1.0 Room Data Sheets
The FPU Schedules of Accommodation by Role Delineation Levels (RDL) includes listings of
Standard Room Types required. In order to assist designers to better understand the
requirements of each room type, the HAAD Guidelines includes a comprehensive set of
Standard Components. These Standard Components are represented by two sets of
documents:
These are written descriptions of each room type, described under various categories:
Room Primary Information; includes Briefed Area, Occupancy, Room Description and
relationships, and special room requirements)
Building Fabric and Finishes; identifies the fabric and finish required for the room ceiling,
floor, walls, doors, and glazing requirements
Furniture and Fittings; lists all the fittings and furniture typically located in the room
Fixtures and Equipment; includes all the serviced equipment typically located in the room
along with the services required such as power, data, hydraulics
Building Services; indicates the requirement for communications, power, Heating,
Ventilation and Air conditioning (HVAC), medical gases, nurse/ emergency call and
lighting along with quantities and types as relevant
The Room Data Sheets (RDS’s) represent the detailed briefing requirements of each room
type. Some RDS’s provide options for certain elements such as materials. If an external
document refers to these RDS’s, without qualifying the choice of options, then the default
options will prevail. In case of any discrepancy between various documents, the RDS’s will
take precedence.
Where materials or elements are mentioned by generic type (eg Vinyl), the requirements may
be satisfied by other materials and elements which have very similar properties (eg impervious
sheet flooring).
Detailed Room Data Sheets for Standard Components are attached below.
Standard Components
HAAD
HAAD Health Facility Guidelines
Room Data Sheets Instructions for Use
Room Data Sheets are a briefing document providing information on the minimum requirements for each room in the
facility incorporating Room Details, Room Fabric, Fittings and Furniture, Fixture, Equipment with associated services
and Services.
Room Details:
This section includes Room Name, Hours of Operation and Occupancy as well as the following:
Room Tag:
This is a room number allocated for briefing purposes only. The number is not re-used if the room is deleted and is
moved with the room if an area is re-planned. It should not be confused with the Room Label/ Room Number
which may be the final room identifier indicated in the Signage Package.
Room Area:
Room Area and circulation is the target for planning only. The builder should build rooms to sizes shown
on the plans not Room Data Sheets.
Also covers these rooms:
Indicates all other room numbers (with the same room name) which have identical room requirements - this avoids
repeating the same information for every similar room.
Special Requirements:
Includes any special provisions that the room requires which may include requirements for locking, special air
conditioning, acoustic requirements and additional regulations or Australian Standards the room must comply with
- such as Body Protected electrical requirements. These requirements are mandatory.
Amendments:
All reviews to the Room Data Sheets are dated and changes identified.
Room Fabric
This section includes the acceptable room fabric requirements for floors, skirtings, walls, celings , cornice and
identifies wall protection, handrails and door protection where required. Door protection should be assumed to be
applied to both sides of doors to the room nominated. Fabric types are identified in generic terms only - Brands are
generally not nominated.
Fittings and Furniture
This section lists all fittings (items which are attached to walls or floors) and loose furniture items required in each
room. These items are identified with an ID number, a description and the quantity required. All items are identified
with a group number which indicates who is responsible for providing the item according to a health industry wide
accepted description as follows:
Group Description
1 Provided and Installed by the builder
2 Provided by the Client and installed by the builder
2T Provided by the Client, an existing item to be transferred
3 Provided and installed by the Client
3T Provided by the Client, an existing item to be transferred
Services
This section lists all services requirements for the room including communications outlets (telephone, data, etc) air
conditioning, exhaust, special hydraulics such as floor wastes, lighting, medical gases, nurse call outlets and power.
Quantities are indicated where appropriate; not every item requires a quantity to be identified such as air conditioning.
Provision of Services items listed is mandatory.
HAAD Health Facility Guidelines Milestone: Version 3.3
Room Data Sheets
Description/ A 1 Bed Room will accommodate one patient for the delivery of nursing
and medical care and treatment; natural light and outlook is essential;
Special Requirements
requires ability to view out of the window from either the chair or bed. The
1 Bed Room may also be used as an Isolation Room - Class S (Standard
Pressure). Door glazing and an internal window is recommended with
this option.
The 1 Bed Room may vary in configuration to suit different Ensuite options
including:
- 1 BR-ST-A1 Inboard Ensuite
- 1 BR-ST-B1 Outboard Ensuite
Services
ID Description Service Category Qty Selection / Remarks
Description/ A 1 Bed Room will accommodate one patient for the delivery of nursing
and medical care and treatment; natural light and outlook is essential;
Special Requirements
requires ability to view out of the window from either the chair or bed. The
1 Bed Room may also be used as an Isolation Room - Class S (Standard
Pressure). Door glazing and an internal window is recommended with
this option.
The 1 Bed Room may vary in configuration to suit different Ensuite options
including:
- 1 BR-LG-A1 Inboard Ensuite
- 1 BR-LG-B1 Outboard Ensuite
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for
telephone to each panel
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6060 Special: night lights Lighting
6050 Special: reading Lighting Up/down light
7020 Medical Air (MA) Medical Gases 1
7000 Oxygen (O2) Medical Gases 1
7040 Suction Medical Gases 1
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button & light switch on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 1 to desk
9010 GPO: Emergency power, single Power 4 Bedhead
9000 GPO: Single Power 4 Bedhead
9000 GPO: Single Power 3 adjacent to patient chair; 2 on walls
9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;
1-refrigerator in cupboard
9060 GPO: Special: for equipment Power 1 TV
Room Name 1 Bed Room - Isolation - Positive Pressure Room Code: 1 BR-IS-P-U
Description/ The 1 Bed Isolation Room - Postivie Pressure may be used to isolate
patients to protect them from acquiring an infection. natural light and
Special Requirements
outlook is essential; Glazing to room front and doors is recommended for
patient visibility. Each Isolation room is to have an internal handwash
basin and direct access to ensuite toilet and shower facilities.
Room Name 1 Bed Room - Isolation - Positive Pressure Room Code: 1 BR-IS-P-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for
telephone to each panel
5000 Airconditioning HVAC
5040 Pressure: positive HVAC
6001 General: colour corrected Lighting
6065 Special: night lights Lighting
6050 Special: reading Lighting Up/down light
7020 Medical Air (MA) Medical Gases 1
Room Name 1 Bed Room - Isolation - Positive Pressure Room Code: 1 BR-IS-P-U
Room Name 1 Bed Room - Isolation - Negative Pressure Room Code: 1 BR-IS-N-U
Description/ Single bed room which may be used to isolate patients with known
infectious conditions; natural light and outlook is essential. Glazing to
Special Requirements
room front and doors is recommended for patient visibility. The Isolation
Room - Negative Pressure will require an internal staff handwash basin,
direct access to ensuite toilet and shower facilities, and an Anteroom or
Airlock to maintain air pressurisation.
Room Name 1 Bed Room - Isolation - Negative Pressure Room Code: 1 BR-IS-N-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for
telephone to each panel
5000 Airconditioning HVAC
5050 Pressure: negative HVAC
6001 General: colour corrected Lighting
6065 Special: night lights Lighting
6050 Special: reading Lighting Up/down light
7020 Medical Air (MA) Medical Gases 1
Room Name 1 Bed Room - Isolation - Negative Pressure Room Code: 1 BR-IS-N-U
Description/ Single bed room for general mental health patients; natural light and
outlook is essential; The room is to be internally lockable with a master
Special Requirements
keyed lock from the outside; All fittings are to have a breaking strain of not
more than 15kg. All glazing (including external windows) is to comply with
standards for Mental Health Facilities.
The 1 Bed Room - Mental Health may vary in configuration to suit different
Ensuite options including:
- 1 BR-MH-A Inboard Ensuite
- 1 BR-MH-B Shared Ensuite, access from corridor
- 1 BR-MH-C Back-to-Back Ensuites
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6065 Special: night lights Lighting blue
6050 Special: reading Lighting vandal proof
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, Duress call (optional)
9040 Body protected Power
9015 GPO: Cleaner Power 1
9000 GPO: Single Power 3 1 over desk; 2 on wall
9000 GPO: Single Power 4 2 to each side of bed
9060 GPO: Special: for equipment Power 1 TV
Description/ A 1 Bed Room - Special will accommodate one patient for the delivery of
nursing and medical care and treatment. It will be a larger room to
Special Requirements
accommodate special needs patients such as Palliative Care, Sub-acute
Care, Rehabilitation and High Dependency. The additional floor area
allows for larger or additional furniture and equipment. It also permits
overnight stay by relatives. Natural light and outlook is essential; the room
requires the ability to view out of the window from either the chair or bed.
Bedrooms for Palliative Care may also include a beverage making area
with a small refrigerator.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for
telephone to each panel
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6060 Special: night lights Lighting
6050 Special: reading Lighting up/down light
Description/ A 1 Bed Room - Special, Coronary Care will accommodate one patient for
the delivery of cardiac care treatment. Glazed doors and partition walls are
Special Requirements
recommended for patient visibility and privacy. Natural light and outlook is
essential; the room requires the ability to view out of the window from
either the chair or bed.
Services
ID Description Service Category Qty Selection / Remarks
1120 Monitor connection facilities and Communications 1 optional
cabling
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for
telephone to each panel
Description/ A 1 Bed Room - Super VIP will accommodate one VIP patient for the
delivery of nursing and medical care and treatment; natural light and
Special Requirements
outlook is essential; requires ability to view out of the window from either
the chair or bed. The 1 Bed Room - Super VIP may also be used as an
Isolation Room - Class S (Standard Pressure). Door glazing and an
internal window is recommended with this option. The Super VIP room
will include superior level of finishes and fittings. An Ensuite will be
located within the space. The Super VIP room will have access to a
Waiting room, Family/Carer Room and a Pantry.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 4 1-patient services panel; 1-desk; 1 in
entertainment cabinet; 1-near patient chair; 1
outlet for telephone to each panel
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6046 Indirect lighting Lighting
6200 Light switches Lighting sensor operated room lights
45570471 Special: decorative Lighting may include chandelier or pendant lighting
6030 Special: downlights Lighting recessed
6060 Special: night lights Lighting
6050 Special: reading Lighting Up/down light
6045 Wall washers Lighting
7020 Medical Air (MA) Medical Gases 1
7000 Oxygen (O2) Medical Gases 1
7040 Suction Medical Gases 1
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button & light switch on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 5 2 to desk; 2 in entertainment cabinet; 1 near
patient chair
9010 GPO: Emergency power, single Power 4 Bedhead
9000 GPO: Single Power 4 Bedhead
9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;
1-refrigerator in cupboard
9060 GPO: Special: for equipment Power 1 TV
Description/ A 1 Bed Room - VIP will accommodate one patient for the delivery of
nursing and medical care and treatment; natural light and outlook is
Special Requirements
essential; requires ability to view out of the window from either the chair or
bed. The 1 Bed Room - VIP may also be used as an Isolation Room -
Class S (Standard Pressure). Door glazing and an internal window is
recommended with this option.
The 1 Bed Room - VIP may vary in configuration to suit different Ensuite
options including:
- 1 BR-ST-A Inboard Ensuite
- 1 BR-ST-B Outboard Ensuite
- 1 BR-ST-C Shared Ensuite
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3120 Basin: vanity 1 1 ___ ___ yes ___ yes yes yes ___ Type B; refer to BHWS-B
(sim)
3700 Bed: inpatient, electric 3 1 yes ___ ___ ___ ___ ___ ___ ___
43800 Refrigerator: under-bench, 120 Litre 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ wall mounted
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for
telephone to each panel
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6060 Special: night lights Lighting
6050 Special: reading Lighting Up/down light
7020 Medical Air (MA) Medical Gases 1
7000 Oxygen (O2) Medical Gases 1
7040 Suction Medical Gases 1
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button & light switch on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 2 1 to desk; 1 to low table
9010 GPO: Emergency power, single Power 4 Bedhead
9000 GPO: Single Power 4 Bedhead
9000 GPO: Single Power 4 1 adjacent to patient chair; 3 on walls
9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;
1-refrigerator in cupboard
9060 GPO: Special: for equipment Power 1 TV
Description/ A 2 Bed Room will accommodate two patients with similar nursing needs
for the delivery of nursing and medical care. Each space will be individually
Special Requirements
curtained and allow for treatment of patients either in bed or sitting beside
the bed in a comfortable chair; natural light and outlook is essential;
patients require the ability to view out of the window from either the chair or
bed. The room may also be used for obstetric care, either pre or post
natal, and may include bassinets.
Each room is to have direct access to Ensuite toilet and shower facilities
and the Unit corridor. The room layout is to allow movement of equipment
around bedspaces.
The 2 Bed Room may vary in configuration to suit different Ensuite options
including:
- 2 BR-ST-A-U Inboard Ensuite
- 2 BR-ST-B-U Outboard Ensuite
- 2 BR-ST-C-U Shared Ensuite
Services
Description/ A 2 Bed Room for general mental health patients; natural light and outlook
is essential; The room is to be internally lockable with a master keyed lock
Special Requirements
from the outside; All fittings are to have a breaking strain of not more than
15kg. All glazing (including external windows) is to comply with standards
for Mental Health Facilities.
