You are on page 1of 64

EDFMT391738

201709

Engineering Data

FXMQ-PAVE
50 / 60 Hz
FXMQ-PAVE EDFMT391738

FXMQ-PAVE
Ceiling Mounted Duct Type
50 / 60 Hz

1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................8
4. Piping Diagrams........................................................................................13
5. Wiring Diagrams........................................................................................14
6. Electric Characteristics..............................................................................15
7. Safety Devices Setting..............................................................................16
8. Capacity Tables.........................................................................................17
8.1 Cooling Capacity for Te: Auto..........................................................17
8.2 Cooling Capacity for Te: 6°C...........................................................17
8.3 Cooling Capacity for Te: 9°C...........................................................18
8.4 Heating Capacity..............................................................................18
9. Fan Performances.....................................................................................19
10. Airflow Auto Adjustment Characteristics...................................................28
11. Sound Levels.............................................................................................36
12. Centre of Gravity.......................................................................................41
13. Accessories...............................................................................................42
13.1 Optional Accessories (for Unit)........................................................42
13.2 Optional Accessories (for Controls).................................................43
14. Installation Manual....................................................................................44

1
FXMQ-PAVE EDFMT391738

1. Lineup

2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP
Capacity index 20 25 31.25 40 50 62.5 80 100 125 140

FXMQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE

FXMQ 20PAVS 25PAVS 32PAVS 40PAVS 50PAVS 63PAVS 80PAVS 100PAVS 125PAVS 140PAVS
(for Thailand)
FXMQ 20PAV4 25PAV4 32PAV4 40PAV4 50PAV4 63PAV4 80PAV4 100PAV4 125PAV4 140PAV4
(for Indonesia)

VE : 1 phase, 220-240/220 V, 50/60 Hz


VS : 1 phase, 220 V, 50 Hz (for Thailand)
V4 : 1 phase, 220-240/220 V, 50/60 Hz (for Indonesia)

2
FXMQ-PAVE EDFMT391738

2. Specifications

Model FXMQ20PAVE FXMQ25PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 1,900 2,400
1 3 Cooling capacity Btu/h 7,500 9,600
kW 2.2 2.8
kcal/h 2,200 2,800
2 3 Heating capacity Btu/h 8,500 10,900
kW 2.5 3.2
50 Hz kW 0.056 0.056
Cooling
7 60 Hz kW 0.056 0.056
Power input 50 Hz kW 0.044 0.044
Heating
60 Hz kW 0.044 0.044
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×550×700 300×550×700
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 90×1 90×1
Number of units
m³/min 9/7.5/6.5 9/7.5/6.5
Fan Airflow rate l/s 150/125/108 150/125/108
(HH/H/L)
cfm 318/265/230 318/265/230
External static Pa Rated 50 (100-30 4) Rated 50 (100-30 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (External dia. 32
Internal dia. 25 )
Mass kg 25 25
6 Sound pressure level dB(A) 33/31/29 33/31/29
(HH/H/L)
Sound power level (H) dB 51 51
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, Screws, hose, Sealing pads, Clamps, Washers, Screws,
Standard accessories Insulation for fitting, Clamp metal, Air discharge Insulation for fitting, Clamp metal, Air discharge
flange, Air suction flange flange, Air suction flange
Specification C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D062535A C: 4D062535A

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

3
FXMQ-PAVE EDFMT391738

Model FXMQ32PAVE FXMQ40PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,100 3,900
1 3 Cooling capacity Btu/h 12,300 15,400
kW 3.6 4.5
kcal/h 3,400 4,300
2 3 Heating capacity Btu/h 13,600 17,100
kW 4.0 5.0
50 Hz kW 0.060 0.151
Cooling
7 60 Hz kW 0.059 0.150
Power input 50 Hz kW 0.048 0.139
Heating
60 Hz kW 0.048 0.139
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×550×700 300×700×700
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 90×1 140×1
Number of units
m³/min 9.5/8/7 16/13/11
Fan Airflow rate l/s 158/133/116 267/216/183
(HH/H/L)
cfm 335/282/247 565/459/388
External static Pa Rated 50 (100-30 4) Rated 100 (160-30 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (External dia. 32
Internal dia. 25 )
Mass kg 25 27
6 Sound pressure level dB(A) 34/32/30 39/37/35
(HH/H/L)
Sound power level (H) dB 52 57
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, Screws, hose, Sealing pads, Clamps, Washers, Screws,
Standard accessories Insulation for fitting, Clamp metal, Air discharge Insulation for fitting, Clamp metal, Air discharge
flange, Air suction flange flange, Air suction flange
Specification C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D062536A C: 4D060446C

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

4
FXMQ-PAVE EDFMT391738

Model FXMQ50PAVE FXMQ63PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 4,800 6,100
1 3 Cooling capacity Btu/h 19,100 24,200
kW 5.6 7.1
kcal/h 5,400 6,900
2 3 Heating capacity Btu/h 21,500 27,300
kW 6.3 8.0
50 Hz kW 0.128 0.138
Cooling
7 60 Hz kW 0.127 0.138
Power input 50 Hz kW 0.116 0.127
Heating
60 Hz kW 0.116 0.127
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×1,000×700 300×1,000×700
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 350×1 350×1
Number of units
m³/min 18/16.5/15 19.5/17.5/16
Fan Airflow rate l/s 300/275/250 325/292/267
(HH/H/L)
cfm 635/582/530 688/618/565
External static Pa Rated 100 (200-50 4) Rated 100 (200-50 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (External dia. 32
Internal dia. 25 )
Mass kg 35 35
6 Sound pressure level dB(A) 41/39/37 42/40/38
(HH/H/L)
Sound power level (H) dB 59 60
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, Screws, hose, Sealing pads, Clamps, Washers, Screws,
Standard accessories Insulation for fitting, Clamp metal, Air discharge Insulation for fitting, Clamp metal, Air discharge
flange, Air suction flange flange, Air suction flange
Specification C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D060428C C: 4D060447C

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

5
FXMQ-PAVE EDFMT391738

Model FXMQ80PAVE FXMQ100PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 7,700 9,600
1 3 Cooling capacity Btu/h 30,700 38,200
kW 9.0 11.2
kcal/h 8,600 10,800
2 3 Heating capacity Btu/h 34,100 42,700
kW 10.0 12.5
50 Hz kW 0.185 0.215
Cooling
7 60 Hz kW 0.184 0.214
Power input 50 Hz kW 0.173 0.203
Heating
60 Hz kW 0.173 0.203
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×1,000×700 300×1,400×700
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 350×1 350×1
Number of units
m³/min 25/22.5/20 32/27/23
Fan Airflow rate l/s 417/375/333 533/450/383
(HH/H/L)
cfm 883/794/706 1,130/953/812
External static Pa Rated 100 (200-50 4) Rated 100 (200-50 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (External dia. 32
Internal dia. 25 )
Mass kg 35 45
6 Sound pressure level dB(A) 43/41/39 43/41/39
(HH/H/L)
Sound power level (H) dB 61 61
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, Screws, hose, Sealing pads, Clamps, Washers, Screws,
Standard accessories Insulation for fitting, Clamp metal, Air discharge Insulation for fitting, Clamp metal, Air discharge
flange, Air suction flange flange, Air suction flange
Specification C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D060429C C: 4D060448C

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

6
FXMQ-PAVE EDFMT391738

Model FXMQ125PAVE FXMQ140PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 12,000 13,800
1 3 Cooling capacity Btu/h 47,800 54,600
kW 14.0 16.0
kcal/h 13,800 15,500
2 3 Heating capacity Btu/h 54,600 61,400
kW 16.0 18.0
50 Hz kW 0.284 0.405
Cooling
7 60 Hz kW 0.283 0.404
Power input 50 Hz kW 0.272 0.380
Heating
60 Hz kW 0.272 0.380
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×1,400×700 300×1,400×700
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 350×1 350×1
Number of units
m³/min 39/33/28 46/39/32
Fan Airflow rate l/s 650/550/466 767/650/533
(HH/H/L)
cfm 1,377/1,165/988 1,624/1,377/1,130
External static Pa Rated 100 (200-50 4) Rated 100 (140-50 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (External dia. 32
Internal dia. 25 )
Mass kg 45 46
6 Sound pressure level dB(A) 44/42/40 46/45/43
(HH/H/L)
Sound power level (H) dB 62 64
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, Screws, hose, Sealing pads, Clamps, Washers, Screws,
Standard accessories Insulation for fitting, Clamp metal, Air discharge Insulation for fitting, Clamp metal, Air discharge
flange, Air suction flange flange, Air suction flange
Specification C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D060449C C: 4D063786A

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

7
FXMQ-PAVE EDFMT391738

3. Dimensions

FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE


Unit: mm

3D105236

8
FXMQ-PAVE EDFMT391738

FXMQ40PAVE
Unit: mm

3D105231

9
FXMQ-PAVE EDFMT391738

FXMQ50PAVE
Unit: mm

3D105232

10
FXMQ-PAVE EDFMT391738

FXMQ63PAVE / FXMQ80PAVE
Unit: mm

3D105233

11
FXMQ-PAVE EDFMT391738

FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE


Unit: mm

3D105235

12
FXMQ-PAVE EDFMT391738

4. Piping Diagrams

FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /


FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

4D104913

„„ Refrigerant pipe connection port diameters


Unit: mm
Model Gas Liquid
FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE φ12.7 φ6.4
FXMQ63PAVE / FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE φ15.9 φ9.5

13
FXMQ-PAVE EDFMT391738

5. Wiring Diagrams

FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /


FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

3D103336

14
FXMQ-PAVE EDFMT391738

6. Electric Characteristics

FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /


FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

4D104911

15
FXMQ-PAVE EDFMT391738

7. Safety Devices Setting

Model FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A
Drain pump thermal fuse °C — — — —

