AN ICON OF THE FUTURE
SYSTEM OVERVIEW
NORD
PLC
AN ICON OF THE FUTURE
Messung Systems, a leading pioneer in indigenous PLC in India, has constantly innovated to achieve global
standards in designing and manufacturing PLC products. With pride, it has now launched a high performance
series of world class CPUs viz. Nexgen 5000; coupled with basic building blocks of its earlier launched and
established Nexgen 4000 PLC. This Nexgen 5000 PLC family offers a wide range of CPU variants, with
IEC 61131-3 compatibility, having performance excellence and Windows® based programming software.
In the earlier days of industrial automation, application specific machines or process plants were designed with
huge control panels having Relay Contactor Logic and Hardware Timers, Counters, Thumbwheels. These were
very bulky in size, complex for fault finding, less reliable with limited and unpredictable life. Similarly these
systems were very rigid in terms of any up-gradation.
This has evolved concept of Programmable Logic Controllers (PLC) which were compact in size, having better
edge over earlier electro-mechanical devices. PLC implementation has resulted in several benefits like:
minimized panel and wiring volume, expedited program development, reliability of operations with an improved
life, PLC re-usability across the applications (conditionally), easy and quick fault finding, and ease of interface
with HMIs, SCADA like external devices.
Over the time, only application specific hardware and software products were developed by various vendors,
which addressed the problem of compatibility and portability. This has initiated necessity of products
standardization in terms of hardware as well as software.
Similarly, with the growing Industrial Automation, industry has started facing typical problems of PLC
processing speed, memory, handling of a complex or very big program, logic re-usability, avoiding
duplicate variables in programming, choice of programming language selection as per application, user
friendly software along with documentation, standardized program interface.
Subsequently, International Electro-technical Commission worked upon complete design of PLC, which
comprised of hardware design, installation, testing, programming and documentation. Several inputs from
various machine manufacturers, end-users and research institutes has evolved five part IEC 61131 standard.
This international standard IEC 61131-3 is the first substantial endeavor to standardize programming languages
for industrial automation. It emphasizes on consistent method of PLC programming which encourages the
development of quality software. IEC 61131-3 provides tools to improve intrinsic quality of software in terms of its
persistent correctness, integrity, reliability, robustness, modularity, flexibility and safety. It also deals with
programming, installation and maintenance phases of software development projects in industrial control.
Nexgen 5000 series of CPU family is programmed with CoDeSys, the Windows® based, IEC 61131-3
compatible programming software.
1
NEXGEN 5000 PLC : AN ICON OF THE FUTURE Max. 32
A truly
l modular PLC modules
NEXGEN
More
l I/O Capacity - 1024 Inputs / 1024 Outputs
Enhanced
l Data Memory - 160 KB
64 KB - Data Memory (Selectively retainable)
32 KB - Marker Memory (Selectively retainable)
64 KB - File Marker Memory (Super retainable)
Better
l processing speed - Boolean - 0.4 µsec max.
Word - 1.2 µsec upto
9 mtrs.
Higher
l program memory -
Application Program Code - 256 KB
Application Source Code - 1 MB
Wide
l assortment of Analog modules - Thermocouple,
RTD, Fast Analog Input and Output Modules
Highlights :
User
l has an optional choice of pluggable keyboard display
It has
l built-in freely programmable 6 functions keys &
4 character alphanumeric display
The keyboard
l display can be used as a self diagnostic tool.
This is helpful for assistance in :
Displaying
n fault messages
Displaying
n systems messages
Viewing
n / modifying PLC variables
Redirection
n of Digital I/O points
2
The display and keyboard are freely programmable for application specific functionality. Display
l
and keyboard is accessible in the application program through the system variables. Using these
system variables, the user can develop their own function blocks to handle display and keypad as
per the application need.
Standard FB library for I/O/M Monitoring, Redirection of Digital I/O points are also available.
l
The Keyboard Display Unit can be fixed to / removed from,
l the Processor module during the
module powered ON condition.
Bootstrap
Loader Tool / CoDeSys
Memory PC COM
Cassette Programming cable 9910 Port
Cassette adapter
30 VAC to 5 VDC
power supply
5 VDC Power supply
3
IEC 61131-3 : A GLOBAL STANDARD
Better Structuring of large programs
l
High Reusability
l
Combination of ladder program and high level programming language
l
ST : Structured Text
l
FBD : Function Block
l
Diagram
IL : Instruction List
l
SFC : Sequential
l
Function Chart
CFC : Continuous
l
Function Chart
LD : Ladder Diagram
FBD :
Function
Block Diagram
4
REMOTE PROGRAMMING VIA MODEM
PSTN
Network PC
Port - 1,
RS-232 C CoDeSys
PC2 PC1
In this setup, the programming software 'CoDeSys' is running on PC1 and the gateway server is
running on PC 2. The link between CoDeSys & Gateway Server is established via TCP/IP bus. The
Nexgen-5000 PLC is connected to COM port of PC2, the link between Gateway Server & PLC is
established via RS-232 bus. Or otherwise the PC2 can be directly interfaced with PLC via
programming cable.
5
MODBUS CONNECTIVITY MADE EASIER
MODBUS MASTER
Master
Master : Nexgen 5000 PLC
Slave : Enercon Energy Meter
P : Port - 2 / 3, RS 485
Network having 31 nos. of Enercon Energy Meters as slave connected to one Master Nexgen-522x / 523x CPU, using MODBUS Master.
Master FB : This FB handles serial communication with MODBUS RTU Protocol as master device. It is
useful to interface HMI, SCADA as a slave with Nexgen 5000 PLC. PLC communication can be
established with one PLC as Master and other(s) as slave(s). It can also be used to have CPU as data
logger to collect the data from Energy meters, VFDs etc.
Highlights :
User need not know the MODBUS protocol.
l
Protocol implementation is physical layer independent i.e. it can be used with RS232C, RS422 or
l
RS485.
Communicates with any third party MODBUS RTU slaves inclusive of Messung PLCs with the
l
MODBUS RTU_Slave FB
Easy interface with various SCADA and HMI packages as slaves is possible with appropriate FBs. No
l
need to develop any special driver.
Easy connection to multiple Beijer E-terminals with it's MODBUS Slave driver
l
Easy application interface by defining data exchange records with various stations
l
Allows exchanging data via I, Q and M devices in Nexgen 5000 with MODBUS devices in various
l
stations
Data exchange records can be grouped and called in manual, auto-cyclic and super cyclic modes.
l
Flexibility in data exchange records programming.
l
Programmable Retry and Time-out facility if a station fails to respond.
l
Supports variety of baud rates to suit the application needs.
l
6
These FBs are useful -
To interface Beijer make E terminals as master or slave with MODBUS RTU Driver.
l
To interface any SCADA software as master or slave which supports MODBUS RTU protocol.
l
For PLC to PLC communication in Nexgen 5000 PLC. One PLC can be a Master PLC and other/s can
l
be slave/s.
Master
Master : Nexgen 5000 PLC
Slave : Nexgen 5000 PLC
OR P : Port - 2 / 3, RS 485
P
P P P
Converter for
RS 232C to RS 485
Network having 31 Nos. of Nexgen 522x / 523x PLCs as slave connected to one Master Nexgen 522x / 523x CPU, using MODBUS Master
and MODBUS Slave.
MODBUS Slave FB :
It emulates MODBUS slave functionality. This FB handles serial communication with MODBUS RTU
Protocol as slave device. The RTU slave FB is useful to communicate with any external master PLC,
SCADA or DCS systems. Communication speed can be up to 56Kbps.
Highlights :
User need not know the MODBUS protocol
l
Protocol implementation is physical layer independent i.e. it can be used with RS232C, RS422 or
l
RS485.
Communicates with any third party MODBUS RTU master or Messung PLC with MODBUS
l
RTU_Master FB Easy connection to various SCADA and HMI packages. No need to develop any
special driver.
Easy connection to Beijer E-terminals with it's MODBUS Master driver
l
Allows to exchange data via I, Q and M devices in Nexgen.
l
Ready to use FB with few parameters to define to go
l
Flexibility in station number programming.
l
Supports variety of baud rates to suit the application needs.
l
8 7
DATA EXCHANGE VIA MODEM
PLC 2
Dial-up modem
Dial-up modem
PSTN
PLC 3 Network
PC
SCADA package with
SCADA protocol driver and
modem connectivity
Dial-up modem
Dial-up modem
Multiple PLCs can be connected to PSTN network via modem. Multiple PLCs can communicate with one
or more PC/PLC at a time through modem. Either of PLC / PC or both can initiate a communication.
