219mmx64mm SAIVER – Pantone: 2925C

Integrated
Variable Refrigerant Flow
AHU/PAU
(R410A)
CONTENTS

Features of VRF AHU/PAU 2

WELAIRE i-GT Concept 9

VRF Outdoor Unit Performance Data 10

Drawings & Performance Data 12

Dimensions 13

Notes 14
Features of VRF AHU/PAU

Designing of air conditioning system is simple, no water pump, no cooling tower and no
cooling / chilled water piping
Simple control system, built-in controls for VRF outdoor unit plus field installed LMCP for
AHU/PAU
Integrated package with VRF system
Easy installation and maintenance
Simple cable and refrigerant piping connection
Max 224kW (80HP) cooling capacity
Built-in backup, interlock and heat pump operation
Long pipe run available for greater design flexibility
Excellent full load COP for VRF outdoor unit (10HP) is 3.6, 50% COP is 4.3
Custom design of AHU/PAU arrangement to improve IAQ

Flexible Design

Exhaust Air Fan


Heat Wheel or Heat Pipe (Optional)
EX
Filter
Supply Air Fan

VRF AHU/PAU
OA
EEV Control Unit RA
SA
Filter

Humidifier
(Optional) Variable
Refrigerant
Flow Outdoor
Re-heat DX Coil
Unit
(Optional)
A pair of
Refrigerant Tube

DX Cooling Coil
one
eZ Variable
Se rvic Refrigerant
Sup Flow Outdoor
ply Unit
Air
Retu
rn Ai
r
2
Simple Installation

Compare VRF AHU to chiller plant system


VRF AHU/PAU system Chiller system
om
Machine Ro
Pump Chiller Water
PAU Tank
PAU

VRF Chiller System


AHU/PAU
Simple Design √
Easy Installation √
Easy Maintenance √
Low Running Cost √
System Integration √

Better Fresh Air Treatment

Compare Custom made VRF PAU to VRF Conventional Fresh Air Pre-treated Unit
VRF PAU system Traditional VRF System for Fresh Air

Up to 6,000 l/s or even more Small air flow rate (Max. 1800l/s)
Large cooling capacity (up to 80HP) Small cooling capacity (Max. 20HP)
Large external static pressure provided (up to 1,800Pa) Limited external static pressure (Max. 150Pa)
Lots of IAQ options No space to install IAQ components
(Eg. dehumidifier, UV light, PCO, Heat pipe or heat wheel)

3
Excellent Energy Saving

Compare VRF AHU to Traditional DX AHU


COP RG
Y SAVING ●

gy
NE E

5.0
Ener in

NE
E
SAVING ●

RG
g Y SAVING ● E
VRF Outdoor (10HP)
Sav

RGY
4.0

NE
Outdoor with 2 scroll

N
ER E
GY
SAVING ●

compressor (10HP)
3.0 with "ON/OFF" control
Custeosmign
2.0 D
1.0

0 on &
100% Part Load (50%) Load % a s y I n stallati ce
E nan
Mainte

Comfort Temperature Control

Compare VRF AHU to Traditional DX AHU


- Preventive of temperature hunting

Temp.
Temp.
Supply air temperature is closer to setpoint Supply air temperature will be colder than
Zone Zone temperature is kept tightly near setpoint at needed due to excess capacity
Temperature all times by continuous load-matching operation. Zone Zone setpoint is maintained by on-off cycling
Temperature

Setpoint Setpoint
Time Time
With VRF compressor With Scroll compressor

Post-cooling unit

- Improve the existing chiller plant


60mm thick double skin casing

NEW
DX Cooling Coil
OLD
12°C 16°C
Duct AHU

r
Post-Cooling Section
or
Heat mode is standard
provision for heating or Chiller
dehumidifying ller system with
in g ch i
Ex i s t ooling capacity
JJ JJ JJ JJ JJ
f fic ient c
JJ JJ JJ JJ JJ insu

4
Control System

Compare VRF AHU to Traditional DX system


- Interlock function - Duty and Standby function
When AHU started operation, it If the duty AHU have fault, the
activates PAU to run automatically standby AHU will be cut-in
with simple wiring connection automatically in 30 seconds

Alarm occured
(Duty Unit) Unit "ON"
AHU "ON" PAU "ON" Duty & Standby Mode (Standby unit)
Automatic Mode