Model FXMQ50PAVE FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
Drain pump thermal fuse °C — — — —

Model FXMQ125PAVE FXMQ140PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A
Drain pump thermal fuse °C — —
C: 3D104897

16
FXMQ-PAVE EDFMT391738

8. Capacity Tables
8.1 Cooling Capacity for Te: Auto

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.9 1.9 2.1 2.1 2.2 2.0 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
FXMQ25PAVE 25 2.5 2.2 2.6 2.3 2.8 2.5 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
FXMQ32PAVE 32 3.2 2.6 3.4 2.7 3.5 2.9 3.6 2.8 3.6 2.7 3.7 2.7 3.8 2.6
FXMQ40PAVE 40 4.0 3.7 4.2 4.0 4.4 4.2 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
FXMQ50PAVE 50 4.9 4.3 5.3 4.7 5.5 5.0 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
FXMQ63PAVE 63 6.3 5.1 6.7 5.5 7.0 5.8 7.1 5.5 7.2 5.4 7.3 5.3 7.5 5.2
FXMQ80PAVE 80 7.9 6.5 8.5 7.0 8.8 7.4 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
FXMQ100PAVE 100 9.9 8.2 10.5 8.8 11.0 9.1 11.2 8.5 11.3 8.4 11.6 8.1 11.8 7.8
FXMQ125PAVE 125 12.3 10.2 13.2 10.9 13.8 11.3 14.0 10.5 14.2 10.4 14.5 10.1 14.8 9.6
FXMQ140PAVE 140 14.1 11.8 15.0 12.5 15.7 12.8 16.0 12.0 16.2 11.9 16.5 11.5 16.9 11.2

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.2 Cooling Capacity for Te: 6°C

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
FXMQ25PAVE 25 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
FXMQ32PAVE 32 2.4 2.1 2.9 2.4 3.4 2.7 3.6 2.8 3.6 2.7 3.7 2.7 3.8 2.6
FXMQ40PAVE 40 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
FXMQ50PAVE 50 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
FXMQ63PAVE 63 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.2 5.4 7.4 5.3 7.5 5.2
FXMQ80PAVE 80 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
FXMQ100PAVE 100 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.8
FXMQ125PAVE 125 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.2 10.4 14.5 10.1 14.9 9.7
FXMQ140PAVE 140 10.8 9.0 12.9 10.4 15.0 11.7 16.0 12.0 16.2 11.9 16.6 11.5 17.0 11.3

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

17
FXMQ-PAVE EDFMT391738

8.3 Cooling Capacity for Te: 9°C

For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.0 1.0 1.3 1.3 1.6 1.6 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
FXMQ25PAVE 25 1.3 1.3 1.6 1.6 2.0 1.9 2.2 2.0 2.3 1.9 2.4 1.8 2.6 2.0
FXMQ32PAVE 32 1.6 1.6 2.0 2.0 2.6 2.3 2.9 2.4 2.9 2.3 3.1 2.4 3.3 2.4
FXMQ40PAVE 40 2.1 2.1 2.6 2.6 3.3 3.3 3.6 3.3 3.8 3.2 3.9 3.1 4.1 3.3
FXMQ50PAVE 50 2.6 2.6 3.2 3.2 4.0 3.8 4.4 3.9 4.6 3.9 4.9 3.8 5.1 3.3
FXMQ63PAVE 63 3.2 3.2 4.0 4.0 5.1 4.6 5.6 4.7 5.8 4.7 6.2 4.7 6.5 4.7
FXMQ80PAVE 80 4.2 4.1 5.1 5.0 6.5 5.9 7.2 6.0 7.4 6.0 7.8 5.8 8.2 6.0
FXMQ100PAVE 100 5.2 5.0 6.4 6.0 8.0 7.0 8.9 7.3 9.2 7.3 9.7 7.1 10.2 7.1
FXMQ125PAVE 125 6.5 6.2 8.0 7.5 10.1 8.8 11.2 9.1 11.6 9.0 12.2 8.9 12.8 8.8
FXMQ140PAVE 140 7.5 7.0 9.2 8.6 11.7 10.0 12.8 10.4 13.2 10.4 13.9 10.1 14.6 10.3

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.4 Heating Capacity

Indoor air temp.


Capacity
Model 16°CDB 18°CDB 20°CDB 21°CDB 22°CDB 24°CDB
indication
kW kW kW kW kW kW
FXMQ20PAVE 20 2.6 2.6 2.5 2.4 2.3 2.2
FXMQ25PAVE 25 3.4 3.4 3.2 3.1 3.0 2.8
FXMQ32PAVE 32 4.2 4.2 4.0 3.9 3.7 3.5
FXMQ40PAVE 40 5.2 5.2 5.0 4.8 4.7 4.4
FXMQ50PAVE 50 6.6 6.6 6.3 6.1 5.9 5.5
FXMQ63PAVE 63 8.4 8.4 8.0 7.7 7.5 7.0
FXMQ80PAVE 80 10.5 10.5 10.0 9.7 9.4 8.7
FXMQ100PAVE 100 13.1 13.1 12.5 12.1 11.7 10.9
FXMQ125PAVE 125 16.8 16.8 16.0 15.5 15.0 13.9
FXMQ140PAVE 140 18.9 18.9 18.0 17.4 16.8 15.7

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

18
FXMQ-PAVE EDFMT391738

9. Fan Performances

FXMQ20PAVE / FXMQ25PAVE

3D062537B

19
FXMQ-PAVE EDFMT391738

FXMQ32PAVE

3D062538B

20
FXMQ-PAVE EDFMT391738

FXMQ40PAVE

3D060456D

21
FXMQ-PAVE EDFMT391738

FXMQ50PAVE

3D060457E

22
FXMQ-PAVE EDFMT391738

FXMQ63PAVE

3D060458D

23
FXMQ-PAVE EDFMT391738

FXMQ80PAVE

3D060459C

24
FXMQ-PAVE EDFMT391738

FXMQ100PAVE

3D060460D

25
FXMQ-PAVE EDFMT391738

FXMQ125PAVE

3D060461D

26
FXMQ-PAVE EDFMT391738

FXMQ140PAVE

3D063787A

27
FXMQ-PAVE EDFMT391738

10. Airflow Auto Adjustment Characteristics

FXMQ20PAVE / FXMQ25PAVE

3D062539B

28
FXMQ-PAVE EDFMT391738

FXMQ32PAVE

3D062540B

29
FXMQ-PAVE EDFMT391738

FXMQ40PAVE

3D060577E

30
FXMQ-PAVE EDFMT391738

FXMQ50PAVE

3D060578E

31
FXMQ-PAVE EDFMT391738

FXMQ63PAVE

3D060579E

32
FXMQ-PAVE EDFMT391738

FXMQ80PAVE

3D060580E

33
FXMQ-PAVE EDFMT391738

FXMQ100PAVE

3D060581E

34
FXMQ-PAVE EDFMT391738

FXMQ125PAVE

3D060582E

35
FXMQ-PAVE EDFMT391738

11. Sound Levels

FXMQ20PAVE / FXMQ25PAVE

4D062535A
FXMQ32PAVE

4D062536A

36
FXMQ-PAVE EDFMT391738

FXMQ40PAVE

4D060446C
FXMQ50PAVE

4D060428C

37
FXMQ-PAVE EDFMT391738

FXMQ63PAVE

4D060447C
FXMQ80PAVE

4D060429C

38
FXMQ-PAVE EDFMT391738

FXMQ100PAVE

4D060448C
FXMQ125PAVE

4D060449C

39
FXMQ-PAVE EDFMT391738

FXMQ140PAVE

4D063786A

40
FXMQ-PAVE EDFMT391738

12. Centre of Gravity

FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /


FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE
Unit: mm

4D104912

41
FXMQ-PAVE EDFMT391738

13. Accessories
13.1 Optional Accessories (for Unit)

Model
Item
FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE
High efficiency 65% KAF372AA36 KAF372AA56 KAF372AA80
filter 90% KAF373AA36 KAF373AA56 KAF373AA80
Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80
Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80
Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80
White KTBJ25K36W KTBJ25K56W KTBJ25K80W
Fresh
Service panel KTBJ25K36F KTBJ25K56F KTBJ25K80F
white
Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T
Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A

Model
Item
FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
High efficiency 65% KAF372AA80 KAF372AA160
filter 90% KAF373AA80 KAF373AA160
Filter chamber KDDF37AA80 KDDF37AA160
Long life replacement filter KAF371AA80 KAF371AA160
Long life filter chamber kit KAF375AA80 KAF375AA160
White KTBJ25K80W KTBJ25K160W
Fresh
Service panel KTBJ25K80F KTBJ25K160F
white
Brown KTBJ25K80T KTBJ25K160T
Air discharge adaptor KDAJ25K71A KDAJ25K140A
C: 3D104914

42
FXMQ-PAVE EDFMT391738

13.2 Optional Accessories (for Controls)

Model
Item
FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE
Cooling Only BRC4C66 (Note 4)
Wireless
Remote controller Heat Pump BRC4C65 (Note 4)
Wired BRC1C62 (Note 4)
Navigation remote controller (Wired remote controller) BRC1E62 (Note 4, 5)
Simplified remote controller (Exposed type) BRC2C51
Remote controller for hotel use (Concealed type) BRC3A61
Adaptor for wiring H KRP1C64
Wiring adaptor for electrical appendices (1) H KRP2A61
Wiring adaptor for electrical appendices (2) H KRP4AA51
Remote sensor (for indoor temperature) KRCS01-4B
Installation box for adaptor printed circuit board KRP4A97 (Note 2, 3)
External control adaptor for outdoor unit H DTA104A61
Adaptor for multi tenant H DTA114A61

Model
Item
FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Cooling Only BRC4C66 (Note 4)
Wireless
Remote controller Heat Pump BRC4C65 (Note 4)
Wired BRC1C62 (Note 4)
Navigation remote controller (Wired remote controller) BRC1E62 (Note 4, 5)
Simplified remote controller (Exposed type) BRC2C51
Remote controller for hotel use (Concealed type) BRC3A61
Adaptor for wiring H KRP1C64
Wiring adaptor for electrical appendices (1) H KRP2A61
Wiring adaptor for electrical appendices (2) H KRP4AA51
Remote sensor (for indoor temperature) KRCS01-4B
Installation box for adaptor printed circuit board KRP4A97 (Note 2, 3)
External control adaptor for outdoor unit H DTA104A61
Adaptor for multi tenant H DTA114A61
C:3D104915A
Notes:
1. Installation box is necessary for each adaptor marked H.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.
5. Auto airflow rate can be set only via wired remote controller BRC1E62. Cannot be set via other remote controllers.

