Professional Documents
Culture Documents
201709
Engineering Data
FXMQ-PAVE
50 / 60 Hz
FXMQ-PAVE EDFMT391738
FXMQ-PAVE
Ceiling Mounted Duct Type
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................8
4. Piping Diagrams........................................................................................13
5. Wiring Diagrams........................................................................................14
6. Electric Characteristics..............................................................................15
7. Safety Devices Setting..............................................................................16
8. Capacity Tables.........................................................................................17
8.1 Cooling Capacity for Te: Auto..........................................................17
8.2 Cooling Capacity for Te: 6°C...........................................................17
8.3 Cooling Capacity for Te: 9°C...........................................................18
8.4 Heating Capacity..............................................................................18
9. Fan Performances.....................................................................................19
10. Airflow Auto Adjustment Characteristics...................................................28
11. Sound Levels.............................................................................................36
12. Centre of Gravity.......................................................................................41
13. Accessories...............................................................................................42
13.1 Optional Accessories (for Unit)........................................................42
13.2 Optional Accessories (for Controls).................................................43
14. Installation Manual....................................................................................44
1
FXMQ-PAVE EDFMT391738
1. Lineup
2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP
Capacity index 20 25 31.25 40 50 62.5 80 100 125 140
FXMQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE
FXMQ 20PAVS 25PAVS 32PAVS 40PAVS 50PAVS 63PAVS 80PAVS 100PAVS 125PAVS 140PAVS
(for Thailand)
FXMQ 20PAV4 25PAV4 32PAV4 40PAV4 50PAV4 63PAV4 80PAV4 100PAV4 125PAV4 140PAV4
(for Indonesia)
2
FXMQ-PAVE EDFMT391738
2. Specifications
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
3
FXMQ-PAVE EDFMT391738
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
4
FXMQ-PAVE EDFMT391738
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
5
FXMQ-PAVE EDFMT391738
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
6
FXMQ-PAVE EDFMT391738
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
7
FXMQ-PAVE EDFMT391738
3. Dimensions
3D105236
8
FXMQ-PAVE EDFMT391738
FXMQ40PAVE
Unit: mm
3D105231
9
FXMQ-PAVE EDFMT391738
FXMQ50PAVE
Unit: mm
3D105232
10
FXMQ-PAVE EDFMT391738
FXMQ63PAVE / FXMQ80PAVE
Unit: mm
3D105233
11
FXMQ-PAVE EDFMT391738
3D105235
12
FXMQ-PAVE EDFMT391738
4. Piping Diagrams
4D104913
13
FXMQ-PAVE EDFMT391738
5. Wiring Diagrams
3D103336
14
FXMQ-PAVE EDFMT391738
6. Electric Characteristics
4D104911
15
FXMQ-PAVE EDFMT391738
16
FXMQ-PAVE EDFMT391738
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
17
FXMQ-PAVE EDFMT391738
For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.0 1.0 1.3 1.3 1.6 1.6 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
FXMQ25PAVE 25 1.3 1.3 1.6 1.6 2.0 1.9 2.2 2.0 2.3 1.9 2.4 1.8 2.6 2.0
FXMQ32PAVE 32 1.6 1.6 2.0 2.0 2.6 2.3 2.9 2.4 2.9 2.3 3.1 2.4 3.3 2.4
FXMQ40PAVE 40 2.1 2.1 2.6 2.6 3.3 3.3 3.6 3.3 3.8 3.2 3.9 3.1 4.1 3.3
FXMQ50PAVE 50 2.6 2.6 3.2 3.2 4.0 3.8 4.4 3.9 4.6 3.9 4.9 3.8 5.1 3.3
FXMQ63PAVE 63 3.2 3.2 4.0 4.0 5.1 4.6 5.6 4.7 5.8 4.7 6.2 4.7 6.5 4.7
FXMQ80PAVE 80 4.2 4.1 5.1 5.0 6.5 5.9 7.2 6.0 7.4 6.0 7.8 5.8 8.2 6.0
FXMQ100PAVE 100 5.2 5.0 6.4 6.0 8.0 7.0 8.9 7.3 9.2 7.3 9.7 7.1 10.2 7.1
FXMQ125PAVE 125 6.5 6.2 8.0 7.5 10.1 8.8 11.2 9.1 11.6 9.0 12.2 8.9 12.8 8.8
FXMQ140PAVE 140 7.5 7.0 9.2 8.6 11.7 10.0 12.8 10.4 13.2 10.4 13.9 10.1 14.6 10.3
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
18
FXMQ-PAVE EDFMT391738
9. Fan Performances