AHU/PAU Timer wired remote controller


-Function ON/OFF
- Mode setting
- Temperature setting (AHU only)
- Weekly program
- Alarm history

NEW

System Controller
Individual control is possible for Max. 32 AHUs.
Control of 32 AHUs / PAUs individually into 4 zones. (One zone can have up to 8 units)
Control is possible for ON/OFF, operation mode, operation monitoring, alarm monitoring,
remote controller local operation prohibition, etc…

Serial Interface for LonWorks Network


This interfaces is a communication converter for connecting LonWorks to the
control network.
From the host connected to LonWorks, basic settings of status monitoring is
LonWorks possible for up to 32 no. of AHU/PAU.
Interface Board

5
Simple Wiring Requirement

LonWorks Interface

LON
Center Control Device
LonWorks (Field Supply)
Communication Line
System Controller
(Max. 64nos. AHU/PAU)

System Overview

B K

A A
AIR HANDLING UNIT KIT TO CONNECT
A : AHU kit controller box (with control PCB)
www.eggeassociats.net

TO YOUR VENTILATION SYSTEM


5-25 kW FOR PACi
28 kW AND 56 kW FOR ECOi AND

B : AHU unit
GHP
AHU CONNECTION KIT

J
Remote control can be easily installed
PCB, Power trans, Terminal block on the AHU Kit box. Remote control Optional parts: Following functions
must be purchase separately.
are Technical Zoom
available by using different type
of · Maximum capacity: 60 HP (168
control accessories: kW)
· Maximum piping length: 180 m
CZ-RTC2 Wired remote controller · Maximum total piping: 210 m

F C : VRF outdoor unit


· Operation-ON/OFF · Elevation difference (in/out):
Expansion
valve
Thermistor x2
(Refrigerant: E1, E3)
Thermistor x2 (x1 in PACi)
(Air: Tf, Tb)
· Mode select 50 m (outdoor unit above)
· Temperature setting · Elevation difference (in/in): 4
m
* Fan operation signal can be
taken from the PCB. · In/Out capacity ratio: 50~100%.
Maximum indoor units number:
CZ-T10 terminal 2 units
· Available temperature range in
· Input signal= Operation ON/OFF Heating: -15~15.5 °C
· Available temperature range for

G
the suction air at AHU Kit: Cool:

D : Gas piping (field supplied)


OPTIONAL REMOTE CONTROLLER · Remote controller prohibition 15~24 °C / Heat: 10~30 °C
Standard wired remote controller.
CZ-RTC2
· Output signal= Operating-ON status CZ-280PAH1 // CZ-280MAH1 //
CZ-560MAH1
· Alarm output (by DC12 V) · The system controlled by the
suction air (or return air from room)
standard indoor unit. (Selectable temperature as same as
without the express authorisation of Panasonic UK Ltd.

PAW-OCT, DC12 V outlet. Option mode: Automatic / Cooling / Heating


as Cool) / Fan / Dry (but same
terminal
· The discharge air temperature
· Output signal= Cool / Heat/Fan is also controlled to prevent too-low
status or too-high air discharge in Heating. air discharge in Cooling
· Defrost (in case
· Demand control (Forcible thermostat-OFF of VRF system)

E : Liquid piping (field supplied)


· Thermostat-ON control by operating current)
· Defrost operation signal, Thermo-ON/OFF

H
states output
CZ-CAPBC2 Mini seri-para I/O · Drain pump control (Drain-pump
unit and the float switch to be supplied
PRO Club · Temperature setting by 0-10 V · External target temperature setting in local)
or 0-140 Ω via Indoor/Outdoor signal interface
CZ-CAPBC2. (Ex. 0 – 10 V) is available with
warning in order to improve the product. The total or partial reproduction of this catalogue is prohibited

Calculation software is available input signal


on

I
www.panasonicproclub.com · Room (inlet air) temp outlet by · Connectable with P-LINK system
4-20 mA
Or connect simply with your · Mode select or/and ON/OFF control · Fan control signal from the PCB
Smartphone to the PRO Club using
· Fan operation control can be used for control the air volume
this QR. for Th-off) (High/Mid/Low and LL

F : Electronic expansion valve


· Operation status output/ Alarm
output
SYSTEM & REGULATIONS. SYSTEM
OVERVIEW G: Liquid piping (Field supplied)
A: AHU Kit controller box (with control
PCB) H: Electronic expansion valve
B: AHU Kit equipment (Field supplied) C