43
FXMQ-PAVE EDFMT391738

14. Installation Manual

VRV SYSTEM Inverter Air Conditioners Installation manual

CONTENTS • Consult your local dealer regarding what to do in case of


refrigerant leakage. When the air conditioner is to be
1. SAFETY PRECAUTIONS................................................ 1
installed in a small room, it is necessary to take proper
2. BEFORE INSTALLATION ................................................ 2 measures so that the amount of any leaked refrigerant does
3. SELECTING INSTALLATION SITE ................................. 4 not exceed the concentration limit in the event of a leakage.
4. PREPARATIONS BEFORE INSTALLATION.................... 4 Otherwise, this may lead to an accident due to oxygen
5. INDOOR UNIT INSTALLATION ....................................... 5 depletion.
• Be sure to use only the specified accessories and parts for
6. REFRIGERANT PIPING WORK ..................................... 6 installation work.
7. DRAIN PIPING WORK .................................................... 7 Failure to use the specified parts may result in the unit
8. DUCT WORK .................................................................. 9 falling, water leakage, electric shocks or fire.
9. ELECTRIC WIRING WORK ............................................ 9 • Install the air conditioner on a foundation strong enough to
10. WIRING EXAMPLE AND HOW TO SET withstand the weight of the unit.
A foundation of insufficient strength may result in the
THE REMOTE CONTROLLER...................................... 10 equipment falling and causing injury.
11. FIELD SETTING............................................................ 13 • Carry out the specified installation work after taking into
12. TEST OPERATION........................................................ 15 account strong winds, typhoons or earthquakes.Failure to
13. WEIGHT AND DIMENSION...........................................15 do so during installation work may result in the unit falling
and causing accidents.
• Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by
1. SAFETY PRECAUTIONS qualified personnel according to local laws and regulations
and this installation manual.
Please read these “SAFETY PRECAUTIONS” carefully before An insufficient power supply capacity or improper electrical
installing air conditioning unit and be sure to install it correctly. construction may lead to electric shocks or fire.
After completing the installation, make sure that the unit • Make sure that all wiring is secured, the specified wires are
operates properly during the start-up operation. used, and that there is no strain on the terminal connections
After completing installation, conduct a trial operation to or wires.
check for faults and explain to the customer how to operate the Improper connections or securing of wires may result in
air conditioner and take care of it with the aid of the operation abnormal heat build-up or fire.
manual. • When wiring the power supply and connecting the remote
Ask the customer to store the installation manual along with controller wiring and transmission wiring, position the wires
the operation manual for future reference. so that the control box lid can be securely fastened.
Please instruct the customer on how to operate the unit and Improper positioning of the control box lid may result in
keep it maintained. electric shocks, fire or the terminals overheating.
Also, inform customers that they should store this installation • If refrigerant gas leaks during installation, ventilate the area
manual along with the operation manual for future reference. immediately.
Toxic gas may be produced if the refrigerant comes into
This air conditioner comes under the term “appliances not
contact with fire.
accessible to the general public”. • After completing installation, check for refrigerant gas
Safety Precaution leakage.
This unit is a class A product. In a domestic environment this Toxic gas may be produced if the refrigerant gas leaks
product may cause radio interference in which case the user into the room and comes into contact with a source of fire,
may be required to take adequate measures. such as a fan heater, stove or cooker.
• Be sure to switch off the unit before touching any electrical
Meaning of WARNING and CAUTION notices
parts.
WARNING ............. Failure to follow these instructions • Be sure to earth the air conditioner.
properly may result in personal injury Do not earth the unit to a utility pipe, lightning conductor or
or loss of life. telephone earth lead. Imperfect earthing may result in
electric shocks or fire.
CAUTION ..............Failure to observe these instructions A high surge current from lightning or other sources may
properly may result in property dam- cause damage to the air conditioner.
age or personal injury, which may be • Be sure to install an earth leakage breaker.
serious depending on the circum- Failure to install an earth leakage breaker may result in
stances. electric shocks or fire.
• Do not allow children to climb on the outdoor unit and
WARNING avoid placing objects on the unit.
• Ask your dealer or qualified personnel to carry out installation Injury may result if the unit becomes loose and falls.
work. • Do not directly touch refrigerant that has leaked from
Do not attempt to install the air conditioner yourself. Improper refrigerant pipes or other areas, as there is a danger of
installation may result in water leakage, electric shocks or fire. frostbite.
• Install the air conditioner in accordance with the instructions
in this installation manual.
Improper installation may result in water leakage, electric
shocks or fire.

English 1

3P432203-1B

44
FXMQ-PAVE EDFMT391738

due to composition change, the system will not function


CAUTION
normally). The indoor unit is designed for R410A use.
• While following the instructions in this installation manual, See the catalogue for indoor unit models that can be
install drain piping to ensure proper drainage and insulate connected. (Normal operation is not possible when connecting
piping to prevent condensation. units that are originally designed for other refrigerants.)
Improper drain piping may result in indoor water leakage and
property damage.
• Install the indoor and outdoor units, power cord and 2. BEFORE INSTALLATION
connecting wires at least 1 meter away from televisions or
radios to prevent picture interference and noise. • When moving the unit while removing it from the carton
(Depending on the incoming signal strength, a distance of box, be sure to lift it by holding on to the four lifting lugs
1 meter may not be sufficient to eliminate noise.) without exerting any pressure on other parts, especially,
• Remote controller (wireless kit) transmitting distance can be the refrigerant piping, drain piping, flanges and other
shorter than expected in rooms with electronic fluorescent resin parts.
lamps (inverter or rapid start types). • Be sure to check the type of R410A refrigerant to be used
Install the indoor unit as far away from fluorescent lamps as before installing the unit. (Using an incorrect refrigerant will
possible. prevent normal operation of the unit.)
• Do not install the air conditioner in the following locations: • The accessories needed for installation must be retained in
1. Where there is a high concentration of mineral oil spray or your custody until the installation work is completed. Do not
vapour (e.g. a kitchen). discard them!
Plastic parts will deteriorate, parts may fall off and water • Decide upon a line of transport.
leakage could result. • Leave the unit inside its packaging while moving, until
2. Where corrosive gas, such as sulphurous acid gas, is reaching the installation site. Where unpacking is unavoidable,
produced. use a sling of soft material or protective plates together with
Corroding of copper pipes or soldered parts may result in a rope when lifting, to avoid damage or scratches to the unit.
refrigerant leakage. • When moving the unit or affter opening, hold the unit by the
3. Near machinery emitting electromagnetic radiation. hanger brackets (× 4). Do not apply force to the refrigerant
Electromagnetic radiation may disturb the operation of the piping, drain piping, flanges or plastic parts.
control system and result in a malfunction of the unit. • For the installation of outdoor unit, refer to the installation
4. Where flammable gas may leak, where there is carbon manual attached to the outdoor unit.
fibre or ignitable dust suspensions in the air, or where • Do not install or operate the unit in rooms mentioned below.
volatile flammables such as paint thinner or gasoline are • Laden with mineral oil, or filled with oil vapor or spray
handled. like in kitchens. (Plastic parts may deteriorate which
Operating the unit in such conditions may result in fire. could eventually cause the unit to fall out of place, or
• The air conditioner is not intended for use in a potentially could lead to leaks.)
explosive atmosphere. • Where corrosive gas like sulfurous gas exists.
• Install in a machine room that is free of moisture. The unit is (Copper tubing and brazed spots may corrode which
designed for indoor use. could eventually lead to refrigerant leaks.)
• Make sure to provide for adequate measures in order to • Where exposed to combustible gases and where
prevent that the outdoor unit be used as a shelter by small volatile flammable gas like thinner or gasoline is used.
animals. (Gas in the vicinity of the unit could ignite.)
• Small animals making contact with electrical parts can • Where machines can generate electromagnetic
cause malfunctions, smoke or fire. Please instruct the waves. (Control system may malfunction.)
customer to keep the area around the unit clean. • Where the air contains high levels of salt such as that
• Disposal requirements near the ocean and where voltage fluctuates greatly
Dismantling of the unit, treatment of the refrigerant, of oil such as that in factories.
and of other parts must be done in accordance with relevant Also in vehicles or vessels.
local and national legislation. • This unit, both indoor and outdoor, is suitable for installation in a
commercial and light industrial environment.
If installed as a household appliance it could cause
SPECIAL NOTICE PRODUCT electromagnetic interference.
• The refrigerant R410A requires that strict precautions be
observed for keeping the system clean, dry and tightly sealed. 2-1 PRECAUTIONS
A. Clean and dry • Be sure to read this manual before installing the indoor unit.
Strict measures must be taken to keep impurities • Entrust installation to the place of purchase or a qualified
(including SUNISO oil and other mineral oils as well as serviceman. Improper installation could lead to leaks and,
moisture) out of the system. in worse cases, electric shock of fire.
B. Tightly sealed • Use only parts provided with the unit or parts satisfying
R410A contains no chlorine, does not destroy the ozone required specifications. Unspecified parts could cause the
layer and so does not reduce the earth's protection against unit to fall out of place, or could lead to leaks and, in worse
harmful ultraviolet radiation. R410A will contribute only slightly cases, electric shock or fire.
to the greenhouse effect if released into the atmosphere. • Be sure to mount an air filter (part to be procured in the field)
in the suction air passage in order to prevent water leaking,
• Since design pressure is 4.0 MPa or 40 bar (for R407C units:
etc.
3.3 MPa or 33 bar), the thickness of pipes must be greater
than previously. Since R410A is a mixed refrigerant, the
required additional refrigerant must be charged in its liquid state.
(If the system is charged with refrigerant in its gaseous state,

