E 240 GENERAL CFM (TYP 4)

STRI

TE 800
CFM
CFM OFFICE

A 92707
CLASSROOM CLASSROOM

VE,SUI
12"

LLE DI
A144 24x14 46x18

FORNI
(TYP) A134 A131

HUTTON CENTRE DRI


UNIT EXCLUSIVE
300

SANTA ANA, CALI


8" E 400 CFM UNIT 400 CFM SPACE
CFM 27 A A

SVI

TEL (714) 327-1600


300

SVI
3-WAY COMMON SPACE 2-WAY
J A135
12"0 CFM (TYP 6)

LOUI
U.S.ARMY

LOUI
210 $ A143 46x14 10"
J 350

4
CFM 375 18x18 (TYP) 10"
1535 400 CFM J C
A CFM CFM (TYP) 350 CFM
C 3-WAY 24x18 34x18 A
CFM (TYP 8)
N

SORTING 300
ng\gbna\m oraja\dm s97636\LCARC_M-112A.dgn

J 18x12 350
CFM A
ROOM CFM
10"
10 (TYP 8)
A149A

DISTRIBUTION

RST FLOOR PLAN-SECTOR TW O


RESERVE CENTER
ROOM

CO
MEXI
A149B

CAL
LAS CRUCES,NEW

MECHANI
A

U.S.ARMY
SEE SHEET M-111A
NE
LI

ARC-FI
B
c:\pwworki
7/22/2011

MATCH

OMS

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-112A
ARC-FIRST FLOOR PLAN-SECTOR TWO Sheet 123 of 222
A1 SCALE :1/8"=1’-0" KEY PLAN
AM
8:56:37
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

1 2 3

3/4" HWS/R UH A5
TO EA. UH 5 M-5000 GENERAL NOTES US Army Corps
(TYP) of Engineers

SEE SHEET M-114A


LOUISVILLE DISTRICT
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES

NE
A AND ABBREVIATIONS.

LI
1-1/4" HWS/R

Appr.
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,

MATCH
STAGING ARMORER
SUPPLY M-6010 AND 6020.
AREA WORK AREA
OFFICE

Date
A5
UH A110 A109 3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
HVU A111 AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
M-5000 4
1-1 CEILING PLAN.
B
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND
EXHAUST BRANCH OUTLET.

1-1/2" 5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


D
HWS/R
REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


SPECIFICATIONS.
ARMS
VAULT 7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL
A108 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

A5UH 8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


M-5000 3 UH A5 FINISHED GRADE PER ATFP REQUIREMENTS.

on
pti
6 M-5000

Descri
9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL


EQUIPMENT.

3/4"
HWS/R
1-1/2"
KEY NOTES
HWS/R
1 1-1/4" HWS/R PIPING UTR TO EC 1-1. ROUTE
PIPING THRU ROOF CURB.
UH
UH 8
2-1/2" 2 1" HWS/R PIPING UTR TO EC 1-7. ROUTE PIPING
7 4
1" HWS/R HWS/R (TYP) THRU ROOF CURB.
1" HWS/R

1" HWS/R PIPING UTR TO EC 1-6. ROUTE PIPING


3
THRU ROOF CURB.

Mark
1" HWS/R 1-1/4" HWS/R
4 FOR PIPE HANGER DETAILS SEE D3 D5

Appr.
M-5010 M-5010

Date
F
3/4"
C HWS/R

U H A5
2 D5 A5
SEE FOR PIPE UH
M-5000
HANGER DETAIL M-5010 1 M-5000

UNIT
STORAGE
A107

on
pti
Descri
STORAGE
A106

WEAPONS
CONTROL
SIMULATOR RM.
ROOM
A105A
2-1/2" A105B
HWS/R

4 (TYP)

Mark
K

dgn
2

113A.
Rev.
1-1/2" HWS/R

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS NOTED
on No.

F-171-40-160
Project Code:
B
TABLE AND
KITCHEN

tati

ot date:

ot scal
11
CHAIR STORAGE

ci
A103A

28-
Date:

i
Sol
2" HWS/R 4

07-
3 A104

Pl

Pl
Fi
(TYP)

C.KORPASH
LOBBY

Ckd by:
OFFICE A101

tted by:
A103B

ewed by:
gned by:
1

.FRANCO
Dwn by:
M

M .BETZ
A.REED

A.REED

Subm i
Revi
Desi

I
JANITOR

NEERS
A103C

CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


STRI

TE 800

A 92707
VE,SUI
LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


SVI

TEL (714) 327-1600


SVI
LOUI
U.S.ARMY

LOUI

4
ASSEMBLY
A102
P
ng\gbna\m oraja\dm s97636\LCARC_M-113A.dgn

NG PLAN-SECTOR ONE
RESERVE CENTER

CO
MEXI

CAL
LAS CRUCES,NEW

MECHANI
A

PI
RST FLOOR PI
SEE SHEET M-114A

U.S.ARMY
NE

Q
LI

B
c:\pwworki
7/22/2011

ARC-FI
MATCH

OMS

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-113A
ARC-FIRST FLOOR PIPING PLAN-SECTOR ONE Sheet 124 of 222
A1 SCALE :1/8"=1’-0" KEY PLAN
AM
8:57:18
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

4 5 6 7 8 9 9.8 10 11

GENERAL NOTES
US Army Corps
of Engineers

SEE SHEET M-113A


1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES LOUISVILLE DISTRICT

NE
AND ABBREVIATIONS.

LI
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,

Appr.
MATCH
M-6010 AND 6020.

3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN

Date
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLAN.

4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND


EXHAUST BRANCH OUTLET.

5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


D REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


FINISHED GRADE PER ATFP REQUIREMENTS.

on
VESTIBULE VESTIBULE

pti
9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

Descri
UH A5 A120B A123B
UH A5
9 M-5000 10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL
10 M-5000
EQUIPMENT.

ELECTRICAL KEY NOTES


A114
MECHANICAL 1 1 -1/4" HWS/R PIPING UTR TO EC 1-2. ROUTE
3/4" PIPING WITHIN ROOF CURB.
A117 WOMENS MENS
HWS/R
3/4" LOCKER LOCKER
WOMENS MENS 1 -1/4" HWS/R PIPING UTR TO EC 1-3. ROUTE
2 1/2" HWS/R 2
A118 A125 PIPING WITHIN ROOF CURB.
HWS/R SHOWER SHOWER
6 (TYP) A119S MECH A124S 1 " HWS/R PIPING UTR TO EC 1-4. ROUTE PIPING
A122 3
EF WITHIN ROOF CURB.

Mark
A113
1 -1/4" HWS/R PIPING UTR TO EC 1-5. ROUTE
4
PIPING WITHIN ROOF CURB.

Appr.
5
5 3" HWS/R PIPING POC, FOR CONT. SEE ENLARGED
DWG
A1

Date
SIPRNET WOMENS 4 M-400A
MENS
1 1/4" JANITORIAL
TER CAFE 2 1/2" TOILET
HWS/R TOILET D5 D3
STORAGE 6 FOR PIPE HANGING DETAILS SEE
A112 A115 HWS/R A119T A124T
C A121 M-5010 M-5010

FACILITY WOMENS MENS

MAINTENANCE VESTIBULE VESTIBULE

A116 A120A A123A

on
pti
Descri
INTERIOR
PHYSICAL
YARD
READINESS

A126

INTERIOR

CORRIDOR

RESTROOM A150

A146

Mark
dgn
3

114A.
2

Rev.

7/22/2011
W 912QR-11-R-0071
1" HWS/R

e nam e:LCARC_M -

e:AS NOTED
on No.
1 6 (TYP)

F-171-40-160
Project Code:
B

tati

ot date:

ot scal
BREAK

11

ci
28-
Date:
2" HWS/R

i
Sol
AREA

07-

l
STOR

Pl

Pl
Fi
FAMILY FULL TIME FULL TIME FULL TIME FULL TIME FULL TIME FULL TIME UNIT EXCLUSIVE LIBRARY LIBRARY LEARNING
A128 A127

C.KORPASH
SUPPORT OFF. SPACE OFF. SPACE OFF. SPACE OFF. SPACE OFF. SPACE OFF. SPACE SPACE READING STORAGE CENTER

Ckd by:
A147 ELEC A142 A141 A140 A139 A138 A137 A136 A133 A132 A130
A145 TRAINING AID

tted by:
ewed by:
gned by:
1-1/2" STORAGE

.FRANCO
Dwn by:

M .BETZ
A.REED

A.REED

Subm i
HWS/R A129

Revi
Desi

I
RETENTION

NEERS
A148

CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


GENERAL

STRI

TE 800
OFFICE

A 92707
CLASSROOM CLASSROOM

VE,SUI
LLE DI
A144

FORNI
A134 A131

HUTTON CENTRE DRI


UNIT EXCLUSIVE

SANTA ANA, CALI


UNIT SPACE

SVI

TEL (714) 327-1600


SVI
COMMON SPACE A135

LOUI
U.S.ARMY

LOUI
A143

4
SORTING
ng\gbna\m oraja\dm s97636\LCARC_M-114A.dgn

ROOM

A149A

NG PLAN-SECTOR TW O
DISTRIBUTION

RESERVE CENTER
ROOM

CO
MEXI
A149B

CAL
LAS CRUCES,NEW

MECHANI
A

PI
RST FLOOR PI
SEE SHEET M-113A

U.S.ARMY
NE
LI

B
c:\pwworki
7/22/2011

ARC-FI
MATCH

OMS

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-114A
ARC-FIRST FLOOR PIPING PLAN-SECTOR TWO Sheet 125 of 222
A1 SCALE :1/8"=1’-0" KEY PLAN
8:57:56 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

GENERAL NOTES
US Army Corps
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES of Engineers

AND ABBREVIATIONS. LOUISVILLE DISTRICT

2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,


M-6010 AND 6020.

Appr.
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED

Date
CEILING PLAN.

4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND


EXHAUST BRANCH OUTLET.

1 2 3 4 5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
D
6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER
SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


24x24 EA LOUVER, 50% FA,
FINISHED GRADE PER ATFP REQUIREMENTS.
BIRDSCREEEN. SEE ARCH FOR
DETAIL
ELEC MECH

on
9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

pti
Descri
24x24 EA LOUVER, 50% FA, UH A5 EF C2
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL
BIRDSCREEEN. SEE ARCH FOR
DETAIL
B102 12 M-5000 B103
2-4 M-5020 FOR ENLARGED A1 EQUIPMENT.
C2 EF
27 PLAN SEE
M-400B 2-2
M-5020 11. FOR SOLAR HEAT PIPING INSIDE MECHANICAL ROOM SEE
ENLARGED PLAN
24 A1
M-400B
A
T T
KEY NOTES
29 9 C5
2
C2 EF
1 FOR UNDERSLAB RADIANT HEATING DETAIL SEE AND
STAGING M-5020 2-7
A5
UH 3 20x16
M-7000 M-5000

M-5000 11 2 EMERGENCY AIR DISTRIBUTION STOP SWITCH. KELE


7
ST120 BREAK GLASS TYPE. REFER TO CONTROL
AREA C2 EF
26
DRAWINGS.
16 17
23 M-5020 2-3 23 23
B101B 15 18 3
VX VENTILATOR.
8

Mark
T 2-2
14 36x36 MAKE-UP DUCT AIR FOR CAR EXHAUST.
4
20 2800 CFM MAX. COVER WITH 1/2" WELDED WIRE

Appr.
F 645 CFM MESH.
EAD UTR
FOUR BUTTON MOUNTED CONTROL STATION FOR

Date
5
SD CAR EXHAUST SYSTEM.
190 EQUIPMENT ALCOVE 5
CFM
A
6 12x12 OUTSIDE AIR UP TO INTAKE VENTILATOR ON
250
C B105 ROOF.
C CFM
GD
25 CARBON MONOXIDE AND NO2 CONTROLLER 1
SD 7
STOR
16x14 WITH LOCAL ALARM STROBE. REFER TO CONTROL
19 F 640 CFM DRAWINGS
250
WORK
J B104
CFM 20x16
VEHICLE EXHAUST FAN, COORDINATE WITH
C2
8
BAYS OVERHEAD CRANE SYSTEM. FOR DETAIL SEE
M-5000

200
B116 9 20x16 DOWN TO 12" AFF. COVER INLET WITH 1/2"
J CFM SD WELDED WIRE MESH. 1920 CFM.

on
pti
F 640 CFM 24x24 THRU WALL TO HVU 2-1 ON ROOF. SEE

Descri
10
SD 21 C M-130B FOR CONT.

UNHEATED WOMEN’S EF
200 300 11 10x10 TRANSFER GRILLE.
C
2-6
CFM TR CFM
12 20x20 SAD UTR TO EC 2-1 ON ROOF.
STORAGE B108 12
A
B106 13
SD
B101A A1
EF 100 CFM
M-300B
2-5 F 640 CFM 14 12x12 OSA DUCT DOWN TO 6" AFF WITH 1/2"

20x20
WIRE MESH SCREEN.
16" SD
MEN’S
16x16 OSA DUCT DOWN TO 6" AFF WITH 1/2"
15
13 C WIRE MESH SCREEN IN ELECTRICAL ROOM.
B109 TOOLS 24x24 DN
430 16
14x14 OSA 16x16 OSA DUCT UTR TO IV-7 ON ROOF.
CFM 300
DUCT UTR J
CFM B107 10
17 12x12 OSA DUCT UTR TO IV-6 ON ROOF.

18x14
22
B
FSD 18 PUMP CONTROL PANEL WITH VFD’S AND
A
CONTROLS.
100 CFM FLOOR
S RADIANT
19 20x16 RAD UTR TO EC2-1.

Mark
T 4 HEATING
180 ZONE
A 11
CFM 28 20 1-1/2" HWS/R PIPING POC FOR HEATING HOT
VESTIBULE 1 WATER PIPING TO MECHANICAL EQUIPMENT. FOR

dgn
11 120 HVU 2-1
A1
ENLARGED PLAN SEE

110B.
A
CFM

Rev.
110 M-400B

7/22/2011
VESTIBULE

W 912QR-11-R-0071
A
B113

e nam e:LCARC_M -
HALL

e:AS NOTED
CFM F 640 CFM

on No.

F-171-40-160
Project Code:
B
B115 21 3/4" HWS/R PIPING UP THRU ROOF. PIPE ROUTED
B114

tati

ot date:
WITHIN PIPE CHASE OF UNIT.

ot scal
11
2

ci
28-
Date:

i
Sol
07-

Pl

Pl
Fi
$ 22 1-1/2" HWS/R PIPING UP THRU ROOF. PIPE
300 ROUTED WITHIN PIPE CHASE OF UNIT.
C
SHOP

C.KORPASH
CFM 5

Ckd by:
23 FULLSIZE EA DUCT WITH BELLMOUT OPENING AND
WMS.
OFFICE
F 645 CFM

tted by:
ewed by:
gned by:
UTR 24
3/4" HWS/R TO UNIT HEATERS (TYP).

.FRANCO
F

Dwn by:
B110

M .BETZ
A.REED

A.REED

Subm i
Revi
Desi
320 300 VX 25 DDC CONTROL PANEL WITH 120 V POWER
J 8
SHOP CFM 2-1

I
CFM 9 SECURED TO WALL.

NEERS
26 BOILER CONTROL PANEL WITH 120 V POWER
OFFICE 200
SECURED TO WALL.
C CFM 3

CORPS OF ENGI

LLE,KENTUCKY
B112 200

CT
27 WALL MOUNT UNDERSLAB RADIANT HEATING

FAX (714) 327-1601


J J 20x16

STRI

TE 800
CFM VALVE MANIFOLD.

A 92707
VE,SUI
320

LLE DI
28 PROVIDE C02, RH, AND TEMPERATURE SENSOR

FORNI
CFM

HUTTON CENTRE DRI

SANTA ANA, CALI


MOUNTED ON WALL.