C: AHU Kit system controller (Field I: Thermistor for Gas pipe B


C
supplied) J: Thermistor for Liquid pipe E
D: Outdoor unit A B
E
F: Gas piping (Field supplied) K: Thermister for Suction air A

L: Thermistor for Discharge air

G : Thermistor for gas pipe


L
L
H
J
I F H
J
AHU CONNECTION KIT, 28 kW K D I F
Cooling Heating Horsepower Cooling Airflow G
AND 56 kW FOR ECOi AND ECO Bypass Factor
K D
typographic errors, and may be subject to minor modifications by the manufacturer without prior

G capacity capacity Dimensions of Piping length Elevation Pipe


G

Nominal Nominal the box Diameters Intake temperature of Ambient


High / Low diff. (in/out) temperature
kW kW HP HxWxD Min / Max AHU Kit
CZ-280MAH1 m³/min Max Liquid pipe Gas pipe of outdoor unit
28.0 31.5 10 mm m Min / Max
CZ-560MAH1 5,000 / 3,500 0.9 (recommended) 420 x 280 m Inch (mm) Min / Max
56.0 63.0 20 x 160 10 / 100 Inch (mm) °C
CZ-280MAH1 + CZ-560MAH1 10,000 / 7,000 0.9 (recommended) 10 °C

H : Thermistor for liquid pipe


84.0 420 x 280 x 160 3/8 (9.52) 7/8 (22.22) Cooling:18 - 32DB
CZ-560MAH1 x2 95.0 30 15,000 / 10,500 0.9 (recommended) 10 / 100 10 Cooling: -5 - 43 DB /
112.0 420 x 280 x 160 5/8 (15.88) 1 1/8 (28.58) (13
CZ-560MAH1 x2 + CZ-280MAH1 127.0 40 20,000 / 14,000 0.9 (recommended) 10 / 100 10 - 23 WB) / Heating: -15 - 15.5 WB
140.0 420 x 280 x 160 3/4 (19.05) 1 1/4 (31.75) Heating:16

E
CZ-560MAH1 x3 155.0 50 25,000 / 17,500 0.9 (recommended) 10 / 100 10 - 30 DB
168.0 420 x 280 x 160 3/4 (19.05) 1 1/2 (38.15)
189.0 60 30,000 / 21,000 0.9 (recommended) 10 / 100 10
420 x 280 x 160 3/4 (19.05) 1 1/2 (38.15)
10 / 100 10

D
3/4 (19.05) 1 1/2 (38.15)
AHU Connection Kit / System
Combination
PACi Capacity (HP) Outdoor unit combination
2-PIPE ECOi 6N SERIES All capacities Common use for all outdoor units AHU kit combination

I : Thermistor for suction air


28 kW (10 HP) Standard and Elite
U-10ME1E81 CZ-280PAH1 (Only 1 by 1 connection
56 kW (20 HP) U-20ME1E81 is allowed)
CZ-280MAH1
84 kW (30 HP) U-16ME1E81 CZ-560MAH1
Due to the ongoing innovation of our products, the specifications of this catalogue are valid barring

112 kW (40 HP) U-14ME1E81


U-20ME1E81 U-20ME1E81 CZ-560MAH1
140 kW (50 HP) CZ-280MAH1
U-18ME1E81 U-16ME1E81 CZ-560MAH1
168 kW (60 HP) U-16ME1E81 CZ-560MAH1
ECO G AND ECO G MULTI U-20ME1E81 U-20ME1E81 CZ-560MAH1
56 kW (20 HP) U-20ME1E81 CZ-560MAH1 CZ-280MAH1
U-20GE2E5 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
CZ-560MAH1

To find out how Panasonic cares

Contact Details: Telephone: 01344

Berkshire // RG12 8FP


853182
for you, log on to: www.aircon.panasonic.e

Address: Panasonic Air Conditioning: / www.aircon.panasonic.eu


Panasonic House // Willoughby
Road // Bracknell //
u

J : Thermistor for discharge air


K : Fan local control panel (optional)

Flexible Refrigerant piping design

Level difference between


PAU/AHU & outdoor unit
50M (Outdoor unit above)
40M (Outdoor unit below)

Equivalent tubing length


available up to 120M

6
Optional - EC Plug Fan

Transformation of Power

Comparison
level for ηe(s)

Po

Features of EC Plug Fan


- Compact design
- Integrated assembly - Built in control
- Infinitely variable speed settings
- Control signal 0-10 V DC and MODBUS
- Compatible with existing BMS
- High energy saving potential