Once the communication is established, Protocol FB like MODBUS, Nexgen or Micro can take over a
control for Data Exchange.
PLC 1
PLC initiates a call via modem FB. Now, modem FBs establish a communication between any of the two
Nexgen-522x / 523x PLCs ( As shown in above figure ). Once the connection is established, the control
is passed to protocol FBs like MODBUS, Nexgen protocol.
The calling line / connection status can be monitored and failure of the link can be detected. In case of
lines getting busy or unreachable auto redial, auto retry is possible. Dial-In facility with auto connect
modems & Dial-Out predefined number is also feasible. Various communication speeds can be gained
based on line conditions. Connect, Initialize and Hang-up sequence for the modem can be also
controlled.
Nexgen-522x / 523x PLC, which initiates a call will implement Dial-Out FB. While PLC at other
end i.e.the responding PLC, will implement Dial-In FB.
Note : The calling PLC ( i.e. PLC which has initiated a communication call ) can be a Master or Slave.
8
CONVENIENT FAULT MESSAGE ALERT
User can be alerted, on occurrence of faults, by :
Sending SMS ( using GSM Modem ), Numeric Message or Mobile Ring Alert ( using dial-up Modem )
PLC : Nexgen 5000 with CPU 522x / 523x PLC : Nexgen 5000 with CPU 522x / 523x
P : Port 1 / 2 / 3 , RS-232C P : Port 1 / 2 / 3 , RS-232C
Numeric
Message
P PSTN P
Network
Dial-up modem
GSM modem
with SIM card
Dial up modem connected to Nexgen 5000 CPU , sends GSM modem connected to Nexgen 5000 CPU, sends
Numeric Messages on pager, or only Ring Alert on mobile. SMS (text messages )
Patch Panel
4960 / 4962
9
CPU 522x - P4 : 2 ch HSC + 2 ch PTO + Z Interrupt I/Ps
CPU 523x - P4 : 2 ch HSC + 2 ch PTO + Z Interrupt I/Ps
There are two variants in the patch panel
a. PNP type ( 4960 ) : The output of PTO is PNP type & can be interfaced to 24V signal level.
b. Differential type ( 4962) : The output of PTO is differential type & can be interfaced to
Rs422 differential signal level
HSC-PTO Function Library :
Nexgen 5000 CPU provides 2 channels of HSC I/P and 2 channels of PTO O/P. To handle these
hardware resources the OS of Nexgen 5000 CPU supports external FB library PTO lib.
MC-MoveAbsolute
HSC MC-MoveRelative Analog
MFIP MC-MoveVelocity Out
Axis1 MC-Stop
Analog MC-ReadActualPosition
MC-ReadParameter PWM
Pot MC-ReadBoolParameter
Data Data
In MC-WriteParameter Out
MC-WriteBoolParameter
PTO PTO
MC-MoveHome
Under Development
Axis2 2 Axis_Interpolation
Electronic_Gearing
CANbus Phasing CANbus
CAM_Control
Its based on PLC open motion control FB guidelines. It's a universal method of motion control
irrespective of front-end interface.
10
NEXGEN SLAVE
Nexgen slave FB is provided in FB library. By defining input parameters of FB, user can select
communication port and communication parameters to establish communication with HMI. This FB
handles serial communication with Nexgen 5000 as slave device and interfaces HMI, SCADA as a
Master.
This FB is useful to interface -
Sr Jr
Messung make HMIs SMARTLINE and SMARTLINE
l
Beijer make E terminals with NEXGEN 4000 Driver
l
SCADA software which supports Nexgen protocol
l
Slave
Network having 31 Micro PLCs (XMP81x Series i.e. XMP-8 11/12/13/15/16/17) are connected to a Master Nexgen 5000 PLC, where PLC
implements XMP8_10 Master block.
Here, 31 Micro PLCs are networked with one master, where master can be :
- Nexgen 5000 PLC using RS 485 port
- PC with SCADA
Here, FB used is XMP8_10Master.
11
VARIABLE FREQUENCY DRIVES IN MUTIDROP
Nexgen 522x / 523x interfaced with Beijer HMI E-Terminal on 2'nd port and network of Mitsubishi make Inverter is interfaced with 3'rd port.
User need not know the Inverter interface protocol. It Reads/Writes data to multiple inverters.
l
It can have direct serial inverter control from user program
Transfer data to central SCADA / HMI on other port
l
Extendible to serial connection up to 31 inverters
l
Fast response to set point changes
l
Direct Inch, On/Off control
l
Cyclic updation of actual data from inverters
l
Individual Inverter Error handling
l
Automatic communication recovery as soon as Inverter is switched ON
l
Inverter data may be modified or controlled from HMI, SCADA or result of application program
l
Communication on 9.6K or 19.2K baud
l
Easy access to parameters via structured data for each inverter.
l
Support some On-demand command execution such as initialisations etc.
l
Predefined Parameters Handling (selectable)
l
- Write control : Start, Stop, Reset, Set Frequency.
- Read info : Frequency, Voltage, Current, Inv-status.
12
Automation of 'Two For One' (TFO) Twister
Induction motor rotate bobbins with constant speed. Servo controls the traverse movement. PLC generates Pulse Train Output
(PTO), with preset maximum speed. Traverse stroke is controlled from encoder feedback. High-speed counter controls
interrupt, which facilitates the accurate control of traverse stroke and direction reversal. HMI provides setting options and
machine status.
Machine Tools : SPMs for Welding, Drilling, Tapping, Grinding, Boring, Press, Die-casting,
Industrial Washing, Industrial Test Rigs, Axis Control applications, Cut to length etc.
Material Handling : Ash Handling, Coal Handling, Belt Conveyors, Electroplating Plants, Paint Shops,
‘ANDON’ Systems etc.
Plastics : Plastic Injection Moulding Machines, Blow Moulding, Extrusion, Sheet Line Lamination etc.
Textiles : TFO Twisters, Dyers & Jiggers, Winders, Sectional Warping Machines, Winders etc.
Pharmaceuticals : Sterilizers, Auto-clave, Liquid Injection, Lab Equipments-Chilers etc.
Packaging : FFS, Auger Filling, Coil Wrapping Machine
Food : Biscuit Making Lines, Ovens etc.
Utilities : DG Sets, Compressors, Energy Monitoring
13
Attributes Specifications Remarks
CPU 522x CPU 523x
Processor 16 bit Micro controller -
14
Attributes Specifications Remarks
CPU 522x CPU 523x
Project File
Application
Program POU Password Facility Read / Write Password available
Security Source Code
Uploading
Cyclic Available
Task Periodic Event -
Supported Available
Interrupt Event Available
Numbers Unlimited *
*Limited by available data memory.
Resolution 1 ms
Timers TON, TOFF, TP, RTC
Max. Range 24.855 Days Supported by user definable retentive
feature
Retentivity User Selectable
Numbers Unlimited *
*Limited by available data memory.
Max. Count 65536 CTD, CTU, CTUD
Counters
Retentivity User Selectable
Input points 1024 2048* * 1024 as local
I/O Capacity
Output points 1024 2048* *1024 as remote
6 Keys
Keyboard Keyboard & Display are programmable
Diagnostic User Configurable
Tools through an application program
Display 4 Character Alpha-numeric
Current
Consumption At 5V DC 600 mA -
15
Nexgen 523x : CPU Variants And Communication Ports
Nexgen 523x is advanced PLC core CPU backed by internationally accepted CANopen protocol. The CAN bus connectivity is built
in and any CANopen device having NMT slave capability can be interfaced with this CPU. Apart from controlling remote stations, it
has got capability to interface & control Local I/Os also.
1. V-
2. CAN_L
3. Shield
CP 5230-P4 CP 5230-B0 CP 5232-P4 CP 5232-B0
4. CAN_H
CPU with HSC PTO 1 port CPU CPU with HSC PTO 3 port CPU
5. V+
Ld
Node 1 Node n
Lt
According to DN specifications the power supply to the CAN interface must be connected via V+ and V- terminals. Power
supply rated at +24V must be with in range of +15V to +30V.
Termination resistance:
A 120-ohm terminating resistor must be fitted at each end of trunk line between CAN_L and CAN_H terminals. BOTH END
TERMINATIONS IS MUST.
16
Nexgen 522x : CPU Variants And Communication Ports
Nexgen 522x series itself has 6 CPU variants. This wide range of CPU empowers user to select a CPU as per application specific
requirement, with enhanced memory viz. feature wise as well as capacity wise.
