Culture Documents
2
170 kW, Tier 1, Chilled Water, 2640 ft
Facility Power
The facility power system provides power to all of the critical and non-critical
components within the datacenter. It consists of a single power path with N UPS
to achieve a Tier 1 redundant architecture. An optional generator has been
added to provide additional availability in the event of an extended power
outage.
The facility power system has a QED-2 switchboard with an 800 amp main bus
that feeds both the IT space and facility cooling UPSs. A 225 kVA Galaxy VM
UPS serves as the IT space UPS, and provides highly-efficient critical power in
TM
double conversion, ECO, or ECOnversion modes with a small footprint. A 40
DESIGN OPTIONS kVA Galaxy 5000 UPS supplies protected power to N+1 pumps. The main bus
This reference design can be modified as also feeds an I-Line facility cooling distribution panel, providing power to a chiller
follows without a significant effect on the in the mechanical space. The power distribution architecture from the electrical
space to the IT space utilizes a combination of LV panels and rack-based three
design’s performance attributes:
phase power distribution units (PDUs). The design can also support additional
peripheral devices like lighting, access control systems, and environmental
Add StruxureWare Power Monitoring
monitoring and control devices.
Expert
Power meters in the electrical path integrate with (optional) StruxureWare Power
Provision for load bank
Monitoring Expert to monitor power quality and allow for predictive maintenance
Change UPS batteries
& diagnostics of the system.
(classic or modular batteries,
short or long backup times) Every component in this design is built and tested to the applicable ANSI,
NEMA, UL or IEEE standards.
Add/change standby generator options
(location, tank size, fuel type) Further design details and schematics are available in the engineering package.
Packaged
Chiller Humidifier
2014Schneider
©©2014
Facility Cooling
The facility cooling design is comprised of a chilled water cooling system in the
IT space, integrated with a single chilled water loop with N+1 pumps in the
mechanical space and a single packaged chiller outdoors. Altogether, they form
a Tier 1 architecture.
The facility cooling contains a 232 kW air-cooled water chiller with a free-cooling
system. Economization is achieved with dry coolers integrated within the chiller
to save energy during favorable outdoor conditions.
The piping architecture feeds room-based Uniflair chilled water CRAHs in the IT
space. It also feeds a room-based Uniflair CRAH in the electrical space. More
information on the cooling configuration is provided in the IT space section of
DESIGN OPTIONS this document.
This design is instrumented to work with (optional) StruxureWare Cooling
This reference design can be modified as
follows without a significant effect on the Monitoring Expert.
design’s performance attributes: Further design details such as dimensions, equipment placement, temperature
set points, pipe sizing, flow rates, and pressure drops are available in the
Add StruxureWare Cooling engineering package.
Monitoring Expert
VFD Chilled
Water
Dirt/air Return
separator
VFD
Chiller
232 kW
System
bypass
Chemical dosing
pot
Chilled
Water
Supply
IT Space
A single power distribution path from the electrical space powers the Tier 1 IT
space, consisting of 25 kW of critical cooling load and 170 kW of critical IT load,
fed by PDUs in an N configuration.
61 NetShelter racks of an average 2.8 kW per rack density are arranged in a
highly scalable and adaptable “pod” fashion. Smaller starting loads can be
supported by making adjustments such as reducing the number of IT pods or
decreasing the capacity of the UPS. Likewise, larger loads can be reached by
using a “step and repeat” approach with this design as the baseline. This
flexibility drives efficiency and defers capital expenditure until needed.
Each pod is powered by floor-mount modular PDUs. Each rack is configured
DESIGN OPTIONS with a metered rack-mount PDU to enable remote monitoring of the units for
This reference design can be modified as efficiency and capacity management.
follows without a significant effect on the Uniflair chilled water room-based CRAHs, in an N configuration, control the
design’s performance attributes: removal of heat by monitoring the temperature in the room and the pressure in
the contained hot aisle.
Add environmental and security
The security of the room is maintained at multiple points. At the rack level,
management
Change rack options (tall, wide, access is controlled by a door lock and sensor. At the room level, security
deep) cameras are utilized for monitoring.
Change power distribution options
(Rack PDU type: basic, switched)
Add StruxureWare Data Center
Expert
IT SPACE ATTRIBUTES
R R R R R R R R R R
R/C-2/Z3 R/C-3/Z3 R/C-4/Z3 R/C-5/Z3 R/C-6/Z3 R/C-7/Z3 R/C-8/Z3 R/C-10/ R/C-10/ R/C-10/
Z3 Z3 Z3
R R R R R R R R R P
P/B-16/
Number of racks 61 racks
R/F-6/Z5 R/D-3/Z4 R/D-4/Z4 R/D-5/Z4 R/D-6/Z4 R/D-7/Z4 R/D-8/Z4 R/D-10/ R/D-10/
Z4 Z4 Z1
2
IT floor space 1790 ft © 2014 Schneider Electric. All rights reserved.
R R R R R R R R R R
Single or dual cord Single
R/C-2/Z3 R/C-3/Z3 R/C-4/Z3 R/C-5/Z3 R/C-6/Z3 R/C-7/Z3 R/C-8/Z3 R/C-10/ R/C-10/ R/C-10/
Z3 Z3 Z3
R
R/F-6/Z5
R
R/F-6/Z5
R
R/F-5/Z5
R
R/F-5/Z5 Containment type Hot-Aisle
Design Attributes
OVERVIEW Value Unit
Target availability Tier 1 Tier
Annualized PUE at 100% load 1.54 / 1.36 / 1.43
Data center IT capacity 170 kW
2
IT & facility floor space 2640 ft
Average density 2.8 kW/rack
FACILITY POWER Value Unit
Total amps (main bus) 800 A
Input voltage (main bus) 480 V
Switchboard kAIC 65 kA
Power path Single
Generator redundancy N (Optional)
IT space UPS capacity 202/225 kW/kVA
IT space UPS redundancy N
IT space UPS runtime @ rated load 5 minutes
IT space UPS output voltage 480 V
Facility cooling UPS capacity 36/40 kW/kVA
Facility cooling UPS redundancy N
Facility cooling UPS runtime @ rated load 5 minutes
FACILITY COOLING Value Unit
Total cooling capacity 232 kW
Input voltage 480 V
Heat rejection medium Chilled Water
Mechanical redundancy N
Outdoor heat exchange Air-Cooled, Packaged Chiller
Coolant supply temperature 59 F
Coolant return temperature 69 F
Storage tank size None gallons
Ride-through time None minutes
Economizer type Water-Side
IT SPACE Value Unit
IT load 170 kW
Input voltage 480 V
Supply voltage to IT 240 V © 2014 Schneider Electric. All rights reserved.
Control level: Experts, on site or remotely, can control process performance and
ensure business continuity in real time, while tracking energy consumption in a highly
critical and secure environment.
Operations level: Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.
Enterprise level: C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to conserve
enterprise-wide resources.
StruxureWare for Data Centers allows for flexibility when requirements and
implementation strategies change over time. StruxureWare software applications
and suites simplify integration time, improve reliability, enhance visibility to energy
information, and streamline operational efficiency.
>
© 2014 Schneider Electric. All rights reserved.
Demo:
Visit www.apc.com/software to learn more about StruxureWare for Data Centers!
Engineering Package
Bill of materials
One-line schematics
> Click here to register to receive the Engineering Package for this design, or email
ReferenceDesigns@Schneider-Electric.com.