Maintenance Aspect between Centrifugal Fan & EC Plug Fan

Centrifugal Fan EC Plug Fan


Fan Bearing Regular greasing None
Fan Shaft Potential breakage None
Belt Alignment, wear & tear None
Pulley Alignment None

7
Other Features

A. Operating Range - Cooling & Heat pump mode

Heating operation range:


Extended heating operation range Outside air temperature (°C WB)
enables heating even when the outdoor
temperature is as low as -25°C. Using
a wired remote control, indoor heating -25 -20 -15 -10 -5 0 5 10 1518
temperature range can be set from 16°C
to 30°C*.
Outside air temperature (°C DB)
Cooling operation range:
-10°C DB to +52°C DB
* Depending on the type of remote controller
-10 -5 0 5 10 15 20 25 30 35 40 52

B. Extended compressor life by uniform compressor operation time

The total run-time of compressors are Compressors with histories showing shorter
monitored by a built-in microcomputer, run times are selected first, ensuring equal
which ensures that operation times of all wear and tear across all units and extended
compressors within the same refrigerant circuit the working life of the system.
are balanced.

System example
A,C : DC inverter compressor
B,D : Constant speed compressor
Load Load Load

A B C D increase
A B C D increase
A B C D increase
A B C D
* Depending on accumulated operation time of each compressor
* Compressor priority has possibility to be changed
(e.g) Case1: AACABAD, Case2: CAAADAB, Case3: AACADAB, Case 4: CAAABAD
* Also other cases available

C. Automatic backup operation in the case of compressor failure or outdoor unit malfuction
(Except for single unit installation) Even if fan motor or Even if a whole Even if a compressor in
sensor fail outdoor unit fails a single system fails
Backup operation allows uninterrupted
X
X
cooling or heating to continue whist waiting
for service. X
Users should contact their authorized
service centre as soon as fault occurs. X
NEW function The other outdoor unit The other compressor
can keep running can keep running

Automatic backup operation.

8
Innovative
CONCEPT
Green & Technolog
y Solution

VRF Dual Coil (CHW+DX) Package Air Handling Unit

Internal lining

EC plug fan

DX cooling coil

Chilled
water
coil

Features of Dual coil design


- Back-up function
- Post cooling function
- Dehumidity function
- Light-load function

Slim Type VRF Dual Coil (CHW+DX) Package Air Handling Unit (Slim VDC AHU)
F
AHU
V DC EC Plug Fan DX Coil C/W
m
Y

Sli
(Multi-fans for Water Coil variable flow
Filter section standby/duty C/W 2-way electrical
(Optional) function) valve expansion valve

Height in mm
=650

- mini shop
- Server room

Length in mm = 1450(+250)
Width in mm = 900

9
VRF Outdoor Unit Performance Data (Standard Series)

HP 10 20 30 40 50 60 70 80

U-10ME2H7 U-20ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7


U-14ME2H7 U-20ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7
Model Name
U-14ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7
U-10ME2H7 U-20ME2H7

Power Supply 380 / 400 / 415V-3-phase / 50Hz ; 380 / 400V / 3-phase / 60Hz

kW 28 56 85 113 140 168 196 224


Cooling Capacity
BTU/h 95,600 191,100 290,100 385,700 477,800 573,400 668,900 764,500

COP-Cooling W/W 5.03 3.76 4.31 3.74 4.09 3.76 3.90 3.76

Height mm 1,842 1,842 1,842 1,842 1,842 1,842 1,842 1,842

Dimension Width mm 770 1,540 2,420 3,140 4,020 4,740 5,570 6,340

Depth mm 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000

Net Weight kg 210 375 630 750 1,005 1,125 1,335 1,500

9.6/ 24.6/ 33.6/ 49.9/ 57.7/ 73.8/ 84.0/ 98.4/


Electrical Ratings-
Cooling
A 9.1/ 23.4/ 31.9/ 47.4/ 54.8/ 70.1/ 79.8/ 93.5/
8.8 22.5 30.8 45.7 52.9 67.6 76.9 90.1

Power Input kW 5.57 14.90 19.70 30.20 34.20 44.70 50.30 59.6

Starting Current A 1 2 4 4 6 6 7 8

Airflow Rate m3/h 13,440 24,300 27,840 48,600 52,140 72,900 86,340 97,200
Refrigerant Amount at
shipping
kg 5.6 9.5 16.6 19.0 26.1 28.5 34.1 38.0

