Professional Documents
Culture Documents
Condensate
Return
Vacuum
Control or Breaker
Shutoff Valve
Air Vent
Vacuum 6
7 Breaker
18”
If Possible
Steam Steam
Main Drip Coil
Trap 7
Airflow 12"
Min. 1
12" Min.
Air 3
Vent
12"
Safety
Drain
Main
2 Trap 4
Condensate
Return
1. 24" minimum if safety drain is used. 4. The main trap may be either an inverted bucket or a
2. Safety drain is used if steam supply is modulated float & thermostatic type depending upon the service
and the condensate system is pressurized or overhead. conditions. See the chart below for recommendations.
Armstrong’s pumping traps or Posi-Pressure Control Inverted bucket type steam trap required with Posi-
system provides additional protection or may substitute Pressure Control system.
for the safety drain, especially if condensate conservation 5. Overhead condensate return system.
is desired. 6. Required only on a modulated system.
3. Air venting must be provided on all steam coils except 7. Provide a flexible connection or swing joint at the coil inlet
those using low-pressure Posi-Pressure Control and outlet connections to isolate the coil from vibration,
systems. The air vent may either be an orifice bleed piping stresses and differential expansion within the coil.
or a thermostatically operated element, with the orifice
bleed being the preferred choice. The air vent or orifice NOTE: See Bulletin AH-825 for detailed operation and
bleed should be piped so that it cannot be valved out maintenance procedures. Recommended practice valid for
independently of the trap. all steam coils (Duralite, Series 6000 and Duramix.)
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com for up-to-date information.
357
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim
Next armstronginternational.com