SCHEDULE OF LOADS
SWITCH
CIRCUIT NO. LOAD DESCRIPTION POWER / WATTAGE VOLTAGE CURRENT CIRCUIT PROTECTION CONDUCTOR SIZE CONDUIT SIZE
S1 S2 S3
1 LIGHTING OUTLET 1 2 106W 220V 0.4818A 15 AT,2P 3.5mm
2 LIGHTING OUTLET 3 2 106W 220V 0.4818A 15 AT,2P 3.5mm
3 LIGHTING OUTLET 3 2 97W 220V 0.4409A 15 AT,2P 3.5mm
4 LIGHTING OUTLET 3 2 97W 220V 0.4409A 15 AT,2P 3.5mm
5 LIGHTING OUTLET 3 1 97W 220V 0.4409A 15 AT,2P 3.5mm
6 ACU OUTLET 3200VA 220V 14.5454A 20 AT,2P 5.5mm
7 ACU OUTLET 3200VA 220V 14.5454A 20 AT,2P 5.5mm
8 CONVENIENCE OUTLET 1200VA 220V 5.4545A 20 AT,2P 5.5mm
9 CONVENIENCE OUTLET 1600VA 220V 7.2727A 20 AT,2P 5.5mm
10 CONVENIENCE OUTLET 1200VA 220V 5.4545A 20 AT,2P 5.5mm
11 ACU OUTLET 3200VA 220V 14.5454A 20 AT,2P 5.5mm
12 SPARE 220V 20 AT,2P 5.5mm

ELECTRICAL SPECIFICATIONS
220V, 60 Hz 1. ALL ELECTRICAL WORKS AND INSTALLATION THERE IN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF
2-38.0mm THE LATEST APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE WITH THE RULES AND REGULATIONS OF THE
NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES AND
WITH THE POLICIES OF THE LOCAL UTILITY COMPANY CONCERNED.
M 2. NO WIRE SMALLER THAN No. 3.5 mm2 AWG TWG SHAAL BE USED.
3. ALL MATERIALS USED SHALL BE NEW AND OF APPROVED TYPE FOR BOTH LOCATION AND PURPOSES INTENDED.
4. ALL OUTDOOR INSTALLATION SHALL BE OF WEATHER PROOF TYPE.
100 AT 5. ALL ELECTRICAL WORKS AND INSTALLATIONS HERE IN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY
2-3.5mm 2-3.5mm REGISTERED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.

15 AT
2-3.5mm 2-3.5mm
15 AT Computation for the total current:
2 1
15 AT 15 AT
2-3.5mm 2-3.5mm
4 3 It = [total connected load + 25% of the largest motor]
20 AT 15 AT
6
2-5.5mm 2-3.5mm
5
220 V
20 AT 20 AT It =14,103 W + (0.25)(3200W)
2-5.5mm 2-5.5mm
8 7 It = 67.74 amperes
20 AT 20 AT
10
2-5.5mm 2-5.5mm
9
Ita = (67.74 A) ( .90 )
20 AT 20 AT Ita =60.96 amperes
2-5.5mm 2-5.5mm
SPARE 11
Note: Assume 90% demand factor for commercial building
Therefore: Use 100 AT, 2P circuit breaker for main protection.

FROM THE OFFICE OF: SEAL NAME OF PROJECT: APPROVED AS PER PLAN: SHEET CONTENTS: SHEET NUMBER

NO PORTION OF THIS SET OF PLAN SHOULD BE


C:\Users\user\Documents\calimbas plan\logo copy.bmp
COPIED EITHER MANUALY OR ELECTRONICALLY SLSU ALUMNI
WITHOUT THE WRITTEN CONSENT OF THIS OFFICE.
ELECTRICAL ENGINEER OWNER
PRC No.: Date Reg. T I N No. LOCATION: BRGY. SAN ROQUE,SOGOD, SOUTHERN LEYTE LOCATION: BRGY. SAN ROQUE,SOGOD, SOUTHERN LEYTE
PTR No. Date: Place:

You might also like