The processor module supports three independent serial communication ports with well defined availability criteria as :
All the serial ports are provided on-board and are open for user to define communication parameters and handle serial
communication using function blocks as per requisite protocol.
The communication port-1 is RS 232C hardware interface port and it automatically gets assigned for programming through
programming software 'CoDeSys', if programming cable (having an ordering code 9910) is connected. Otherwise it is open for user
to define protocol and handle serial communication through application program. Port 1 is used to transfer an application program,
from memory cassette to PLC, when ever required.
The detailed pin configuration is illustrated in below diagram. For the communication port 1, 9-pin D male connector is provided on
the Processor module. The figure below shows front view of the connector.
Pin-1 provides carrier detection status when
5 modem is connected. This status is available in
GND : 5 9
9 : Modem Ring Indicator application program on activating
5V:4
8 : Reserved for programming PORT_STATUS. Pin-9 provides ring indicator
TxD : 3
7 : No Connection
RxD : 2
6 : No Connection
when modem is connected and if any controlling
Carrier Detect : 1 6 device is dialing. Pin-4 and Pin-5 provides 5 VDC*
1
Nexgen 522x / 523x : Port 1 and Ground, which is used for memory cassette
operation.
* This 5 V DC is strongly recommended only for restricted use. ( Not for driving the 5V DC operated external devices.)
17
Communication Port 2 and Port 3
Communication Port-2 and Port-3 are open for RS 232C/422/485 hardware interface. The signals are terminated on different pins
on 9 pin D connector. The processor module provides requisite hardware for serial interface. The operating system provides driver
functions and function blocks which directly controls the hardware interface. For a serial port, processor provides system buffer of
256 bytes each for reception and transmission. The relevant driver function blocks like Nexgen_Slave and RTU_Slave are
provided in the library Nexgen 522x.lib / 523x.lib.
For the communication ports 2 and port 3, 9-pin D male connectors are provided on the Processor module. The figure below
shows front view of the connector. The connections for both ports are identical.
5
GND : 5 9
9 : Rx+ (RS 422)
Tx+(RS 422) : 4
8 : Rx- (RS 422)
TxD (RS 232C) : 3
7 : Tx- (RS 422)
RxD (RS 232C) : 2
6 : No Connection
Carrier Detect (RS 232C) : 1 6
1
Nexgen 522x / 523x : Port 2 / 3
The detailed pin configuration is illustrated in above diagram. Pin-1 provides carrier detection status when modem is connected.
This status is available in application program on activating PORT_STATUS.
Instruction Execution
Nexgen 522x / 523x series CPUs are faster in execution, which makes it suitable for any sophisticated application, where
processing speed and computation matters. Nexgen 522x / 523x series CPUs are faster (about 30%) than 521x series. Due to
built -in optimization, it consumes 20 % less of Application Program Memory.
Execution Speed for Various Instructions and Data Types ( *Following Data is for CPU 522x )
Memory Configuration
Nexgen 522x / 523x series CPU has two on-board memory resources viz. RAM and Flash PROM. This is similar to Nexgen 521x,
but it has enhanced memory capacity and also has file marker memory.
RAM
Nexgen 522x series CPU has 256 KB RAM with battery back-up, where this is further enhanced to 320 KB in Nexgen 523x series
CPU. This has various memory components like Input process image, Output process image, Application program code memory,
Data memory, Marker memory, File marker memory and system variable memory.
18
Address Specifier In Size
Memory Type Application Program CPU : 522x CPU : 523x
Input Process Image %I 128 Bytes 256 Bytes
Marker Memory is used to store the intermediate results and stored at addressable global memory area, accessible to external
devices like HMI, SCADA.
File Marker Memory is the data memory, which needs to retain after a PLC cold start or even after program change. Thus it is used
to store the reciepe, history and data logged. This memory is accessible to user only by using specific functions and function blocks
in application program. It is possible to access the file marker area for external devices also via serial communication by
MODBUS_RTU and Nexgen protocol.
Data Memory is used to store the intermediate results like instances of function blocks and variables used in application program.
Unlike marker memory, data memory addressing is not handled by application developer, but these addresses are generated by
compiler. Hence data memory is not accessible to external devices like HMI and SCADA.
System Variables are implicitly global and used to exchange the information with PLC operating system and its functionalities.
Flash PROM
Nexgen 522x / 523x series CPU has 512 KB Flash PROM. This serves as on-board backup memory.
PLC run-time execution takes place through RAM only. PLC programming software downloads executable binary code in RAM
and the same is optionally transferred to Flash PROM, creating Boot Project.
Programming software (CoDeSys) facilitates user to select source code downloading option. Unless specified explicitly,
Executable Binary code will get transferred to RAM.
For every power ON operation, program gets transferred from Flash PROM to RAM. In case of no program in Flash PROM,
'MEMR' gets displayed on CPU Display.In case boot project is not created, RAM and Flash PROM will have two different programs.
On next power ON, this will cause copying of old program from Flash PROM to RAM.
During run-time, program executes from RAM. When on-line change in an application program occurs, modified application
program is transferred to additional memory space in RAM. During this download, PLC continues to execute the earlier program
from standard memory location of RAM. When downloading is completed, from immediate next scan, latest (modified) program
gets executed.
PLC programming software (CoDeSys) generates application program project file in a compressed format. This file gets
downloaded to Flash PROM as source code download occurs. This project file contains all project related data like ladder,
comments, variable name, variable declaration, password, libraries (optional).
19
Source Code Uploading
This uploads the complete project from CPU to PC. Here, password protection facilitates controlled access for uploading.
Battery Back Up
PLC variables are stored in RAM, which is of volatile nature, demands a battery backup to retain its contents. This battery also
serves as a backup to on-board RTC. Nexgen 522x / 523x CPUs use 3.6V Ni-MH (Nickel Metal Hydride) rechargeable battery,
which is mounted on board. The battery provides backup period around 6 months, from its fully charge status.
Optional pluggable keyboard display unit can be used as diagnostic tool. It provides 4-character alpha-numeric display with
6 keys keypad. This is helpful for:
Displaying
l fault messages Displaying
l system messages
Viewing
l / modifying PLC Variables Redirection
l of I/O points
Display and keypad are accessible to application program and its information is available in form of system variables. User
can develop customized function blocks to handle the display and keypad routines as per required by application.
_BKEYSTATUS is the system variable (byte). Its first six bits access corresponding to key of the keypad.
_ADISPLAY is the system variable (array of 4 bytes). Each byte represents an individual character of the alpha-numeric
display.
On-board Interrupt Inputs (Available with CPU 522x-P4 and CPU 523x-P4Only)
Industrial automation applications are ever demanding with increased level of sophistication. Especially real-time systems
demand flexible and configurable control over the execution of different parts of program, which can be in response to any
Interrupt Event.
Interrupts suspend the current (normal) execution, completes the interrupt-linked POU execution and then returns back to
suspended point, to resume normal execution.
In case of multiple interrupt events, these event needs to be prioritized. System interrupt events like serial communication
interrupt, internal timer interrupt are executed at highest priority. Here scheduler manages the execution of queued events as per
defined priority.
20
High Speed Counters (HSC)
522x - P4, CPU 523x - P4 provide 2 independent channels for high speed counters. Each channel provides three input interfaces
as A, B and Z. This channel provides hardware interface for open collector (PNP / NPN) inputs of 24 VDC or differential 5 V inputs.
To configure for its use, these CPUs provide driver function blocks for each channel in library PTO.lib. This facilitates application
developer to set the mode of operation and fetch the accumulated count and status of Z input. Counter provides pulse count in
double integer format.
Open collector With patch panel 2 HSC & 2 PNP type PTO
(18-30 VDC including ripple) (Ordering Code-4960)
Type (Selectable by
type of patch panel) With patch panel 2 HSC & 2 RS 422 type PTO
Differential
(Ordering Code-4962)
60 mA maximum for differential output with patch panel 4962.
Current
1.5 Amp maximum for open collector (PNP) output with patch panel 4960.
21
IEC 61131-3 CoDeSys is a Windows ® based, an
international quality software which is IEC
61131-3 compatible.
Modular Programming
CoDeSys encourages use of modular programming. Developed application is called as project, which has .pro as
file extension. Every CoDeSys project must have at least one POU. POU stands for program organisation unit
which either could be a program, function-block (FB) or function. One project can have many POUs.
PLC_PRG is a program, which is mandatory POU in every project. This PLC_PRG is a master routine where from
all the other POUs (sub-routines) are called. In a way, PLC_PRG can be viewed as main function in C language.
