Professional Documents
Culture Documents
The horizontal and vertical confining elements shall be bonded together and
anchored to the elements of the main structural system.
In order to obtain an effective bond between the confining elements and the
masonry, the concrete of the confining elements shall be cast after the masonry has
been built.
1
- Hall system – a structural system with distance between walls >9.00m
and <18.00m and level height >4.00m and <9.00m
Types of construction:
The aria of the walls is computed in plan, without voids for windows and doors.
2. The density of the walls on each main direction should be larger than the values
from the table:
According to P100-1/2013 the map for the design ground acceleration is:
2
3
3. The minimum length of the structural walls is:
4. The ratio ρ between the aria in plan of the openings and aria in plan of the
masonry must be smaller than the values from the table:
The ratio r is computed for each line of walls (each axes) and it has different
maximum values function of wall position: exterior or interior.
5. The ratio between the height of the level and the thickness of the wall should be:
Hlevel / twall ≤ 15
4
Position of the tie-columns:
c. At both sides of any wall opening with an area larger than >2.5m2 for seismic
area with ag≤0.20g and larger than >1.5m2 for seismic area with ag≥0.25g
d. Within the wall if necessary in order not to exceed a spacing between tie-
columns of:
f. In all piers with the length smaller than the minimum one stipulated in rule no.
3 (table 8.11 from P100-1/2013).
1. Cross section should have aria ≥ 625 cm2 and one side ≥ 25 cm
1. Cross section should have aria ≥ 500 cm2, the width ≥ 25 cm, the height larger
than the height of the slab and twice larger for the exterior walls and for the
stairs area.
2. The width of the lintel should be equal to the thickness of the wall, or smaller
with 5 cm for the exterior walls.