FXMQ20PAVE / FXMQ25PAVE
3D062537B
19
FXMQ-PAVE EDFMT391738
FXMQ32PAVE
3D062538B
20
FXMQ-PAVE EDFMT391738
FXMQ40PAVE
3D060456D
21
FXMQ-PAVE EDFMT391738
FXMQ50PAVE
3D060457E
22
FXMQ-PAVE EDFMT391738
FXMQ63PAVE
3D060458D
23
FXMQ-PAVE EDFMT391738
FXMQ80PAVE
3D060459C
24
FXMQ-PAVE EDFMT391738
FXMQ100PAVE
3D060460D
25
FXMQ-PAVE EDFMT391738
FXMQ125PAVE
3D060461D
26
FXMQ-PAVE EDFMT391738
FXMQ140PAVE
3D063787A
27
FXMQ-PAVE EDFMT391738
FXMQ20PAVE / FXMQ25PAVE
3D062539B
28
FXMQ-PAVE EDFMT391738
FXMQ32PAVE
3D062540B
29
FXMQ-PAVE EDFMT391738
FXMQ40PAVE
3D060577E
30
FXMQ-PAVE EDFMT391738
FXMQ50PAVE
3D060578E
31
FXMQ-PAVE EDFMT391738
FXMQ63PAVE
3D060579E
32
FXMQ-PAVE EDFMT391738
FXMQ80PAVE
3D060580E
33
FXMQ-PAVE EDFMT391738
FXMQ100PAVE
3D060581E
34
FXMQ-PAVE EDFMT391738
FXMQ125PAVE
3D060582E
35
FXMQ-PAVE EDFMT391738
FXMQ20PAVE / FXMQ25PAVE
4D062535A
FXMQ32PAVE
4D062536A
36
FXMQ-PAVE EDFMT391738
FXMQ40PAVE
4D060446C
FXMQ50PAVE
4D060428C
37
FXMQ-PAVE EDFMT391738
FXMQ63PAVE
4D060447C
FXMQ80PAVE
4D060429C
38
FXMQ-PAVE EDFMT391738
FXMQ100PAVE
4D060448C
FXMQ125PAVE
4D060449C
39
FXMQ-PAVE EDFMT391738
FXMQ140PAVE
4D063786A
40
FXMQ-PAVE EDFMT391738
4D104912
41
FXMQ-PAVE EDFMT391738
13. Accessories
13.1 Optional Accessories (for Unit)
Model
Item
FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE
High efficiency 65% KAF372AA36 KAF372AA56 KAF372AA80
filter 90% KAF373AA36 KAF373AA56 KAF373AA80
Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80
Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80
Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80
White KTBJ25K36W KTBJ25K56W KTBJ25K80W
Fresh
Service panel KTBJ25K36F KTBJ25K56F KTBJ25K80F
white
Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T
Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A
Model
Item
FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
High efficiency 65% KAF372AA80 KAF372AA160
filter 90% KAF373AA80 KAF373AA160
Filter chamber KDDF37AA80 KDDF37AA160
Long life replacement filter KAF371AA80 KAF371AA160
Long life filter chamber kit KAF375AA80 KAF375AA160
White KTBJ25K80W KTBJ25K160W
Fresh
Service panel KTBJ25K80F KTBJ25K160F
white
Brown KTBJ25K80T KTBJ25K160T
Air discharge adaptor KDAJ25K71A KDAJ25K140A
C: 3D104914
42
FXMQ-PAVE EDFMT391738
Model
Item
FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE
Cooling Only BRC4C66 (Note 4)
Wireless
Remote controller Heat Pump BRC4C65 (Note 4)
Wired BRC1C62 (Note 4)
Navigation remote controller (Wired remote controller) BRC1E62 (Note 4, 5)
Simplified remote controller (Exposed type) BRC2C51
Remote controller for hotel use (Concealed type) BRC3A61
Adaptor for wiring H KRP1C64
Wiring adaptor for electrical appendices (1) H KRP2A61
Wiring adaptor for electrical appendices (2) H KRP4AA51
Remote sensor (for indoor temperature) KRCS01-4B
Installation box for adaptor printed circuit board KRP4A97 (Note 2, 3)
External control adaptor for outdoor unit H DTA104A61
Adaptor for multi tenant H DTA114A61
Model
Item
FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Cooling Only BRC4C66 (Note 4)
Wireless
Remote controller Heat Pump BRC4C65 (Note 4)
Wired BRC1C62 (Note 4)
Navigation remote controller (Wired remote controller) BRC1E62 (Note 4, 5)
Simplified remote controller (Exposed type) BRC2C51
Remote controller for hotel use (Concealed type) BRC3A61
Adaptor for wiring H KRP1C64
Wiring adaptor for electrical appendices (1) H KRP2A61
Wiring adaptor for electrical appendices (2) H KRP4AA51
Remote sensor (for indoor temperature) KRCS01-4B
Installation box for adaptor printed circuit board KRP4A97 (Note 2, 3)
External control adaptor for outdoor unit H DTA104A61
Adaptor for multi tenant H DTA114A61
C:3D104915A
Notes:
1. Installation box is necessary for each adaptor marked H.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.
5. Auto airflow rate can be set only via wired remote controller BRC1E62. Cannot be set via other remote controllers.
43
FXMQ-PAVE EDFMT391738
English 1
3P432203-1B
44
FXMQ-PAVE EDFMT391738
2 English
3P432203-1B
45
FXMQ-PAVE EDFMT391738
NOTE
• If you wish to use a remote controller that is not listed in
Table 1, select a suitable remote controller after consulting
catalogs and technical materials.