The 2 Bed Room - Mental Health may vary in configuration to suit different
Ensuite options including:
- 2 BR-MH-A-U Inboard Ensuite
- 2 BR-MH-B-U Shared Ensuite with access off the corridor
- 2 BR-MH-D-U Back to Back Ensuites
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6065 Special: night lights Lighting blue
6050 Special: reading Lighting to each bed
8000 Patient/ Staff call Nurse Call 2 + indicator buttons & light; 1 per bed
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, Duress call (optional)
9015 GPO: Cleaner Power 1
9000 GPO: Single Power 11 4 per bed at bedhead; 1 per desk; 1 on wall
Description/ A 4 Bed Room will accommodate four patients with similar nursing needs
for the delivery of nursing and medical care and treatment. Each space will
Special Requirements
be individually curtained and allow for treatment of patients either in bed or
sitting beside the bed in a comfortable chair; natural light and outlook is
essential; patients require the ability to view out of the window from either
the chair or bed.
Each room is to have direct access to ensuite toilet and shower facilities,
and a staff handwash basin, either within the room or immediately
adjacent.
The 4 Bed Room may vary in configuration to suit different Ensuite options
including:
- 4 BR-ST-A Inboard Ensuite
- 4 BR-ST-B Outboard Ensuite
- 4 BR-ST-C Inboard/ Outboard Ensuite
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 4 1 / bed
1006 Voice / Data outlet: double Communications 4 1 / bed; one outlet for telephone, each bed
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6060 Special: night lights Lighting
6050 Special: reading Lighting 4 Up/down lights
Occupancy 2-10
Description/ The Ablution room is an airlock entry prior to the Prayer Room where
visitors and patients can wash-up prior to entering the prayer room.
Special Requirements
Separate Ablution Room shall be provided for male and female and direct
access to prayer room is recommeded.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 2
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
Description/ A bathroom for patient 'Activities of Daily Living' assessment and training.
The ADL Bathroom provides for training of patients to use a domestic bath,
Special Requirements
patient dressing, undressing, grooming and handwashing. Facilities
include a domestic bath installed in a corner of the room, accessible toilet
and handbasin and a separate shower within the room. A low height
adjustable shower is required over the bath.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 2
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 3 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 2 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Description/ Single Bed Room for Activities of Daily Living patient assessment and
training; natural light and outlook is desirable; The room is to be lockable.
Special Requirements
The room furnishings will be domestic style to mimic home conditions.
Services
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 2 1 near bed; 1 near desk
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6050 Special: reading Lighting
8005 Patient call handset Nurse Call 1 call button & light switch on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 1 near desk
9000 GPO: Single Power 4 2 to bedhead; 2 on walls
Occupancy Up to 4
Description/ The ADL Dining Room is an area provided within the Transitional Living
Unit for the patient along with their visitors to eat their meals, away from
Special Requirements
the bedroom environment. The Dining Room will be located adjacent to
the ADL Kitchen.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting optional
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1
Occupancy 2-3
Description/ An accessible kitchen for patient Activities of Daily Living assessment and
training; bench is to be wheelchair accessible. The Kitchen will include
Special Requirements
benches, sink, cooktop, wall oven/grill, rangehood, microwave , wheelchair
accessible storage, and refrigerator/ freezer.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
37200 Oven: electric 1 1 yes ___ ___ ___ ___ ___ ___ ___ wall oven, retractable/
side opening doors
35400 Oven: microwave, domestic 3 1 yes ___ ___ ___ ___ ___ ___ ___
42950 Rangehood 1 1 yes ___ ___ ___ ___ ___ ___ ___ over stove
44150 Refrigerator: 300 Litre, domestic 3 1 yes ___ ___ ___ ___ ___ ___ ___
47890 Sink & drainer: single, 930mmL 1 1 ___ ___ yes opt opt yes yes ___ heat lined, warm water
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC 1 to rangehood
6000 General fluorescent Lighting
9040 Body protected Power
9001 GPO: Double Power 3 benchtop
9060 GPO: Special: for equipment Power 3 cooktop, oven, rangehood
9060 GPO: Special: for equipment Power 2 Microwave, fridge
Occupancy 2-3
Description/ An accessible kitchen for patient Activities of Daily Living assessment and
training; bench is to be wheelchair accessible. The Kitchen will include
Special Requirements
benches, sink, cooktop, wall oven/grill, rangehood, microwave , wheelchair
accessible storage, and refrigerator/ freezer.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC 1 to rangehood
6000 General fluorescent Lighting
9040 Body protected Power
9001 GPO: Double Power 3 benchtop
9060 GPO: Special: for equipment Power 4 cooktop, oven, rangehood, fridge
Occupancy 1-2
Description/ Domestic style laundry for patient Activities of Daily Living (ADL)
assessment and training, wheelchair accessible. The room will include
Special Requirements
benches, laundry tub, domestic washing machine, dryer and ironing
facilities.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC extra steam/ heat extraction to room
5037 Special exhaust: dryer HVAC 1
4010 Cold water: outlet Hydraulics 1 to washing machine
4033 Floor waste Hydraulics 1
4000 Hot water: outlet Hydraulics 1 to washing machine
6000 General fluorescent Lighting
9040 Body protected Power
9001 GPO: Double Power 1 washer & dryer
9000 GPO: Single Power 2 1-over bench; 1-ironing cabinet
Description/ The ADL Lounge provides a lounge area for ADL patient assessment and
training. A range of variable height seating will be included. Fittings and
Special Requirements
furniture will be domestic in nature to simulate the patient's home
environment. Doors to this room are optional.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
9040 Body protected Power
9000 GPO: Single Power 5
9060 GPO: Special: for equipment Power 1 TV, optional
Occupancy 1 - 2 intermittently
Description/ The After Hours Blood Fridge is a discreet area for refrigerated storage of
blood and blood products for after hours access by authorised personnel.
Special Requirements
The After Hours Blood Fridge may be located in close proximity to a Critical
Care Unit.
Services
ID Description Service Category Qty Selection / Remarks
1085 Temperature monitor & alarm Communications 2 1 to each blood fridge/ freezer
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9011 GPO: Emergency power, double Power 2 1 to each blood fridge/ freezer
Occupancy 1 - 2 intermittently
Description/ Secured storage for drugs required after hours, accessible only by
authorised personnel. Refrigerated storage will be required for some
Special Requirements
medications. The Store may be a pass though type, replenished by
Pharmacy personnel with access within the Pharmacy and accessed
externally by authorised personnel. Room to be lockable both sides.
Services
ID Description Service Category Qty Selection / Remarks
1085 Temperature monitor & alarm Communications 1 to fridge
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9011 GPO: Emergency power, double Power 1 for refrigerator
Occupancy N/A
Description/ Airlock entry to a Unit to maintain air pressurisation. Entry doors may be
automatic. Access to the Unit may require intercom or special security
Special Requirements
provisions.
Services
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional; to entry door
1040 Intercom Communications 1 optional; to entry door
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
Occupancy N/A
Description/ Airlock associated with a Main Entry Area for wind/ weather protection and
to maintain air pressurisation. Entry doors may be glazed and automatic.
Special Requirements
Walls may also be glazed. 'After-hours' access may require intercom or
special security provisions.
Services
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional
1040 Intercom Communications 1 optional
1100 TV: CCTV Communications 1 optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
9060 GPO: Special: for equipment Power 1 optional; for CCTV
10020 Card access Security 1 optional; swipe card access
Occupancy N/A
Description/ Airlock associated with a Main Entry Area for wind/ weather protection and
to maintain air pressurisation. It will be used by a wide range of people
Special Requirements
including fully ambulant, persons using a wide range of walking aids,
persons in wheelchairs or on trolleys and the general public.
The size of the air lock should allow for several people to enter before the
second door opens and should reflect the level of service provision.
Entry doors may be glazed and automatic. Walls may also be glazed.
'After-hours' access may require intercom or special security provisions.
Services
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional
1040 Intercom Communications 1 optional
1100 TV: CCTV Communications 1 optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy N/A
Description/ Airlock associated with a Main Entry Area for wind/ weather protection and
to maintain air pressurisation. It will be used by a wide range of people
Special Requirements
including fully ambulant, persons using a wide range of walking aids,
persons in wheelchairs or on trolleys and the general public.
The size of the air lock should allow for several people to enter before the
second door opens and should reflect the level of service provision.
Entry doors may be glazed and automatic. Walls may also be glazed.
'After-hours' access may require intercom or special security provisions.
Services
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional
1040 Intercom Communications 1 optional
1100 TV: CCTV Communications 1 optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy Up to 3
Description/ The Ambulance Triage is an area for receival and assessment of patients
arriving in the Unit by ambulance. The Ambulance Triage will be adjacent
Special Requirements
to the Ambulance entry which should include an Airlock.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall telephone
1006 Voice / Data outlet: double Communications 3 1 to write-up bench
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
7020 Medical Air (MA) Medical Gases 1 optional
7000 Oxygen (O2) Medical Gases 2 optional
7040 Suction Medical Gases 2 optional
8080 Emergency call Nurse Call 1
8010 Staff/ Nurse assist call Nurse Call 1
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 1 to write-up bench
9010 GPO: Emergency power, single Power 2
9000 GPO: Single Power 2
Description/ The Anaesthetic Room is for holding patients on mobile beds or trolleys
prior to operative procedures at times when the Operating Room is not
Special Requirements
available. Local, regional or general anaesthesia may be administered in
this area. Depending on special circumstances an Anaesthetic Induction
Room of 18 m2 is also acceptable.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5005 Air conditioning: special HVAC positive pressure, filtered
6001 General: colour corrected Lighting variable lighting level
6055 Special: task light, built in Lighting under O/H cupboards
7020 Medical Air (MA) Medical Gases 1 services panel
7010 Nitrous Oxide (N2O) Medical Gases 1 services panel
7000 Oxygen (O2) Medical Gases 2 services panel
7070 Scavenge Medical Gases 1 services panel
7040 Suction Medical Gases 2 services panel
8080 Emergency call Nurse Call 1 + indicator button & light
8090 Orderly/ Porter call Nurse Call 1 optional
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
Occupancy 2-3
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5005 Air conditioning: special HVAC positive pressure, filtered
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9001 GPO: Double Power 4
9000 GPO: Single Power 1 refrigerator, under bench
Occupancy 2-3
Description/ The Anaesthetic Workroom provides an area for the repair, maintenance
and calibration of anaesthetic and biomedical equipment, in the Operating
Special Requirements
Unit. The room may also serve as a work base for anaesthetic and
biomedical technicians visiting the Unit. The room will be accessible from
both the sterile areas and the non-sterile areas of the Operating Unit.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3
5005 Air conditioning: special HVAC positive pressure, filtered
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
7020 Medical Air (MA) Medical Gases 1 for testing/ calibrating equipment
7010 Nitrous Oxide (N2O) Medical Gases 1 for testing/ calibrating equipment
7000 Oxygen (O2) Medical Gases 1 for testing/ calibrating equipment
7070 Scavenge Medical Gases 1 for testing/ calibrating equipment
7040 Suction Medical Gases 1 for testing/ calibrating equipment
9001 GPO: Double Power 6
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 handsfree to control room
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6001 General: colour corrected Lighting
7020 Medical Air (MA) Medical Gases 1 patient services panel on table
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel on table
7000 Oxygen (O2) Medical Gases 2 patient services panel on table
7070 Scavenge Medical Gases 1 patient services panel on table
7040 Suction Medical Gases 2 patient services panel on table
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9030 Cardiac protected Power
9015 GPO: Cleaner Power 1
9011 GPO: Emergency power, double Power 3 2 above bench; 1- wall panel
9010 GPO: Emergency power, single Power 6 patient services panel
9000 GPO: Single Power 6 patient services panel
9060 GPO: Special: for equipment Power 1 20 amp, patient services panel
Occupancy Up to 3 staff
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 with handsfree microphone to Angio room
1006 Voice / Data outlet: double Communications 5 3 outlets under bench for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 8
9060 GPO: Special: for equipment Power 1 Angiography console equipment
Occupancy 1 - 2 intermittently
Description/ A room for the storage and preparation of radiological media, sterile stock,
medications and where set-up for Angiography procedures is undertaken.