Hence, rather than dumping the complete logic into one POU (PLC_PRG), multiple POUs are developed, as per
objectives. Thus any project can be developed into split components. This approach resembles with object
oriented programming in higher level languages like C++ or Java.
This reduces development time for a machine manufacturer or end-user. Simply write it once and implement
many times. Password protection facility conceals the application logic in POUs (function & function blocks).
Modular programming and library management has indeed eased the task of application program development,
to a great extent.
22
Ladder Diagram (LD)
It is the simplest graphical method of PLC
programming comprised of normally open and
normally closed contacts and coils, widely used in
discrete control applications. IEC ladder program
encourages, use of other program organization
units (POU) i.e. functions, function blocks and
programs. This has enhanced its wide acceptance
to process control applications also.
23
Structured Text (ST)
It is a textual language resembling with high level
programming language like Ada, Pascal or C. It exhibits
its suitability for logic with complex algorithms or
mathematical computations. It can be used to build
POUs i.e. functions, function blocks or programs.
This can be very well harmonized with ladder.
24
A simplified step consists of an action and flag to indicate whether the step is active. An IEC step has a flag and one or more
associated actions or Booleans. An action has series of instructions in either of IEC language. In addition to step action, there can
be an entry action and/or an exit action. These entry and exit steps get executed once only, right after the step is activated or just
before step is deactivated, respectively.
Off-line Simulation
CoDeSys has an off-line simulation facility. This is very vital utility for an application program developer, as one can develop
complete program logic independent of PLC. This feature helps the developer to complete the application program development
on or before scheduled time. Off-line simulation is built-in* feature of CoDeSys.
Please note that offline simulation does not support some of the CPU resource specific function / function blocks.
(e.g. it does not support RTC related, System variable related functions and function blocks.
*In case of some PLC vendors, Application program development software and simulation software are different.
On-line Functionality
CoDeSys has on-line program monitoring and on-line
program modifications features. This makes it suitable
for continuous process application, where program
modifications without process interrupt may be
required. Watch and Receipt window facilitates to
monitor multiple variables, simultaneously from
multiple program organization units (POUs). On-line
power flow monitoring serves as ready tool for fault
Watch & Receipt window, shows, different variables from, various POUs.
diagnostics.
25
PLC I/O Configuration
Hierarchical and Graphical method of PLC rack
configuration and module configuration minimises the
chance of errors in I/O addresses.
PLC Browser
CoDeSys facilitates use of PLC Browser for viewing or
setting certain PLC parameters. PLC Browser is textual
command monitor which is a analogous to DOS prompt.
It has command entry line cum result display window,
which is like a combo-box.
It has smart history of latest executed commands, which Sample for using PLC browser, a handy and quick tool for developer
displays it without repetition of command. User can
check /set RTC from PLC browser.
In case direct DDE Server is used, which works with symbols rather than addresses, CoDeSys is not required to read the variables
from PLC and transfer them to application with DDE interface. Direct Addresses are not read with DDE Server. One needs to use
symbolic variables.
CoDeSys has assured and tested DDE interface, with Microsoft® Excel 97 and Microsoft® Word 97, only with Microsoft
Windows® NT 4.0
26
Sample Trace Function with Graphical Display
This on-line feature of CoDeSys enables user to
monitor progression of maximum eight different
analog or digital variables, simultaneously in trace
window (graphical format). This sampling rate is user
settable. The sampled values are stored in internal
trace buffer. If this ring buffer gets full, data purging
takes place i.e. older values are overwritten with
newer ones.
Other features like stretch, compress, Y Scaling Typical example of sampled temperature and pressure,
in a process application
allows user to adjust the trace window for the
requisite visibility. Enabled show grid option makes
grid as well as X-Y axis values to be visible.
Parameter Description
Trigger Variable This terminates sampling activity. (Trigger OFF)
Trigger Level This initiates sampling activity. (Trigger ON)
Number Minimum 32
of Samples Maximum 1024
Sampling Minimum 1 ms
Rate (ms) Maximum 20000 ms
Single Displays only once the samples 'Number of samples'
Recording Continuous Displays continuously selects 'Number of samples'
Manual Used to read trace recording with 'Read Trace' from ‘Extras'
Variables These are variable for sampling ( Maximum 8 )
Similarly the saved text file for sampled data can be readily transported to Microsoft Excel, where user can take further
analytical and database storage actions.
27
Process Visualisation for On-Line Testing
This on-line feature of CoDeSys facilitates a user for
designing interactive graphic user interface or screens.
This allows user to design application specific screens,
using various GUI elements or visualisation elements like:
rectangles, rounded rectangles, ellipse, polygon, polyline,
curves, BMP images, buttons (with limited events) and the
other visualisation itself. It also facilitates a user to have a
regular configuration of these elements. e.g. rectangle has
shape, text, line-width, color, motion-absolute, motion-
relative, variables, input and tool-tip. These configuration
parameters vary as per visualisation element.
In comparison with other front end tools (Visual Basic, Power Builder, Oracle Forms), this has limited capacity and features.
Even though it is comparable to SCADA, one should not use this feature as SCADA, as its response and performance are not
assured. It is strongly recommended to use this tool for test and monitoring purpose rather than control action.
As a general rule, any POU (calling POU) can call other POU (called POU), which is hierarchically at equal or lower level of calling
POU. A POU can not call other POU, which is hierarchically above the calling POU. Thus, a function block can call other function
block or function and cannot call program.
28
CoDeSys supports other data types, which are specific to date and time.
Type Resolution Remark Example Memory
TIME 1 ms 25 Days ( Max Value ) t#23h02m12s247ms 32 Bit
DATE 1 sec Counts from 1'st Jan.1970 d#2003-05-23 32 Bit
DATE_AND_TIME 1 sec Counts from 1'st Jan.1970 dt#2003-05-12-15:36:57 32 Bit
TIME_OF_DAY 1 ms Counts from 12.00 am, everyday tod#14:27:09.986 32 Bit
Class
Class defines the scope of the variable viz. local and global. Global elements are accessible to all the POUs in a project. CoDeSys
compiler forcibly insists data type declaration for an every variable used in the project, except PLC addresses.
Local Variables:
These variables are declared & defined specifically for the POU, thus the scope is valid only for the declared POU.
Global Variables:
These variables are declared and defined for a POU, with its widen accessibility. Thus these variables can be referred in other
POUs of the same project.
VAR
These are the local variables, necessarily meant for storing intermittent results of any POU. VAR variables restrict their
accessibility to the POU itself.
VAR_IN
These are read only type local variables, acting as inputs to POU (e.g. function block). Value of the variable can be given along with
the call, in calling POU.
VAR_OUT
These are local variables, acting as output to POU (e.g. function block). Value of these variables are returned back at the calling
POU. These variables can be used further, in the POU.
VAR_IN_OUT
These are local variables, acting as input as well as output of any POU. Value of such a variable is always passed by reference
rather than value. These variables are not applicable to the function.
29
Nexgen 5000 Series of CPUs supports extensive instruction set to built the control logic across variety of applications, from
machine tools to process industry. The CPU is capable of handling various data types.
Data types supported are
Boolean
l String
l of sequential ASCII characters
8, 16,
l 32 bit signed / unsigned numbers 1-, 2-,
l 3- dimensional arrays
Real numbers
l (32 bit IEEE floating point format) Structures
l (User Defined Data Types)
Date,
l Time, Date and Time.
COMMUNICATION BASICS
Communication is handled with seven layers. But, still most of the time communication is handled with Application Layer, Protocol
Layer, Data Link Layer and Physical Layer.
Physical Layer
Physical layer is comprised of several elements viz. media of transmission (like wires, fiber optics, wire-less), signal drivers, method
of transmission, inter connections, connectors and inter signal converters. Most commonly employed physical layer protocols are
RS 232C, RS 422 and RS 485.
* Isolator drivers are required for a distance more than 50 m. ( Maximum supported distance is 1 KM )
30
RS 422 to RS 485 Conversion
As a common practice, RX+ is shorted to TX+ and RX- is shorted to TX-. The RS 485 connected station is called as Half
Duplex as it either receives or transmits the signal. In some cases, TX needs to put to tri-state when receiving starts. Such
convertible ports are marked as RS 422 / RS 485.
Nexgen 522x / 523x series having serial 2'nd and 3'rd port, are convertible from RS 422 to RS 485 and vice versa.