English 3
3P432203-1B
46
FXMQ-PAVE EDFMT391738
b. Items to be checked at time of delivery (2) Use hanging bolts to install the indoor unit. Check that the
place of installation withstands the weight of the indoor unit.
Items to be checked Check
Secure the hanging bolts with proper beams if necessary.
Are you sure the control box lid, air filter, air inlet grille, and
(length: mm)
air outlet grille are mounted?
Min. 20
Did you explain about operations while showing the
operation manual to your customer?
*H2=Min. 620
Did you deliver the operation manual along with the
Min. 450
Min. 2500
Ceiling
Did you deliver instruction manual, if any, for the field
supplies to the customer?
Min. 700 (service space)
c. Points for explanation about operations Floor surface
The items with WARNING and CAUTION marks in the operation
manual are the items pertaining to possibilities for bodily injury and • The H1 dimension indicates the [Required installation place]
material damage in addition to the general usage of the product. height of the product. The dimensions indicate the
Accordingly, it is necessary that you make a full explanation about • Determine the H2 dimension by minimum required space of
the described contents and also ask your customers to read the maintaining a downward slope of installation.
operation manual. at least 1/100 as specified in
“7. DRAIN PIPING WORK”. Fig. 2-1
631 (450×450)
• Where sufficient clearance for maintenance and service (Hanging bolt pitch)
can be ensured. (Refer to Fig. 2-1)
Control box
• Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the
installation manual of the outdoor unit.)
500
CAUTION
• Install the indoor and outdoor units, power supply wiring and
C
B
connecting wires at least 1 meter away from televisions or Air outlet Air inlet
radios in order to prevent image interference or noise.
Inspection hatch 2
(Depending on the radio waves, a distance of 1 meter may (450 x 450) Bottom of unit
not be sufficient enough to eliminate the noise.)
(For remove drain pan and
• In the case of the installation of a wireless remote controller, change part) Hanging bolt (× 4)
the transmission distance of the wireless remote controller * In case can work at space
may be shortened if the room has a fluorescent light of of below product, inspection
hatch 2 is unnecessary.
electronic lighting type (i.e., an inverter or rapid-start
fluorescent light). Keep the distance between the receiver
and the fluorescent light as far as possible.
4 English
3P432203-1B
47
FXMQ-PAVE EDFMT391738
• FXMQ20 • 25 • 32 • 40 type (4) Install the hanging bolts. Make sure that the hanging bolts
700 Inspection hatch 1 are M10 in size.
• Use hole-in anchors if the hanging bolts already exist;
200 or less (450×450)
631
(Hanging bolt pitch) otherwise use embedded inserts and embedded
foundation bolts so that they will withstand the weight
Control box of the unit.
Adjust the distance to the ceiling surface in advance.
C
B
Air inlet
Long nut or turn-buckle
unit size +300 or more) hanging bracket. (Refer to Fig. 3) At that time, the fall of
Control box the washer (11) for the hanging bracket can be
prevented if the washing fixing plate (9) is used.
Min. D=B+300
English 5
3P432203-1B
48
FXMQ-PAVE EDFMT391738
(2) Make adjustments so that the unit will be in the right (1) Connect the piping.
position. • The outdoor unit is filled with refrigerant.
(3) Check the level of the unit. • When connecting or disconnecting piping to or from the
(4) Remove the washer fixing plates for the falling prevention of unit, be sure to use two spanners and two torque
the washers for the hanging brackets, tighten the nuts on wrenches. (Refer to Fig. 4)
the upper side, and securely fix the unit. Torque wrench
Level
Spanner
Hanging bracket
Flare nut
Piping union
A
φ 12.7 49.5 – 60.3 N·m 16.2 – 16.6
if the ambient temperature is high, or otherwise dew
condensation may result on the surface of the insulation φ 15.9 61.8 – 75.4 N·m 19.3 – 19.7
material.〉
〈Make sure that the refrigerant is R410A before refrigerant CAUTION
piping work. If the refrigerant is different, the air conditioner
will not operate normally.〉 • Do not excessively tighten the flare nut.
Doing so will break the flare nut and refrigerant leakage may
CAUTION result.
This product uses new refrigerant (R410A) only. Be sure to • Make sure that all parts around the flare are free of oil.
keep the items on the right-hand side and conduct the The drain pan and the resin part may be deteriorated if oil is
installation work. attached.
• Use a dedicated pipe cutter and flare tool for R410A. • If no torque wrenches are available, refer to Table 3 as a
• When connecting the flare, apply ether oil or ester oil standard.
only to inner side of the flare. When the flare nut is tightened with the spanner, the
• Be sure to use the flare nut provided with the unit. (Do tightening torque should increase suddenly. Tighten the
not use a different flare nut (such as a type-1 flare nut), flare nut further for the corresponding angle shown in
or otherwise refrigerant leakage may result.) Table 3.
• Perform the curing of the piping with pinching or taping
of the piping in order to prevent the intrusion of dirt, Table 3
dust, and moisture into the piping.