Special Requirements
Secured staff only access to the room may be required.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9001 GPO: Double Power 1
9000 GPO: Single Power 1 Refrigerator, under bench
9000 GPO: Single Power 2
Occupancy 1-2
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy Up to 6 staff
Description/ The Assembly/ Collation/ Coding area is an open plan area use for
processing the medical record prior to filing.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
Occupancy Up to 5
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
47890 Sink & drainer: single, 930mmL 1 1 ___ ___ yes opt opt yes yes ___ hot water
54500 Telephone: cordless 3 1 yes yes ___ ___ ___ ___ ___ ___ mobile
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 5 workstations; 1 outlet per workstation for
telephone
1006 Voice / Data outlet: double Communications 2 printers
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
9001 GPO: Double Power 12 2 per workstation, 2-printers
Occupancy Up to 8
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
47890 Sink & drainer: single, 930mmL 1 1 ___ ___ yes opt opt yes yes ___ hot water
54500 Telephone: cordless 3 4 yes yes ___ ___ ___ ___ ___ ___ mobile
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 10 8 - workstations; 2 - printers; 1 outlet per
workstation for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 18 2 per workstation, 2-printers
Occupancy Up to 3
Description/ Room with an internal sound proof booth to specifications, for audiology
testing. Audiometric booth should be ventilated or connected to
Special Requirements
airconditioning, power and data. Level access to the Audiometric Booth is
recommended.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
1600 Audiometric booth 3 1 yes yes ___ ___ ___ ___ ___ ___ to specification
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ on desk
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 to booth, 1 outlet to desk for telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6000 General fluorescent Lighting
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 4 2- desk; 2-booth
9060 GPO: Special: for equipment Power 1 audiometric booth
10005 Duress alarm Security 1
Occupancy Up to 4
Description/ The Audio-visual room will provide a quiet area for viewing of audivisual
material.
Special Requirements
Services
Description/ The bathroom provides for assisted bathing of patients, patient dressing,
undressing, grooming and handwashing. It is also used for bathing of
Special Requirements
patients for treatment or aromatherapy. Facilities include an island bath,
toilet, and handbasin; a separate shower within the room is optional. A low
height adjustable shower is required over the bath. Hydraulic lift baths may
be considered for Occupational Health & Safety purposes.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC temp. to 26 degrees C
5019 Exhaust HVAC
4033 Floor waste Hydraulics 3 + special floor drain for height adjustable bath
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 2 + indicator button & light
8070 Patient call pendant Nurse Call 1 waterproof, for bath
8000 Patient/ Staff call Nurse Call 3 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 3 + indicator button & light
Occupancy N/A
Description/ The Bay - ATM will provide an area for an Automatic Teller Machine which
may require access to the rear of the ATM by staff or authorised personnel
Special Requirements
only. The ATM Bay may be located in close proximity to a waiting area.
Provision of power and data to be according to ATM specifications. Security
requirements need to be considered.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 ATM machine, telephone line, concealed
1006 Voice / Data outlet: double Communications 1 ATM machine, data line, concealed
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 ATM machine, concealed, as specified
9020 UPS (uninterruptible power) Power 1 ATM machine
Description/ The Beverage Bay is an area for preparing and/or heating refreshments,
snacks and some meals, washing some utensils, storing food and drink
Special Requirements
and disposing of food waste. The Beverage Bay may be located with ready
access to patient areas, staff rooms, or meeting rooms. The Beverage Bay
should be adequately recessed to avoid encroachment into the corridor.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
35400 Oven: microwave, domestic 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
44100 Refrigerator: 250 Litre, domestic 3 1 yes ___ ___ ___ ___ ___ ___ ___ or underbench
refrigerator
47890 Sink & drainer: single, 930mmL 1 1 ___ ___ yes opt opt yes yes ___ lever taps, warm water
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1 above bench
9000 GPO: Single Power 4 fridge; boiling water unit; m/wave; ice
machine
Description/ The Beverage Bay, Enclosed is a room for preparing and/or heating
refreshments, snacks and some meals, washing some utensils, storing
Special Requirements
food and drink and disposing of food waste. The Beverage Bay may be
located with ready access to patient areas, staff rooms, or meeting rooms.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1 above bench
9000 GPO: Single Power 4 fridge; boiling water unit; m/wave, ice
machine
Occupancy N/A
Description/ A Bay for a blanket or combined blanket / fluid warming cabinet. The bay
should have close access to patient areas and operating rooms.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9010 GPO: Emergency power, single Power 1
Occupancy 1
Description/ The Cleaning Bay provides an area with sink for rinsing and clean-up of
equipment and materials used in Engineering Services. The Cleaning
Special Requirements
Bay should be located in close proximity to Workshop areas.
Services
ID Description Service Category Qty Selection / Remarks
5015 Ventilation HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
Room Name Bay - Cleaning, 18m2 (Patient Transport) Room Code: BCL-18-U
Occupancy 1 - 2 intermittently
Description/ The Cleaning Bay, Patient Transport, is a covered area for cleaning of
patient transport vehicles and other equipment, and will be located in an
Special Requirements
external area.
Services
ID Description Service Category Qty Selection / Remarks
4010 Cold water: outlet Hydraulics 1
4033 Floor waste Hydraulics 1
4000 Hot water: outlet Hydraulics 1
6072 Special: external Lighting 1
9000 GPO: Single Power 1 weatherproof
Occupancy 1
Description/ Readily accessible area with safety shower and eyewash equipment for
emergency use.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1 waste water containment may be required
6000 General fluorescent Lighting
Occupancy N/A
Description/ An open storage bay located close to the loading dock area for parking
equipment which may include linen trolleys, wheelchairs or other mobile
Special Requirements
equipment. The parking area may be used for equipment waiting for
repair, returning from repair or surplus equipment.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy N/A
Description/ An open storage bay for holding wheelchairs, trolleys and other mobile
equipment not in use.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2 1 each side of bay
Occupancy N/A
Description/ An open storage bay for holding, trolleys and other mobile equipment not
in use.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2 1 each side of bay
Occupancy N/A
Description/ An open storage bay located close to the loading dock area for parking
equipment which may include linen trolleys, wheelchairs or other mobile
Special Requirements
equipment. The parking area may be used for equipment waiting for
repair, returning from repair or surplus equipment.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2 general use or for equipment that requires
recharging
Occupancy 1 intermittently
Description/ Area with bench and sink for use by staff and volunteers to maintain
patients' flowers. The Flower Bay will have direct access to the Unit
Special Requirements
corridor.
Services
ID Description Service Category Qty Selection / Remarks
Occupancy 1 intermittently
Description/ A room with bench and sink for use by staff and volunteers to maintain
patients' flowers. The room will have direct access to the Unit corridor.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1 Above bench
Occupancy 1
Description/ An area which may be a recessed bay, with handwashing facilities for staff
to cleanse their hands before and after every patient contact. Type A
Special Requirements
refers to a Clinical Scrub basin (Large) with wall mounted, elbow action
lever taps - for surgical scrubbing.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy 1
Description/ An area off the corridor, which may be a recessed bay, with handwashing
facilities for staff to cleanse their hands before and after every patient
Special Requirements
contact. Type B refers to a Medium Handbasin with elbow action lever
taps - for procedural handwashing; taps may be basin mounted or wall
mounted. A vanity unit is optional.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
Occupancy 1
Description/ A recessed bay off the corridor with handwashing facilities for staff to
cleanse their hands before and after every patient contact. Type C refers to
Special Requirements
a Small to Medium handbasin with basin mounted lever or standard taps
or a flickmixer tap- for general handwashing.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy 1
Description/ An area off the corridor, which may be a recessed bay, with handwashing
facilities for staff to cleanse their hands before and after every patient
Special Requirements
contact and for the storage of PPE (Personal Protective Equipment). The
Handwashing, PPE bay will include a medium handbasin (Type B) with
elbow action lever taps - for procedural handwashing; taps may be basin
mounted or wall mounted. A vanity unit is optional.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ elbow action lever taps,
basin or wall mounted
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC consistent with adjacent area
6000 General fluorescent Lighting consistent with adjacent area
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy N/A
Description/ An open storage bay for holding meal trolleys during meal delivery and
collection times. Meal service trolleys to be confirmed; special power may
Special Requirements
be required for Cook/chill rethermalisation trolleys.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 2 rethermalisation trolleys
Room Name Bay - Mobile Equipment (Enclosed), 4m2 Room Code: BMEQE-4-U
Occupancy N/A
Description/ An enclosed storage bay for one or more items of mobile equipment in
frequent use which may include wheelchairs, mobile scales, commode
Special Requirements
chairs, patient lifting devices or other mobile equipment.
Services
Room Name Bay - Mobile Equipment (Enclosed), 4m2 Room Code: BMEQE-4-U
Occupancy N/A
Description/ An open storage bay for one or more items of mobile equipment in
frequent use which may include IV stands, trolleys or other mobile
Special Requirements
equipment.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2 For recharging of electrical equipment
Occupancy N/A
Description/ An open storage bay for one or more items of mobile equipment in
frequent use which may include wheelchairs, mobile scales, commode
Special Requirements
chairs, patient lifting devices or other mobile equipment.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy N/A
Description/ An open storage bay for one or more items of mobile equipment in
frequent use which may include mobile X-ray equipment, wheelchairs,
Special Requirements
mobile scales, commode chairs, patient lifting devices, or other mobile
equipment.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
35700 IMG: X-ray machine, mobile 3 yes ___ ___ ___ ___ ___ ___ ___ spatial provision only
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2 For recharging of electrical equipment
Occupancy N/A
Description/ An open storage bay for parking mobile equipment which may include
patient beds, wheelchairs trolleys or other mobile equipment. The parking
Special Requirements
area may be used for equipment waiting for repair, returning from repair or
surplus equipment.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2 For recharging of electrical equipment
Occupancy 1
Description/ The Pathology Bay provides an area for preparation, holding of patient
specimens and may include processing of some patient specimens. The
Special Requirements
bay may be located in Critical Care Units or an Operating Unit.
Services
ID Description Service Category Qty Selection / Remarks
Room Name Bay - PPE (Personal Protective Equipment) Room Code: BPPE-U
Occupancy N/A
Description/ An open storage bay for location of personal protection equipment such as
gloves, gowns, overshoes and masks.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy 1-2
Description/ An area with provision for public telephones; Disabled access should be
provided to a minimum of one telephone bay. The Public Telephone Bay
Special Requirements
should be located with ready access to waiting areas.
Services
ID Description Service Category Qty Selection / Remarks
1011 Telephone: public phone Communications 2 1/ bay
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9000 GPO: Single Power 2 1/ bay
Occupancy N/A
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9011 GPO: Emergency power, double Power 2 for recharging emergency equipment
Occupancy N/A
Description/ An open storage bay located adjacent to patient treatment areas for
holding of supplies in frequent use. Stock will be stored in open, heavy
Special Requirements
duty, adjustable shelving units.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy N/A
Description/ A secure enclosed storage bay, located off a corridor, for storage of
supplies. The storage bay will include adjustable heavy duty shelving.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5015 Ventilation HVAC
6000 General fluorescent Lighting light obtained from adjacent corridor
Occupancy N/A
Description/ An open storage bay located adjacent to patient treatment areas for
holding of supplies in frequent use. Stock will be stored in open, heavy
Special Requirements
duty, adjustable shelving units.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy N/A
Description/ An open storage bay located adjacent to patient treatment areas for
holding of supplies in frequent use. Stock will be stored in open, heavy
Special Requirements
duty, adjustable shelving units.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy N/A
Description/ An open storage bay located adjacent to patient treatment areas for
holding of supplies in frequent use. Stock will be stored in open, heavy
Special Requirements
duty, adjustable shelving units.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy 1
Description/ The Utility Bay provides an area with a bench and sink for use as a
preparation area. The bay may be located adjacent to patient treatment
Special Requirements
areas. The bay should be located in close proximity to a staff handwashing
basin.
Services
ID Description Service Category Qty Selection / Remarks
Occupancy 1
Description/ The Utility Bay provides an area with a bench and sink for use as a
preparation area. The bay may be located adjacent to patient treatment
Special Requirements
areas. The bay should be located in close proximity to a staff handwashing
basin.
Services
Occupancy 1
Description/ The Utility Bay provides an area with a bench and sink for use as a
preparation area. The bay may be located adjacent to patient treatment
Special Requirements
areas. The bay may incorporate a staff handwashing basin.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
Occupancy 1 - 2 intermittently
Services
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 2 1 per vending machine (optional)
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9000 GPO: Single Power 2 1 per vending machine
Occupancy 1 - 2 intermittently
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 per vending machine (optional)
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2
Occupancy 1 intermittently
Description/ Recessed bay off a corridor, a public waiting area or associated with a
Main Entry/ lobby area for a water fountain.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC consistent with adjacent area
6000 General fluorescent Lighting consistent with adjacent area
Occupancy N/A
Description/ An open storage bay for wheelchairs, located in close proximity to the main
entrance.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy N/A
Description/ An open storage bay for wheelchairs, located in close proximity to the main
entrance.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC consistent with adjacent area
6000 General fluorescent Lighting consistent with adjacent area
9001 GPO: Double Power 2
Description/ The Birthing Room LDR provides for the entire process of delivery
including patient preparation, relaxation and analgesia during labour,
Special Requirements
delivery, infant resuscitation, post natal recovery and observation. The
Birthing Room shall include a scrub basin. Clinical items such as medical
gases and services may be concealed but within easy reach.
Services
ID Description Service Category Qty Selection / Remarks
Description/ The Blood Collection Chair Bay is used for collection of blood specimens
from patients, and will be located within the Pathology Unit or an
Special Requirements
Ambulatory Care Unit. A staff handwashing basin will be located nearby.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6032 Downlights: colour corrected Lighting over each collection chair
6000 General fluorescent Lighting
9040 Body protected Power
9010 GPO: Emergency power, single Power 1 to each collection chair
Room Name Blood Checking/ Labelling/ Work Area Room Code: BLDWK-U
Occupancy 1 - 2 staff
Description/ The Blood Checking/ Labelling/ Work area provides an area for storage
and preparation, checking & labelling of blood products and
Special Requirements
documentation. Staff only access to the room will be required.
