Professional Documents
Culture Documents
45
Digital Object Identifier 10.1109/MIAS.2008.927531
1077-2618/08/$25.00©2008 IEEE
from load centers. Generators in eastern prior to a complete system voltage col-
Canada and the midwestern United lapse. Voltage separation, in addition
States provide large amounts of power UNDERFREQUENCY to frequency, may be required to allow
to the east coast load centers such as the industrial system to detect utility
New York City. Generators in Wash- AND impeding system collapse. This article
ington, Oregon, and western Canada discusses the need for undervoltage as
provide substantial power to California. UNDERVOLTAGE well as underfrequency separation and
This contrasts with the operation of SCHEMES ON THE proposes secure undervoltage load sepa-
utilities 35 years ago, when each utility ration schemes that avoid false opera-
had in-house generation to supply its UTILITY SYSTEM ARE tions for such events as slow-clearing
own load. Two factors promote genera- system faults.
tion that is remote from load centers: DESIGNED TO
1) the economics of purchasing pow- Types of Power System
er from lower-cost remote sources RESTORE THE Instabilities During System
rather than more expensive local Blackouts
generation BALANCE BY
2) the public’s reluctance or refusal SHEDDING LOAD. Voltage Versus Frequency Stability
to permit new generating plants In a power system, frequency is a
to be built in urban high-load measure of the balance of MW genera-
areas, causing utilities/independ- tion and MW load. When MW gener-
ent power producers (IPPs) to build these plants re- ation and MW load are exactly in balance, the frequency is
mote from these load centers. at the normal level of 60 Hz. When the load exceeds gen-
These two fundamental changes in the operation of the eration, the frequency goes down. The rate of decline
U.S. power grid result in the transmission of power over depends on the inertia of the generators within the system.
long distances. This makes the power grid dependent on Under normal conditions, there are slight changes of
the transmission system to deliver power to the load cen- frequency when load suddenly increases or generation
ters. It also results in increased reactive power losses trips offline, which results in a slight (generally in hun-
because the impedance of transmission lines is primarily dreds of hertz) reduction in frequency until the aggregate
reactive. Thus, when transmission lines trip, the remain- generation in the system can be increased to meet the new
ing lines must carry the load, which results in much load condition. If there is a large negative unbalance
higher reactive (vars) than resistive [megawatt (MW)] between MW load and MW generation, the frequency
losses, and consequently, a voltage drop at the load center, will go down. Underfrequency schemes on the utility sys-
IEEE INDUSTRY APPLICATIONS MAGAZINE SEPT j OCT 2008 WWW.IEEE.ORG/IAS
whereas the frequency remains normal. tem are designed to restore the balance by shedding load.
Reactive power (vars) cannot be transmitted very far, Voltage in a power system is a measure of the balance of
especially under heavy load conditions and instead must MVAr load and MVAr capability within the system. If that
be generated close to the point of consumption. This is reactive support is not available, the voltage will drop. The
because the difference in voltage causes vars to flow. Volt- impact of reduced voltage on load depends on the nature of
age on a power system can vary only by 5% of nominal. the load. For resistive load, the load current will decrease
This small voltage change will not cause substantial var and help limit the need for local reactive support. Motor
flow over long distances. Real power (MW) can be trans- loads are essentially constant kVA devices. The lower the
mitted over long distances through the coordinated opera- voltage, the more current they draw, increasing the need for
tion of the interconnected grid. Reactive power must be local reactive support. Power system loads consist of both
generated at, or near, the load center. resistive loads as well as reactive motor loads. However, dur-
Since vars cannot be transmitted over long distances, ing hot weather, air conditioning motor loads make up a
the sudden loss of transmission lines results in an instanta- large portion of utility total load, thereby making the
neous need for local reactive power to compensate for the power system more susceptible to voltage collapse.
increased losses of transporting the same power over fewer Reactive power system support can only come from two
transmission lines. If that reactive support is not available sources: shunt capacitors and generators/synchronous con-
at the load center, the voltage will decrease. System densers. Shunt capacitors are a double-edged sword. They
frequency, on the other hand, will remain stable because do provide reactive support, but they also generate fewer
the real power from remote generators continues to flow vars as the voltage dips. The VAr output of a capacitor bank
over fewer transmission lines. is reduced by the square of the voltage. Shunt capacitor
For these reasons, voltage rather than frequency has banks cannot quickly adjust the level of reactive power.