2 English

3P432203-1B

45
FXMQ-PAVE EDFMT391738

2-2 ACCESSORIES 2-3 OPTIONAL ACCESSORIES


• These are two types of remote controllers: wired and
Check that the following accessories are provided and that each
wireless. Select a remote controller according to customer
accessory is correct in amount.
request and install in an appropriate place.
Refer to the Fig. 1 of this sheet.
[PRECAUTION] Table 1
The accessories are required for the installation of the air Remote controller
conditioner. Be sure to keep them until the installation work is Wired type
completed. Heat pump type
Wireless type
Cooling only type

NOTE
• If you wish to use a remote controller that is not listed in
Table 1, select a suitable remote controller after consulting
catalogs and technical materials.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL


(1) - (14) CARE DURING CONSTRUCTION AND CHECK
Operation manual AFTER INSTALLATION IS FINISHED.
Installation manual Fig. 1
a. Items to be checked after completion of work
If not properly done, what is
Items to be checked Check
Metal Drain Screws for duct Insulation for likely to occur.
Name
clamp (1) hose (2) flanges (3) fitting Are the indoor and outdoor The units may drop, vibrate
As described in unit fixed firmly? or make noise.
Quantity 1 pc. 1 pc. 1 each
table below Was the installation of the The unit may malfunction or
outdoor unit completed? the components burn out.

M5×16 Thin Is the gas leak test


No cooling or heating.
finished?
20 • 25 • for liquid pipe Is the unit fully insulated?
32 type 6 (4) (Refrigerant piping, drain Condensate water may drip.
Shape
40 type 10 piping, and duct)
50 • 63 • Dose drainage flow
18 Condensate water may drip.
80 type Thick
smoothly?
100 • 125 •
140 type 26 for gas pipe Does the power supply volt- The unit may malfunction or
(5) age conform to the indication
the components burn out.
on the name plate?
Washer Wire sealing Are wiring and piping The unit may malfunction or
Name Sealing pad Clamp (8) correct? the components burn out.
fixing plate (9) material (10)
Quantity – 9 pcs. 4 pcs. 2 pcs. Is the air conditioner Dangerous in case of
properly grounded? current leakage.
Is wiring size according to The unit may malfunction or
specifications? the components burn out.
Is something blocking the
1 pc.
air outlet or inlet of either No cooling or heating.
Large
the indoor or outdoor units?
Shape (Dark gray) (6)
Did you set the external
No cooling or heating.
static pressure?
Small
Are refrigerant piping length
2 pcs. (Gray) The refrigerant charge in
and additional refrigerant
Middle the system is not clear.
charge noted down?
(Dark gray) (7)
Did you check that no wiring
connection screws were Electric shock or fire.
Washer Wire fixing Wire fixing Insulation loose?
Name for drain
(11) bracket (12) screw (13) Also review the “SAFETY PRECAUTIONS”.
socket (14)
Quantity 8 pcs. 2 pcs. 2 pcs. 1 pc. (Other)
• Operation
manual
M4×8 • Installation
Shape manual
Thick

English 3

3P432203-1B

46
FXMQ-PAVE EDFMT391738

b. Items to be checked at time of delivery (2) Use hanging bolts to install the indoor unit. Check that the
place of installation withstands the weight of the indoor unit.
Items to be checked Check
Secure the hanging bolts with proper beams if necessary.
Are you sure the control box lid, air filter, air inlet grille, and
(length: mm)
air outlet grille are mounted?

Min. 20
Did you explain about operations while showing the
operation manual to your customer?

*H2=Min. 620
Did you deliver the operation manual along with the

Min. 300 *H1=300

(If no ceiling board is provided.)


installation manual to the customer?
Did you explain the customer the handling and cleaning
methods of the field supplies (e.g., the air filter, air inlet
grilles, and air outlet grille)?

Min. 450
Min. 2500
Ceiling
Did you deliver instruction manual, if any, for the field
supplies to the customer?
Min. 700 (service space)
c. Points for explanation about operations Floor surface
The items with WARNING and CAUTION marks in the operation
manual are the items pertaining to possibilities for bodily injury and • The H1 dimension indicates the [Required installation place]
material damage in addition to the general usage of the product. height of the product. The dimensions indicate the
Accordingly, it is necessary that you make a full explanation about • Determine the H2 dimension by minimum required space of
the described contents and also ask your customers to read the maintaining a downward slope of installation.
operation manual. at least 1/100 as specified in
“7. DRAIN PIPING WORK”. Fig. 2-1

2-4 NOTE TO INSTALLER


• Be sure to instruct customers how to properly operate the 4. PREPARATIONS BEFORE INSTALLATION
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out (1) Check the positional relationship between the ceiling
operations themselves while looking at the manual. opening hole and the hanging bolt of the unit.
• For the maintenance, inspection, and other servicing
purposes of the control box and drain pump, prepare one
3. SELECTING INSTALLATION SITE of the following service spaces.
1. Inspection hatch 1 (450 × 450) for the control box and
〈Hold the hanging brackets in the case of moving the a minimum space of 300 mm for the lower part of the
indoor and outdoor units at the time of and after opening product. (Refer to Fig. 2-2)
the packages. Do not impose undue force on other parts, 2. Inspection hatch 1 (450 × 450) for the control box and
such as the refrigerant piping, drain piping, or flanges, inspection hatch 2 for the lower part of the product
in particular.〉 (see axial direction view A-1). (Refer to Fig. 2-3)
〈Add heat insulation material to the indoor unit if the 3. Inspection hatch 3 for the lower part of the product
temperature above the ceiling is likely to exceed 30°C and and the lower part of the control box (see axial
a relative humidity of 80%.〉 direction view A-2). (Refer to Fig. 2-3)
〈Make sure that the insulation material is made of glass wool
Case 1
or polyethylene foam, has a minimum thickness of 10 mm, Control box
and can be accommodated in the opening on the ceiling.〉 *H3=Min. 300
(1) Select an installation site where the following conditions are
fulfilled and that meets with your customer’s approval.
• A place where cool (warm) air is delivered to the entire
room.
• Where nothing blocks the air passage.
• Where condensate can be properly drained. Ceiling Inspection hatch
• If supporting structural members are not strong enough
to take the unit’s weight, the unit could fall out of place
abd cause serious injury. • FXMQ50 • 63 • 80 • 100 • 125 • 140 type
• Where the false ceiling is not noticeably on an incline. 700 Inspection hatch 1
• Where there is no risk of flammable gas leakage.
200 or less

631 (450×450)
• Where sufficient clearance for maintenance and service (Hanging bolt pitch)
can be ensured. (Refer to Fig. 2-1)
Control box
• Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the
installation manual of the outdoor unit.)
500

(Hanging bolt pitch)

CAUTION
• Install the indoor and outdoor units, power supply wiring and
C
B

connecting wires at least 1 meter away from televisions or Air outlet Air inlet
radios in order to prevent image interference or noise.
Inspection hatch 2
(Depending on the radio waves, a distance of 1 meter may (450 x 450) Bottom of unit
not be sufficient enough to eliminate the noise.)
(For remove drain pan and
• In the case of the installation of a wireless remote controller, change part) Hanging bolt (× 4)
the transmission distance of the wireless remote controller * In case can work at space
may be shortened if the room has a fluorescent light of of below product, inspection
hatch 2 is unnecessary.
electronic lighting type (i.e., an inverter or rapid-start
fluorescent light). Keep the distance between the receiver
and the fluorescent light as far as possible.

4 English

3P432203-1B

47
FXMQ-PAVE EDFMT391738

• FXMQ20 • 25 • 32 • 40 type (4) Install the hanging bolts. Make sure that the hanging bolts
700 Inspection hatch 1 are M10 in size.
• Use hole-in anchors if the hanging bolts already exist;
200 or less (450×450)
631
(Hanging bolt pitch) otherwise use embedded inserts and embedded
foundation bolts so that they will withstand the weight
Control box of the unit.
Adjust the distance to the ceiling surface in advance.