Room Name Blood Checking/ Labelling/ Work Area Room Code: BLDWK-U
Services
ID Description Service Category Qty Selection / Remarks
1002 Alarm Communications 2 blood fridge & freezer
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9011 GPO: Emergency power, double Power 1
9000 GPO: Single Power 1 refrigerator, under bench
9000 GPO: Single Power 4
Occupancy 1 - 2 staff
Description/ The Blood Collection Work area provides an area for preparation, holding
of specimens and documentation, and will be located adjacent to the
Special Requirements
Blood Collection Bays.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9000 GPO: Single Power 1 refrigerator, under bench
9000 GPO: Single Power 4
Occupancy N/A
Description/ The Blood Store is a bay for refrigerated storage of blood and blood
products. The Bay will be located with ready access to Operating Rooms
Special Requirements
and patient treatment areas.
Services
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 2 for temperature monitor/alarms, optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9011 GPO: Emergency power, double Power 2
Occupancy Up to 4 staff
Description/ A secure workroom provided for the calibration and testing of biomedical
equipment used in the complex. Space will be required for parking of
Special Requirements
mobile items of equipment. This workshop will include all medical gases
and all laboratory gases for testing and calibrating equipment. This
workshop should be located with direct access to the Biomedical
Workshop.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 9 2/workstation; 1-wall
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
7024 Carbon Dioxide (CO2) Medical Gases 1 for testing/ calibrating equipment
7020 Medical Air (MA) Medical Gases 2 for testing/ calibrating equipment; MA-4 &
MA-7
7015 Nitrogen Medical Gases 1 for testing/ calibrating equipment; other
laboratory gases as specified
7010 Nitrous Oxide (N2O) Medical Gases 1 for testing/ calibrating equipment
7000 Oxygen (O2) Medical Gases 1 for testing/ calibrating equipment
7070 Scavenge Medical Gases 1
7040 Suction Medical Gases 1 for testing/ calibrating equipment
9001 GPO: Double Power 17 4/workstation; 1-wall
9011 GPO: Emergency power, double Power 4 1/workstation
11000 Wall panel Services Panels 1 services duct for gases, power & data
Occupancy 1-2
Description/ A secure room for the Cashier to receive payments for patient services and
supplies. The Cashier may be located in close proximity to the Main
Special Requirements
Reception Area with ready access to the Pharmacy Unit. Facilities for
EFTPOS payments will be required.
Services
ID Description Service Category Qty Selection / Remarks
1045 EFTPOS connection Communications 1
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 5
10005 Duress alarm Security 1
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 handsfree to control room
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6001 General: colour corrected Lighting
7020 Medical Air (MA) Medical Gases 2 patient services panel on table
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel on table
7000 Oxygen (O2) Medical Gases 2 patient services panel on table
7070 Scavenge Medical Gases 1 patient services panel on table
7040 Suction Medical Gases 2 patient services panel on table
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9030 Cardiac protected Power
9015 GPO: Cleaner Power 1
9011 GPO: Emergency power, double Power 3 2 above bench; 1-wall panel
9010 GPO: Emergency power, single Power 6 patient services panel
9000 GPO: Single Power 6 patient services panel
9060 GPO: Special: for equipment Power 1 20 amp, patient services panel
Room Name Catheter Lab Control/ Reporting Room Room Code: CLCRT-U
Occupancy Up to 3 staff
Description/ Room adjacent to Catheter Lab Procedure Room/s with direct visibility to
the patient for remote control of equipment, and review and reporting of
Special Requirements
procedure images. The Control/ Reporting room may serve two procedure
rooms.
Room Name Catheter Lab Control/ Reporting Room Room Code: CLCRT-U
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 with handsfree microphone to Cath lab room
1006 Voice / Data outlet: double Communications 6 3 outlets for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
9001 GPO: Double Power 9
9060 GPO: Special: for equipment Power 1 Cath lab console equipment
Occupancy 1 patient
Description/ A screened area for ambulant patients to change from street clothes into a
hospital gown, as appropriate, prior to examination or treatment. Following
Special Requirements
examination or treatment, the patient will chnage in street clothes. The
Change Cubicle should provide facilities for hanging clothes and a bench
for the patient to sit on whilst changing.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light, outside cubicle entry
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
Occupancy 1 patient
Description/ A screened area for disabled patients to change from street clothes into a
hospital gown, as appropriate, prior to examination or treatment. Following
Special Requirements
examination or treatment, the patient will change in street clothes. The
Change Cubicle should provide facilities for hanging clothes and a bench
for the patient to sit on whilst changing.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Occupancy Up to 3
Description/ The Patient Change areas are provided for patients to change into gowns,
to store their street clothing and to perform personal ablutions. Change
Special Requirements
Rooms should be divided into Male and Female areas on a proportional
basis and will include Chane Cubicle, Toilet, handbasin and lockers for
secure storage of personal property.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 3
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1
8000 Patient/ Staff call Nurse Call 2 WC & Shower Cubicles
8010 Staff/ Nurse assist call Nurse Call 1
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Occupancy Up to 3
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing or gowns, to store their street clothing and to perform personal
Special Requirements
ablutions. Change Rooms should be divided into Male and Female areas
on a proportional basis and will include Showers, Toilets and handbasins.
Secure storage for personal property will be required. Secured, staff only
access to Change Rooms is required.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone optional
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 3
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
10040 Key pad access Security 1 or card access to door
Occupancy Up to 4
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing or gowns, to store their street clothing and to perform personal
Special Requirements
ablutions. Change Rooms should be divided into Male and Female areas
on a proportional basis and will include Showers, Toilets and handbasins.
Secure storage for personal property will be required. Secured, staff only
access to Change Rooms is required.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone optional
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 3
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
10040 Key pad access Security 1 or card access to door
Occupancy Up to 4
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing or gowns, to store their street clothing and to perform personal
Special Requirements
ablutions. Change Rooms should be divided into Male and Female areas
on a proportional basis and will include Showers, Toilets and handbasins.
Secure storage for personal property will be required. Secured, staff only
access to Change Rooms is required.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone optional
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 3
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
10040 Key pad access Security 1 or card access to door
Occupancy Up to 4
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing or gowns, to store their street clothing and to perform personal
Special Requirements
ablutions. Change Rooms should be divided into Male and Female areas
on a proportional basis and will include Showers, Toilets and handbasins.
Secure storage for personal property will be required. Secured, staff only
access to Change Rooms is required.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone optional
5000 Airconditioning HVAC
5019 Exhaust HVAC to toilet/ shower area
4033 Floor waste Hydraulics 3
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
10020 Card access Security 1 or keypad; to entry door from corridor
Occupancy Up to 10
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing or gowns, to store their street clothing and to perform personal
Special Requirements
ablutions. Change Rooms should be divided into Male and Female areas
on a proportional basis and will include Showers, Toilets and handbasins.
Secure storage for personal property will be required. Secured, staff only
access to Change Rooms is required.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone optional
5000 Airconditioning HVAC
5019 Exhaust HVAC to toilet/ shower area
4033 Floor waste Hydraulics 2
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
10020 Card access Security 1 or keypad; to entry door from corridor
Occupancy Up to 15
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing or gowns, to store their street clothing and to perform personal
Special Requirements
ablutions. Change Rooms should be divided into Male and Female areas
on a proportional basis and will include Showers, Toilets and handbasins.
Secure storage for personal property will be required. Secured, staff only
access to Change Rooms is required.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone optional
5000 Airconditioning HVAC
5019 Exhaust HVAC to toilet/shower area
4033 Floor waste Hydraulics 5
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
10020 Card access Security 1 or keypad access outside room
Occupancy Up to 15
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing, to store their street clothing and to perform personal ablutions.
Special Requirements
Secure storage for personal property will be required. Change Rooms
should be divided into Male and Female areas on a proportional basis.
Showers and Toilets will be included within the general Staff Change area.
Secured, staff only access to Change Rooms is required.
The area may increase according to the number of staff showers/ toilets
and lockers to be accommodated; Allow an additional 2 m2 for each
additional toilet, 1 m2 for each additional basin, and 0.5 m2 for each
additional locker.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC to toilet/ shower area
4033 Floor waste Hydraulics 6
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Occupancy Up to 15
Description/ Staff Change areas are provided for staff to change into appropriate work
clothing, to store their street clothing and to perform personal ablutions.
Special Requirements
Secure storage for personal property will be required. Change Rooms
should be divided into Male and Female areas on a proportional basis.
Showers and Toilets will be included within the general Staff Change area.
Secured, staff only access to Change Rooms is required.
The area may increase according to the number of staff showers/ toilets
and lockers to be accommodated; Allow an additional 2 m2 for each
additional toilet, 1 m2 for each additional basin and 0.5 m2 for each
additional locker.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC to toilet/ shower area
4033 Floor waste Hydraulics 5
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Occupancy 1 - 2 intermittently
Description/ A secure room for the storage and decanting of cleaning materials and
agents, storage of cleaning equipment and trolley, washing and storage of
Special Requirements
mops, buckets, brooms etc. and for waste disposal.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4050 Cold water: hosecock Hydraulics 1 to detergent/ chemical mixer if required
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy 1 - 2 intermittently
Description/ A secure room for the storage and decanting of cleaning materials and
agents, storage of cleaning equipment and trolley, washing and storage of
Special Requirements
mops, buckets, brooms etc. and for waste disposal. The larger floor area
provides for additional storage or trolley holding.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
49200 Sink: cleaner 1 1 ___ ___ yes yes ___ yes yes ___
58400 Vacuum cleaner: commercial 3 1 yes ___ ___ ___ ___ ___ ___ ___
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4050 Cold water: hosecock Hydraulics 1 to chemical mixer if required
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy 1-2
Description/ The Clean-Up Room is used for holding of used trolleys and articles from
an Operating or Procedure room. Items may be sorted, rinsed or
Special Requirements
disposed of and despatched to waste holding/ CSSU areas as
appropriate.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
Occupancy 1 - 2 staff
Description/ The Clean-Up Room is used for holding of used trolleys and articles from
Operating or Procedure rooms. Items may be sorted, rinsed or disposed
Special Requirements
of and despatched to waste holding/ CSSU areas as appropriate. The
Clean-Up room may be shared between two Operating or Procedure
Rooms.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
Occupancy 1-2
Description/ The Clean-up Room, 12m2 is used for rinsing and cleaning of equipment
and utensils and disposal of waste. Items may be sorted, rinsed or
Special Requirements
disposed of and despatched to waste holding/ CSSU areas as
appropriate.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy 1-2
Description/ The Clean-Up Room, Shared is used for rinsing and cleaning of medical
equipment or endoscopes used in the Operating Rooms or Procedure
Special Requirements
Rooms. Low temperature sterilisation of endoscopes may also be
undertaken in this room. The shared Clean-up Room should be located
between two Minor Operating Rooms or Procedures rooms where
endoscopy procedures are undertaken.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC efficient exhaust required
4010 Cold water: outlet Hydraulics 1 for low temp steriliser, optional
4033 Floor waste Hydraulics 1
4000 Hot water: outlet Hydraulics 1 for low temp steriliser, optional
4037 Tundish drain Hydraulics 1 for low temp steriliser, optional
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 under O/H cupboards
7020 Medical Air (MA) Medical Gases 1 over dry bench for tube drying
7040 Suction Medical Gases 1 near sink for tube cleaning
9001 GPO: Double Power 1 over bench
9011 GPO: Emergency power, double Power 1 over bench
9060 GPO: Special: for equipment Power 1 optional, for low temp steriliser
Occupancy 1-2
Description/ The Clean-up Room is used for rinsing and cleaning of equipment and
utensils used in the Pathology Unit, and disposal of waste.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC efficient exhaust required
4010 Cold water: outlet Hydraulics 1 for ioniser
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
7020 Medical Air (MA) Medical Gases 1 near sinks for tube cleaning
9001 GPO: Double Power 1
9060 GPO: Special: for equipment Power 1 utensil washer, optional
Occupancy 1 - 2 staff
Description/ A room for the storage and preparation of clean and sterile consumables
and equipment for patient treatment; secure storage and preparation of
Special Requirements
medications, including intravenous fluids. It may also function as an
alternative storage area for the medication trolley. The room may provide
storage for dangerous drugs in accordance with relevant legislation.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
8040 Annunciator Nurse Call to be heard in this room
9000 GPO: Single Power 1 refrigerator
9000 GPO: Single Power 5
Occupancy 1 - 2 staff
Description/ A room for the storage and preparation of clean and sterile consumables
and equipment for patient treatment; secure storage and preparation of
Special Requirements
medications, including intravenous fluids. It may also function as an
alternative storage area for the medication trolley. The room may provide
storage for dangerous drugs in accordance with relevant legislation. The
Clean Utility 14m2 will provide for access doors both sides of the room.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
8040 Annunciator Nurse Call to be heard in this room
9000 GPO: Single Power 1 refrigerator, under bench
9000 GPO: Single Power 4
Occupancy 1 - 2 intermittently
Description/ A small Clean Utility for the storage and preparation of clean and sterile
stock, patient care items and secure storage of medications. The Clean
Special Requirements
Utility-Sub should not be provided in Inpatient Units used for overnight
stay.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 under O/H cupboards
9000 GPO: Single Power 1 Refrigerator, under bench
9000 GPO: Single Power 4
Description/ A room for clerical activities including record sorting and secure storage of
medical records. The photocopier, facsimile and printer may also be
Special Requirements
located in this area if required.