SVI

TEL (714) 327-1600


SVI
C 29 ROUTE UNDERSLAB RADIANT HEATING PIPING

LOUI
U.S.ARMY

LOUI
BELOW WALL AND AROUND CONCRETE FOOTINGS.

4
C2 EF
M-5020 2-1
SHOP
ng\gbna\m oraja\dm s97636\LCARC_M-110B.dgn

C1

M-300B OFFICE
B111

RESERVE CENTER

CO
MEXI

OMS-FLOOR PLAN
CAL
LAS CRUCES,NEW

MECHANI
A

U.S.ARMY
B
c:\pwworki
7/22/2011

OMS

A1 SHEET
OMS-FLOOR PLAN REFERENCE
A1 SCALE :1/4"=1’-0"
N
A2 N NUMBER:

ARC M-110B
Sheet 126 of 222
KEY PLAN
8:54:51 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

GENERAL NOTES

SEE SHEET M-121A


1 2 3 4

NE
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES

LI
US Army Corps
IV B2 IV B2 AND ABBREVIATIONS.
of Engineers
2 M-5000 1 M-5000

MATCH
LOUISVILLE DISTRICT
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,
M-6010 AND 6020.

Appr.
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLAN.

Date
18x18 OSA
DUCT DN 4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND
EXHAUST BRANCH OUTLET.

B 5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


D
SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


FINISHED GRADE PER ATFP REQUIREMENTS.

9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

on
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL

pti
Descri
EQUIPMENT.
RV B2
3 M-5000

12x12 EA DUCT DN

C
KEY NOTES
1 14x12 WELDED GREASE EXHAUST DUCT DN THRU ROOF

TERMINATE 14x12 WELDED GREASE EXHAUST DUCT 40"


2

DUCT THRU WALL SEE


A1
M-5020

3 REFRIGERANT PIPING DN THRU ROOF

Mark
4 24x14 SA AND RA DUCTS DN THRU ROOF

Appr.
5 16x16 MAKE-UP AIR DUCT DN THRU ROOF

6 26x14 SA AND RA DUCTS DN THRU ROOF

Date
7 36x24 RA DUCT DN THRU ROOF
D2
8 44x18 SA DUCT DN THRU WALL SEE M-5010
F
C 9 PROVIDE MINIMUM OF 42" CLEARANCE FOR ACCESS TO HIGH
VOLTAGE VFD’S, MOTOR CONTROLS, AND PANELS, ETC ALL
ACCESSED FROM ONE SIDE OF THE UNIT.

10 PROVIDE MINIMUM OF 30" CLEAR ON OPPOSITE SIDE OF


UNIT. NO EQUIPMENT OR COMPONENTS THAT REQUIRE
MAINTENANCE SHALL BE INSTALLED ON THIS SIDE OF THE
UNIT. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.

11 PROVIDE MINIMUM OF 18" CLEAR ON OPPOSITE SIDE OF UNIT.


NO EQUIPMENT OR COMPONENTS THAT REQUIRE

on
MAINTENANCE SHALL BE INSTALLED ON THIS SIDE OF THE

pti
UNIT. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.

Descri
12 6x6 EA DUCT DN
18x18 EA 18x18 EA
DUCT DN DUCT DN

J
RV B2 RV B2
1 M-5000 2 M-5000

EF A1
A1 1-9 M-5020 EC C1
KSF
1-1 M-5020 1-7 M-5020

Mark
5 2 11

dgn
K

120A.
Rev.

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS NOTED
on No.

F-171-40-160
Project Code:
HP
B
5
9

tati

ot date:

ot scal
11
9

ci
Date:
28-
3 7

i
Sol
6

07-

Pl

Pl
Fi
9
12

C.KORPASH
B5 EF

Ckd by:
M-5000 1-14

EC C1

tted by:
B4

ewed by:
EF

gned by:
1-1 M-5020
M-5000 1-8

.FRANCO
Dwn by:
4 10 8

M .BETZ
A.REED

A.REED

Subm i
8x8 EA

Revi
Desi
M DUCT DN

I
NEERS
EC C1
1-6 M-5020

CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


STRI

TE 800

A 92707
VE,SUI
LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


SVI

TEL (714) 327-1600


SVI
LOUI
U.S.ARMY

LOUI

4
ng\gbna\m oraja\dm s97636\LCARC_M-120A.dgn

RESERVE CENTER

CO

LEVEL
MEXI

AND LOW ER ROOF PLAN -


ARC-OVERALL PLENUM

SECTOR ONE
CAL
LAS CRUCES,NEW

MECHANI
A

U.S.ARMY
B
c:\pwworki

SEE SHEET M-121A


7/22/2011

Q
OMS
NE
LI
MATCH

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-120A
ARC-OVERALL PLENUM LEVEL AND LOWER ROOF PLAN - SECTOR ONE Sheet 127 of 222
A1 SCALE :1/8"=1’-0" KEY PLAN
AM
8:58:33
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

GENERAL NOTES
3 4 5 6 7 8 9 9.8 10 11

SEE SHEET M-120A


1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES
US Army Corps
AND ABBREVIATIONS.

NE
of Engineers

LI
LOUISVILLE DISTRICT
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,

MATCH
M-6010 AND 6020.

Appr.
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLAN.

Date
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND
EXHAUST BRANCH OUTLET.

5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

D 6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


FINISHED GRADE PER ATFP REQUIREMENTS.

9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

on
pti
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL

Descri
EQUIPMENT.

KEY NOTES

D 1 18x40 SA AND RA DUCTS DTR

2 18x26 SA AND RA DUCTS DTR

IV B2
3 18x46 SA AND RA DUCTS DTR
5 M-5000

16x16 OSA DUCT HD 4 16x28 SA AND RA DUCTS DTR


DN 1 IV B2 SOLAR HEATING
4 M-5000 COLLECTORS (TYP)

Mark
IV B2
SEE D1
A1 5
3 M-5000 18x18 OSA
M-5010
DUCT DN M-400A

Appr.
10x10 OSA
DUCT DN 6 PROVIDE MINIMUM OF 42" CLEARANCE FOR HIGH VOLTAGE
E

Date
VFD’S, MOTOR CONTROLS, AND PANELS, ETC. ALL ACCESSED
C1 FROM ONE SIDE OF THE UNIT.
10x10 EA 6 EC
HP HP 1-5 M-5020
DUCT DN
2 1 7 PROVIDE MINIMUM OF 30" CLEARANCE ON OPPOSITE SIDE OF
UNIT. NO EQUIPMENT OR COMPONENTS THAT REQUIRE
C
MAINTENANCE SHALL BE INSTALLED ON THIS SIDE OF THE
6 UNIT. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.
B5 EF
M-5000 1-13
7
G
RS/RL 4
PIPES DTR
DUCT DTR DTR SEE
D1 D1 D3

M-5010 M-5010 M-5000

on
H

pti
Descri
Mark
2 3

dgn
K

121A.
Rev.

7/22/2011
W 912QR-11-R-0071
7

e nam e:LCARC_M -

e:AS NOTED
C1

on No.
EC

F-171-40-160
Project Code:
B 5 1-2 M-5020
6

tati

ot date:

ot scal
11

ci
Date:
28-
L

i
Sol
07-

Pl

Pl
Fi
7
B5
EF EF B5 CONDENSING
CU

C.KORPASH
1-10 M-5000 UNIT PART
6 6
M-5000 1-4 1 12x12 EA

Ckd by:
12x12 EA OF EC 1-2 C1 DUCT DN
C1 EC
12x12 EA EC
DUCT DN 1-3 M-5020

tted by:
1-4 M-5020

ewed by:
B5

gned by:
DUCT DN EF
EF B5
1 1-3 M-5000

.FRANCO
Dwn by:
1-12 M-5000 6 6

M .BETZ
A.REED

A.REED

Subm i
Revi
Desi
M

I
10x10 EA
DUCT DN

NEERS
CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


STRI

TE 800

A 92707
VE,SUI
LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


SVI

TEL (714) 327-1600


SVI
LOUI
U.S.ARMY

LOUI

4
N
ng\gbna\m oraja\dm s97636\LCARC_M-121A.dgn

RESERVE CENTER

CO

LEVEL
MEXI

AND LOW ER ROOF PLAN -


ARC-OVERALL PLENUM
CAL

SECTOR TW O
LAS CRUCES,NEW

MECHANI
A

U.S.ARMY
B
c:\pwworki

SEE SHEET M-120A


7/22/2011

OMS
NE
LI
MATCH

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-121A
ARC-OVERALL PLENUM LEVEL AND LOWER ROOF PLAN - SECTOR TWO Sheet 128 of 222
A1 SCALE :1/8"=1’-0" KEY PLAN
AM
8:59:15
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

US Army Corps
GENERAL NOTES of Engineers
LOUISVILLE DISTRICT

1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES


AND ABBREVIATIONS.

Appr.
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,
M-6010 AND 6020.

Date
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLAN.

4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND


1 2 3 4 EXHAUST BRANCH OUTLET.
D
5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND
REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE

on
pti
FINISHED GRADE PER ATFP REQUIREMENTS.

Descri
9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL


EQUIPMENT.

KEY NOTES
B2 IV 1 3/4" HWS/R PIPING FROM BELOW PIPE SHALL
M-5000 7 BE ROUTED INSIDE PIPE CHASE OF UNIT
RV B2

B2 5 M-5000
16x16 DN IV
6 M-5000 B2 2 1-1/2" HWS/R PIPING FROM BELOW. PIPE SHALL
RV
BE ROUTED INSIDE PIPE CHASE OF UNIT.
7 M-5000

Mark
3 PROVIDE MINIMUM OF 42" CLEARANCE FOR
ACCESS TO HIGH VOLTAGE VFD’S, MOTOR

Appr.
12x12 DN CONTROLS, AND PANELS, ETC ALL ACCESSED
FROM ONE SIDE OF THE UNIT.

Date
3
DN 4 PROVIDE MINIMUM OF 12" CLEARANCE ON
OPPOSITE SIDE OF UNIT. NO EQUIPMENT OR
16x20 RA DUCT
COMPONENTS THAT REQUIRE MAINTENANCE SHALL
C DTR
BE INSTALLED ON THIS SIDE OF THE UNITS. ALL
ACCESS SHALL BE FROM INSIDE THE UNIT.

5 EC 2-1 SHALL HAVE ECONOMIZER OUTSIDE AIR


INLET ONLY ON THIS SIDE OF UNIT.

EC C1
2-1 M-5020

on
5

pti
Descri
20x20 SA DUCT
DTR

IV B2
8 M-5000

4
EXHAUST AIR
3
DUCT ROOF D2
24x24 THRU WALL
CAP (TYP)
14x14 DN M-5010
IV B2
9 M-5000

B
2

Mark
HVU C1

dgn
2-1 M-5020

130B.
Rev.

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS NOTED
OUTSIDE AIR HOOD

on No.

F-171-40-160
Project Code:
B

tati

ot date:

ot scal
11

ci
28-
Date:
3

i
Sol
07-

Pl

Pl
Fi
C.KORPASH
Ckd by:
B2 RV
M-5000 6

tted by:
ewed by:
gned by:

FRANCO
Dwn by:

M .BETZ
A.REED

A.REED

Subm i
Revi
Desi

.
I
B2

NEERS
RV
M-5000 4

CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


STRI

TE 800

A 92707
VE,SUI
LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


SVI

TEL (714) 327-1600


SVI
C

LOUI
U.S.ARMY

LOUI

4
ng\gbna\m oraja\dm s97636\LCARC_M-130B.dgn

RESERVE CENTER

CO
MEXI

OMS-ROOF PLAN
CAL
LAS CRUCES,NEW

MECHANI
A

U.S.ARMY
B
c:\pwworki
7/22/2011

OMS

A1 SHEET

OMS-ROOF PLAN N
A2
REFERENCE

A1 SCALE :1/4"=1’-0"
N NUMBER:

ARC M-130B
Sheet 129 of 222
KEY PLAN
8:59:50 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

GENERAL NOTES US Army Corps


of Engineers
LOUISVILLE DISTRICT
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES
AND ABBREVIATIONS.

Appr.
K M P Q 2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,
M-6010 AND 6020.
GREASE
DUCT THRU

Date
A1 3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
WALL SEE
EC C1 AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
M-5020
1-6 M-5020 CEILING PLAN.
DISCHARGE
GREASE 4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND
DUCT 40" EXHAUST BRANCH OUTLET.
ABV ROOF
KSF A1
D 5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND
1-1 M-5020 REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

EF A1 6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


1-9 M-5020 SPECIFICATIONS.

(BEYOND) 7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
16x16 1" HWS/R DRAWINGS.
MAKE-UP TO EC 1-6
AIR DUCT 8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE
DTR 14x24 FINISHED GRADE PER ATFP REQUIREMENTS.

on
pti
SA E 640 CFM E
26x18 SA

Descri
DUCT 26x18 SA DUCT 9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
DUCT
640 CFM
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL
10" LINEAR DIFFUSER A
EQUIPMENT.
SA AROUND ENTIRE
12" 700 CFM
26x14 RA 1875 CFM SOFFIT PERIMETER.
26x14 SA
H
DUCT (TYP 4) BLANK-OFF UNUSED
DUCT PORTIONS
16x16
MAKE-UP AIR
A A 36x24
DUCT
FC RA DUCT
275 CFM 275 CFM A
5
420 CFM
A1
WEAPONS
SIMULATOR M-5000
KITCHEN ASSEMBLY
A105
A103A OFFICE A102
A103B

Mark
Appr.
Date
C

ARC-SECTION
C1 SCALE :1/4"=1’-0"

on
pti
Descri
G E D G E D

Mark
POC TO HEATING
IV B2
C3 SYSTEM. FOR
FLUE THRU 4 M-5000

dgn
CONT SEE
C3 HWP ROOF M-5000 A1 EF C2

300A.
Rev.
M-5000 4 D5 1-2 M-5020

7/22/2011
ET 3/4" HWS/R

W 912QR-11-R-0071
M-400A

e nam e:LCARC_M -

e:AS NOTED
1-1/2" HWR
M-5020 1

on No.
18x18 EA

F-171-40-160
Project Code:
B 18x18
DUCT

tati

ot date:

ot scal
11
SECURE

ci
28-
Date:

i
Sol
DUCT TO

07-

Pl

Pl
Fi
WALL 48x24 EA LOUVER,
50%FA, WITH

C.KORPASH
(TYP)
HWP BIRDSCREEN. SEE

Ckd by:
AS C4 MOTORIZED
3 4" COMBUSTION AIR D ARCH
1 M-5000 INTAKE THRU WALL DAMPER
C3
HWP 600 CFM

tted by:
ewed by:
gned by:
(TYP 2)
M-5000 2B AS 8x8 EA DUCT
(TYP 2)
ET D1 EXHAUST AIR

FRANCO
Dwn by:
2 THRU WALL TO

M .BETZ
A.REED

A.REED

Subm i
2 M-5020 PLENUM CONNECTED

Revi
Desi
C3
HWP RM A116 WITH
TO LOUVER AND EF
B

.
2" VENT FROM HWT-1 SMOKE DAMPER

I
M-5000 2B B A5 UH 1-1, 1-2
2 UTR
MECHANICAL 400 CFM M-5000 10

NEERS
3" HWS 2" SHWS/R GFA
A117 2" VENT FROM HWT-1 (TYP 3)
1-1/2" 3" HWS/R 1
FOR CONT SEE

CORPS OF ENGI
HWS TO MECHANICAL
A1

LLE,KENTUCKY
A117

CT
HX-1

FAX (714) 327-1601


M-400A

STRI

TE 800

A 92707
VE,SUI
LLE DI
HST B D4 8x8 OSA 10x10 EA DUCT THRU 16x16 EA DUCT THRU

FORNI
HUTTON CENTRE DRI
1 1 M-5010 DUCT THRU WALL TO RM A113 WALL TO RM A114 WITH
3" HWS

SANTA ANA, CALI


WALL TO RM WITH SMOKE DAMPER SMOKE DAMPER

SVI

TEL (714) 327-1600


SVI
3" HWR
A116 WITH

LOUI
U.S.ARMY

LOUI
SMOKE

4
DAMPER
ng\gbna\m oraja\dm s97636\LCARC_M-300A.dgn

RESERVE CENTER

CO
MEXI
ARC-MECHANICAL ROOM SECTION ARC-MECHANICAL ROOM SECTION
A1 A3

ONS
CAL
SCALE :1/4"=1’-0" SCALE :1/4"=1’-0"

LAS CRUCES,NEW

ARC-SECTI
MECHANI
A

U.S.ARMY
c:\pwworki
7/22/2011

SHEET
REFERENCE
NUMBER:

M-300A
Sheet 130 of 222
AM
9:00:27
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

NE

SEE BELOW
LI
MATCH
GENERAL NOTES US Army Corps
1 2 3 4 of Engineers
LOUISVILLE DISTRICT
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES
AND ABBREVIATIONS.

