Professional Documents
Culture Documents
The first part of the experiment was to observe and analyze the standing waves on a short-ended line
for different electrical lengths. It was done by using the transmission lines circuit board. First, the signal
generator 50Ω output was connected to the sending end of the transmission line A, the receiving end of
transmission line A to the sending end of transmission line B, and the receiving end of transmission line
B to the input if the load section with the use of a coaxial cable. The channel 1 of the oscilloscope was
connected to the 0-meter probe turret of the transmission line A and the signal generator 100 Ω output
was connected to the triggering input of the oscilloscope using a coaxial cable. In the load section, the
toggle switches were set in such a way as to connect the input of the section directly to the common in
order to place the impedance of the load at the receiving end of the line made by transmission lines A
and B connected end-to-end in the short circuit condition, as shown in figure 1, using the oscilloscope
settings below.
Figure 1
In order to set the frequency of the sinusoidal voltage produced by the generator in the signal generator
section, the frequency knob was set to the fully clockwise position. The frequency of the signal generator
voltage was decreased by slowly turning the frequency knob fully counter clockwise in order to observe
that as the frequency is decreased, the amplitude of the displayed voltage continually varies, alternating
between some maximum and some minimum values. The oscilloscope probe was connected to each
probe turrets listed below in order to measure the peak amplitude of the sinusoidal voltage along the
entire length of the line.
∙ 0-m turret of line A
Figure 2
The insertion loss in dB was calculated using 20log(VR/VS). The distributed attenuation constant per unit
length, a’, in dB/m, was calculated using Insertion loss(48 m/157.4 ft)/l, in which l is the length of the line (m).