Services
ID Description Service Category Qty Selection / Remarks
Room Name Coffee Shop - Seating/ Dining, 30m2 Room Code: COFS-D-30-U
Occupancy Up to 18
Description/ Seating/ Dining area for the Coffee Shop adjacent to the Servery counter.
Seating includes tables and chairs and a bar bench with stools. The
Special Requirements
Dining area includes waste collection and recycling bins along with a tray
return area adjoining the Wash-up Room. Glazed front walls are
recommeded. Direct access to an outdoor eating area is desirable.
Room Name Coffee Shop - Seating/ Dining, 30m2 Room Code: COFS-D-30-U
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6030 Special: downlights Lighting optional
9001 GPO: Double Power 1
9060 GPO: Special: for equipment Power 1 drinks fridge, optional
Occupancy Up to 3
Description/ The Coffee Shop Preparation provides an area for food prepration which
may include sandwich making, reheating, some cooking and prepration of
Special Requirements
hot drinks. The extent of food prepration and cooking will be determined
by the Operational Policy. The Preparation area will be located with close
access to a Wash-up area and the Servery counter.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
6215 Cabinet: refrigerated 1 1 yes ___ ___ ___ ___ ___ ___ ___ under bench
25850 Hotplate: single element 1 2 yes ___ ___ ___ ___ ___ ___ ___
35400 Oven: microwave, domestic 3 1 yes ___ ___ ___ ___ ___ ___ ___ over bench
42950 Rangehood 1 1 yes ___ ___ ___ ___ ___ ___ ___ over hotplates
49110 Sink: 450x350x300D 1 ___ ___ yes opt opt yes yes ___ hot water
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC to rangehood
4033 Floor waste Hydraulics
6000 General fluorescent Lighting
9001 GPO: Double Power 5
9000 GPO: Single Power 1 for microwave
9060 GPO: Special: for equipment Power 2 refrigerated cabinet, rangehood
Occupancy Up to 3
Description/ The Coffee Shop Servery provides an area for food display, prepration of
hot and cold drinks, ready made hot food, a serving counter and cash
Special Requirements
register. The Servery will be located with direct access from a circulation
corridor and adjacent to the Dining Area, Preparation and Wash-up areas.
Services
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 1 wall telephone
5000 Airconditioning HVAC
4033 Floor waste Hydraulics
6000 General fluorescent Lighting
6030 Special: downlights Lighting optional
6055 Special: task light, built in Lighting under O/H cupboards
9001 GPO: Double Power 6
9060 GPO: Special: for equipment Power 2 refrigerated cabinet, food display
Occupancy 1 - 2 intermittently
Description/ The Store provides a secure area for the storage of general and dry goods
used within the Coffee Shop. Referigerated storage may also be required.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy 1 - 2 intermittently
Description/ The Coffee Shop Wash-up room provides an area for washing and
cleaning of utensils, crockery glassware and trays. used in the
Special Requirements
Preparation, Servery and Dining areas. The Wash-up will have a tray return
and a waste bin area.
Services
Occupancy 1 - 2 intermittently
Services
Occupancy N/A
Description/ A secure room for computer equipment modules associated with imaging
equipment. The room will be located adjacent to the Imaging Procedure
Special Requirements
room or the Control Room. Modules which may be installed in this room
include control cabinets, power cabinets, transformer cabinet and heat
exchange units. Room temperature must be maintained for heat
generating equipment. Cable ducts from Procedure Room and the
Computer Equipment Room may be required.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC maintain temperature for heat generating
equipment; confirm heat load generated by
equipment
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 6 to each module; qty will vary depending on
equipment used
9020 UPS (uninterruptible power) Power may be required
Occupancy 1 - 2 intermittently
Services
ID Description Service Category Qty Selection / Remarks
Occupancy 1 - 2 intermittently
Services
ID Description Service Category Qty Selection / Remarks
Occupancy Up to 7
Description/ The Computer Training Room is provided for computer based staff
training sessions.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
Description/ The Consult Room will provide for private consultation and examination of
patients with or without support persons present. A second egress door
Special Requirements
may be required for staff safety and security.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6055 Special: task light, built in Lighting 1 optional
7020 Medical Air (MA) Medical Gases 1 optional
7000 Oxygen (O2) Medical Gases 1 optional
7040 Suction Medical Gases 1 optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 2 workstation / desk area
9001 GPO: Double Power 1 patient examination area
Description/ The Consult Room ENT/ Ophthalmology will provide for private
consultation and examination of patients for ENT/ Ophthalmology using
Special Requirements
specialised equipment. The Consult room may also be used for general
consultations.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
7020 Medical Air (MA) Medical Gases 1 optional
7000 Oxygen (O2) Medical Gases 1 optional
7040 Suction Medical Gases 1 optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 as required
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 1 patient examination area
9001 GPO: Double Power 2 workstation / desk area
9011 GPO: Emergency power, double Power 1 patient examination area
Room Name Consult/ Interview Room - Mental Health Room Code: CONS-INT-MH-U
Occupancy Up to 8
Description/ A room used for consultation and assessment of patients, and/or interview
and counselling of family members and significant others. External
Special Requirements
outlook and toughened glazing on corridor aspect with window treatment
allowing observation but perception of privacy. A second egress door will
be required for staff safety and security. Furniture placed so that the
clinician has both a view of entry door and access to the second door for
emergency egress. All fittings and fixtures to be suitable for mental health
patients, fittings should have a breaking strain of not more than 15kg.
Room Name Consult/ Interview Room - Mental Health Room Code: CONS-INT-MH-U
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 2
10005 Duress alarm Security 1
Occupancy N/A
Description/ Refrigerated room for storage of goods requiring cool storage. Coolroom
temperature should be monitored and alarmed. Essential power supply
Special Requirements
may be required.
Services
ID Description Service Category Qty Selection / Remarks
1085 Temperature monitor & alarm Communications 1
5021 Special ventilation: cool room HVAC
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power essential supply to cool room plant
Occupancy Up to 10
Services
ID Description Service Category Qty Selection / Remarks
4010 Cold water: outlet Hydraulics for cleaning & watering plants; secured
6015 Security lighting Lighting vandal proof
6072 Special: external Lighting vandal proof
Description/ X-ray Room for CT scanning procedures with an adjacent Control Room
and Computer Room. The Control Room may serve more than one CT
Special Requirements
Scanning Room
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 handsfree to control room
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6000 General fluorescent Lighting
7020 Medical Air (MA) Medical Gases 1 patient services panel
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel
7000 Oxygen (O2) Medical Gases 2 patient services panel
7070 Scavenge Medical Gases 1 patient services panel
7040 Suction Medical Gases 2 patient services panel
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9011 GPO: Emergency power, double Power 2 to walls
9010 GPO: Emergency power, single Power 6 to patient services panels
9000 GPO: Single Power 1 XR Viewer
9060 GPO: Special: for equipment Power 1 CT equipment
11000 Wall panel Services Panels 3 patient services
12030 Lead lining Shielding to walls and doors as specified
Occupancy Up to 2 staff
Description/ Room adjacent to CT Scanning Room/s with direct visibility to the patient
for remote control of equipment, and review and reporting of procedure
Special Requirements
images. The Control room may serve two procedure rooms.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 with handsfree microphone to CT Scan room
1006 Voice / Data outlet: double Communications 3 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 5
9060 GPO: Special: for equipment Power 1 CT Scanning equipment
12030 Lead lining Shielding to wall shared with CT Procedure Room
Occupancy 1 - 2 intermittently
Description/ The Cytotoxic room provides for the storage and preparation of cytotoxic
patient preparations including intravenous fluids and sterile items.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9000 GPO: Single Power 1 Refrigerator, under bench
9000 GPO: Single Power 4
Occupancy 1
Description/ Dark room for processing and developing light sensitive radiographic film.
Room requirements include good ventilation, light proof door and dark
Special Requirements
room lighting.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
Occupancy 1-2
Description/ Area for automatic daylight processing equipment with sorting and viewing
of images and films. The processing area should be located with ready
Special Requirements
access to X-Ray procedure rooms and reporting rooms.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ on bench
69000 Xray viewer: 6 screen 1 1 yes ___ ___ ___ ___ ___ ___ ___ over bench
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3 1 outet on sorting bench for telephone
4037 Tundish drain Hydraulics 1 for processor
6055 Special: task light, built in Lighting under O/H shelving
9001 GPO: Double Power 4
9060 GPO: Special: for equipment Power 1 for processor
Occupancy Up to 12
Description/ The Demonstration Room will provide for seminars, tutorials and clinical
demonstrations simulating an inpatient bed space. The room will
Special Requirements
accommodate a patient bed/ trolley, resuscitation equipment,
demonstration mannequins and bench with sink and storage cupboards.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1 outlet on bedhead panel for telephone
1005 Voice / Data outlet: single Communications 1 wall phone
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6050 Special: reading Lighting Up/down light
7020 Medical Air (MA) Medical Gases 1
7000 Oxygen (O2) Medical Gases 1
7040 Suction Medical Gases 1
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button & light switch on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9001 GPO: Double Power 3 1 to bench
9010 GPO: Emergency power, single Power 4 Bedhead
9000 GPO: Single Power 4 Bedhead
9000 GPO: Single Power 1 Bedhead low level, for electric bed
9060 GPO: Special: for equipment Power 1 exam light, optional
Occupancy 1-2
Description/ The Dental Clean-up Sterilising area will provide for washing,
decontaminating and sterilising dental instruments and equipment as
Special Requirements
required.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
52210 Steriliser: benchtop, electric 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
57600 Ultrasonic cleaner: mobile 3 1 yes ___ ___ ___ ___ ___ yes ___
60200 Washer disinfector: 1 door, multi-cart 1 1 yes opt yes yes ___ yes yes ___ under bench, for dental
instruments, optional
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 4
9000 GPO: Single Power 1 washer/ disinfector
Occupancy 1-2
Description/ The Dental Laboratory provides facilities and equipment for dental
technicians to make adjustments to dentures or other dental prosthetics,
Special Requirements
for polishing dentures, for construction of prosthetic appliances and other
items and and to store prosthetic supplies. Natural light desirable.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
15850 Denture processing unit 3 1 yes ___ yes ___ ___ ___ yes ___
23400 Grinder 3 1 yes ___ ___ ___ ___ ___ ___ ___
40620 Lathe: polishing, dental 3 1 yes ___ ___ ___ ___ ___ ___ ___
40300 Plaster trap 1 1 ___ ___ ___ ___ ___ ___ yes ___ under sink
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 optional
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
5035 Special exhaust: hood HVAC 1 over dental processing equipment
4005 Cold water Hydraulics 1 additional outlet for equipment
4033 Floor waste Hydraulics 1
6001 General: colour corrected Lighting
7022 Compressed air Medical Gases 1
7025 Natural gas Medical Gases 1 for bunsen burner
9001 GPO: Double Power 4
Occupancy 1-2
Description/ The Dental Laboratory provides facilities and equipment for dental
technicians to make adjustments to dentures or other dental prosthetics,
Special Requirements
for polishing dentures, for construction of prosthetic appliances and other
items and and to store prosthetic supplies. Natural light desirable.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ Refer to BHWS-B (sim)
5350 Bunsen burner 3 1 yes ___ ___ ___ ___ ___ ___ yes
15850 Denture processing unit 3 1 yes ___ yes ___ ___ ___ yes ___
23400 Grinder 3 1 yes ___ ___ ___ ___ ___ ___ ___
40620 Lathe: polishing, dental 3 1 yes ___ ___ ___ ___ ___ ___ ___
40300 Plaster trap 1 1 ___ ___ ___ ___ ___ ___ yes ___ under sink
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 optional
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
5035 Special exhaust: hood HVAC 1 over dental processing equipment
4005 Cold water Hydraulics 1 additional outlet for equipment
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 to underside of O/H shelving
7022 Compressed air Medical Gases 1
7025 Natural gas Medical Gases 1 for bunsen burner
9001 GPO: Double Power 8
Description/ The Dental Surgery provides for dental consultation, examination and
treatment for patients. An external outlook is desirable. The 14m2 room
Special Requirements
provides for two door access if required.
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 wall mounted (optional)
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6055 Special: task light, built in Lighting under O/H cupboards
7010 Nitrous Oxide (N2O) Medical Gases 1
Description/ The Dental Surgery provides for dental consultation, examination and
treatment for patients. An external outlook is desirable. The 16m2 room
Special Requirements
provides for access by patient trolleys as required.