(Hanging bolt pitch)


Installation example
Air outlet Bottom of unit Ceiling slab
Anchor

C
B
Air inlet
Long nut or turn-buckle

Inspection hatch 2 Hanging bolt


Hanging bolt (× 4) (450 x 450)
Indoor unit
(For remove drain pan and change part)
* In case can work at space of below Note) All the above parts are field supplied.
product, inspection hatch 2 is
Fig. 2-2 unnecessary.
Case 2, 3 Inspection hatch
Control box
5. INDOOR UNIT INSTALLATION
(Ceiling opening)
〈It may be easier to install accessories (sold separately)
before installing the indoor unit. Refer to the installation
*H3=Min. 20

manuals provided to the accessories as well.〉


Be sure to use the accessories and specified parts for
installation work.
Inspection hatch A Ceiling (1) Temporally install the indoor unit.
• Connect the hanging brackets to the hanging bolts. Be
Inspection hatch 1
(450×450) Inspection hatch 3 sure to use and tighten the nut and washer (11) for each
(Same as the indoor hanging bracket from both upper and lower sides of the
Min. 200

unit size +300 or more) hanging bracket. (Refer to Fig. 3) At that time, the fall of
Control box the washer (11) for the hanging bracket can be
prevented if the washing fixing plate (9) is used.
Min. D=B+300

Control box [Fixing hanging brackets]


B

Inspection Part to be procured in the field


hatch 2
Washer (11) (accessory)
700 (Same as the 700
indoor unit
size or more)
Axial direction view A-1 Axial direction view A-2
Fig. 2-3 Tighten from above and below
(Double nut)
Model B C D
• Determine the H3 20 • 25 • 32 type 550 588 850
dimension by maintaining a [Fixing method of washers]
downward slope of at least 40 type 700 738 1000
50 • 63 • 80 type 1000 1038 1300 Nut on the upper side
1/100 as specified in
“7. DRAIN PIPING WORK”. 100 • 125 • 140 type 1400 1438 1700
(length: mm)
(2) Mount the canvas ducts to the air outlet and inlet so that the Insert
vibration of the air conditioner will not be transmitted to the
duct or ceiling. Apply a sound-absorbing material (insulation
material) to the inner wall of the duct and vibration insulation
rubber to the hanging bolts (refer to 8. DUCT WORK). Washer fixing plate (9)
(3) Open installation holes (if the ceiling already exists). (accessory)
• Open the installation holes on the ceiling. Lay the Fig. 3
refrigerant piping, drain piping, power line, transmission
wiring, and remote controller wiring for the piping and
wiring connection port of the unit. CAUTION
In the case of the installation of a wireless remote • During the installation work, perform the curing of the air
controller, refer to the installation manual provided with outlet and protect the resin drain pan of the indoor unit
the wireless remote controller. from the intrusion of foreign substances, such as
Refer to 6. REFRIGERANT PIPING WORK, 7. DRAIN welding spatters.
PIPING WORK, and 10. WIRING EXAMPLE AND HOW Otherwise, water leakage may occur as a result of damage,
TO SET THE REMOTE CONTROLLER. such as hole damage, to the resin drain pan.
• The ceiling framework may need reinforcement in order
to keep the ceiling horizontal and prevent the vibration of
the ceiling after the installation holes are opened. For
details, consult your construction or interior contractor.

English 5

3P432203-1B

48
FXMQ-PAVE EDFMT391738

(2) Make adjustments so that the unit will be in the right (1) Connect the piping.
position. • The outdoor unit is filled with refrigerant.
(3) Check the level of the unit. • When connecting or disconnecting piping to or from the
(4) Remove the washer fixing plates for the falling prevention of unit, be sure to use two spanners and two torque
the washers for the hanging brackets, tighten the nuts on wrenches. (Refer to Fig. 4)
the upper side, and securely fix the unit. Torque wrench
Level

Spanner
Hanging bracket
Flare nut

Piping union

Bottom of product Fig. 4


• Refer to Table 2 for the processing dimensions of the
Vinyl tube flare.
• Use the flare nut provided with the unit.
• Apply ether oil or ester oil only to inner side of the
CAUTION flare and screw in the flare nut three to four turns first by
• Use the level and check that the unit is installed horizontally. hand at the time of connecting the flare nut.
(4-directions) (Refer to Fig. 5)
• In the case of using a vinyl tube in place of the level, put the Apply ester oil or ether oil
both edges of the vinyl tube in close contact with the bottom only to inner side of flare.
of the product to make levelness adjustment.
If the unit is installed at a slant with the drain pipe side set
high, in particular, the float switch will not operate normally
and water leakage may result.
Fig. 5
• Refer to Table 2 for the corresponding tightening torque.

6. REFRIGERANT PIPING WORK Table 2


Flare
〈As for the refrigerant piping of the outdoor unit, refer to Pipe
Tightening torque dimensions Flare shape
the installation manual provided to the outdoor unit.〉 size
A (mm)
〈Perform heat insulation work on both gas piping and
liquid piping, or otherwise water leakage may result.〉 φ 6.4 14.2 – 17.2 N·m 8.7 – 9.1
〈Use the insulation material that withstands a temperature
0
R0.4-0.8
of 120°C.〉
φ 9.5 32.7 – 39.9 N·m 12.8 – 13.2 45 ±2
0
0
90 ±2

〈Reinforce the insulation material for the refrigerant piping


0

A
φ 12.7 49.5 – 60.3 N·m 16.2 – 16.6
if the ambient temperature is high, or otherwise dew
condensation may result on the surface of the insulation φ 15.9 61.8 – 75.4 N·m 19.3 – 19.7
material.〉
〈Make sure that the refrigerant is R410A before refrigerant CAUTION
piping work. If the refrigerant is different, the air conditioner
will not operate normally.〉 • Do not excessively tighten the flare nut.
Doing so will break the flare nut and refrigerant leakage may
CAUTION result.
This product uses new refrigerant (R410A) only. Be sure to • Make sure that all parts around the flare are free of oil.
keep the items on the right-hand side and conduct the The drain pan and the resin part may be deteriorated if oil is
installation work. attached.
• Use a dedicated pipe cutter and flare tool for R410A. • If no torque wrenches are available, refer to Table 3 as a
• When connecting the flare, apply ether oil or ester oil standard.
only to inner side of the flare. When the flare nut is tightened with the spanner, the
• Be sure to use the flare nut provided with the unit. (Do tightening torque should increase suddenly. Tighten the
not use a different flare nut (such as a type-1 flare nut), flare nut further for the corresponding angle shown in
or otherwise refrigerant leakage may result.) Table 3.
• Perform the curing of the piping with pinching or taping
of the piping in order to prevent the intrusion of dirt, Table 3
dust, and moisture into the piping.
Recommended arm length of
Pipe size Further tightening angle
tool
CAUTION φ 6.4 60 to 90 degrees Approx. 150mm
• Be sure to use the specified type of refrigerant for the φ 9.5 60 to 90 degrees Approx. 200mm
refrigeration cycle and do not contaminate the φ 12.7 30 to 60 degrees Approx. 250mm
refrigerant with air. φ 15.9 30 to 60 degrees Approx. 300mm
• Ventilate the room in case of refrigerant leakage during
installation work. (2) On completion of installation work, check that there is no
gas leakage.

6 English

3P432203-1B

49
FXMQ-PAVE EDFMT391738

(3) Refer to the illustration on the right-hand side and be sure to • Perform nitrogen substituent or apply nitrogen into the
perform heat insulation work on the piping joints after gas refrigerant piping (see NOTE 1) in the case of refrigerant
leakage checks. (Refer to Fig. 6) piping blazing (see NOTE 2). Then perform the flare
connection of the indoor unit. (Refer to Fig. 7)
Heat insulation procedure for liquid piping
Insulation for fitting (4) (accessory) Refrigerant Pressurereducing valve
Insulation material piping
Flare nut joint Part to be
for piping Taping
(on unit side) brazed
Make sure that hands
Middle sealing pad (7) valve
Attached to the seam faces
upward. (accessory) Nitrogen
the surface.
Main unit Nitrogen
Clamp (8) Fig. 7
(accessory)

Insulation material Wrap the insulation material CAUTION


for piping (field supply) around the portion from the
surface of the main unit to the
• Do not use any antioxidant at the time of piping blazing.
upper part of the flare nut joint. The piping may be clogged with a residual antioxidant and
parts may malfunction.

NOTE
Liquid pipe 1. At the time of blazing, set the pressure of nitrogen to
approximately 0.02 MPa (close to the pressure of a
breeze coming in contact with the cheek) with a
decompression valve.
Gas pipe 2. Do not use flux at the time of blazing and connecting the
refrigerant piping. Use a copper phosphorus brazing alloy
Fig. 6 (BCuP-2: JIS Z 3264/BCu 93P-710/795: ISO3677), which
does not require flux, for blazing.
Heat insulation procedure for gas piping (Flux has a bad influence on the refrigerant piping. Chlo-
rine-based flux will cause piping corrosion. Furthermore, if
Insulation for fitting (5) (accessory)
Insulation material it contains fluorine, the flux will deteriorate refrigerant oil.)
Flare nut joint
for piping
• As for the branching of the refrigerant piping or refrigerant,
(on unit side) Make sure that
Middle sealing pad (7) refer to the installation manual provided with the outdoor unit.
Attached to the seam faces
upward. (accessory)
the surface.

Clamp (8)
7. DRAIN PIPING WORK
(accessory) (1) Conduct drain piping work.
Refrigerant
Insulation material Wrap the insulation material Check that the piping
piping
for piping (field supply) around the portion from the ensures proper draining.
surface of the main unit to the • Make sure that the
upper part of the flare nut joint. diameter of the piping Drain socket
excluding the rising part
Socket for
• Use the insulation for fitting (4) and (5) provided to the is the same as or larger maintenance
liquid piping and gas piping, respectively, and conduct than the diameter of the connecting (with rubber cap)
heat insulation work. pipe (vinyl chloride pipe with an outer diameter of
(Tighten both edges of the insulation for fitting (4) and (5) 32 mm and a nominal inner diameter of 25 mm).
for each joint with the clamp (8).) • Make sure that the piping is short enough with a down-
• Make sure that the joint of the insulation for fitting (4) and ward slope of at least 1/100 and that there is no air
(5) for the joint on the liquid piping and gas piping side bank formed. No drain trap is required.
faces upward.
• Wrap the middle sealing material (7) around the CAUTION
insulation for fitting (4) and (5) for the joint (flare nut • The drain piping will be clogged with water and water
part). leakage may result if the water is accumulated in the drain
piping.
CAUTION
• Conduct drain-up piping work if the gradient is
• Be sure to perform the heat insulation of the local piping
insufficient.
up to the piping joint.
• Attach a support bracket at 1 to 1.5 m intervals for the
If the piping is exposed, dew condensation may result.
Furthermore, a burn may be caused if a human body comes prevention of piping deflection.
in contact with the piping. Support bracket
1 - 1.5 m

Downward slope of at least 1/100

English 7

3P432203-1B

50
FXMQ-PAVE EDFMT391738

• Be sure to use the drain hose (2) and metal clamp (1). (2) Check the smooth draining of the piping on completion of
Insert the drain hose (2) deep into the base of the the installation of the piping.
drain socket, and securely fasten the metal clamp (1)
[Before electrical work]
within the taped part on the insertion front end of the
hose.
Be sure to fasten the screw of the metal clamp (1) until CAUTION
the margin of the screw thread decreases to 4 mm or • A licensed electrical engineering technician must conduct
less. electrical wiring work (including grounding work).
• If no licensed electrical engineering technician is
Metal clamp (1)
available, take steps 3 and 4 after the test operation of
(accessory)
the air conditioner is finished.