Appr.
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,
M-6010 AND 6020.

A1

Date
A1 EF 3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
KSF C1
1-9 M-5020 EC B5 B5 AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
(BEYOND) EF EF EF B5
M-5020 1-1 1-7 M-5020
M-5000 1-4 1-10 M-5000 1-12 M-5000 CEILING PLAN.
C1 EC 1-1/4"
HP 16x16
1-6 HWS/R 12x12 EA 10x10 EA 4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND
5 M-5020 14x12 WELDED
MAKE-UP AIR PIPING TO EXHAUST BRANCH OUTLET.
GREASE DUCT DUCT DTR DUCT DTR
1" HWS/R TO DUCT DTR EC 1-1 12x12 EA
THRU ROOF C1
EC 1-6 EC 2" HWS/R DUCT DTR 5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND
D
1-1 M-5020 PIPING REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


DAC
SPECIFICATIONS.
1

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
DRAWINGS.

8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE


SA 16x16 20x18 RA DUCT TO 20x18 SA FINISHED GRADE PER ATFP REQUIREMENTS.
A

on
MAKE-UP 26x14 RA

pti
WEAPONS DUCT TO

Descri
AIR DUCT DUCT 130 CFM 9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
SIMULATOR ROOM WEAPONS
330 CFM J C
12x8 WELDED SIMULATOR
36x24 RA DUCT 10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL
GREASE DUCT TO ROOM 330
FROM EC 1-1 DTR EQUIPMENT.
TYPE 1 HOOD CFM
KITCHEN 420 KITCHEN A 10x8 WELDED
A 12x10 MAKEUP KITCHEN
A103 CFM A103 GREASE DUCT TO TABLE AND
AIR DUCT TO A103 420 LOBBY FAMILY
(TYP) TYPE 1 HOOD CHAIR
HOOD CFM A101 SUPPORT
12x10 MAKE-UP AIR STORAGE A147
DUCT TO HOOD A104

Mark
NE

SEE BELOW
LI
NE

SEE ABOVE
LI

Appr.
MATCH
5 6 7
MATCH

Date
C

EC C1
1-2 M-5020
DUCT THRU 18x46 RA 1 -1/4"
ROOF SEE D1 HWS/R CU
DUCT DTR
PIPINGTO 1
M-5020 FROM EC 1-2
EC 1-2
1-1/2"
26x18 RA 26x18 RA 20x46 SA HWS/R
1 -1/2" HWS/R 10" RA DUCT PIPING
PIPING
10" RA 10" RA 10" RA 18x16 RA 12" RA 12" SA
12" RA

on
pti
Descri
10" RA
14" RA 12" SA

EF 10" RA
1-11 18x26 RA
26x14 RA

J C J C C J J C J C
C J C C J C
240 240 240 240 240 240 240 240 240 240
240 240 1535 245 245 375
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
RESTROOM CFM CFM CFM CFM CFM CFM
A146 UNIT UNIT
FULLTIME FULLTIME FULLTIME FULLTIME FULLTIME FULLTIME COMMON EXCLUSIVE
LIBRARY READING
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE SPACE SPACE
A142 A141 A140 A139 A138 A137 A133
A136 A136

Mark
dgn
301A.
Rev.

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS NOTED
on No.

F-171-40-160
Project Code:
B

tati

ot date:

ot scal
11

ci
28-
Date:

i
Sol
07-

Pl

Pl
Fi
C.KORPASH
Ckd by:
NE

SEE ABOVE

tted by:
LI

ewed by:
gned by:

FRANCO
Dwn by:
MATCH

M .BETZ
A.REED

A.REED

Subm i
Revi
Desi
7 8 9 9.8 10 11

.
I
NEERS
CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


STRI

TE 800

A 92707
VE,SUI
LLE DI
EC C1 EC C1

FORNI
HUTTON CENTRE DRI
1-4 M-5020 1-3 M-5020

SANTA ANA, CALI


SVI

TEL (714) 327-1600


SVI
18x48 RA EF B5

LOUI
U.S.ARMY

LOUI
DUCT DTR 1-3 M-5000

4
1-1/4" 1" HWS/R
24x20 SA HWS/R 24x20 SA UTR TO 46x18 SA
DUCT DTR UTR TO DUCT DTR DUCT OVER EC 1-3 DUCT DTR
1 -1/2"
EC 1-4
HWS/R
ng\gbna\m oraja\dm s97636\LCARC_M-301A.dgn

12" 14x14 EA
FSD FSD DUCT UTR
FSD 12"
12" RA DUCT
8" 10"

RESERVE CENTER

CO
MEXI
8" 8" 12" RA 12" SA 8"
FSD FSD 6"
6"
DUCT

ONS
46x18

CAL
LAS CRUCES,NEW
C C A

ARC-SECTI
MECHANI
A C J C A J C 46x18 RA 100 35 35 J D
DUCT CFM CFM CFM
375 375 100 100 310 310 350 700

U.S.ARMY
CFM CFM CFM CFM CFM CFM CFM CFM

LIBRARY LIBRARY LEARNING TRAINING STORAGE BREAK B


c:\pwworki

READING STORAGE CENTER STORAGE AREA


7/22/2011

A133 A A130 A129 A128 A127


OMS

A1 SHEET
REFERENCE
A2 N NUMBER:
ARC-SECTION M-301A
A1 SCALE :1/4"=1’-0" ARC
Sheet 131 of 222
KEY PLAN
AM
9:01:54
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

GENERAL NOTES US Army Corps


of Engineers
LOUISVILLE DISTRICT
1. REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES
AND ABBREVIATIONS.

Appr.
2. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000,
M-6010 AND 6020.

Date
3. MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLAN.

4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND


A C EXHAUST BRANCH OUTLET.

D 5. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND


REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.

6. INSULATE SUPPLY AND RETURN AIR DUCTWORK PER


SPECIFICATIONS.

7. MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL


4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL
3/4" 1-1/2" DRAWINGS.
C1 EC HVU C1
HWS/R TO HWS/R TO 2-1 M-5020
M-5020 2-1 8. INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE
EC 2-1 HVU 2-1
FINISHED GRADE PER ATFP REQUIREMENTS.

on
pti
Descri
9. INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.

10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL


B2 IV
BOILER FLUES THRU EQUIPMENT.
M-5000 7 1-1/2"
ROOF SEE
HWS/R
D5 16x16 OSA
POC TO
DUCT DTR
M-5000 HEATING
3/4" SYSTEM,
HWS/R SEE
A1

24x24 EA LOUVER, M-400B 20x16 RA 20x20 SA


12" RA
50% FREE AREA, WITH ET UTR UTR
BIRDSCREEN. SEE ARCH 4 12" RA 12" SA
FOR DETAIL
8" SA

18x14
C2 DUCT
EF
M-5020 2-4
ET 26x10 RA 10" SA

Mark
5 8" RA
HWP DUCT 8" SA
A5 UH 6A
D1

Appr.
M-5000 11 190
AS A 200 200 300 110 200
M-5020 CFM J C J A C C J
B 3 CFM CFM CFM CFM CFM
3,4 HWP 300 200
EXTERIOR

Date
GFA 7B 10x10 CFM CFM
ALCOVE
2 HST TRANSFER
MECH B105 HALL
2 GRILLE
B103 TR B114
FOR PIPING IN THE B106
C MECHANICAL ROOM SEE
SHEET M-400B AND
DIAGRAM M-7020

SECURE DUCT TO
16x16 OSA DUCT WALL (TYP)
TO ELEC ROOM
B102 WITH 1/2"
WMS

on
pti
Descri
OMS-SECTION
C1 SCALE :1/4"=1’-0"

4 3 2 1

Mark
B2 RV B2 IV RV B2
M-5000 7 4 M-5000
M-5000 9

dgn
300B.
C2

Rev.
VX

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -
2-1 M-5000

e:AS NOTED
on No.

F-171-40-160
Project Code:
B

tati

ot date:

ot scal
11
HVU C1

ci
28-
Date:

i
Sol
2-1 M-5020

07-

Pl

Pl
Fi
C.KORPASH
Ckd by:
16x20 24x24 SA
DUCT THRU

tted by:
ewed by:
WALL

gned by:

FRANCO
Dwn by:
C2 EF D2

M .BETZ
A.REED

A.REED

Subm i
IV B2

Revi
Desi
M-5020 2-1 M-5010
8 M-5000

.
I
ROOF TO ROOF CAP
WITH BIRDSCREEN 14x14 OSA

NEERS
16x14 RA
DUCT DTR

CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


STRI

TE 800

A 92707
VE,SUI
LLE DI
640
F

FORNI
8" EA DUCT

HUTTON CENTRE DRI


WORK BAYS CFM

SANTA ANA, CALI


B116

SVI

TEL (714) 327-1600


SVI
20x20

LOUI
U.S.ARMY

LOUI
SA DUCT

4
EF
2-5

A 100
300 C UNHEATED
J CFM
ng\gbna\m oraja\dm s97636\LCARC_M-300B.dgn

CFM STORAGE
430
B101A
TOOLS CFM MENS
FOR B107 B109
B3 HALL
DETAIL
M-5000 B114
SEE

RESERVE CENTER

CO
MEXI

ONS
CAL
LAS CRUCES,NEW

OMS-SECTI
MECHANI
A

U.S.ARMY
B
c:\pwworki
7/22/2011

OMS

OMS-SECTION
A1 SCALE :1/4"=1’-0"

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-300B
Sheet 132 of 222
KEY PLAN
AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


9:01:12

1 2 *** Support Value Engineering - It Pays *** 4 5


1 2 *** Safety Pays *** 4 5

US Army Corps
4 5 6 7 8
of Engineers
LOUISVILLE DISTRICT

Appr.
Date
D

SC SC SC SC SC SC SC SC SC SC SC SC SC SC SC SC SC SC
30 29 28 27 26 25 SC SC SC SC SC SC 18 17 16 15 14 13 SC SC SC SC SC SC 6 5 4 3 2 1
D
24 23 22 21 20 19 12 11 10 9 8 7 18 TYP

1" SHWR 1" SHWR


1" SHWR

1" SHWR 1" SHWR


1" SHWS
1" SHWS 2"
1-1/4" SHWR 1-1/2" SHWR 1-1/4" SHWR
1" SHWS 1" SHWS 1" SHWS
1-1/2" SHWS 1-1/2" SHWS 1-1/4" SHWS

2"

on
pti
16

Descri
HD
17
1
20

ARC-PARTIAL ROOF PLAN

Mark
C1 SCALE :1/4"=1’-0" KEYED NOTES:

Appr.
1 MOUNT VERTICAL INLINE PUMP OVERHEAD. PROVIDE SPRING VIBRATION
ISOLATORS. SEE C3/M-5000

Date
5 2 3" HWS&R PIPING FOR CONTINUATION SEE SHEET M-114A

3 INSTALL EXPANSION TANK ON 6" CONCRETE HOUSE KEEPING PAD.


PIPE DRAIN TO NEAREST FLOOR SINK. CHARGE TANK TO SYSTEM
C DESIGN PRESSURE.

4 2" SHWS&R PIPES UP THROUGH ROOF TO SOLAR COLLECTORS.

5 3" HWS CONNECTION TO HST-1. PROVIDE PRESSURE RELIEF VALVE


AT TANK AND PIPE DISCHARGE TO NEAREST FLOOR SINK.

13
HWT 6 CONNECT 2" SOLAR HOT WATER SUPPLY AND RETURN PIPING TO
1 HST-1 INTERNAL HEAT EXCHANGER CONNECTIONS. PROVIDE 3/4" DRAIN
VALVE AT LOWEST POINTS IN SYTEM. CONNECT 3" HWS&R/ SUPPLY
FROM BOILER CONNECTION SHALL BE HIGH AND THE RETURN
CONNECTION TO THE BOILER SHALL BE LOW. PROVIDE ISOLATION

on
BALL VALVES IN PIPE RISERS DOWN TO TANK.

pti
1-1/2" DHWR

Descri
7 INSTALL EXPANSION TANK ABOVE. SUSPEND FROM DECK ABOVE WITH
THREADED ROD. SEE DETAIL D1/M-5020.
2" DHWS
2" DHWR 1-1/2" DHWS 8 INSTALL B-1 AND B-2 IN STACKED CONFIGURATION ON 6" CONCRETE
HOUSEKEEPING PAD. PROVIDE PRESSURE RELIEF VALVES ON
CONDENSATE P-TRAP. PIPE PSV AND CONDENSATE DRAIN DISCHARGE
2" VENT TO NEAREST FLOOR SINK. SEE PLUMBING DRAWINGS FOR NATURAL
GAS PIPING.

9 2" DHWS TERMINATE WITH ISOLATION VALVE AT 9’-6" AFF SEE


PLUMBING DRAWINGS FOR CONTINUATION.

10 2" DHWR TERMINATE AT 9’-6" AFF FOR CONTINUATION BY PLUMBING


CONTRACTOR AND CONNECTION TO DOMESTIC WATER SUPPLY AND
HOT WATER RETURN FROM THE DOMESTIC WATER RECIRCULATING
PUMP.
12
11 TERMINATE HWFI VENT AT 9’6" AFF WITH THERMOSTATIC PRESSURE
RELIEF VALVE. PIPE DISCHARGE TO NEAREST FLOOR SINK.

10
15-
11-
12 1-1/2" DOMESTIC HOT WATER SUPPLY AND RETURN TO HX-1 AND 2"
DOMESTIC HOT WATER SUPPLY AND RETURN TO DISTRIBUTION

Mark
POINTS. PIPES SHALL BE LOCATED A MINIMUM OF 36" BELOW GRADE
OF BELOWFROST LINE. PROVIDE ISOLATION VALVES IN RISERS WITHIN
MECHANICAL ROOM.

dgn
22

400A.
Rev.
13
UNDERGROUND POTABLE WATER STORAGE TANK. SEE DETAIL

7/22/2011
W 912QR-11-R-0071
19

e nam e:LCARC_M -
A4/M-5020. PROVIDE MANHOLE AND EXTENSION TO GRADE . TOP OF

e:AS NOTED
TANK SHALL BE A MINIMUM OF 48" BELOW GRADE. PROVIDE ANCHOR

on No.

F-171-40-160
Project Code:
B SLAB AND TIE DOWN STRAPS PER DETAIL. BACKFILL WITH PEA
GRAVEL.

tati

ot date:

ot scal
D

11

ci
EPO

28-
Date:
10

i
Sol
14 1" MAKE-UP WATER SUPPLY, PROVIDE CHECK VALVE AND PRESSURE

07-

Pl

Pl
Fi
11 REDUCING VALVE SET AT 15 PSIG. TERMINATE AT 10’-0" AFF WITH
9 HWP

C.KORPASH
21 1 BALL VALVE FOR MAKE-UP WATER POC, SEE PLUMBING DRAWING
5 C1/P-411A FOR CONTINUATION.