Recommended arm length of
Pipe size Further tightening angle
tool
CAUTION φ 6.4 60 to 90 degrees Approx. 150mm
• Be sure to use the specified type of refrigerant for the φ 9.5 60 to 90 degrees Approx. 200mm
refrigeration cycle and do not contaminate the φ 12.7 30 to 60 degrees Approx. 250mm
refrigerant with air. φ 15.9 30 to 60 degrees Approx. 300mm
• Ventilate the room in case of refrigerant leakage during
installation work. (2) On completion of installation work, check that there is no
gas leakage.
6 English
3P432203-1B
49
FXMQ-PAVE EDFMT391738
(3) Refer to the illustration on the right-hand side and be sure to • Perform nitrogen substituent or apply nitrogen into the
perform heat insulation work on the piping joints after gas refrigerant piping (see NOTE 1) in the case of refrigerant
leakage checks. (Refer to Fig. 6) piping blazing (see NOTE 2). Then perform the flare
connection of the indoor unit. (Refer to Fig. 7)
Heat insulation procedure for liquid piping
Insulation for fitting (4) (accessory) Refrigerant Pressurereducing valve
Insulation material piping
Flare nut joint Part to be
for piping Taping
(on unit side) brazed
Make sure that hands
Middle sealing pad (7) valve
Attached to the seam faces
upward. (accessory) Nitrogen
the surface.
Main unit Nitrogen
Clamp (8) Fig. 7
(accessory)
NOTE
Liquid pipe 1. At the time of blazing, set the pressure of nitrogen to
approximately 0.02 MPa (close to the pressure of a
breeze coming in contact with the cheek) with a
decompression valve.
Gas pipe 2. Do not use flux at the time of blazing and connecting the
refrigerant piping. Use a copper phosphorus brazing alloy
Fig. 6 (BCuP-2: JIS Z 3264/BCu 93P-710/795: ISO3677), which
does not require flux, for blazing.
Heat insulation procedure for gas piping (Flux has a bad influence on the refrigerant piping. Chlo-
rine-based flux will cause piping corrosion. Furthermore, if
Insulation for fitting (5) (accessory)
Insulation material it contains fluorine, the flux will deteriorate refrigerant oil.)
Flare nut joint
for piping
• As for the branching of the refrigerant piping or refrigerant,
(on unit side) Make sure that
Middle sealing pad (7) refer to the installation manual provided with the outdoor unit.
Attached to the seam faces
upward. (accessory)
the surface.
Clamp (8)
7. DRAIN PIPING WORK
(accessory) (1) Conduct drain piping work.
Refrigerant
Insulation material Wrap the insulation material Check that the piping
piping
for piping (field supply) around the portion from the ensures proper draining.
surface of the main unit to the • Make sure that the
upper part of the flare nut joint. diameter of the piping Drain socket
excluding the rising part
Socket for
• Use the insulation for fitting (4) and (5) provided to the is the same as or larger maintenance
liquid piping and gas piping, respectively, and conduct than the diameter of the connecting (with rubber cap)
heat insulation work. pipe (vinyl chloride pipe with an outer diameter of
(Tighten both edges of the insulation for fitting (4) and (5) 32 mm and a nominal inner diameter of 25 mm).
for each joint with the clamp (8).) • Make sure that the piping is short enough with a down-
• Make sure that the joint of the insulation for fitting (4) and ward slope of at least 1/100 and that there is no air
(5) for the joint on the liquid piping and gas piping side bank formed. No drain trap is required.
faces upward.
• Wrap the middle sealing material (7) around the CAUTION
insulation for fitting (4) and (5) for the joint (flare nut • The drain piping will be clogged with water and water
part). leakage may result if the water is accumulated in the drain
piping.
CAUTION
• Conduct drain-up piping work if the gradient is
• Be sure to perform the heat insulation of the local piping
insufficient.
up to the piping joint.
• Attach a support bracket at 1 to 1.5 m intervals for the
If the piping is exposed, dew condensation may result.
Furthermore, a burn may be caused if a human body comes prevention of piping deflection.
in contact with the piping. Support bracket
1 - 1.5 m
English 7
3P432203-1B
50
FXMQ-PAVE EDFMT391738
• Be sure to use the drain hose (2) and metal clamp (1). (2) Check the smooth draining of the piping on completion of
Insert the drain hose (2) deep into the base of the the installation of the piping.
drain socket, and securely fasten the metal clamp (1)
[Before electrical work]
within the taped part on the insertion front end of the
hose.
Be sure to fasten the screw of the metal clamp (1) until CAUTION
the margin of the screw thread decreases to 4 mm or • A licensed electrical engineering technician must conduct
less. electrical wiring work (including grounding work).
• If no licensed electrical engineering technician is
Metal clamp (1)
available, take steps 3 and 4 after the test operation of
(accessory)
the air conditioner is finished.
Tape Drain hose (2) 1. Remove the control box lid, and connect the single-
(accessory) phase electric wires to terminals L and N of the terminal
block and the ground wire to the ground terminal.
NOTE Perform wiring according to 10-1 CONNECTING POWER
SUPPLY, GROUND, REMOTE CONTROLLER, AND
Be sure to follow the instructions as below.