This is characterized by :
l
Optical isolation between input and output signals l
Auto detection of direction, in case of RS 485
l
Can be used as RS 422 isolated repeater l
Supports 3 baud rates viz. 9600,19.2,38.4 Kbps
l
Can be used as RS 485 isolated repeater l
Provides diagnostic LED indications
l
Operates directly on 85-260 V AC range l
DIN rail mountings
l
Does signal level correction l
Provides output signal short circuit protection
l
Provides auxiliary output power supply for local device connection
Item Description
Function RS 422(4 Wire) to RS 485(2 Wire) Conversion or Vice versa
Input supply voltage 85-260 VAC,15VA, 50/60Hz
Operating modes RS 422 (4-wire) or RS 485(2 wire ), set by switch settings
Auto direction sensing Facility available for RS 485(2-wire) interface
Baud rates supported 9600, 19200 and 38400 ( set by DIP Switch setting )
Signal isolation 1.5 KV optical isolation
These are used in various networking schemes where PC (RS 232) side is interfaced with RS 422 / RS 485
or vice versa.
lOptical isolation between input and output signals Auto detection of direction, in case of RS
l 485
31
Item Description
Function RS 232(3 Wire) to RS 422/485(4/2 Wire) Conversion or Vice versa
Input supply voltage 85 260 VAC,15VA, 50/60Hz
Operating modes RS 422 (4-wire) or RS 485(2 wire ), set by DIP switch settings
Auto direction sensing Facility available for RS 485(2-wire) interface
Baud rates supported 9600, 19200 and 38400 ( set by DIP Switch setting )
Signal isolation 1.5 KV optical isolation
Signal short circuit protection Applicable
Model 6010 24 V DC, 250 mA
Auxiliary power output
Model 6015 12 V DC, 250 mA
Model 6016 5 V DC, 500 mA
Supply protection 2 Amp miniature glass fuse protection at input supply
Protocol
Protocol is synonymous to language as both the devices should communicate and understand the same language. It is predefined
sequence of codes for data exchange. By using protocol converter, two devices having un-identical protocols can communicate. A
protocol is command and response having, header, body and a trailer. Header is indicative of a new message begin, body is
comprised of command number, data and any other information need to communicate. Trailer has error checking checksum and
end of transmission character. Protocols work independent of physical layer.
MODBUS is a widely used protocol in industry being established and open for use. Messung Protocols are specific to Messung
products and are not open for its use. To communicate with Messung products, application developer has to write a protocol
converter like SCADA driver.
Typical communication string has Header, Station ID, Length, Command/Response byte, Data, Checksum and Trailer.
Communication parameters are Baud rate, Data bits, Parity bits and Number of stop bits. Typically one byte frame consumes 11
bits and at 9600 bits per seconds, it takes 1ms per byte frame.
Nexgen 5000 has an Application Layer and Protocol Layer, which are open to user, Data Link Layer which is implicitly handled by
PLC operating system and Physical Layer which is hardware dependent.
Function blocks for MODBUS master and slave are developed by Messung, for Nexgen 5000 PLCs.
Nexgen5000 has two buffers viz. RX buffer and TX buffer which simultaneously handle transmission and reception, functions
independently and in parallel to PLC scan. Data Link Layer handles conversion of Data Frame to Byte Frame.
32
Protocol FB get executed in logic scan and consumes application as well as data memory. It delivers same throughput, facilitates
variety of communication speeds and exerts complete control on communication scheme.
MODBUS Protocol
MODBUS protocol, introduced by MODICON, is open to 01 Read Coil Status ( 1 bit )
everybody for use, which has MODBUS RTU (binary),
03 Read Holding Register ( 16 bit )
MODBUS ASCII and MODBUS TCP protocols. Presently
Messung supports MODBUS RTU protocol, which is efficient 04 Read Input Register ( 16 bit )
being in binary format. Messung FB has MODBUS Master
05 Write Single Coil / Preset single holding register
and MODBUS Slave which support various commands as :
15 Write Multiple Coils / Preset multiple holding register
MODBUS RTU_Slave
It emulates MODBUS Slave functionality. User can create only single instance of the block and can be attached to any port . It is
interface able with SCADA, DCS, E Terminals, Nexgen PLC with MODBUS Master FB.
MODBUS RTU_Master
Its design is characterized by its facility to handle Cyclic, Super Cyclic and On-demand data updates, User defined exchange
requirements in source as well as destination formats of records and Error reporting with record number.
RTU_MAST
ModeSel can have values as 0, 1 or greater than 1. Its 0 value stands for on-demand or manual updation, only once but in
overriding mode. Its value 1 stands for cyclic execution but only once per network scan. When ModeSel has value greater than 1,
it can be grouped and gets executed along with cyclic.
MODBUS supporting devices may not support all the MODBUS commands, this emphasizes due care while putting such a device
to network. Nexgen 5000 to Nexgen 5000 communication can be established with MODBUS Master function block.
Nexgen_Slave
It emulates Nexgen 4000 HMI port protocol, facilitating connectivity for Smartline Sr., Smartline Jr., E-Series HMIs and SCADA
with Nexgen Drivers. Communication speed is selectable up to 56 Kbps, incase of E-series HMIs and SCADA only. This can be
attached to any of the Nexgen 5000 communication port.
Freqrol Inverter FB
This block facilitates a user to connect 31 freqrol Inverters and user need not know Inverter interface protocol. User can have
control over Direct Inch, ON/OFF operations, Cyclic data updation, Individual error handling and automatic communication
recover on Inverter switched ON. It reflects fast changes to set point changes. Communication speed is settable to 9.6 Kbps or
19.2 Kbps.
33
Base Plate
The base plate holds Power Supply, CPU and I/O modules. It is available in varieties to suit I/O and expansion requirement. The
base plate is available with or without expansion connector to offer economic solution. Both the base plates are available in 3 I/O, 5
I/O and 8 I/O slots. x mm
NEXGEN
Expansion Plate
161.5mm
190mm
In multi-rack system, the expansion plate can be mounted
next to each other or one below other. The expansion
plate is available in varieties to suit I/O and power supply
requirement. It is available with or without power supply
connection facility. Both the expansion plates are
available in 3 I/O, 5 I/O and 8 I/O slots. At the most 3 3 I/O Base Plate (248 mm) (Depth 145 mm)
expansion plates can be connected to the base plate. 5 I/O Base Plate (332 mm)
MOV
l for incoming over voltage
Protections
Output
l short circuit protection
34
Digital Input Modules
35
MIXED DIGITAL I/O MODULES
Mixed 16 pt DC Input / Mixed 16 pt DC Input /
8 pt DC Output Module 8 pt Relay Output Module
8 Channel Non-isolated Analog Input Module - (A successor module to 4308 with much improved performance)
n Converts analog voltage and current signal values No. of Input Channels 8 differential or single ended non isolated
into equivalent binary values. Conversion Method Sigma Delta with digital filter
Voltage Input type Output type
n User programmable filter and averaging feature.
Analog ± 10 VDC ± 32,000
input ± 5 VDC ± 32,000
4309 module can be used in Nexgen-4000 & Nexgen- type and ± 1 VDC ± 32,000
5000 CPU based PLC Systems. This module has output 1 to 5 VDC 6,400 to 32,000
range Current 0 to 20 mA 0 to 32,000
enhanced performance for 0-20 mA current signal 4 to 20 mA 6,400 to 32,000
interface on all 8 channels - in differential mode. High Input type Effective Significant Bits Resolution
(50 Hz filter)
voltage withstanding capability for a short duration on ± 10 VDC 15 bits + Sign 312.5 m V
any of the analog inputs. Resolution ± 5 VDC 15 bits + Sign 156.3 m V
± 1 VDC 14.7 bits + Sign 45 m V
1 to 5 VDC 15 bits 156.3 m V
0 to 20 mA 15 bits 0.625 m A
4 to 20 mA 14.7 bits 0.625 m A
Overall accuracy* At 25°C ± 5°C At 55°C ± 5°C
with 50 Hz filter ± 0.2 % of FSR ± 0.65 % of FSR
Analog to digital Filter freq. Channel update time Significant bits
conversion time 10 Hz 320 ms 15 bits + Sign
50 Hz 60 ms 15 bits + Sign
60 Hz 50 ms 15 bits + Sign
250 Hz 12 ms 12 bits + Sign
500 Hz 6 ms 9 bits + Sign
Absolute Voltage 220 VAC / 220 VDC if voltage signal is
maximum input connected across channel terminals Vn+
and Vn- i.e. for differential input connections
protection
Current ± 30 mA
Channel to Channel Nil
Isolation
Channel to internal circuit 1.5 KV optical
External power 24 VDC, 200 mA
supply requirement (18 to 30 VDC including ripple)
External power l 315 mA miniature glass fuse on module
n Accuracy is degree of correctness of ADC output supply protection l Reverse polarity protection
Indications l No 24V SUPPLY l Configuration Error
n Repeatability is degree of consistency between Channel Status (8 Nos.)