Tape Drain hose (2) 1. Remove the control box lid, and connect the single-
(accessory) phase electric wires to terminals L and N of the terminal
block and the ground wire to the ground terminal.
NOTE Perform wiring according to 10-1 CONNECTING POWER
SUPPLY, GROUND, REMOTE CONTROLLER, AND
Be sure to follow the instructions as below.
TRANSMISSION WIRING in 10. WIRING EXAMPLE
• Do not connect the drain piping directly to a sewer that
AND HOW TO SET THE REMOTE CONTROLLER.
smells of ammonia.
The ammonia in the sewer may reach through the drain
CAUTION
piping and corrode the heat exchanger of the indoor unit.
• Do not bend or twist the provided drain hose (2) in order • In order not to impose tension on the wire connections,
not to impose excessive force on the hose. (Doing so perform clamping securely with the provided clamp (8)
may result in water leakage.) specified in 3 in 10-1 CONNECTING POWER SUPPLY,
• Take the procedure shown in the following illustration to GROUND, REMOTE CONTROLLER, AND TRANSMISSION
perform concentrated drain piping. WIRING.

2. Check that the control box lid is closed before turning the
0 - 467 mm

air conditioner ON.


3. Provide approximately one liter of water gradually into
the drain pan through the water inlet on the bottom of the
drain socket or the outlet. Make sure that the water is not
Concentrated drain piping spilled onto the drain pump.
Maintain a downward slope of at least 4. The drain pump will operate with the power turned ON.
1/100 so that no air bank will be formed. Check that the pump drains water smoothly. (The drain
The drain piping will be clogged with water pump will stop automatically in 10 minutes.)
and water leakage may result if the water is The drainage can be checked with the water level change
accumulated in the drain piping.
in the drain pan through the water inlet.
• Select the diameter of the concentrated drain piping to
suit the capacity of equipment connecting to the CAUTION
concentrated drain piping (see the equipment design • Do not touch the drain pump.
sheet). Otherwise, an electric shock may be received.
Ceiling slab • Do not impose external force on the float switch.
300 mm max. 1 - 1.5 m
Otherwise, a failure may result.
Support bracket

5. On completion of the drainage check, shut off the power


700 mm max.

supply and disconnect the power supply line.


Drain-up piping 6. Put the control box lid to the original position.
(field supply)
[After electrical work]
Adjustable • After completion of 8. DUCT WORK provide approximately
Metal clamp (1) (accessory)
(467 mm max.) one liter of water gradually into the drain pan through the
Drain hose (2) (accessory) water inlet on the bottom of the drain socket, and check that
the water is drained while the air conditioner is in cooling
operation according to 11. FIELD SETTING and 12. TEST
Drain hose (2) (accessory)
OPERATION. Make sure that the water is not spilled onto
the electric parts of the drain pump and others.
Horizontal or
upward slope
(3) Be sure to conduct heat insulation work on the
following portions, or otherwise water leakage may
occur as a result of dew condensation.
Locate the drain hose horizontally • Drain piping indoors
or with a little upward gradient. • Drain socket
If there is an air bank, noise may be generated
as a result of a water backflow when the drain
pump comes to a stop.

8 English

3P432203-1B

51
FXMQ-PAVE EDFMT391738

• Explain the operation and washing methods of the locally


Drain pan Drain socket
procured components (i.e., the air filter, air inlet grille, and air
Service port
outlet grille) to the customer.
Control box lid • Locate the air outlet grille on the indoor side for the prevention
Control box of drafts in a position where indirect contact with people.
• The air conditioner incorporates a function to adjust the fan to
rated speed automatically. (11. FIELD SETTING)
Terminal block for
power supply Therefore, do not use booster fans midway in the duct.
Air outlet

Drain pump position Connection method of ducts on air inlet and outlet sides.
Inspection window • Connect the field supply duct in alignment with the inner side
Socket for maintenance of the flange.
(with rubber cap) Screw (3 positions) • Connect the flange and unit with the flange connection screw
Plastic water container (3).
Water inlet lid
• Wrap aluminum tape around the flange and duct joint in order
• On completion of the drainage check, refer to the following to prevent air leakage.
illustration, attaching insulation for drain socket (14) Flange on air inlet side Flange on air outlet side
without gap, and insulation from the top of drain hose (2) (provided with the unit) (provided with the unit)
• clamp of metal clamp (1) using large sealing pad (6).
Screws for duct Insulation material
flanges (3) (field supply)
Large sealing pad (6) (accessory) Screws
(accessory) Air inlet Unit Air outlet for duct
Pile on (14) and roll flanges (3)
Insulation material Canvas duct (accessory)
(field supply) (field supply)
Insulation for drain
socket (14) Shall not have gap
(accessory)
CAUTION
Start roll from near Connect the flange and unit with the flange connection screw (3)
tightening area of metal regardless of whether the duct is connected to the air inlet side.
clamp (1) Roll large sealing pad (6)
to make end side of clamp
fixture to be 2 layers
Metal clamp (1)
(accessory) 9. ELECTRIC WIRING WORK
Large sealing pad (6)
Drain hose (2) (accessory) 9-1 GENERAL INSTRUCTIONS
(accessory)
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
8. DUCT WORK • For electric wiring work, refer to also “Wiring diagram”
attached to the control box lid.
Pay the utmost attention to the following items and conduct • For remote controller wiring details, refer to the installation
the ductwork. manual attached to the remote controller.
• Check that the duct will not be in excess of the setting range • All wiring must be performed by an authorized electrician.
of external static pressure for the unit. (Refer to the technical • This system consists of multiple indoor units. Mark each
datasheet for the setting range. Each model has each setting indoor unit as unit A, unit B..., and be sure the terminal board
range of external static pressure.) wiring to the outdoor unit and BS unit are properly matched.
• Attach a canvas duct each to the air outlet and air inlet so that If wiring and piping between the outdoor unit and an indoor
the vibration of the equipment will not be transmitted to the unit are mismatched, the system may cause a malfunction.
duct or ceiling. • A circuit breaker capable of shutting down power supply to
Use a sound-absorbing material (insulation material) for the the entire system must be installed.
lining of the duct and apply vibration insulation rubber to the • Refer to the installation manual attached to the outdoor unit
hanging bolts. for the size of power supply wiring connected to the outdoor
• At the time of duct welding, perform the curing of the duct so unit, the capacity of the circuit breaker and switch, and wiring
that the sputter will not come in contact with the drain pan for instructions.
the filter. • Be sure to ground the air conditioner.
• If the metal duct pass through a metal lath, wire lath, or metal • Do not connect the ground wire to gas and water pipes,
plate of a wooden structure, separate the duct and wall lightning rods, or telephone ground wires.
electrically. • Gas pipes : might cause explosions or fire if gas leaks.
• Be sure to heat insulate the duct for the prevention of dew • Water pipes : no grounding effect if hard vinyl piping is
condensation. (Material: Glass wool or styrene foam; used.
Thickness: 25 mm) • Telephone ground wires or lightning rods : might cause
• Be sure to attach the field supply air filter to the air inlet of the abnormally high electric potential in the ground during
unit or field supply inlet in the air passage on the air suction lighting storms.
side. (Be sure to select an air filter with a duct collection
efficiency of 50 weight percent.)

English 9

3P432203-1B

52
FXMQ-PAVE EDFMT391738

9-2 ELECTRICAL CHARACTERISTICS NOTE


1. Shows only in case of protected piping. Use H07RN-F in
Units Power supply Fan motor case of no protection. (Do not lighter than 60245 IEC 57.)
Voltage 2. Vinyl cord with sheath or cable (Insulated thickness : 1 mm
Model Hz Volts MCA MFA kW FLA
range or more)
3. This size is based on IEC 60335-1 (Table 11), and this
FXMQ20PAVE 0.6 16 0.09 0.5
size must comply with local codes.
FXMQ25PAVE 0.6 16 0.09 0.5

FXMQ32PAVE 0.6 16 0.09 0.5


10. WIRING EXAMPLE AND HOW TO SET
FXMQ40PAVE 1.4 16 0.140 1.1
THE REMOTE CONTROLLER
FXMQ50PAVE 220- Max. 264 1.6 16 0.350 1.3
50
240 Min. 198 10-1 CONNECTING POWER SUPPLY, GROUND,
FXMQ63PAVE 1.8 16 0.350 1.4
REMOTE CONTROLLER, AND TRANSMISSION
FXMQ80PAVE 2.3 16 0.350 1.8 WIRING
FXMQ100PAVE 2.9 16 0.350 2.3 (Remove the control box lid as shown below and connect each
wire.)
FXMQ125PAVE 3.4 16 0.350 2.7

FXMQ140PAVE 3.4 16 0.350 2.7


(1) Remove the control box lid.