Ckd by:
2"
B AS
15 CONNECT CHEMICAL POT FEEDER TO SUCTION AND DISCHARGE

R.SALLW ASSER

tted by:
ewed by:
1

CALLAHAN
1

gned by:
8 PIPING OF HWP-1A AND HWP-1B WITH 3/4" PIPE. PROVIDE ISOLATION
GFA B HX BALL VALVES AND PIPE 1/2" DRAIN TO NEAREST FLOOR SINK.

Dwn by:
1

M .BETZ
2

A.REED
1

Subm i
1-1/2" HW R

D.O’

Revi
Desi
ET 16 2" SHWS&R PIPES DOWN THROUGH ROOF. SEE DETAIL D3/M5000 FOR
7 ROOF PIPE PENETRATION.
2 1"
ET
3

NEERS
3 17 INSTALL HEAT-DUMP DRYCOOLER ON ROOF. CONNECT TO SHWS WITH
1-1/2" HW S

3" 2" PIPE. PROVIDE AUTOMATIC AIRVENT, FLEXIBLE CONNECTIONS,

CORPS OF ENGI
3-WAY MOTORIZED CONTROL VALVE AND BALANCING VALVE.

LLE,KENTUCKY
1"
14 4

CT

FAX (714) 327-1601


ET

STRI

TE 800
3 HWP 18
INSTALL FLAT PLATE SOLAR COLLECTORS ON STRUCTURAL
1 1

A 92707
1A

VE,SUI
SUPPORTS PROVIDED BY MANUFACTURER. GROUP COLLECTORS IN

LLE DI

FORNI
ARRAYS OF SIX COLLECTORS EACH. PROVIDE AIR VENT AND

HUTTON CENTRE DRI


HWP

SANTA ANA, CALI


1 PRESSURE RELIEF VALVE AT AHWR CONNECTIO. COLLECTORS SHALL
1B

SVI
BE INSTALLED AT 0^ AZIMUTH AND 47^ SLOPE. OFFSET EACH

TEL (714) 327-1600


20 3"

SVI
3" ARRAY OF COLLECTORS TO ALLOW CLEARANCE FOR PIPING OF

LOUI
U.S.ARMY

LOUI
HST
2" SHWS&R ADJACENT ARRAYS.

4
1
6
19 4" COMBUSTION AIR INTAKE ROUTE FROM BOILER TO EXTERIOR
HWP WALL AND TERMINATE WITH WALL CAP WITH BACKDRAFT DAMPER.
5 1
3/4" 3
20 ROUTE VENT EXHAUST UP THROUGH ROOF. TERMINATE AT LEAST
ng\gbna\m oraja\dm s97636\LCARC_M-400A.dgn

AS
15 3’-0" ABOVE NEARBY EQUIPMENT AND ROOF SEE DETAIL D5/M-5000.
2
HORIZONTAL OFFSETS SHALL BE SLOPED 1/4" PER FOOT TOWARD
BOILER.
HWP
1
4
HWP E 21
PROVIDE MANUAL EMERGENCY BOILER SHUTDOWN SWITCH. INTERLOCK

ARC-SOLAR HEAT ENLARGED PLANS


RESERVE CENTER
1 SWITCH WITH MAIN GAS SOLENOID SHUTOFF VALVE SHOWN ON

CO
2A
P-411A. SWITCH SHALL CLOSE GAS SUPPLY AND TURN OFF 120V

MEXI
HWP 3" POWER TO BOILERS. MOUNT SWITCH 48" ABOVE FLOOR. FOR
1 CONTROL DIAGRAM SEE M-8050.
2B
2

CAL
LAS CRUCES,NEW
22
PROVIDE EMERGENCY SHUTOFF ALARM/STROBE IN WEATHER PROOF

MECHANI
SURFACE MOUNTED BOX. KELE #868STR. MOUNT STROBE/HORN 8’-0"
A ABOVE FLOOR.

U.S.ARMY
B
c:\pwworki
7/22/2011

OMS

A1 SHEET
N REFERENCE
22 A2 N NUMBER:

ARC M-400A
ARC-ENLARGED MECHANICAL ROOM PLAN Sheet 133 of 222
A1 SCALE :1/4"=1’-0" KEY PLAN
AM
9:02:37
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

US Army Corps
of Engineers
LOUISVILLE DISTRICT

Appr.
1 2 3

Date
D

on
pti
A

Descri
13

1"

10
SC SC
31 32

11

Mark
Appr.
Date
1"

KEYED NOTES:
1 MOUNT VERTICAL INLINE PUMP OVERHEAD. PROVIDE SPRING VIBRATION
SC SC
ISOLATORS. SEE C3/M-5000
33 34

on
2" HWS&R PIPING FOR CONTINUATION SEE SHEET M-110B

pti
Descri
3 1" SHWS&R PIPES UP THROUGH ROOF TO SOLAR COLLECTORS.

4 PROVIDE PRESSURE RELIEF VALVE AT HST-2 AND PIPE DISCHARGE


TO NEAREST FLOOR SINK.

5 CONNECT 1" HOT WATER SUPPLY AND RETURN PIPING TO HST-2


CONNECTIONS. PROVIDE 3/4" DRAIN VALVE AT LOWEST POINTS IN
SYTEM. CONNECT 2" HWS&R. SUPPLY CONNECTIONS FROM BOILERS
AND HPAK-1 SHALL BE HIGH AND THE RETURN CONNECTIONS TO THE
BOILERS AND HPAK-1 SHALL BE LOW. PROVIDE ISOLATION VALVES IN
B PIPE RISERS DOWN TO TANK.

6 INSTALL EXPANSION TANK ABOVE. SUSPEND FROM DECK ABOVE WITH


THREADED ROD. SEE DETAIL D1/M-5020

7 INSTALL B-3 AND B-4 IN STACKED CONFIGURATION ON 6" CONCRETE


HOUSEKEEPING PAD. PROVIDE PRESSURE RELIEF VALVES ON
CONDENSATE P-TRAP. PIPE PSV AND CONDENSATE DRAIN DISCHARGE
TO NEAREST FLOOR SINK. SEE PLUMBING DRAWINGS FOR NATURAL
GAS PIPING.

8 1" MAKE-UP WATER SUPPLY. PROVIDE CHECK-VALVE AND REDUCING


OMS-PARTIAL ROOF PLAN

Mark
VALVE SET AT 15 PSIG. TERMINATE AT 10’-0" AFF WITH BALL VALVE
B1 SCALE :1/4"=1’-0" FOR MAKE-UP WATER POC, SEE PLUMBING DRAWING C1/P-411B FOR
CONTINUATION

dgn
400B.
9 CONNECT CHEMICAL POT FEEDER TO SUCTION AND DISCHARGE

Rev.

7/22/2011
W 912QR-11-R-0071
PIPING OF HWP-6A AND HWP-6B WITH 3/4" PIPE. PROVIDE ISOLATION

e nam e:LCARC_M -

e:AS NOTED
BALL VALVES AND PIPE 1/2" DRAIN TO NEAREST FLOOR SINK.

on No.

F-171-40-160
Project Code:
10
B

15-
10 1" SHWS&R PIPES DOWN THROUGH ROOF. SEE DETAIL D3/M-5000

tati

ot date:
11-

ot scal
FOR ROOF PIPE PENETRATION.

ci
Date:

i
Sol

Pl

Pl
Fi
11 INSTALL FLAT PLATE SOLAR COLLECTORS ON STRUCTURAL
SUPPORTS PROVIDED BY MANUFACTURER. PROVIDE AIR VENT AND

C.KORPASH
PRESSURE RELIEF VALVE AT HWR CONNECTION. COLLECTORS SHALL

Ckd by:
BE INSTALLED AT 0^ AZIMUTH AND 47^ SLOPE. MINIMUM DISTANCE
BETWEEN SOLAR COLLECTOR ROWS IS 14’-0".

R.SALLW ASSER

tted by:
ewed by:
CALLAHAN
gned by:
15
12 4" COMBUSTION AIR INTAKE ROUTE FROM BOILER TO EXTERIOR

Dwn by:
RADIANT HEATING 12

M .BETZ
A.REED
WALL AND TERMINATE WITH WALL CAP WITH BACKDRAFT DAMPER.

Subm i
VALVE MANIFOLD 13

D.O’

Revi
Desi
A 13 ROUTE VENT EXHAUST UP THROUGH ROOF. TERMINATE AT LEAST
3’-0" ABOVE NEARBY EQUIPMENT AND ROOF SEE DETAIL D5/M-5000.

NEERS
EPO
14 PROVIDE MANUAL EMERGENCY BOILER SHUTDOWN SWITCH. INTERLOCK

CORPS OF ENGI
SWITCH WITH MAIN GAS SOLENOID SHUTOFF VALVE SHOWN ON
9

LLE,KENTUCKY
14 P-411B. SWITCH SHALL CLOSE GAS SUPPLY AND TURN OFF 120V

CT

FAX (714) 327-1601


STRI

TE 800
GFA POWER TO BOILERS. MOUNT SWITCH 48" ABOVE FLOOR. FOR
3/4" AS

A 92707
2 CONTROL DIAGRAM SEE M-8050.

VE,SUI
LLE DI
3

FORNI
HUTTON CENTRE DRI
8 B
7 15 PROVIDE EMERGENCY SHUTOFF ALARM/STROBE IN WEATHER PROOF

SANTA ANA, CALI


3
SURFACE MOUNTED BOX. KELE #868STR. MOUNT STROBE/HORN 8’-0"

SVI

TEL (714) 327-1600


SVI
B
7 ABOVE FLOOR.

LOUI
U.S.ARMY
2" 4

LOUI
1"

4
1" 1-1/2" HWS/ R DOWN TO RADIANT HEATING VALVE MANIFOLD AND
HWP 16
1
6B ET UNIT HEATER UH-11
6
4
17 3/4" HWS/ R TO UNIT HEATER UH-12
HWP
1
ng\gbna\m oraja\dm s97636\LCARC_M-400B.dgn

6A
1"
2"

AS
3

OMS - SOLAR HEAT ENLARGED PLANS


4

RESERVE CENTER

CO
MEXI
HPAK
1

CAL
LAS CRUCES,NEW

MECHANI
A 2" HST
4 5
HWP HWP 2
7B 7A

U.S.ARMY
1 1
2"
B
c:\pwworki
7/22/2011

2 ET
6 OMS
5

A1 SHEET
N REFERENCE
A2 N NUMBER:

ARC M-400B
OMS-ENLARGED MECHANICAL ROOM PLAN Sheet 134 of 222
A1 SCALE :1/2"=1’-0" KEY PLAN
9:03:19 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

DRAW BAND US Army Corps


of Engineers
PIPING THROUGH ROOF
WITH INSULATION AND ROUND COPPER WEATHER CAP, LOUISVILLE DISTRICT
CAULK THE SEAM BETWEEN THE WEATHERPROOF
ALUMINUM JACKET
CAP AND THE ALUMINUM JACKET CAP

SQUARE SHAPED COPPER FLASHING

Appr.
WITH FLANGE BASE, SET IN
METAL FLUE

NFPA
BED OF PLASTIC CEMENT

Date
SECURE FLASHING IN PLACE

TH
WITH 8 EVENLY SPACED GUY WIRES

ED
ACCORDANCE W I
SEAL ENDS OF INSULATION ROOFING NAILS IF REQUIRED

FI
WITH PLASTIC CEMENT BY HEIGHT

AS SPECI
TWO LAYERS 15 LB. FELT, SET (3 TYPICAL)
IN BEDS OF PLASTIC CEMENT
FINISH ROOF AS DETAILED
8" MIN. AND EXTENDED MIN. 3" AND 6"
D ON ARCHITECTURAL DRAWINGS
BEYOND EDGE OF FLASHING ON STORM COLLAR
EACH SIDE AND MOP INTO
EXISTING ROOFING FLASHING
CORRUGATED METAL ROOF

N
ROOF

I
WITH RIGID INSULATION AND
BUILT-UP ROOFING

TREATED WOOD NAILER, SECURED


TO METAL DECK FROM BELOW WITH
LAG BOLT, TYP.
4 LAG BOLTS, ONE EACH SIDE

on
pti
Descri
METAL FLUE
LONG
RADIUS
ELBOW
PIPING THRU ROOF DETAIL FLUE THRU ROOF DETAIL
D3 N.T.S.
D5 N.T.S.
12" STEEL

N. 3’ TO
EXHAUST
PIPE

ROOF
ROOF
5

MI
HEAT
8" DIA PEX TUBING
RESISTANT
THIMBLE THRU COMPRESSION TANK @ 9" O.C. SECURED
ROOF TO WIRE MESH WITH
CHARGE VALVE FOR
WIRE TIES
TANK PRESSURIZATION

UNION (UP TO 2-1/2") AIR VENT


FASTEN TO CONCRETE

Mark
MANUFACTURER FLANGE (3" & OVER) SERVICE VALVE
STRUCTURE. SLAB
PROVIDED BLADDER NON-STRUCTURAL
INCLUDE SWAY WATER SUPPLY
ROOF CHECK VALVE (OPTIONAL)

Appr.
WIRE MESH
BRACING SWING TYPE JOINT
CURB PRESSURE GAUGE TYP THIS LINE PRV
W/GAGECOCK SLOPE MIN OF

Date
TRANSITION TO
1" IN 5’-0"
12" DIA
EXHAUST AT SERVICE VALVE
WATER
DISCHARGE GATE MAKE-UP
C IN-LINE PUMP BACKFLOW
VALVE
PREVENTER TO FLOOR
EXHAUST FAN CHECK VALVE Y-STRAINER W/ DRAIN
STRAINER REMOVAL SPACE
BLOW-OFF VALVE
VEHICLE EXHAUST BALANCING VALVE

DRUM
HANGER SUPPORTS 2 SIDES
8" HOSE
FROM HEATING
REDUCER (IF REQ’D) EQUIPMENT

TO PUMP

NOTE: AIR SEPARATOR


NOZZLE
PROVIDE 4-BUTTON CONTROLLER

on
W/ CLIP

pti
MOUNTED 5’ A.F.F. TO COLUMN BELOW COMPACTED 2" EXPANDED POLYSTYRENE

Descri
DRAIN VALVE GRADE FOAM INSULATION BOARD
WITH VAPOR BARRIER

VEHICLE EXHAUST FAN DETAIL VERTICAL INLINE PUMP PIPING DETAIL HEATING HOT WATER PIPING DIAGRAM RADIANT SLAB CROSS-SECTION DETAIL
C2 N.T.S.
C3 N.T.S.
C4 N.T.S.
C5 N.T.S.

R FLOW
AI
SECURE HOOD TO
CURB WITH LAG
BOLTS MANUFACTURER
EXHAUST
PROVIDED ROOF
CURB. DUCT SIZE
VARIES 2X NAILING STRIP

Mark
ROOF STRUCTURE
SECURE TO WALL 40" MIN MANUFACTURER’S
FRAMING MANUFACTURER PROVIDED
ROOF CURB

dgn
ROOF CURB.

5000.
Rev.

7/22/2011
W 912QR-11-R-0071
CURB FLASHING

e nam e:LCARC_M -

e:AS SHOW N
R FLOW

on No.

F-171-40-160
Project Code:
B CANT STRIP

AI

tati

ot date:

ot scal
11
DUCTWORK

ci
28-
Date:

i
Sol
07-

Pl

Pl
Fi
C.KORPASH
Ckd by:
METAL GUARD ROOF STRUCTURE
BACKDRAFT DAMPER 18"

tted by:
ewed by:
gned by:
2"
ROOF OPENING FRAMING,

.FRANCO
Dwn by:
PROVIDE 1/2" WIRE MESH REFER TO STRUCTURAL BACKDRAFT DAMPER

M .BETZ
A.REED

A.REED

Subm i
SCREEN AT INLET

Revi
DRAWINGS

Desi

I
FINISHED FLOOR

NEERS
NOTE: EXTEND DUCT TO 2" FROM METAL

CORPS OF ENGI
GRATE IN FLAMMABLE STORAGE ROOM.