External Static Pressure Pa 80 80 80 80 80 80 80 80


Gas
Pipe
mm Ø22.22 Ø28.58 Ø31.75 Ø38.10 Ø38.10 Ø38.10 Ø41.28 Ø44.45
Piping Liquid
Connections Pipe
mm Ø9.52 Ø15.88 Ø19.05 Ø19.05 Ø19.05 Ø19.05 Ø22.22 Ø22.22
Balance
Pipe
mm Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35
Ambient Temperature
Operation Range
Cooling : -10°C (DB)~+52°C (DB), Heating: -25°C (WB)~+18°C (WB)
Sound Pressure Level
Normal Mode
dB(A) 56.0 59.0 63.0 62.0 64.5 64.0 64.5 65.0
Sound Power Level
Normal mode
dB 77.0 80.0 84.0 83.0 85.5 85.0 85.5 86.0

10
VRF Outdoor Unit Performance Data (High Efficiency Series)

10 20 30 40 50 60
HP U-10ME2H7 U-20ME2H7HE U-30ME2H7 U-40ME2H7HE U-50ME2H7HE U-60ME2H7HE

U-10ME2H7 U-10ME2H7 U-14ME2H7 U-12ME2H7 U-10ME2H7 U-12ME2H7


Model Name U-10ME2H7 U-16ME2H7 U-12ME2H7 U-12ME2H7 U-16ME2H7
U-16ME2H7 U-12ME2H7 U-16ME2H7
U-16ME2H7 U-16ME2H7
Power Supply 380 / 400 / 415V-3-phase / 50Hz ; 380 / 400V / 3-phase / 60Hz

kW 28 56 85 113 140 168


Cooling Capacity
BTU/h 95,600 191,100 290,100 385,700 477,800 573,400

COP-Cooling W/W 5.03 5.05 4.31 4.45 4.58 4.24

Height mm 1,842 1,842 1,842 1,842 1,842 1,842

Dimension Width mm 770 1,600 2,420 3,660 4,490 4,900

Depth mm 1,000 1,000 1,000 1,000 1,000 1,000

Net Weight kg 210 420 630 855 1,065 1,215


Electrical Ratings-
Cooling
A 9.6/9.1/8.8 19.2/18.2/17.5 33.6/31.9/30.8 42.4/40.3/38.8 51.7/49.1/47.3 66.9/63.5/61.2

Power Input kW 5.57 11.10 19.70 25.40 30.60 39.60

Starting Current A 1 2 4 4 5 7

Airflow Rate m3/h 13,440 26,880 27,840 41,760 55,200 55,680


Refrigerant Amount
at shipping
kg 5.6 11.2 16.6 24.9 30.5 33.2
External Static
Pressure
Pa 80 80 80 80 80 80
Gas
Pipe
mm Ø22.22 Ø28.58 Ø31.75 Ø38.10 Ø38.10 Ø38.10
Piping Liquid
Connections Pipe
mm Ø9.52 Ø15.88 Ø19.05 Ø19.05 Ø19.05 Ø19.05
Balance
Pipe
mm Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35
Ambient Temperature
Operation Range
Cooling : -10°C (DB)~+46°C (DB), Heating: -25°C (WB)~+15°C (WB)
Sound Pressure Level
Normal Mode
dB(A) 53.0 59.0 63.0 63.5 64.5 66.5
Sound Power Level
Normal mode
dB 74.0 80.0 84.0 84.5 85.5 87.5

11
Drawings

H
W

Performance Data
AHU Performance Data
Standard Unit Dimensions On Coil Off Coil System
AHU Air flow
VRF Outdoor Cooling
AHU Model No. rate Height Width Length DB/RH DB
Model No. Capacity
m /s
3
mm mm mm °C/% °C kW
A1-1170H-1050W U-10ME2H7 1.49 1,210 1,050 1,595 25/55 12.5 28
A1-1450H-1350W U-20ME2H7 2.90 1,550 1,350 1,595 25/55 12.5 56
U-16ME2H7
A1-1770H-1650W 4.47 1,870 1,500 1,595 25/55 12.5 85
U-14ME2H7
U-20ME2H7
A1-1770H-1950W 5.92 1,870 1,950 1,900 25/55 12.5 113
U-20ME2H7
U-20ME2H7
A1-1930H-2250W U-16ME2H7 7.45 2,030 2,250 2,205 25/55 12.5 140
U-14ME2H7
U-20ME2H7
A1-2250H-2250W U-20ME2H7 8.94 2,250 2,250 2,205 25/55 12.5 168
U-20ME2H7

