You are on page 1of 62

NFPA 13 2016 and NFPA 25

2017 Edition Standard Updates


Karl Wiegand, PE
Technical Education and Research Engineer

Rochester, NY
April 24, 2018
Program Agenda

• NFPA 13
– Chapter 6 and 7
– Chapter 8
– Design
– Storage

• NFPA 25
– General Changes
– General Requirements
– Sprinkler Systems
– Comment Components and Valves
Chapter 6 and 7 (NFPA 13)

• Replacement sprinklers
• Air vents
Replacement Sprinklers (NFPA 13)

• Once a sprinkler is removed from a


system it must be replaced – new 2013
• Dry sprinklers can be reused per
manufacturer’s instructions – new 2016
• If a sprinkler drop is taken out and the
sprinkler left in the drop it can be reused
again - loophole
Air Vents (NFPA 13)

• Single air vent


– ½ in manual valve
– Automatic air vent
– Other approved means
• Near a high point in the system
• Wet systems using metallic piping
• Location on general information sign
Chapter 8 (NFPA 13)

• Sprinklers with QR and SR ratings


• Obstruction rules for columns
• Residential sprinkler maximum ceiling height and slope
• Small openings
• Cloud ceilings
• Alternative fire rated window assembly
• Miscellaneous
Sprinklers with QR and SR Listings (NFPA 13)

• Extended coverage sprinklers


• They can be installed in a space without
separation when they are in configurations
where they are both QR and SR
• They can be installed in light hazard in
spaces when they are in their SR listed
spacings
Obstruction Rules for Columns (NFPA 13)

• “3 times rule”
• “4 times rule”
• The maximum dimension doesn’t work
– 24 inches for 3 times
– 36 inches for 4 times
Residential Sprinkler Maximum Ceiling Height and Slope
(NFPA 13)

• 24 ft ceiling height
• 8 in 12 slope
Small Openings (NFPA 13)

• Small openings type 1


– 20 percent of ceiling
– If length is greater than 4 feet then width is 8
inches or less
• Small openings type 2
– 20 percent of ceiling
– Meet the cloud ceiling requirements
Cloud Ceilings (NFPA 13)

• Cloud spacing
• Spacing
requirements
• Irregular shaped
clouds
Cloud Spacing (NFPA 13)

Ceiling Cloud Maximum area Maximum area Maximum area


Minimum width (sqft) opening (sqft) opening (sqft) opening
dimension (ft) width ≤0.5 in/ft of width ≤0.75 in/ft of width ≤1 in/ft of
ceiling height ceiling height ceiling height
2 - <2.5 175 70 NP
2.5 – 4 225 120 70
>4 225 150 150
Spacing Requirements (NFPA 13)

• Maximum cloud ceiling height: 20 ft


• Maximum spacing and design area as per
LH and OH tables
– 15 foot spacing
– 225 sqft maximum spacing in LH
– 130 sqft maximum spacing in OH
– Not greater than permitted by the table
Irregular Shaped Clouds (NFPA 13)

• Width dimension of
the cloud is the
smallest width
dimension of the
cloud
• Gap width is the
maximum gap size
Alternate Fire Rated Window Assembly (NFPA 13)

• Wet-pipe system
• Heat-strengthened, tempered, glass
ceramic glazing
• Protected on both sides by sprinklers
• Non-load-bearing
• No horizontal members
• Water duration equal to fire rating
Sprinklers for Alternate Fire Rated Window Assembly
(NFPA 13)

• Listed
• Standard spray as allowed by building
code (IBC 404.6)
• Standard spray as allowed by AHJ
Design (NFPA 13)

• Residential small room rule


• Replacement residential sprinklers
Replacement Residential Sprinklers (NFPA 13)

• Prior to 2003 residential density was 0.03


gpm/sqft
• Prior to 2016: replacement residential
sprinklers or recalculate system to current
requirements
• 2016: Sprinklers ± 5% of K factor
Storage (NFPA 13)

• Bumping to group A plastic design


• Alternate protection
• Solid shelf storage
• Exposed expanded plastics
Bumping to Group A (NFPA 13)