become the key indicator that the power system is under Generation at the load center can provide a dynamic
stress. Utilities have begun to recognize this and are imple- source of reactive power. As the voltage goes down, the
menting undervoltage load shedding (UVLS) schemes to generator can quickly provide increased reactive support
complement their existing underfrequency load shedding within its capability limits. Unlike shunt capacitors, the
(UFLS). Industrial customers with in-house cogeneration amount of reactive support does not drop as system volt-
have long used underfrequency as the principle means of age goes down. The amount of reactive power is controlled
deciding when to separate from the utility system and by the generator automatic voltage regulator (AVR). It is
transfer their critical loads to their own generation. But essential that the AVR control is properly set and the gener-
46
frequency can remain normal, as voltage sags to a low level ator protection system allows the generator to contribute
the maximum reactive power to support the system with- from key transmission system substations because of a
out exceeding the generator’s capability. computer problem at the system operating center.
In the case described above, voltage decay was relatively
Voltage Instability slow and there was time for utility system operator interven-
Figure 1 illustrates a simplified power system with a tion to address the voltage decay problem. There have been
remote generator supplying a substantial portion of the cases where the voltage decayed so rapidly that operator
load at the load center through six transmission lines. Es is action was not possible. These cases involve slow-clearing
the voltage at the remote generator buses, and Eg is the multiphase transmission system faults that occur during
voltage at the load center buses. heat storm conditions when the utility load is primarily
Figure 2 illustrates how the voltage decays as real made up of air conditioning motors. The extended length of
power transferred to the load center increases. This type of the voltage dip causes motors in the area to stall and draw
P-V analysis (real power relative to voltage) is an analysis large amounts of reactive power after the fault is cleared.
tool used by utility system planners to determine the real The rapid change in load power factor results in low system
power transfer capability across a transmission interface to voltage. Since there is little reserve of reactive power during
supply local load. Starting from a base-case system (all peak load periods, the area voltage collapses. Such an event
lines in service), computer-generated load flow cases are occurred in western Tennessee and resulted in an outage to
run with increasing power transfers while monitoring vol- 1,100 MW of load. The entire event took less than 15 s [2].
tages at critical buses. When power transfers reach a maxi-
mum level, a stable voltage cannot be sustained, and the Phase Angle Instability
system voltage collapses. When the voltage phase angle between remote generators
On a P-V curve (Figure 2), this point is called the nose and local generators (hg hs in Figure 1) becomes too
of the curve. The shape of the nose of the curve depends on
the nature of the load at the load center. High levels of
motor load combined with capacitor bank support of load MW Power Flow
center voltage tend to make the voltage drop very rapidly
for a small increase of power at the nose of the curve. The Line 1
set of P-V curves illustrates that for baseline conditions Line 2
shown in Curve A, the voltage remains relatively steady Line 3
Remote Local Load
(changing along the vertical axis) as local load increases. Generation Line 4 Center
System conditions are secure and stable to the left of Point
Line 5
A1. After a contingency occurs, such as a transmission cir-
cuit tripping, the new condition is represented by Curve B, Line 6
Line 2 trips, the height of the power angle curve is reduced larger the generator, the shorter is the time to drive the
further to where the power being transferred cannot be machine unstable for a system fault.
maintained and the system goes unstable. Figure 4 illustrates a typical breaker-and-a-half power
At this point, the power system is in deep trouble. Dur- plant substation with a generator and a short circuit on a
ing unstable conditions, the power system breaks up into transmission line near the substation. If the short circuit is
islands. If there is more load than generation within the three phase, very little real power (MW) will flow from
island, frequency and voltage go down. If there is an excess the generator to the power system until the fault is
of generation in an island, frequency and voltage generally cleared. The high fault current experienced during the
go up. Voltage collapse and steady-state instability occur short circuit is primarily reactive or VAr current. From
together as transmission line tripping increases the reactance the power transfer equation (Figure 3), it can be seen that
Pmax = Eg Es
X
Maximum Power Transfer Equation
Power All Lines Pe = Eg Es sin (θg – θs)
Transfer in Service
X
Line 1
Es = Voltage at the Load Center Generation
Tripped
Eg = Voltage at the Remote Generation
Pe Pe = Electrical Real Power Transfer
Line 2
X = Reactance Between Local and
Tripped
Remote Generation
θs = Voltage Angle at Local Generation
θg = Voltage Angle at Remote Generation
0 90° 180°
θg – θs
3
48
Power angle analysis: steady-state instability.