l CPU FAULT l
ADC output readings under the same condition. Back-plane current 210 mA
*Overall accuracy includes both accuracy and repeatability
I/O points consumed 8 Input Bits & 8 Output Bits
and is defined separately at 25°C and 58°C Ambient,
considering temperature drift. Terminal / Connection Removable 38 pin Terminal Block
Ordering Code 4309
36
8 Channel Thermocouple Input Module
equivalent temperature values of 0.1oC resolution with RTD Input Type -200°C To 850°C
and 3 Wire PT 100
Lead Compensation. Output Range (385) -200.00°C To 140.00°C
37
4 Channel Non Isolated Analog Output Module
The module converts digital values data from CPU to
No. Of Output Channels 4 Non Isolated, 16 Bit
equivalent analog output voltage.It provides 4 non-
isolated channels with 16 bit resolution. Conversion Method R-2R Ladder
Resolution 312.5 m
V
Load Resistance > 1 K Ohm
50 mS (Irrespective of
Conversion Time No. of ON Channels)
24 V DC, 300 mA
External Power Requirement
18-30 VDC, Including Ripple)
l
No 24 V Supply
Indications l
Channel On (For Each Channel)
38
2 Channel Isolated Analog Output Module (Voltage/Current)
The module provides 2 isolated channels with 12-bit
No. Of Output Channels 2 Isolated, 12 Bit
resolution. Output type can be Voltage/Current. Conversion Method R-2R Ladder
Voltage -10 to +10 VDC
Types
Current 4 to 20 mA
Voltage / Current Significant Resolution
Range Bits per LSB
Resolution
-10 to +10 VDC 12 Bits 4.88 mV
4 to 20 mA 11 Bits 7.8 mA
Voltage > 1 K Ohms
Load Resistance 500 Ohms
Current
Conversion Time 20 m S
Isolation Channel to Channel 1.5 KV optical
Channel to internal circuit
External Power Requirement 24 V DC, 500 mA
External Supply Protection Reverse Polarity Protection
Indications No 24 V Supply
Back-plane current 150 mA
I/O points consumed 32 Input Bits and 32 Output Bits
Terminal/Connection Removable 20 Pin Terminal Block
Ordering Code 4332
Input Channel To
Isolation Output Channel Nil
Indications l
CPU Fault
l
Analog Input Channel Status (4)
Back-plane current 1000 mA
Note: This module does not require any external power supply.
I/O points consumed 8 Input Bits And 8 Output Bits
Terminal/Connection Removable 38 Pin Terminal Block
Ordering Code 4366A
39
4 Channel Counter Input Module
The Multifunction Input module provides mix of inputs with programmable filter
time, pulse catch input, interrupt input and counters with programmable 16 bit
operational mode. Programmable filter (10ms) and up counter is the default
configuration. In such case, the inputs are not available as normal inputs.
The counters can be programmed for external reset using normal inputs.
Counting direction for up/down counter can be selected by external inputs
40
Human-Machine Interfaces (HMI) are panel mounted devices that provide effective dialogue between the operator and machine.
Equipped with programmable display and keys, HMIs allow easy operation and monitoring in the production area. HMIs display
operational and fault messages, enable machine specific parameters to be monitored and modified in suitable format. HMI keeps
the operator fully informed of the current status of operations at all times.
Benefits of using Human Machine Interface along with PLC
! Replaces conventional push button panel (and related wiring), indicating lamps etc.
! Connects to PLC via serial interface. So easy and quick installation
! Simple operation and control
! Clear display of information
! Fault messages and instructions help reduce down time thereby improving productivity directly
The table summarises key features of Smartline series of Human Machine Interfaces.
User Configurable Keys 4 (+ fixed function keypad) 20-12 fixed + 8 function keys 24-12 fixed + 8 function keys 28
Buzzer - - - Potential free contact
Password - 3 levels 3 levels 3 levels
Memory 8 K EEPROM 16 K Flash 16 K Flash 16 K EEPROM
Maximum screens 256 256 256 256
PC Based
Software Package SFL V4.22 SFL V4.22 SFL V4.22 SFL V4.22
* - “X” Stands for type of PLC Connectivity (e.g. N - for Nexgen PLC Connectivity)
* For HMI SmartlineJr both the cables are required, as specified in above table.
Product development is a continuous process. Consequently specifications are subject to change without prior notice.
For latest information please contact our nearest sales office.
41
E50 E100 E150 E200 E300 E600 E610
Display type LCD Backlit STN Backlit STN Backlit STN Backlit STN Backlit STN Backlit STN, Backlit STN,
black / white 16 grays, touch
Presentation form Text Text Text Text Graphic + Text Graphic + Text Graphic + Text
Display size 2 rows x 2 rows x 2 rows x 4 rows x 240 x 64 pixels 240 x 128 pixels 320 x 240 pixels
16 characters 20 characters 20 characters 20 characters
Active area of display
W x H (mm) 55.7 x 11.0 73.5 X 11.5 73.5 X 11.5 70.4 x 20.8 (5.2”) (5.3”) (5.7”)
Backlight Lifetime (h) 50,000 50,000 50,000 50,000 50,000 15,000 25,000
Text height (mm) 5 5 5 5 Variable Variable Variable
LEDs -- -- -- 5 (two colors) 16 (two colors) 16 (two colors) --
Function keys 4 4 6 (text strip) 5 (text strip) 8 (text strip) 16 ( 8 with text strip) --
Dual drivers -- · · · · · ·
Passthrough mode -- · · · · · ·
Web functionality -- -- -- -- · · ·
Terminal reflection -- -- -- -- · · ·
via Internet
Multi Language / Unicode -- ·
/- ·
/- ·
/- ·
/· ·
/· ·
/·
Recipe handler -- · · · · · ·
Alarm management -- -- - 1 group Up to 4 groups Up to 4 groups Uup to 5 groups
Time channels -- · · · · · ·
Real-time clock -- · · · · · ·
Trend graphs -- -- -- -- Real time Historic Historic
Report printouts -- · · · · · ·
Password for security -- 8 levels 8 levels 8 levels 8 levels 8 levels 8 levels
Buzzer -- -- -- -- -- -- --
400 kb Flash / 400 kb Flash / 400 kb Flash /
Memory for application 16 kb Flash 64 kb Flash 64 kb Flash 64 kb Flash 8 Mb expansion 8 Mb expansion 8 Mb expansion
Number of expansion -- -- -- -- 1 1
card positions 1
RS485, RS422,
Communication interfaces RS422 or RS 232C RS422 and RS 232C RS422 and RS 232C RS422 and RS 232C RS422 and RS 232C RS422 and RS 232C RS 232C (4)
Support for PalmTMhandhelds · · · · · · ·
Support for extended -- -- -- -- · · ·
keyboard
Ambient temperature 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC
Waterproof front IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2)
EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1,
EMC
EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2
UL UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3)
DNV · · · · · · ·
Power supply + 5 V DC ± 5 % + 5 V DC ± 5 % + 5 V DC ± 5 % +24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V
Power consumption 200 mA (5 V) 200 mA (5 V) 200 mA (5 V) 150 mA (24 V) 450 mA (24 V) 450 mA (24 V) 400 mA (24 V)
104 X 69 X 38 142 X 100 X 29 142 X 100 X 29 147 X 163.5 X 38 211 X 198 X 69 214 X 232 X 879 200 X 150 X 69
Dimensions W x H x D (mm)
(401” X 2.7” X 1.5”) (5.6” X 3.5” X 1.1”) (5.6” X 3.5” X 1.1”) (5.8” X 6.4” X 1.5”) (8.3” X 7.8” X 2.7”) (8.4” X 9.1” X 3.4”) (7.8” X 5.9” X 2.7”)
Weight (kg) 0.2 0.5 0.5 0.7 1.5 1.4 1.5
42
E615 / E615T E1071 E1101 E1151 E1070 E1100
Backlit STN / TFA
Graphic 60K color TFT-LCD, resistive touch Graphic 64K color TFT-LCD Graphic 64K color TFT-LCD
colour, touch
320 x 240 pixels 640 x 4800 pixels 800 x 600 pixels 1024 x 768 pixels 640 x 480 pixels 800 x 600 pixels
40,000 / 50,000 -- -- -- -- --
Variable Variable Variable Variable Variable Variable
-- -- -- -- 16 (8with integrated 22 (10with integrated
-- -- -- -- LED and text strip LED and text strip
· · · · · ·
· ·
( dependent on driver) ·
( dependent on driver) ·
( dependent on driver) ·
( dependent on driver) ·
( dependent on driver)
· ·
( dependent on driver) ·
( dependent on driver) ·