PAU Performance Data


Standard Unit Dimensions On Coil Off Coil System
AHU Air flow
VRF Outdoor Cooling
PAU Model No. rate Height Width Length DB/RH DB
Model No. Capacity
m /s
3
mm mm mm °C/% °C kW
A1-830H-1050W U-10ME2H7 0.50 950 985 1,595 35/70 15 28
A1-850H-1050W U-20ME2H7 1.00 950 985 1,595 35/70 15 56
U-16ME2H7
A1-1170H-1050W 1.50 1,430 985 1,595 35/70 15 85
U-14ME2H7
U-20ME2H7
A1-1170H-1350W 2.00 1,430 1,290 1,595 35/70 15 113
U-20ME2H7
U-20ME2H7
A1-1330H-1350W U-16ME2H7 2.50 2,030 1,290 1,900 35/70 15 140
U-14ME2H7
U-20ME2H7
A1-1330H-1650W U-20ME2H7 3.00 2,030 1,595 2,205 35/70 15 168
U-20ME2H7
Remarks:
1. Height does not include the unit base 100mm*
2. Standard length include coil and fan, external mounted per filter is 50mm**
3. Specifications are subjected to change without prior notice.

12
Dimensions (Standard Series)

10 HP
U-10ME2H7 According to the installation site, you may
Air Outlet choose the setting positionin the depth
Installation anchor hole direction of the anchor bolt from A, B or C.
8-15x21 elongated holes
A: (Installation hole pitch)
Air intake
For removing tube forward
B: (Installation hole pitch)
For removing tube downward
C: (Installation hole pitch)
1842
A:964
1000
Air intake

Air intake

953
B: 730
18
C:730

15 740
770

Top View Front View

14-16 HP According to the installation site, you may


U-14ME2H7 choose the setting positionin the depth
Air Outlet direction of the anchor bolt from A, B or C.
U-16ME2H7
Installation anchor hole
8-15x21 elongated holes A: (Installation hole pitch)
Air intake
For removing tube forward
B: (Installation hole pitch)
For removing tube downward
C: (Installation hole pitch)
1842
A:964
1000

C:730 Air intake


Air intake

953
18

15 1150
B: 730

1180

Top View Front View

20 HP
According to the installation site, you may
U-20ME2H7
choose the setting position in the depth
Air Outlet
direction of the anchor bolt from A, B or C.
Installation anchor hole
8-15x21 elongated holes A: (Installation hole pitch)
Air intake Air intake 740
For removing tube forward
B: (Installation hole pitch)
For removing tube downward
1842

C: (Installation hole pitch)


A:964
1000
Air intake

C:730 Air intake

953

15 1510
B:730
18

1540

Top View Front View

Unit in mm

13
Dimensions (High Efficiency Series)
10 HP
U-10ME2H7

According to the installation site, you may choose the setting position in the depth direction of the
anchor bolt from A, B or C.

A (Installation hole pitch) For removing tube forward


B (Installation hole pitch) For removing the downward
C (Installation hole pitch)
Top view
Installation anchor hole,
Front view
8-15x21 elongated holes Air outlet
Air Intake

B:730
1000 A:964
C:730
Air Intake
Air Intake

15 740 18 1842
770
953

12/14/16 HP
U-12ME2H7
U-14ME2H7
U-16ME2H7
According to the installation site, you may choose the setting position in the depth direction of the
anchor bolt from A, B or C.
A (Installation hole pitch) For removing tube forward
B (Installation hole pitch) For removing the downward Air outlet
C (Installation hole pitch)

Installation anchor hole,


8-15x21 elongated holes
Air Intake

Air Intake

B:730
1000 A:964
C:730

Air Intake 1842

953

15 1150 18
1180

Top view Front view

Unit in mm

14
SAIVER S.R.L
Via M. da Besozzo,
219mmx64mm SAIVER – Pantone: 2925C

16 20052 Monza (Milan) Italy.


Tel : +39. 039. 282 831
Fax : +39. 039. 202 5668
E-mail : info@saiver.com
Website: www.saiver.com

SRPC-PDFCE-VRFAHUPAU-Italy-2018.05