TRANSMISSION WIRING in 10. WIRING EXAMPLE
• Do not connect the drain piping directly to a sewer that
AND HOW TO SET THE REMOTE CONTROLLER.
smells of ammonia.
The ammonia in the sewer may reach through the drain
CAUTION
piping and corrode the heat exchanger of the indoor unit.
• Do not bend or twist the provided drain hose (2) in order • In order not to impose tension on the wire connections,
not to impose excessive force on the hose. (Doing so perform clamping securely with the provided clamp (8)
may result in water leakage.) specified in 3 in 10-1 CONNECTING POWER SUPPLY,
• Take the procedure shown in the following illustration to GROUND, REMOTE CONTROLLER, AND TRANSMISSION
perform concentrated drain piping. WIRING.
2. Check that the control box lid is closed before turning the
0 - 467 mm
8 English
3P432203-1B
51
FXMQ-PAVE EDFMT391738
Drain pump position Connection method of ducts on air inlet and outlet sides.
Inspection window • Connect the field supply duct in alignment with the inner side
Socket for maintenance of the flange.
(with rubber cap) Screw (3 positions) • Connect the flange and unit with the flange connection screw
Plastic water container (3).
Water inlet lid
• Wrap aluminum tape around the flange and duct joint in order
• On completion of the drainage check, refer to the following to prevent air leakage.
illustration, attaching insulation for drain socket (14) Flange on air inlet side Flange on air outlet side
without gap, and insulation from the top of drain hose (2) (provided with the unit) (provided with the unit)
• clamp of metal clamp (1) using large sealing pad (6).
Screws for duct Insulation material
flanges (3) (field supply)
Large sealing pad (6) (accessory) Screws
(accessory) Air inlet Unit Air outlet for duct
Pile on (14) and roll flanges (3)
Insulation material Canvas duct (accessory)
(field supply) (field supply)
Insulation for drain
socket (14) Shall not have gap
(accessory)
CAUTION
Start roll from near Connect the flange and unit with the flange connection screw (3)
tightening area of metal regardless of whether the duct is connected to the air inlet side.
clamp (1) Roll large sealing pad (6)
to make end side of clamp
fixture to be 2 layers
Metal clamp (1)
(accessory) 9. ELECTRIC WIRING WORK
Large sealing pad (6)
Drain hose (2) (accessory) 9-1 GENERAL INSTRUCTIONS
(accessory)
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
8. DUCT WORK • For electric wiring work, refer to also “Wiring diagram”
attached to the control box lid.
Pay the utmost attention to the following items and conduct • For remote controller wiring details, refer to the installation
the ductwork. manual attached to the remote controller.
• Check that the duct will not be in excess of the setting range • All wiring must be performed by an authorized electrician.
of external static pressure for the unit. (Refer to the technical • This system consists of multiple indoor units. Mark each
datasheet for the setting range. Each model has each setting indoor unit as unit A, unit B..., and be sure the terminal board
range of external static pressure.) wiring to the outdoor unit and BS unit are properly matched.
• Attach a canvas duct each to the air outlet and air inlet so that If wiring and piping between the outdoor unit and an indoor
the vibration of the equipment will not be transmitted to the unit are mismatched, the system may cause a malfunction.
duct or ceiling. • A circuit breaker capable of shutting down power supply to
Use a sound-absorbing material (insulation material) for the the entire system must be installed.
lining of the duct and apply vibration insulation rubber to the • Refer to the installation manual attached to the outdoor unit
hanging bolts. for the size of power supply wiring connected to the outdoor
• At the time of duct welding, perform the curing of the duct so unit, the capacity of the circuit breaker and switch, and wiring
that the sputter will not come in contact with the drain pan for instructions.
the filter. • Be sure to ground the air conditioner.
• If the metal duct pass through a metal lath, wire lath, or metal • Do not connect the ground wire to gas and water pipes,
plate of a wooden structure, separate the duct and wall lightning rods, or telephone ground wires.
electrically. • Gas pipes : might cause explosions or fire if gas leaks.
• Be sure to heat insulate the duct for the prevention of dew • Water pipes : no grounding effect if hard vinyl piping is
condensation. (Material: Glass wool or styrene foam; used.
Thickness: 25 mm) • Telephone ground wires or lightning rods : might cause
• Be sure to attach the field supply air filter to the air inlet of the abnormally high electric potential in the ground during
unit or field supply inlet in the air passage on the air suction lighting storms.
side. (Be sure to select an air filter with a duct collection
efficiency of 50 weight percent.)
English 9
3P432203-1B
52
FXMQ-PAVE EDFMT391738
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) (2) Lay the wires in the control box through the wire inlet on the
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A) side of the control box.