LLE,KENTUCKY
CT

FAX (714) 327-1601


ROOF MOUNTED INTAKE/RELIEF PENTHOUSE FLOOR LEVEL EXHAUST DETAIL UPBLAST EXHAUST FAN MOUNTING DETAIL ROOF MOUNTED EXHAUST FAN

STRI

TE 800
B2 B3 B4 B5

A 92707
N.T.S. N.T.S. N.T.S. N.T.S.

VE,SUI
LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


SEE NOTE 3, RETURN

SVI

TEL (714) 327-1600


SVI
4 (TYP)

LOUI
BALANCING PLUG VALVE INSTALL CONCENTRIC REDUCERS

U.S.ARMY

LOUI
2-WAY MODULATING VALVE
(SEE NOTE NO. 1)

4
(SEE NOTE NO. 1) BOTH SIDES OF CONTROL AND
AIR VENT (3/4" GATE REDUCER BALANCE VALVE IF REQD AS SHOWN (TYP)
FASTEN FLASHING VALVE WITH CAP) SECURE TO STRUCTURE
WITH SHEET METAL THERMOMETER WITH BALANCING SEE NOTE 6
SEPARABLE SOCKET VALVE
SCREWS & SEAL 1/4" MANUAL AIR VENT REMOVABLE CAP W/SELF OPTIONAL PRESSURE TAP
ng\gbna\m oraja\dm s97636\LCARC_M-5000.dgn

ALL FLASHING WITH 1/4" N.P.T. ALIGNING O-RING SEAL COIL AIR VENT UNION

WITH MASTIC SEE NOTE 5


20 GA. 3/4" N.P.T. BOLT UNIT HEATER
BALANCE
GALVANIZED SHEET HOT WATER COIL
VALVE TO WALL
SUPPLY N
METAL FLASHING O
2"x6" CURB PROVIDE WALL
3/4" BALL VALVE SERVICE VALVE

RESERVE CENTER
20 GA. BRACKET WITH

CO
SEE NOTE 1
HWR SWIVEL COCK

MEXI
CANT STRIP GALVANIZED SHEET GAUGES AND GAUGE COCK
UNION (TYP.) 3/4" TO
METAL COUNTER W/THERMOWELLS OR PETE’S
PUMP SUCTION
FLASHING HWS PLUGS (SEE NOTE 2)
ROOFING UP

LAS CRUCES,NEW
1-1/2" x 1-1/2" x 1/4" GALVANIZED MANUAL OR AUTOMATIC AIR
TO FLASHING

LS
ANGLE IRON STAND HANGER STRAP VENT IF TAP PROVIDED BY

DETAI
BALL VALVE (UP TO
A PER IMC AND COIL MFG (SEE NOTE 4)
1-1/2")
5 GALLON MINIMUM O
W SMACNA
FL NOTES:
10 GAUGE TANK SHELL R
AI
Y-STRAINER w/

U.S.ARMY
AND HEADS BLOW-OFF VALVE 1 PROVIDE DIELECTRIC UNIONS WHERE PIPING
3/4" FROM PUMP
AND MATERIALS DIFFER
PRESSURE GAUGE W/GATE VALVE
DISCHARGE 3/4" TEE 2 PETE’S PLUG SHOWN
3/4" DRAIN W/GATE VALVE & HOSE COUPLING
ROOF 3/4" TO 1/2" 3 WHEN TAPPING INTO TOP OF MAINS, AIR
c:\pwworki
7/22/2011

DUCT THROUGH BUSHING W/NIPPLE VENTS ARE REQD AS SHOWN


STRUCTURE 1/2" GLOBE VALVE 3/4" COIL DRAIN VALVE W/HOSE COUPLING
ROOF (TYP.) 4 NORMALLY USE MANUAL AIR VENT;
W/HOSE COUPLING
3" x 3" x 1/4" AUTOMATIC VENT ACCEPTABLE ONLY
STEEL PAD BOLTED WITH BLADDER COMPRESSION TANK CAPPED HOSE BIBB AT
NOTES:
6" CONCRETE PAD TO CONCRETE PAD LOWEST POINT FOR
1. WHERE 3-WAY MODULATING VALVES ARE REQUIRED, 5 ARRANGEMENT SHOWN FOR HOT WATER
DRAINAGE IF NOT
PROVIDE ADDITIONAL PIPING AND ADDITIONAL ACCESSORIES AS SHOWN. RECTANGULAR COIL WITH FULL FLOW THROUGH COIL ON FAILURE
SUPPLIED ON COIL
DUCTWORK SHEET
6 WHERE SIZE PERMITS, ELIMINATION OF BALANCE VALVE AND REFERENCE
LEAVING SERVICE VALVE W/CIRCUIT SETTER IS PERMISSIBLE NUMBER:

M-5000
DUCT THRU ROOF DETAIL CHEMICAL POT FEEDER DETAIL HEATING COIL DETAIL STANDARD DUCT SUPPORT UNIT HEATER DETAIL
A1 N.T.S.
A2 N.T.S.
A3 N.T.S.
A4 N.T.S.
A5 N.T.S.
Sheet 135 of 222
AM
9:03:48
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

SEISMIC BRACE
24 GA. FLASHING-SECURE
PER SMACNA AND
METAL SCREEN W/ SHEETMETAL SCREWS
ANGLE IRON REINFORCING FRAME UFC 3-301-01 (TYP.)
OR RIVETS TO WALL & 5’-0" MAX US Army Corps
WHERE REQUIRED
of Engineers
SEAL ALL ROUND (TYP.) SHEET METAL
NOTE LOUISVILLE DISTRICT
(20 GA.)
"A" = PIPE AND INSULATION
SCREEN STANDARD DUCT MADE 24 GA. MIN. COUNTER-
WATER TIGHT. STIFFENERS DIAMETER PLUS ONE INCH MINIMUM
FLASHING RESILIENT CAULKING
MAY BE INSIDE. "A" "A"

Appr.
HANGER ROD
SIZED FOR LOAD
BOLTS ANGLE RIVETED OR SPOT

Date
WELDED AS REQUIRED. BOILER EXTERIOR PANEL
2 MAX
5 MI 1 MIN
13 N
. INSULATION (RIGID INSULATION
1
18" LONG ADJUSTABLE
DUCT SIZE + 25% CENTERED ON WROUGHT CLEVIS
SUPPORT)
WELD
1/2" SCREEN R PIPE
ANGLE

N.
D 18 GAGE GALV
IRON

12" MI
N. SADDLE 12" LONG 18 GAGE GALVANIZED
W SEE NOTE 3
SEE NOTE 3
18" MI
R = W/2
SEE NOTE 4 (TYP.)
SADDLE 12" LONG
NOTE:
SEE NOTE 5 (TYP.)
MATCH OD OF INSULATION FOR INSULATED LINE,
U.S.G. THERMA FIBER PENETRATING
MATCH OD OF PIPE FOR UNINSULATED LINES.
DUCT
OR EQUAL DENSITY REFER TO SMACNA SEISMIC RESTRAINT MANUAL AND
UFC 3-301-01
PACKING (TYP.) NOTES:
FIRE STOP EXPANSION CONCRETE CURB
SYSTEM (TYP.) ANCHOR 1. ANCHOR BOLT SIZE AND QUANTITY PER SMACNA REQUIREMENTS.

NOTES: 2. PIPE INSULATION IS NOT SHOWN FOR CLARITY.

on
EXTERIOR INTERIOR 3. PROVIDE DOUBLE WASHER AND NUT ASSEMBLY.

pti
1. SEE ARCHITECTURAL DRAWINGS

Descri
4. OPTIONAL HORIZONTAL SEISMIC RESTRAINT.
FOR ROOF PENETRATION DETAILS. NOTES 5. STRUCTURAL MEMBER, REFER TO STRUCTURAL PLANS.
1. SUBMIT FOR STRUCTURAL REVIEW

GOOSENECK DETAIL DUCT THRU WALL DETAIL PIPE HANGER DETAIL - SINGLE PIPE BOILER ANCHOR DETAIL TO CONCRETE CURB PIPE HANGER DETAIL - TRAPEZE TYPE
D1 N.T.S.
D2 N.T.S.
D3 N.T.S.
D4 N.T.S.
D5 N.T.S.

SECURE TO
METAL SLEEVE STRUCTURE
ABOVE
SECURE TO
SECURE TO STRUCTURE ABOVE STRUCTURE
PIPE 1-1/2" MIN.
MAX. 6’-0" LENGTH PER SMACNA SEISMIC GUIDELINES ABOVE
FLEXIBLE DUCT 4’-0" MAX. 1-1/2" MIN.
WIRE TO BE SECURED TO
STRUCTURE ABOVE

Mark
SUPPLY AIR VOLUME
DAMPER WALL CONSTRUCTION VARIES
SILICONE SEALANT

Appr.
1-1/2" MIN.
SPIRAL DUCT FLEX DUCT
6’ MAX.

Date
4" WIDE SHEET METAL FLEXIBLE
DUCT SUPPORT STRAP
DUCT
MINERAL FIBER PACKING
C
SAFETY HANGER 12 GA. WIRE OR
18 GA. 1" METAL STRAP SAG 1/2" PER
FOOT OF SUPPORT
#10 SCREWS SPACING
FLEXIBLE DUCT
CLAMPING DEVICE
(TYP.)
CEILING

CEILING DIFFUSER NOTES:


OR GRILLE 1.INSTALL DUCTWORK PER SMACNA
NOTE:
GUIDELINES. REFER TO "SMACNA DUCT

on
NOTES: 1.REFER TO SPECIFICATIONS FOR ESCUTCHEON PLATE CONSTRUCTION STANDARDS,"LATEST

pti
REQUIREMENTS. EDITION.

Descri
1.LOCATE VOLUME DAMPER AS FAR AWAY FROM 2.SUPPORT PIPES & DUCTS ON EITHER SIDE OF WALL.
DIFFUSER OR GRILLE AS POSSIBLE

LAY-IN DIFFUSER/GRILLE CONNECTION DETAIL DUCT/PIPE PENETRATION THRU NON RATED WALL FLEXIBLE DUCTWORK HANGER DETAIL
C2 C3 C4 N.T.S.
N.T.S. N.T.S.

Mark
dgn
2 2
A 4B

5010.
Rev.
3 3

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS SHOW N
on No.

F-171-40-160
Project Code:
B

tati

ot date:

ot scal
11

ci
28-
Date:
1" MIN. OVERLAP (4 SIDES)

i
Sol
07-

Pl

Pl
Fi
4A 1 4A 1" MIN. OVERLAP (4 SIDES)
1/4"MIN. CLEARANCE A

C.KORPASH
Ckd by:
SECTION A-A 1/4"MIN. CLEARANCE

SEE NOTE #4

tted by:
ewed by:
gned by:
SEE NOTE #4

.FRANCO
1.

Dwn by:
FLOOR WALL ASSEMBLY - MIN.. 2-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF

M .BETZ
A.REED

A.REED

Subm i
Revi
Desi
ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER. OF OPENING IS 18 IN.

I
1A. SEE CONCRETE BLOCK (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. DUCT CONNECTION

NEERS
DUCT CONNECTION (TYPICAL)
(TYPICAL)
2. STEEL SLEEVE - (OPTIONAL, NOT SHOWN) - NOM 10 IN. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL

CORPS OF ENGI

LLE,KENTUCKY
ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. AS AN ALTERNATE, NOM 10 IN. (254 MM)

CT

FAX (714) 327-1601


STRI

TE 800
RE-USEABLE DIAM.. (OR SMALLER) SLEEVE FABRICATED FROM NOM 0.019 IN. (0.48 MM) THICK GALV STEEL CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY FLUSH WITH FLOOR DUCT SMOKE DETECTOR
STYLE "B"

A 92707
VE,SUI
FUSIBLE LINK OR WALL SURFACES. T RATING IS 0 HR WHEN SLEEVE IS USED.

LLE DI

FORNI
HUTTON CENTRE DRI

SANTA ANA, CALI


3. THROUGH PENETRATE - NOM 4 IN. (102 MM) DIAM.. (OR SMALLER) TYPE L (OR HEAVIER) COPPER PIPE, NOM 12 IN. (305 MM) DIAM.. (OR SMALLER) SERVICE WEIGHT SLEEVE

SVI

TEL (714) 327-1600


SVI
(OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. (305 MM) DIAM.. (OR SMALLER) CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE OR NOM 12 IN. (305 MM) (SEE NOTES #2 & #3)

LOUI
U.S.ARMY

LOUI
DIAM.. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE CENTERED IN THE OPENING AND RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR OR WALL
SLEEVE

4
ASSEMBLY.
(SEE NOTES #2 & #3)

4. PIPE COVERING* - NOM 1/2 TO 2 IN. (13 TO 15 MM) THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN... 3.5 PCF OR 56kg/m‡) GLASS FIBER UNITS JACKETED ON 6" MAX.
ON ALL
THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS
SIDES
ng\gbna\m oraja\dm s97636\LCARC_M-5010.dgn

SECURED WITH METAL FASTENERS OR FACTORY -APPLIED SELF - SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT STRIP TAPE
SUPPLIED WITH THE PRODUCT.
6" MAX. ON WALL CONSTUCTION
ALL SIDES
SEE PIPE AND EQUIPMENT COVERING - MATERIALS* (BRGU) CATEGORY IN BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING
MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED NOTES

RESERVE CENTER

CO
INDEX OF 50 OR LESS MAY BE USED.
WALL CONSTUCTION

MEXI
1. OPENING IN WALL SHALL BE A MINIMUM 1/8" PER 4. MOUNTING ANGLES SHALL BE A MINIMUM OF 1 1/2" X 1
FOOT LARGER THAN OVERALL SIZE OF DAMPER AND 1/2" X 14 GAGE AND BOLTED, WITH 1/4" - 20 BOLT,
FIRESTOP SYSTEM - THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE AS FOLLOWS:
SLEEVE ASSEMBLY FOR GALVANIZED STEEL DAMPERS WELDED, OR SCREWED WITH NO. 10 SCREWS TO SLEEVE AT
NOTES AND A MINIMUM 3/16" PER FOOT FOR STAINLESS A MAXIMUM SPACING OF 6" FOR STAINLESS STEEL AND 12"

LAS CRUCES,NEW
A. PACKING MATERIAL - MIN.. 1 IN. (25 MM) THICKNESS OF FIRMLY PACKED MINERAL WOOL BATT INSULATION USED AS A PERMANENT FORM. PACKING MATERIAL STEEL DAMPERS. MAXIMUM OPENING NOT TO FOR GALVANIZED WITH A MINIMUM OF TWO CONNECTIONS IN

LS
TO BE RECESSED FROM TOP SURFACE OF FLOOR OR SLEEVE OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF EXCEED 1/8" PER FOOT PLUS ONE INCH FOR EACH SIDE, TOP, AND BOTTOM (SEE ILLUSTRATION).

DETAI
1. OPENING IN WALL SHALL BE A MINIMUM 1/8" PER 3. IF ANY OTHER DUCT-SLEEVE CONNECTIONS ARE USED, SLEEVE
GALVANIZED STEEL DAMPERS. OPENING SHALL NOT MOUNTING ANGLES SHALL OVERLAP WALL A MINIMUM OF ONE
A FOOT LARGER THAN OVERALL SIZE OF DAMPER AND SHALL BE MINIMUM OF 16 GAGE FOR DAMPERS UP TO CAULK FILL MATERIAL (ITEM B).
SLEEVE ASSEMBLY FOR GALVANIZED STEEL DAMPERS BE LESS THAN 1/4" LARGER FOR ANY SIZE DAMPER INCH.
36"Wx24"H AND 14 GAGE IF DAMPER WIDTH EXCEEDS 36" OR
AND SLEEVE ASSEMBLY.
AND A MINIMUM HEIGHT EXCEEDS 24".