FXMQ20PAVE 0.6 16 0.09 0.5

FXMQ25PAVE 0.6 16 0.09 0.5

FXMQ32PAVE 0.6 16 0.09 0.5

FXMQ40PAVE 1.4 16 0.140 1.1

FXMQ50PAVE 1.6 16 0.350 1.3 Screw


Max. 242
60 220 (3 position)
FXMQ63PAVE Min. 198 1.8 16 0.350 1.4

FXMQ80PAVE 2.3 16 0.350 1.8

FXMQ100PAVE 2.9 16 0.350 2.3

FXMQ125PAVE 3.4 16 0.350 2.7

FXMQ140PAVE 3.4 16 0.350 2.7

MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) (2) Lay the wires in the control box through the wire inlet on the
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A) side of the control box.

9-3 SPECIFICATIONS FOR FIELD SUPPLIED Low-voltage wiring inlet


Transmission wiring
FUSES AND WIRE
(Low voltage)
Remote controller wiring
Remote controller wiring (Low voltage)
Power supply wiring
Transmission wiring
Model
Field fuses
Wire Size Wire Size

FXMQ20PAVE
FXMQ25PAVE High-voltage wiring inlet
FXMQ32PAVE Power supply wiring
Sheathed (High voltage)
FXMQ40PAVE H05VV- wire Earth wiring (High voltage)
FXMQ50PAVE U3G 2.5 mm2 (2 wire) 0.75 -
16A 1.25 mm2
FXMQ63PAVE (NOTE 1) (NOTE 3) (NOTE 2) CAUTION
FXMQ80PAVE
• Do not lay the remote controller wiring or transmission wiring
FXMQ100PAVE along with the power supply wiring or other electric wiring in
FXMQ125PAVE the same route. Separate the remote controller wiring and
FXMQ140PAVE
transmission wiring at least 50 mm from the power supply
wiring or other electric wiring, or otherwise malfunctions or
Allowable length of transmission wirings and remote controller failures may be caused by external electric noise that may
wiring are as follows. interfere with the remote controller wiring and transmission
(1) Outdoor unit – Indoor unit: wiring.
Max. 1000 m (Total wiring length: 2000 m) • For the installation and wiring of the remote controller, refer
(2) Indoor unit – Remote controller: to the remote controller installation manual provided with the
Max. 500 m remote controller.
• For power supply wiring, refer to the wiring diagram as well.
• Be sure to connect the remote controller wiring and
transmission wiring correctly to the right terminal block.

10 English

3P432203-1B

53
FXMQ-PAVE EDFMT391738

(3) Follow the instructions below, and lay the wires in the (5) Mount the provided wire fixing bracket (12) with the wire
control box. fixing screw (13). Fix each wire with the provided clamp (8).

Transmission wiring
Fix clamp material (8) at Low voltage wiring
accessory fixture on the connection method
Remote
control wiring
Remote controller wiring
control box. • If stranded About of sleeve area
wires are used, 7 mm Power supply wiring
do not solder After Earth wiring
Transmission wiring the front end scalping
(Low voltage) of the wires. wiring,
twisted
Remote controller wiring together 70~90mm
(Low voltage) PROHIBITED
Never connect Operation
the power supply terminal
(X2M)
strip
wiring. Transmission
Pass through wiring Clamp material
internal control box (No polarity) (8) (accessory)

P1 P2 F1 F2 T 1 T2
within sleeve area

Wire fixing screw


Power supply wiring (13) (accessory)
(High voltage) Remote
Earth wiring controller wiring
(No polarity)
(High voltage)
Wire fixing bracket
Insert the cord into the (12) (accessory)
wire clips provided with High voltage wiring connection method
the control box. Sleeve area
Power supply terminal strip
(X1M)
Fix the wires with clamp (8) Power L
supply N
to the wire fixing wiring [Precautions for Power Supply Wiring]
bracket provided to 70~90mm Earth
the control box. wire
(Sleeve • Connect round crimp-style terminals provided with insulation
stripping length)
sleeves to the terminal block for power supply.

Attach insulation sleeve


WARNING
Trim and lay the wiring neatly and attach the control box lid
securely.
An electric shock or fire may result if the control box lid catches Round crimp-style terminal
any wiring or the wires push up the lid. Electric wire

(4) Put the control box lid, and wrap the wire sealing material Be sure to follow the instructions provided below if the
(Small) (10) around the wires so as to block the wire specified terminals cannot be used.
through holes. Otherwise, abnormal heat may be generated as a result
of the loosening of the wires.
Wire through
holes Connect the wires Do not connect a Do not connect
evenly. wire to the single wires different
side only. from each other in
Putty or insulation diameter.
Sealing material material
small (10) (Field supply)
(Accessories part)

Transmission wire • earth wire • If stranded wires are used, do not solder the front end of the
• power supply wire or remote
controller wiring wires.
• Connect proper wires securely and fix the wires so that
external force will not be imposed on the terminals.
• Use an appropriate screwdriver to tighten the terminal
screws. The screw heads may be damaged if the screwdriver
CAUTION
is too small and the terminal screws will not be tightened
• After all the wiring connections are done, fill in any gaps in properly.
the through holes with putty or insulation (procured locally) to • Do not tighten the terminal screws excessively, or otherwise
prevent small animals and insects from entering the unit from the screw heads may be damaged.
outside. (If any do get in, they could cause short circuits in • Refer to the table below for the required tightening torque
the control box.) values of the terminal screws.
Tightening torque (N·m)
Terminal block for remote controller
0.80 - 0.96
and transmission wires
Terminal block for power supply 1.18 - 1.44

10-2 WIRING EXAMPLE


WARNING
Install an earth leakage breaker.
The installation of an earth leakage breaker is imperative for the
prevention of electric shocks and fire accidents.

English 11

3P432203-1B

54
FXMQ-PAVE EDFMT391738

No. 1 system: When using 1 remote controller for 1 indoor No. 3 system: When including BS unit
unit
Power supply
single phase
Power supply Power supply Power supply
50Hz 220-240V
single phase single phase single phase
50Hz 220-240V 50Hz 220-240V 50Hz 220-240V or
or or or single phase Outdoor unit BS unit
60Hz 220V
single phase single phase single phase
60Hz 220V Outdoor unit 60Hz 220V 60Hz 220V L N
IN/D OUT/D OUT/D IN/D
F1 F2 F1 F2 F1 F2 F1 F2
L N L N L N
IN/D OUT/D
F1 F2 F1 F2

L N P1 P2 F1 F2 T1 T2
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2

Indoor unit A Indoor unit B Most Indoor unit A


downstream
Indoor unit
P1 P2 P1 P2 P1 P2 P1 P2

Remote controller Remote controller Remote controller


Remote controller
(option) (option) (option)
(option)

[ PRECAUTIONS ]
No. 2 system: For group control or use with 2 remote
1. If no earth leakage breaker is required, install a breaker or
controllers
load switch with a fuse for the wiring. If an earth leakage
breaker is required, make sure that the earth leakage
Power supply
single phase breaker is designed to protect the air conditioner from
50Hz 220-240V ground faults, overloads, and short-circuiting.
or 2. The remote controller wiring (P1 and P2) and transmission
single phase
60Hz 220V Outdoor unit Note) There is not need to set the indoor unit
wiring (F1 and F2) have no polarity.
L N address when using group control.
IN/D OUT/D
F1 F2 F1 F2 (It is automatically set when the power 10-3 CONTROL BY 2 REMOTE CONTROLLERS
is turned on.)
(Controlling 1 indoor unit by 2 remote controllers)
• Set one of the remote controllers to main and the other to sub
in the case of remote control with two remote controllers.

Most down- Switching Main/Sub


L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 stream
indoor unit (1) Insert a screwdriver into the clearance between the
Indoor Indoor unit B
grooves of the lower casing and the upper casing to remove
unit A
the upper casing. (2 grooves) (The remote controller PCB is
P1 P2
Case of group control
P1 P2 P1 P2 attached to the upper casing.)
Remote controller Remote controller Remote controller Upper part of
(option) (option) remote controller
For use with 2
remote controllers

Lower part of
remote controller

Insert the screwdriver here and gently work


off the upper part of remote controller.