FXMQ20PAVE
FXMQ25PAVE High-voltage wiring inlet
FXMQ32PAVE Power supply wiring
Sheathed (High voltage)
FXMQ40PAVE H05VV- wire Earth wiring (High voltage)
FXMQ50PAVE U3G 2.5 mm2 (2 wire) 0.75 -
16A 1.25 mm2
FXMQ63PAVE (NOTE 1) (NOTE 3) (NOTE 2) CAUTION
FXMQ80PAVE
• Do not lay the remote controller wiring or transmission wiring
FXMQ100PAVE along with the power supply wiring or other electric wiring in
FXMQ125PAVE the same route. Separate the remote controller wiring and
FXMQ140PAVE
transmission wiring at least 50 mm from the power supply
wiring or other electric wiring, or otherwise malfunctions or
Allowable length of transmission wirings and remote controller failures may be caused by external electric noise that may
wiring are as follows. interfere with the remote controller wiring and transmission
(1) Outdoor unit – Indoor unit: wiring.
Max. 1000 m (Total wiring length: 2000 m) • For the installation and wiring of the remote controller, refer
(2) Indoor unit – Remote controller: to the remote controller installation manual provided with the
Max. 500 m remote controller.
• For power supply wiring, refer to the wiring diagram as well.
• Be sure to connect the remote controller wiring and
transmission wiring correctly to the right terminal block.
10 English
3P432203-1B
53
FXMQ-PAVE EDFMT391738
(3) Follow the instructions below, and lay the wires in the (5) Mount the provided wire fixing bracket (12) with the wire
control box. fixing screw (13). Fix each wire with the provided clamp (8).
Transmission wiring
Fix clamp material (8) at Low voltage wiring
accessory fixture on the connection method
Remote
control wiring
Remote controller wiring
control box. • If stranded About of sleeve area
wires are used, 7 mm Power supply wiring
do not solder After Earth wiring
Transmission wiring the front end scalping
(Low voltage) of the wires. wiring,
twisted
Remote controller wiring together 70~90mm
(Low voltage) PROHIBITED
Never connect Operation
the power supply terminal
(X2M)
strip
wiring. Transmission
Pass through wiring Clamp material
internal control box (No polarity) (8) (accessory)
P1 P2 F1 F2 T 1 T2
within sleeve area
(4) Put the control box lid, and wrap the wire sealing material Be sure to follow the instructions provided below if the
(Small) (10) around the wires so as to block the wire specified terminals cannot be used.
through holes. Otherwise, abnormal heat may be generated as a result
of the loosening of the wires.
Wire through
holes Connect the wires Do not connect a Do not connect
evenly. wire to the single wires different
side only. from each other in
Putty or insulation diameter.
Sealing material material
small (10) (Field supply)
(Accessories part)
Transmission wire • earth wire • If stranded wires are used, do not solder the front end of the
• power supply wire or remote
controller wiring wires.
• Connect proper wires securely and fix the wires so that
external force will not be imposed on the terminals.
• Use an appropriate screwdriver to tighten the terminal
screws. The screw heads may be damaged if the screwdriver
CAUTION
is too small and the terminal screws will not be tightened
• After all the wiring connections are done, fill in any gaps in properly.
the through holes with putty or insulation (procured locally) to • Do not tighten the terminal screws excessively, or otherwise
prevent small animals and insects from entering the unit from the screw heads may be damaged.
outside. (If any do get in, they could cause short circuits in • Refer to the table below for the required tightening torque
the control box.) values of the terminal screws.
Tightening torque (N·m)
Terminal block for remote controller
0.80 - 0.96
and transmission wires
Terminal block for power supply 1.18 - 1.44
English 11
3P432203-1B
54
FXMQ-PAVE EDFMT391738
No. 1 system: When using 1 remote controller for 1 indoor No. 3 system: When including BS unit
unit
Power supply
single phase
Power supply Power supply Power supply
50Hz 220-240V
single phase single phase single phase
50Hz 220-240V 50Hz 220-240V 50Hz 220-240V or
or or or single phase Outdoor unit BS unit
60Hz 220V
single phase single phase single phase
60Hz 220V Outdoor unit 60Hz 220V 60Hz 220V L N
IN/D OUT/D OUT/D IN/D
F1 F2 F1 F2 F1 F2 F1 F2
L N L N L N
IN/D OUT/D
F1 F2 F1 F2
L N P1 P2 F1 F2 T1 T2
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
[ PRECAUTIONS ]
No. 2 system: For group control or use with 2 remote
1. If no earth leakage breaker is required, install a breaker or
controllers
load switch with a fuse for the wiring. If an earth leakage
breaker is required, make sure that the earth leakage
Power supply
single phase breaker is designed to protect the air conditioner from
50Hz 220-240V ground faults, overloads, and short-circuiting.
or 2. The remote controller wiring (P1 and P2) and transmission
single phase
60Hz 220V Outdoor unit Note) There is not need to set the indoor unit
wiring (F1 and F2) have no polarity.
L N address when using group control.
IN/D OUT/D
F1 F2 F1 F2 (It is automatically set when the power 10-3 CONTROL BY 2 REMOTE CONTROLLERS
is turned on.)
(Controlling 1 indoor unit by 2 remote controllers)
• Set one of the remote controllers to main and the other to sub
in the case of remote control with two remote controllers.