( dependent on driver) ·
( dependent on driver) ·
( dependent on driver)
· · · · · ·
· · · · · ·
·
/· With upto 10 languages in one project
· · · · · ·
1 1 1 1 1 1
RS485, RS422, Ethernet 10/100 Nbit/sec Rj45 connector, USB host, USB device, RS485/RS422 25-pin D-sub contact)RS485 available through Rs422 with software setting),
RS 232C (4) Rs232 9-pin D-sub contact
· · · · · ·
· · · · · ·
0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC
EN 50081-2, EN 61000-6-2 / EN 61000-6-2 immunity, EN 61000-6-2 immunity, EN 61000-6-2 immunity, EN 61000-6-2 immunity, EN 61000-6-2 immunity,
EN 50081-1, EN 61000-6-2 / EN 61000-6-4 emission EN 61000-6-4 emission EN 61000-6-4 emission EN 61000-6-4 emission EN 61000-6-4 emission
UL 508, UL 1604 (3) / - UL 1604 Class I, UL 1604 Class I, UL 1604 Class I, UL 1604 Class I, UL 1604 Class I,
Div. 2,UL 508, Ul50 Div. 2,UL 508, Ul50 Div. 2,UL 508, Ul50 Div. 2,UL 508, Ul50 Div. 2,UL 508, Ul50
·
/- · · · · ·
+24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V 100-240 V AC
+24 V DC, / V
20-30
24 V DC, 20-30 V
450 mA (24 V) Max 0.9 A Max 1.0 A Max 1.7 A Max 0.9 A Max 1.0 A
200 X 150 X 69 219 X 154 X 61 302 X 228 X 64 398 X 304 X 66 285 X 177 X 62 382 X 252 X 64
(7.8” X 5.9” X 2.7”) (8.6” X 6” X 2.4”) (11.89” X 8.97” X 2.52”) (15.66” X 11.96” X 2.59”) (11.22” X 6.96” X 2.44”) (15” X 9.92” X 2.52”)
1.5 1.7
-- 1.7
-- 1.7
-- 3.5
-- 3.3
--
43
GT 1595-XTBA GT 1585-STBA GT 1575-STBA GT 1575-VTBA GT 1575-VNBA GT 1572-VNBA
Performance Specifications
Specifications
Item GT1585-STBA GT1575-STBA GT1575-VTBA GT1575-VNBA GT1572-VNBA GT1565-VTBA GT1562-VNBA
GT1595-XTBA
GT1585-STBD GT1575-STBD GT1575-VTBD GT1575-VNBD GT1572-VNBD GT1565-VTBD GT1562-VNBD
TFT color display TFT color display
Type TFT color display (Highbrightness, TFT color display
(High-brightness, wide viewing angle) wide viewing angle)
Screen size 15” 12.1” 10.4” 8.4”
Resolution XGA:1024 x 768 [dot] SVGA:800 x 600 [dot] VGA:640 x 480 [dot]
Display size 304.1(W) x 228.1(H) [mm] 246(W) x 184.5(H)[mm] 211(W) x 158(H) [mm] 171(W) X128(H) [mm]
For 16-dot standard font For 16-dot standard font
Number of :64 chars. x 48 lines( two bytes) :50 chars. x 37 lines (two bytes) For 16-dot standard font : 40 chars. x 30 lines (two bytes)
Display display For 12-dot standard font For 12-dot standard font For 12-dot standard font : 53 chars. x 40 lines (two bytes)
characters :85 chars. x 64 lines(two bytes) :66 chars. x 50 lines(two bytes)
Display color 256 colors / 65536 colors*1 256 colors 16 colors 256 colors / 65536 colors*1 16 colors
View angle Right/Left:75o, Up:50o, Down:60o Right/Left:60o,Up:40o, Down:50o Right/Left:50o,Up:35o, Down:45o Right,Left,Up,Down:85o Right/Left:45o,Up:30o, Down:20o Right/Left:65o,Up:50o, Down:60o Right/Left:45o,Up:20o, Down:20o
Contrast adjustment 450[cd/m2] 350[cd/m2] 280[cd/m2] 380[cd/m2] 200[cd/m2] 380[cd/m2] 150[cd/m2]
Intensity 8-step adjustment 4-step adjustment 8-step adjustment 4-step adjustment
Approx.52,000hours(operating Approx.50,000 hours Approx.41,000 hours
Life ambient temperature:25oC) (operating ambient temperature: 25°C) (operating ambient temperature: 25°C)
Cold cathode fluorescent tube (replaceable) with backlight OFF detection function, and selectable backlight OFF / screen save time
Back
light Life *2 Approx.50,000hours or more Approx.40,000hours or more
(time for display intensity to become 50 % at operating ambient temperature of 25°C)
Number of 3072 keys per screen 1900 keys per screen 1200 keys per screen
touch keys (481ines x 64 columns ) (38 lines x 50 columns matrix resistive type) (30 lines x 40 columns matrix resistive type)
Touch Key size Min. 16 x 16 [dots] Min. 16 x 16 [dots] Min. 16 x 16 [dots]
panel (per key) (per key) (16 x 8 at final line only) (per key)
No. of simultaneous Simultaneous touch
touch points prohibited*3 (1 point only) Max. 2 points
44
GT 1565-VTBA GT 1562-VNBA GT1155HS-QSBD GT1150-QLBD GT1155HS-QSBD GT1155-QSBD
Performance Specifications
Specification
Item
GT1155-QSBD GT1150-QLBD GT1155HS-QSBD GT1150HS-QLBD
Type STN color display STN monochrome (black/white)display STN coIor display STN monochrome (black/white)display
Screen Size 5.7"
Resolution QVGA:320 x 240 [dot]
Display size 115(W) x 86(H) [mm]
Number of display characters For 16-dot standard font: 20 chars. x 15Lines (two bytes), For 12-dot standard font: 26 chars. x 201ines (two bytes)
Display color 256 colors 16-tone gray scales 256 colors 16-tone gray scales
Right / Left: 50°, Right / Left: 45°, Right / Left: 50°, Right / Left: 45°,
View angle Up: 50°, Down: 60° Up: 20°, Down: 40° Up: 50°, Down: 60° Up: 20°, Down: 40°
Display Contrast adjustment 16-step adjustment
Contrast adjustment 350 [cd/m2] 220 [cd/m2] 350 [cd/m2] 220 [cd/m2]
Intensity 8step adjustment
Life Approx. 50,000 hours (operating ambient temperature: 25°C)
Cold cathode fluorescent tubel(not replaceable) with backlight OFF detection function and selectable backlight OFF / screen save time
Backlight
Approx. 75,000 hours or more Approx. 54,000 hours or more Approx. 75,000 hours or more Approx. 54,000 hours or more
Life*1
(time for display intensity to become 50 % at operating ambient temperature of 25°C)
Number of touch keys 300 keys per screen (15 lines x 20 columns matrix resistive type)
Touch
panel Key size Min. 16 x 16 [dots] (per key)
No. of simultaneous touch points Max- 2 points
Life 1.000,000 or more operations (pressing force of 0.98N or less)
C drive 3 MB built-in flash memory (for saving project data)
Memory*2
Life (number of writings) 100,000 writings
GT11-50BAT type lithium battery
Battery Backed up data Clock, alarm history, recipe data
Life Approx. 5 years (operating ambient temperature: 25°C)
RS-422, 1 ch, Transmission speed: 115200,
57600,38400,19200,9600,4800 bps --
RS-422 Connector shape : D-sub 9 pin (female)
Application: Communication with connected devices
RS-422/232, 2 ch (select 1ch when using
Transmission speed: 115200, 57600, 38400,
RS-422/232 -- 19200, 9600, 4800 bps
Connector shape : Round 32- pin (male)
Application: Communication with connected devices
RS-232, 1ch, Transmission speed. 115200, RS-232, 1ch, Transmission speed: 115200,
Built-in
57600, 38400, 19200, 9600, 4800 bps 57600, 38400, 19200, 9600, 4600 bps
interface
Connector shape: D-sub 9 pin (male) Connector shape: Mini-DIN6-pin (female)
RS-232 Application: Communication with connected devices, Application: Communication with connected devices,
connection to personal computer (for project data uploads/ connection to personal computer (for project data uploads/
downloads, OS installation, FA transparent function) downloads, OS installation, FA transparent function)
USB USB (Full Speed 12Mbps), device, 1ch Connector shape: Mini-B Application: communication with
personal computer (for project data uploads/downloads, OS installation, FA transparent function)
CF card Compact Flash slot 1ch. Connector shape: TYPE I, Application: For data transmission and data saving
Optional Function board 1 ch for optional function board installation
Buzzer output Single tone (tone length is adjustable)
Environmentally protective construction JEM1030 Front face:IP67f*3 Inside paneI:IP2X JEM1030 IP65f*4
External dimensions(without USB port cover) 164(W) x 135(H) x 56(D) [mm] 176(W) x 220(H) x 93(D) [mm]
Panel cut dimensions 153(W) x 121(H) [mm] --
Weight 0.7 [kg] (excluding the mounting bracket) 1.0 [kg] (Main unit only)
Supported Drawing software GT Designer2 Version 2.18U or later
software package Simulator function GT Simulator2 Version 2.18U or late
*1: Using the GOT screen save / backlight OFF functions prevents screen burn-in and extends the backlight life.