12 English

3P432203-1B

55
FXMQ-PAVE EDFMT391738

(2) Set the main/sub switch on one of the remote controller • For setting and operation, refer to the “FIELD SETTING” in
PCBs to sub. (Keep the switch of the other remote controller the installation manual of the remote controller.
PCB set to main.)
SECOND
CODE NO.
MODE NO.
S FIRST
(Factory setting)
M CODE NO.
SETTING FIELD SET
Remote controller MODE
PC board
Only one remote
S
controller needs to be • Set the remote controller to the “FIELD SET MODE”. For
M
changed if factory details, refer to the “HOW TO SET IN THE FIELD”, in the
settings have
remained untouched. remote controller manual.
• When in the “FIELD SET MODE”, select “MODE NO.
12”, then set the “FIRST CODE NO.” to “1”. Then set
10-4 COMPUTERISED CONTROL (FORCED OFF “SECOND CODE NO.” to “01” for FORCED OFF and “02”
AND ON/OFF OPERATION) for ON/OFF OPERATION. (FORCED OFF at factory set)
(1) Wire specifications and how to perform wiring
• Connect the input from outside to terminals T1 and T2 of With Wireless Remote Controller Used
the terminal block for remote controller. Set the wireless remote controller address before using the
wireless remote controller.
For the setting method of the address, refer to the operation
F2 T1 T2 manual provided with the wireless remote controller.
FORCED NOTE
OFF
• A “MODE NO.” is set on a group basis. To make a mode
Input A setting on a room unit basis or check the setting made, however,
set the corresponding mode number in the parentheses.
Wire specification Sheathed vinyl cord or cable (2 wire) 1. Settings for Optional Accessories
Gauge 0.75 - 1.25 mm
2 • In the case of connecting optional accessories, refer to
the operation manuals provided with the optional
Length Max. 100 m
accessories and make necessary settings.
Contact that can ensure the minimum appli-
External terminal 2. External Static Pressure Settings
cable load of 15 V DC, 10 mA.
Make settings in either method (a) or method (b) as
(2) Actuation explained below. (FXMQ140PAVE cannot be selected
• The following table explains FORCED OFF and ON/OFF method (a). Please select method (b).)
OPERATIONS in response to Input A. (a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is
FORCED OFF ON/OFF OPERATION automatically adjusted to the rated quantity.
Input “ON” stops operation (impossible by Input OFF → ON turns (1) Check that power supply wiring to the air conditioner
remote controllers.) ON unit. is completed along with duct installation. If a closing
damper is installed in the air-conditioning system,
Input OFF enables control by remote con- Input ON → OFF turns make sure that the closing damper is opened.
troller. OFF unit.
Furthermore, check that the air filter as a field supply
(3) How to select FORCED OFF and ON/OFF OPERATION is attached to the air passage on the suction side.
• Turn the power on and then use the remote controller to (2) If there are a number of air outlets and inlets, adjust the
select operation. throttles so that the airflow rate of each air outlet and
inlet will coincide with the designed airflow rate. At that
10-5 CENTRALIZED CONTROL time, operate the air conditioner in “fan operation mode”.
• For centralized control, it is necessary to designate the group To change the airflow rate, press and set the airflow
No. For details, refer to the manual of each optional control- adjustment button of the remote controller to HH, H, or L.
lers for centralized control. (3) Make settings for airflow automatic adjustment. After
setting the air conditioner to “fan operation mode”,
stop the air conditioner, go to “FIELD SET MODE”,
11. FIELD SETTING select “MODE NO. 21” (11 in the case of group
settings), set the setting “FIRST CODE NO.” to 7, and
NOTE
set the setting “SECOND CODE NO.” to 03.
• Before the test operation of the outdoor unit as explained in Return to normal mode after these settings, and press
12. TEST OPERATION, be sure to make the following field the ON/OFF OPERATION button. Then the operation
settings as explained in 11. FIELD SETTING. lamp will be lit and the air conditioner will go into fan
operation for airflow automatic adjustment. Do not
Make sure the control box lids are closed on the indoor and adjust the throttles of the air outlets or inlets during
outdoor units. automatic adjustment of the air conditioner. After the
Field setting must be made from the remote controller in air conditioner runs approximately one to eight
accordance with the installation condition. minutes, the air conditioner will finish airflow
• Setting can be made by changing the “MODE NO.”, “FIRST adjustment automatically, the operation lamp will be
CODE NO.”, and “SECOND CODE NO.”. turned OFF, and the air conditioner will come to a stop.

English 13

3P432203-1B

56
FXMQ-PAVE EDFMT391738

Table 4 Table 5
MODE NO. FIRST CODE NO. Setting contents External Static FIRST SECOND
MODE NO.
Airflow Pressure CODE NO. CODE NO.
11 (21) 7
adjustment 30Pa (*1)(*4) 01
SECOND CODE NO. 50Pa 02
01 02 03 60Pa 03
Completion of Start of airflow 70Pa 04
OFF
airflow adjustment adjustment 80Pa 05
90Pa 06
(4) After the air conditioner stops operating, check with
100Pa 07
“MODE NO. 21” on an indoor unit basis that 02 is set
for the “SECOND CODE NO.” in Table 4. If the air 110Pa (*3) 08
conditioner does not stop operating automatically or 120Pa (*3) 13 (23) 06 09
the “SECOND CODE NO.” is not 02, repeat steps 130Pa (*3) 10
from (3). If the outdoor unit is not turned ON, U4 or 140Pa (*3) 11
UH as explained in Table 8 will be displayed. This
150Pa (*3)(*4) 12
display is not problematic, because this function is
set for the indoor unit. Continue setting the function. 160Pa (*3)(*4) 13
After setting this function, be sure to turn ON the 180Pa
14
outdoor unit before the test operation of the outdoor (*2)(*3)(*4)
unit. If any other error is displayed, refer to Table 8 200Pa
15
and the operation manual provided with the outdoor (*2)(*3)(*4)
unit and check the defective point.
CAUTION
CAUTION Keep in mind that a shortage of airflow quantity or water leakage
will result because the air conditioner will be operated outside
• If there is any change after airflow adjustment in the the rated range of airflow quantity if the external static pressure
ventilation paths (e.g., the duct and air outlet), be sure to is wrongly set.
make airflow auto adjustment again.
• Consult your Daikin representative if there is any change
3. Filter Sign Settings
in the ventilation paths (e.g., the duct and air outlet) after
• The remote controller is provided with an LCD that tells
the test operation of the outdoor unit is finished or the the time of air filter cleaning.
air conditioner is moved to another place. • If the air conditioner is used in places with excessive dust,
change the “SECOND CODE NO.” as shown in Table 6.
(b) Select External Static Pressure with Remote Controller The “SECOND CODE NO.” is set to 01 (standard) at
Check that 01 (OFF) is set for the “SECOND CODE NO.” factory set.
in “MODE NO. 21” for airflow adjustment on an indoor Table 6
unit basis in Table 4. The “SECOND CODE NO.” is set to
Time for MODE FIRST SECOND
01 (OFF) at factory set. Change the “SECOND CODE Dirt display NO. CODE NO. CODE NO.
NO.” as shown in Table 5 according to the external static
Standard Approximately
pressure of the duct to be connected. 01
2500 hours
(1) The “SECOND CODE NO.” is set to 07 (an external 0
Excessive Approximately 10 (20)
static pressure of 100 Pa) at factory set. (FXMQ40 · dust 1250 hours 02
50 · 63 · 80 · 100 · 125 · 140PAVE) No display (*) 3
The “SECOND CODE NO.” is set to 02 (an external
* Select “No display” under conditions in which the cleaning
static pressure of 50 Pa) at factory set. (FXMQ20 · 25
display is not required, such as the time of regular maintenance.
· 32PAVE)
*1 The FXMQ50 · 63 · 80 · 100 · 125PAVE cannot
be set to 30 Pa. 4. Switching time of the dry operation at VRTsmart control
*2 The FXMQ40PAVE cannot be set to 180 or 200 Pa. setting.
*3 The FXMQ20 · 25 · 32PAVE cannot be set to • If you change the operation mode to “Dry” when
110-200 Pa. VRTsmart control is in effect, the operation mode is
change to “Cooling” after certain period of time.
*4 The FXMQ140PAVE cannot be set to 30 Pa and
If you want to continue dry operation longer, please change
150-200 Pa. the setting position as mentioned in the table below.
(Setting position of factory setting is “0”.)
※ If you keep dry operation longer, energy saving
performance decrease.
Mode Setting switch Setting position
Dry operation number
number number
30 min 01
60 min 02
10 10
90 min 03
Continuous (Not return 04
to Cooling)

※ At the time of Group control setting, Dry operation time for


the indoor units in the same group shall be the same
setting value.

14 English

3P432203-1B

57
FXMQ-PAVE EDFMT391738

NOTE 13. WEIGHT AND DIMENSION


For VRTsmart control function it is necessary to connect with
Width Length Height Weight
an outdoor unit with a compatible function. Model
(mm.) (mm.) (mm.) (kg.)
FXMQ20 • 25 • 32PAVE 700 550 300 25
12. TEST OPERATION FXMQ40PAVE 700 700 300 27
Refer to the installation manual of the outdoor unit. FXMQ50 • 63 • 80PAVE 700 1,000 300 35
• The operation lamp of the remote controller will flash when FXMQ100 • 125PAVE 700 1,400 300 45
an malfunction occurs. Check the malfunction code on the
liquid crystal display to identify the point of trouble. An FXMQ140PAVE 700 1,400 300 46
explanation of malfunction codes and the corresponding
trouble is provided in “CAUTION FOR SERVICING” of the
outdoor unit. If any of the items in Table 8 are displayed,
there may be a problem with the wiring or power, so check
the wiring again.

Table 7
Remote controller display Contents
Error in power supply voltage to
“A8” lit
indoor unit.
Fan driver PCB of indoor unit ↔
“C1” lit indoor control PCB transmission
error.
Improper combination of fan driver
“C6” lit PCB of indoor unit or setting failure
in control PCB type.
Test operation of outdoor unit has
“U3” lit
not been finished.

Table 8
Remote control display Content
• There is a short circuit at the
“ ” is lit up
FORCED OFF terminals (T1, T2)
• The power on the outdoor unit is
off.
• The outdoor unit has not been
“U4” is lit up
wired for power supply.
“UH” is lit up
• Incorrect wiring for the transmis-
sion wiring and / or FORCED OFF
wiring.
• The power on the indoor unit is
off.
• The indoor unit has not been
wired for power supply.
No display
• Incorrect wiring for the remote
controller wiring, the transmission
wiring and / or the FORCED OFF
wiring.

CAUTION
If interior finish work is continuing on completion of the test
operation of the air conditioner, explain the customer not to
operate the air conditioner until the interior finish work is
completed for the protection of the air conditioner.
Otherwise, substances that will be generated from interior finish
work materials, such as paint and adhesive agents, may
contaminate the air conditioner.

English 15

3P432203-1B

58
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trade mark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

●Specifications, designs and other content appearing in this brochure are current as of September 2017 but subject to change without notice.

©All rights reserved 09/17 FS

You might also like