• Group A plastic can be used to protect


class I through IV commodities
• This actually allows a reduction in density
in some situations
– Encapsulated I-III causes a 25 percent
density increase
– Encapsulated IV causes a 50 percent density
increase
Alternate Storage Protection (NFPA 13)

• Sectioning off an area and protecting it


from within the rack instead of protecting it
from the ceiling
• “Where commodities require greater
protection than available at the ceiling”
• Can be used for class I through IV as well
as group A plastics
Interaction With Adjacent Commodity (NFPA 13)

• Horizontal
– Provide alternative protection for one pallet
beyond where higher class commodity is
being protected or
– Provide vertical barriers
• Vertical
– Commodities not requiring the higher class of
protection can be stacked above the higher
class commodity
Protection Requirements (NFPA 13)

• Solid horizontal barriers


– Every tier of storage for solid shelf
– Not greater than 12 ft for open frame
– Cover all flue spaces
– 3 inch gaps allowed in barriers at uprights, rack
members and equipment
– 3/8th inch plywood or 22 gauge sheet metal
• Sprinklers
– QR K 8.0 or larger
– Close to the barrier
– Protection schemes differ depending on rack
Single Row Rack (NFPA 13)
Double Row Rack (NFPA 13)
Multiple Row Rack (NFPA 13)
Hydraulic Design (NFPA 13)

• 60 gpm per sprinkler


• Single row racks – 6 remote
• Double and multiple row racks – 8 remote
Solid Shelf Storage (NFPA 13)

• ESFR and CMSA


– Sprinklers under every tier
• Solid shelves covering a portion of the
rack
– Sprinklers in the flue 4 ft beyond the shelf
– CMDA
• 20 to 64 ft^2 sprinklers every 6 ft vertical
• <64 ft^2 sprinklers under every tier
– ESFR and CMSA – sprinklers under every tier
Exposed Expanded Plastics (NFPA 13)

• K 25 ESFR intermediate temp sprinklers


• 12 sprinklers
– @30 psi or
– @60 psi
• 8 ft aisles
• Solid vertical barriers
Building and Storage Height (NFPA 13)

• 30 ft building with 25 ft of storage


– 30 psi
• 40 ft building with 25 ft of storage
– 60 psi
• 40 ft building with 35 ft of storage
– 60 psi
Solid Vertical Barriers (NFPA 13)

• Spaced maximum 16.5 ft


• Maximum of 124 ft^2 of storage between
barriers
• 4 inches above the floor to maximum height
• Across the longitudinal flue
• Commodity can extend 4 inches beyond the
barrier
• Barrier 3/8th plywood or 22 gauge sheet metal
General Changes (NFPA 25)

• New Change Markers


• Common Components and Valves
• ITM Frequency Tables
• Removing Unenforceable Language
• Seeing the Handbook
New Change Markers (NFPA 25)

• 2014 Edition and Prior

• 2017 Edition
Common Components and Valves (NFPA 25)

• Trim
• Valve components
• FDCs
• Backflow preventers
• Switches
ITM Frequency Tables (NFPA 25)

• Sections are alphabetical


• References to other chapters only site the
chapter number
Removing Unenforceable Language (NFPA 25)

• “In good condition”


• Instead
– Operable/operating correctly
– Free of physical damage
“Seeing the Handbook” (NFPA 25)
General Requirements (NFPA 25)

• Owner Requirements
• Building Evaluation
• Automated Inspection and Testing
• Performance Based Compliance
Owner Requirements (NFPA 25)

• Minimize water damage


• Correct or repair deficiencies or
impairments
Requirements for a Building Evaluation (NFPA 25)

• Occupancy changes such as converting office or


production space into warehousing
• Process or material changes such as metal stamping to
molded plastics
• Building revisions such as relocated walls, added
mezzanines, and ceilings added below sprinklers
• Removal of heating systems in spaces with piping
subject to freezing
• Changes to the storage method, arrangement, height or
commodities
• Changes in water supplies
Automated Inspection and Testing (NFPA 25)

• Performed in accordance with the standard


• Permitted to replace visual tests
• Automated equipment needs to produce the
same action required by the standard
• Testing frequencies of the standard must be
maintained
• Equipment needs to be listed
• Record of all tests maintained
Human Intervention (NFPA 25)