Lower part of
remote controller
12 English
3P432203-1B
55
FXMQ-PAVE EDFMT391738
(2) Set the main/sub switch on one of the remote controller • For setting and operation, refer to the “FIELD SETTING” in
PCBs to sub. (Keep the switch of the other remote controller the installation manual of the remote controller.
PCB set to main.)
SECOND
CODE NO.
MODE NO.
S FIRST
(Factory setting)
M CODE NO.
SETTING FIELD SET
Remote controller MODE
PC board
Only one remote
S
controller needs to be • Set the remote controller to the “FIELD SET MODE”. For
M
changed if factory details, refer to the “HOW TO SET IN THE FIELD”, in the
settings have
remained untouched. remote controller manual.
• When in the “FIELD SET MODE”, select “MODE NO.
12”, then set the “FIRST CODE NO.” to “1”. Then set
10-4 COMPUTERISED CONTROL (FORCED OFF “SECOND CODE NO.” to “01” for FORCED OFF and “02”
AND ON/OFF OPERATION) for ON/OFF OPERATION. (FORCED OFF at factory set)
(1) Wire specifications and how to perform wiring
• Connect the input from outside to terminals T1 and T2 of With Wireless Remote Controller Used
the terminal block for remote controller. Set the wireless remote controller address before using the
wireless remote controller.
For the setting method of the address, refer to the operation
F2 T1 T2 manual provided with the wireless remote controller.
FORCED NOTE
OFF
• A “MODE NO.” is set on a group basis. To make a mode
Input A setting on a room unit basis or check the setting made, however,
set the corresponding mode number in the parentheses.
Wire specification Sheathed vinyl cord or cable (2 wire) 1. Settings for Optional Accessories
Gauge 0.75 - 1.25 mm
2 • In the case of connecting optional accessories, refer to
the operation manuals provided with the optional
Length Max. 100 m
accessories and make necessary settings.
Contact that can ensure the minimum appli-
External terminal 2. External Static Pressure Settings
cable load of 15 V DC, 10 mA.
Make settings in either method (a) or method (b) as
(2) Actuation explained below. (FXMQ140PAVE cannot be selected
• The following table explains FORCED OFF and ON/OFF method (a). Please select method (b).)
OPERATIONS in response to Input A. (a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is
FORCED OFF ON/OFF OPERATION automatically adjusted to the rated quantity.
Input “ON” stops operation (impossible by Input OFF → ON turns (1) Check that power supply wiring to the air conditioner
remote controllers.) ON unit. is completed along with duct installation. If a closing
damper is installed in the air-conditioning system,
Input OFF enables control by remote con- Input ON → OFF turns make sure that the closing damper is opened.
troller. OFF unit.
Furthermore, check that the air filter as a field supply
(3) How to select FORCED OFF and ON/OFF OPERATION is attached to the air passage on the suction side.
• Turn the power on and then use the remote controller to (2) If there are a number of air outlets and inlets, adjust the
select operation. throttles so that the airflow rate of each air outlet and
inlet will coincide with the designed airflow rate. At that
10-5 CENTRALIZED CONTROL time, operate the air conditioner in “fan operation mode”.
• For centralized control, it is necessary to designate the group To change the airflow rate, press and set the airflow
No. For details, refer to the manual of each optional control- adjustment button of the remote controller to HH, H, or L.
lers for centralized control. (3) Make settings for airflow automatic adjustment. After
setting the air conditioner to “fan operation mode”,
stop the air conditioner, go to “FIELD SET MODE”,
11. FIELD SETTING select “MODE NO. 21” (11 in the case of group
settings), set the setting “FIRST CODE NO.” to 7, and
NOTE
set the setting “SECOND CODE NO.” to 03.
• Before the test operation of the outdoor unit as explained in Return to normal mode after these settings, and press
12. TEST OPERATION, be sure to make the following field the ON/OFF OPERATION button. Then the operation
settings as explained in 11. FIELD SETTING. lamp will be lit and the air conditioner will go into fan
operation for airflow automatic adjustment. Do not
Make sure the control box lids are closed on the indoor and adjust the throttles of the air outlets or inlets during
outdoor units. automatic adjustment of the air conditioner. After the
Field setting must be made from the remote controller in air conditioner runs approximately one to eight
accordance with the installation condition. minutes, the air conditioner will finish airflow
• Setting can be made by changing the “MODE NO.”, “FIRST adjustment automatically, the operation lamp will be
CODE NO.”, and “SECOND CODE NO.”. turned OFF, and the air conditioner will come to a stop.
English 13
3P432203-1B
56
FXMQ-PAVE EDFMT391738
Table 4 Table 5
MODE NO. FIRST CODE NO. Setting contents External Static FIRST SECOND
MODE NO.
Airflow Pressure CODE NO. CODE NO.