U.S.ARMY
B. FILL, VOID OR CAVITY MATERIAL* - CAULK SEALANT - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH THE TOP SURFACE OF THE FLOOR OR SLEEVE OR 5. WHEN MULTIPLE DAMPER ASSEMBLIES ARE JOINED OR WHEN
3/16" PER FOOT FOR STAINLESS STEEL DAMPERS. 2. SLEEVE GAGE SHALL BE AT LEAST EQUAL TO THE
MAXIMUM OPENING NOT TO EXCEED 1/8" PER FOOT FLUSH WITH BOTH SURFACES OF WALL. WHEN NOM PIPE COVERING THICKNESS IS 2 IN. (51MM), MIN.. THICKNESS OF CAULK FILL MATERIAL IS 2 IN. (51 MM). WHEN GAGE OF THE DUCT AS DEFINED BY THE APPROPRIATE FASTENING DAMPER TO SLEEVE, DAMPERS SHALL BE
PLUS ONE INCH FOR GALVANIZED STEEL DAMPERS. 4. MOUNTING ANGLES SHALL BE A MINIMUM OF SMACNA DUCT CONSTRUCTION STANDARD AND FASTENED WITH NO. 10 BOLTS OR SCREWS, 3/16" RIVET
NOM PIPE COVERING THICKNESS IS 1-1/2IN. (38 MM) OR LESS, MIN.. THICKNESS OF CAULK FILL MATERIAL IS 1 IN. (25 MM). THE HOURLY F AND T RATINGS OF THE
OPENING 1 1/2" X 1 1/2" X 14 GAGE AND BOLTED, WITH DESCRIBED IN NFPA 90A WHEN ONE OR MORE OF THE OR 1/2" TACK WELD STAGGERED INTERMITTENTLY, AND
c:\pwworki

FIRESTOP SYSTEM ARE DEPENDENT UPON THE THICKNESS OF THE FLOOR OR WALL, THE SIZE OF PIPE, THE THICKNESS OF PIPE COVERING MATERIAL AND THE SIZE OF
7/22/2011

SHALL NOT BE LESS THAN 1/4" LARGER FOR ANY 1/4" - 20 BOLT, WELDED, OR SCREWED WITH FOLLOWING DUCT-SLEEVE CON- NECTIONS ARE USED SPACED 12" MAXIMUM C-C FOR GALVANIZED AND 6"
SIZE DAMPER AND SLEEVE ASSEMBLY. NO. 10 SCREWS TO SLEEVE AT A MAXIMUM THE ANNULAR SPACE (BETWEEN THE PIPE COVERING MATERIAL AND THE EDGE OF THE CIRCULAR THROUGH OPENING), AS SHOWN IN THE FOLLOWING TABLE: (PLAIN ’S’ SLIP, HEMMED ’S’ SLIP, MAXIMUM C-C FOR STAINLESS STEEL.
SPACING OF 6" FOR STAINLESS STEEL AND 12" FOR GALVANIZED STANDARD ’S’ SLIP, REINFORCED STANDING ’S’ SLIP,
WITH A MINIMUM OF TWO CONNECTIONS IN EACH SIDE, TOP, AND MIN FLOOR OR WALL MAX PIPE NOM PIPE COVERING ANNULAR SPACE F RATING T RATING W RATING INSIDE SLIP JOINT, AND DOUBLE ’S’ SLIP.)
2. SLEEVE GAGE SHALL BE AT LEAST EQUAL TO THE GAGE OF 6. FURNISH WITH DUCT SMOKE DETECTOR
BOTTOM (SEE ILLUSTRATION). MOUNTING THKNS IN. (mm) DIAM IN. (mm) THKNS IN. (mm) IN. (mm) HR HR CLASS
THE DUCT AS DEFINED BY THE APPROPRIATE SMACNA DUCT ANGLES SHALL OVERLAP WALL A MINIMUM OF ONE INCH.
CONSTRUCTION STANDARD AND DESCRIBED IN NFPA 90A 2-1/2 (64) 4 (102) 1 OR 1-1/2 (25 OR 38) 1/2 TO 2-3/8 (13 OR 60) 2 1 1 7. FOR APPLICATIONS REQUIRING MULTIPLE ACTUATORS,
WHEN ONE OR MORE OF THE FOLLOWING DUCT-SLEEVE 4-1/2 (114) 4 (102) 2 (51) 1/4 TO 3-5/8 (6 OR 92) 2 1-1/2 1 3. IF ANY OTHER DUCT-SLEEVE CONNECTIONS ARE USED, COORDINATE POWER REQUIREMENTS WITH ELECTRICAL.
2-1/2 (64) 12 (305) 1 (25) 1/2 TO 1-1/2 (13 OR 38) 2 1/2 1 SLEEVE SHALL BE MINIMUM OF 16 GAGE FOR DAMPERS
CONNECTIONS ARE USED (PLAIN ’S’ SLIP, HEMMED ’S’ SLIP, SHEET
STANDARD ’S’ SLIP, REINFORCED STANDING ’S’ SLIP, INSIDE 4-1/2 (114) 12 (305) 1 (25) 1/2 TO 2-3/8 (13 OR 60) 3 1 1 UP TO 36" WX 24" H AND 14 GAGE IF DAMPER WIDTH
EXCEEDS 36" OR HEIGHT EXCEEDS 24". REFERENCE
SLIP JOINT, AND DOUBLE ’S’ SLIP.) 2-1/2 (64) 12 (305) 1/2 (13) 1/2 TO 2-3/8 (13 OR 60) 2 0 1
NUMBER:

M-5010
FIRE DAMPER FIRE RATED PIPE PENETRATION COMBINATION FIRE/SMOKE DAMPER
A1 N.T.S.
A2 N.T.S.
A3 N.T.S.
Sheet 136 of 222
9:04:16 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

LIFTING RING PRESSURE GAGE


EXPANSION TANK SUPPORT RODS
TYP US Army Corps
1/8 of Engineers
CHARGING VALVE WITH DOUBLE NUTS AT TOP
AND BOTTOM (TYP 4) CHARGING VALVE 3/4" FROM SUCTION SIDE OF PUMP LOUISVILLE DISTRICT

BLADDER TYPE EXPANSION TANK,


SEE SCHEDULE FOR SIZE

Appr.
MANUAL AIR VENT

Date
"A" DIA

CLIP ANGLE BLADDER TYPE EXPANSION TANK,


SEE SCHEDULES FOR SIZES
WELD TO
NUTS AND
D SUPPORT
WASHERS
ANGLE
PROVIDE OPENING IN THE MOUNTING
SEISMIC BRACE RING TO ALLOW ACCESS FOR THE DRAIN
1" HOSE GATE VALVE ANGLE "B"X"C"X"D" (TYP 1 FOR EACH VALVE
CORNER). INSTALL

PRESSURE GAUGE
SIDE RAILS. SLOPE
EXPANSION ANCHOR 3/4" GATE VALVE
TO SYSTEM PUMP FOR SEISMIC
FROM AIR SEPARATOR
GAL A B C D TYP
1/8
SUPPORT (TYP)
3/4" DRAIN LINE, ROUTE
MOUNTING RAIL
TO FLOOR DRAIN

on
PROVIDE 5mm STEEL
0-50 1/2" 2" 2" 1/4"

pti
CHECKER PLATE. MOUNT

Descri
EQUIPMENT TO STEEL 6" CONCRETE PAD
PLATE WITH NEOPRENE
0-100 5/8" 3" 3" 1/4"
PAD.

SUSPENDED EXPANSION TANK DETAIL PLATFORM FOR SUSPENDING EQUIPMENT FROM ABOVE EXPANSION TANK DETAIL
D1 N.T.S.
D3 N.T.S.
D5 N.T.S.

INTAKE VENTILATOR

ROOF STRUCTURE

Mark
EC
SIDE PANEL (UNIT) -
FAN

Appr.
DUCT SUPPORT COORDINATE WITH
INSULATION (UNIT) SPRING VIBRATION
CROSS MEMBER STRUCTURAL
ISOLATION, TYP. STEEL TRUSS,
CURB MOUNTING MEMBERS FOR
DUCT FLANGE

Date
PLAN REFER TO SPECS TYP.
ANGLE 2’x2"x1/4" SPREADER
SEALING GASKET FURNISHED LOCATION.
WITH CURB AROUND ENTIRE
PERIMETER. TYPICAL STRUCTURAL STEEL

C GALVANIZED SHEET MEMBER FOR EQUIPMENT


5/8" ALL
UNIT BASE METAL COUNTER
ROOF STRUCTURE THREADED ROD,
FLASHING. (TYP)
OSA B-LINE STRUT
FLEX. DUCT
CHANNEL,
CONNECTOR FACTORY SEISMIC ROOF
B-12, TYP.
CURB EXTENDED AROUND C 1/8" SLACK AIRCRAFT
L
0.5 CLEARANCE CABLE, TYP.
ENTIRE PERIMETER OF SPRING
M H
NAILING STRIP UNIT. VIBRATION REFER TO STRUCTURAL SHOTO
AF R A
DUCTWORK ISOLATION, DRAWINGS FOR T
4" RIGID ACOUSTICAL F
SPREADER MEMBER T
TYP. EN EN C
L
INSULATION WITHIN V M M
LOCATION AND UPPER I P
R
REFER D UI

on
ENTIRE CURB FRAME C

pti
EQ S
TO ATTACHMENT DETAILS

Descri
ROOFING C
L
SPECS PARALLEL
THREADED ROD, TYP.
AIR FLEX.
OF 4 SIZED FOR LOAD BLADE/
FLOW B-LINE STRUT
ALL-DIRECTIONAL SEISMIC LOW LEAK CONN FILTER
CHANNEL B12, TYP.
1/8" SLACK AIRCRAFT SNUBBERS (TYP) MONITORING (TYP) RACK
REFER TO STRUCTURAL AND MOTORIZED AIR UNIT
CABLE, TYP. STATION
ARCHITECTURAL DRAWING DAMPER A3
NUMBER OF ISOLATION FOR HEATING
FOR EQUIPMENT SUPPORT TYPE "B"
UNITS AS REQUIRED WELDED STEEL BASE COIL DETAILS SEE M-5000
FRAMING MEMBERS
SIMILAR TO MASON
KSL/Z-1225
DUCT
PLAN
ELEVATION
FLEX CONNECTION,
TYP.

ROOF TOP UNIT CURB DETAIL IN-LINE FAN SUSPENSION DETAIL VIBRATION ISOLATION BASES HEAT AND VENT UNIT SUSPENSION DETAIL
C1 N.T.S.
C2 N.T.S.
C3 N.T.S.
C4 N.T.S.

Mark
D2

dgn
DUCT THRU WALL

5020.
M-5010

Rev.

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -

e:AS SHOW N
on No.

F-171-40-160
Project Code:
B

tati

ot date:

ot scal
11

ci
28-
Date:

i
24" ACCESS MANHOLE

Sol
07-

Pl

Pl
Fi
TO ACCESS LADDER

C.KORPASH
Ckd by:
8’ X 23’ X 6" THK.
PROTECTIVE CONCRETE FIBERGLASS MANWAY

tted by:
ewed by:
gned by:
MAKE-UP AIR UNIT SLAB
EXTENSION (TYP.)

.FRANCO
Dwn by:
ELECTRIC HEAT

M .BETZ
A.REED

A.REED

Subm i
GAGE HATCH

Revi
Desi
VIBRATION ISOLATION STEEL DIRECT EVAPORATIVE COOLER

I
GRADE
BASE FRAME WITH SEISMIC C3

NEERS
SNUBBER. FOR DETAIL SEE
M-5020

N
MI
3"
2" TANK VENT 2" DHWR

CORPS OF ENGI

LLE,KENTUCKY
CT

FAX (714) 327-1601


2" DHWS

STRI

TE 800
1-1/2" HWS

A 92707
VE,SUI
CLEANOUTS PER IMC BIRD SCREEN 1-1/2" HWR

LLE DI
FROM HX-1

FORNI
TO HX-1

HUTTON CENTRE DRI

SANTA ANA, CALI


SVI
FOR BACKFILL

TEL (714) 327-1600


SVI
40"
REFER TO

LOUI
U.S.ARMY

LOUI
MIN DUCT THRU ROOF
SPECIFICATION

4
FACTORY C1
A1 SECTION 31 00 00
GREASE SEISMIC CURB
SEE
TROUGH M-5020 EARTHWORK
M-5000

6,800 GAL., POTABLE


ng\gbna\m oraja\dm s97636\LCARC_M-5020.dgn

HOT WATER UNDERGROUND


EXHAUST DUCT
ENCLOSURE SHAFT STORAGE TANK
* MAINTAIN A MIN.
WITH MIN. 3" AIR
SPACE AROUND CLEARANCE OF 2FT.
1-HOUR FIRE RATED CHASE BY *
EXHAUST DUCT BETWEEN TANK AND

RESERVE CENTER
GENERAL CONTRACTOR TANK HOLD DOWN STRAP SIDES OF EXCAVATION

CO
(ABOVE CEILING ONLY) AND MASONRY ANCHOR

MEXI
(TYP.)

16 GA. WELDED GREASE

N.

LAS CRUCES,NEW
12"
EXHAUST DUCT

LS
MI

DETAI
THREADED ROD COUPLING WITH PEA GRAVEL
A
STRUCTURAL CHANNEL REINFORCEMENT 8’X 22’X 18" THK.

N.
18"
REINFORCED

MI

U.S.ARMY
CEILING
CONCRETE PAD
6 AT 1 FT. EACH
WAY
UL LISTED VAPOR PROOF
c:\pwworki
7/22/2011

FLOURESCENT LIGHT

U.L. CLASSIFIED
GREASE FILTERS
NOTES:
FOR HOOD DETAILS
1.CONTROL PANEL FOR LIGHTS AND FANS SHALL BE REMOTE MOUNTED. SEE KITCHEN DRAWINGS
SHEET
REFERENCE
NUMBER:

M-5020
KITCHEN HOOD AND SUPPLY/EXHAUST DUCT SECTION THRU 6800 GAL. TANK
A1 N.T.S.
A4 N.T.S.
Sheet 137 of 222
9:04:46 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

EVAPORATIVE COOLER UNITS SCHEDULE (INDIRECT/DIRECT)


US Army Corps
DIRECT EVAPORATIVE COOLER of Engineers
OUTDOOR AIR SUPPLY FAN INDIRECT EVAPORATIVE COOLER (IDEC) WINTER HEAT RECOVERY EXHAUST FAN HOT WATER COIL WITH 30% PROPYLENE GLYCOL ELECTRICAL
(DEC) LOUISVILLE DISTRICT
STATIC MAX APPROX
MARK MANUFACTURER MAX
LOCATION SERVES MIN OA RA IDEC OA RA HX EAT LAT ESP PREFILTER/ WEIGHT REMARKS
NO PRESS MOTOR CFM OPERATING HEATING EAT LAT EWT LWT PRESS
MODEL NO OSA CFM IN WG FAN FILTER GPM ROWS FPI APD MCA FLA VOLTS PHASE HZ
IN WG HP MIN HP CFM ^F ^F ^F DROP LB

Appr.
CFM DB ^F WB ^F DB ^F WB ^F DB ^F WB ^F DB ^F WB ^F DB ^F EFF % DB WB DB WB RPM (IN WG)
TOTAL EXT WBDE % TOTAL EXT (FT)

EC MERV 8/ 2 3 4 5 6 7 8 9 10
ENERGY LABS 7500

Date
ARC BUILDING ASSEMBLY 1500 7500 3.6 0.5 7.5 99 64 78 65 74.6 56.5 70 18 72 45 50 74.6 56.5 58.0 56.5 1.2 0.3 1740 3 3600 58 77 180 160 8.1 1 13 2.0 .2 27.6 24.1 460 3 60 9000
1-1 MERV 13 12 13 14 15 18 19 20 21

7000 1 1
EC 1 1 1 1 MERV 8/ 1 2 3 4 5 6 7 8 9 10
ARC BUILDING ENERGY LABS OFFICES 700 (5000 DX 3.92 0.5 7.5 99 64 78 65 74.2 56.4 70 18 72 45 50 7000 1.1 0.3 1740 3 3000 63 82 180 160 7.0 1 13 2.0 .2 61.3 58.2 460 3 60 10000
1-2 MERV 13 11 12 13 14 15 18 19 21
MODE)