when Eg drops to almost zero, almost no real power can be Utility Load-Shedding Programs
transferred to the system. The generator AVR senses the Automatic load-shedding programs are designed into utility
reduced generator terminal voltage and increases the field cur- electrical systems to operate as a last resort, under the theory
rent to attempt to increase the generator voltage during the that it is wise to shed some load in a controlled fashion if it
fault. The AVR control goes into field-forcing mode, where can forestall the loss of a great deal of load to an uncontrolled
field current is briefly increased beyond steady-state field cir- cascading event. There are two kinds of automatic load-
cuit thermal limits. During the short circuit, the mechanical shedding installed in North America—UVLS, which sheds
turbine power (PM ) of the generator remains unchanged. The load to prevent local area voltage collapse, and UFLS,
resulting unbalance between mechanical (PM ) and electrical designed to rebalance load and generation within an electri-
power (Pe ) manifests itself with the generator accelerating, cal island once it has been created by a system disturbance.
increasing its voltage phase angle with respect to the system Automatic UVLS responds directly to voltage condi-
phase angle as illustrated in the power angle plot in Figure 5. tions in a local area. UVLS drops several hundred mega-
The speed with which the generator accelerates depends watts of load in preselected blocks within load centers,
on its inertia. If the transmission system fault is not cleared
quickly enough, the generator phase angle will advance so
that it will be driven out of synchronism with the power
system. Computer transient stability studies can be used to
establish this critical switching angle and time. The equal Power System Es ∠ θs
area criteria can also be applied to estimate the critical
switching angle (hc ). When area A1 ¼ A2 in Figure 5, the
generator is just at the point of losing synchronism with Three-Phase
the power system. Note that after opening Breakers 1 and 2 Short Circuit
to clear the fault, the resulting power transfer is reduced Substation
because of the increase in reactance (X) between the genera-
tor and the power system. This is due to the loss of the 1 2
faulted transmission line. In the absence of detailed studies,
many users establish the maximum instability angle at
120°. Because of the dynamic nature of the generator to
recover during fault conditions, the 120° angle is larger
than the 90° instability point for steady-state instability
conditions. The time that the fault can be left on the system GSU
that corresponds to the critical switching angle is called the
each reliability coordinator region. These systems are Today, most industrial facilities use frequency as a measure
designed to drop predesignated customer loads automati- of utility power system security and initiate separation
cally if frequency gets too low (since low frequency indi- when the frequency drops to a specific level for a short
cates too little generation relative to load), starting time (typically 8–12 cycles). Some industrial facilities use
generally when frequency drops to 59.3 Hz. More load is rate of change of frequency to separate from the utility.
progressively dropped as frequency levels fall farther. The The use of frequency alone will not separate the industrial
last step of load shedding is set at the frequency level just facility for cases where the voltage is collapsing. Since volt-
above the setpoint for generation underfrequency protec- age is the leading edge indicator of recent utility power sys-
tion relays (around 57.5 Hz) to prevent frequency from tem collapse, voltage as well as frequency needs to be used
falling so low that generators could be damaged. to initiate separation from the utility system. Figure 7
There are two basic types of UVLS schemes that utilities shows a typical industrial installation with both undervolt-
have installed. Both types involve the installation of under- age (27) and underfrequency (81) relays.
voltage relays at key utility substations. These relays must Because of VT availability, underfrequency relays are
measure the transmission system voltage and are typically typically connected on the secondary at the industrial
facility because frequency is the same on both the high
and low side of the transformer. In new installations, both
voltage and frequency could be measured for the VTs on
Utility Transmission System
the primary of the utility supply transformer. As in the
27
case of utility UVLS, voltage measurement for undervolt-
Typical Distribution age separation must be on the transformer primary
Trip Selected Substation Transformer because transformer losses and LTC controls will distort
Circuits (A-D) with LTC the true transmission system voltage level. Once the sig-
nal to separate from the utility is generated, the main
81 27 = Undervoltage Relay incoming breakers (A and/or B) are tripped and the facil-
81 = Underfrequency Relay
ity load is isolated on to in-house cogeneration. This may
result in a momentary overload on the in-house genera-
A B C D tion. Traditionally, after separation, some industrial fa-
cilities have used in-house UFLS schemes to match load
6 to cogeneration. In recent years, load-monitoring systems
50
Typical utility substation load shedding. that monitor in-house generation and facility loads in real
time have been used to match load to generation after To account for the 120° phase angle displacement between
utility separation [5]. phases, unit phasors (a and a2 ) are used in symmetrical
Without the use of voltage to augment frequency to component terminology. For completely balanced three-
decide when to separate from the utility, the industrial phase voltages, the negative sequence voltage is zero. Nega-
facility risks being dragged down for a voltage collapse. If tive sequence voltage blocking is used to detect unbalanced
utilities are starting to implement UVLS, it makes sense fault conditions and block the separation scheme from im-
for industrials to consider installing undervoltage separa- proper operation.
tion schemes.