*2: The internal memory is a ROM that permits new data overwriting without having to delete the existing data.
*3: Conforms to the IP67f (JEM1030) standard when the USB port cover is installed. (The USB interface conforms to IP2X(JEM1030) when a USB cable is connected.)
However, this does not guarantee protection in all user environments.
*4: Does not apply when IP65f-rated interface covers on top and rear face are removed.
On LCD screens, bright dots (permanently lit) and black dots (not to be lit) generally appear. Because the large number of display elements exist on an LCD screen, it is not possible to reduce appearance
of the bright and black dots to zero. Note that the existence of bright and black dots is a standard characteristic of LCD screens, and it does not mean that the products are defective or damaged.
45
General Specifications
*1: Wet bulb temperature for STN display type is 39°C or lower
Item Specification *2:Refer to the Communication Unit User's Manual for
Operating ambi- Display 0 to 50°C*6 vibration re-sistance specifications when using a
ent temperature Other than display 0 to 55°C*6 MELSECNET/10 communication unit
(GT15-75J71LP23-Z, GT15-75J71BR13-Z) or a CC-Link
Storage ambient temperature -20 to 60°C Communication unit (GT15-75J61 BT13-Z).
Operating ambient humidity*1 10 to 90 % RH, no condensing Communication units specs. are different from GOT specs.
Storage ambient humidity*1 10 to 90 % RH, no condensing *3: Do not operate or store the GOT unit in pressurized
Frequency Acceleration Single amplitude Sweep count environments where the pressure exceeds the 0m elevation
Based on atmospheric pressure, as this could result in abnormal
If intermittent 5 to 9Hz -- 3.5mm 10 times operation.
JIS B 3502,
Vibration resistance*2 IEC61131-2
vibration occurs 9 to 150Hz 9.8m/s2 -- in each *4: Assuming that the device is connected at some point
If continuous 5 to 9Hz 4.9m/s2 1.75mm of X, Y, and Z between a public power distribution network and local
vibration occurs 9 to 150Hz directions system equipment. Category II applies to devices that are
-- --
supplied with power from fixed equipment. The surge
Impact resistance Based on JIS B 3502, IEC 61131-2 (147m/s2, 3 times in X, Y and Z directions) withstand voltage is 2500V for devices with ratings up to
Operating atmosphere No corrosive gas 300V.
2000m or less *5: Index that indicates the level of foreign conductive matter in
Altitude*3 the operating environment of device. Contamination level 2
Installation location Inside the control panel denotes contamination by non-conductive matter only,
Overvoltage category*4 II or lower though momentary conductivity may occur due to occasional
Contamination*5 2 or less condensation.
Self cooling *6: 0 to 40°C for GT115 HS.
Cooling method
*7: Excluding GT115 HS.
Component Names
46
F940WGOT-TWD-E F940GOT-SWD-E F940GOT-LWD-E F930GOT-BWD-E F930GOT-BBD-K-E
*1 When the power is turned ON a maximum current of 750 mA/24V DC is consumed. *5 The life of the backlight above indicates the value at 25°C.
*2 0 to 50°C when the screen is installed laterally. 0 to 40°C when the screen is installed vertically or horizontally. *6 Between all power terminals of the PLC and ground terminal.
*3 0 to 40°C when the extension interface is used. *7 This test result does not provide any guarantees that the
*4 Italian, Dutch, Swedish, Spanish, German, Portuguese, French product stands against use in all types of environment
*8 As regarding the front panel
47
Nexgen 5000 PLCs and HMI Interface
CPU 522x / 523x 1st port Setup (RS 232 C) CPU 522x / 523x - 2nd / 3ndport Setup (RS 422)
Master Master
6016
(Port converter)
+ 12V Supply
+ 12V Supply
When an HMI Smartline Jr. is to be interfaced with CPU 522x / 523x-1st / 2nd / 3rd Port:
+An external 5VDC / 12VDC power needs to be provided.
+The same is also true for Beijer make HMI models E-50, E-100, E-150.
Nexgen 522x / 523x Series of CPU Connectivity to Beijer HMI & Mitsubishi GOT
5221-B0 / P4 & 5222-B0 / P4
HMI Features
Port 2 / Port 3
Beijer Port 1 : RS 422 ECAB ü
ü
09 23
E50,
E100,
E150 Port 2 : RS 232 C ECAB 020 05 09 123
48
Sr.
No.
Item Description Ordering
Code
* Back Plane
Current (mA) at 5 V DC
1 Patch Panel, 2 Ch.,100 KHz Max. HSC & 2 Ch.,5 KHz Max. PNP Type PTO 4960
2 Patch Panel, 2 Ch.HSC,100 KHz Max. & 2 Ch.,100 KHz RS-422 Type PTO 4962
3 Interface Cable (0.5 Meter Length) 4944
4 Interface Cable (1 Meter Length) 4945
Ordering Ordering
Item Description Code Item Description Code
BASE PLATES EXPANSION PLATES
8 I/0 without expansion connector 4906 8 I/0 without Slot for Aux Power Supply 4934
5 I/0 without expansion connector 4932 5 I/0 without Slot for Aux Power Supply 4935
3 I/0 without expansion connector 4930 3 I/0 without Slot for Aux Power Supply 4936
8 I/0 with expansion connector 4937 8 I/0 with Slot for Aux Power Supply 4907
5 I/0 with expansion connector 4938 5 I/0 with Slot for Aux Power Supply 4933
3 I/0 with expansion connector 4939 3 I/0 with Slot for Aux Power Supply 4931
1 meter 4941
2 meters 4942
3 meters 4943
49
POWER SUPPLY MODULE Ordering Code
I/O MODULES
Ordering * Back Plane
Current (mA)
Terminal
Block
Code Required
at 5 V DC
8 Channel, RTD 850°C / RTD 140°C Interface Analog Input Module 4311A 250 38 pin
* Please note that if current consumption at 5 V DC of CPU, for all Digital & Analog Module I/O modules exceeds 5 A,
an additional power supply is required to be ordered.
4366A is superceded version of 4366
50
Nexgen 5232-B0 With CANOpen Interface
CANopen Network
Node ID 2
Node ID 31
PLC
OR
51
RiX CANopen Remote I/O Module
Dimensional Details:
140
C6616
Base Unit : 16pt. 24 VDC Input
Node Id
x10 x1
Inputs
46
PWR STS
RUN ERR
0
10
1
11
2
12
3
13
4
14
5
15
6
16
7
17
50
Inputs
17
50
54
16
16 } Optional
Material Handling : Ash Handling, Coal Handling, Belt Conveyors, Electroplating Plants, Paint Shops,
Assembly lines, ‘ANDON’ Systems etc.
Food Process : Biscuit Making Lines, Edible Oil Processing, Ovens etc.
Utilities : Energy Monitoring, Machine Supervisory Management Systems, MCC Panels Monitoring Systems
Machine Tools : Various SPMs, Presses, Industrial Washing Machines, Ultrasonic Cleaning Machines etc.
Many More Applications : Building Automation, Elevators, Furnace Control, Boiler Control, Asbestos Sheet Mfg. Plant etc.
52 * Introducing Soon ! RiX Modbus Remote I/O Series * Also Available - RiX DeviceNet Remote I/O Series
Version : 2.3
Release Date : May, 2008
Kohinoor House, EL-2, J Block, M.I.D.C. Bhosari, Pune - 411 026. India Manufacturer of PLCs, RIOs, HMIs
MESSUNG SYSTEMS Tel. : +91(020) 27102000 / 27102125 Fax: +91(020) 27102100
email: corpgroup@messung.com Website: www.messung.com