11 (21) 7
adjustment 30Pa (*1)(*4) 01
SECOND CODE NO. 50Pa 02
01 02 03 60Pa 03
Completion of Start of airflow 70Pa 04
OFF
airflow adjustment adjustment 80Pa 05
90Pa 06
(4) After the air conditioner stops operating, check with
100Pa 07
“MODE NO. 21” on an indoor unit basis that 02 is set
for the “SECOND CODE NO.” in Table 4. If the air 110Pa (*3) 08
conditioner does not stop operating automatically or 120Pa (*3) 13 (23) 06 09
the “SECOND CODE NO.” is not 02, repeat steps 130Pa (*3) 10
from (3). If the outdoor unit is not turned ON, U4 or 140Pa (*3) 11
UH as explained in Table 8 will be displayed. This
150Pa (*3)(*4) 12
display is not problematic, because this function is
set for the indoor unit. Continue setting the function. 160Pa (*3)(*4) 13
After setting this function, be sure to turn ON the 180Pa
14
outdoor unit before the test operation of the outdoor (*2)(*3)(*4)
unit. If any other error is displayed, refer to Table 8 200Pa
15
and the operation manual provided with the outdoor (*2)(*3)(*4)
unit and check the defective point.
CAUTION
CAUTION Keep in mind that a shortage of airflow quantity or water leakage
will result because the air conditioner will be operated outside
• If there is any change after airflow adjustment in the the rated range of airflow quantity if the external static pressure
ventilation paths (e.g., the duct and air outlet), be sure to is wrongly set.
make airflow auto adjustment again.
• Consult your Daikin representative if there is any change
3. Filter Sign Settings
in the ventilation paths (e.g., the duct and air outlet) after
• The remote controller is provided with an LCD that tells
the test operation of the outdoor unit is finished or the the time of air filter cleaning.
air conditioner is moved to another place. • If the air conditioner is used in places with excessive dust,
change the “SECOND CODE NO.” as shown in Table 6.
(b) Select External Static Pressure with Remote Controller The “SECOND CODE NO.” is set to 01 (standard) at
Check that 01 (OFF) is set for the “SECOND CODE NO.” factory set.
in “MODE NO. 21” for airflow adjustment on an indoor Table 6
unit basis in Table 4. The “SECOND CODE NO.” is set to
Time for MODE FIRST SECOND
01 (OFF) at factory set. Change the “SECOND CODE Dirt display NO. CODE NO. CODE NO.
NO.” as shown in Table 5 according to the external static
Standard Approximately
pressure of the duct to be connected. 01
2500 hours
(1) The “SECOND CODE NO.” is set to 07 (an external 0
Excessive Approximately 10 (20)
static pressure of 100 Pa) at factory set. (FXMQ40 · dust 1250 hours 02
50 · 63 · 80 · 100 · 125 · 140PAVE) No display (*) 3
The “SECOND CODE NO.” is set to 02 (an external
* Select “No display” under conditions in which the cleaning
static pressure of 50 Pa) at factory set. (FXMQ20 · 25
display is not required, such as the time of regular maintenance.
· 32PAVE)
*1 The FXMQ50 · 63 · 80 · 100 · 125PAVE cannot
be set to 30 Pa. 4. Switching time of the dry operation at VRTsmart control
*2 The FXMQ40PAVE cannot be set to 180 or 200 Pa. setting.
*3 The FXMQ20 · 25 · 32PAVE cannot be set to • If you change the operation mode to “Dry” when
110-200 Pa. VRTsmart control is in effect, the operation mode is
change to “Cooling” after certain period of time.
*4 The FXMQ140PAVE cannot be set to 30 Pa and
If you want to continue dry operation longer, please change
150-200 Pa. the setting position as mentioned in the table below.
(Setting position of factory setting is “0”.)
※ If you keep dry operation longer, energy saving
performance decrease.
Mode Setting switch Setting position
Dry operation number
number number
30 min 01
60 min 02
10 10
90 min 03
Continuous (Not return 04
to Cooling)
14 English
3P432203-1B
57
FXMQ-PAVE EDFMT391738
Table 7
Remote controller display Contents
Error in power supply voltage to
“A8” lit
indoor unit.
Fan driver PCB of indoor unit ↔
“C1” lit indoor control PCB transmission
error.
Improper combination of fan driver
“C6” lit PCB of indoor unit or setting failure
in control PCB type.
Test operation of outdoor unit has
“U3” lit
not been finished.
Table 8
Remote control display Content
• There is a short circuit at the
“ ” is lit up
FORCED OFF terminals (T1, T2)
• The power on the outdoor unit is
off.
• The outdoor unit has not been
“U4” is lit up
wired for power supply.
“UH” is lit up
• Incorrect wiring for the transmis-
sion wiring and / or FORCED OFF
wiring.
• The power on the indoor unit is
off.
• The indoor unit has not been
wired for power supply.
No display
• Incorrect wiring for the remote
controller wiring, the transmission
wiring and / or the FORCED OFF
wiring.
CAUTION
If interior finish work is continuing on completion of the test
operation of the air conditioner, explain the customer not to
operate the air conditioner until the interior finish work is
completed for the protection of the air conditioner.
Otherwise, substances that will be generated from interior finish
work materials, such as paint and adhesive agents, may
contaminate the air conditioner.
English 15
3P432203-1B
58
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
●Specifications, designs and other content appearing in this brochure are current as of September 2017 but subject to change without notice.