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 wall mounted (optional)
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
Occupancy 1-2
Description/ The Dental Workroom provides facilities and equipment for dental
technicians to make adjustments to dentures or other dental prosthetics,
Special Requirements
and to store prosthetic supplies.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
15850 Denture processing unit 3 1 yes ___ yes ___ ___ ___ yes ___
23400 Grinder 3 1 yes ___ ___ ___ ___ ___ ___ ___
40620 Lathe: polishing, dental 3 1 yes ___ ___ ___ ___ ___ ___ ___
40300 Plaster trap 1 1 ___ ___ ___ ___ ___ ___ yes ___ under sink
49111 Sink: 450x350x250D 1 1 ___ ___ yes opt opt yes yes ___ provide hot water;
confirm sink dimensions
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 optional
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
5035 Special exhaust: hood HVAC 1 over dental processing equipment
4005 Cold water Hydraulics 1 additional outlet for equipment
4033 Floor waste Hydraulics 1
4055 Natural gas Hydraulics 1 for bunsen burner
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
9001 GPO: Double Power 4
Occupancy 1-2
Description/ The Dental X-Ray area will provide for processing, inspection and viewing
of dental X-rays.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
Room Name Dining Room (Mental Health), 30m2 Room Code: DINMH-30-U
Description/ The Dining Room is an area provided for patients within the Mental Health
Unit to eat their meals, away from the bedroom environment. The Dining
Special Requirements
Room may be combined with the Lounge/ Activites area and used for other
patient activities when not in use for meals. Access and dining space
should be provided for disabled patients. The Servery will be located
adjacent and will require restricted access. Access to an external courtyard
area is desirable. Finishes, fittings & fixtures and furniture should be
suitable for mental health patients. All glazing (including external windows)
is to comply with Mental Health Guidelines.
Room Name Dining Room (Mental Health), 30m2 Room Code: DINMH-30-U
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall telephone, optional
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting optional
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 or Duress call
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 2
Room Name Dining Room/ Beverage Bay (Mental Health), Room Code: DINBEV-25-U
25m2
Description/ The Dining Room/ Beverage Bay is an area provided for patients within the
Mental Health Unit to eat their meals, away from the bedroom
Special Requirements
environment. The Dining Room may be used for other patient activities
when not in use for meals. Access and dining space should be provided
for disabled patients. The Beverage Bay will include a servery counter and
will require restricted access. Access to an external courtyard area is
desirable. Finishes, fittings & fixtures and furniture should be suitable for
mental health patients. All glazing (including external windows) is to
comply with Mental Health Facility Guidelines.
Room Name Dining Room/ Beverage Bay (Mental Health), Room Code: DINBEV-25-U
25m2
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting optional
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 or Duress call
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 4 2 above bench
9000 GPO: Single Power 3 BWU, fridge, microwave
Room Name Dining Room/ Beverage Bay (Mental Health), Room Code: DINBEV-38-U
38m2
Description/ The Dining Room/ Beverage Bay is an area provided for patients within the
Mental Health Unit to eat their meals, away from the bedroom
Special Requirements
environment. The Dining Room may be used for other patient activities
when not in use for meals. Access and dining space should be provided
for disabled patients. The Beverage Bay will include a servery counter and
will require restricted access. Access to an external courtyard area is
desirable. Finishes, fittings & fixtures and furniture should be suitable for
mental health patients. All glazing (including external windows) is to
comply with Mental Health Guidelines.
Room Name Dining Room/ Beverage Bay (Mental Health), Room Code: DINBEV-38-U
38m2
Services
ID Description Service Category Qty Selection / Remarks
1050 Telephone: wall mounted, PABX Communications 1 for wall telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting optional
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 or Duress call
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 4 2 above bench
9000 GPO: Single Power 3 BWU, fridge, microwave
Description/ The Dining Room is an area provided for patients to eat their meals, away
from the bedroom environment. The Dining Room may be used for other
Special Requirements
patient activities when not in use for meals. Access and dining space will
be required for patients with limited mobility, including wheelchairs,
walking frames and other walking aids. The area will also include a
Servery.
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall telephone
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting optional
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 4 2 above bench
9000 GPO: Single Power 2 BWU, fridge
Occupancy 1 - 2 intermittently
Description/ The Dirty Utility provides for cleaning and holding of used equipment for
collection and sterilisation elsewhere, disposal of clinical and other
Special Requirements
wastes and soiled linen, testing and disposing of patient specimens and
decontamination and storage of patient utensils such as pans, urinals
and bowls.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9060 GPO: Special: for equipment Power 2 Pan Sanitiser, Utensil Washer
Occupancy 1 - 2 intermittently
Description/ The Dirty Utility provides for cleaning and holding of used equipment for
collection and sterilisation elsewhere, disposal of clinical and other
Special Requirements
wastes and soiled linen, testing and disposing of patient specimens and
decontamination and storage of patient utensils such as pans, urinals
and bowls.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
4033 Floor waste Hydraulics
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9060 GPO: Special: for equipment Power 2 Pan Washer, Utensil Washer, or combined
utensil/pan washer optional
Occupancy 1 - 2 intermittently
Description/ The Dirty Utility provides for cleaning and holding of used equipment for
collection and sterilisation elsewhere, disposal of clinical and other
Special Requirements
wastes and soiled linen, testing and disposing of patient specimens and
decontamination and storage of patient utensils such as pans, urinals
and bowls.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9060 GPO: Special: for equipment Power 2 Pan Sanitiser, Utensil Washer, or combined
utensil/pan washer optional
Occupancy 1 - 2 intermittently
Description/ The Dirty Utility - Sub is a small Dirty Utility Room providing for cleaning
and holding of used equipment for collection, disposal of clinical and other
Special Requirements
wastes and soiled linen testing and disposal of patient specimens.
Decontamination and storage of patient bedpans, urinals and bowls is
optional in the Dirty Utility-Sub.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9060 GPO: Special: for equipment Power 1 Pan/ Utensil Washer-sanitiser
Occupancy 1 - 2 intermittently
Description/ The Disposal Room provides for the temporary holding of clinical waste,
general waste, sharps, soiled linen and recyclables prior to removal. The
Special Requirements
Disposal Room should include a handwashing basin within the room if
waste will be handled in this area.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2850 Basin: handwash, Type C 1 1 ___ ___ yes ___ yes yes yes ___ optional, refer to
BHWS-C (sim)
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
6000 General fluorescent Lighting
Occupancy 1 - 2 intermittently
Description/ The Disposal Room provides for the temporary holding of clinical waste,
general waste, sharps, soiled linen and recyclables prior to removal. The
Special Requirements
Disposal Room should be located in close proximity to a handwashing
basin or be provided within the room (optional) if waste will be handled in
this area.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
6000 General fluorescent Lighting
Occupancy 1 - 2 intermittently
Description/ The Disposal Room provides for the temporary holding of clinical waste,
general waste, sharps, soiled linen and recyclables prior to removal. The
Special Requirements
Disposal Room should be located in close proximity to a handwashing
basin or be provided within the room (optional) if waste will be handled in
this area.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1
Occupancy 1 intermittently
Description/ A Bay with a bench and computer for use by Pharmacists or other
personnel to access drug information by computer or in manuals. The bay
Special Requirements
should not impede corridor traffic.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6001 General: colour corrected Lighting
6055 Special: task light, built in Lighting under O/H cupboards
8080 Emergency call Nurse Call 1
8005 Patient call handset Nurse Call 2 1- bed area; 1 - exam couch; bed and couch
may share one point if handset will reach both
8000 Patient/ Staff call Nurse Call 2 1- bed area; 1 - exam couch; bed and couch
may share one point if handset will reach both
8010 Staff/ Nurse assist call Nurse Call 1
9040 Body protected Power
9001 GPO: Double Power 4
9010 GPO: Emergency power, single Power 4 patient services panel
9000 GPO: Single Power 2 to exam couch
9060 GPO: Special: for equipment Power 3 Echocardigraphy machine, exam light, XRV
Occupancy 1 - 2 Staff
Description/ The Electronics Laboratory provides a secure workshop area for use by
electricians to handle, test, repair, calibrate or service items of electrical
Special Requirements
equipment used in the hospital. This includes specialist medical
equipment serviced by Biomedical Technicians. The workshop may be
located in close proximity to the Biomedical Workshop.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9040 Body protected Power
9001 GPO: Double Power 9 3 per workstation; 3-walls for floor standing
equipment
9060 GPO: Special: for equipment Power 1 3 phase for equipment testing
9060 GPO: Special: for equipment Power 1 20A, for equipment testing
Description/ The Birthing Room Ensuite is for the Birthing Room patient to wash,
shower, use the toilet, and bath as desired for pain relief, either
Special Requirements
independently or with assistance. The area and layout must
accommodate an assisting nurse. The Ensuite will include a shower,
handbasin, toilet and an island bath. The island bath will include steps
and a seating platform at the bath edge.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
4033 Floor waste Hydraulics 2
6001 General: colour corrected Lighting
7010 Nitrous Oxide (N2O) Medical Gases 1 Optional
7000 Oxygen (O2) Medical Gases 1 Optional
7070 Scavenge Medical Gases 1 Optional
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 3 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Description/ An Ensuite, Birthing Room is for the patient to wash, shower and use the
toilet, either independently or with assistance. The area and layout must
Special Requirements
accommodate an assisting nurse, and wheelchair access. The Ensuite
will have direct access from the Birthing Room.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Description/ An Ensuite is for a patient to wash, shave, groom themselves, shower and
use the toilet, either independently or with assistance. The area and layout
Special Requirements
must accommodate an assisting nurse, patient lifter and wheelchair
access.
The Ensuite may vary in configuration to suit different room types including:
- ENS-ST-A Inboard Ensuite
- ENS-ST-B Outboard Ensuite.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Description/ An Ensuite is for a patient to wash, shave, groom themselves, shower and
use the toilet, either independently or with assistance. The layout
Special Requirements
accommodates two assisting nurses, patient lifter and wheelchair access.
The Ensuite may vary in configuration to suit different room types including
an Inboard Ensuite and Outboard Ensuite.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for heat/ steam
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8070 Patient call pendant Nurse Call 1 or locate NC directly on drop down rail
8000 Patient/ Staff call Nurse Call 2 + indicator button & light; may be located on
drop down rail beside toilet
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
The Ensuite - Super may vary in configuration to suit different patient types
or room types including:
- ENS-SP-A Ensuite Super, Inboard
- ENS-SP-B Ensuite Super, Stand alone
The actual choice of Ensuite will depend on the patient type, the
Operational Policy and floor layout of the facility.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for heat/ steam
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Description/ The Ensuite - Mental Health will provide a shower, toilet and handbasin for
use by mental health patients. The Ensuite will be lockable and Master
Special Requirements
Keyed from the outside with a privacy latch on the inside.
The Ensuite - Mental Health may vary in configuration to suit different room
types including:
- ENS-MH-A Inboard Ensuite with direct access, for 1 or 2 Bed Rooms
- ENS-MH-B Inboard Ensuite with access from corridor, for 1 or 2 Bed
Rooms
- ENS-MH-D Inboard Ensuite for 2 Bed Room, with direct access
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for heat/ steam
4033 Floor waste Hydraulics 2
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
Description/ An Ensuite - Super VIP is for a patient to wash, shave, groom themselves,
shower and use the toilet, either independently or with assistance. The
Special Requirements
area and layout must accommodate an assisting nurse, patient lifter and
assisted wheelchair access. The Ensuite - Super VIP may include a bath.
An island bath will require an increase in the room area.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1005 Voice / Data outlet: single Communications 1 to telephone
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
Description/ An Ensuite - Super VIP is for a patient to wash, shave, groom themselves,
shower and use the toilet, either independently or with assistance. The
Special Requirements
area and layout must accommodate an assisting nurse, patient lifter and
wheelchair access.
The Ensuite - VIP may vary in configuration to suit different room types
including:
- ENS-ST-A Inboard Ensuite
- ENS-ST-B Outboard Ensuite.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Occupancy 1
Description/ An Ensuite with Shower, Toilet and Handbasin adjoining the Family/ Carer
Room for use by carers, visitors or family members.
Special Requirements
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
47500 Shower: fixed rose 1 1 ___ ___ yes ___ yes yes yes ___
55600 Toilet suite: standard 1 1 ___ ___ yes ___ ___ yes yes ___
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics
6000 General fluorescent Lighting
9040 Body protected Power
9001 GPO: Double Power 1 locate near door outside room
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply
with relevant electric safety guidelines
Occupancy 1-2
Description/ The Equipment Clean-Up Room is used for cleaning and maintaining of
equipment used in the Unit. Storage may be required for holding cleaned
Special Requirements
equipment and spares. Equipment may also be recharged in this room.
Natural light is desirable.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 2
Occupancy 1-2
Description/ The Equipment Clean-Up Room is used for cleaning and maintaining of
equipment used in the Unit. Storage may be required for holding cleaned
Special Requirements
equipment and spares. Equipment may also be recharged in this room.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 2
Occupancy 1-2
Description/ The Equipment Clean-Up Room is used for cleaning and maintaining of
equipment used in the Unit. Storage may be required for holding cleaned
Special Requirements
equipment and spares. Equipment may also be recharged in this room.