• Equipment needs to be observed


performing its tests or manual tests need
to be performed every three years
• Some tests may be required to be
monitored to intervene if necessary
Failure (NFPA 25)

• Failure of a component to pass an automated test will


result in an audible supervisory signal
• Failure of automated testing equipment that impairs the
system
– Supervisory signal
– Impairment procedure
• Failure of automated testing equipment that does not
impair the system
– Trouble signal
Changes to Systems (NFPA 25)

• Vane-type water flow alarms tested by


smallest K-factor sprinkler in the system or
smaller
• Testing water flow accomplished by
opening inspector’s test valve or
automated test equipment
Performance-Based Compliance (NFPA 25)

• Clear identifiable goals


• Goals and goal achievement reviewed and
adjusted every three years
• History available to the AHJ
Performance-Based Compliance (NFPA 25)

• Building criticality
• Consequences of maloperation
– Loss and damage
– Business interruption
– Hazard to fire fighters
– Impact on adjacent buildings
– Economic impact
• How acceptable is a failure?
Sprinkler Systems (NFPA 25)

• Replacing sprinklers
• Replacing escutcheons
• Replacing residential sprinklers
• Antifreeze
• Miscellaneous
Replacing Sprinklers (NFPA 25)

• Location of corrosion
– Lightly loaded or limited corrosion
• Sprinkler operations in facilities without a
fire occurring
• Glass bulb sprinklers exposed to sunlight
or in freezers
Recessed Escutcheons and Cover Plates (NFPA 25)

• Need to be replaced when missing


• Replacement needs to be the listed
replacement
• If not available the whole assembly needs
to be replaced
Residential Sprinklers (NFPA 25)

• Current residential sprinklers can used to


replace old residential sprinklers
• K-factor within 5 percent
Antifreeze (NFPA 25)

• Sign – type, brand, concentration (by


volume), volume (chapter 4)
• TIA language incorporated
• Specific section requirements sited
– “Step 1”, “acceptable solution” “permitted by NFPA 25”

• Wording for triggering deterministic risk


assessment
Miscellaneous (NFPA 25)

• Hangers and Braces


– “Seismic” removed
– “Supports” added

• Sign Inspection Frequency


– Annual - hydraulic design information sign was quarterly

• 20 Sprinkler ITM
– Table 5.5.1 was fixed to address 20 sprinklers being affected by
adjustment or replacement
Common Components and Valves (NFPA 25)

• Supervisory Signal Devices


• Control Valves
• Alarm Valve Inspection
• Dry Valves
• PRV Testing
• FDC
• Miscellaneous
Supervisory Signal Devices (NFPA 25)

• Not including valve supervisory switches


• Inspected quarterly
• Tested annually
Control Valves (NFPA 25)

• Inspected quarterly when electronically


supervised
• Valve status test when valve is closed and
reopened
Alarm Valve Inspection (NFPA 25)

• Externally inspected quarterly


• Trim also free of damage
Dry Valves (NFPA 25)

• Record valve tripping time


• Record water transit time
PRV Testing (NFPA 25)

• 2014 Edition:
– A.13.5.1.2 The sectional drain valve should
be opened to compare the results with the
original installation or acceptance tests.
• 2017 Edition:
– A.13.5.1.2 The sectional drain valve should
be opened to compare the results with the
original installation or acceptance tests.
FDC (NFPA 25)

• Quarterly inspection
– Visible piping is undamaged
• Annual interior inspection
– When locking caps or plugs are installed
Miscellaneous (NFPA 25)

• Preaction and Deluge Valves


• Electrically connected water based
protection system initiating device
supervisory alarms
• Air Compressors
Questions For You

• Can sprinklers that have been removed from a sprinkler system be


reinstalled?
• What are the requirements for replacing 0.03 gpm/sqft density
residential sprinklers?
What is the largest percent of a ceiling that can be an opening while
still being considered a small opening?
• What needs to occur if there is a change to storage commodities in
a building?
• When automated inspection and testing is used to maintain a
system how frequently must the testing be observed or manual
testing be performed?
Questions?
Karl Wiegand, P.E.
karl@globesprinkler.com
(989)846-4583 ex 215
(914) 447-8484

You might also like