EC MERV 8/ 2 3 4 5 6 7 8 9 10
ARC BUILDING ENERGY LABS CLASSROOM 1400 7270 3.6 0.5 7.5 99 64 78 65 74.5 56.5 70 18 72 45 50 74.5 56.5 58.0 56.5 7270 1.1 0.3 1740 3 3500 59 80 180 160 8.9 1 13 2.0 .2 27.6 24.1 460 3 60 8000
1-3 MERV 13 12 13 14 15 18 19 21
D
EC PHYSICAL MERV 8/ 2 3 4 5 6 7 8 9 10
ARC BUILDING ENERGY LABS 650 3350 3.6 0.5 5 99 64 78 65 72.7 55.8 70 18 72 45 50 72.7 55.8 57.4 55.8 3350 0.9 0.3 1740 2 1800 60 82 180 160 4.8 1 13 2.0 .2 23.2 21.3 460 3 60 8000
1-4 READINESS MERV 13 12 13 14 15 16 18 19 21

EC MERV 8/ 2 3 4 5 6 7 8 9 10
ARC BUILDING ENERGY LABS TOILETS 1800 3250 3.6 0.5 5 99 64 78 65 71.4 55.4 70 18 72 45 50 71.4 55.4 56.8 55.4 3250 1.0 0.3 1740 2 3250 55 77 180 160 8.6 1 13 2.0 .2 23.2 21.3 460 3 60 8000
1-5 MERV 13 12 13 14 15 16 18 19 21

EC MERV 8/ 2 3 4 5 6 7 8 9 10
ARC BUILDING ENERGY LABS KITCHEN 1000 2250 3.6 0.5 3 99 64 78 65 72.3 55.7 70 18 72 45 50 72.3 55.7 57.0 55.7 2250 0.8 0.3 1740 1-1/2 2250 58 73 180 160 4.1 1 13 2.0 .2 22.3 21.1 460 3 60 5800
1-6 MERV 13 12 13 14 15 16 18 19 21

EC MERV 8/ 2 3 4 5 6 7 8 9 10

on
ARC BUILDING ENERGY LABS WEAPONS 825 2600 3.6 0.5 3 99 64 78 65 73.5 56.2 70 18 72 45 50 73.5 56.2 57.7 56.2 2600 0.8 0.3 1740 1-1/2 1900 58 74 180 160 3.6 1 13 2.0 .2 22.3 21.1 460 3 60 7250

pti
1-7 MERV 13 12 13 14 15 16 18 19 21

Descri
EC MERV 8/ 2 3 4 5 6 7 8 9 10
OMS BUILDING ENERGY LABS OFFICES 250 2200 3.6 0.5 3 99 64 78 65 72.6 56 70 18 72 45 50 72.6 56 57.2 56 2200 0.8 0.3 1740 3 1700 63 76 180 160 2.0 1 13 2.0 .2 22.3 21.1 460 3 60 7250
2-1 MERV 13 12 13 14 16 17 18 19 21

1 FOR CONDENSING UNIT (CU-1) INFORMATION SEE SCHEDULE BELOW 6 DUCT SMOKE DETECTOR IN SUPPLY DUCT 10 PROVIDE 120V HEATTRACE SYSTEM FOR ICW MAKE-UP WATER 15 PROVIDE FACTORY MOUNTED SUMP PUMP INTEGRAL WITH UNIT FOR IDEC, SIZED PER MANUFACTURER. 20 PROVIDE SIDE DISCHARGE SUPPLY AIR OPENING WITH PLUG FAN
2 FURNISH WITH VFD AND INVERTER DUTY MOTOR ON SUPPLY & EXHAUST FAN 7 SINGLE POINT POWER CONNECTION WITH 480V/120V 11 PROVIDE WITH STAINLESS STEEL DRAIN PAN 16 PROVIDE FACTORY MOUNTED SUMP PUMP INTEGRAL WITH UNIT FOR DEC SECTION. SIZED PER MANUFACTURER. 21 PROVIDE AIRFLOW VOLUME AND TRANSMITTER ON INLET TO SUPPLY FAN.
TRANSFORMER FOR CONV. OUTLETS, LIGHTS, HEAT
3 DOUBLE WALL CONSTRUCTION, OUTDOOR UNIT WITH PERFORATED LINER AT THE FAN SECTION 12 TEFC PREMIUM EFFICIENCY MOTORS 17 PROVIDE WITH CLEARWATER SYSTEMS DOLPHIN NON-CHEMICAL WATER TREATMENT PACKAGE OR EQUAL WITH MICROTRAC CONTROLLER.
TRACE, UPSTREAM OF DISCONNECT
4 PROVIDE 2"(MERV 8 PRE-FILTERS) AND 4"(MERV 13 EFFICIENCY FINAL FILTER) 8 PROVIDE WITH ROOF CURB 13 PROVIDE OUTSIDE AIR HOOD WITH 2" MERV 8 PRE- FILTER AND LOW LEAKAGE DAMPER 18 PROVIDE MINIMUM OUTDOOR AIR AIRFLOW MONITORING STATIONS
5 PROVIDE WITH STRUCTURAL STEEL BASE FRAME 9 PROVIDE 30% GLYCOL AT HEATING HOT WATER COIL 14 PROVIDE INTERNAL PIPE CHASE FOR ALL PIPING TO COILS, IDEC,AND DEC 19 PROVIDE INTERNAL 2" SPRING ISOLATORS FOR SUPPLY FAN

HEAT AND VENTILATING UNIT SCHEDULE

OUTDOOR AIR SUPPLY FAN HOT WATER COIL WITH 30% PROPYLENE GLYCOL ELECTRICAL BASIS OF DESIGN

MARK
LOCATION SERVES MIN FILTER APPROX REMARKS
ESP MOTOR EAT LAT EWT LWT PRESS MANUFACTURER

Mark
NO CFM RPM GPM ROWS FPI APD VOLTS PHASE HZ
CFM WEIGHT
IN WG HP ^F ^F ^F DROP MODEL NO
IN WG LB
(FT)

Appr.
HVU INDOOR UNIT SINGLE POINT POWER WITH VFD AND FACTORY MOUNTED CONTROL CENTER TO INCLUDE CONTROL CIRCUIT FUSING, CONTROL TRANSFORMER &
ARC UNIT STORAGE 2000 2000 0.4 1050 3/4 2" MERV 13 18 68 180 160 12.0 2 13 7 0.12 120 1 60 250 ENERGY LABS
1-1 INTEGRAL DISCONNECT SWITCH.

Date
HVU OUTDOOR UNIT NEMA 3R RATED VFD. SINGLE POINT POWER AND FACTORY MOUNTED CONTROL CENTER TO INCLUDE CONTROL CIRCUIT FUSING, CONTROL
OMS ROOF OMS WORK BAYS 4040 6060/4040 0.5 1800 5.0 2" MERV 13 18 60 180 160 19.4 2 13 3.5 0.25 460 3 60 2700 ENERGY LABS
2-1 TRANSFORMER & INTEGRAL DISCONNECT SWITCH,OSA AIRFLOW MONITORING STATION, INTERNAL SPRING ISOLATORS.

SUPPLY DIFFUSER, REGISTER, AND GRILLE SCHEDULE


CFM (BASED ON NC 30)
VEHICLE EXHAUST SCHEDULE (OMS BUILDING) MARK TYPE FACE SIZE NECK SIZE
REMARKS
NO (FACE) (INxIN OR DIA.) (INxIN OR DIA.) 1 &2-WAY 4-WAY
THROW THROW

MODEL HOSE HOSE REEL FAN PERFORATED SQUARE CEILING 24x24 6 - 0-125 TITUS PAS
MARK TSP REEL FAN
AREA SERVED MANUFACTURER REEL/ DIA. LENGTH CFM DRIVE MOTOR REMARKS
NO IN.W.G. V/PH/HZ V/PH/HZ
FAN IN. FT. HP HP

on
pti
PERFORATED SQUARE CEILING 24x24 8 - 126-200 TITUS PAS

Descri
A
VX VX TSR HUNG FROM STRUCTURE, DISCHARGE THRU ROOF. UNIT MOUNTED CONTROL PACKAGE INCLUDING STARTER, TRANSFORMER AND
TO VEHICLE WORKBAYS CARMON 8 40 1400 3.0 1/6 1.5 120/1/60 460/3/60
2-1 2-2 CMW13 INTERNAL WIRING. FURNISH WITH FOUR FUNCTION (ON/OFF/UP/DOWN). SPECIAL REEL TO ACCOMODATE 40 FT HOSE PERFORATED SQUARE CEILING 24x24 10 - 201-300 TITUS PAS

PERFORATED SQUARE CEILING 24x24 14 - 401-500 TITUS PAS

CONDENSING UNIT AND DX COIL SCHEDULE


SUPPLY GRILLE 8x8 6x6 0-100 - TITUS 300RL

COOLING DX COIL(EC 1-2) COMPRESSOR ELECTRICAL 8


SUPPLY GRILLE 20x14 18x12 400-700 - TITUS 300RL
MIN.
MARK
MANUFACT. AREA SERVED DUTY EER TOTAL REFRIG. RL RS EAT EAT LAT LAT CFM QTY TYPE HP WEIGHT REMARKS B
NO VOLT PH HZ FUSE UNIT
CAPACITY TYPE SIZE SIZE (DB) (WB) (DB) (DB) (EA) SUPPLY GRILLE 32x22 30x20 850 - TITUS 300RL
MBH 1 FLA
^F ^F ^F ^F

CU ENERGY 480
OFFICES COOLING 11.8 208.2 410A 4 4 77.4 64.5 55 54 5000 2 SCROLL 7.5 3 60 15 33.4 2000 1 2 3 4 5 6 7 8 9 SUPPLY GRILLE 10x10 10x10 150-450 - TITUS 300RL
1 LABS
5

1 CONDENSING UNIT SHALL BE FACTORY TESTED AS PART OF THE EC UNIT. 5 WEIGHT INCLUDED IN EC 1-2 9 MANUFACTURER’S GUARANTTED RATE OF 0.5% ANNUAL REFRIGERANT LEAKAGE. TITUS FL-15-JT (1) 1-1/2" SLOT -
E LINEAR DIFFUSER - - 640 -

Mark
2 UNIT SHALL BE MOUNTED ON STRUCTURAL BASE (SLEEPER SYSTEM) INDEPENDENT OF EC UNIT ROOF CURB 6 PROVIDE MINIMUM 4 STEPS OF CAPACITY CONTROL UNLOADING 120 CFM/FT. WITH BOOT.

3 7 WITH HOT GAS BYPASS


TITUS DL

dgn
4 REFRIGERANT PIPING SHALL BE FACTORY INSTALLED AND TESTED 8 CU-1 IS POWERED AND CONTROLLED FROM A SINGLE POINT POWER CONNECTION F DRUM LOUVER - 20X10 600-700 -

6000.
PROVIDED WITH EC 1-2. (STARTER, DISCONNECT SWITCH, AND CONTROLS ALL FACTORY PROVIDED)

Rev.

7/22/2011
W 912QR-11-R-0071

e nam e:LCARC_M -
6" - 0-150
J SQUARE PLATE 24X24 THERMA-FUSER TF-HC, DIGITAL WALL ADJUSTER

on No.

e:NONE
F-171-40-160
Project Code:
B 8" - 151-250

tati

ot date:
10" - 251-400

ot scal
11
SPLIT SYSTEM FAN COIL UNIT SCHEDULE (TRAINING BUILDING)

ci
28-
Date:

i
Sol
07-

Pl

Pl
Fi
C.KORPASH
RETURN, TRANSFER AND EXHAUST REGISTER AND GRILLE SCHEDULE

Ckd by:
COOLING HEATING
BASIS OF DESIGN
ARI 95F/75F
MARK

tted by:
REMARKS

ewed by:
AREA SERVED DUTY REFRIG. RL RS SUPPLY WEIGHT

gned by:
80F/67F
NO
MANUFACT. MODEL CAPACITY TYPE SIZE SIZE CFM MARK TYPE FACE SIZE NECK SIZE MAX

.FRANCO
CAPACITY

Dwn by:
CFM REMARKS

M .BETZ
A.REED

A.REED

Subm i
MBH (TOT) MBH NO (FACE) (INxIN OR DIA.) (INxIN OR DIA.) NC

Revi
Desi

I
FC
MITSUBISHI PCA-A24 SIPRNET HEAT PUMP 24 26 410A 3/8" 5/8" 600 71 1 2 3 4 5
1

NEERS
CAFE PERFORATED SQUARE CEILING 24x24 6x6 0-200 20 TITUS PAR

FC

CORPS OF ENGI
MITSUBISHI PCA-A24 TER HEAT PUMP 24 26 410A 3/8" 5/8" 600 71 1 2 3 4 5

LLE,KENTUCKY
2
24x24 8x8 201-300 20 TITUS PAR

CT
PERFORATED SQUARE CEILING

FAX (714) 327-1601


STRI

TE 800
C

A 92707
FC

VE,SUI
MITSUBISHI PCA-A24 ARMORER HEAT PUMP 24 26 410A 3/8" 5/8" 600 71 1 2 3 4 5

LLE DI
3

FORNI
24x24 10x10 301-400 20 TITUS PAR

HUTTON CENTRE DRI


PERFORATED SQUARE CEILING

SANTA ANA, CALI


FC SUPPLY

SVI

TEL (714) 327-1600


SVI
MITSUBISHI PCA-A24 HEAT PUMP 24 26 410A 3/8" 5/8" 600 71 1 2 3 4 5
4 OFFICE

LOUI
U.S.ARMY
PERFORATED SQUARE CEILING 24x24 22x22 980-1300 20 TITUS PAR

LOUI

4
FC KITCHEN
MITSUBISHI PCA-A24 HEAT PUMP 24 26 410A 3/8" 5/8" 600 71 1 2 3 4 5
5 OFFICE
PERFORATED SQUARE CEILING 24x48 22x46 1301-2800 20 TITUS PAR

1 SINGLE POINT POWER. CONTROL PANEL TO INCLUDE MOTOR STARTER, CONTROL TRANSFORMER, AND INTEGRAL DISCONNECT 4 CEILING MOUNTED
ng\gbna\m oraja\dm s97636\LCARC_M-6000.dgn

2 CONDENSATE PUMP. 5 WALL MOUNTED REMOTE CONTROLLER EXHAUST GRILLE 8X8 6X6 0-100 22 TITUS 350FL

3 POWERED FROM HP UNIT


EXHAUST GRILLE 10X10 8x8 101-250 22 TITUS 350FL
D
EXHAUST GRILLE 12x12 10X10 251-350 22

RESERVE CENTER
TITUS 350FL

CO
HEAT PUMP UNIT SCHEDULE (TRAINING BUILDING)

MEXI
EXHAUST GRILLE 16x16 12X12 351-750 22 TITUS 350FL

ELECTRICAL EXHAUST GRILLE 26x16 24X14 751-1100 22 TITUS 350FL

SCHEDULES
LAS CRUCES,NEW
BASIS OF DESIGN
MARK REFRIG EXHAUST GRILLE 38x20 36X18 1101-2000 22 TITUS 350FL
A NO TYPE REMARKS
SEER HSPF VOLT PH HZ MCA WEIGHT
MANUFACT. MODEL
G SECURITY EXHAUST GRILLE 16x16 16x16 615-750 22 TITUS SG-3300RL

U.S.ARMY
HP 208/
MITSUBISHI PUZ-A24 410A 16.8 10.9 1 60 19 165
1 230 H SIDEWALL RETURN 38x24 36x20 1875 22 TITUS 350FL
c:\pwworki
7/22/2011