Natural light is desirable.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 2
Occupancy 1-2
Description/ The Equipment Clean-Up Room is used for cleaning and maintaining of
equipment used in the Unit. Storage may be required for holding cleaned
Special Requirements
equipment and spares. Equipment may also be recharged in this room.
Natural light is desirable.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4010 Cold water: outlet Hydraulics 1
4033 Floor waste Hydraulics 1 if utensil washer provided
4000 Hot water: outlet Hydraulics 1 if utensil washer provided
6000 General fluorescent Lighting
9001 GPO: Double Power 2
9060 GPO: Special: for equipment Power 1 if utensil washer provided
Occupancy 1-2
Description/ The Equipment Clean-Up Room is used for cleaning and maintaining of
equipment used in the Unit. Storage may be required for holding cleaned
Special Requirements
equipment and spares. Equipment may also be recharged in this room.
Natural light is desirable.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
4010 Cold water: outlet Hydraulics 1 if utensil washer provided
4033 Floor waste Hydraulics 1
4000 Hot water: outlet Hydraulics 1 if utensil washer provided
6000 General fluorescent Lighting
9001 GPO: Double Power 2
9060 GPO: Special: for equipment Power 1 if utensil washer provided
Room Name Equipment Clean-Up, Loan Equipment, 10m2 Room Code: ECL-LE-10-U
Occupancy 1-2
Description/ The Equipment Clean-Up provides a room with a hose reel and sink for
cleaning of equipment loaned to patients following return.
Special Requirements
Room Name Equipment Clean-Up, Loan Equipment, 10m2 Room Code: ECL-LE-10-U
Services
ID Description Service Category Qty Selection / Remarks
5015 Ventilation HVAC
4010 Cold water: outlet Hydraulics 1 with hose connection
4033 Floor waste Hydraulics 1
4000 Hot water: outlet Hydraulics 1 with hose connection
6000 General fluorescent Lighting
Room Name Equipment Clean-Up, Loan Equipment, 12m2 Room Code: ECL-LE-12-U
Occupancy 1-2
Description/ The Equipment Clean-Up provides a room with a hosereel and sink for
cleaning of equipment loaned to patients following return.
Special Requirements
Room Name Equipment Clean-Up, Loan Equipment, 12m2 Room Code: ECL-LE-12-U
Services
ID Description Service Category Qty Selection / Remarks
5015 Ventilation HVAC
4010 Cold water: outlet Hydraulics 1 with hose connection
4033 Floor waste Hydraulics 1
4000 Hot water: outlet Hydraulics 1 with hose connection
6000 General fluorescent Lighting
Occupancy 1-2
Description/ The Clean-up/ Sub Pathology room is used for rinsing and cleaning of
equipment used in the Unit, and for satellite pathology equipment such as
Special Requirements
a blood gas analyser for urgent blood testing. The room may be located in
a Critical Care Unit.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
4650 blood gas analyser 3 1 yes ___ ___ ___ ___ ___ yes ___ optional
47850 Sink, SS: double in bench 1 1 ___ ___ yes opt opt yes yes ___ hot water
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 to underside of O/H cupboards
9001 GPO: Double Power 2
9060 GPO: Special: for equipment Power 1 blood gas analyser, as required
Description/ The Mental Health Assessment Room will provide for private consultation
and examination of patients. Provide a discreet observation panel and
Special Requirements
lockable cupboard doors. A second egress door will be required for staff
safety and security, and multiple duress alarm points. All fittings and
fixtures to be suitable for mental health patients, fittings should have a
breaking strain of not more than 15kg. Control panel for water to the
handbasin to be easily accessible from a corridor hatch.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6032 Downlights: colour corrected Lighting over exam couch
6001 General: colour corrected Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 2 workstation / desk area
9011 GPO: Emergency power, double Power 1 patient exam area
9000 GPO: Single Power 1 for XRV
10005 Duress alarm Security 2
Room Name Family / Carer Room - Super VIP Room Code: F-CR-SVIP-U
Occupancy 1
Description/ A Family/ Carer Room with an adjoining Ensuite for carer of patients
needing to stay overnight within the Super VIP Suite. It is connected to the
Special Requirements
1 Bedroom - Super VIP via another Lounge/ Lobby. The room shall be
lockable. An external outlook is required.
Room Name Family / Carer Room - Super VIP Room Code: F-CR-SVIP-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1 to desk; 1 to wall
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 under O/H cupboard
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 4 2 to desk; 1 to bed; 1 to seating area
9000 GPO: Single Power 1 TV
Occupancy Up to 3
Description/ The Feeding Room provides an area for mothers to feed babies with staff
assistance as required or to express breast milk. The Feeding Room will
Special Requirements
be located adjacent to the General Nursery with ready access to the
Formula Room.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6000 General fluorescent Lighting
9040 Body protected Power
9000 GPO: Single Power 4
Room Name Film Processing, Viewing and Reporting Room Code: FPVR-U
Occupancy Up to 4
Description/ A room located within the Medical Imaging Unit to accommodate the film
processing equipment along with a workstation area for viewing, and
Special Requirements
reporting of images.
Room Name Film Processing, Viewing and Reporting Room Code: FPVR-U
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 4 2 outlets on workstations for telephone
1006 Voice / Data outlet: double Communications 1 printer
5000 Airconditioning HVAC
6005 Dimmable Lighting for image viewing
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shleving
9001 GPO: Double Power 5 2 per workstation + 1- printer
9060 GPO: Special: for equipment Power 2 Processor, XRV
Occupancy 1-2
Description/ The Flash Steriliser is a bay for washing and rapid sterilising of
instruments that are dropped in Operating Room procedures. The Flash
Special Requirements
Steriliser Bay will be located with ready access to the Operating Rooms.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC for steriliser
Occupancy 1-2
Description/ The Formula Room provides space for the preparation, distribution and
storage of baby feeds. Pre-packaged feeds will also be stored in this
Special Requirements
area.
The room will provide facilities for washing, sterilisation and storage of
baby bottles, teats and equipment, preparation of baby formulas,
refrigerated storage of baby feeds and demonstration of formula
preparation to mothers.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9000 GPO: Single Power 5 above bench
9060 GPO: Special: for equipment Power 1 fridge
Room Name Fracture Clinic (Hand & Prosthetics) Room Code: FRACL-U
Description/ The Fracture Clinic provides a room for carrying out follow-up
consultations, examinations and treatments for patients referred to the
Special Requirements
Fracture Clinic. Treatments may include hand therapy, change of plasters
and exercise therapy.
Room Name Fracture Clinic (Hand & Prosthetics) Room Code: FRACL-U
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
Room Name Fracture Clinic (Hand & Prosthetics) Room Code: FRACL-U
Occupancy N/A
Description/ Room for storage of frozen goods. Freezer Room temperature should be
monitored and alarmed. Essential power supply may be requried.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
1085 Temperature monitor & alarm Communications 1
5021 Special ventilation: cool room HVAC 1
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power essential supply to cool room plant
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1-control console; 1-patient services
5005 Air conditioning: special HVAC 24 Hour with standby capacity
5080 Humidity control HVAC 45% to 80%
5070 Temperature control HVAC 22 degrees C +/- 2 degrees
6110 Downlights: dimmable Lighting
6001 General: colour corrected Lighting
6055 Special: task light, built in Lighting under O/H cupboards ( if cupboards required)
7020 Medical Air (MA) Medical Gases 1 patient services panels
7000 Oxygen (O2) Medical Gases 1 patient services panels
7040 Suction Medical Gases 1 patient services panels
8080 Emergency call Nurse Call 1 patient services panel
8010 Staff/ Nurse assist call Nurse Call 1 patient services panel
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1
1000 Telephone: PABX Communications 1 wall telephone
1006 Voice / Data outlet: double Communications 2
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting
6001 General: colour corrected Lighting
7020 Medical Air (MA) Medical Gases 1 patient services panel
7000 Oxygen (O2) Medical Gases 1 patient services panel
7040 Suction Medical Gases 1 patient services panel
8080 Emergency call Nurse Call 1 patient services panel
8010 Staff/ Nurse assist call Nurse Call 1 patient services panel
9040 Body protected Power
9001 GPO: Double Power 3 walls
9010 GPO: Emergency power, single Power 2 patient services panel
9000 GPO: Single Power 2 patient services panel
9060 GPO: Special: for equipment Power 2 Xray Equipment, chest bucky
12030 Lead lining Shielding to walls and doors as specified
Occupancy 1 - 2 intermittently
Services
ID Description Service Category Qty Selection / Remarks
1040 Intercom Communications 1 audiovisual type to external door
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 to wall phone
1006 Voice / Data outlet: double Communications 1 to bench
1006 Voice / Data outlet: double Communications 2 to plinths, optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 2 call button on the handset
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 8 quantity will be determined by equipment to be
used and Operational Policy
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 to wall phone
1006 Voice / Data outlet: double Communications 3 1 to each plinth space; 1 to bench
5000 Airconditioning HVAC
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 2 1 to each plinth space; call button on the
handset
8000 Patient/ Staff call Nurse Call 2 1 to each plinth space; + indicator button &
light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 9 quantity will be determined by equipment to be
used and Operational Policy
Occupancy Up to 10
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 3
Occupancy 1
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H cupboards
9001 GPO: Double Power 2
9000 GPO: Single Power 2 fridge, microwave
Occupancy Up to 12
Services
ID Description Service Category Qty Selection / Remarks
1140 Public address system Communications 1
5005 Air conditioning: special HVAC to prevent condensation; ensure all ductwork
& grilles are corrosion resistant
4010 Cold water: outlet Hydraulics 1 for washing down concourse
4033 Floor waste Hydraulics every 3-4 metres on concourse
6000 General fluorescent Lighting to avoid reflection on water; avoid luminaires
over actual water area (for maintenance)
8080 Emergency call Nurse Call 4 waterproof, chlorine resistant; 1 each side of
pool
9000 GPO: Single Power 4 waterproof, chlorine resistant; 1 each side of
pool
9060 GPO: Special: for equipment Power 1 motorised pool blanket if required
Occupancy 1 - 2 intermittently
Description/ Recessed bay on the pool concourse to accommodate lockers for storage
of personal property. A bench seat may be provided under the lockers.
Special Requirements
Lockers need to be lockable and withstand moisture.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC as for pool concourse
6000 General fluorescent Lighting
Room Name Hydrotherapy Pool Open Shower Area Room Code: HYDSH-U
Occupancy Up to 4, intermittently
Description/ The Hydrotherapy Pool Open Shower area is located off the Hydrotherapy
Pool concourse for showering after pool sessions before entering the
Special Requirements
Change Room/s.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC for pool concourse area
5019 Exhaust HVAC
4033 Floor waste Hydraulics 2
6000 General fluorescent Lighting water resistant
8080 Emergency call Nurse Call 1
8000 Patient/ Staff call Nurse Call 4 to each shower
8010 Staff/ Nurse assist call Nurse Call 4 to each shower
Occupancy 1 - 2 intermittently
Description/ The Hydrotherapy Pool Store is a secure room located off the Hydrotherapy
Pool concourse for the storage of equipment used in the pool.
Special Requirements
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC to aid drying of wet equipment
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1 waterproof
Occupancy Up to 6 persons
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 outlet on each panel for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
9001 GPO: Double Power 3
10005 Duress alarm Security 1
Occupancy N/A
Description/ An open bay to accommodate a dry laser camera for printing of digital
images, located within the Medical Imaging Unit. The Laser Camera area
Special Requirements
should have ready access to Imaging Procedures Rooms.
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9060 GPO: Special: for equipment Power 1 Laser camera
Occupancy 1 - 2 Staff
Description/ A small laundry with commercial quality equipment for washing and drying
of small items not laundered by an external linen supplier; this may
Special Requirements
include sheep skins and mop heads The room will include a bench,
laundry tub, commercial small washing machine and dryer and ironing
facilities.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
18200 Dryer: clothes, industrial 3 1 yes ___ ___ ___ ___ ___ ___ ___
29200 Iron: electric 3 1 yes ___ ___ ___ ___ ___ ___ ___ inside cupboard
49400 Sink: laundry, single 1 1 ___ ___ yes opt opt yes yes ___ hot water, with overflow
drain
60600 Washing machine: industrial 3 1 yes ___ yes yes ___ yes yes ___
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC extra steam/ heat extraction to room
5037 Special exhaust: dryer HVAC 1
5015 Ventilation HVAC
4033 Floor waste Hydraulics 1
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9000 GPO: Single Power 3 washer, dryer, ironing cabinet
Occupancy 1-2
Description/ Domestic style laundry for use by mental health patients with staff
supervision. The room will include a bench, laundry tub, domestic
Special Requirements
washing machine and dryer and ironing facilities. All fittings to be suitable
for mental health patients. All glazing (including external windows) is to
comply with Mental Health Facility Guidelines.
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC extra steam/ heat extraction to room for dryer
4033 Floor waste Hydraulics 2
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9000 GPO: Single Power 3 washer, dryer, ironing cabinet
Occupancy 1-2
Description/ Domestic style laundry for patient use. The room will include a bench,
laundry tub, domestic washing machine and dryer and ironing facilities.