Positive Sequence Separation Logic
Designing a Secure Undervoltage Another logic scheme to enhance security for voltage sepa-
Separation Scheme ration is shown in Figure 9. The scheme is similar to that
The design of a secure undervoltage separation scheme that shown in Figure 8. The blocking elements are the same.
avoids false operations for such events as slow clearing system But, this logic scheme uses positive sequence rather than
faults requires some logic as well as a relay that can accurately individual phase-to-neutral voltages to detect an undervolt-
measure voltage within acceptable limits. The undervoltage age condition. Positive sequence voltage is a symmetrical
relay needs to be highly accurate. A measurement accuracy of component term and is defined by the following equation:
0.5 V on a 120 V basis is required. Also, the undervoltage
relay that is used needs to have a high pickup-dropout ratio. V1 ¼ 1=3 (Va þ aVb þ a2 Vc ),
This ratio needs to be near 100% so that when voltage recov-
ers after a system fault, the relay will quickly reset to the where Va , Vb , and Vc are line-to-neutral voltages,
non-trip condition. To meet these requirements, as well as
the logic described in the following section, digital relays are a ¼ 1=120 ,
almost exclusively being used for UVLS. Industrial facilities
can benefit from the logic schemes employed by utilities that a2 ¼ 1=240 :
have implemented UVLS.
condition. Two-out-of-three logic is common in nuclear of undervoltage separation schemes in addition to their
plant voltage separation schemes. existing underfrequency schemes to address the voltage
collapse scenario.
Setting Considerations This article proposes undervoltage separation logic
Prior to embarking on the design of an undervoltage sepa- schemes that can be easily installed within digital relays to
ration scheme, it is prudent to contact the utility to which enhance the security of an undervoltage separation to pre-
the industrial customer is connected and also the local area vent false operation due to slow-clearing system faults. The
NERC regional reliability council. Councils such as the article also indicates the required point of installation of
WECC have developed UVLS guidelines for their mem- these relays so that they properly measure system voltage.
bers [4]. It is also difficult for the industrial customer to
References
[1] U.S.-Canada Power System Outage Task Force. (2004, Apr. 5). Final
report on the August 14, 2003 blackout in the United States and Canada:
V1 < Setpoint 1 Causes and recommendations [Online]. Available: http://www.nerc.com
27
[2] G. C. Bullock, ‘‘Cascading voltage collapse in West Tennessee,’’
Positive presented at Georgia Tech Protective Relaying Conf., Atlanta, GA,
Sequence May 1990.
Undervoltage [3] IEEE Guide for AC Generator Protection, ANSI/IEEE C37.102-1992.
[4] UVLS Task Force, WECC. (1999). Undervoltage Load Shedding Guide-
Va < Setpoint 2 lines [Online]. Available: http://www.wecc.biz
27B
Vb < Setpoint 2 OR x AND [5] K. Shah, R. Hofstetter, M. S. Miguel, and M. Tiffany, ‘‘Load preserva-
Undervoltage Vc < Setpoint 2 tion systems at facilities utilizing co-generation for real time protec-
Block tion of critical loads during utility outages,’’ in Proc. IEEE Industry
Applications Society 52nd Annu. Petroleum and Chemical Industry Conf.,
Adjustable 2005, pp. 85–93.
Timer [6] J. L. Blackburn, Symmetrical Components for Power System Engineers. New
47B V2 > Setpoint 3 x York: Marcel Dekker, 1993.
Negative
Sequence Undervoltage Charles J. Mozina (cmozina@aol.com) is with Beckwith Elec-
Overvoltage Trip tric Co. Inc., Largo, Florida. He is a Member of the IEEE.
Block This article first appeared as ‘‘Power System Blackouts—Mini-
9 mizing Their Impact at Industrial Cogeneration Facilities’’ at
52
Positive sequence undervoltage separation logic. the 2006 Petroleum and Chemical Industry Conference.