HP 16.8 10.9 208/


MITSUBISHI PUZ-A24 410A 1 60 19 165
2 230
I EXHAUST GRILLE 10X10 8x8 101-250 22 TITUS 350FL

HP 16.8 10.9 208/ 19


MITSUBISHI PUZ-A24 410A 1 60 165
3 230
EXHAUST GRILLE 12x12 10X10 251-400 22 TITUS 350FL

HP 16.8 10.9 208/ 19 SHEET


MITSUBISHI PUZ-A24 410A 1 60 165
4 230 REFERENCE
EXHAUST GRILLE 14X14 12x12 401-650 22 TITUS 350FL NUMBER:

HP 208/
MITSUBISHI PUZ-A24 410A 16.8 10.9 1 60 19 165 M-6000
5 230
Sheet 138 of 222
EXHAUST GRILLE 18x18 16X16 651-1000 22 TITUS 350FL
9:05:21 AM
m oraja

CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11


1 2 *** Support Value Engineering - It Pays *** 4 5
1 2 *** Safety Pays *** 4 5

PUMP SCHEDULE DOOR AIR CURTAIN SCHEDULE (TRAINING BUILDING)


US Army Corps
of Engineers
BASIS OF DESIGN MOTOR BASIS OF DESIGN MOTOR
LOUISVILLE DISTRICT
APPROX
MARK MARK
LOCATION SERVES MFR MODEL TYPE GPM TOTAL EFFICIENCY RPM OPERATING REMARKS LOCATION SERVES MAX MAX WEIGHT REMARKS
NO HP V PH HZ NO HP V PH HZ FLA
NO. HEAD WEIGHT MANUFACTURER MODEL CFM FPM LBS

Appr.
(FT) (LBS)

HWP SERIES
ARC ARC HEATING DAC TRAINING BUILDING FURNISH WITH WALL MOUNTED CONTROL

Date
1A B&G 90 INLINE 48 30 45% 1750 1 480 3 60 25 2 KITCHEN MARS 48C 1700 1700 .5 120 1 60 9.8 -
HOT WATER 1 KITCHEN PANEL WITH MICROSWITCH.
1-1/2A
HWP SERIES
ARC ARC HEATING
1B B&G 90 INLINE 48 30 45% 1750 1 480 3 60 25 2
HOT WATER
1-1/2A
SERIES
HWP ARC HEATING
ARC B&G 80 SC INLINE 74 70 55% 1750 5 480 3 60 75 2 3
2A
D
HOT WATER
2X2X9-1/2 EXPANSION TANK SCHEDULE
SERIES
HWP ARC HEATING
ARC B&G 80 SC INLINE 74 70 55% 1750 5 480 3 1 2
2B HOT WATER 60 75 3
2X2X9-1/2 BASIS OF DESIGN DIMENSION
MAX MAX
HWP ARC ARC HEATING SERIES OPERATING OPERATING
B&G INLINE 30 100 45% 3500 2 480 3 60 50 2 MARK LOCATION SERVICE MFR. MODEL TYPE VOLUME
- ACCEPTANCE OPERATING REMARKS
3 HOT WATER 1535-356 PRESSURE TEMPERATURE
NO. NO. (GAL) VOLUME (GAL) HEIGHT DIAMETER WEIGHT
(PSIG) ^F
(IN) (IN) (LBS)
HWP ARC HEATING SERIES
ARC B&G INLINE 18 30 40% 3250 0.4 120 1 60 25 2
4 HOT WATER PL-55
ET MECHANICAL ARC VERTICAL 2000
B&G D-260V 159 56 125 200 58 30 1 2 3 4 5 6 7 8 9 10 11
1 ROOM B-1,2 BLADDER
ARC HEATING SERIES

on
HWP
B&G INLINE 18 30 25

pti
ARC 40% 3250 0.4 120 1 60 1 2
5 HOT WATER PL-55

Descri
ET MECHANICAL ARC VERTICAL 300
B&G D-40V 21.7 11.3 125 200 30 17 1 2 3 4 5 6 7 8 9 10 11
SERIES 2 ROOM B-1,2 BLADDER
HWP MECH RM
OMS B&G 80 INLINE 22 30 50% 1750 1 480 3 60 50 2
6A OMS
1-1/2X1-1/2X7B ET MECHANICAL ARC VERTICAL 5000 - 7 8 9
B&G PTA-455 370 240.5 125 200 82 48 1 2 3 4 5 6 10 11
SERIES 3 ROOM B-1,2 BLADDER
HWP MECH RM
OMS B&G 80 INLINE 22 30 50% 1750 1 480 3 60 2
6B OMS 50 1
1-1/2X1-1/2X7B ET MECHANICAL OMS VERTICAL 300 - 7 8 9
B&G D-40V 21.7 8 125 200 30 17 1 2 3 4 5 6 10 11
4 ROOM B-3,4 BLADDER
HWP MECH RM SERIES90
OMS B&G INLINE 35 70 45% 3450 3 480 3 60 2 3
7A OMS 50
1-1/2 AA MECHANICAL OMS VERTICAL
ET 200 - 7 8 9
1 2 3 4 5 6
B&G D-20V 10.9 2.4 125 200 26 12 10 11
HWP MECH RM 5 ROOM B-3,4 BLADDER
OMS B&G SERIES90 INLINE 35 70 45% 3450 3 480 3 60 50 1 2 3
7B OMS 1-1/2 AA
1 30% PROPYLENE GLYCOL 4 PROVIDE SIGHT GLASS 7 PROVIDE WITH AUTOMATIC AIR VENT 10 PROVIDE WITH SEISMIC RESTRAINTS
1 STAND BY 2 MOTOR STARTER, CONTROLS, HOA, INDICATOR LIGHTS AND SELECTOR SWITCHES FURNISHED AS PART OF FACTORY PUMP CONTROL PANEL WITH DISCONNECT AND INSTALLED BY ELECTRICAL 3 PROVIDE VFD
2 PER ASME SECTION VIII DIVISION 1 STANDARDS 5 FURNISH WITH AIR RELEASE FITTING AND LEVEL GAGE 8 PROVIDE WITH AIR PURGER 11 PROVIDE 18" CLEARANCE FOR SYSTEM PIPING

3 PEPLACEABLE BLADDER DESIGN 6 FACTORY PRE-CHARGED TO 12 PSIG 9 PROVIDE WITH LIFTING RING

HEATING HOT WATER BOILER SCHEDULE

Mark
BASIS OF DESIGN MIN. CAPACITY OPERATING
CHEMICAL POT FEEDER

Appr.
ASME POWER OPERATING
(MBH) 1 TEMPERATURE
MARK TYPE EFF.
LOCATION MFR MODEL PRESSURE GPM PD WEIGHT REMARKS
NO (AFUE) BASIS OF DESIGN
NO. RATING OUTPUT EWT LWT (FT) (LBS) MAX

Date
INPUT V PH HZ
(PSIG) (GROSS) FILL OPERATING
^F ^F OPERATING
MARK LOCATION SERVICE MFR. MODEL CAPACITY CAPACITY PRESS NOZZLE SIZE REMARKS
TEMPERATURE
B ARC NO. NO. (GAL) (GAL) (PSIG) (IN)
BURNHAM ALP 500 CONDENSING 125 95% 500 399 160 ^F 180 ^F 48 5 120 1 60 700 1 2 3 4 5 6 7 ^F
1,2 MECH. RM
C
CPF MECHANICAL HEATING HOT
B OMS CONDENSING J.L.WINGERT HP-5-ASME 5.0 6.3 200 200 3/4
BURNHAM ALP 285 125 95% 285 220 160 ^F 180 ^F 22 5 120 1 60 400 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
3,4 ROOM WATER
MECH RM

1 RATINGS AT 4000 FEET ASL 2 PROVIDE MANUFACTURERS SEALED STAINLESS STEEL FLUE/COMBUSTION AIR KIT 3 STACKABLE UNITS WITH MOUNTING FRAME 4 FULLY MODULATING 5:1 TURN DOWN

5 BOILER CONTROL PANEL 6 STAINLESS STEEL HEAT EXCHANGER 7 PROVIDE NEOPRENE RUBBER ISOLATION PAD

1 30% PROPYLENE GLYCOL 5 PROVIDE WITH 1/4" NPT AIR RELEASE VALVE

AIR / DIRT SEPARATOR TANK SCHEDULE 2 ASME CODE RATED 6 PROVIDE WITH 1/4" NPT PRESSURE GAUGE

3 DOME BOTTOM WITH SUPPORT LEGS 7 PROVIDE WITH SIGHT LEVEL AND SIGHT FLOW INDICATOR

on
pti
4 STEEL CONSTRUCTION WITH INTERNAL/EXTERNAL EPOXY COATING

Descri
BASIS OF DESIGN
MAX MAX OPERATING REMARKS
MARK OPERATING OPERATING WEIGHT
LOCATION SERVES MFR. MODEL GPM
NO PRESSURE TEMPERATURE (LBS)
NO.
(PSIG) ^F
GLYCOL MAKE-UP UNIT
AS MECHANICAL ARC
B&G RL-3F 96 125 270 160 1 2 3
1 ROOM B-1,2
BASIS OF DESIGN PRESSURE

AS MECHANICAL ARC
B&G EAS-2" 30 125 270 100 1 2 3 MARK LOCATION SERVICE MFR. MODEL CAPACITY REMARKS
2 ROOM B-1,2
NO. NO. CUT-IN CUT-OUT
(PSIG) (PSIG)
AS MECHANICAL OMS
B&G EAS-2" 40 125 270 100 1 2 3
3 ROOM B-3,4 ARC
GFA HEATING HOT
MECHANICAL B&G GMU-30 5 GPM/10GPM 10-45 20-50 1 2 3 4 5 6
1 WATER
AS MECHANICAL OMS ROOM 55 GAL
B&G EAS-1" 3 125 270 50 1 2 3
4 ROOM B-3,4 OMS
GFA HEATING HOT
MECHANICAL B&G GMU-30 5 GPM/10GPM 10-45 20-50 1 2 3 4 5 6
2 WATER
1 PROVIDE WITH STRAINER, HIGH CAPACITY AIR VENT FITTING AND MANUAL BLOWDOWN VALVE. 2 30% PROPYLENE GLYCOL 3 ASME 125 PSIG RATED ROOM 55 GAL

1 PROVIDE WITH (1) 1/2 HP MOTOR PUMP, 115V/1PH/60HZ, NEMA 4X CONTROL PANEL 4 PRV, SHUT-OFF VALVES, PRESSURE SWITCHES AND GAUGES 6 FOR PROPYLENE GLYCOL

Mark
HOT WATER UNIT HEATER SCHEDULE 2 LOW LEVEL FLOAT SWITCH 5 DISCONNECT BY ELECTRICAL. REFER TO ELECTRICAL DWGS

3 POLYETHYLENE TANK WITH CARBON STEEL STAND

dgn
6010.
Rev.

7/22/2011
BASIS OF DESIGN HOT WATER COIL ELECTRICAL

W 912QR-11-R-0071

e nam e:LCARC_M -
MARK CEILING FAN SCHEDULE

on No.

e:NONE
F-171-40-160
Project Code:
LOCATION PRESS WEIGHT REMARKS
B NO TYPE CFM EAT EWT LWT GPM
DROP HP V PH HZ (LB)
MANUFACT. MODEL ^F ^F

tati

ot date:

ot scal
11
(FT)

ci
28-
Date:

i
BASIS OF DESIGN ELECTRICAL

Sol
07-

l
WALL

Pl

Pl
Fi
UH ARC
1 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3 MARK SERVES BLADE WEIGHT REMARKS

C.KORPASH
UNIT STORAGE
PROPELLER NO SIZE VOLT PH HZ WATTS

Ckd by:
WALL MANUFACT. MODEL
UH ARC
2 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3

tted by:
UNIT STORAGE

ewed by:
gned by:
PROPELLER SEE OFFICE /
WALL ARCH MODERN FAN CIRRUS HUGGER CLASSROOMS 36" 115 1 60 85 50 1 2 3 5 6 7

.FRANCO
UH

Dwn by:
ARC

M .BETZ
A.REED

A.REED

Subm i
3 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3 RCP /

Revi
Desi
UNIT STORAGE
PROPELLER SEE

I
UH ARC WALL ARCH MODERN FAN CIRRUS HUGGER ASSEMBLY 52" 115 1 60 85 1 2 3 4
50
MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3

NEERS
4 UNIT STORAGE RCP
PROPELLER
1 BRUSHED ALUMINUM BODY AND BLADES 2 FAN SPEED CONTROLLER, WALL MOUNTED 3 CEILING MOUNTED BRACKET, HUGGER STYLE FAN 4 (1) ONE CEILING FAN LOCATED IN THE CENTER OF ASSEMBLY ROOM A102
WALL

CORPS OF ENGI
UH
ARC 5 (3) THREE CEILING FANS LOCATED IN THE LOWER CEILING OF ASSEMBLY ROOM A102 6 (2) TWO CEILING FANS LOCATED IN EACH CLASSROOM A134 & A131 7 (2) TWO CEILING FANS LOCATED IN THE PHYSICAL READINESS ROOM A126

LLE,KENTUCKY
5 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3

CT

FAX (714) 327-1601


UNIT STORAGE

STRI

TE 800
PROPELLER

A 92707
WALL

VE,SUI
UH ARC

LLE DI
MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 DEHUMIDIFIER SCHEDULE

FORNI
6 1 2 3

HUTTON CENTRE DRI


UNIT STORAGE

SANTA ANA, CALI


PROPELLER

SVI

TEL (714) 327-1600


SVI
UH ARC
MODINE VERTICAL 950 60 180 160 3.1 0.6 1/30 120 1 60 50 1 2 3

LOUI
V-42

U.S.ARMY
7

LOUI
UNIT STORAGE BASIS OF DESIGN ELECTRICAL

4
WATER
MARK REMOVAL
UH ARC CFM WEIGHT REMARKS
8 MODINE V-42 VERTICAL 950 60 180 160 3.1 0.6 1/30 120 1 60 50 1 2 3 NO PINTS/DAY VOLT PH HZ KW
UNIT STORAGE MANUFACT. MODEL

UH WALL
ARC
ng\gbna\m oraja\dm s97636\LCARC_M-6010.dgn

9 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3
MECHANICAL RM DH
PROPELLER THERMA-STOR HI-E DRY 195 190 540 115 1 60 1.25 110 1 2 3
1
UH WALL
ARC
10 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3
ELECTRICAL RM 1 6FT POWER CORD 2 3 INTERNAL CONDENSATE PUMP
PROPELLER

RESERVE CENTER

CO
UH WALL
OMS

MEXI
11 MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3
MECHANICAL RM
PROPELLER KITCHEN SUPPLY FAN MAKE-UP AIR UNIT SCHEDULE
WALL
UH OMS
MODINE HC-18 MOUNT 340 60 180 160 1.3 0.5 1/60 120 1 60 20 1 2 3

SCHEDULES
LAS CRUCES,NEW
12 ELECTRICAL RM
PROPELLER
BASIS OF DESIGN ELECTRIC HEATER EVAPORATIVE COOLING FAN MOTOR ELECTRICAL DATA
A EXTERNAL APPROX
1 PROVIDE MOUNTING BRACKET 2 30% PROPYLENE GLYCOL 3 RATINGS AT 4000 FEET ASL MARK MAX FAN
LOCATION SERVES CFM SP DRIVE EAT LAT KW LAT TYPE GPM WEIGHT REMARKS
NO RPM
MANUFACTURER MODEL ^F ^F HP RPM V PH HZ

U.S.ARMY
(IN. (#STAGES) LBS
WG)
GAS DETECTOR SCHEDULE
KSF TRAINING BUILDING 12 DIRECT
c:\pwworki

GREENHECK MSX109H12 GREASE HOOD 1600 0.4 BELT 905 18 55 73^F 4 3/4 1750 480 3 60 1000 1 2 3 4 5 6
7/22/2011

1-1 KITCHEN (3) CELDEK


BASIS OF DESIGN
ALARMS POWER
DETECTED
MARK
LOCATION MFR MODEL REMARKS
GASES
NO
NO.
LOW LEVEL HIGH LEVEL V PH HZ