Special Requirements
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
29200 Iron: electric 3 1 yes ___ ___ ___ ___ ___ ___ ___ inside cupboard
49400 Sink: laundry, single 1 1 ___ ___ yes opt opt yes yes ___ with overflow drain,
warm water
60650 Washing machine: domestic 3 1 yes ___ yes yes ___ yes yes ___ heavy duty, warm water
Services
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC extra steam/ heat extraction to room
5037 Special exhaust: dryer HVAC 1
4005 Cold water Hydraulics 1 to washing machine
4033 Floor waste Hydraulics 1
4020 Warm water: outlet Hydraulics 1 to washing machine
6000 General fluorescent Lighting
9001 GPO: Double Power 1
9000 GPO: Single Power 3 washer, dryer, ironing cabinet
Occupancy Up to 65
Description/ The Lecture Rooms will accommodate educational sessions for staff and
other groups as required. Access and space should be provided for
Special Requirements
disabled persons. Seating to the rear of the room may be raised on a
platform. The room should be located in close proximity to Staff/ Public
amenities.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
41400 Projector 2 1 yes ___ ___ ___ ___ ___ ___ ___ ceiling mounted
50950 Speaker: wall mounted 1 4 yes ___ ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall phone outside room
entry
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone outside room entry
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 3 1 in ceiling for projector
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting for audiovisual presentations
6000 General fluorescent Lighting
9040 Body protected Power as required
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 6
9060 GPO: Special: for equipment Power 1 projector, ceiling mounted
Occupancy Up to 83
Description/ The Lecture Rooms will accommodate educational sessions for staff and
other groups as required. Access and space should be provided for
Special Requirements
disabled persons. Seating to the rear of the room may be raised on a
platform. The room should be located in close proximity to Staff/ Public
amenities.
ID Description Group Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
41400 Projector 2 1 yes ___ ___ ___ ___ ___ ___ ___ ceiling mounted
50950 Speaker: wall mounted 1 4 yes ___ ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall phone outside room
entry
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall phone outside room entry
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 3 1 in ceiling for projector
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting for audiovisual presentations
6000 General fluorescent Lighting
9040 Body protected Power as required
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 6
9060 GPO: Special: for equipment Power 1 projector, ceiling mounted
Room Name Library & Study/ Reading Area, 40m2 Room Code: LSRA-40-U
Occupancy Up to 15
Description/ A room for library reference materials including books, magazines and
on-line references and catalogues. The area will include a reading area, a
Special Requirements
meeting area and workstation for the Librarian. An external outlook is
desirable.
Room Name Library & Study/ Reading Area, 40m2 Room Code: LSRA-40-U
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 to workstation, 1 outlet for telephone
1006 Voice / Data outlet: double Communications 4 1 per desk
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 6 1 per desk; 2 to workstation
Room Name Library & Study/ Reading Area, 50m2 Room Code: LSRA-50-U
Occupancy Up to 15
Description/ A room for library reference materials including books, magazines and
on-line references and catalogues. The area will include a reading area, a
Special Requirements
meeting area and workstation for the Librarian. An external outlook is
desirable.
Room Name Library & Study/ Reading Area, 50m2 Room Code: LSRA-50-U
Services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 to workstation, 1 outlet for telephone
1006 Voice / Data outlet: double Communications 5 1 per desk
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 7 1 per desk; 2 to workstation
Occupancy 1 - 2 intermittently
Description/ The Linen Holding - Clean, provides for the receipt and temporary holding
of clean linen in trolleys from an external linen supplier, prior to tranport to
Special Requirements
Inpatient and clinical Units. The Clean Linen Holding Room should
include a handwashing basin within the room. The Linen Holding room
will have ready access to the Loading Dock area.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
Occupancy 1 - 2 intermittently
Description/ The Linen Holding - Soiled, provides for the temporary holding of soiled,
bagged linen in trolleys, awaiting collection by an external linen supplier.
Special Requirements
The Soiled Linen Holding Room should include a handwashing basin
within the room. The Linen Holding room will have ready access to the
Loading Dock area.
Services
ID Description Service Category Qty Selection / Remarks
5019 Exhaust HVAC
5015 Ventilation HVAC
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
Occupancy N/A
Description/ The Loading Dock is a covered area for transport access to service Units
for delivery or collection of goods and should be zoned into clean and dirty
Special Requirements
areas. The Loading Dock may be shared between Service Units including
Supply, Linen Handling and Catering Unit. Security to all external
entrances will be required. An intercom or door buzzer may be required to
alert staff to a delivery or collection. Consideration should be given to the
need for manual handling devices such as dock levellers.
Services
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional
1040 Intercom Communications optional
4010 Cold water: outlet Hydraulics 1 required for cleaning
4033 Floor waste Hydraulics 1 external
6015 Security lighting Lighting
6072 Special: external Lighting 1
9060 GPO: Special: for equipment Power 1 for dock leveller, if required
Room Name Lounge - Activities (Mental Health), 20m2 Room Code: LNAC-20-U
Description/ The Lounge/ Activities room provides an area within the Mental Health Unit
where patients, visitors and family groups can visit and undertake
Special Requirements
recreational activities. An external outlook is essential. The Lounge/
Activities room should have access to an external courtyard. Finishes,
fittings & fixtures and furniture should be suitable for mental health
patients. All glazing (including external windows) is to comply with Mental
Health guidelines.
Room Name Lounge - Activities (Mental Health), 20m2 Room Code: LNAC-20-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 or Duress call
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 5
Room Name Lounge - Activities (Mental Health), 30m2 Room Code: LNAC-30-U
Description/ The Lounge/ Activities room provides an area within the Mental Health Unit
where patients, visitors and family groups can visit and undertake
Special Requirements
recreational activities. An external outlook is essential. The Lounge/
Activities room should have access to an external courtyard. Finishes,
fittings & fixtures and furniture should be suitable for mental health
patients. All glazing (including external windows) is to comply with Mental
Health guidelines.
Room Name Lounge - Activities (Mental Health), 30m2 Room Code: LNAC-30-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 or Duress call
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 5
Room Name Lounge - Activities (Mental Health), 55m2 Room Code: LNAC-55-U
Description/ The Lounge/ Activities room provides an area within the Mental Health Unit
where patients, visitors and family groups can visit and undertake
Special Requirements
recreational activities. An external outlook is essential. The Lounge/
Activities room should have access to an external courtyard. Finishes,
fittings & fixtures and furniture should be suitable for mental health
patients. All glazing (including external windows) is to comply with Mental
Health guidelines.
Room Name Lounge - Activities (Mental Health), 55m2 Room Code: LNAC-55-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 or Duress call
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 5
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 2
9000 GPO: Single Power 5
Occupancy Up to 8
Description/ The Medical Officer's Lounge is used by Medical Staff for respite, rest and
relaxation. The room may also be used for small meetings. Facilities for
Special Requirements
food and beverage preparation and storage should be provided. An
external outlook is desirable.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 3 1 outlet on each panel for phone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting wall lights, optional
9001 GPO: Double Power 7 1 over bench
9000 GPO: Single Power 3 fridge, BWU, microwave
9060 GPO: Special: for equipment Power 1 TV
Occupancy Up to 10
Description/ The Medical Officers Lounge is used by Medical Staff for respite, rest and
relaxation. The room may also be used for small meetings. Facilities for
Special Requirements
food and beverage preparation and storage should be provided. An
external outlook is desirable.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 3 1 outlet on each panel for phone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting wall lights, optional
9001 GPO: Double Power 7 1 over bench
9000 GPO: Single Power 3 fridge, BWU, microwave
9060 GPO: Special: for equipment Power 1 TV
Occupancy Up to 15
Description/ The Medical Officer's Lounge is used by Medical Officers staff for respite,
rest and relaxation. The room may also be used for small meetings.
Special Requirements
Facilities for food and beverage preparation and storage should be
provided. An external outlook is desirable.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 3 1 outlet on each panel for phone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting wall lights, optional
9001 GPO: Double Power 7 1 over bench
9000 GPO: Single Power 3 fridge, BWU, microwave
9060 GPO: Special: for equipment Power 1 TV
Occupancy Up to 20
Description/ An area for patients to have meals away from the bedroom environment.
The Lounge/Dining area may also be used by super VIP families and
Special Requirements
other visitors to a Super VIP area to wait in comfort prior to or during visits
to a Super VIP Unit. The room will require facilities for a range of
occupants including adults and children, both able-bodied and disabled.
An external outlook is desirable. The Lounge/Dining - Super VIP should be
located in close proximity to other Super VIP facilities.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 2 1 on wall; 1 in entertainment cabinet
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting
45570471 Special: decorative Lighting may include chandelier or pendant lighting
6030 Special: downlights Lighting
6045 Wall washers Lighting
9015 GPO: Cleaner Power 1 as required
9001 GPO: Double Power 3 2 in entertainment cabinet; 1 on wall
9000 GPO: Single Power 1 TV
Room Name Lounge/ Dining - Activites (Mental Health), Room Code: LDA-MH-20-U
20m2
Description/ The Lounge/ Dining - Activities Room is an area provided for patients
within the Mental Health Unit to eat their meals, away from the bedroom
Special Requirements
environment. The Dining area may be used for other patient activities
when not in use for meals. Access and dining space should be provided
for disabled patients. A Servery with resitricted access will be located
adjacent to the Dining area and will include a servery counter. Access to
an external courtyard area is desirable. Finishes, fittings & fixtures and
furniture should be suitable for mental health patients. All glazing
(including external windows) is to comply with Mental Health Guidelines.
Room Name Lounge/ Dining - Activites (Mental Health), Room Code: LDA-MH-20-U
20m2
Services
ID Description Service Category Qty Selection / Remarks
1000 Telephone: PABX Communications 1 wall telephone
5000 Airconditioning HVAC
6110 Downlights: dimmable Lighting optional
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 or Duress call
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 2
Occupancy Up to 6 visitors
Description/ The Parent Lounge provides a change of environment away from clinical
areas for parents or visitors to patients in the Paediatric/ Adolescent Unit.
Special Requirements
An external outlook is desirable.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
9000 GPO: Single Power 4
9060 GPO: Special: for equipment Power 1 TV, optional
Description/ The Patient Lounge provides a change of environment away from clinical
areas for patients and visitors. It is an area where family groups can visit
Special Requirements
and patients can socialise. An external outlook is essential.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 + indicator button & light
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1 as required
9000 GPO: Single Power 4
9060 GPO: Special: for equipment Power 1 TV, optional
Description/ The Patient Lounge provides a change of environment away from clinical
areas for patients and visitors. It is an area where family groups can visit
Special Requirements
and patients can socialise. An external outlook is essential.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9000 GPO: Single Power 6
9060 GPO: Special: for equipment Power 1 TV, optional
Description/ The Patient Lounge provides a change of environment away from clinical
areas for patients and visitors. It is an area where family groups can visit
Special Requirements
and patients can socialise. An external outlook is essential.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9000 GPO: Single Power 5
9060 GPO: Special: for equipment Power 1 TV, optional
Description/ The Patient Lounge provides a change of environment away from clinical
areas for patients and visitors. It is an area where family groups can visit
Special Requirements
and patients can socialise. An external outlook is essential.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 2 + indicator button & light
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9000 GPO: Single Power 8
9060 GPO: Special: for equipment Power 1 TV, optional
Occupancy Up to 8
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
8080 Emergency call Nurse Call 1 + indicator button & light
8070 Patient call pendant Nurse Call 1 call button on the pendant
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1
9001 GPO: Double Power 1 over bench
9000 GPO: Single Power 3 fridge, BWU, microwave
9000 GPO: Single Power 5
9060 GPO: Special: for equipment Power 1 TV, optional
Description/ The Special Patient Lounge provides a change of environment away from
clinical areas for patients and visitors and may include a beverage
Special Requirements
preparation area. It is an area where family groups can visit and patients
can socialise. An external outlook is essential.
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1 optional
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8080 Emergency call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9040 Body protected Power
9001 GPO: Double Power 1 to bench
9000 GPO: Single Power 5 patient area
9000 GPO: Single Power 3 BWU, fridge, microwave
9060 GPO: Special: for equipment Power 1 TV, optional
Room Name Lounge - Recovery, Stage 2 (Typical Bay) Room Code: LNPT-RS2-U
Room Name Lounge - Recovery, Stage 2 (Typical Bay) Room Code: LNPT-RS2-U
Services
ID Description Service Category Qty Selection / Remarks
1090 TV: MATV Communications 1
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
7020 Medical Air (MA) Medical Gases 1 per patient chair
7000 Oxygen (O2) Medical Gases 1 per patient chair
7040 Suction Medical Gases 3 per patient chair
8080 Emergency call Nurse Call 1 per room + indicator button & light
8005 Patient call handset Nurse Call 1 per patient chair; call button on the handset
8000 Patient/ Staff call Nurse Call 1 per patient chair; + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 per patient chair; + indicator button & light
9040 Body protected Power
9015 GPO: Cleaner Power 1 per room
9010 GPO: Emergency power, single Power 1 per patient chair
9000 GPO: Single Power 2 per patient chair + 1 telephone table
9060 GPO: Special: for equipment Power 1 TV